RLH Industries, Inc. Cleaning and Testing Fiber Optic Cable. Reference Guide MD A 0507

Similar documents
4-Channel Contact Closure Fiber Link Card System

Field Test Procedure for Optical Fibre Link Measurements

Ensuring Cabling Performance in the Customer-Owned Outside Plant

Ensuring Cabling Performance in the Customer-Owned Outside Plant. Keith Foord Product Manager Greenlee Communications

MicrOTDR. Optical Fault Locator. User Manual

Ensuring the Health of Tomorrow s Fiber LANs Part II OTDR Trace Analysis Become an Expert Troubleshooter with Advanced OTDR Trace Analysis

Fiber Optic Connector Cleaning and Inspection Kit Instructions

White Paper Fiber optic connections: check and clean first, then connect!

White Paper: Fiber Contamination, Cleaning and Inspection. Introduction.

Certified Fibre Optic Specialist - Testing

The Rise of Tier 2 Testing

Wilcom. Model FR2 Fiber Ranger Optical Fault Locator OPERATING INSTRUCTIONS

The True Value of Connector Inspection: New Challenges and Best Practices

Fiber Optics for Todays Industry Applications

4 Channel Contact Closure SFP DIN Fiber Link System

A Quick Start Guide to Fiber-to-the-Antenna (FTTA) Installation and Maintenance Testing. Vol. 2 Tier 2 Certification

SECTION TESTING OF FIBER OPTIC CABLES

Fibre Optic Basics FIA Summer Seminar 2014

2016 CDM Smith All Rights Reserved July 2016 SECTION FIBER OPTIC DATA NETWORK

Best Practice Briefing

A Quick Start Guide to Fiber-to-theAntenna (FTTA) Installation and Maintenance Testing. Vol. 2 Tier 2 Certification

Reflectance, The Hidden Danger That Increases Bit Error Rates in Your Fiber Networks Denver, May 22nd, 2010

FTTH NETWORK TESTING: REAL APPLICATIONS USING THE OLTS METHOD

Fibre Specification Standards

Fiber Optic and CAT 5, 6, 7 and 8 Installer Premise Cabling

White Paper: Standard-Compliant Certification & Best Practices Ensure Fiber End-face Cleanliness to Eliminate the #1 Cause of Fiber Failure

Link loss measurement uncertainties: OTDR vs. light source power meter By EXFO s Systems Engineering and Research Team

Hands-On CAT 5/6 & Fiber Optic Installer

Fibre (TIA) Field Test Specification

Hands-On Fiber Optics ISP/OSP - Advanced Combo- Tech

Hands-On Fiber Optic ISP / OSP Combo-Tech Splicing, Termination & Testing

This is to certify that the optical output of the: SENSORNET LR-DTS Temperature Sensing System: (Variants Mark 1, Mark 2a and Mark 2b)

MOST EFFECTIVE METHOD FOR WIPING A FIBRE

A. General: Horizontal and backbone cabling shall be verified in accordance with ANSI/TIA/EIA-568-C and the addendum for fiber optic testing.

Benefits of Enhanced Event Analysis in. Mark Miller

NX8601BF-AA. Data Sheet R08DS0109EJ0100 Rev.1.00 Apr 19, 2013 LASER DIODE DESCRIPTION FEATURES

USER GUIDE. RLH Auxiliary Fan Kit. Description. The leader in rugged fiber optic technology. ENCLOSURE TEMPERATURE CONTROL. RLH Industries, Inc.

EXECUTING HIGHLY ACCURATE FIBER MEASUREMENTS IN A FRACTION OF THE TIME

OPTICAL TIME-DOMAIN REFLECTOMETER

LASER DIODE NX7637BF-AA

LAB REPORT SUBMISSION COVER PAGE ETN4106 OPTOELECTRONICS AND OPTICAL COMMUNICATIONS

Field Testing and Troubleshooting of PON LAN Networks per IEC Jim Davis Regional Marketing Engineer Fluke Networks

STANDARD TEST PROCEDURE PRE-TEST QUALITY OF OPTIC FIBRE CABLE ON DRUMS TYPE OF CABLE :

OTDR II. Tier-2 Optical Time Domain Reflectometer for Multimode and Single-mode Fiber Cabling

MT-RJ Optical Fiber System Field Testing

Optical Return Loss Measurement by Gregory Lietaert, Product Manager

OWL. Laser OWL Series. Operations Guide. Singlemode Light Sources. Optical Wavelength Laboratories. Date: October 1, 2015

Connections You Can Count On.

ECP OPTICAL FIBRE SPLICING, TESTING AND COMMISSIONING REQUIREMENTS

Accelerating NBN fiber testing. Tom Ronan Marketing Lead Fiber Optics Melbourne

SECTION TESTING OF FIBER OPTIC CABLES

ENCIRCLED FLUX (EF) TEST SOLUTIONS SPSB-EF LAUNCH MODE CONDITIONER AND FLS-600-NS1548 LIGHT SOURCE DESIGNED FOR CONTROLLED MULTIMODE LOSS TESTING

Qualification Test Report LightCrimp* Plus Singlemode and Multimode LC Connector (Field Installable)

The Optical Time Domain Reflectometry and the Fusion Splicer Laboratory exercise


T3/E3 Fiber Optic Line Drivers

The Importance of Properly Cleaning Fiber During Splicing

Installation and Operation Manual

STATE OF NEW JERSEY DEPARTMENT OF TRANSPORTATION TRENTON, NEW JERSEY SPECIFICATIONS FOR FUSION SPLICE AND SPLICE ENCLOSURE FIBER OPTIC CABLE

STANDARD CONFORMANCE

MTTplus Modular Test Platform

OTDR. Optical Time Domain Reflectometer. User Guide

VTI Services Technical Bulletin (TB) OTDR Measurement of Installed Optical Fibre Cabling Permanent Links and Links

Connector Maintenance

Advanced Test Equipment Rentals ATEC (2832) LS-1310/1550 Laser Source. Service Information Sheet.

FACULTY OF ENGINEERING LAB SHEET OPTICAL COMMUNICATION SYSTEMS EOP4066 TRIMESTER 1 (2013/2014)

TECHNICAL - *All Pricing are Exclusive of VAT. Introduction to Fibre Optics for non-fibre Technicians (can also be done on-site) TARGET AUDIENCE:

M210 Multifunction Micro OTDR

Simplex ES Network. ES Net Network Applications, Communications, Options and Specifications. ES Net features. UL, ULC Listed*

M700-Series Multifunction OTDR

Platinum Split 4000 & Platinum Split 4000 Fully Ducted COLD WEATHER START KIT Installation Manual

M-Series Compact OTDRs User s Guide

COLD WEATHER START KIT Ceiling Mount 4000

Special Provision No. 683S28 December 2017

STANDARD FOR INDOOR-OUTDOOR OPTICAL FIBER CABLE

4120 Fire Alarm Network Reference

Basic Professional Fiber Optic Installation

OPX-BOX. Platform Highlights. Software Support. Key Features

FLX380-30x FlexTester OTDR

GR-326-CORE Singlemode Optical Connectors and Jumper Assemblies

M310 Data Center OTDR

M210 Multifunction Micro OTDR

INTERNATIONAL STANDARD

TFS-FS1 Optical Leakage Detector. Operation Manual

FTBx-740C-DWC TUNABLE OTDR C-BAND DWDM METRO ETHERNET LINK CHARACTERIZATION

IDEAL INDUSTRIES, INC. USER MANUAL IDEAL OTDR

Fiber Optic Products Catalog

INTERNATIONAL STANDARD

ASSMANN ELECTRONIC GmbH ASSMANN SYSTEM GUARANTEE. DIGITUS Professional Fiber Optic Cabling System. Appendix B - Provisions for acceptance

Fiber Optic Distribution Cables (6-144 Fibers)

infrastructure for 10, 40 and 100Gbits/s readiness

Sources of End Face Contamination on Fiber Optical Interconnects and Recommended Best Practices for Removing the Contaminates

TRM 2.0 Test Results Manager All-In-One Comprehensive Analysis and Reporting Software

Chargebuster Ion Gun Installation, Operation and Maintenance

ENCIRCLED FLUX (EF) TEST SOLUTIONS

9 W, 15 W and 25 W Industrial Fiber Laser Systems IFL Series

Jan07 Rev B

OF-500 OptiFiber. Advanced Test Equipment Rentals ATEC (2832) Users Manual. Certifying OTDR

Flexibility, scalability andsecurity

ACCESS Master MT9085 Series. Product Introduction

Transcription:

RLH Industries, Inc. Cleaning and Testing Fiber Optic Cable Reference Guide MD-019 2014A 0507

RLH Industries, Inc. Copyright 2013 RLH Industries, Inc. All rights reserved. No part of this document may be copied or distributed without permission. The RLH logo may not be used for commercial purposes without the prior written consent of RLH and may constitute trademark infringement. Other company and product names mentioned herein are trademarks of their respective companies. Mention of third-party products is for informational purposes only and constitutes neither an endorsement nor a recommendation. RLH assumes no responsibility with regard to the performance or use of these products. The information contained in this document is the property of RLH Industries, Inc. and may not be reproduced or disseminated to third parties without the express written permission of RLH. Every effort has been made to ensure that the information in this manual is accurate. RLH is not responsible for printing or clerical errors. Because we are constantly seeking ways to improve our products, specifications and information contained in this document are subject to change without notice. RLH Industries, Inc. 936 North Main Street Orange,CA 92867 Ph. 714 532-1672 email: info@fiberopticlink.com www.fiberopticlink.com 2 RLH Industries, Inc. 866-DO-FIBER www.fiberopticlink.com Contents

1. Important Information Contents Intended Audience 4 Conventions 4 General Safety Practices 4 2. Introduction 3. Clean and Inspect All Connectors Inspection 6 Cleaning 6 Static Charge 6 ESD 6 Fiber Optic Cleaning Fluids 6 IPA Alcohol 7 4. Testing Fiber Optic Cables 5. Support Measuring Loss 7 OLTS Testing- Always Required 7 OTDR Testing- Optional but Beneficial 8 Recommended Approach to Cleaning, 10 Inspecting, and Testing 10 Technical Support 11 Contact Information 11 Contents RLH Industries, Inc. 866-DO-FIBER www.fiberopticlink.com 3

1. Important Information Intended Audience This document is intended for use by knowledgeable telco/network installation, operation and repair personnel. Every effort has been made to ensure the accuracy of the information is accurate. However, due to constant product improvement, specifications and information contained in this document are subject to change without notice. Conventions Symbols for notes, attention, and caution are used throughout this manual to provide readers with additional information, advice when special attention is needed, and caution to prevent injury or equipment damage. Notes: Helpful information to assist in installation or operation. Attention: information essential to installation or operation. Caution: Important information that may result in equipment damage or injury if ignored. General Safety Practices The equipment discussed in this manual may require tools designed for the purpose being described. RLH recommends that installation and service personnel be familiar with the correct handling and use of any equipment used, and follow all safety precautions including the use of protective personal equipment as required. Laser Safety Radiation emitted by laser devices is invisible and dangerous to the human eye. Avoid eye exposure to direct or indirect radiation. Do not operate without fiber cable attached or dust caps installed. 4 Important Information

2. Introduction Fiber optic cable provides a low loss medium for high-speed communications. It also has the benefit of being dielectric. In other words, the glass fiber itself does not conduct electricity, and is immune to electromagnetic interference and power surges. Signals are transmitted through fiber using light, not electrical energy. While the continuous fiber cable itself has very low transmission loss, the fiber terminations at each access point provide a potential Achilles heel. Light must pass from the end of one fiber optic connector to another with a minimum of attenuation. The biggest cause of signal loss across fiber optic connectors is contamination. Substandard installation practices in pathways and enclosures can also affect the signal loss of the fiber. The growing prevalence of fiber requires network technicians have a general understanding of fiber optic cable testing to enable them to troubleshoot or qualify cables. A majority of issues can be identified with two steps: Cleaning/inspection of connector end-faces. Loss testing. The TIA/TSB 140 standard requires that each fiber link be tested for attenuation with an Optical Loss Test Set (OLTS) kit. This standard considers an Optical Time Domain Reflectometer (OTDR) optional. An OLTS tester, using the appropriate reference method, will yield the most accurate loss reading. However, the OLTS tester cannot characterize the fiber to show the quality of the fiber spans, connections, and splices. 3. Clean and Inspect All Connectors A note on regarding to size helps to visualize the impact of dust and dirt. Comparing an average human is around 85 microns in diameter. The core, being the signal carrying portion, of most widely used optical fibers is either 62.5 microns or 9 microns. It takes minimal amount of dust particles to block a 9 micron window. A blocked window means light is blocked and the network experiences signal loss. ➆ ➅ ➄ ➃ ➂ Optical fiber cord ➁ ➀ ➀ Core ➁ Cladding ➂ Optical fiber ➃ Primary coat ➄ Buffer ➅ Kebler (A tensile strength material) ➆ Jacket 5 RLH Industries, Inc. 866-DO-FIBER www.fiberopticlink.com Introduction

Inspection To view fiber connector ends for cleanliness use a fiber optic microscope with proper magnification, typically 200x to 400x. Some microscopes are all optical, which can direct laser light into a user s eye, while others are available with no optical path to the eye. All manufactures caution users not to view live fibers. A technician can easily inadvertently view live fiber because laser emissions are invisible to the human eye. Cleaning Using a fiber optic microscope the user can determine if the connectors are dirty, cracked, or pitted. Cracked or pitted fiber ends will need to be re-polished or replaced. More commonly the connector ends will be dirty. Do not make the mistake of cleaning a fiber end with a normal cloth, this is not helpful. Other contaminates capable of blocking a 9 micron window may be on that material no matter how clean it appears. Cleaning fiber optic connectors requires proper fiber optic grade cleaning materials. Materials vary from optical grade wipes to cassette cleaners. Technicians often use these materials effectively alone as a dry wipe, but doing so can add a static charge across a connector end-face. Depending on the climate and season this may not present much of an issue. Although, in dry winter months and air-conditioned areas allow static charge to be a significant interference to the connector cleaning process. For further questions and to acquire an order number for a cleaning kit contact a RLH sales representative or visit the RLH website. Static Charge Static charge build up on connectors attracts charged particles to the connector end-face. This can effectively nullify the dry cleaning process. Particles are drawn to the foremost part of the connector endfaces during mating and un-mating. Since fiber optic connectors are polished to have a radius end-face with the fiber core at the center, static charge may cause particles to migrate to the optimal signal blocking position. ESD Static charge is not ESD. Optical fiber is glass and single fiber connector ferrules are ceramic. There is no conductive path from the connector end-face to the fiber jacket. Therefore ESD protection will not eliminate static charge from connector end-faces. Fiber optic cleaning fluids are optimal for eliminating static charges. Fiber Optic Cleaning Fluids These fluids are static dissipative. A technician, using an optical-grade cleaning wipe, can wet a corner with the appropriate cleaning fluid and drag the connector end-face from the wet area into the dry area. The fluid will neutralize static charge and help to release particles from the end-face. 6 RLH Industries, Inc. 866-DO-FIBER www.fiberopticlink.com Introduction

IPA Alcohol The standard for fiber optic cleaning has long been IPA alcohol, which is a static dissuasive. However, it is far from an ideal optical cleaning fluid. For starters, it is hydrophilic - meaning it absorbs water. IPA in a dispenser bottle will absorb atmospheric moisture over time. This has a negative effect on the cleaning process for two reasons. First, water slows down the drying process and requires more air to evaporate off all the fluid. More air brings more dust unless working in a clean room. Water absorption into IPA is also bad as water can leave a streaky residue on the connector end-face. Although IPA has been a successful standard cleaning fluid there are safer cleaning solution alternatives available today that dry faster than alcohol, do not absorb water, are non-hazardous, and are not regulated. It is important when cleaning to do both connectors on jumpers and the connector behind the panel. In the case of having an unaccessible connector or one where there is live traffic on adjacent fibers a commonly used option is to use a fiber optic cleaning stick to clean the end-face inside the adaptor. Insert the stick until it makes contact with the end-face, twist around ten times and discard. The twisting can generate a static charge so a quick drying static dissipative cleaning fluid is a plus. 4. Testing Fiber Optic Cables Measuring Loss The TIA-standard requires you to make one and only one measurement, insertion loss, to certify a fiber optic cable. This is also known as db loss, attenuation, or simply loss. Insertion loss is singled out by the TIA because it can be impacted by poor installation practices. Poorly polished or dirty connectors can cause high loss, or a cable pulled around a corner that does not meet minimum bend radius specifications may exhibit high loss. OLTS Testing- Always Required TIA-standards specify that you must measure loss using an optical power meter and the proper light source to certify an optical fiber cable. Multimode fiber loss measurements must be made using an LED source. Single-mode fiber loss measurements require a laser source. Light sources and optical power meters are available as low-cost, stand-alone units, or may be integrated into optical loss tests sets (OLTS). OLTS offers additional features such as dual-fiber testing, length measurement, and pass/fail analysis. Either type of tester will provide accurate standards-compatible results as long as you use proper reference setting and connector cleaning procedures. Introduction RLH Industries, Inc. 866-DO-FIBER www.fiberopticlink.com 7

Optical Power Meter and Light Source Diagram Equipment Room Telecom Room Optical Power Meter connection splice connection Light Source Testing Using OLTS Diagram Equipment Room Telecom Room OLTS (main) connection splice connection OLTS (remote) TIA-standards also specify maximum lengths for horizontal and backbone optical fiber cables, which you must verify as part of the certification process. Although the TIA-standard does not require that you optically measure cable length. You may use a tape measure or simply refer to length markings on the cable itself. Note: To certify an optical fiber cable you will need either an optical power meter and compatible light source(s) or an OLTS main-remote pair. Other test equipment may be very useful as discussed next, but nothing else is required. OTDR Testing- Optional but Beneficial TIA-standards also contain component specifications including maximum loss values for connections, splices, and optical fiber segments. It is good practice to measure the loss of each connection and splice, and check cables for macro-bends and other defects for quality assurance purposes. The type of fiber tester normally used for these functions is an Optical Time Domain Reflectometer or OTDR. OTDR to Measure End-to-End Loss Diagram Equipment Room Telecom Room OTDR Launch Cable connection splice connection Receive Cable 8 RLH Industries, Inc. 866-DO-FIBER www.fiberopticlink.com Introduction

OTDR s operate like a radar. They generate short pulses of light and then sample the light backscattered by fiber segments and related by connections and other events. This allows the user (or OTDR software) to estimate the loss slope or attenuation of fiber segments and the insertion loss of individual connections and splices. To measure the loss of the first and last connection in each fiber link or link segment under test you must use a launch and receive cable respectively. Launch and receive cables may also be called launch reels, pulse suppressors, or test cables. Test cables usually include 100 or more meters of fiber in a ring-shaped or rectangular case, terminated by jumpers that will mate with the fiber under test. To illustrate the advantages of an OTDR, consider a 100m (328ft.) backbone cable with the following component loss values. Equipment room connection 1.2 db Splice 0.1dB Fiber 0.1dB Telecom closet connection 0.3dB According to the TIA-standards, the maximum acceptable loss for this cable is : OTDR Trace Showing a Bad Connection connection loss 1.2dB - too high! End-to-End loss 1.9dB - OK 1.5dB of connection loss (0.75dB for each connection) 0.3dB splice loss 0.1dB fiber loss A total of 1.9dB Since this cable has an overall (end-to-end) insertion loss of 1.7dB, it would probably be passed by an OLTS measurement. An OTDR trace of this cable would reveal that the telecom closet connection has a loss of 1.2dB, which exceeds the TIA-standard specified maximum of 0.75dB. Equipment Room Telecom Room Note: An OTDR can indicate and localize problems that would often be missed by an OLTS or optical power meter and light source kit. In cases where an OLTS can detect a fault, for example the infinite loss caused by an open connection or fiber break, it cannot tell you where the fault is located. An OTDR trace, on the other hand, will locate such events as shown below. Introduction RLH Industries, Inc. 866-DO-FIBER www.fiberopticlink.com 9

OTDR Trace Showing a Break in the Fiber Fiber break Original trace New trace Note: An OTDR test can not replace an OTLS measurement. The OLTS test is required by the TIA-standards, and OTDR measurements can slightly under-estimate loss, especially on multimode fibers. An OLTS test would indicate fiber mis-matches of 50/125 and 62.5/125um fibers with a high loss reading. An OTDR which uses a laser and does not fill the outer modes may not pick up the core mismatch. OTDR tests offer additional information that can help you detect and proactively fix problems often missed by OLTS tests. Some jobs may require tests on all optical fiber cables using an OTDR by a quality-conscious consumer. On other jobs, having an OTDR characterization of fiber(s) at the time you signed-off on the project can protect the installer from damages caused by installers that come in later and pull other cable(s) into the pathways that may damage the fiber, causing macro- or micro-bends or breaks. Dust, dirt, oils, and other common contaminates, along with poor installation practices can cause hours of grief for network service technicians. Fortunately, proper cleaning tools and good test techniques allow trained technicians to effectively remove contaminates, find and correct fiber problems, and get networks back in service. Whether or not you do OTDR testing is up to your schedule, budget, and often your customer. Recommended Approach to Cleaning, Inspecting, and Testing Always presume connectors are dirty prior to mating. Fiber optic termination has two connectors. Always clean both! Cleaning one and re-mating it to a dirty connector is counter productive. Use optical quality cleaning materials to clean fiber end-faces. Use an optical quality cleaning fluid to minimize the static build up. Use a fiber optic microscope with built in eye-protection to inspect connectors prior to mating. Use Light Source & Power Meter or OLTS kits to test for Attenuation. Use OTDR test to characterize the installation and get sign-off when required. 10 RLH Industries, Inc. 866-DO-FIBER www.fiberopticlink.com Introduction

5. Support Technical Support Email: support@fiberopticlink.com 24/7 technical support: Toll Free 1-855-RLH-24X7 Toll Free 1-855-754-2497 Contact Information Corporate Headquarters: RLH Industries, Inc. 936 N. Main Street Orange, CA 92867 USA Phone: (714) 532-1672 Toll Free 1-800-877-1672 Toll Free 1-866-DO-FIBER Fax: (714) 532-1885 Email: info@fiberopticlink.com Web site: www.fiberopticlink.com Introduction RLH Industries, Inc. 866-DO-FIBER www.fiberopticlink.com 11

RLH Industries, Inc. 936 N. Main Street, Orange, CA 92867 USA T: (714) 532-1672 F: (714) 532-1885 Please contact your RLH sales representative for pricing and delivery information. Specifications subject to change without notice. 12 RLH Industries, Inc. 866-DO-FIBER www.fiberopticlink.com Introduction