1 Field Testing of fiber optic infrastructure for 10, 40 and 100Gbits/s readiness Christian Schillab Product Manager Media Test Fluke Networks Europe Member BritishStandards Institute Working Group TCT 7/ /1 /1 & CENELEC TC215 WG1 PTH und PTT
2 Topics Intelligent test regimes which optimize performance margins with little increase in testing time The evaluation & documentation of the performance and condition of the test tset up Choosing the optimal test method for complex hybrid channels Testing of complex and demanding MPO cassettes based channels with a later migration to 40GBASE R4, 100GBSE SR10 in mind
3 With 40GBASE R4, 100GBSE SR10 a trend continues which provides significantly higher bandwidth at the expense of distance and insertion loss budget?
4 From The Archive. BICSI 2002
5 IEEE 802.3ba 40/100GB/s Justification for Field Testing / Inspection 1. Field ermination 2. Patched multi segment channels Multi vendor Add Changes and Moves performed by operator 3. Dusteffects performance 4. Demanding limits
6 IEEE 802.3ba Field Testing? Wie wichtig ist die Abnahmemessung? Structured Cabling Connector Less Channel Permanent Link / Channel
7 40/100 GbE Fiber Applications 40GBASE SR4 40GBASE LR4 40GBASE FR Mulitmode Single Mode Source 4 x 10Gb VCSEL 4 x 10Gb Laser 1 x 40Gb 100GBASE SR10 100GBASE LR4 Laser 100GBASE ER4 Optics Parallel Mulitmode Simplex Single Mode Connnector Source MPO 10 x 10Gb VCSEL LC 4 x (or 10Gb similar) Laser 1 x 40Gb Laser Wavelenght Optics 850 nmparallel nm Simplex Gb) Fiber Connnector OM3 OM4 MPO OS2 LC (or OS2similar) MaxDistance Wavelenght 100 m m nm 10, nm 2,000m 1550 nm Loss Budget 1,9 db 1,53 db 6.7 db (DWDM) 4.0 db (DWDM) Fiber OM3 OM4 OS2 OS2 Max Distance 100 m 150 m 10,000 m 40,000m Loss Budget 1,9 db 1,53 db 8.3 db 18 db
8 40/100GBase SR/LR/ER: Which ISO Channel supports it?
9 Fiber Optic Test Methodes Standard Methods TIA 568 C Tier 1 Tier 2 ISO AMD.1 / ISO/IEC BASICTest Regime LSPM:Light Source & Power Meter EXTENDED Test Regime OTDR: Optical Time Domain Reflectometer The two methods are complimentary! OTDR based method does not replace the LSPM based solution Both methods have advantages and limitations
10 OTDR s Have Multiple Points of View db db 0.33 db 0.32 db db db
11 Causes for Directivity Potential causes for different results depending on the direction i 1. Two fibers are different Diameter Back Scatter Index NA. Numerical Aperture Major difference in IR Index of Refraction 2. Damaged fiber end faces Glassis chipped off
12 Bi Directional Averaging The averaging can be performed manually or by advanced results management software
13 Can We Quantify Directivity No standard defines how to calculate it but it is simple ISO/IEC defines no maximum allowed directivity
14 How to Quantify Directivity Delta of measured loss from End 1 and End 2 divided by 0m: Δ ( and 0.41) / 2 = 06/ = 03dB Δ (0.44 and 0.20) / 2 = 0.6 / 2 = 0.3dB Inthisexample: Priorto averaging the result willbe over stated by 0.30dB in one and understated by 0.3dB in the other directions NOTE: The overall loss is not suffering from directivity Only if launch and receive fiber exhibit no directivity if tested without a link
15 No Bi Directional Averaging Consequences A directivity of can often be seen with out mixing 50 and 60µm and new and OM1/2 fiber Even fiber from the same supplier will show up to 0.15dB of directivity For this example we assume a 100m patch panel to patch panel link with connectors win an IL ranging from 0.15 to 0.25dB. The fibers loss is 3dB/km The assumed directivity is 0.2dB for launch/tail fiber link and ~ 0dB between launch & tail Meas. Meas. Avg. Actual Limit f. End 1 Meas. f. End 2 Meas. Meas. Avg. Actual Limit f. End 1 f. End 2 Meas. 0 m 0.15 db 0.75 db m 0.15 db 0.30 db m 0.25 db 0.75 db m 0.25 db 0.30 db Atten.Koeff. 3dB/km 3.5dB/km Atten.Koeff. 3dB/km 3.5dB/km Overall Loss 0.70 db 1.85 db Overall Loss 0.70 db 0.95 db Take Away: PASS/FAIL / info for a is available right away for over all Panel to Panel loss for individual elements in the link only after computing the average
16 MPO Cassettes / Panel Panel Loss Budgets what you need 10GBASES SR requirement is nm 40/100GBASE SR requirement is 850 nm 300 m 150 m LC MPO Trunk MPO LC Total TIA ISO (2002) ISO (2006) MPO treated as a splice nd Gen. Cassettes State of the art Cherry Picked Components
17 Low Loss MPO The Drivers Zoned Data Centers Distributor in accordance with ISO/IEC Network access cabling system Main distribution cabling system Zone distribution cabling system Equipm. cabling Courtesy: TE Connectivity
18 Testing Zoned Data Centers After the installation only the links can be testet The Patched Channel is configured by the network user Link Test #1 Link Test #2 Link Test #3 Channel Courtesy: TE Connectivity A common mistake is to test a links to channel limits Correct is to certify compliance with the link limit and/or compliance with component limits
19 Testing a Complex Channel Assumptions: Complex cannel consisting iti of 4 segments One connection is very poor (1.00dB) All other connections 0.25dB and fiber 3.0dB/km Conn. #1 Fiber #1 Conn. #2 Fiber #2 Conn. #3 Fiber #3 Conn. #4 Fiber #4 Conn. #5 Total L (m) Value Take Away: Tier1/BASIC LSPM Testing: The good connections may cover up for one very poor one Only an OTDR can find the unnecessary bottle neck
20 Testing a Complex Channel Assumptions: Complex cannel consisting iti of 4 segments One connection is very poor (1.00dB) All other connections 0.25dB and fiber 3.0dB/km Conn. #1 Fiber #1 Conn. #4 Total L (m) ) Value Take Away: PASS/FAIL based on the length depended link budget will flag bad connectors. The OTDR will allow to identify the poor end and which cassette to swap/connector inspect and clean Conn. #1 Fiber #1 Conn. #4 Total L (m) Value Take Away: OTDR PASS/FAIL testing should be based on component limits. More generous component limits make the information valuable even before computing the accurate average
21 Can OTDRs PASS/FAIL a link based on a length dependent limits? This function is common in LSPMs (Light Source and power meters) Directivity and tight ISO or even tighter project specific limits i makes this function also desirable for an OTDR The time saving is significant > 50% Such a function in an OTDR will not obsolete LSPMs because they will always provide the most accurate loss measurement They are less expensive and often considered to be easier to use
22 OTDR PASS/FAIL Based on a Length Dependent Link Limit db 0.33 db db Automatic Limit Calculation for OTDR PASS/FAIL testing: First Connector 0.30 db Fiber 50.49*3.5/1000 = 0.18 db Last Connector 0.30 db Total 0.78 db
23 Bi Directional OTDR Tests Without a Tail Fiber db 0.33 db 0.32 db db db
24 Testing Of Parallel Optics Based Cabling Infrastructure MPO / MPT
25 Fiber Inspection Equipment exists for inspecting MPO connectors
26 Polarity MPO/MTP System Type A 26
27 Polarity MPO/MTP System Type A 27
28 Polarity MPO/MTP System Type B Tech Forum "Verkabelung Netze Infrastruktur" 28
29 Polarity MPO/MTP System Type B 29
30 Polarity MPO/MTP System Type C Tech Forum "Verkabelung Netze Infrastruktur" 30
31 Polarity MPO/MTP System Type C 31
32 Field Test Method Available Today Multiplesteps arerequiredrequired because 1. Lack of a non critical MPO connection on the meter 2. Lack of a switchable source 3. Keys prevent a modified 2 jumper method with fan out (Hydra) only 4. Tight limit require a initial verification of the auxiliary SC / LC cords 5. Tight limits require a normalization of the auxiliary SC/LC cords
33 MPO Field Tester Wish List 1. Testing of all fibers in the link in one go 2. Non critical MPO connector on the meter to support the most accurate one jumper method 3. Switchable MPO source to verify polarity System A, B, C,. Field terminated connectors 4. MPO Test Reference Cords with reference grade connectors A definition for reference grade MPO connectors!
34 Conclusio Standards d based dlimits it can not be used to test tan installation ti Test needs to be based on limits agreed by the supplier, customer/consultant and the installer Procedures for testing and setting the reference need to be agreed on by Test cords (Fan Out) will be specific for the project Attention needs to be paid to cleaning and inspection Complex channels constructions can only be supported with components exceeding the normative requirements
35 Thank You! for Your Attention I would be happy to answer an further question christian.schillab@flukenetworks.com
Reflectance, The Hidden Danger That Increases Bit Error Rates in Your Fiber Networks Denver, May 22nd, 2010
Reflectance, The Hidden Danger That Increases Bit Error Rates in Your Fiber Networks Denver, May 22nd, 2010 Adrian Young Sr. Customer Support Engineer Foreword Reflectance is measured using an Optical
More informationFibre (TIA) Field Test Specification
This document has been prepared to aid consultants or engineers in developing contractual specifications covering the testing of duplex fibre optic cabling installations. It is offered as a general guide.
More informationCHALLENGE OF THE NEW OPTICAL FIBRE TECHNOLOGIES
THE CHALLENGE OF THE NEW OPTICAL FIBRE TECHNOLOGIES 17th September 2002 Botanical Gardens Birmingham The Way We Were 1GbE and 10GbE OF Categories Channel Design Cleaning SFF Connecting Hardware Testing
More informationField Testing and Troubleshooting of PON LAN Networks per IEC Jim Davis Regional Marketing Engineer Fluke Networks
Field Testing and Troubleshooting of PON LAN Networks per IEC 61280-4 Jim Davis Regional Marketing Engineer Fluke Networks Agenda Inspection and Cleaning APC vs UPC PON basics Wavelengths Architecture
More informationSTAND OUT FROM THE CROWD. Bisham Abbey, 14th May 2002 INTRODUCTION. Work Smart FIA. The Fibreoptic Industry Association STAND OUT FROM THE CROWD
INTRODUCTION Work Smart FIA STAND OUT FROM THE CROWD 14th May 2002, Bisham Abbey Mike Gilmore 2002 Fibreoptic Industry Association Work Smart www.it-cabling.com www.e-readybuilding.com PO Box MT65, LEEDS,
More informationEXECUTING HIGHLY ACCURATE FIBER MEASUREMENTS IN A FRACTION OF THE TIME
10 /0 /100Gb/s transmission links are typically shared by a vast number of application and users. EXECUTING HIGHLY ACCURATE FIBER MEASUREMENTS IN A FRACTION OF THE TIME Claiming that they are most of the
More informationThe Rise of Tier 2 Testing
The Rise of Tier 2 Testing Why enterprises today demand better visibility into their fiber infrastructure Unprecedented demand for more bandwidth, faster network speeds, lower latency, and improved data
More informationVTI Services Technical Bulletin (TB) OTDR Measurement of Installed Optical Fibre Cabling Permanent Links and Links
VTI Services Technical Bulletin (TB) OTDR Measurement of Installed Optical Fibre Cabling Permanent Links and Links TB Number 004 This bulletin is supplied for information only and is intended to provide
More informationOLTS vs OTDR Tier-2 Expert; How far from Tier-1?
OLTS vs OTDR Tier-2 Expert; How far from Tier-1? Christian Till, Application Engineer 2016/12/09 1 Why this industry is exciting! Bandwidth grows like crazy Global DC traffic 5ZB now, 10.4ZB 2019 Hyperscale
More informationTESTING HIGH SPEED FIBER LINKS
TESTING HIGH SPEED FIBER LINKS Rodney Casteel, RCDD, DCDC, NTS, OSP - CommScope, Chair TIA FOTC Tyler Vander Ploeg - Viavi Solutions Jamie Humphreys - EXFO Rob Gilberti - AFL Jim Davis - Fluke Networks
More informationThis is a preview - click here to buy the full publication
ISO/IEC 14763-3 CONSOLIDATED VERSION Edition 2.1 2018-08 colour inside Information technology Implementation and operation of customer premises cabling Part 3: Testing of optical fibre cabling INTERNATIONAL
More informationData sheet OpDAT breakout cable 12x1 OM4 - bend insensitive, class Dca s1 d1 a1
Page 1/9 Illustrations Principle diagram See enlarged drawings at the end of document Product specification connection cable I-V(ZN)HH breakout cable for direct connector termination for indoors and outdoors
More informationLAB REPORT SUBMISSION COVER PAGE ETN4106 OPTOELECTRONICS AND OPTICAL COMMUNICATIONS
1/10 FACULTY OF ENGINEERING LAB REPORT SUBMISSION COVER PAGE ETN4106 OPTOELECTRONICS AND OPTICAL COMMUNICATIONS TRIMESTER 3, SESSION 2016/2017 Student Name: Student ID: Degree Major (please circle): EE
More information4120 Fire Alarm Network Reference
4120 Fire Alarm Network Reference Features Autocall 4120 Fire Alarm Network communications are available for wired or fiber optic connections Wired communications are available on Network Interface Cards
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD ISO/IEC 14763-3 First edition 2006-06 Information technology Implementation and operation of customer premises cabling Part 3: Testing of optical fibre cabling Reference number ISO/IEC
More informationDatasheet: OptiFiber Pro OTDR
Datasheet: OptiFiber Pro OTDR The OptiFiber Pro OTDR is the Tier 2 (extended) fiber certification solution and part of the Versiv Cabling Certification product family. The Versiv line also includes copper
More informationAccelerating NBN fiber testing. Tom Ronan Marketing Lead Fiber Optics Melbourne
Accelerating NBN fiber testing and workforce Performance. Tom Ronan Marketing Lead Fiber Optics Melbourne Agenda Network Elements and Parameters Distributed Fiber Network (DFN) Construction Network Activation
More informationDesigned for Enterprise Fiber
Datasheet: OptiFiber Pro OTDR - The OptiFiber Pro OTDR is the Tier 2 (extended) fiber certification solution and part of the Versiv Cabling Certification product family. The Versiv line also includes copper
More informationEnsuring Cabling Performance in the Customer-Owned Outside Plant. Keith Foord Product Manager Greenlee Communications
Ensuring Cabling Performance in the Customer-Owned Outside Plant Keith Foord Product Manager Greenlee Communications Introduction: Outside plant fiber networks require low reflectance terminations for
More informationOptiFiber Pro OTDR Built for the enterprise
OptiFiber Pro OTDR Built for the enterprise As enterprise networks and datacenter architectures evolve, IT infrastructure administrators demand better OTDR technology to maintain fiber network performance.
More informationRLH Industries, Inc. Cleaning and Testing Fiber Optic Cable. Reference Guide MD A 0507
RLH Industries, Inc. Cleaning and Testing Fiber Optic Cable Reference Guide MD-019 2014A 0507 RLH Industries, Inc. Copyright 2013 RLH Industries, Inc. All rights reserved. No part of this document may
More informationFACULTY OF ENGINEERING LAB SHEET OPTICAL COMMUNICATION SYSTEMS EOP4066 TRIMESTER 1 (2013/2014)
FACULTY OF ENGINEERING LAB SHEET OPTICAL COMMUNICATION SYSTEMS EOP4066 TRIMESTER 1 (2013/2014) OC1 FIBER LINK CHARACTERIZATION WITH OTDR *Note: On-the-spot evaluation may be carried out during or at the
More informationM310 Data Center OTDR
Designed for Data Center Testing, Troubleshooting and Documentation Features Event Dead Zone 0.8 m Attenuation Dead Zone
More informationAS/NZS ISO/IEC :2012
AS/NZS ISO/IEC 14763.3:2012 (ISO/IEC 14763-3:2011, MOD) Australian/New Zealand Standard Telecommunications installations Implementation and operation of customer premises cabling Part 3: Testing of optical
More informationEnsuring Cabling Performance in the Customer-Owned Outside Plant
Ensuring Cabling Performance in the Customer-Owned Outside Plant Needs to be able to qualify the installation to validate bandwidth requirements are met Future high bandwidth applications Future Proof
More informationEnsuring the Health of Tomorrow s Fiber LANs Part II OTDR Trace Analysis Become an Expert Troubleshooter with Advanced OTDR Trace Analysis
Ensuring the Health of Tomorrow s Fiber LANs Part II OTDR Trace Analysis Become an Expert Troubleshooter with Advanced OTDR Trace Analysis Experience designing cable and network testers has enabled a breakthrough
More informationMT-RJ Optical Fiber System Field Testing
MT-RJ Optical Fiber System Field Testing Table of Contents INTRODUCTION... 3 TEST JUMPERS... 4 LAUNCH CONDITIONS... 4 MT-RJ TEST KITS... 5 MT-RJ SYSTEM TESTING: Fixed transmit and receive (SC or ST-style)
More informationDatasheet: OptiFiber Pro OTDR
Datasheet: OptiFiber Pro OTDR Accelerates enterprise fiber troubleshooting and certification. The OptiFiber Pro OTDR is the Tier 2 (extended) fiber certification solution and part of the Versiv Cabling
More informationA. General: Horizontal and backbone cabling shall be verified in accordance with ANSI/TIA/EIA-568-C and the addendum for fiber optic testing.
3.4 TESTING OF FIBER OPTICS CABLING A. General: Horizontal and backbone cabling shall be verified in accordance with ANSI/TIA/EIA-568-C and the addendum for fiber optic testing. B. General: In the event
More informationUniversal Connectivity Platform A Modular Approach to Infrastructure Design
A Modular Approach to Infrastructure Design TE Connectivity s Universal Connectivity Platform (UCP) provides a fully modular approach to designing data centers and telecommunications rooms. This patch
More informationDatasheet: OptiFiber Pro OTDR
Datasheet: OptiFiber Pro OTDR Accelerates enterprise fiber troubleshooting and certification. The OptiFiber Pro OTDR is the Tier 2 (extended) fiber certification solution and part of the Versiv Cabling
More informationFiber Tes)ng 101 Essen)als Every Network Analyst Needs to Know. David S(llwell BCNET Oscar Rondon BCNET Gwenn Amice - EXFO
Fiber Tes)ng 101 Essen)als Every Network Analyst Needs to Know David S(llwell BCNET Oscar Rondon BCNET Gwenn Amice - EXFO Workshop format The Workshop is going to start with three short lecture style power
More informationLCS 2 THE CATEGORY 6A GUARANTEE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES
LCS 2 THE CATEGORY 6A GUARANTEE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES Legrand is one of the global leaders in data communication networks in the development and design of
More informationFire Control Panels. Multiple Signal Fiber Optic Modems and Accessories for 4120 Network. UL, ULC, CSFM Listed; FM Approved* Features
Fire Control Panels UL, ULC, CSFM Listed; FM Approved* Features Compatible with Simplex 4120 Network Converts multiple 4120 network communications signals into a single fiber optic link to: Multiplex audio
More informationData sheet OpDAT mini breakout cable 24x1 OM4 - bend insensitive
Page 1/8 Illustrations Principle diagram See enlarged drawings at the end of document Product specification mini-breakout installation cable U-VQ(ZN)H laser-optimized, bend insensitive fiber UV-resistant,
More informationFire Control Panels. Multiple Signal Fiber Optic Modems and Accessories for Panel and Remote Mounting. Features. Operation.
UL, ULC Approved* Fire Control Panels Multiple Signal Fiber Optic Modems and Accessories for Panel and Remote Mounting Features Converts multiple fire alarm communications signals into a single fiber optic
More informationM700-Series OTDRs. or (800) , (603)
Features M700 Compact QUAD OTDR M700 OTDR with DFS1 Digital FiberScope Integrated OPM and VFL (650 nm) Inspection capable with the DFS1 FiberScope Full Auto, Expert, and Real-Time OTDR test modes Automatic
More informationAcceptance Requirements. Fibre Optic Systems. Revised 12/2017. December 5th, Alexander Kölbel
December 5th, 2017 Acceptance Requirements Fibre Optic Systems Revised 12/2017 Alexander Kölbel +49 6190 8880-40 alexander.koelbel@datwyler.com Dätwyler Cables GmbH, Auf der Roos 4-12, 65795 Hattersheim,
More informationOPX-BOX. Platform Highlights. Software Support. Key Features
Ultra Compact, Highly Versatile OTDR with Bluetooth Wireless and USB Control The VeEX is an ultra-compact, OTDR designed to operate remotely using Fiberizer software. The unit can be controlled via USB
More informationM310 Enterprise OTDR. Designed for Enterprise Network Testing, Troubleshooting and Documentation. or (800) , (603)
Designed for Enterprise Network Testing, Troubleshooting and Documentation Features Industry leading TruEvent analysis Short dead zones provide precise testing of closely spaced events Front Panel and
More informationLink loss measurement uncertainties: OTDR vs. light source power meter By EXFO s Systems Engineering and Research Team
Link loss measurement uncertainties: OTDR vs. light source power meter By EXFO s Systems Engineering and Research Team INTRODUCTION The OTDR is a very efficient tool for characterizing the elements on
More informationWhite Paper: Fiber Contamination, Cleaning and Inspection. Introduction.
White Paper: Fiber Contamination, Cleaning and Inspection. Introduction. Despite industry best practice of inspecting and cleaning fiber optic endfaces, contaminated connections remain the number one cause
More informationM700-Series Multifunction OTDR
M700-Series Multifunction OTDR Test, Troubleshoot and Document Single-mode and Multimode Fiber Networks Test Modes Full Auto OTDR Normal (point-to-point) fiber cable construction testing and fault location
More informationOptiFiber Pro OTDR Built for the enterprise
OptiFiber Pro OTDR Built for the enterprise As enterprise networks and datacenter architectures evolve, IT infrastructure administrators demand better OTDR technology to maintain fiber network performance.
More informationSumitomo Fiber Specification SE-6** Non-Zero Dispersion Shifted Single-Mode Fiber. PureGuide SM Optical Fiber, TIA Type IVd. Issued: November 2003
Sumitomo Fiber Specification SE-6** Non-Zero Dispersion Shifted Single-Mode Fiber PureGuide SM Optical Fiber, TIA Type IVd Issued: November 2003 78 Alexander Drive, Research Triangle Park, NC 27709 Phone
More informationSECTION TESTING OF FIBER OPTIC CABLES
SECTION 27 08 23 TESTING OF FIBER OPTIC CABLES PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction,
More informationThe True Value of Connector Inspection: New Challenges and Best Practices
The True Value of Connector Inspection: New Challenges and Best Practices Vincent Racine Product Line Manager August 2011 1 Table of contents 1 Best Practices 2 Connector Inspection Tools 3 Connector Inspection
More informationOptical Return Loss Measurement by Gregory Lietaert, Product Manager
White Paper Optical Return Loss Measurement by Gregory Lietaert, Product Manager Introduction With the increasing frequency of high-speed transmission systems and DWDM deployment, optical return loss (ORL)
More informationM210 Multifunction Micro OTDR
Test, Troubleshoot and Document Single-mode and Multimode Fiber Networks Features 30 db dynamic range single-mode 16-hour battery life Remote display capable Touch and Test intuitive user interface New
More information100% DATASHEET REV.1.0 Data center System. Datasheet. 3RU Slide-Out Fiber Enclosure Unloaded #51615 FHD-3UFRME. Tested.
3RU Slide-Out Fiber Enclosure Unloaded #51615 FHD-3UFRME Fiber Rack Mount Enclosure are available in 1U, 2U, 3U and 4U sizes (FHD-1UFRME, FHD-2UFRME, FHD-3UFRME, FHD-4UFRME) and mount in standard EIA 19"
More informationM310 Enterprise OTDR. Designed for Enterprise Network Testing, Troubleshooting and Documentation. or (800) , (603)
Designed for Enterprise Network Testing, Troubleshooting and Documentation Features Integrated Optical Power Meter and Visual Fault Locator Short dead zones provide testing of closely spaced events Industry
More informationBasic Professional Fiber Optic Installation
Basic Professional Fiber Optic Installation QUICK SUMMARY Length: 32 hours; or 40 hours with Fiber Optic Association CFOT certification Hands-on Activities: 40 activities, 70-75 % Text/Field Reference:
More informationMicrOTDR. Optical Fault Locator. User Manual
Optical Fault Locator Datacom Textron 11001 31 st Place West Everett, WA 98204 TEL: 425-355-0590 Toll Free: 800-468-5557 FAX: 425-290-1600 Internet: www.datacom.textron.com Warranty The MicrOTDR Optical
More informationUniversal Connectivity Platform
Enabling Business Transformation through Agility Availability Efficiency UCP provides a fully modular approach to accommodate both copper and fiber into one common footprint, simplifying network architecture
More informationWilcom. Model FR2 Fiber Ranger Optical Fault Locator OPERATING INSTRUCTIONS
Wilcom Model FR2 Fiber Ranger Optical Fault Locator OPERATING INSTRUCTIONS Model FR2 Operating Instructions 812-655-002 January, 2002 Copyright (c) 1999 Wilcom All Rights reserved Wilcom reserves the right
More informationSumitomo Fiber Specification SE-9** Non-Zero Dispersion Shifted (NZDF) Zero Water Peak Large Effective Area Single Mode Fiber
Sumitomo Fiber Specification SE-9** Non-Zero Dispersion Shifted (NZDF) Zero Water Peak Large Effective Area Single Mode Fiber PureGuide -LA SM Optical Fiber, TIA Type IVd ITU G.655 C and D Compliant Issued:
More informationWhite Paper: Standard-Compliant Certification & Best Practices Ensure Fiber End-face Cleanliness to Eliminate the #1 Cause of Fiber Failure
White Paper: Standard-Compliant Certification & Best Practices Ensure Fiber End-face Cleanliness to Eliminate the #1 Cause of Fiber Failure White Paper: Standard-Compliant Certification & Best Practices
More informationM210 Multifunction Micro OTDR
Test, Troubleshoot and Document Single-mode and Multimode Fiber Networks Features 30 db dynamic range single-mode 16-hour battery life Remote display capable Touch and Test intuitive user interface New
More informationLCS 2 YOUR digital infrastructure
FIBRE OPTIC SOLUTIONS IN BUILDINGS LCS 2 YOUR digital infrastructure THE GLOBAL SPECIALIST in electrical and digital building infrastructures fibre Optic solutions in buildings Legrand presents its new
More informationASSMANN ELECTRONIC GmbH ASSMANN SYSTEM GUARANTEE. DIGITUS Professional Fiber Optic Cabling System. Appendix B - Provisions for acceptance
ASSMANN ELECTRONIC GmbH ASSMANN SYSTEM GUARANTEE DIGITUS Professional Fiber Optic Cabling System Appendix B - Provisions for acceptance Page 1 Table of contents 1. Acceptance test of the installation link
More informationSimplex ES Network. ES Net Network Applications, Communications, Options and Specifications. ES Net features. UL, ULC Listed*
Simplex ES Network UL, ULC Listed* ES Net features ES Network (ES Net) is a high bandwidth (100 Mbps) IP based fire alarm network that supports up to 99 nodes and uses industry standard network technology
More informationSECTION COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING
SECTION 27 13 23 COMMUNICATIONS OPTICAL FIBER PART 1 - GENERAL 1.1 SUMMARY A. Section Includes the following: 1. 50/125-micrometer, optical fiber cabling. 2. Cable connecting hardware, termination panels,
More informationMTTplus Modular Test Platform
MTTplus-410 Fiber Optics Test Module 2017 MTTplus Modular Test Platform The Fiber Optics module for the VeEX MTTplus supports a full range of test functions including OTDR, OPM, Light Source and VFL. Geo
More informationHands-On CAT 5/6 & Fiber Optic Installer
Hands-On BICSI CECs This course has been approved for CEC credits by BICSI. Please read below for a breakdown of the credits that we offer for this course. For more information regarding BICSI please visit
More informationNoyes OFL 250B Specs Provided by
Noyes OFL 250B Specs Provided by www.aaatesters.com OFL 250 Handheld OTDR The Noyes OFL 250 from AFL Telecommunications is a single-mode OTDR with an integrated Optical Power Meter (OPM), Source (OLS),
More informationHands-On Fiber Optic ISP / OSP Combo-Tech Splicing, Termination & Testing
Hands-On Splicing, Termination & Testing BICSI CECs This course has been approved for CEC credits by BICSI. Please read below for a breakdown of the credits that we offer for this course. For more information
More informationFibre Specification Standards
Fibre Specification Standards User Manual The most important thing we build is trust Cobham Wireless - Coverage Table of Contents 1. Single-mode Fibre to ITU-T Recommendation G.652 3 2. SC/APC Mated Pair
More informationWe are leading ISO 9001:2008 certified distributors, traders and importer of telecom, electronics & electrical test and measurement equipments.
+91-8079446606 V Tech Communications http://www.vtech.net.in/ We are leading ISO 9001:2008 certified distributors, traders and importer of telecom, electronics & electrical test and measurement equipments.
More informationOTDR II. Tier-2 Optical Time Domain Reflectometer for Multimode and Single-mode Fiber Cabling
Tier-2 Optical Time Domain Reflectometer for Multimode and Single-mode Fiber Cabling Tier-2 Optical Time Domain Reflectometer for Multimode and Single-mode Fiber Cabling The OTDR II is the first tablet
More informationTRM 2.0 Test Results Manager All-In-One Comprehensive Analysis and Reporting Software
TRM 2.0 Basic Software Features Generate professional acceptance reports including: OTDR traces Certification loss results/opm loss results Connector end-face images from FOCIS and DFS1 Create certification
More informationHands-On Fiber Optics ISP/OSP - Advanced Combo- Tech
Hands-On Fiber Optics ISP/OSP - Advanced Combo- Tech Course Description This Hands-On 3-day course has been customized to provide technicians with a practical understanding of fiber optic theory and fiber
More informationAV6416 OTDR. Product Overview: Main Features:
AV6416 OTDR Product Overview: AV6416 OTDR is a test instrument designed for FTTx. It s mainly used to measure the physical characteristics of optical fiber & cables, including length, transmission loss
More informationA Quick Start Guide to Fiber-to-the-Antenna (FTTA) Installation and Maintenance Testing. Vol. 2 Tier 2 Certification
A Quick Start Guide to Fiber-to-the-Antenna (FTTA) Installation and Maintenance Testing Vol. 2 Tier 2 Certification Notice Copyright Every effort was made to ensure that the information in this document
More informationRefurbished EXFO Instruments
The following list of available refurbished EXFO instruments is only updated daily. Consequently, it may not reflect recent changes in the inventory. Once an order is placed ofr a refurbished unit, the
More informationFiretuf OFC-UT-CST Fire resistant Armoured Central Tube Cable, variant in red
Indoor/Outdoor steel tape armoured (CST) double LSHF-FR sheathed optical cable with 2 24 fibres. VDE: A/I-DQ(ZN)H(SR)H 3rd party verification of the fire tests by BUREAU VERITAS December 2014 OFC-UT-CST
More informationA Quick Start Guide to Fiber-to-theAntenna (FTTA) Installation and Maintenance Testing. Vol. 2 Tier 2 Certification
A Quick Start Guide to Fiber-to-theAntenna (FTTA) Installation and Maintenance Testing Vol. 2 Tier 2 Certification A Quick Start Guide to Fiber-to-the-Antenna enna (FTTA) Installation and Maintenance Testing
More information100% DATASHEET REV.1.0 Data center System. Datasheet. 2 RU Slide-Out Fiber Enclosure Unloaded #51616 FHD-2UFRME. Tested. Description.
2 RU Slide-Out Fiber Enclosure Unloaded #51616 FHD-2UFRME Fiber Rack Mount Enclosure are available in 1U, 2U, 3U and 4U sizes (FHD-1UFRME, FHD-2UFRME, FHD-3UFRME, FHD-4UFRME) and mount in standard EIA
More informationECP OPTICAL FIBRE SPLICING, TESTING AND COMMISSIONING REQUIREMENTS
Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE ECP 11-0009 OPTICAL FIBRE SPLICING, TESTING AND COMMISSIONING REQUIREMENTS EPN, LPN, SPN This standard details the requirements for the splicing,
More informationENCIRCLED FLUX (EF) TEST SOLUTIONS
ENCIRCLED FLUX (EF) TEST SOLUTIONS Tier-1/2 solutions with controlled source launch conditions for maximum accuracy and repeatability designed to remove uncertainty from multimode fiber testing. KEY FEATURES
More informationENCIRCLED FLUX (EF) TEST SOLUTIONS SPSB-EF LAUNCH MODE CONDITIONER AND FLS-600-NS1548 LIGHT SOURCE DESIGNED FOR CONTROLLED MULTIMODE LOSS TESTING
ENCIRCLED FLUX (EF) TEST SOLUTIONS SPSB-EF LAUNCH MODE CONDITIONER AND FLS-600-NS1548 LIGHT SOURCE DESIGNED FOR CONTROLLED MULTIMODE LOSS TESTING Tier-1/2 solutions with controlled source launch conditions
More informationOPTICAL TIME DOMAIN REFELECTOMETER (OTDR): PRINCIPLES
OPTICAL TIME DOMAIN REFELECTOMETER (OTDR): PRINCIPLES Why Test Fiber with an OTDR? Single ended test that......characterizes fiber from end-to-end...locate and measure each event...provides a detailed
More informationOTDR - FHO5000-xxx. Optical Time Domain Reflectometer
OTDR - FHO5000-xxx Optical Time Domain Reflectometer FHO5000 series Optical Time Domain Reflectometer (OTDR) is the latest generation of intelligent instrument for test and detection of fiber optic communication
More informationM210 Multifunction Micro OTDR
Test, Troubleshoot and Document Single-mode and Multimode Fiber Networks Features 30 db dynamic range single-mode 16-hour battery life Remote display capable Touch and Test intuitive user interface New
More informationFastReporter 2 DATA POST-PROCESSING SOFTWARE
DATA POST-PROCESSING SOFTWARE Consolidated data management and post-processing tool designed to increase the reporting productivity for connector endface inspection and all types of optical-layer testing:
More informationSECTION TESTING OF FIBER OPTIC CABLES
PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such construction, all materials and equipment incorporated
More informationOPX-BOXe Rugged, Pocket-sized Mini OTDR
OPX-BOXe Rugged, Pocket-sized Mini OTDR Highly Versatile OTDR with Wireless and USB Control The VeEX OPX-BOXe is an ultra-compact, OTDR designed to operate remotely using Fiberizer software. The unit can
More informationFibre optic media options and trends
Fibre optic media options and trends Presented by D Stockton & P Lascelles of Miniflex Ltd, branded as m2fx 23 February 2012 1 Contents Cable constructs Indoor/outdoor LSZH Armouring Micro Bends Singlemode,
More informationFastReporter 2 DATA POST-PROCESSING SOFTWARE
DATA POST-PROCESSING SOFTWARE Consolidated data management and post-processing tool designed to increase the reporting productivity for connector endface inspection and all types of optical-layer testing:
More informationOPTICAL FIBER SOLUTIONS
RightWave Erbium-Doped Optical Fiber Critical component for the amplification of optical transmission signals A Furukawa Company Broad portfolio suited to diverse needs Proven product uniformity, quality
More informationOPTICAL TIME-DOMAIN REFLECTOMETER
Tallinn University of Technology Laboratory exercise 1 of Fiber Optical Communication course OPTICAL TIME-DOMAIN REFLECTOMETER Tallinn 2016 Aim of the laboratory exercise: The aim of this laboratory exercise
More informationFTTH NETWORK TESTING: REAL APPLICATIONS USING THE OLTS METHOD
FTTH NETWORK TESTING: REAL APPLICATIONS USING THE OLTS METHOD 157 APPLICATION NOTE Mario Simard, Product Manager, Optical Business Unit The purpose of any fiber-optic network is to perform high-speed,
More informationData sheet OpDAT universal cable 1x24 OM4 - bend insensitive
Illustrations Principle diagram Page 1/7 Product specification installation cable U-DQ(ZN)BH universal fiber optic cable for indoors/outdoors with central or stranded loose tube bend insensitive fiber
More informationFIA. The Fibreoptic Industry Association. TECHNICAL SUPPORT GUIDE FIA-TSD
FIA The Fibreoptic Industry Association www.fibreoptic.org.uk TECHNICAL SUPPORT GUIDE FIATSD000 TESTING INSTALLED CABLING USING OPTICAL TIME DOMAIN RELFECTOMETER (OTDR) EQUIPMENT This document has been
More informationDATASHEET REV.1.0 Data center System
1RU Side-out Rack Mount LGX Fiber Enclosure Unloaded #51608 FLG -1UFMX-N An integrated unit for fiber management a protection function. Fiber Rack-Mount Enclosure shall be designed to house, organize and
More informationFiber Optic and CAT 5, 6, 7 and 8 Installer Premise Cabling
Hands-On Fiber Optic and CAT 5, 6, 7 and 8 Installer Premise Cabling Certification Course Description This Hands-On course is customized to give Technicians the confidence and skills to maintain Fiber
More informationFlexibility, scalability andsecurity
THE OF INFORMATION TECHNOLOGY SYSTEMS An Official Publication of BICSI January/February 2014 l Volume 35, Number 1 data center Flexibility, scalability andsecurity plus + The Next Five Years in AV + Measuring
More informationSERIES G: TRANSMISSION SYSTEMS AND MEDIA, DIGITAL SYSTEMS AND NETWORKS Transmission media and optical systems characteristics Optical fibre cables
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU G.650.3 (03/2008) SERIES G: TRANSMISSION SYSTEMS AND MEDIA, DIGITAL SYSTEMS AND NETWORKS Transmission media and
More informationFiber Optics for Todays Industry Applications
Hands-On Fiber Optics for Todays Industry Applications (A Non-Telephone Company Course) Course Description This Hands-On course is designed to provide technicians with a practical understanding and Hands-On
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 61280-4-1 Edition 2.0 2009-06 Fibre-optic communication subsystem test procedures Part 4-1: Installed cable plant Multimode attenuation measurement IEC 61280-4-1:2009(E) THIS
More informationLuna Technologies Webinar Series. New Rayleigh-Based Technique for Very High Resolution Distributed Temperature and Strain Sensing
Luna Technologies Webinar Series New Rayleigh-Based Technique for Very High Resolution Distributed Temperature and Strain Sensing Dr. Dawn Gifford Senior Optical Engineer Mr. Ed Valigursky VP of Sales
More information