ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems)

Similar documents
ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15

ISOMETER IR1575. Insulation monitoring device for unearthed AC/3(N)AC systems up to 480 V and DC systems up to 480 V

1.7 A-ISOMETER IRDH575. RoHS. Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems)

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances

isopv and AGH-PV Ground Fault Detector for Ungrounded Solar Arrays up to 1100 V And Isolation Tester Prior to Array Startup (Grounded and Ungrounded)

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

Residual current monitor RCM470LY/RCM475LY. for TN and TT systems (AC and pulsating DC currents)

ISOMETER isomed427p. Application Medical IT system in accordance with IEC , IEC , IEC and DIN VDE

1.7. Insulation fault evaluators EDS460/490 EDS461/491

Insulation fault evaluator EDS460-DG

1.7. Insulation fault evaluators EDS460/490 EDS461/491

LINETRAXX RCMA420. Residual current monitor for monitoring AC, DC and pulsed DC currents in TN and TT systems

IT system floor-standing distribution

LINETRAXX VMD420. Multi-functional voltage relay for 3(N)AC systems, frequency/overvoltage/undervoltage, phase, phase failure, asymmetry

LINETRAXX VME420. Multi-functional relay for overvoltage, undervoltage and frequency monitoring in AC/DC systems with external supply voltage

isopv425 and AGH420 Ground Fault Detector for Ungrounded Solar Arrays < 100 kw And Isolation Tester Prior to Array Startup (Grounded and Ungrounded)

Remote alarm indicator and test combination MK2430

ISOMETER IRDH265 IRDH365

BENDER A-ISOMETER IRDH265 IRDH365

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Phone: Fax:

ISOMETER IRDH375 IRDH375B

A-ISOMETER IRDH575. Operating Manual

LINETRAXX RCMS460-D/-L RCMS490-D/-L

Bender GmbH & Co. KG All rights reserved. Reprinting only with permission of the publisher. Subject to change! Photos: Bender archives.

RCMA423-DM RCMA423-DM1C RCMA423-DM2C RCMA423-DM3C. Operating Manual

TM800. Remote alarm indicator and operator panels

Operating Manual RCM420

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE /

Operating Manual VMD420

VME420 Voltage and frequency monitor

Line Isolation Monitor (LIM) LIM2000plus

VME421H Voltage and frequency monitor

Manual CME420. Multi-functional current relay, AC, overcurrent/undercurrent/ window discriminator function CME420_D00034_02_M_XXEN/05.

RCMA423-DM1C Residual current monitor

CMD420 / CMD421 Series

RCMA423. Residual current monitor for monitoring AC-, DC- and pulsed DC currents in TN- and TT systems Software-Version: D330 V1.0x.

T M LIM2010. Line Isolation Monitor (LIM) Technical Bulletin NAE /

Bender GmbH & Co. KG. All rights reserved. Reprinting only with permission of the publisher. Subject to change! Photos: Bender archives

RTA421. Technical Information. Limit alarm switch Alarm switch and power supply for monitoring current or voltage signals

LINETRAXX RCMS150. Residual current monitor type B with integrated measuring current transformers for earthed AC/DC systems (TN and TT systems)

Parameterisable compact fault annunciator with permanent display

ISOMETER isopv1685rtu isopv1685p isopv1685pfr

MK Series. Remote Indicators For Line Isolation Monitors and Fault Location. Technical Bulletin NAE /

02/11/2015

02/11/2015

T M. User Manual LIM2010. Line Isolation Monitor

Connection. e. g. Pt100. reference limit. yellow Output I. Composition

Analog Annunciator Unit SACO 16 A3. Product Guide

Universal fault annunciator for panel mounting

Interface and EOL Modules 8

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl

Process Alarm Module RTA 421

Operating Manual MS220DA

DEB71. Earth Leakage Monitoring Relay. Benefits. Description

General Routing Interface

OilSET Installation and Operating Instructions. Oil Separator Alarm Device

AL3000 SERIES 100MM CHART MULTI-POINT TYPE HYBRID RECORDER

OilSET-1000 (12 VDC)

KHA6-GT*-Ex1. Thermocouple trip amplifiers. Composition. Hazardous area. Safe area. Function. 230 V AC 1-channel. Input EEx ia IIC

SET Installation and Operating Instructions. Level switch for one sensor

EARTH LEAKAGE RELAY. User Manual - Issue 1.0

IR5002. Operating Manual. Insulation monitoring device for IT DC systems V ISO Quality System Certified

SCHMIDT LED Measured Value Display MD Instructions for Use

HTC-915-CONT. Heat-Trace Control system

Operating Manual MS220KA and MSR220KA

PolyGard Single Point Controller SPC-X3-20XX for refrigerant gases and vapours

DPB52. True RMS 3-Phase, Multifunction monitoring relay. Benefits. Description

EARTH FAULT METER MD-08

SLATE. Base Module INSTALLATION INSTRUCTIONS R8001A1001

SET-2000 Hi Level/Oil

Cat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE

SET-2000 Oil/Sludge. Alarm Device for Oil Separators. Installation and Operating Instructions

PolyGard 2-channel Gas Controller MGC-03

AH3000 SERIES 180MM CHART PEN TYPE HYBRID RECORDER

Process & TeMPerATUre UniversAl input DigiTAl MeTers

SET-2000 Oil/Sludge 12 VDC

PROTECT SRB 200EXi-1A

Operating Manual TR600

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

GMA4100-DP. Control Panel. Operation Manual. Worldwide Supplier of Gas Detection Solutions

DPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1-

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-nA.

Operating Instructions Edition 02/2007

PROFIBUS-PA Display RID 261 PROFIBUS-PA

OilSET Installation and Operating Instructions. Oil Separator Alarm Device with SET/DM3AL sensor

GMA 301. Operation Manual. Worldwide Supplier of Safety Solutions. Part Number

Booster Power Supply Manual

Overload relays. General descriptions. Configuration of the front

Monitoring Devices 11/1

AO Annunciator Module

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

PolyGard Single Point Controller SPC-X3-11XX for Toxic Gases and Oxygen

Oxygen (O2) Single-Point Gas Detection System

Electrical safety costs little. a human life is priceless

Product overview. Alarm indicator, operator and display panels

General Specifications

Transcription:

Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) IRDH375_D00124_01_D_XXEN/07.2018

Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Product description The ISOMETER of the IRDH375(B) series is designed to monitor the insulation resistance of unearthed main circuits (IT systems) AC, AC/DC 0 793 V resp. DC 0 650 V. The AMP Plus measurement method meets the particular requirements of modern power supplies which often include rectifiers, converters, thyristor-controlled DC drives and directly connected DC components. In these systems often high leakage capacitances against earth occur due to interference suppression measures. The IRDH375(B) automatically adapts itself to the existing system conditions. In combination with a coupling device, the devices can also be used for higher voltages. An external supply voltage allows de-energised systems to be monitored too. ISOMETER IRDH375 Device features Insulation monitoring for unearthed AC, AC/DC systems 0 793 V, DC 0 650 V Nominal voltage extendable via coupling device Two separately adjustable response values AMP Plus measurement method Automatic adaptation to the system leakage capacitance Info button to display device settings and the system leakage capacitance Continuous self monitoring, with automatic alarm message Automatic self test, selectable Connection for external kω indication Test and reset button Connection external test and reset button Two separate alarm relays with two potential-free changeover contacts N/O or N/C operation Alarm relay for system fault (N/C operation) Backlit LC display RS-485 interface Plug-in terminals Approvals Application AC, DC or AC/DC main circuits AC/DC main circuits with directly connected DC components, such as rectifiers, converters, and thyristorcontrolled DC drives UPS systems, battery systems Function When the insulation resistance between the system conductors and earth falls below the set response value, the alarm relays switch and the alarm LEDs light up. Two separately adjustable alarm relays allow to distinguish between prewarning and alarm. The measured value is indicated on the LC display or an externally connectable measuring instrument. In this way any changes, for example when circuits are connected to the system, can be recognised easily. The fault message can be stored. The fault memory can be reset by pressing the reset button. By pressing the test button, the function of the device as well as the connections to system and earth can be tested. Pressing the Info button provides additional information, such as the existing system leakage capacitance or device settings. The function of the device and the earth connections are monitored. When a fault occurs, the system fault relay switches and the alarm LED system fault lights up. The parameterisation of the device can be carried out via the LC display or the function buttons integrated in the front plate. Device version IRDH375B Device version IRDH375B includes the following additional functions: History memory with real-time clock to store all alarm messages with date and time stamp Electrically isolated RS-485 interface (BMS protocol) for communication with other Bender devices Isometer disconnecting relays for the operation of several ISOMETER s in coupled IT systems Current output 0(4) 20 ma Use in coupled IT systems Heaters with phase control Installations including switch-mode power supplies IT systems including high leakage capacitances Coupled IT systems Only one ISOMETER may be active when several IT systems are coupled. Isometer disconnecting relays and the control inputs F1/F2 integrated in version IRDH275B guarantee that only one ISOMETER is active at any one time. Measurement method The IRDH375(B) uses the patented AMP Plus measurement method. This measurement method allows concise monitoring of modern power supply systems, also in case of extensive, directly connected DC components and high system leakage capacitances. Standards The ISOMETER of the IRDH375 series complies with the requirements of the device standards: DIN EN 61557-8 (VDE 0413-8), EN 61557-8, IEC 61557-8, IEC 61326-2-4, DIN EN 60664-1 (VDE 0110-1), DIN EN 60664-3 (VDE 0110-3), ASTM F1669M-96 (2007), ASTM F1207M-96 (2007) 2 IRDH375_D00124_01_D_XXEN/07.2018

Operating elements Wiring diagram ISOMETER IRDH375 1 2 3 4 1 2 3 4 5 6 7 8 1 - INFO button: to query standard information ESC button: back to the menu function 2 - TEST button: to call up the self test Arrow up button: Parameter changes, scroll 3 - RESET button: to delete alarm and fault messages Arrow down button: Parameter changes, scroll 4 - MENU button: to activate the menu system Enter button: to confirm parameter changes 5 - Alarm LED 1, yellow, lights when the value falls below the set response value R ALARM1 6 - Alarm LED 2, yellow, lights when the value falls below the set response value R ALARM2 7 - Alarm LED, yellow, lights in case of fault in the connecting leads to the system or to earth, or in case of system fault 8 - Transparent front plate cover (accessory) Response times tan [sec] C e [µf] Wiring diagram rear view 1 R f U S 5 1-3AC system 9 6 2-3NAC system 4 - DC system 5 - Supply voltage U S (see ordering information) via 6 A fuse; for UL and CSA applications, it is mandatory to use 5 A fuses. 6 - Alarm relay R ALARM1 7 - Alarm relay RALARM2 8 - Alarm relay system fault 9 - External kω indication 0 400 µa or current output 0(4) 20 ma (option). *10 - External reset button (N/C contact or wire jumper) when the terminals R1/R2 are open, the fault message will not be stored, provided that the memory has not been activated via the operating menu. *11 - External test button, if required 7 8 10 11 12 3 - AC system 13 *12 - STANDBY by means of the function input F1, F2: When the contact is closed, insulation measurement does not take place; system disconnection 13 - DIP switch, S1 ON - RS-485 terminated (120 Ω on), S2 - unassigned * The terminal pairs 10, 11 and 12 must be wired galvanically isolate and must not have a connection to PE! 2 1 - Rear view IRDH375 2 - Detachable terminal cover IRDH375_D00124_01_D_XXEN/07.2018 3

Ordering information RS-485 interface Coupled IT systems Output ASCII BMS not applicable applicable external kω indication 0 400 µa Current output 0(4 20 ma) 1 - Supply voltage U S AC DC Type Art. No. 88 264 V 77 286 V IRDH375-435 B91065000 19.2 55 V 19.2 72 V IRDH375-427 B91065002 88 264 V 77 286 V IRDH375B-435 B91065004 19.2 55 V 19.2 72 V IRDH375B-427 B91065006 1) Absolute values Device Option-W with increased shock and vibration resistance: Indicated by the letter W at the end of the order number. Suitable system components Type designation Type Page Dimension diagram X300 Dimensions in mm 138 +0,8/ 0 External kω measuring instruments Coupling devices Transparent front plate cover IP65 7204-1421 B986763 9604-1421 B986764 9620-1421 B986841 AGH150W-4 B98018006 AGH204S-4 B914013 AGH520S B913033 144x72 B98060005 155 72 142 133 144 66 +0,8/ 0 Wiring diagrams IRDH375 connected to different types of coupling devices ISOMETER IRDH375 with coupling device AGH150W-4 ISOMETER IRDH375 with coupling device AGH204S-4 1 2 U n U n DC 0 1760 V ISOMETER IRDH375 with coupling device AGH520S U n 3/(N)/AC 50 400 Hz 0 7200 V 1 - without rectifier Un = 3AC 0 1650 V (DC max. 1000 V) 2 - with rectifier U n = 3AC 0 1300 V (peak voltage downstream of the rectifier or intermediate circuit voltage of max. 1840 V) 2 AGH520S 5 4 3 4 IRDH375_D00124_01_D_XXEN/07.2018

Technical data Insulation coordination acc. to IEC 60664-1 Rated insulation voltage Rated impulse voltage/pollution degree Voltage ranges AC 800 V 8 kv/3 IRDH375 : Nominal system voltage Un AC, 3/(N)AC 0 793 V* Nominal frequency fn (for f < 50 Hz see characteristic curve in the manual) 0,1 460 Hz Nominal system voltage Un DC 0 650 V* IRDH375-435: Supply voltage US (also see nameplate) AC 88 264 V* Frequency range US 42 460 Hz Supply voltage US (also see nameplate) DC 77 286 V* IRDH375-427: Supply voltage US (also see nameplate) AC 19.2 55 V* Frequency range US 42 460 Hz Supply voltage US (also see nameplate) DC 19.2 72 V* IRDH375 : Power consumption Response values 14 VA Response value Ran1 (Alarm1) Response value Ran2 (Alarm2) Relative uncertainty (20 kω 1 MΩ) (acc. to IEC 61557-8) ± 15 % Relative uncertainty (1 20 kω) +2 kω/+20 % Relative uncertainty (1 10 MΩ) 0.2 MΩ/+20 % Response time tan at R F = 0.5 x R an and C e = 1 μf 5 s Hysteresis (1 10 kω) +2 kω Hysteresis (10 kω 10 MΩ) 25 % Measuring circuit Measuring voltage Um 40 V Measuring current Im (at R F = 0 Ω 220 μa Internal DC resistance Ri 180 kω Impedance Zi at 50 Hz 180 kω Permissible extraneous DC voltage Ufg DC 1200 V Permissible system leakage capacitance Ce 500 μf Factory setting 150 µf Displays Display, illuminated two-line display Characteristics (number) 2 x 16 Display range measured value Operating uncertainty (20 kω 1 MΩ) (acc. to IEC 61557-8) ±15 %** Operating uncertainty (1 20 kω) ±1 kω/±15 %** Operating uncertainty (1 MΩ 10 MΩ) ±0.1 MΩ/±15 %** Outputs/Inputs Test/reset button internal/external Cable length test/reset button, external 10 m Current output for measuring instrument SKMP (scale centre point = 120 kω): Current output IRDH375 (load) 400 μa ( 12.5 kω) Current output IRDH375B (load) 20 ma ( 500 Ω) Accuracy current output (1 kω 1 MΩ) related to the value indicated ±10 %, ±1 kω Serial interface Interface/protocol IRDH375 RS-485/ASCII Interface/protocol IRDH375B RS-485/BMS Connection terminals A/B Cable length 1200 m Cable (twisted in pairs, one end of shield connected to PE) recommended: J-Y(St)Y min. 2 x 0.8 Terminating resistor 120 Ω (0.5 W) Device address, BMS bus 1 30 (factory setting = 3) Switching elements Switching elements 3 changeover contacts K1 (Alarm 1), K2 (Alarm 2), K3 (device error) Operating principle K1, K2 (Alarm 1/Alarm 2) N/O or N/C operation Factory setting (Alarm 1/Alarm 2) N/O operation Operating principle K3 (device error) N/C operation Electrical endurance, number of cycles 12000 Contact class IIB acc. to DIN IEC 60255 Part 0-20 Rated contact voltage AC 250 V/DC 300 V Making capacity AC/DC 5 A Breaking capacity 2 A, AC 230 V, cos phi = 0.4 0.2 A, DC 220 V, L/R = 0.04 s Contact rating at DC 24 V 2 ma (50 mw) Environment/EMC EMC according to IEC 61326-2-4 Ed. 1.0 Shock resistance IEC 60068-2-27 (device in operation) 15 g/11 ms Bumping IEC 60068-2-29 (transport) 40 g/6 ms Vibration resistance IEC 60068-2-6 (device in operation) 1 g/10 150 Hz Vibration resistance IEC 60068-2-6 (transport) 2 g/10 150 Hz Ambient temperature (during operation) -10 +55 C Ambient temperature (during storage) -40 +70 C Climatic class acc. to IEC 60721-3-3 3K5 Connection Connection screw-type terminals Connection properties rigid/flexible 0.2 4 mm²/0.2 2.5 mm² flexible with ferrules without/with plastic sleeve 0.25 2.5 mm² Conductor sizes (AWG) 24 12 Other Operating mode continuous operation Mounting display-oriented Distance to adjacent devices 30 mm Degree of protection, internal components (DIN EN 60529) IP30 Degree of protection, terminals (DIN EN 60529) IP20 Type of enclosure X300, free from halogen DIN rail mounting acc. to IEC 60715 Flammability class UL94 V-0 Documentation number D00124 Weight 510 g Option W Shock resistance IEC 60068-2-27 (device in operation) 30 g/11 ms Bumping IEC 60068-2-29 (transport) 40 g/6 ms Vibration resistance IEC 60068-2-6 1.6 mm/10 25 Hz 4 g/25 150 Hz Ambient temperature, during operation -25 +70 C Ambient temperature for storage -40 +85 C Screw mounting 2 x M4 The data labelled with an * are absolute values ** = Under EMC test conditions in accordance with IEC 61326-2-4 the specified tolerances can double IRDH375_D00124_01_D_XXEN/07.2018 5

Bender GmbH & Co. KG P.O. Box 1161 35301 Gruenberg Germany Londorfer Strasse 65 35305 Gruenberg Germany Tel.: +49 6401 807-0 Fax: +49 6401 807-259 E-Mail: info@bender.de www.bender.de BENDER Group IRDH375_D00124_01_D_XXEN / 07.2018 / pdf / Bender GmbH & Co. KG, Germany Subject to change! The specified standards take into account the edition valid until 07.2018 unless otherwise indicated.