INDOOR INFRASCAN. Passive Infrared Motion Sensors 751 SERIES INSTALLATION MANUAL. Please leave these instructions at the installation site

Similar documents
Indoor Infrascan Passive Infrared Motion Sensor. Series. Installation Instructions. Please leave these instructions at the installation site.

Push Button Electronic Timer. 31VETR Series. Installation Instructions

Push Button Electronic Timer. 31VETR3 Series. Installation Instructions

Infrascan Passive Infrared Motion Sensor Surface-Mount 753SSR Series. Installation Instructions

C-Bus PIR Occupancy Sensor. Installation Instructions 5751L

Trailing Edge Dimmer. 32E450T Series. Installation Instructions REGISTERED DESIGN REGISTERED PATENT

Universal Dimmer. 31E2RUD Series ROTARY CONTROL. Installation Instructions. Integrally Switched Rotary Controlled INTEGRALLY SWITCHED 240V

TrailingE dge Dimmer. 32E450T Series. Installation Instructions REGISTERED DESIGN REGISTERED PATENT

WAFER Recessed Edgelite Exit LED EXITREC. Installation Instructions REGISTERED DESIGN REGISTERED PATENT

Passive Infrared Motion Detector 5420/90P. Installation Instructions

Ceiling-Mounted Motion Detector. 752/CD, 752/CP, 752/CU and 752/Cx180. Installation Instructions

Dimmer / Fan Controller Installation Instructions

QUICKSMART Universal Exit Light EXITSM. Installation Instructions REGISTERED DESIGN REGISTERED PATENT

Universal Dimmer. 31E2RUD Series ROTARY CONTROL. Installation Instructions. Integrally Switched Rotary Controlled INTEGRALLY SWITCHED 240V

Universal Dimmer E450UD Series. Installation Instructions

C-Bus Black & White MK II Desktop Touchscreen. 5000CTD2 Series. User s Guide REGISTERED DESIGN REGISTERED PATENT

60W Security Spotlight. 754HB1/180/ Outdoor Motion Sensor. Installation Instructions. Please leave these instructions at the installation site.

C-Bus Bus Coupler with Scenes 5102BCLEDL 5104BCL

Line Isolation & Overload Monitor. E05 Series. Installation Instructions MU TE TE S T E. S.P. ALARM MUT E D OVE R LOAD WAR NING PHC WARNING

Light Level Detector, Surface Mount 5754PE. Installation Instructions

Motion sensors for every application

Mains Power Filter 970MF10 970MF20. Installation Instructions

C-Bus Pascal Automation Controller 5500PACA. Installation Instructions

C-Bus Black & White MK II Touch Screen. 5000CT2 Series. User s Guide

F Type Shielded Masthead Amplifier 3105MH35U18V DIGITAL TERRESTRIAL TELEVISION READY. Installation Instructions

Compact Movement Activated Sensor Installation Instructions

Ceiling Mounted Ducted Exhaust Fan Kit

Universal Clamp Meter

Clipsal is a registered trademark of Clipsal Australia Pty Ltd. Saturn is a trademark of Clipsal Australia Pty Ltd.

754 Series. See Motion Sensors. in a new light. Sleek new styling and more features than ever before.

360º Surface Mount Ceiling PIR Light Controller

2000W PIR LIGHT CONTROLLER SLB2000-Black SLW2000-White INSTALLATION & OPERATING INSTRUCTIONS

Iconic Series ControlLink Pushbutton 41EPBM-VW PDL356PBSS-VW. Installation Instructions REGISTERED DESIGN

DETECTOR TRANSMITTER INSTALLATION & OPERATING. Cat No. TLTX2000B INSTRUCTIONS

360 Surface Mount Ceiling PIR Light Controller

For assistance with the product please contact: HELPLINE. For a product brochure please contact:

12W Round LED Wall/Ceiling Light with Microwave Sensor

Surface Mount Wall PIR Light Controller. Model: PDWM1500. Installation & Operating Instructions

60W Multi PIR Bulkhead

PIR/INT & PIR/INT-D. Batten mount PIR detectors. Product Guide. Overview. Features

"Options" Sensor Module

, ,

360º FLUSH MOUNT CEILING PIR LIGHT CONTROLLER INSTALLATION & OPERATING. Cat No. SLFM360 INSTRUCTIONS

Model: MLSA360N. Installation & Operating Instructions. 360º Night Eye PIR Light Controller

360 Ceiling PIR Light Controller

Intercom Systems Video Intercoms

EBMPIR-MB. Batten mount PIR detectors. Product Guide. Overview. Features

5W LED Energy Saver PIR Bulkhead

For assistance with the product please contact: HELPLINE. For a product brochure please contact:

User Manual 120/240/300 Outdoor Motion Detector

18W Round LED Wall/Ceiling Light with Microwave Sensor

FR-A180 FR-A360. Occupancy detector. Use

Integrated PIR detectors

. w. POWERHOUSE n MOTION DETECTOR MODEL PR511 OWNER S MANUAL

PRODUCT DATA AND INSTALLATION SHEET MWS5-SA STAND ALONE MINIATURE CEILING MOUNTED MICROWAVE PRESENCE DETECTOR

High bay PIR presence detector DALI / DSI dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

High bay PIR presence detector 1-10V dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

Three Speed Capacitive Fan Controller. 4060CSFM Series. Installation Instructions 75VA

DON T WAIT UNTIL IT S TOO LATE! Discover the seven steps to a safe and secure home.

SECURITY LIGHT MODEL NO: CL6PIR OPERATION INSTRUCTIONS PART NO: GC0215

Ceiling PIR HS presence detector 1-10V, low temperature. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. IR Receiver

Lantern Receiver E-997 INSTALLER GUIDE. SF-LA-BC-RX-W.qxd 13/04/ :36 Page 1

MWS5. Miniature Microwave Presence Detector (standalone) Product Guide. Overview. Features

PMCSF6 OCCUPANCY SENSOR

EBDSPIR-PRM-VFC & EBDSPIR-PRM-VFC-NC

Model: PDSM1500. Installation & Operating Instructions 360º Surface Mount Ceiling PIR Light Controller

Ceiling PIR HS presence detector. Product Guide. Overview. Features

Pedestal Fan. 12 months. 3 Speed, 40cm R2000B

MST-1. Varifan USER S MANUAL MST-1 ADJUST. 9 per day HI F2. DIFF on off TIMER. reduc.

Motion tracking. sensor led light. Installation & operating manual NIGHTWATCHER. Model no: nw1200x

VITMR-EBDSPIR-PRM. PIR Presence/Absence Detector IR with Ceiling Rose. Product Guide. Overview. Features

SWITCHLITE MRE SLD MAN SWITCHLITE MRE SLD IP55

Ceiling PIR presence detector DALI / DSI dimming. PIR Sensor. IR Receiver. Light Level Sensor. Status LEDs. PIR Sensor.

High Frequency Sensor

PPAD-C-230V. Ceiling PIR presence/absence detector. Product Guide. Overview. Features

30W LED PIR FLOODLIGHT. Model: LEDX30PIRB Model: LEDX30PIRWH

DS9370-BEL. Installation Instructions TriTech Ceiling Mount PIR/Microwave Intrusion Detector

EBDSPIR-PRM-2CH, EBDSPIR-PRM-2CH-NC

1 Safety instructions. 2 Device components. Observer 220. Art.-No.: W 220 WW. Operationsmanual

Detailed operating instructions

Model: PDFM1500. Installation & Operating Instructions 360º Flush Mount Ceiling PIR Light Controller

Product Guide. Ceiling microwave presence detector DALI / DSI. Microwave Sensor. IR Receiver. Light Level Sensor. Status LEDs.

Installation Manual. Features SMART SWITCH OCCUPANCY SENSOR. Maximum Versatility. Maximum Energy Savings

Airflow. Add a little Sunshine to your bathroom

Detailed operating instructions

1.7L KETTLE INSTRUCTION MANUAL 220~240V 2200W

EBMHS (standard & slim-line PSU)

1. Basic safety information 3 2. Proper use 3

Electronically controlled instantaneous water heater. MCX: 27300, and models. Installation instructions

Wall Fan. 3 Speed, 40cm MWF40

Centrif Duo & Centrif Duo Plus

Schneider Electric occupancy sensor range. Lighting the way to simple energy saving solutions

TOCR02 2 PART MICRO MOTION SENSOR W/IR REMOTE CONTROLLER

D-TECT Introduction. Connecting the Unit. Quick Installation. Multi Beam Alignment & Masking. Mounting the Unit

ILVAN AUSTRALIA PTY. LTD.

PräsenzLight PräsenzLight PräsenzLight A.. PräsenzLight A..

ECO-IR 360C NT. Presence detector. Art. Nr Bedienungsanleitung 2. Notice d utilisation 22. Installation manual 42

EBDSPIR-PRM-LV Product Guide

Ceiling Microwave presence detector - DALI / DSI 12-24V AC/DC. Microwave Sensor. IR Receiver. Light Level Sensor. Status LEDs.

CPS-1 USER S MANUAL AIR INLET / CURTAIN CONTROL

Transcription:

INDOOR INFRASCAN Passive Infrared Motion Sensors 751 SERIES INSTALLATION MANUAL Please leave these instructions at the installation site

Contents Section...Page 1 Product Range...3 2 Description...3 3 Product Selection...3 4 How It Works...4 5 Identification Of Parts...5 6 Installation Location...6 7 Field Of View...6 8 Mounting Procedure...7 9 Wiring Diagrams 751 2 Wire Infrascan...8 10 Wiring Diagrams 751R 3 Wire Infrascan...9 11 Commissioning...10 11.1 Set Up For Walk Test...10 11.2 Adjustment Of Time-On and Light-Level...10 12 Troubleshooting...11 13 Technical Specifications...12 14 Warning: Using The 751 With Special s...14 15 Warranty...16 16 Technical Support and Troubleshooting...16 Copyright 2006 Clipsal Australia Pty Ltd Page 2

1 Product Range 751 Infrascan Indoor, 240V a.c., 50Hz, 2-Wire, 2A, 20 Minute 751R Infrascan Indoor, 240V a.c., 50Hz, 3-Wire, 10A, 20 Minute 2 Description Packed with features that have made Clipsal the leader in Passive Infrared (PIR) motion sensor technology, the new 751 Series Indoor Infrascan is the next generation of the constantly evolving family of Clipsal PIR sensing devices. The compact, unobtrusive appearance of the unit, combined with simplified installation and a range of new features, make it the smart light switch for the modern era. The unit is designed to monitor the immediate environment, and detect people moving within its Field of View. When movement is detected, the unit will activate an electrical load, such as a light, in response to that movement. Designed and developed in Australia, the unit offers benefits in security, energy management, hospitality and true hands-free switching convenience in a wide range of domestic and commercial applications. 3 Product Selection Be sure to select the appropriate Infrascan product to suit your application: The 751 is a 2 wire (does not require neutral connection), but can only switch a limited range of load types. The 751R is a 3 wire device (requires neutral connection to operate) capable of switching a wide range of load types. Catalogue Number Neutral Required Maximum * 751 NO 2A 751R YES 10A * Please refer to Technical Specifications for further information about compatible load types. Copyright 2006 Clipsal Australia Pty Ltd Page 3

4 How It Works With power applied and a suitable load connected, the Infrascan will be able to detect any moving Infrared source (for example a person) that may intrude upon its Field of View. The operation of the Infrascan may be set by the user. The unit has two adjustments on the underside of the sensor head for Light-Level and Time-On duration. The Light-Level adjustment activates the load dependent on the ambient light level in the Field of View of the sensor. This adjustment can be set to allow the Infrascan to operate the load at any light level between full daylight and almost complete darkness. For example, the user can ensure the load is only activated when movement is detected at night time. During the day time, when there is adequate natural light, the unit can be set such that it does not activate the load, as it is not necessary to do so. The Time-On adjustment varies the time span that the load will remain on for after the Infrared source moves out of or stops moving within the Field of View. The load will automatically be switched off after the Time-On period has elapsed. Any period between 5 seconds and approximately 20 minutes may be set by the time adjustment screw. Rotate to aim 120 o Figure 1 Copyright 2006 Clipsal Australia Pty Ltd Page 4

5 Identification Of Parts 84mm mounting centres suit 154, 155, etc. Standard Pattern mounting accessories Mounting flange ter mi nals Line and load wires to sensor head 50mm mounting centres (suits 240 Series, etc. round junction boxes). (Neutral terminal on 751R) Spare looping terminals Sensor head Viewing window Time-on adjustment Diagram shown in normal ceiling mount position. Centre mounting screw recess Figure 2 Light level sensor adjustment Note: The sensor head is specially designed to give optimum performance. Under no circumstances should it be tampered with. There are no user serviceable parts inside. Do not apply any pressure on the actual sensor lens itself, as this may damage the lens, and adversely affect the performance of the unit. Copyright 2006 Clipsal Australia Pty Ltd Page 5

6 Installation Location An Infrascan must be positioned correctly to ensure effective operation. The Field of View is optimum when the sensor head is mounted in a vertical position at a height of 2.4 metres and the approach path is across the face of the sensor. Note: Do not mount the Infrascan close to objects which can create rapid temperature changes eg. air conditioning vents, heater flues, moving water ie. fountains and sprinklers. Avoid locations where condensation is likely to form on the lens. Do not mount the Infrascan on any surface that is subject to movement due to wind or other causes. In all cases, locate the Infrascan so that the approach path is across the Field of View and not directly towards the Infrascan. 7 Field of view Ceiling Suitable for: 90 o 8.5m approx. Ceiling Mounting Scanned Area FLOOR Vertical Plane 90 o Viewing Angle Scanned Area Horizontal Plane Detection area 6 x 6 metres Note: The absolute range of all PIR Detectors is subject to variation because of daily differences in the background temperature characteristics and type or amount of clothing worn. Rapid and large changes in temperature may be detected even if they appear to be well beyond the stated range. Wall Mounting Copyright 2006 Clipsal Australia Pty Ltd Page 6

8 Mounting Procedure Step 1: Fit the Mounting Base in the required location. The unit is suitable for either: a) Ceiling Mount b) Wall Mount Orient the Base such that the small arrow indicating the Field of View is pointing toward the required detection area. Step 2: Terminate incoming wiring on the appropriate terminals as marked. Refer to Section 9, Wiring Diagrams for further information about wiring for different applications. Step 1 Install the Mounting Base Line and wires to Sensor Head Neutral wire to Sensor Head (751R only) Step 2 Terminate Wiring Step 3: Fit the Sensor Head to the Mounting Base via the single, centrally located mounting screw (between the Time-On and Light-Level adjustment screws). Rotate to aim 120 o Note: If leads from the Sensor Head are disconnected from the Terminal Block: 751 Reconnect either lead to the Line terminal and the remaining lead in the terminal. 751R Connect brown to Line, white to and blue to Neutral terminal. Do not fully tighten the screw until the sensor head has been aimed at the area you wish to monitor. The sensor allows up to 120 degrees rotational movement to allow it to be aimed in the required direction. Step 3 Fitting the Sensor Head to the Mounting Base Copyright 2006 Clipsal Australia Pty Ltd Page 7

9 Wiring Diagrams 751 2 Wire Infrascan 1a) Automatic Operation 10A Fuse or MCB Active/Line Red/Brown 751 Black/White A N 1b) Automatic with manual override ON or OFF Active/Line Red/Brown 751 On Auto Black/White 2x30M or 30MAM Off Auto 10A Fuse or MCB A N 1c) ON, OFF or AUTOMATIC Operation using a 3 position switch Active/Line Red/Brown Auto 751 Off On Black/White 39MAOM 10A Fuse or MCB A N Note: When switching to AUTO for any of the above configurations the Infrascan will turn on. Allow 30 seconds plus Time-On period for the sensor to stabilise for normal operation. Wiring diagram 1(a), without override switches is preferred as there is no settling period. More than one 751 CANNOT be connected in parallel to a common load. If parallel connection of multiple devices to control a common load is required, use Cat. No. 751R. Copyright 2006 Clipsal Australia Pty Ltd Page 8

10 Wiring Diagrams 751R 3 Wire Infrascan 2a) Automatic Operation Active Red/Brown 751R White Neutral Black/Blue 10A Fuse or MCB A N 2b) Automatic with manual override ON or OFF Active Red/Brown 751R On Auto Off White Neutral Auto Black/Blue 2x30M or 30MAM 10A Fuse or MCB A N 2c) ON, OFF or AUTOMATIC Operation using a 3 position switch Active Red/Brown On Off 751R White Auto Neutral Black/Blue 39MAOM 10A Fuse or MCB A N Warning: It is illegal for persons other than licensed electricians or persons authorised by legislation to work on fi xed wiring of any electrical installation. Penalties for conviction are severe. Installation must be carried out in accordance with local wiring rules (AS/NZS3000 Australia and New Zealand). Copyright 2006 Clipsal Australia Pty Ltd Page 9

11 Commissioning When setting the Time-On or Light-Level adjustments keep clear of the Field of View when assessing the effect of the adjustment. 11.1 Set Up For Walk Test Connect unit to mains power and allow at least 30 seconds for the unit to stabilize before 1 conducting any tests. 2 Set the Time-On adjustment fully anti-clockwise (5 second timer set). Set the Light-Level sensor adjustment fully anti-clockwise (unit set to respond in light or 3 dark conditions). Loosen the centre mounting screw slightly, and aim the sensor head towards the desired 4 Field of View. Tighten the centre mounting screw. Walk slowly around the area in the desired Field of View to confi rm the load is activated from within the desired area. 5 Check that the unit responds appropriately when entering the room. Check that the unit does not trigger unnecessarily when walking past open entry ways (eg adjoining hallway or corridor). If necessary, re-aim the sensor head. 6 Set the Light-Level as desired for activation at dusk for normal operation. 7 Set the Time-On interval to the desired time for normal operation. 11.2 Adjustment Of Time-On and Light-Level Settings Adjustment Range: 5 seconds to 20 minutes. Rotate clockwise to set required time-out period. 5sec Daylight Step 2 Step 3 20min Darkness a b c Minimum setting (5 seconds). Set for areas with constant occupation but infrequent movement. Set for areas with less occupation but constant movement. a b c Light-Level Adjustment Adjustment Range: 1 Lux to Full Sunlight. Rotate clockwise to avoid having load activated when natural light is adequate. a b c To activate the load at dusk, set adjustment to this area. activated at night only. activated both day and night. a b c Copyright 2006 Clipsal Australia Pty Ltd Page 10

12 Troubleshooting Problem Possible Cause Possible Action Light turns on for no apparent reason. Light turns on during daylight. Lights do not turn on in dim and dark conditions. Light remains permanently on. Momentary power failure. Unseen target. Extreme draughts of hot and cold air. Trees / bushes moving in the wind. Vehicular or pedestrian traffic on edge of Field of View. Wrong setting on Light Adjustment. Wrong setting on Light Adjustment. Light globe blown. Manual override switch fitted and set to Manual. Moving infrared source being detected. Note: Do not mount to close objects which can change temperature rapidly eg air Conditioner vents, heater flues, moving water ie fountains, sprinklers. None, unit will reset after Time-Out. Check for animals eg dogs/cats etc. Check doors, windows or air conditioning outlets. Re-aim sensor head. Re-aim sensor head. Reset according to Commissioning Instructions. Reset according to Commissioning Instructions. Replace light globe. Reset according to Commissioning Instructions. Remove unwanted infrared source. If unable to resolve, blank off viewing window. Light should turn off after Time-Out. If light still remains on, call installer. Note: Take care not to scratch or damage the translucent window on the front of the Infrascan as it forms part of the optical detection system. For continued optimum performance ensure that the window is cleaned periodically with mild soap, water and a soft cloth. Copyright 2006 Clipsal Australia Pty Ltd Page 11

13 Technical Specifications Catalogue Number 751 751R Operating Voltage 200 265V 50Hz a.c. Maximum Current 2A 10A Minimum (Watts) * 40W 0W Maximum Off-State Leakage Current 5mA 0mA Stand-By Power Consumption < 1W < 1W Conductors Required 2 WIRE 3 WIRE Neutral Required NO YES Operating Temperature Range 0-40 C Warm-Up Time 30 seconds Rated Detection Field at Maximum Sensitivity ** Optimal Mounting Height for Rated Detection Field Timer Delay Range Light Level Inhibit Threshold Mounting Surface Mounting Centres International Protection Rating Overall Dimensions 6m x 6m, 8.5m from Sensor Head. Head Rotatable through 120 2.4 metres 5 Seconds to 20 Minutes, User Adjustable Continuous from 1 Lux to Full Sunlight, User Adjustable Wall or Ceiling Mount (flat surface required) 50mm, 60.3mm, 84mm IP44 100mm diameter x 57mm high Cables Accommodated 3 terminals, up to 1 x 2.5mm 2 cable per terminal Copyright 2006 Clipsal Australia Pty Ltd Page 12

Catalogue Number 751 751R Compatible Types Incompatible Types Incandescent 240V Halogen Iron Core Transformers Electronic Transformers Fluorescent s Discharge Lamps Motor s Specifications Typical @ 240V a.c., 25 C No user serviceable parts inside Incandescent 240V Halogen Fluorescent Iron Core Transformers Electronic Transformers Shaded Pole Induction Motors (exhaust fans) (8A Max) Split Phase Induction Motors (ceiling fans) (8A Max) Other Motor s (Limit to 2A Max) N/A This product is recommended for INDOOR USE ONLY * The 751, 2 Wire Infrascan must be connected to a minimum 40W load, unless the 31CAP (sold separately) is fi tted. Failure to do so may cause unexpected or erratic switching of the load. ** The range specifications given are based on a 90kg person travelling at greater than 1 metre per second across the fi eld of view, where there is a temperature differential greater than 5 degrees Celsius between the person and the background. Objects that are hotter or moving faster (eg motor vehicle on nearby roadway) may be detected at greater distances. A person covered in heavy clothing or walking directly towards the sensor may not be detected until they get much closer to the unit. Copyright 2006 Clipsal Australia Pty Ltd Page 13

14 Warning: Using the 751 with Special s Small loads (<40W) The 751 product can only drive loads greater than 40W. If you wish to drive a smaller load, the 31CAP Correction Device is required to be fitted in parallel with the load. For example: when driving a single contactor, be sure to use the 31CAP. s Which Are Sensitive To Leakage Currents The 751 is a two wire device. Two wire devices draw their power through the load. If this device is used in conjunction with a load which cannot provide enough continuous load current in the off-state, or the load is sensitive to a high off-state leakage current (for example: relays, contactors, various loads with built-in electronic control etc.) a 31CAP Correction Device must be connected in parallel with the load. Small (Non-Power Factor Corrected) Fluorescent s When a 31CAP is fitted, some small non-power factor corrected fluorescent loads may be controlled using the 751. Success varies from manufacturer to manufacturer. Recommend testing before installation. Installation must be compliant with local wiring rules. Line Neutral Line 31CAP 751 31CAP Correction Device Figure 10 Note: Please note the 751R is a three wire device, and switches the load using an internal relay. Power is not drawn through the load and so the 31CAP is not required. Copyright 2006 Clipsal Australia Pty Ltd Page 14

Copyright 2006 Clipsal Australia Pty Ltd Page 15

15 Warranty 1. The benefi ts conferred herein are in addition to, and in no way shall be deemed to derogate; either expressly or by implication, any or all other rights and remedies in respect to the Clipsal Product, which the consumer has under the Commonwealth Trade Practices Act or any other similar State or Territory Laws. 2. The warrantor is Clipsal Australia Pty Ltd of 12 Park Terrace Bowden, South Australia 5007. Telephone (08) 8269 0511. With registered offices in all Australian States. 3. This Clipsal Product is guaranteed against faulty workmanship and materials for a period of two (2) years from the date of installation. 4. Clipsal Australia Pty Ltd reserves the right, at its discretion, to either repair free of parts and labour charges, replace or offer refund in respect to any article found to be faulty due to materials, parts or workmanship. 5. This warranty is expressly subject to the Clipsal Product being installed, wired, tested, operated and used in accordance with the manufacturer s instructions. 6. All costs of a claim shall be met by Clipsal Australia Pty Ltd, however should the product that is the subject of the claim be found to be in good working order all such costs shall be met by the claimant. 7. When making a claim the consumer shall forward the Clipsal Product to the nearest office of Clipsal Australia Pty Ltd with adequate particulars of the defect within 28 days of the fault occurring. The product should be returned securely packed, complete with details of the date and place of purchase, description of load, and circumstances of malfunction. 16 Technical Support and Troubleshooting For all technical enquiries and assistance please contact our National Customer Service Enquiries Hotline Tel 1300 2025 25 Fax 1300 2025 56 (Call cost 25c, number valid within Australia only) Product of Clipsal Group of Companies ABN 27 007 873 529 12 Park Terrace, Bowden, South Australia 5007 Telephone (08) 8269 0511 Facsimile (08) 8340 1724 E-Mail plugin@clipsal.com.au clipsal.com Clipsal Australia Pty Ltd reserves the right to change specifications, modify designs and dis con tin ue items without incurring obligation and whilst every effort is made to ensure that descriptions, specifications and other in for ma tion in this catalogue are correct, no warranty is given in respect thereof and the company shall not be liable for any error therein. Copyright Clipsal Australia Pty Ltd 2006. All rights reserved. F1955/01 CLIPCOM/9447 10320706