Title: Fire resistance test utilising the general principles of BS 476: Part 20: 1987 on four specimens of Uninsulated Air Valves.

Test Report No. AJHG FB Date: FEB.17, 2015 Page 1 of 13

WARRES No Page 1 of 27. Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier

FIRE-RESISTANCE TEST ON DOWNLIGHT COVERS INSTALLED IN PLASTERBOARD CEILINGS

Title: Indicative fire test. WF Report No: /A. Prepared for: Hoody Speaker Hoods Ltd

Title: WF Assessment Report No B. Prepared for: CHEMOLLI S.A.S. di Eros Chemolli & C. Via Fitta, Arco (TN), Italy

ASSESSMENT REVIEW. Review of Assessment Report WFRA C91415

Fire-resistance test on fire collars protecting a concrete slab penetrated by services

Benefiting Government, Industry and the Public Through Innovative Science and Technology. Barry L. Badders, Jr. P.E.

Fire-resistance test on fire collars protecting a plasterboard wall penetrated by services

BUSHFIRE TEST ON GLAZED VERTICAL ELEMENTS

Fire-resistance test on fire collars protecting a plasterboard wall penetrated by services

Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly

STEEL DUCT - FIRE RATED CLADDING INSTALLATION MANUAL

Fire resistance test on fire collars protecting a concrete slab penetrated by services

Life Safety and Fire Resistant Glazing Systems

FTSG RESOLUTIONS. This document of FTSG resolutions was issued by the Company Secretary 20 July 2012.

FIRE-RESISTANCE TEST ON FIRE COLLARS PROTECTING A PLASTERBOARD WALL PENETRATED BY SERVICES

Title: The Air Leakage Performance of Timber Doorsets fitted with NOR710 Smoke Seals in Accordance with BS 476: Part 31, Section 31.

Report of Surface Burning Characteristics Tests on Samples As Submitted By Eco-Sol Ltd

Determination of the fire resistance according to EN : 2006 of vertical linear joints sealed with Henkel PATTEX FR55

Report of Surface Burning Characteristics Tests on Samples As Submitted By Jotun UAE Ltd (LLC)

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome

C-01 FIRE DECKS AND BULKHEADS

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Railtech Ltd.


Report Of Surface Burning Characteristics Tests On Coated Louvered Door Panels As Submitted By Contego International Inc.

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Textures 3D

Report Of Surface Burning Characteristics Tests On Felt Material As Submitted By Rieke Office Interiors

We Identify and S.T.O.P. Your Noise Problems

THE HOME OF REACTIVE PROTECTION SYSTEMS

Acoustical Surfaces, Inc.

Fire resistance testing of technical cabinets in accordance with EN

The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318

Report of Surface Burning Characteristics Tests on Skyfold Panel Samples As Submitted By Railtech Ltd

HORIZONTAL COMPLEMENT TO THE MANDATES TO CEN/CENELEC CONCERNING THE EXECUTION OF STANDARDISATION WORK FOR

CERTIFICATE OF COMPLIANCE

PERFORMANCE OF PASSIVE FIRE PROTECTION IN JET FIRES

Behaviour of an Intumescing System Subjected to Different Heating Conditions. Johansson, Nils; Van Hees, Patrick; Jansson, Robert; Sjöström, Johan

The Fire Resistance Performance Of Timber Or Mineral Composite Based Insulated Doorsets When Fitted With D & E Architectural Hardware Spring Hinges

Intumescents & Accessories for use in Consumer Units for Domestic Household and other Premises. Amendment No. 3 BS 7671

Test Report No. AJD Date: JUN.09, 2013 Page 1 of 6

Intumescent Fire Dampers

Protective & Marine Coatings Europe, Middle East, Africa & India

BS EN : 2001 & IEC :2000

NF X : Parts 1, 2, 3, 4 & 5

FIBERSHIELD EW NEW PRODUCT LOW RADIANT HEAT TRANSFER ( PARTIAL PARTIAL INSULATION ) FIRE CURTAINS. Supported by full scale fire test data

BURNING BRAND PERFORMANCE TEST REPORT. Rendered to: VELUX AMERICA, INC. SERIES/MODEL: TGF/TGR (Acrylic Dome) VELUX SUN TUNNEL

25 th November Title:

Report Of Surface Burning Characteristics Tests On PVC Sheeting As Submitted By Jain (Americas) Inc.

Contents: 4. Report of Surface Burning Characteristics Tests on LP FlameBlock/BlazeGuard (30-minute test) Updated April, 2010

NMFS Intumescents & Accessories for use in Consumer Units for Domestic Household Premises. Amendment No. 3 BS 7671

RetardantsInc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318

SIGMADEK, LTD. FIRE TEST REPORT

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Ebrille SRL

Furenflex RWV Advanced Liner

Darchem Thermal Protection

1.0 INTRODUCTION 2.0 CLASSIFICATION CRITERIA

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

BCTC CARPET TECHNICAL CENTRE

CERTIFICATE OF FIRE APPROVAL

TEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota

Report on the Fire Testing of a Roofing System with a Synthetic Underlayment in Accordance with ASTM E a. Trinity ERD Columbia, SC

BS EN 13823: A Report To: Contra Vision. Document Reference: Date: 25 th November Issue No.: 1

Fire Protection. Intumescent fire and smoke seals for door assemblies

PERFORMANCE TEST REPORT. Rendered to: EVERBLOCK SYSTEMS, LLC. PRODUCT: Modular Block Product

WARNING: DOWNLIGHTS MUST BE FITTED CORRECTLY IN FIRE RATED CEILINGS

REPORT NUMBER: SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE:

Fire Collars for Floor Wastes Understanding BCA Compliance Options

Fire Risk Assessment

Saving lives with coatings

Determination of the fire resistance according to EN of vertical linear joints sealed with Henkel PATTEX FR66

Intertek. REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: November 19, 2008

Report of Surface Burning Characteristics Test on Acoustical Panel

Classification of reaction to fire performance in accordance with BS EN : A1: 2009 on Sandwich Panel, WP 50.

CEPE guidance to a quality control fire test regime for intumescent coatings Date of issue: 24 May 2011

FIREMASTER PLUS 2 TENABLE ZONE / HEAT PROTECTION ACTIVE FIRE CURTAIN BARRIER ASSEMBLIES LEADING THE WAY IN FIRE PROTECTION

Clear Installation guide

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

This document is a preview generated by EVS

Test Report No. AJFS FF Date: OCT.17, 2018 Page 1 of 6

Report Of Surface Burning Characteristics Tests On Fire Retardant Coating As Submitted By Contego International

Animals:Goats:Bleat.Calls,Warbling.Baa,Movements.Rubbing,Barn,Medium.Close,Interior,BG.Dog.Barks 01:21.618

Darchem Thermal Protection

2.2 Factors in design

TEKNISK DOKUMENTATION VENTILATION BG BURCHARTH A/S

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Tile-diy LLC

New European Fire Testing Classification for Construction Products

Cylinders for Domestic Purposes Heat Pumps

Forbo Flooring Attn. Mr. A. Tijhof Postbus AA Krommenie. Report. Sponsor : Contractor, manufacturer : Forbo Flooring. Lot. No. : 66869/3877.

Section 2 - Applications - General. Section 2A - FD30 Strebord 35+, 38+, 44 & Superpan with MDF & Wood Frames

Introducing the. Subklew SM24 Mosaic System

Department for Communities and Local Government Research Report:

PERFORMANCE TEST REPORT. Rendered to: Metal Building Manufacturers Association Cleveland, Ohio

Test Report: ICL/CR15/11/087

FIRE PROTECTION INNOVATORS IN CABLE MANAGEMENT

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

EnviroScape Mural. pre-pasted printable wallcovering material. Choose your GREEN resource from a leading solutions provider.

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c

NFPA Technical Committee on Fire Tests

Transcription:

Contents Page No Page 1 of 14... 1 1 Introduction... 3 2 Specimen verification... 3 3 Description of supporting constructions... 3 4 Description of specimen... 3 4.1 Air transfer grille blocks... 3 5 Test conditions... 4 5.1 Ambient temperature... 4 5.2 Furnace temperature... 4 5.3 Pressure readings... 5 5.4 Thermocouple positions... 5 5.5 Unexposed face temperatures... 6 6 Observations... 8 7 Expression of results... 10 8 Limitations... 11 9 Photograph... 12 Appendix figures 1, 3... 14 Test for: Norseal Ltd Page 2 of 14

1 Introduction Four air transfer grille blocks were installed into an aerated autoclaved concrete wall and tested to evaluate their fire resistance. 2 Specimen verification The specimens were delivered to Chiltern International Fire Ltd (CIFL) during September 2010. CIFL fabricated the supporting construction, and installed the specimens into the supporting construction to the clients specifications. 3 Description of supporting constructions The supporting construction comprised a lightweight aerated autoclaved concrete wall, 215mm thick x 1080mm wide x 1080mm high. The supporting construction included 4No apertures 300mm wide x 300mm high x 215mm deep to accept the air transfer grille blocks. 4 Description of specimen Details of the specimens are shown in the Appendix. All measurements are in mm and the descriptions are written viewing the specimens from the unexposed face unless stated otherwise. 4.1 Air transfer grille blocks Each air transfer grille block was installed into its corresponding aperture within the supporting construction. Each air transfer grille block measured 298mm high x 298mm wide x 40mm thick and were fitted 50mm from the unexposed face of the wall. Each grille block was located within the aperture by means of 4No. 50mm long wood screws, two on each face and then sealed to the wall with intumescent mastic. A 340mm high x 340mm wide steel grille cover was fixed to the wall with 50mm long wood screws, over the cut outs on both faces. Each air transfer grille block comprised a profiled galvanised steel framework and slats, supporting flexible intumescent strips, 3mm thick x 38mm wide (details held in confidence on file by Chiltern International Fire Ltd.). The intumescent sheet strips and supporting slats were fitted at various distances apart:6 Air transfer grille block A Air transfer grille block B Air transfer grille block C Air transfer grille block D Slats and intumescent sheet fitted 35mm apart Slats and intumescent sheet fitted 37mm apart Slats and intumescent sheet fitted 25mm apart Slats and intumescent sheet fitted 30mm apart Test for: Norseal Ltd Page 3 of 14

5 Test conditions 5.1 Ambient temperature The ambient temperature of the test area at commencement of test was 18 C. 5.2 Furnace temperature The furnace was controlled to follow the temperature/time relationship specified in BS 476: Part 22: 1987, as closely as possible, using the average of four thermocouples suitably distributed within the furnace. The furnace temperatures for the duration of the test are shown graphically below: 1500 1000 C 500 BS 476 temperature curve (blue line) Mean furnace temperature (green line) 0 0 50 100 150 Time Test for: Norseal Ltd Page 4 of 14

5.3 Pressure readings After the first 5 of the test, the furnace pressure was maintained at 5 ± 5 Pa and after 10 was maintained at 5 ± 3 Pa with respect to atmosphere 550mm above the top of the top grille vent, equating to 0Pa at the top of the top grille vents for the first 66. At the request of the sponsor, the pressure was then increased to 20Pa ± 3 Pa at the top of the top grille vents for the remainder of the test for indication purposes only. The pressure readings are shown graphically below: 30 25 20 Pa 15 10 5 0 65 50 100 150 Time 5.4 Thermocouple positions The temperature of the unexposed face was monitored by means of five thermocouples fixed to each steel grille cover: (see Appendix figure 3) Test for: Norseal Ltd Page 5 of 14

5.5 Unexposed face temperatures Air transfer grille block A 400 300 Maximum temperature of grille block ºC 200 Average temperature of grille block 100 0 0 50 100 150 Time Air transfer grille block B 800 600 Maximum temperature of grille block Average temperature of grille block C 400 200 0 0 50 100 150 Time Test for: Norseal Ltd Page 6 of 14

Air transfer grille block C 150 100 Maximum temperature of grille block C 50 Average temperature of grille block 0 0 50 100 150 Time Air transfer grille block D 200 150 Maximum temperature of grille block C 100 50 Average temperature of grille block 0 0 50 100 150 Time Test for: Norseal Ltd Page 7 of 14

6 Observations All observations relate to the unexposed face unless otherwise stated. Time () Comments 04.00 A and B, the intumescent is starting to react. 20.00 A is full sealed. B, approximately 70% is sealed. C and D, no intumescent reaction. 30.00 No change. 50.00 B has fully sealed. D has started to slowly react. 56.50 A and B, there are multiple glows visible as the intumescent breaks down. 66.00 No failures. Pressure is increased to 20 at the top of the vent for indicative purposes, at the request of the test sponsor. 69.00 C and D have fully sealed. 76.00 A and B, there are multiple glows visible through the grille, intumescent seal area continues to break down. 81.00 A, a cotton pad integrity test was performed at the top of grille, no failure or char to cotton pad. 83.00 A, a roving thermocouple reading was taken at thermocouple position 12 where a temperature of 193 C was recorded. 89.01 A, a roving thermocouple reading was taken at thermocouple position 12 where a temperature of 220 C was recorded. 92.45 B, a cotton pad integrity test was performed in the centre of specimen which resulted in ignition of the cotton pad thereby constituting integrity failure. Thermocouple temperature is over 300 C. 95.00 A, a cotton pad integrity test was performed on the centre of specimen, no failure. A roving thermocouple reading was taken and a temperature of 300+ C was recorded. 98.00 A, a cotton pad integrity test was performed on the centre of specimen, no failure. A roving thermocouple reading was taken and a temperature of 300+ C was recorded. 98.20 B, approximately 50% of the intumescent has eroded away in the centre with a large glow visible on the unexposed grille. A, approximately 25% of the intumescent has eroded away. Test for: Norseal Ltd Page 8 of 14

105.00 A, a cotton pad integrity test was performed on specimen, no failure. A roving thermocouple reading was taken where a temperature of 300+ C was recorded. 110.00 A, a cotton pad integrity test was performed on specimen, no failure. A roving thermocouple reading was taken where a temperature of 300+ C was recorded. 114.00 A, a cotton pad integrity test was performed on specimen, no failure. A roving thermocouple reading was taken where a temperature of 300+ C was recorded. 117.00 A, a cotton pad integrity test was performed on specimen*, no failure. a roving thermocouple reading was taken where a temperature of 300+ C was recorded. 122.00 Test terminated. Test for: Norseal Ltd Page 9 of 14

7 Expression of results Performance up to 66 under negative pressure regime Air transfer grill block A Air transfer grill block B Air transfer grill block C Air transfer grill block D Integrity Cotton pad Gap gauge Continuous flaming 66* (sixty six) 66* (sixty six) 66* (sixty six) 66* (sixty six) 66* (sixty six) 66* (sixty six) 66* (sixty six) 66* (sixty six) 66* (sixty six) 66* (sixty six) 66* (sixty six) 66* (sixty six) Insulation 66* (sixty six) 66* (sixty six) 66* (sixty six) 66* (sixty six) * No failure had occurred at 66 * Performance after 66 under a positive pressure regime * These results should be used for indication purposes only as the pressure regime was not positive for the full test duration Air transfer grill block A Air transfer grill block B Air transfer grill block C Air transfer grill block D Integrity Cotton pad Gap gauge Continuous flaming 92 (ninety two) 92** (ninety two) 92** (ninety two) Insulation 89# (one twenty one) recorded with roving thermocouple 78# (seventy eight) hundred and hundred and * Failure criteria were not achieved upon termination of the test at 122 (one hundred and ** Failure criteria were not achieved prior to initial failure # Recorded after the grille blocks had fully reacted Test for: Norseal Ltd Page 10 of 14

9 Photograph Unexposed face of air transfer grille blocks at start of test After 60 Test for: Norseal Ltd Page 12 of 14

After 120 Test for: Norseal Ltd Page 13 of 14

Appendix figures 1 3 Test for: Norseal Ltd Page 14 of 14