LED Driver Module. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment.

Similar documents
Addressable NAC Output Module D327A

Notification Appliance Circuit Module

D7053. Installation Instructions Multiplex Input/Output Module

Booster Power Supply Manual

Remote NAC Power Supply D7038

4100U City and Relay Cards Installation Instructions

30.45 Electric Release PDRP-2001

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

F220-B6PS/M. Installation Guide. Addressable Detector Bases

FireNET Plus Wiring Instructions

AL800ULADA. NAC Power Extender. Installation Guide

Multiplex Eight Input Remote Modules

RELEASE DEVICE CONTROLS

LDM Series Lamp Driver Modules For Graphic Annunciation and Control

D7044. Installation Instructions Multiplex Single Input Module

General Routing Interface

These instructions detail procedures to follow in order to avoid damage to equipment.

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

21-light Remote Annunciator. Owner s Manual

MODEL B2 INSTALLATION MANUAL

Model 17A00 Expansion Enclosure

Operation and Installation Guide. Fire Alarm Control Panel

D7052. Installation Instructions Multiplex Dual Input Module

PSN-1000 & PSN 1000(E) Installation Manual

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Public Safety DAS Annunciator Panel

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Installation Guide. Control/Communicator

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

AL600ULADA. NAC Power Extender. Installation Guide

Installation Guide for models:

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

Conventional Releasing Control Panel

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

ACCURATE ELECTRONICS INC

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note

Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

Fire Control/Communicator

Installation Guide for models:

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

Annunciators, 8 LED. D7030X, D7030X-S2, and D7030X-S8. Installation Manual

Model 4880 Status Output Display Module Manual

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

RTD TEMPERATURE SENSING SYSTEM

ECC-50/100C. Emergency Command Center

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel

TECHNICAL DATA OBSOLETE

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

Conventional Fire Alarm System 2014 V1.2

Installation, Operating and Maintenance Manual

F I R E G A R D D C EXTENDED PERFORMANCE RELEASE DEVICE SAFE A N D SECURE

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

UEI-1 UNIVERSAL END-OF-LINE / ISOLATOR TESTER

DS3MX-E-I. Installation Guide. 3 Zone Mini Control Panel

Series. Access Power Controllers. Installation Guide

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM

Independent Zone Control (I.Z.C.)

DCU 305 R2/R3. Troubleshooting Manual

Battery charger modules

Interface and EOL Modules 8

MODEL ZAC ZONE ANNUNCIATOR/CONTROLLER DESIGNED FOR ZONE ANNUNCIATION AND MONITORING

Cookson Company 1901 South Litchfield Road Goodyear, AZ Phone:

"SS90" SERIES CONTROLS MODEL C INSTALLATION MANUAL

Operation and Installation Guide. Zone Expansion Module D8125

D9412GV2/D7412GV2. Approved Applications Compliance Guide. Control Panels

M2500 Engine Controller Installation Manual

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

R A D I O N I C S. READYKEY K2015A Alarm Event Manager. Installation Data Sheet. Description

1 INTRODUCTION NOTICE WARNINGS AND CAUTIONS NATIONAL APPROVALS EMC COMPATIBILITY UNPACKING...

ECC-50/100(E) Emergency Command Center. General. Features. Emergency Voice Evacuation TYPICAL APPLICATIONS

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

FCPS-24F FIRE ALARM FIELD CHARGER/POWER SUPPLY FOR FIRE PROTECTION/SIGNALING SERVICE FCPS-24F/FCPS-24FE. Field Charger/Power Supply

AL1002ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

D2412 Control / Communicator Installation Manual

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

FMR Installation Instructions. Addressable Fire System Controller

Application, Installation, Operation & Maintenance Manual

SENTROL ZX440F. Security System Control. Installation/ Programming

FEC403EN Installation Manual

OPERATION / INSTALLATION

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)

Transcription:

LED Driver Module Installation Guide 1.0 Notice These instructions are for installing Radionics LED Driver Module in a fire alarm system controlled by Radionics D8024 or D10024 Fire Alarm Control Panels (FACP). The LED Driver Module is a module installed on a two-wire Class A or B circuit connected to the FACP through a D9051 RS-485 Bus Module. It receives 24 VDC power from the FACP or from an auxiliary power supply. See the Analog Fire Alarm Control Panels Programming Guide (P/N: 38789) for programming instructions. Consult each panel s Operator s Manual and Installation Guide for operating and installation instructions. Install, test and maintain the according to these instructions, NFPA 72, Local Codes and the Authority Having Jurisdiction. Failure to follow these instructions may result in failure of the device to operate properly. Radionics is not responsible for improperly installed, tested or maintained devices. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment. NFPA 72 requires a complete system-wide functional test be performed following any modifications, repair, upgrades or adjustments made to the system s components, hardware, wiring, programming and software/ firmware. Make sure that the supply current is sufficient enough for full load conditions when installing this unit. A D9051 RS-485 Bus Module must be installed on the FACP in order to use the LED Driver Module. 2.0 Device Description The LED Driver Module is a graphic annunciator driver board that interprets alarm and trouble data from the Control/Communicator. The then displays the data on individually programmed LEDs. A typical application employs the LED Driver Module as a graphic annunciator. The can also be used to turn on remote relays. The provides an LED logic driver for graphic displays, and is compatible with those manufactured by Light Engineered Displays, WSA, Space-Age Electronics and other manufacturers. It is supported by software revision 610B- U0 or higher. RS-485 Connector LED 2 LED 1 Dip Switch SW2 Dip Switch SW1 DC Supply Connector 0V Terminal VSS+ Terminal Output Terminals Figure 1: LED Driver Module

Installing the 3.0 Installing the Inform the operator and the local authority before installing the in an existing system. Disconnect all power to the FACP before installing the. 3.1 Mounting the LED Driver Module Mount the on the D9013 Analog Modules Mounting Skirt (see the D9013 Installation Guide, P/N: 41379, for mounting instructions) in a suitable enclosure such as the D8109. If the is to be mounted in a graphics display enclosure, then consult the manufacturer s installation instructions. The can be installed up to 4,920 ft. (1,500 m) from the control panel. Use a Radionics D9073 High Integrity RS- 485 Bus Module for greater distances. 3.2 Circuit Wire Connections The communicates with the FACP over an RS-485 circuit connected to the D9051 RS-485 Bus Module. This peripheral circuit can mix LED Driver Modules and other peripheral devices such as Radionics D9072 NAC Module, D9073 High Integrity RS-485 Bus Module and D9069 and D9070 Fire System Controllers and Annunciators. To make circuit wire connections to the, use the following procedure: 1) Remove AC power from the system at the dedicated 120 VAC breaker and remove the standby battery power before making or removing any connections to the FACP. Out Terminals RS-485 Connector In Terminals B A E B A 2) Connect the input A wire to the bottom terminal of the terminal block. 3) Connect the B wire to the next terminal (485 Figure 2: Circuit Wiring Connections IN). The output A and B wires to the next peripheral device connect to the next two terminals (485 A and B OUT). The A and B wires must connect to their respective terminals. Crossing the terminal connections (connecting the A wire to the B terminal) will result in the FACP receiving corrupted data. The last in a Class B (two-wire) circuit must have a 150 ohm, ¼ watt pull-up resistor across the RS-485 OUT A and B terminals. For more information, see Figure 9. 3.3 24 VDC Power Connections A DC supply in the range of 18 V to 28 V, typically 24 V, rated at 300 ma minimum, is required to power the LED Driver Module. An on-board switch mode power supply isolates this input from all communication circuitry. An adequate DC supply can be obtained from the FACP s auxiliary 24 V output (see the FACP s installation manual for location of the auxiliary power output). An earth ground should be connected to the s RS-485 connector from the FACP. DC Supply Connector GND GND VIN VIN The D9142F 24 VDC Power Supply is suitable for this application. Make sure that the supply current is sufficient for full load conditions when installing this unit. Figure 3: Location of DC Supply Connector 38891F Page 2 Copyright 2001 Radionics

Installing the Table 1 shows the current consumption in the idle state and in the fully loaded (all outputs active) state for three input voltage ranges. State 18 VDC 24 VDC 28 VDC Idle State (ma) 19 29 39 Full Load State (ma) 370 277 247 3.4 Output Connections Table 1: Current Consumption Rates Each output on the will drive one or two LEDs when connected in a series configuration without the need for any external limiting resistors. Attempting to drive more than two LEDs will result in a noticeable reduction in the brightness of the LEDs on that output. See Figure 4 for wiring details. LED Power LED Annunciator or Output n (Where n could be 1-40) Figure 4: Wiring LEDs in a Series Configuration If more than two LEDs per output are required, then an external power supply must be provided. The (+)24 VDC of the DC supply must be connected to the LED Power terminal, and the GND to the 0 V terminal. Copyright 2001 Radionics Page 3 38891F

Installing the 0V Terminal -Ve External DC Supply LED Power Terminal Output n (Where n could be 1-40) +Ve External DC Supply VSS+ Terminal Figure 5: Connecting an External Power Supply to the Polarity must follow the pattern shown in Figure 5 or the may be damaged. A current limit resistor must be used to avoid damaging the if more than two LEDs per output are required. External limiting resistors must be calculated depending on the number of LEDs used in order that each output is limited to 15 ma maximum. Figure 6 shows how to calculate an external power source to supply up to five LEDs per output and their relative limiting resistors. Voltage developed across the internal 270 Ω resistor when 15 ma is following is 4.05 V. Therefore, the LED power will need to be at least 4.05 + 0.9 + 10.0 = 14.95 V. If an external power supply is to be 24 V, then R ext would be (24-14.95)/ 15 ma = 603 Ω. LED Power Terminal Rext Output n 10 V Across LEDs 15 ma Standard LED Forward Voltage: 2V 0.9V Figure 6: Calculating External Limiting Resistors 38891F Page 4 Copyright 2001 Radionics

Installing the Table 2 gives suggested externally applied LED power ratings with related external limiting resistors. LEDs per Output Suggested R ext Power Rating 5 620 ohms 0.25 watts 4 750 ohms 0.5 watts 3 910 ohms 0.5 watts Table 2: Suggested External Limiting Resistors LED Driver Module 0V Terminal VSS+ Terminal Up to 40 LEDs can be wired LED 1 LED 2 Wire + LED power side here LED 3 Figure 7: Wiring LEDs to the LED Driver Module The externally supplied LED power must not fall below 8 VDC or exceed 40 VDC. Fitting resistor values lower than the suggested values may result in damage to the LED Driver Module. An external LED power supply must not be derived from the FACP auxiliary supply. When wiring LED outputs to the, be sure to wire each LED negative wire to the output terminal 1-40. See Figure 7 for the wiring location of the 9 V LED power supply. Copyright 2001 Radionics Page 5 38891F

Installing the 3.5 Parallel Connection of Low Current LEDs LED Power Terminal Output n Figure 8: Parallel Connection of Low Current LEDs Low current LEDs with a forward current of 2 ma can be used as an alternative to standard LEDs. The lower forward current will allow these LEDs to be connected in a parallel configuration. The advantage of using such LEDs is that up to seven LEDs can be connected to each output using the internal LED power supply. This configuration allows for the same external resistor value per LED regardless of the number of LEDs connected. Forward voltage of low current LEDs is typically 1.8 V. Each Rext will be in the range of 1880 to 2000 Ω. See Figure 8 for more details. 38891F Page 6 Copyright 2001 Radionics

3.6 Connecting the LED to the Analog FACPs Installing the The LED Driver Module can be connected to the D8024 and D10024 Fire Alarm Control Panels (FACP) in order to provide graphic annunciation or to turn on remote relays. See Figure 9 for wiring details. Although Figure 9 shows the D8024 Control Module, the same connections are made when wiring the LED Driver Module to the D10024 FACP. To next RS-485 module RS-485 Connector B A E B A LED Driver Module LED 2 LED 1 (-) (+) GND GND VIN VIN Earth Ground Auxiliary Power Wiring D9051 RS485 Module PORT-C PL_LOOP2 PL_LOOP1 AUX O/P +24V OV A- A+ B- B+ SOUNDERS D8024 Control Module COM N/C N/O COM N/C N/O RELAY 1 RELAY 2 Figure 9: Connecting the to the Analog FACPs Copyright 2001 Radionics Page 7 38891F

Using the as a Relay Driver 4.0 Using the as a Relay Driver The LED Driver Module can be used to drive high sensitivity relays, such as the Altronix ALTRBST. Figure 10 shows how the can be used in such a way. Using the as a relay driver has not been evaluated by Underwriters Laboratories, Inc. Back EMF protection diodes are included on the module. Maximum coil power rating for 12 V relays is 180 mw. Maximum coil power rating for 24 V relays is 360 mw. LED Power Terminal +Ve External DC Supply Relay Coil IMAX = 15mA 0V -Ve External DC Supply 5.0 Restoring Power to the FACP Figure 10: Using the as a Relay Driver When all wiring connections have been made, restore power to the FACP by connecting the standby batteries and closing the 120 VAC dedicated breaker that controls the power input to the FACP. The green AC Power LED on the panel display lights to show that the 120 VAC power supply is on and the standby power supply is connected. 6.0 LED Programming See the Analog Fire Alarm Control Panels Programming Guide (P/N: 38789) for instructions on programming LED output functions. 38891F Page 8 Copyright 2001 Radionics

7.0 Features 7.1 LED Indicators Table 3 describes the actions of the LEDs on the. Features LED Color Descriptio n Y ellow Flashes when the receives valid RS-485 data. Green Flashes at a rate of 1 second on, 1 second off when the has a DC supply and is operating. 7.2 Zone/Event and Range Selection Table 3: LED Actions The can be configured to display either zone or event information by setting DIP switch SW2. See Table 4 for a summary of SW2 DIP switch settings and outputs. 7.3 Address Selection The LED Driver Module has an eight-position DIP switch (SW1) for address selection. Select a peripheral address that does not conflict with any other devices in the address range of 1 to 126. Once installed, follow the procedure in the FACP s programming guide for learning peripherals. When the has been learned into the system, it is ready for use. See Table 5 for address information. Copyright 2001 Radionics Page 9 38891F

Zone/Event Information SW2, pos 1 SW2, pos 2 SW2, pos 3 SW2, pos 4 SW2, pos 5 SW2, pos 6 Zone Outputs Event Outputs 1-40 - 41-80 - 81-120 - 121-160 - 161-200 - - 1-40 - 41-80 - 81-120 - 121-160 - 161-200 - 201-240 - 241-280 - 281-320 - 321-360 - 361-400 - 401-440 - 441-480 - 481-520 - 521-560 - 561-600 - 601-640 - 641-680 - 681-720 - 721-760 - 761-800 Table 4: SW2 Zone and Event Information 38891F Page 10 Copyright 2001 Radionics

Address Selections Use the following table to set the s address. A checkmark ( ) in the switch column indicates that the switch is. Switch Address Value 1 2 4 8 16 32 64 NA Switch Address Value 1 2 4 8 16 32 64 NA Switch Address Value 1 2 4 8 16 32 64 NA Address 1 2 3 4 5 6 7 8 Address 1 2 3 4 5 6 7 8 Address 1 2 3 4 5 6 7 8 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97 14 56 98 15 57 99 16 58 100 17 59 101 18 60 102 19 61 103 20 62 104 21 63 105 22 64 106 23 65 107 24 66 108 25 67 109 26 68 110 27 69 111 28 70 112 29 71 113 30 72 114 31 73 115 32 74 116 33 75 117 34 76 118 35 77 119 36 78 120 37 79 121 38 80 122 39 81 123 40 82 124 41 83 125 42 84 126 Table 5: Peripheral Analog Device Address Table Copyright 2001 Radionics Page 11 38891F

8.0 Specifications S upply Voltage Typically 24VDC @ 300mA. See Table 1 for more information. LED Displays DC supply/operation; RS-485 Receive Data Communication RS-485 L ength 6.3 in. (16.0 cm) W idth 4.4 in. (11.2 cm) D epth 1.1 in. (2.8 cm) W eight 8 oz. (226 g. ) 2001 Radionics, a division of Detection Systems, Inc. 38891F 8/01 PO Box 80012, Salinas, CA 93912-0012 USA Installation Guide Customer Service: (800) 538-5807 Page 12 of 12