BALANCED PORT Q-VALVE

Similar documents
Catalog 301. Condensed Catalog of Sporlan Products

RACE Catalogue 301 UK. Condensed Catalog of Sporlan Products

THERMOSTATIC EXPANSION VALVES

These valves can also be ordered as a bidirectional valve, allowing control of flow in both directions for use on heat pump applications.

QuickTips. Do you have questions? We have answers.

THERMOSTATIC EXPANSION VALVES

Sporlan 201 航空航天环境控制机电过滤流体与气体处理液压气动过程控制密封与屏蔽

Sporlan Thermostatic Expansion Valves

June 2001 / BULLETIN Way Valves. The right solenoid valve for any job.

TPLP Pre-Assembled. Low Profile Evaporators CONTENTS PRODUCT DATA & INSTALLATION. Air & Electric Defrost

Head Pressure Control Valves

Sporlan Valve Division Parker Hannifan/CIC Group

APPLICATION and INSTALLATION

Sealed Type Liquid Line and Suction Line Specifications

MAKING MODERN LIVING POSSIBLE. Thermostatic expansion valves, type TR 6 REFRIGERATION & AIR CONDITIONING DIVISION.

Thermostatic Expansion Valves Type TR 6

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES

INSTALLATION ADJUSTMENT SERVICE TYPE TM-15, TM-20 (As furnished with models TM-554, TM-356, TM-356-W/HA, TM PRV, 8015, 12520, 15020)

CATALOG. A complete line of products for Refrigerant 717 Ammonia:

Installation. Table of Contents. 1. Description/ Application. Form I-CAUA-CC (04-15) Obsoletes Form I-CAUA-CC (Version C.1)

ACNF Series Ceiling-Mount Air Handlers 1½ to 2½ Tons

Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE REFRIGERATION AND AIR CONDITIONING. Technical leaflet

REFRIGERANT PIPING SYSTEM

REFRIGERATION PRODUCTS

Thermostatic expansion valves for ammonia Type TEA

for Valve Types P-H-M-V-W-D-A

Liquid Distributor Type RD

Bulletin , March Electric Hot Gas Bypass Valves

OUTLET LEONARDH THERMOSTATIC INSTALLATION

DESIGN STANDARDS SECTION 15600

RD refrigerant distributors, for thermostatic expansion valves REFRIGERATION AND AIR CONDITIONING. Technical leaflet

MINI SLIMLINE COOL VUY-A VUY-A

AM Series Proportional Thermostatic Mixing Valve

Product Data. Features/Benefits. 28CB, 28LA Direct-Expansion. evaporator coils. 7 1 / 2 and 10 Nominal Tons Cooling

TPLP PRE-ASSEMBLED LOW PROFILE EVAPORATORS

INSTALLATION ADJUSTMENT SERVICE NEXT-GENERATION MANIFOLD SYSTEMS TM-520B-LF, TM-820B-LF, TM-920B-LF, TM-1520B-LF

November 2006 / BULLETIN ELECTRIC DISCHARGE BYPASS VALVES

Product Data. Features/Benefits. 28CB, 28LA Direct-Expansion. evaporator coils. 7 1 / 2 and 10 Nominal Tons Cooling

ASUF Series. Multi-Position, Multi-Speed ECM-Based Air Handler 1½ to 5 Tons. Contents. Product Features

SECTION REFRIGERATION EQUIPMENT. A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories.

INSTALLATION, OPERATION, SERVICE & PARTS SUPPLEMENT for

Accumulators - Suction Line

MAKING MODERN LIVING POSSIBLE. One valve for all purposes. TGE - thermostatic expansion valves REFRIGERATION & AIR CONDITIONING DIVISION

SOLENOID VALVES FOR REFRIGERATING SYSTEMS

Danfoss Scroll for Refrigeration MLM / MLZ

User s Information and Installation Instructions

A B A B4

DOMESTIC OUTLET. kg/cm 2 11 psi LEONARD LEONARD -10 C F LEONARD R THERMOSTATIC LEONARD LEONARD C F C F 60 COLD INLET HOT INLET

Thermostatic Expansion valves, type TUA/TUAE REFRIGERATION AND AIR CONDITIONING. Technical leaflet

PACKAGE AIR CONDITIONER

SERVICE BULLETIN A

Research Design Quality Value Service Experience

INSTALLATION AND COMMISSIONING MANUAL. Neos 100S Integra 20X, 30S, 35X, 40X, 50X

General Characteristics SM185S3QC. Dimensions. Terminal box. Electrical Characteristics. Recommended Installation torques

INSTALLATION INSTRUCTIONS

PowerPoint Presentation by: Associated Technical Authors. Publisher The Goodheart-Willcox Company, Inc. Tinley Park, Illinois

Installation. Table of Contents. 1. Description/ Application. Form I-CAUA-CC (Version C) Obsoletes Form I-CAUA-CC (Version B)

DESIGN GUIDELINES SPLIT TYPE AIR TO AIR HEAT PUMPS PAGE 1 of 6

INSTALLATION ADJUSTMENT SERVICE TM-1520A-DT, TM-2020A-DT PARALLEL SYSTEMS

RA15/6T & TB Conversion Valve

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

Condensing Unit Installation and Operating Instructions

Research Design Quality Value Service Experience

JCseries EVAPORATIVE CONDENSER. engineering data

CHAMPION SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: N4 (778) N4Y (492)

TECHNICAL MANUAL CX(E) SPLIT SYSTEMS. Tel: Fax:

SECTION (15530) - REFRIGERANT PIPING

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS

an ISO 9001:2008 Registered Company MINI SPACE SAVER HEAT /COOL/DEFROST QUZ-A VUZ-A

KCC Centrifugal Fan Air Cooled Condensers

THERMOSTATIC EXPANSION VALVES Part 1

INSTALLATION SETUP AND OPERATING INSTRUCTIONS THERMOSTATIC WATER MIXING VALVE SYSTEMS TYPE *TM-600, TM-650, *TM-800, *TM-850, TM-5100, TM-5125

Installation Instructions

Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A ), 120/208/240/1/60, R404A, LT/MT APPS

an ISO 9001:2008 Registered Company GOLL ST. - SAN ANTONIO, TX ph fax MINI SPACE SAVER HEAT /COOL

Air Cooled Condenser Installation and Operating Instructions

INSTALLATION INSTRUCTIONS

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

HOT INLET COLD INLET INSTALLATION

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

WIBR SERIES. Unit Coolers - Technical Catalog Hunt St - Pryor, OK Fax

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

Nominal Capacity 024 = 7 kw (2 tons) 036 = 10.5 kw (3 tons) 048 = 14 kw (4 tons) 060 = 17.5 kw (5 tons)

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

A Series T 3. Unit Coolers - Technical Catalog. Product Benefits: Comdustrial TM Refrigeration. Adaptability- Durability- Serviceability-

FSW SECTION. Product guide. Expansion Valves, Solenoid Valves Water Valves & Oil Pressure Switches F SECTION. 71

Wiring Diagrams. 9AB4-12 Air-Cooled Remote Condenser INDEX OPERATING SEQUENCE ACCESSORIES LEGEND AND NOTES FOR FIG. 1-6

CONDENSING UNITS-AIR SUBMITTED BY : Poppy Hudson PROJECT : Brooks Landing REV DATE : 07 Dec 2017 ORDER # : A00

Commercial High-Efficiency Condensing Units

MASS. MARITIME ACADEMY

User s Information/Installation Instructions

TRI-PLATE B INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS PART NO EFFECTIVE MARCH 1, 1983 REPRINT APRIL 16, 1999

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS 15 THROUGH 20 NOMINAL TON HB B-0804

INSTALLATION ADJUSTMENT SERVICE THERMOSTATIC WATER MIXING VALVE TM-200 (NEW STYLE) TMS-200 (VALVE ONLY)

Installation Instructions

R E D I C O N T R O L S

INSTALLATION INSTRUCTIONS R 410A Split System Air Conditioners

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS. HB 180 & thru 20 Nominal Tons NOTES, CAUTIONS AND WARNINGS

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

Transcription:

March 2001 / BULLETIN 10-10-6 ELEMENT BALANED PORT Q-VALVE ARTRIDGE BODY

Page 2 / BULLETIN 10-10-6 Introducing the Balanced Port -Valve The BQ combines the flexibility of the replaceable cartridge style Q valve with the proven performance of the Balanced Port BF, SBF and EBF valve types... a first for the industry! Like the Q valve, the BQ can be supplied as a complete valve or as three component parts: the valve body, the cartridge assembly and the thermostatic element. Since Sporlan s introduction of the Q-Valve in 1994, the family of conventional port interchangeable cartridge valves have become increasingly popular. Q-Valves are ideal for reducing inventory while increasing valve options So, the right valve is always on hand. Now, with the introduction of the Balanced Port Q-Valve (BQ), designed especially for systems with a wide range of operating conditions, the Q-Valve line satisfies over 2,900 TEV applications. And, like the conventional Q-Valve, the BQ reduces your inventory and increases your options. ELEMENT ARTRIDGE BODY

BULLETIN 10-10-6 / Page 3 U.S. Patent No. 5,238,219 For Refrigerants: -22-134a-402A-404A-407A- 407-408A-409A-502-507 SAE Flare & Extended ODF Solder onnections Sporlan selective charges are specifically designed for low temperature, medium temperature and air conditioning applications. Since the valve body and thermostatic element are supplied as independent components, you select the best possible thermostatic charge for the application. The element is manufactured with a large, flat diaphragm to yield maximum power and performance. The thermostatic element to body is Sporlan s proven knife edge, metal-to-metal joint, insuring leak-proof construction. Five cartridges are available with capacities that duplicate the balanced port BF, SBF, and EBF valve types. The cartridges are color-coded and metal stamped for identification. Like other Sporlan TEVs, flow through the BQ valve opposes the pin movement for improved stability at light loads. This design minimizes the risk of charge migration in the thermostatic element, a problem inherent in other cartridge style valves. By design, the Sporlan thermostatic element is warmed by the liquid flow entering through the top of the valve body. The brass body type valve is available with three body styles, the BQ(E), the EBQ(E) and the SBQ(E). While the nomenclature may appear to be unique at first glance, it is patterned after Sporlan s BF and Q valves. The BQ(E) version is designed with the traditional SAE flare connections, the EBQ(E) and SBQ(E) are supplied with ODF connections. All BQ valves have a removable strainer, and share identical internal construction details with external adjustment assemblies. These valves are designed for small refrigeration systems, including refrigerated cases, coolers and freezers. The externally equalized versions are well suited for air conditioning and heat pump duty.

Page 4 / BULLETIN 10-10-6, 134a, 401A, 409A THERMOSTATI EXPANSION VALVE APAITIES for S TONS OF REFRIGERATION AIR ONDITIONING, HEAT PUMP and OMMERIAL REFRIGERATION APPLIATIONS VALVE TYPES BQ-EBQ-SBQ 134a 401A 409A ARTRIDGE REOMMENDED THERMOSTATI HARGES ODE (PORT SIE) F, FP60 J, JP60 X, XP60 F, FP60 TEMPERATURE ( F) 0 0 0 0.22 0.25 0.28 0.26 0.27 0.30 0.29 0.25 0.28 0.27 0.41 0.54 0.54 0.50 0.54 0.55 0.54 0.50 A 0.92 B 1.70 1.69 1.56 2.05 2.03 1.87 2.20 2.20 2.04 2.06 2.05 1.90 3.00 2.99 2.76 3.62 3.59 3.30 3.88 3.88 3.60 3.63 3.62 3.35 LIQUID TEMPERATURE ENTERING TEV ( F) 0 1 3 5 7 8 9 10 11 1 13 1 ORRETION FATOR, F LIQUID TEMPERATURE 1.48 1.42 1.36 1.30 1.24 1.18 1.06 0.94 0.88 0.75 134a 1.70 1.63 1.56 1.49 1.42 1.36 1.14 0.85 0.78 401A 1.48 1.43 1.36 1.31 1.25 1.19 1.13 1.06 0.94 0.87 0.80 0.74 409A 1.55 1.45 1.39 1.28 1.23 1.17 1.06 0.94 0.88 0.76 These factors include corrections for liquid refrigerant density and net refrigerating effect and are based on an evaporator temperature of F. However, they may be used for any evaporator temperature from F to F since the variation in the actual factors across this range is insignificant. PRESSURE DROP AROSS TEV (PSI) TEMPERATURE 20 40 60 80 100 0 140 160 ( F) ORRETION FATOR, F PRESSURE DROP 1.15 1.53 1.63 & 0.50 0.87 1.32 TEV capacity = TEV rating x F liquid temperature x F pressure drop Example: Actual capacity of an A port in a Type BQ valve with R-134a at F evaporator, 100 psi pressure drop across the TEV, and F liquid temperature entering the TEV = (from rating chart) x (F liquid temperature) x (F pressure drop) = 1.73 tons. 22, 407A, 407 THERMOSTATI EXPANSION VALVE APAITIES for S TONS OF REFRIGERATION VALVE TYPES BQ-EBQ-SBQ AIR ONDITIONING, HEAT PUMP and OMMERIAL REFRIGERATION APPLIATIONS 22 407A 407 ARTRIDGE REOMMENDED THERMOSTATI HARGES ODE (PORT SIE) V, VP100, VGA V, VP40 V, VP100, VGA V, VP40 N, NP100, NGA TEMPERATURE ( F) 0-1 - - 0-1 - - 0.35 0.38 0.33 0.27 0.18 0.33 0.35 0.30 0.15 0.32 0.34 0.30 0.75 0.68 0.61 0.70 0.75 0.64 0.60 0.39 0.69 0.74 0.64 A 1.74 1.52 1.09 0.81 1.37 0.96 0.70 1.47 1.58 1.36 B 2.80 3.05 2.67 2.25 2.01 2.62 2.79 2.39 2.00 1.77 2.57 2.76 2.37 5.20 5.67 4.96 4.04 3.62 2.70 4.86 5.19 4.44 3.58 3.17 2.31 4.78 5.13 4.41 LIQUID TEMPERATURE ENTERING TEV ( F) 0 1 3 5 7 8 9 10 11 1 13 1 ORRETION FATOR, F LIQUID TEMPERATURE 22 1.56 1.51 1.45 1.40 1.23 1.17 1.06 0.94 0.88 0.76 407A 1.75 1.68 1.61 1.53 1.46 1.39 1.31 1.24 1.16 0.92 0.83 0.74 0.64 407 1.69 1.62 1.55 1.49 1.42 1.28 1.14 0.85 0.69 PR ESSURE DROP AROSS TEV (PSI) TEMPERATURE 30 50 75 100 5 150 175 200 225 275 (F ) ORRETION FATOR, F PRESSURE DROP 0.55 0.87 1.32 1.58 & 0.49 0.63 1.18 1.26 1.48 1 & 0.91 1.15 0.41 0.65 0.76 0.85 1.13 1.25 These factors include corrections for liquid refrigerant density and net refrigerating effect and are based on an evaporator temperature of F. However, they may be used for any evaporator temperature from -F to F since the variation in the actual factors across this range is insignificant. TEV capacity = TEV rating x F liquid temperature x F pressure drop Example: Actual capacity of an A port in a Type EBQ valve with R-22 at F evaporator, 100 psi pressure drop across the TEV, and 9F liquid temperature entering the TEV = 1.74 (from rating chart) x 1.06 (F liquid temperature) x (F pressure drop) = 1.64 tons.

BULLETIN 10-10-6 / Page 5 THERMOSTATI EXPANSION VALVE APAITIES for S TONS OF REFRIGERATION 404A, 408A, 502 VALVE TYPES BQ-EBQ-SBQ AIR ONDITIONING, HEAT PUMP and OMMERIAL REFRIGERATION APPLIATIONS ARTRIDGE 404A 408A 502 ODE REOMMENDED THERMOSTATI HARGE (PORT SIE) S, SP115 S, SP R, RP115 R, RP R, RP115 R, RP TEMPERATURE ( F) - 1 - - - 1 - - - 1 - - 0.17 0.31 0.33 0.32 0.34 0.30 0.25 0.18 0.46 0.49 0.46 0.39 0.32 0.62 0.66 0.64 0.63 0.55 0.47 0.48 0.46 0.39 0.33 A 1.02 1.04 0.94 0.79 1.37 1.44 1.14 1.09 1.03 0.95 0.80 B 1.89 1.98 1.37 1.14 2.53 2.70 2.30 2.24 1.95 1.85 1.95 1.65 1.38 1.17 2.86 3.00 2.50 2.45 2.10 1.75 3.83 4.08 3.48 3.43 2.98 2.54 2.80 2.96 2.50 2.45 2. 1.78 LIQUID TEMPERATURE ENTERING TEV ( F) 0 1 3 5 7 8 9 10 11 1 13 1 ORRETION FATOR, F LIQUID TEMPERATURE 404A 2.04 1.94 1.84 1.74 1.64 1.43 1.33 1.11 0.65 408A 1.47 1.40 1.27 1.14 0.86 0.79 502 1.86 1.78 1.69 1.61 1.52 1.44 1.26 1.18 1.09 0.91 0.73 0.64 PR ESSURE DROP AROSS TEV (PSI) TEMPERATURE 30 50 75 100 5 150 175 200 225 275 (F ) ORRETION FATOR, F PRESSURE DROP 0.55 0.87 1.32 1.58 & 0.49 0.63 1.18 1.26 1.48 1 & 0.91 1.15 0.41 0.65 0.76 0.85 1.13 1.25 These factors include corrections for liquid refrigerant density and net refrigerating effect and are based on an evaporator temperature of F. However, they may be used for any evaporator temperature from -F to F since the variation in the actual factors across this range is insignificant. TEV capacity = TEV rating x F liquid temperature x F pressure drop Example: Actual capacity of an A port in a Type SBQ valve with R-404A at -F evaporator, 5 psi pressure drop across the TEV, and F liquid temperature entering the TEV = 0.94 (from rating chart) x 1.43 (F liquid temperature) x 0.91 (F pressure drop) = tons. THERMOSTATI EXPANSION VALVE APAITIES for S TONS OF REFRIGERATION 402A & 507 VALVE TYPES BQ-EBQ-SBQ OMMERIAL and LOW TEMPERATURE REFRIGERATION APPLIATIONS ARTRIDGE ODE (PORT SIE) L 3 0.46 0.49 6 A 1.02 4 B 1.88 1.98 6 2.85 3.00 2 402A 507 REOMMENDED THERMOSTATI HARGE L, LP 0-1 - - 0.2 0.18.23 0.4 0.39 0.33.45 1.0 1.11 0.95 0.80.00 1.6 1.61 1.39 1.16.85 2.5 2.47 2. 1.78.79 P P, PP TEMPERATURE ( F) 4 0-1 - - 0 0.22 0.17 0 0.48 0.44 0.38 0.32 1 1.01 1 1.94 1.62 1.57 2 2.93 2.45 2.40 2.06 1.72 LIQUID TEMPERATURE ENTERING TEV ( F) These factors include corrections for liquid refrigerant density and net refrigerating effect and are based on an evaporator 0 1 3 5 7 8 9 10 11 1 13 1 ORRETION FATOR, F LIQUID TEMPERATURE temperature of F. However, they may 402A 507 2.01 1.99 1.91 1.89 1.82 1.79 1.72 1.69 1.62 1.59 1.52 1.42 1.40 1.32 1.30 1.11 0.78 0.65 0.66 0.51 be used for any evaporator temperature from -F to F since the variation in the actual factors across this range is PR ESSURE DROP AROSS TEV (PSI) insignificant. TEMPERATURE 30 50 75 100 5 150 175 200 225 275 300 TEV capacity = TEV rating x F liquid temperature x F (F ) ORRETION FATOR, F PRESSURE DROP pressure drop Example: Actual capacity of an A port in 0.55 0.87 1.32 1.58 1.73 a Type BQ valve with R-402A at -F evaporator, 5 psi 1 & & 0.49 0.63 0.91 1.18 1.26 1.15 1.48 1.55 pressure drop across the TEV, and F liquid temperature entering the TEV = 0.95 (from rating chart) x 1.42 (F 0.41 0.65 0.76 0.85 1.13 1.25 1.31 liquid temperature) x 0.91 (F pressure drop) = 1.23 tons.

Page 6 / BULLETIN 10-10-6 ( Sporlan o de) 22 (V) 407 (N) 407A (V) 134a (J) (F) 401A (X) 409A (F) 404A (S) 502 (R) 408A (R) 507 (P) 402A (L) TYPE 1 Internal BQ- BQ- BQ-A BQ-B BQ- BQ- BQ- BQ-A BQ-B BQ- BQ- BQ- BQ-A BQ-B BQ- BQ- BQ- BQ-A BQ-B BQ- SPEIFIATIONS BQ SAE Flare 2 External ARTRIDGE ODE (Port Size) ELEMENT SIE NO. 43, KNIFE EDGE JOINT NOMINAL APAITY RANGE Tons of Refrigeration Thermostatic harges Available P40 P P Standard Tubing Length-Inches 60 ONNETIONS Inches Blue figures are standard and will be furnished unless otherwise specified. SAE Flare INLET x OUTLET BQ & BQE 1/4 x 3/8 SAE 1/4 x 1/2 SAE 3/8 x 1/2 SAE 3 9 Angle Inlet External Net Weight-Lbs. Shipping Weight-Lbs. 1/4 SAE 1 1-1/ 2 1 Valves listed in this column should not be assembled with MOP Type air conditioning charges. 2 Standard External 1/4 SAE (BQ Body), 1/4 ODF (SBQ and EBQ Body). 3 The 3/8 SAE inlet fitting has a long taper on the flare surface. A 3/8 x 1/4 reducing flare nut will allow 1/4 OD tubing to be attached to this fitting. ( Sporlan o de) 22 (V) 407 (N) 407A (V) 134a (J) (F) 401A (X) 409A (F) 404A (S) 502 (R) 408A (R) 507 (P) 402A (L) TYPE SPEIFIATIONS SBQ Extended ODF Solder (with replaceable strainer) 1 Internal SBQ- SBQ- SBQ-A SBQ-B SBQ- SBQ- SBQ- SBQ-A SBQ-B SBQ- SBQ- SBQ- SBQ-A SBQ-B SBQ- SBQ- SBQ- SBQ-A SBQ-B SBQ- 2 External TYPE EBQ Extended ODF Solder Internal 2 External BQE- 1/8 thru 1/ 3 BQE- 1/ 2/ 3 A 3/ 1-1/ 2 B 1-3/ 3 BQE- 3-1/ 5-1/ 2 BQE- BQE- 1/ 1/ 3 A 1/ 1 B 1-1/ 1-3/ 4 BQE- 3 BQE- BQE- 1/ 1/ 3 A 1/ 1 B 1-1/ 2 BQE- 2-1/ 3 BQE- BQE- 1/ 1/ 3 A 1/ 1 B 1-1/ 2 BQE- 2-1/ 3 SBQE- SBQE- S S SBQE- SBQE- SBQE- S S SBQE- SBQE- SBQE- S S SBQE- SBQE- SBQE- S S SBQE- EBQ- EBQ- EBQ-A EBQ-B EBQ- EBQ- EBQ- EBQ-A EBQ-B EBQ- EBQ- EBQ- EBQ-A EBQ-B EBQ- EBQ- EBQ- EBQ-A EBQ-B EBQ- EBQE- EBQE- BQE- EBQE- EBQE- BQE- EBQE- EBQE- BQE- EBQE- EBQE- BQE- ELEMENT SIE NO. 43, KNIFE EDGE JOINT ARTRIDGE ODE (Port Size) 1/8 thru 1/ 3 1/ 2/ 3 3/ 1-1/ 1-3/ 3-1/ 5-1/ 1/ 1/ 3 1/ 1-1/ 1-3/ 1/ 1/ 3 1/ 1-1/ 2-1/ 1/ 1/ 3 1/ 1-1/ 2-1/ E A 2 E B 3 E 2 E A 1 E B 4 E 3 E A 1 E B 2 E 3 E A 1 E B 2 E 3 1 Valves listed in this column should not be assembled with MOP Type air conditioning charges. 2 Standard External 1/4 SAE (BQ Body), 1/4 ODF (SBQ and EBQ Body). NOMINAL APAITY RANGE Tons of Refrigeration Thermostatic harges Available P40 P P Std. Tubing Lgth.-In. 60 ONNETIONS Inches Blue figures are standard and will be furnished unless otherwise specified. Extended ODF Solder INLET x OUTLET SBQ & SBQE Only 3/8 x 1/2 ODF 9 0 Angle Inlet EBQ Only 3/8 x 1/2 ODF Straight Thru EBQE 3/8 x 1/2 ODF 1/2 x 5/8 ODF 1/2 x 7/8 ODF Straight Thru External 1/4 ODF Pointed Toward Bottom ap Net Weight-Lbs. Shipping Weight-Lbs. 1 1-1/ 2

TYPE BQE BULLETIN 10-10-6 / Page 7 1.94 3.93 2.53 1/4 SAE Removable Strainer P/N 3008-000 3/8 SAE Inlet Strainer P/N 1538-000 2.02 TOP VIEW BQE DIMENSIONS Inches FITTING SIE A B 1/4 SAE, 9 Angle 1.19-1.44 3/8 SAE, 9 Angle - 3/8 SAE - 1.61-1/2 SAE - 1.80 - A B TYPE EBQE 1.94 3.93 2.53 3/8 ODF Insert Strainer P/N 877-003 1/2 ODF Insert Strainer P/N 877-004 (EBQE Only) 2.02 EBQE DIMENSIONS Inches FITTING SIE A B 3/8 2.50-1/2 2.42 2.48 5/8-2.48 7/8-2.39 A B TOP VIEW 1.87 TYPE SBQE 3.93 Removable Strainer P/N 3427-000 1.94 TOP VIEW 2.53 2.02.84 1.87 1.39 2.48 BQE, EBQE, SBQE BULB SIES Inches STANDARD HARGES 22 134a 404A 507 0.50 OD x 3.00 & P Series 0.50 OD x 3.00 0.50 OD x 3.00 P Series 0.50 OD x 3.00 VGA 0.75 OD x 2.00

Page 8 / BULLETIN 10-10-6 BODY OMPLETE VALVE NOMENLATURE BQE - - V - 5' - 3/8 x 1/2 x 1/4 SAE Valve Type BQ, EBQ, SBQ = Internally Equalized BQE, EBQE, SBQE = Externally Equalized artridge Size Refrigerant ode (See page 9) Thermostatic harge SELETING OMPONENTS apillary Tube Length onnection Size and Style: In x Out x Ext. Eq. BQ EBQ SBQ SAE (Internally ODF (Internally ODF (Internally BQE EBQE SBQE Replaceable Strainer U.S. Patent No. 5,232,015 P/N 3427-000 SAE (Externally ARTRIDGE ODF (Externally ODF (Externally U.S. Patent No. 5,238,219 SPORLAN Identification tag with cartridge code (bends around capillary tubing) Top surface is color coded to identify cartridge capacity apacity code on cartridge INDIVIDUAL REPLAEMENT PARTS PART NUMBER SIE OLOR ODE ARTRIDGE AND I.D. TAG BQ- BQ- BQ-A BQ-B BQ- A B RED YELLOW BLUE PINK WHITE MISELLANEOUS PARTS O B-1 Oil Bottle (With Oil) 4444-000 BQ artridge Tool 184007 artridge Service Kit (omplete as noted on page 9) R- R-22 NOMINAL APAITY ( t R-134a ons) of R-401A the VALVE to be R-402A REPLAED R-404A R-502 R-507 1/8 thru 1/5 1/8 thru 1/ 3 1/8 thru 1/ 5 1/8 thru 1/ 5 1/8 thru 1/ 5 1/8 thru 1/ 5 1/8 thru 1/ 5 1/8 thru 1/ 5 1/4 thru 1/3 1/2 thru 2/ 3 1/4 thru 1/ 3 1/4 thru 1/ 3 1/4 thru 1/ 3 1/4 thru 1/ 3 1/4 thru 1/ 3 1/4 thru 1/ 3 BQ VALVE ARTRIDGE SIE OLOR ODE RED YELLOW 1/2 thru 1 3/ 1-1/ 2 1/ 1 1/ 1 1/ 1 1/ 1 1/ 1 1/ 1 A BLUE 1-1/4 thru 1-3/ 4 1-3/ 3 1-1/ 1-3/ 4 1-1/ 1-3/ 4 1-1/ 2 1-1/ 2 1-1/ 2 1-1/ 2 B PINK 3 3-1/ 5-1/ 2 3 3 2-1/ 3 2-1/ 3 2-1/ 3 2-1/ 3 WHITE

BULLETIN 10-10-6 / Page 9 ARTRIDGE SERVIE KIT Part No. 184007 B B A - Red Qty. 2 - Yellow Qty. 4 A - Blue Qty. 4 B - Pink Qty. 1 B - Pink Qty. 2 BQ artridge Tool Oil Bottle SPORLAN ELEMENT BQ - White Qty. 2 apillary Tube Length (standard = 5 ft.) SPORLAN VALVE O WASHINGTON, MO MADE IN U.S. of A. R-22 KT-43-V 43 V DATE 4499 Element Label Date ode Label (by week and year of manufacture) Bulb KT - 43 - V Abbreviation for "Kit" Element Size Number * Refrigerant ode Thermostatic harge SPORLAN ODE - - Element Label olor ode F - R- - Yellow V - R-22 - Green J - R-134a - Blue X - R-401A - Pink L - R-402A - Sand S - R-404A - Orange V - R-407A - Green N - R-407 - Light Brown R - R-408A - Purple F - R-409A - Yellow R - R-502 - Purple P - R-507 - Teal * While many new refrigerants and refrigerant blends have a unique letter code, many use the same thermostatic element as the traditional refrigerant they replace. Refer to the table below to select the correct thermostatic element. APPLIATION AIR ONDITIONING OMMERIAL REFRIGERATION 5 F to 1 F LOW TEMPERATURE REFRIGERATION F to F REOMMENDED THERMOSTATI ELEMENTS THERMOSTATI SYSTEM ELEMENT MOP 22 134a 401A 402A 404A 407A 407 408A 409A 502 507 psig X X X X KT-43-FP60 50 X X X KT-43-VP100 90 X X X K T-43-VGA X X X KT-43-SP115 105 X X X X K T-43-F X X X K T-43-V X X X K T-43-S X X K T-43-P X K T-43-F X KT-43-FP X X K T-43-V X X KT-43-VP40 30 X X X X X K T-43-S X X X X X KT-43-SP 35 The Sporlan type P thermostatic charges have essentially the same characteristics as the conventional cross charges with one exception: they produce a pressure limit or MOP. The P charges are not intended as replacements for the charges - they should only be used where a definite pressure limit is required to prevent overloading the motor.

Page 10 / BULLETIN 10-10-6 OMPONENT ASSEMBLY BQ artridge Tool Thermostatic Element Q Attach cartridge identification tag to element capillary tube. W (Oil) Lubricate O-rings. E Turn clockwise while applying downward force. R Once threads are engaged, Turn clockwise until seated (do not over tighten). T (Oil) Lubricate lock ring surface. Y Hand tighten element. Q-Valve Tool (QVT-1) View of Element 1 2 Before After Q-Valve Tool (QVT-1) Bench Flange (QVT-F) BULB ONTAT and IRUMFERENTIAL LOATION U After hand tight, turn element clockwise (or movement equal to one hex flat). 9:00 8:00 3 3:00 4:00 MULTIPLE S Above and Below Main Suction Line Flow from upper valve cannot affect bulb... line free draining Inverted trap to avoid oil draining into idle evaporator Free draining

FOR USE ON REFRIGERATION and /or BULLETIN 10-10-6 / Page 11 MAXIMUM TEST ONDITIONS M AXIMUM DEHYDRATION TEMPERATURES F THERMOSTATI HARGE VGA P Air onditioning harge 190 134a 190 22 160 185 502 150 170 P MAXIMUM LOW SIDE TEST PRESSURES VALVE TYPE psig BQ(E), EBQ(E), SBQ(E) 450 If elevated temperatures are used to assist in dehydrating the system, the thermostatic expansion valve should not be exposed to temperatures exceeding those shown in the table above. SYSTEM INSURANE Filter-Drier TYPE -163-S LISTED REFRIGERATION FILTER-DRIER 407G FOR USE WITH R R22 R500 5502 R134a AIR ONDITIONING SYSTEMS ONLY SPORLAN VALVE OMPANY WASHINGTON, MO 63090 MADE IN U.S. of A. W.P. 500 psig (3447 kpa) Moisture and Liquid Indicator SOLDER TEHNIQUES INSTALLATION INFORMATION N 2 Direct torch tip away from valve body and wrap body with wet rag. VALVE, EXTERNAL EQUALIER, and BULB LOATIONS