JBM-100-LBTV2 Power Connection, Powered Splice, Dual Power Connection, or Splice with Junction Box

Similar documents
C A Heating Cable Gland Kit

JB-RTD-STAND RTD PIPE STAND FOR COMBINATION POWER CONNECTION BOX AND ELECTRONIC CONTROLLER INSTALLATION INSTRUCTIONS

RayClic Connection System

FTC-HST WARNING: CAUTION:

HWT-P HWAT POWER CONNECTION KIT WITH END SEAL INSTALLATION INSTRUCTIONS

1SC-SSC Splice Connection Kit Installation Instructions

JBS-100-ECP-A COMBINATION POWER CONNECTION BOX AND DIGITAL ELECTRONIC CONTROLLER INSTALLATION INSTRUCTIONS

C Electrical Connection Kit

JBS-100-EC Electronic controller replacement kit for JBS-100-ECP-A and JBS-100-ECW-A Installation Instructions

HS-TSPLICE - HEATSHRINK TEE / SPLICE. Installation Instructions

H908 WinterGard Plug-in Power Connection Kit with End Seal

Gardian W51. Approvals

Raychem Heating System

HEATING CABLE RATINGS APPROVALS* Drexan Energy Systems, Inc. Kelowna, BC, Canada, V4V 1S5

XAGA 550/550-L. Aerial Splice Closure. 1. General Description. 2. Warnings. 3. Cautions

QuickStat-TC Installation & Operation Manual

Consignes d installation

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

NELSON HEAT TRACING SYSTEMS

Data Sheet. Self regulating heating tapes. RS stock numbers

NELSON HEAT TRACING SYSTEMS

Data Sheet. Self regulating process heating tapes RS stock numbers ,

NELSON HEAT TRACING SYSTEMS

Small Box for Cable Termination. 3.1 Preparation of box 3.3 Mounting of the box on the wall

NELSON HEAT TRACING SYSTEMS

SERGE BARIL GTKB GUT TRACE KIT BAG

Commercial and Residential Self-Regulating Heating Products

NELSON HEAT TRACING SYSTEMS

NELSON HEAT TRACING SYSTEMS INSTALLATION

Side Entry Bushing (SEB) High Temperature Cable Clamp Bushing Installation Instructions

SEALING FIBER SEALING COMPOUND

DESTU. Direct Entry Sealed Termination Unit. Installation Instructions. Suitable for use in either safe or hazardous areas.

NELSON HEAT TRACING SYSTEMS ALT-BC STANDARD POWER CONNECTION KIT

Tyco Thermal Controls provides complete heat tracing and speciality. wiring solutions for the industrial, commercial, and residential markets.

SERGE BARIL HEAT TRACING SYSTEMS

XL-Trace System Installation and Operation Manual

C910 Series. Single-point heat-tracing control system

NELSON HEAT TRACING SYSTEMS

HVS S 15kV Class

FOSC. Fiber Optic System Technology. Fiber Optic Splice Closures (FOSC-400)

NELSON HEAT TRACING SYSTEMS

Retro-DWS Other Methods Internal Heating Cable System for Sewer Pipe and Waste Drain Applications

NELSON HEAT TRACING SYSTEMS

FIST-EDSA-D4. 3 Feeder cable/ducts (max 16 mm) 4 Drop cable (DB cable or guiding tubes 5-8 mm) 5 Adding drop cable. 6 Gel part replacement

Installation Procedure for D-200 series Shielded Cable Splice Kits with MiniSeal Crimp Primary Splices

XL-Trace System Application and Design Guide

Frost Heave Protection System Installation and Operation Manual

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels

HVS S Splice Series

TECK-40 Series 1000V Class Splice for 4/C Armored Teck Power Cables

XL-Trace System. Installation and Operation manual for pipe freeze protection and flow maintenance

FIRE SPRINKLER SYSTEM FREEZE PROTECTION XL-TRACE SYSTEM

TraceTek TT1000 Modular Sensing Cable

MAYFIELD CEILING FAN LISTED E ITEM # MODEL #BTH44ABZC5C BTH44BNK5C Español p. 20 ATTACH YOUR RECEIPT HERE.

Pipe Freeze Protection. Flow Maintenance. Introduction. XL-Trace System

The DEF-System by BRUGG. The Best Way to defeat the problem of DEF heat Installation Instructions

TT3000 and TT5000 Series

ACCS-30. Multipoint commercial heat-tracing control system

Seal Kits for BUDI Enclosures

Toll Free:

KE-Series Constant-Wattage Heating Cable

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Toll Free:

TILGHMAN CEILING FAN. LISTED For Damp Location E ITEM # MODEL #WCK52LMW5N WCK52NWZ5N. Español p. 20 ATTACH YOUR RECEIPT HERE

QAA 142 Termination instructions Self-regulating trace heaters type ELSR-NA and -HA in Div1 with heater entry kit EL-HAZELECT Kit part No: 09CA051

ST. KITTS CEILING FAN

ARMITAGE CEILING FAN ITEM # MODEL #CC52WW5L. Español p. 17 ATTACH YOUR RECEIPT HERE. Purchase Date

Eldex Column Heater. Operator s Manual

Manual No: Revision: D. Sump Sensor. Installation Guide

Industrial Strength Leak Detection

Ribbon Breakout Kit Installation Instructions

harborbreezeoutlet.com

TT5000-HS (for fuel leaks) TT5001-HS (for solvent leaks) TraceTek Sensing Cable for Underground Leak Detection

Lifetime Limited Warranty

Electric Space Heater

Air Conditioner. user installation & manual manual. imagine the possibilities

Surge Protective Devices Installation, Operation and Maintenance Manual. LowProfile Series: 080 and 120

HWAT -ECO. Installation and Operation Manual. Electronic controller for hot water temperature maintenance systems

AMERICA AMERICA 52 CEILING FAN INSTALLATION AND OPERATION MANUAL

ITEM # BUILDER S SERIES CEILING FAN MODEL #41391

HOT WATER TEMPERATURE MAINTENANCE HWAT SYSTEM

BAY BRIDGE CEILING FAN

ITEM # , CARATUK RIVER CEILING FAN MODEL #40046, 40303

Fuel Leak Detection Find Leaks Before They Find You

Protocol Station Remote Alarm

RF one-step BNC/TNC connectors for coaxial cable termination

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

KIT NOTICE. These instructions are for replacing the three existing thermostats with a single new solid-state thermostat.

PLSRR Heat Trace Cable Data Sheet

ITEM # SAIL STREAM CEILING FAN MODEL #40048

JOHN DEERE GATOR HPX/XUV 2 PASSENGER HEATER INSTALLATION INSTRUCTIONS (p/n: 9PH20S30)

NISSAN FRONTIER INSTALLATION INSTRUCTIONS

ITEM # SAIL STREAM CEILING FAN MODEL #41695

CSI Master Format 2004 Guide Specification for: Flow Maintenance of Aboveground Fuel Oil Lines

ITEM # , , PAWTUCKET CEILING FAN MODEL #40958, 40959, 40047

EN RaychemRIM2StandardInstallationManual IM H /16 1

Lynwood 52 in Ceiling Fan Owner s Manual. Lynwood Ventilador de Techo de 1,32 m Manual del Propietario

OCH-SS series Direct Wired Units Indoor * and Outdoor Comfort Heaters

Installation Instructions

BUDI-M-SP. Building distributor. Introduction. Seals. Kit content. Accessories. Wrap around cable seals

Transcription:

JBM-100-LBTV2 Power Connection, Powered Splice, Dual Power Connection, or Splice with Junction Box Installation Instructions Description The JBM-100-LBTV2 is a Type 4X-rated connection kit. It is designed for use with Raychem LBTV2-CT and SLBTV2 CT self-regulating heating cables. The kit can be used to connect one or two heating cables to power, connect two separate heat-trace circuits, or to splice two heating cables. This kit may be installed at temperatures as low as 40 F ( 40 C). Store above freezing until just before installation. For technical support, contact Tyco Thermal Controls at (800) 545-6258. Tools Required Heat gun or mini-torch Wire cutters 1/4 in. slotted screwdriver Utility knife Large slotted screwdriver Needle nose pliers Adjustable pliers 3/8 in. hex key (required for splice connections) Approvals CLI, ZN1, AEx e II T6 Ex e II T6 Hazardous Locations -ws Class I, Div. 2, Groups A, B, C, D Class II, Div. 1 and 2, Groups E, F, G Class III Additional Materials Pipe straps (two required) GT 66 or GS 54 glass cloth tape Optional Materials Recommended conduit drain: JB-DRAIN-PLUG-3/4IN P/N 278621 000 Kit Contents Item Qty Description A 1 Stand assembly B 1 Lid C 1 Box with terminals (max: 1 in. conduit & 6 AWG wire) D 1 Grommet plug E 2 Clear yellow heat-shrinkable tubes F 4 Black heat-shrinkable tubes G 2 Green/yellow heat-shrinkable tubes H 1 Spanner I 1 Box plug, o-ring, and locknut J 1 Cable lubricant A B C D E F G H I J WARNING: This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire. Read these important warnings and carefully follow all of the installation instructions. To minimize the danger of fire from sustained electrical arcing if the heat ing cable is damaged or improperly installed, and to comply with the requirements of Tyco Thermal Controls, agency certifications, and national electrical codes, ground-fault equipment protection must be used. Arcing may not be stopped by conven tion al circuit breakers. The power connection may be powered by more than one circuit. Be sure all power sources are de-energized before opening box. Component approvals and performance are based on the use of Tyco Thermal Controls-specified parts only. Do not use substitute parts or vinyl electrical tape. The black heating cable core is conductive and can short. It must be properly insulated and kept dry. Damaged bus wires can overheat or short. Do not break bus wire strands when scoring the jacket or core. Keep components and heating cable ends dry before and during installation. Use only fire-resistant insulation materials, such as fiberglass wrap or flame-retardant foam. Heat-damaged components can short. Use a heat gun or a torch with a soft, yellow, low-heat flame. Keep the flame moving to avoid overheating, blistering, or charring the heat-shrinkable tubes. Avoid heating other components. Replace any damaged parts. CAUTION: Health Hazard: Overheating heat-shrinkable tubes will produce fumes that may cause irritation. Use adequate ventilation and avoid charring or burning. Consult MSDS RAY3122 for further information. CHEMTREC 24-hour emergency telephone: (800) 424-9300. Non-emergency health and safety information: (800) 545-6258.

2 1 This product is for use only with LBTV2-CT and SLBTV2 CT heating cables. 60 cm (24 in) Allow approximately 60 cm (24 in) of heating cable for installation. Cut off heating cable end at a 45 angle. Braid Inner jacket Conductive core Bus wire Outer jacket Centerline of connection 2 Lubricate end of outer jacket. Do not remove box nut from stand. Immediately push heating cable through stand and nut as shown. Square off cable end with 90 angle cut. Repeat for a second heating cable. Do not attach stand to pipe until step 11. Box nut 30 to 45 cm (12 to 18 in) 25 mm (1 in) Do not lubricate end of heating cable 3 Lightly score outer jacket around and down as shown. Bend heating cable to break jacket at score, then peel off jacket. 4 Push braid back to create a pucker. At pucker use a screwdriver to open braid. Do not cut braid. 190 mm (7 1/2 in) Bend heating cable and work it through opening in braid. Pull braid tight to make pigtail.

3 5 6 Lightly score inner jacket around and down as shown. Bend heating cable to break jacket at score, then peel off jacket. 165 mm (6 1/2 in) Notch core. Peel bus wire from core. 6 mm (1/4 in) 7 Score core between bus wires at inner jacket. Bend and snap core. Peel core from bus wire. Remove any remaining core material. 8 Slide on heat-shrinkable tubes. Black Green/ yellow Use heat gun or minitorch with soft yellow flame to gently heat tubes until they shrink. 9 Center clear yellow tube over end of inner jacket. Heat tube until it shrinks and adhesive flows out ends. While still hot, pinch between bus wires and hold for 5 seconds to create a seal. Repeat steps 3 through 9 for a second heating cable. 13 mm (1/2 in) Clear yellow

4 10 Pull heating cable back into stand as shown. Use cable lubricant if needed. 11 Fasten stand to pipe. Do not pinch heating cables. Loop and tape extra heating cable to pipe. 13 mm (1/2 in) 12 Remove box nut. Install grommet plugs in unused openings. 13 Place junction box onto stand. Align key ways in large box hole with alignment feature on stand. Put box nut back onto stand. Tighten box nut using spanner. O-ring 14 Trim bus wires and braid. 16 mm (5/8 in) 16 mm (5/8 in)

5 15 This kit uses spring clamp style terminals to provide improved vibration resistance, reduced maintenance and faster installation. To connect wires, firmly insert a slotted screwdriver into the square hole (1) to open the spring. When fully inserted, the screwdriver will lock into place, allowing you to remove your hand and insert the wire into the round hole (2). Remove the screwdriver to clamp the wire. The wire is held securely against the bus bar for low contact resistance over time without the need to periodically retighten screws. 1 2 Wire Wire hole Screwdriver slot Refer to wiring diagram, step 17a or 17b. Push screwdriver FIRMLY into square hole. Insert wire into round hole. Use green terminal for braid and grounding wires. Remove screwdriver. Repeat for a second heating cable.

6 16a Splice Wiring L1 L2 or N 16b Power Connection Wiring Power connection for one heating cable. L1 Power connection for two heating cables. L1 Power connection for two heating cable circuits WARNING: Shock or fire hazard. When the power connection is energized by two circuits, the L1 and L2 jumpers must be removed to prevent an electrical short. L1 L2 or N Power supply L2 or N Power supply L2 or N Circuit 1 Circuit 2 Power supply Circuit 1 Circuit 2 Remove jumper Remove jumper

7 17a If used as a power connection. Install conduit and fittings as shown. To minimize loosening due to vibration, use flexible conduit. Pull in power and ground wires, strip off insulation, and terminate. Power and ground wires 16 mm (5/8 in) 1 in. lock nut Watertight conduit seal Make sure conductors are not exposed. Conduit drain Tyco Thermal Controls recommends the use of a conduit drain to prevent water condensation build-up. 17b If used as a splice connection. Install box plug. 1in. lock nut O-ring Box plug 18 Install lid. Apply insulation and cladding. Weather-seal the stand entry. Leave these instructions with the end user for future reference. Weather seal

8 Worldwide Headquarters Tyco Thermal Controls 7433 Harwin Drive Houston, TX 77036 USA Tel: 800-545-6258 Tel: 650-216-1526 Fax: 800-527-5703 Fax: 650-474-7711 info@tycothermal.com www.tycothermal.com Tyco is a registered and/or unregistered trademark of Tyco Thermal Controls LLC or its affiliates. Important: All information, including illustrations, is believed to be reliable. Users, however, should independently evaluate the suitability of each product for their particular application. Tyco Thermal Controls makes no warranties as to the accuracy or completeness of the information, and disclaims any liability regarding its use. Tyco Thermal Controls only obligations are those in the Tyco Thermal Controls Standard Terms and Conditions of Sale for this product, and in no case will Tyco Thermal Controls or its distributors be liable for any incidental, indirect, or consequential damages arising from the sale, resale, use, or misuse of the product. Specifications are subject to change without notice. In addition, Tyco Thermal Controls reserves the right to make changes without notification to Buyer to processing or materials that do not affect compliance with any applicable specification. 2012 Tyco Thermal Controls LLC PN 765343-000 H56527 11/12