Product Data. 340AAV 4-Way Multipoise Fixed-Capacity Condensing Gas Furnace Sizes 040 thru 140

Similar documents
Product Data PG9MAB MULTIPOISE CONDENSING GAS FURNACE 3 -PASS PRIMARY HEAT EXCHANGERS FLOW -THROUGH SECONDARY HEAT EXCHANGERS MONOPORT INSHOT BURNERS

Product Data PG9MAB MULTIPOISE CONDENSING GAS FURNACE

Product Data PG9MXA 4-WAY MULTIPOISE TWO-STAGE CONDENSING GAS FURNACE

Model PG9MAB MULTIPOISE CONDENSING GAS FURNACE SS-PG9MAB-01. Time Roman FEATURES. burners seldom, if ever, needs cleaning.

Product Data. S Noise elimination combustion system. S Compact design only 33-1/3 in. (846 mm) tall

Product Data. S Variable-speed ECM blower motor. S Two heating stages. S Humidity control when using a humidity sensing thermostat

Product Data. 58STA/STX WAY MULTIPOISE INDUCED --- COMBUSTION GAS FURNACE Input Capacities: 45,000 thru 155,000 Btuh Series 160

Product Data. 58MEC PERFORMANCE BOOST WAY MULTIPOISE STAGE CONDENSING GAS FURNACE Input Rates: 60,000 thru 120,000 Btuh

355MAV Sizes 040 thru 120 Series E

Product Data. 58STA/STX WAY MULTIPOISE INDUCED --- COMBUSTION GAS FURNACE Input Capacities: 45,000 thru 155,000 Btuh Series 140, 150

350MAV HIGHLY-EFFICIENT 4-WAY MULTIPOISE FIXED-CAPACITY DIRECT-VENT CONDENSING GAS FURNACE. Sizes 040 thru 140 Series D. Form No. PDS 350M.40.

Product Data. S QuieTecht noise reduction system. S SmartEvapt -Humidity control when using a Thermidistat Control

Product Data. 58MCA 4-Way Multipoise Fixed-Capacity Condensing Gas Furnace Series 111 Input Capacities: 40,000 thru 120,000 Btuh

Product Data. 58MXA Deluxe 4-Way Multipoise Fixed-Capacity Condensing Gas Furnace. Series 111 Input Capacities: 40,000 thru 120,000 Btuh

Product Data. 58MSA 4-Way Multipoise Fixed-Capacity Condensing Gas Furnace Series 110 Input Capacities: 40,000 thru 120,000 Btuh

Product Data STANDARD FEATURES

Product Data. S HYBRID HEAT Dual Fuel System compatible S All models are chimney friendly when used with accessory vent kit

Product Data. S Noise elimination combustion system. S Compact design only 33-1/3 in. (846 mm) tall

Product Data. 58MCA 4-Way Multipoise Fixed-Capacity Direct-Vent Condensing Gas Furnace Series 131 Input Capacities: 40,000 thru 120,000 Btuh

Model GB1AAV UPFLOW GAS FURNACE. Series G SS-GB1A-04 FEATURES

Product Data. S ECM Blower Motor included S QuieTecht noise reduction system S SmartEvapt Humidity control when using a Thermidistatt Control

Product Data. 58MVP Deluxe 4-Way Multipoise Variable-Capacity Condensing Gas Furnace. Series 121 Input Capacities: 40,000 thru 120,000 Btuh

FEATURES. Gas Furnace provides the efficiency customers want with 78% Annual Fuel Utilization Efficiency (AFUE).

PLUS 95st MODEL 355CAV DELUXE 4 -WAY MULTIPOISE VARIABLE -SPEED MULTI -STAGE CONDENSING GAS FURNACE Series 100 Input Rates: 60,000 thru 120,000 Btuh

Product Data. 925SA PREFERREDt SERIES SINGLE -STAGE 4-WAY MULTIPOISE CONDENSING GAS FURNACE, SERIES A LIMITED WARRANTY*

Product Data. 58PAV Energy-Efficient Induced-Combustion Upflow Furnace. Input Capacities: 45,000 thru 155,000 Btuh. 80% AFUE At Budget Price

Product Data. 58CVA/CVX INFINITY 80 VARIABLE SPEED 4---WAY MULTIPOISE GAS FURNACE Input Capacities: 70,000 thru 155,000 Btuh Series 160

Product Data. Comfort Heatt technology, the ultimate in heating comfort...

Product Data. 59TP5A Performance Boost Two---Stage Way Multipoise Condensing Gas Furnace Series 100 LIMITED WARRANTY*

Product Data. 59SP5A Performance Boost, Single---Stage Way Multipoise Condensing Gas Furnace Series 100 LIMITED WARRANTY*

395CAV Sizes 045 thru 155 Series H and J

58CTA/CTX PERFORMANCE 80 TWO --- STAGE WAY MULTIPOISE INDUCED---COMBUSTION GAS FURNACE Input Capacities: 45,000 thru 155,000 Btuh Series 140

Product Data. 58STA/STX 4-WAY MULTIPOISE INDUCED-COMBUSTION GAS FURNACE Input Capacities: 45,000 thru 155,000 Btuh THE CARRIER 58STA/STX GAS FURNACE

Product Data 987MA EVOLUTIONR MODULATING 4 -WAY MULTIPOSE, VARIABLE SPEED CONDENSING GAS FURNACE, SERIES A LIMITED WARRANTY*

Product Data A {Jurisdictions where warranty benefits cannot be conditioned on registration

Product Data. Infinity 96 Model 58MVB Deluxe 4-Way Multipoise Variable-Speed Condensing Gas Furnace. Series 100 Input Rates: 40,000 thru 120,000 Btuh

Product Data. IdealComfortt technology, the ultimate in heating comfort...

Product Data. 59TN6A InfinityR Two---Stage, Variable Speed Way Multipoise Condensing Gas Furnace Series 100 LIMITED WARRANTY*

Product Data. 58TUA WeatherMaker 8000TS with Comfort Heat Technology Upflow Furnace. Series 120 Input Capacities: 40,000 thru 135,000 Btuh

Product Data. 59SC2A Comfort Series Single---Stage Way Multipoise Condensing Gas Furnace Series 100 LIMITED WARRANTY*

Cooling Capacity CFM in. w.c. (125 Pa)

Cooling Capacity CFM range

Product Data PG96VAT TWO -STAGE, 4 -WAY MULTIPOISE VARIABLE -SPEED CONDENSING GAS FURNACE

80% Variable Speed, Two Stage Heating Furnace. Cooling Capacity CFM in. w.c. (125 Pa)

Wt. Lbs Model Number (BTUH) Hz

Product Data. 58WAV WeatherMaker 8000 Energy-Efficient Deluxe Upflow Furnace. Series 150 and 160 Input Capacities: 45,000 thru 155,000 Btuh

Cooling Capacity CFM in. w.c. (125 Pa)

Product Data. 59MN7A Infinityr Modulating Way Multipoise Condensing Gas Furnace Series 100

Product Data. 58EFA Horizontal Gas Furnace. 50, ,000 Btuh Input

Product Data PERFECT HEATT TECHNOLOGY, THE ULTIMATE IN HEATING COMFORT...

Product Data. 58CTA/CTX PERFORMANCE 80 TWO-STAGE 4-WAY MULTIPOISE INDUCED-COMBUSTION FURNACE Input Capacities: 45,000 thru 155,000 Btuh

Product Data PG95XAT CONDENSING GAS FURNACE SERIES B STANDARD FEATURES

Product Data. 58TUA WeatherMaker 8000TS with Comfort Heat Technology Deluxe Upflow Furnace

Product Data. 95% AFUE Single Stage Furnace Upflow / Downflow / Horizontal. ama ! WARNING

Product Data. ama. 58BLA, 58BMA, and 58BTA Oil-Fired Furnaces. 58BLA Low-Boy. Copyright 1996 Carrier Corporation

Product Data. 925TA PREFERREDt SERIES TWO -STAGE 4-WAY MULTIPOISE CONDENSING GAS FURNACE, SERIES B

Product Data. 925SA PREFERREDt SERIES SINGLE -STAGE 4-WAY MULTIPOISE CONDENSING GAS FURNACE, SERIES A. Select Models

MERIT SERIES Downflow

RG7D 1-Stage Heat Series

TSTAT0201CW Recommended (sold separately)

Product Data. 59TP6A Performance Two-Stage, Variable Speed 4-Way Multipoise Condensing Gas Furnace Series 2, 3

Product Data. 925SA PREFERREDt SERIES SINGLE -STAGE 4-WAY MULTIPOISE CONDENSING GAS FURNACE, SERIES A AND B. Select Models

Product Data. 59SP5A Performance Boost, Single---Stage Way Multipoise Condensing Gas Furnace Series 100

For More Information Click Here or Call General Supply M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS

TECHNICAL SPECIFICATIONS

Product Data. 59SP2A Performance Boost, Single---Stage Way Multipoise Condensing Gas Furnace Series 100

Cooling Capacity CFM in. w.c. (125 Pa)

Product Data A {Jurisdictions where warranty benefits cannot be conditioned on registration

Product Data 986TA EVOLUTIONR TWO -STAGE 4 -WAY MULTIPOISE, VARIABLE SPEED CONDENSING GAS FURNACE, SERIES A

TSTAT0101SC Recommended. Cooling Capacity CFM in. w.c. (125 Pa)

Product Data. 59SP5A Performance Boost, Single---Stage Way Multipoise Condensing Gas Furnace Series 2

Product Data. 926TA PREFERREDt TWO -STAGE 4 -WAY MULTIPOISE, VARIABLE SPEED CONDENSING GAS FURNACE, SERIES A

Product Data OBM/OVM. MULTIPOISE OIL FURNACE INPUT CAPACITIES 70,000 thru 154,000 BTUH THE LATEST IN OIL FURNACE TECHNOLOGY

KG6RC Series TECHNICAL SPECIFICATIONS FEATURES AND BENEFITS

TECHNICAL SPECIFICATIONS

TSTAT0101SC Recommended (order separately)

Gas Furnaces. Gas Furnaces. 2-Stage Variable-Speed. 2-Stage Multi-Speed Multipoise. Multipoise 80AFUE. 2-Stage Variable-Speed Multi-Speed Multipoise

FG6T(C,L) Series. High Efficiency / Direct Vent or Non Direct Vent 2-Stage Condensing Gas Furnace with Variable Speed Blower TECHNICAL SPECIFICATIONS

KG6TE Series. High Efficiency / Direct Vent or Non Direct Vent 2-Stage Condensing Gas Furnace with Variable Speed Blower TECHNICAL SPECIFICATIONS

G6RC Series TECHNICAL SPECIFICATIONS

Upflow/ Horizontal Downflow/Horizontal Condensing, Direct Vent Gas-Fired Furnace

Product Data. S Unit may also be sidewall vented with an approved A S OVL units equipped with optional ECM 2.3 Variable

13 GEP A L P - 1 A

W92P- SERIES Models with Input Rates from 40 to 115 kbtu [11.72 to kw] (92% A.F.U.E. )

Product Data. 58CMA Multipoise Oil Furnace. Series 120 Input Capacities: 70,000 thru 154,000 Btuh. The Latest in Oil Furnace Technology

Multi-Position Gas Furnaces

8+* Bulletin No November 1997

ELITE SERIES Downflow - High Efficiency Blower Motor

Product Data 986TB EVOLUTIONR TWO -STAGE, VARIABLE SPEED 4 -WAY MULTIPOISE CONDENSING GAS FURNACE SERIES A

TZ96MDP SERIES Model with Input Rates from 40 to 115 kbtu [11.72 to kw] (All Models 96% A.F.U.E. )

MULTI POSITION GAS FURNACE

Product Data 369AAN FEATURES/BENEFITS THE LATEST IN OIL FURNACE TECHNOLOGY

Product Data. 58CMA Multipoise Oil Furnace. Series 110 Input Capacities: 70,000 thru 154,000 Btuh. The Latest in Oil Furnace Technology

MULTI POSITION GAS FURNACE

Rheem Classic Series Multi-position Gas Furnaces

Ruud Achiever Series Multi position Gas Furnaces

TZ95MSX SERIES Model with Input Rates from 40 to 115 kbtu [11.72 to kw] (All Models 95% A.F.U.E. )

M3RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace

FORM NO. G REV. 4 Supersedes Form No. G Rev. 3

Product Data 986TB EVOLUTIONR TWO -STAGE, VARIABLE SPEED 4 -WAY MULTIPOISE CONDENSING GAS FURNACE SERIES A

Transcription:

4-Way Multipoise Fixed-Capacity Condensing Gas Furnace Sizes 040 thru 140 Product Data A0086 The model Multipoise Condensing Furnace is specifically designed to meet the needs of the new construction market. This high -efficiency furnace utilizes a unique 4 -way multipoise design and compact size to fit where other furnaces will not. The model can be installed in any of 4 positions including horizontally in attics or crawlspaces, freeing space formerly used as a utility or furnace room. Except for the 140 size, all sizes of the model can be installed in a manufactured (mobile) home when the optional kit is used. With the exception of the 140 size, all sizes can be installed with 2 -pipe or 1 -pipe venting. The 140 size can be installed only as a 2 -pipe system. Sidewall or through -the-roof venting options and the use of PVC pipe eliminate the need for dedicated chimneys or chaseways to facilitate furnace venting. Time -saving installation features yield a very cost effective way to provide new home buyers with a high -efficiency and high -quality home comfort system. FEATURES Energy Star Compliant Gas Furnace 3 -Pass Primary Heat Exchangers - This design accelerates heat transfer and extracts heat that conventional heat exchangers waste up the flue. The primary heat exchanger is made of aluminized steel for corrosion resistance. Combustion Air and Ventilation - The advanced design allows Schedule 40PVC, PVC -DWV, SDR -21 PVC, SDR -26 PVC (not approved in Canada), ABS -DWV, or ABSF628 Schedule 40 pipe to bring outdoor air into the furnace for combustion. The extracted heat lowers the temperature of the combustion products to a point (typically below 11_F (46_C) that any of the approved types of pipe can also be used for venting combustion products outside the structure. The combustion -air and vent pipes can terminate through a side wall or through the roof when using one of our approved vent termination kits. Flow -Through Secondary Heat Exchangers - Each cell is laminated with our patented Everlastict polypropylene for greater resistance to corrosion. This breakthrough in heating technology helps extend the life of the furnace for years of dependable performance. The heat exchanger is positioned in the furnace to extract additional heat from the combustion products regardless of furnace orientation. Perfect Lightt Igniter - The unique Bryant SiN igniter is not only physically robust but it is also electrically robust. It is capable of running at line voltage and does not require complex voltage regulators as do other brands. This unique feature further enhances the reliability of gas furnace and continues Bryant s tradition of technology leadership and innovation in providing a reliable and durable product. Control Center - The printed -circuit board and all internal wiring are factory installed. Convenient terminals permit quickconnection of a thermostat and air conditioning control circuits. Connections for a humidifier and air cleaner are also provided. 4 -Way Multipoise Design - Allows a model to be installed in an upflow, downflow, or horizontal orientation. The model is available in 12 heat/airflow combinations, and when combined with the 4 -way design, allows for 48 different applications. Factory configured for upflow application, this furnace can easily be made ready for downflow or horizontal installations. Direct or Non -direct Venting - The can be installed as a 1 pipe/non -Direct vent or 2 pipe/direct vent furnace except the 140 size which can be installed as 2 -pipe only. This provides added flexibility to meet diverse installation needs. Insulated Casing - Foil -faced insulation in the heat exchanger section cuts heat loss. The casing also has the required openings for left - or right -side connection of gas, electric, drain, and vent connections. Certifications - The units are CSA (A.G.A./C.G.A.) design certified for use with natural and propane gases, as well as AHRI efficiency rating certified. The furnace is factory shipped for use with natural gas. A CSA (A.G.A./C.G.A.) listed gas conversion kit is required to convert furnace for use with propane gas. The model meets California Air Quality Management District emission requirements. Except for the 140 size unit, all models can be installed in a manufactured (mobile) home when the optional kit is used, and in elevations up to,000 ft. (3048 M) (140 size unit limitation of 7,000 ft. (2133.6 M). Quality Registration - The is engineered and manufactured under an ISO 9001 registered quality system. 1

DIMENSIONS 14 1 2" TYP (368mm) 26 1 16" (684mm) 26 1 4" (667mm) 24 1 2" (666mm) 22 16" (67mm) 2-IN. COMBUSTION- AIR CONN (1mm) 1 2-IN. DIA GAS CONN (13mm) 2-IN. VENT CONN (1mm) 1 2-IN. DIA THERMOSTAT (13mm) ENTRY 22 11 16" (76mm) SIDE INLET CONDENSATE DRAIN TRAP LOCATION (DOWNFLOW & HORIZONTAL LEFT) 7 8-IN. DIA (22mm) POWER CONN 7 8-IN. DIA (22mm) ACCESSORY POWER ENTRY CONDENSATE DRAIN TRAP LOCATION (ALTERTE UPFLOW) 9 7 16" TYP (240mm) 29 11 16" TYP (74mm) 27 8" (2mm) 27 9 16" TYP (0mm) 24 1 2" (622mm) 17 16" (0mm) 30 13 16" (783mm) 32 8" TYP (829mm) 13 16" (21mm) 33 1 4" TYP (84mm) AIRFLOW A D 13 16" OUTLET (21mm) CONDENSATE DRAIN TRAP LOCATION (DOWNFLOW & HORIZONTAL RIGHT) OR ALTERTE 1 2-IN. DIA GAS CONN 30 1 2" (77mm) 9 16" TYP (14mm) 18 1 4" (464mm) 28 1 2" (724mm) 26 1 16" (694mm) 26 1 4" (667mm) 22 16" (67mm) 19" (483mm) OUTLET 2-IN. COMBUSTION- AIR CONN 1 2-IN. DIA GAS CONN 7 8-IN. DIA POWER CONN 1 2-IN. DIA THERMOSTAT ENTRY 2-IN. VENT CONN 22 11 16" SIDE INLET 13 16" (21mm) 8" (16mm) 16" (8mm) 39 7 8" (13mm) 1" (2mm) INLET 1 1 4" (32mm) 23 1 CONDENSATE 1" 4" TYP(91mm) DRAIN LOCATION 11 16" E (2mm) SIDE INLET (UPFLOW) (17mm) 26 1 16" TYP(684mm) 11 16" (17mm) CONDENSATE DRAIN LOCATION (UPFLOW) DIMPLE LOCATORS FOR HORIZONTAL HANGING 22 1 4" TYP (6mm) 24 3 16" BOTTOM INLET (614mm) A003 7 16" (11mm) 11 16" (17mm) NOTES: 1. Minimum return-air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer s recommendation for equivalent diameters. 2. Minimum return-air opening at furnace: a. For 800 CFM 16-in. (406mm) round or 14 1 / 2 (368mm) x 12-in. (30mm) rectangle. b. For 10 CFM -in. (08mm) round or 14 1 / 2 (368mm) x 19 1 / 2-in. (mm) rectangle. c. For 1600 CFM 22-in.(9mm) round or 14 1 / 2 (368mm) x 23 1 / 4-in.(91mm) rectangle. d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side inlets, a combination of 1 side and the, or the only will ensure adequate return air openings for airflow requirements above 1800 CFM at 0. W.C. ESP. Dimensions --- IN. (mm) A D E 024040 17-1/2 () 1-7/8 (403) 16 (406) 036040 17-1/2 () 1-7/8 (403) 16 (406) 024060 17-1/2 () 1-7/8 (403) 16 (406) 036060 17-1/2 () 1-7/8 (403) 16 (406) 048060 17-1/2 () 1-7/8 (403) 16 (406) 036080 17-1/2 () 1-7/8 (403) 16 (406) 048080 17-1/2 () 1-7/8 (403) 16 (406) 060080 21 (33) 19-3/8 (2) 19-1/2 () 0480 21 (33) 19-3/8 (2) 19-1/2 () 0600 21 (33) 19-3/8 (2) 19-1/2 () 0601 24-1/2 (622) 22-7/8 (81) 23 (84) 060140 24-1/2 (622) 22-7/8 (81) 23 (84) 2

CLEARANCE TO COMBUSTIBLES 33122-1 REV. B LIT TOP A0843 D E S I G N Always Ask For C E R T I F I E D CERTIFIED Use of the AHRI Certified TM Mark indicates a manufacturer s participation in the program. For verification of certification for individual products, go to www.ahridirectory.org. 3

CONTROLS - THERMOSTATS AND ZONING Non -Programmable Thermostat Selection T6 --- C, T2 --- C T6 --- NHP, T2 --- NHP T6 --- NRH{} Programmable Thermostat Selection T2 --- PAC T2 --- PHP T6 --- PAC T6 --- PHP T6 --- PRH} For use with 1--- speed Air Conditioner --- deg. F/C, Auto Changeover For use with 1 or 2 --- speed Heat Pumps --- deg. F/C, Auto Changeover For multi-use / stage configurations --- deg. F/C, Auto Changeover/Temperature and Humidity Control For use with 1-speed Air Conditioner - deg. F/C, Auto Changeover, 7-Day Programmable For use with 1 or 2-speed Heat Pumps - deg. F/C, Auto Changeover, -2 Day Programmable For use with 1-speed Air Conditioner - deg. F/C, 7 Day Programmable For use with 1 or 2-speed Heat Pumps F/C, Auto Changeover, 7-Day Programmable For multi-use / stage configurations - deg. F/C, Auto Changeover, 7-Day Programmable/Temperature and Humidity Control Zoning Control Selection ZONEBB3ZAC01 ZONEBB3ZHP01 Zone Perfect Two---Zone kit ZONEBB2KIT01---B Zone Perfect Plus 2---Zone kit/temperature and Humidity Control ZONEBB4KIT01---B Zone Perfect Plus 4---Zone kit/temperature and Humidity Control ZONEBB8KIT01---B Zone Perfect Plus 8---Zone kit/temperature and Humidity Control {Thermidistatt Control control can be configured for multiple use and staging. It must be configured for each specific application. }HYBRID HEAT thermostat is used with furnace and heat pump application. 4

SPECIFICATIONS 024040 036040 024060 036060 048060 036080 Shipping Weight --- Lb. (KG) 164 (74) 16 (7) 172 (78) 1 (77) 1 (77) 189 (86) RATINGS AND PERFORMANCE Input Btuh* 40,000 40,000 60,000 60,000 60,000 80,000 Output Capacity BTUH* (ICS) (Shaded capacities are specified on rating plate) AFUE%{ Nonweatherized ICS Direct Vent (2 --- Pipe) Upflow 37,000 37,000 6,000 6,000 6,000 74,000 Downflow 37,000 37,000 6,000 6,000 6,000 74,000 Horizontal 37,000 37,000 6,000 6,000 6,000 74,000 Non --- Direct Vent (1 --- Pipe) Upflow 37,000 37,000 6,000 6,000 6,000 74,000 Downflow 37,000 37,000 6,000 6,000 6,000 74,000 Horizontal 37,000 37,000 6,000 6,000 6,000 74,000 Direct Vent (2 --- Pipe) Upflow 92.3 92.3 92.3 92.3 92.3 92.3 Downflow 91.2 91.2 91.2 91.2 91.2 91.2 Horizontal 92.1 92.1 92.1 92.1 92.1 92.1 Non --- Direct Vent (1 --- Pipe) Upflow 92.1 Downflow 91 Horizontal 91 Certified Temperature Rise Range F ( C) 30---60 (17 --- 33) 1---4 (8 --- 2) 4---7 (2 --- 41) 30---60 (17 --- 33) ---0 (11 --- 28) 40--- (22 --- 39) Certified External Static Pressure Heating 0. 0. 0.12 0.12 0.12 0.1 Cooling 0.0 0.0 0.0 0.0 0.0 0.0 Airflow CFM} Heating 80 112 88 6 13 1190 Cooling 89 121 900 10 14 124 ELECTRICAL Unit Volts --- Hertz --- Phase 11 --- 60 --- 1 Operating Voltage Range Min ---Max** 4---127 Maximum Unit Amps 6.1 7.4 6.1 7.2 9.6 7.7 Unit Ampacity{{ 8.4.0 8.4 9.8 12.8.4 Minimum Wire Size 14 14 14 14 14 14 Maximum Wire Length --- Ft (M)}} Maximum Fuse Size or Ckt Bkr Amps (Time---Delay Type Recommended) 1 1 1 1 1 1 Transformer (24v) 40va External Control Power Available Heating 12va Cooling 21va Air Conditioning Blower Relay Standard CONTROLS Limit Control SPST Heating Blower Control (Off Delay) Factory---Set at 13 Sec Burners (Monoport) 2 2 3 3 3 4 Gas Connection Size 1/2 ---in. NPT GAS CONTROLS Gas Valve (Redundant) Manufacturer White --- Rodgers Min Inlet Pressure (In. W.C.) 4. (Natural Gas) Max Inlet Pressure (In. W.C.) 13.6 (Natural Gas) Ignition Device Hot Surface BLOWER DATA Direct---Drive Motor HP (Permanent Split Capacitor) 1/ 1/3 1/ 1/3 1/2 1/3 Motor Full Load Amps 4.9.8 4.9.8 7.9.8 RPM (Nominal) --- Speeds 7---3 7---4 7---3 7---4 Blower Wheel Diameter x Width (In.) x 6 x 7 x 6 x 7 11 x 8 x 7 Filter Size (In.)---Sold Separately (1) 16 x 2 x 3/4 FACTORY---AUTHORIZED AND LISTED, DEALER---INSTALLED OPTIONS Gas Conversion Kit --- Natural --- to --- Propane KGANP4601ALL Gas Conversion Kit --- Propane --- to --- Natural KGAPN3901ALL Twinning Kit KGATW N/A 0601HSI N/A Manufactured (Mobile) Home Kit KGAMH0301KIT Downflow Base*** KGASB0301ALL Vent Termination Kit (Bracket Only for 2 Pipes) 2---in.---KGAVT01BRA 3---in.---KGAVT01BRA Vent Termination Kit (Single Exit) 2---in.---KGAVT01CVT 3---in.---KGAVT0801CVT Condensate Freeze Protection Kit KGAHT01CFP Condensate Neutralizer Kit (Obtained Thru RCD) P908---0001 Side Filter Rack (Without Filter)---Upflow ONLY KGAFR06ALL Electronic/Mechanical Air Cleaner Model EACA, EZXCAB, or FILCAB Humidifier Model HUM Heat/Energy Recovery Ventilator Model HRV UV Lights Model UVL Door Gasket Kit KGBAC01DGK Unframed Filter Permanent Washable 3/4---in. thick 16 x 2 (406 x 63 mm) 24 x 2 (6 x 63 mm) KGAWF1306UFR KGAWF106UFR 37 (11.2) 38 (11.) 29 (8.8) 36 (.9)

SPECIFICATIONS (CONTINUED) 048080 060080 0480 0600 0601 060140 Shipping Weight --- Lb. (KG) 193 (88) 1 (91) 21 (98) 218 (99) 246 (112) 2 (113) RATINGS AND PERFORMANCE Input Btuh* 80,000 80,000 0,000 0,000 1,000 138,000 Output Capacity BTUH* (ICS) (Shaded capacities are specified on rating plate) AFUE%{ Nonweatherized ICS Direct Vent (2 --- Pipe) Non --- Direct Vent (1 --- Pipe) Direct Vent (2 --- Pipe) Non --- Direct Vent (1 --- Pipe) Certified Temperature Rise Range F ( C) Certified External Static Pressure Airflow CFM} Upflow 74,000 74,000 93,000 93,000 112,000 127,000 Downflow 74,000 74,000 93,000 93,000 112,000 127,000 Horizontal 74,000 74,000 93,000 93,000 112,000 127,000 Upflow 74,000 74,000 93,000 93,000 112,000 Downflow 74,000 74,000 93,000 93,000 112,000 Horizontal 74,000 74,000 93,000 93,000 112,000 Upflow 92.3 92.3 92.3 92.3 92.3 92.3 Downflow 91.2 91.2 91.2 91.2 91.2 91.2 Horizontal 92.1 92.1 92.1 92.1 92.1 92 Upflow 92.1 Downflow 91 Horizontal 91 30---60 (17 --- 33) ---0 (11 --- 28) 4---7 (2 --- 41) 30---60 (17 --- 33) 40--- (22 --- 39) 0---80 (28 --- ) Heating 0.1 0.1 0. 0. 0. 0. Cooling 0.0 0.0 0.0 0.0 0.0 0.0 Heating 128 178 131 1690 17 19 Cooling 12 192 1 1930 00 1990 ELECTRICAL Unit Volts --- Hertz --- Phase 11 --- 60 --- 1 Operating Voltage Range Min ---Max** 4---127 Maximum Unit Amps.1 14.1.2 14.8 14.6 14.6 Unit Ampacity{{ 13.4 18.4 13. 19.3 19.1 18.8 Minimum Wire Size 14 12 14 12 12 12 Maximum Wire Length --- Ft (M)}} 28 (8.) 31 (9.4) 27 (8.2) 30 (9.1) 30 (9.1) 30 (9.1) Maximum Fuse Size or Ckt Bkr Amps (Time---Delay Type Recommended) 1 1 Transformer (24v) 40va External Control Power Available Heating 12va Cooling 21va Air Conditioning Blower Relay Standard CONTROLS Limit Control SPST Heating Blower Control (Off Delay) Factory---Set at 13 Sec Burners (Monoport) 4 4 6 6 Gas Connection Size 1/2 ---in. NPT GAS CONTROLS Manufacturer White --- Rodgers Gas Valve (Redundant) Min Inlet Pressure (In. W.C.) 4. (Natural Gas) Max Inlet Pressure (In. W.C.) 13.6 (Natural Gas) Ignition Device Hot Surface BLOWER DATA Direct---Drive Motor HP (Permanent Split Capacitor) 1/2 3/4 1/2 3/4 3/4 3/4 Motor Full Load Amps 7.9 11.1 7.9 11.1 11.1 11.1 RPM (Nominal) --- Speeds 7---4 Blower Wheel Diameter x Width --- In. (mm) 11 x 8 (279x 3) 11 x (279x2 4) 11 x 8 (279x 3) 11 x (279x2 4) 11 x (279x24 ) 11 x (279x24 ) Filter Size --- in. (mm) ---Sold Separately (1) x 2 x 3/4 (2)16 x 2 x 3/4 (08 x 63 x 19) (406 x 63 x 19) FACTORY---AUTHORIZED AND LISTED, DEALER---INSTALLED OPTIONS Gas Conversion Kit --- Natural --- to --- Propane KGANP4601ALL Gas Conversion Kit --- Propane --- to --- Natural KGAPN3901ALL Twinning Kit KGATW0601HSI N/A Manufactured (Mobile) Home Kit KGAMH0301KIT N/A Downflow Base*** KGASB0301ALL Vent Termination Kit (Bracket Only for 2 Pipes) 2---in.---KGAVT01BRA 3---in.---KGAVT01BRA Vent Termination Kit (Single Exit) 2---in.---KGAVT01CVT 3---in.---KGAVT0801CVT Condensate Freeze Protection Kit KGAHT01CFP Condensate Neutralizer Kit (Obtained Thru RCD) P908---0001 Side Filter Rack (Without Filter)---Upflow ONLY KGAFR06ALL Electronic/Mechanical Air Cleaner Model EACB, EZXCAB, or FILCAB Humidifier Model HUM Heat/EnergyRecoveryVentilator Model HRV UV Lights Model UVL Door Gasket Kit KGBAC01DGK Unframed Filter Permanent Washable 3/4---in. (19 mm) thick 16 x 2 (406 x 63 mm) 24 x 2 (6 x 63 mm) KGAWF1306UFR KGAWF106UFR * Gas input ratings are certified for elevations to 00 ft. (6 M) In U.S., for elevations above 00 ft. (6 M), reduce ratings 2% for each 00 ft. (30 M)above sea level. In Canada, derate the unit % from 00 to 400 ft. (6 to 1372 M) above sea level. { Capacity and AFUE in accordance with U.S. Government DOE test procedures. } Airflow shown is for only return---air supply with 3/4---in. (19 mm) filter(s). Air delivery above 1800 CFM may require that both sides, a combination of 1 side and, or only of the furnace be used for return air, see Air Delivery table. Where 2 sets of data are listed, the first set is for only return--- airsupply.thesecondsetisforbothsides,or1sideandreturn---airsupply.afilterisrequiredforeachreturn---airsupply. ** Permissible voltage limits for proper furnace operation. {{ Unit ampacity = 12% of largest component s full load amps plus 0% of all other potential operating components (EAC, humidifier, etc.). }} Length shown is measured 1 way along wire path between unit and service panel for maximum 2% voltage drop. *** Required for installation on combustible floors when no coil box is used, or when any coil box other than a Bryant CD, CK, CAP(R), CNP(R), or KCAKC cased coil is used. N/A --- Not applicable ICS --- Isolated Combustion System 6

MAXIMUM ALLOWABLE PIPE LENGTH - ALTITUDE 0 to 00 (0 to 6) ALTITUDE 01 to 3000 (6 to 914) Canada (BTUH) 40,000 60,000 80,000 0,000 1,000 140,000 (BTUH) 40,000 60,000 80,000 0,000 1,000 140,000 DIRECT VENT (2-PIPE) ONLY TERMITION TYPE 2Pipeor3-in NON-DIRECT VENT (1-PIPE) ONLY 1 (2) 1 (2) 3 (76) 3 (76) 2-1/2 (64) one 2-1/2 (64) 3 (76) 3 (76) no 3 (76) 2-1/2 (64) one 3 (76) 3 (76) no 4 (2) no DIRECT VENT (2-PIPE) ONLY TERMITION TYPE 2Pipeor3-in NON-DIRECT VENT (1-PIPE) ONLY 3 (76) 3 (76) 3 (76) 3 (76) 3 (76) no 4 (2) no 3 (76) one 4 (2) no 3 (76) no 4 (2) no NUMBER OF 90 ELBOWS 1 2 3 4 6 (1.) (16.8) (1.) 40 (12.2) 4 (13.7) (1.) 40 (12.1) 60 (18.3) 1 (4.6) 6 (19.8) 60 (18.3) (1.) 60 (18.3) (16.8) 0 (1.2) 3 (.7) 30 (9.1) 30 (9.1) 30 (9.1) 40 (12.2) 3 (.7) 30 (9.1) 2 (7.6) 3 (.6) 6 (17.0) 30 (9.1) 2 (1.8) 2 (7.6) 48 (14.6) NUMBER OF 90 ELBOWS 1 (4.6) 40 (12.2) 1 2 3 4 6 67 (.4) 17 (.2) 3 (.7) 14 (4.3) 63 (19.2) 39 (11.8) 62 (18.9) 12 (3.7) 67 (.4) 26 (7.9) 9 (2.7) 62 (18.9) 1 (4.6) 3 (.6) 7 7 (2.1) 66 (.1) 30 (9.1) 16 (4.9) 2 (1.8) 2 (1.8) 47 (14.3) 61 (18.6) 2 (7.6) 16 (4.9) 61 (18.6) 2 (7.6) 6 (1.8) 66 (.1) 61 (18.6) 1 (4.6) 61 (18.6) 62 (18.9) 63 (19.2) 31 (11.9) 61 (18.6) 6 (17.1) (1.) 27 (8.2) 61 (18.6) 0 (1.2) 23 (7.0) 61 (18.6) 43 (13.1) 19 (.8) See notes at end of table. 7

MAXIMUM ALLOWABLE PIPE LENGTH - ALTITUDE 3001 to 4000 (914 to 1219) ALTITUDE 4001 to 000 (1219 to 124) (BTUH) 40,000 60,000 80,000 0,000 1,000 140,000 (BTUH) 40,000 60,000 80,000 0,000 1,000 140,000 DIRECT VENT (2-PIPE) ONLY TERMITION TYPE 2Pipeor3-in 4 no --- IN (mm)* NON-DIRECT VENT (1-PIPE) ONLY --- IN (mm)* 3 (76) 3 (76) 3 (76) no 3 (76) 4 (2) no 3 (76) one 4 (2) no 3 (76) no 4 (2) no DIRECT VENT (2-PIPE) ONLY TERMITION TYPE 2Pipeor3-in NON-DIRECT VENT (1-PIPE) ONLY 3 (76) 3 (76) 3 (76) no 3 (76) 4 (2) no 4 (2) no 3 (76) no 4 (2) no NUMBER OF 90 ELBOWS 1 2 3 4 6 64 (19.) 16 (4.9) 68 (.7) 46 (14.0) 33 (.1) 6 (19.8) 9 (18.0) 11 (3.4) 30 (9.1) 9 (18.0) 11 (3.4) 63 (19.2) 41 (12.) 24 (7.3) 8 (17.7) 9 (18.0) 6 (1.8) 26 (7.9) 4 (16.) 6 (1.8) 62 (18.9) 28 (8.) 1 (4.6) 1 (1.) 8 (17.7) 48 (14.6) 43 (13.1) 7 23 (7.0) 14 (4.3) 66 (.1) 7 7 22 (6.7) (1.) 61 (18.6) 38 (11.6) 7 6 (17.1) 13 (4.0) 6 (17.1) 31 (9.4) 6 (17.1) 22 (6.7) 18 (.) NUMBER OF 90 ELBOWS 14 (4.3) 1 2 3 4 6 60 (18.3) 1 (4.6) 64 (19.) 31 (9.4) 3 6 (17.1) 21 (6.4) 69 (21.0) (16.8) 9 (18.0) 39 (11.9) 22 (6.7) 46 (14.0) (16.8) 17 (.1) 64 (19.) 0 (1.2) (1.) 8 (17.7) 26 (7.9) 13 (4.0) 67 (.4) 40 (12.2) 4 (16.) 13 (3.9) 9 (17.9) 4 (13.7) 39 (11.9) 3 21 (6.4) 12 (3.7) 62 (18.9) 33 (.1) 3 9 (2.7) 4 (16.4) 2 (1.8) 7 26 (7.9) 2 (1.8) (1.) (1.0) 2 (1.8) 11 (3.4) 2 (1.8) 2 (1.8) See notes at end of table. 8

MAXIMUM ALLOWABLE PIPE LENGTH - ALTITUDE 001 to 6000 (124 to 1829) ALTITUDE 6001 to 00 (1829 to 2134) (BTUH) 40,000 60,000 80,000 0,000 1,000 140,000 (BTUH) 40,000 60,000 80,000 0,000 1,000 140,000 DIRECT VENT (2-PIPE) ONLY TERMITION TYPE 2Pipeor3-in NON-DIRECT VENT (1-PIPE) ONLY 3 (76) 3 (76) 3 (76) no 3 (76) 4 (2) no 4 (2) no 3 (76) no 4 (2) no DIRECT VENT (2-PIPE) ONLY TERMITION TYPE 2Pipeor3-in NON-DIRECT VENT (1-PIPE) ONLY 3 (76) 3 (76) 3 (76) no 3 (76) 4 (2) no NUMBER OF 90 ELBOWS 1 2 3 4 6 7 14 (4.3) 60 (18.3) 41 (12.) 29 (8.8) 42 (12.8) 3 12 (3.6) 42 (12.8) 2 (1.8) 9 (2.7) (16.8) 36 (11.0) 21 (6.4) 67 (.4) 3 (.7) 2 (1.8) 8 (2.4) 37 (11.2) 47 (14.3) 42 (12.8) 40 (12.2) 3 (.7) 4 (16.) 23 (7.0) 12 (3.7) 62 (18.9) 29 (8.8) 0 (1.2) 18 (.) 11 (3.4) 7 22 (6.7) 48 (14.6) 17 (.2) 2 (1.8) 1 (4.6) 48 (14.6) 47 (14.3) 8 (2.4) 47 (14.3) 9 (2.7) 47 (14.3) 32 (9.7) 27 (8.2) NUMBER OF 90 ELBOWS 22 (6.7) 17 (.1) 1 2 3 4 6 3 13 (4.0) 7 38 (11.6) 27 (8.2) 68 (.7) 31 (9.4) 17 (.1) 48 (14.6) 8 (2.4) 2 (1.8) 33 (.1) 19 (.8) 63 (19.2) 24 (7.3) 48 (14.6) 12 (3.6) 43 (13.1 68 (.7) 38 (11.6) 67 (.4) 37 (11.3) 66 (.1) 32 (9.8) 64 (19.) 0 (1.2) 21 (6.4) 68 (.7) 8 (17.7) 18 (.) 47 (14.3) 7 (2.1) 4 (13.7) 16 (4.9) 67 (.4) 9 (2.7) 3 11 (3.4) 4 (13.7) 1 (4.6) 66 (.1) 48 (14.6) 43 (13.1) 6 (1.8) 64 (19.) 43 (13.1) 43 (13.1) See notes at end of table. 9

MAXIMUM ALLOWABLE PIPE LENGTH - ALTITUDE (BTUH) DIRECT VENT (2-PIPE) ONLY NON-DIRECT VENT (1-PIPE) ONLY NUMBER OF 90 ELBOWS TERMITION TYPE 1 2 3 4 6 40,000 66 (.1) 6 (19.8) 39 (11.9) 63 (19.2) 34 (.4) 62 (18.9) 33 (.1) 60 (18.3) 28 (6.) 9 (18.0) 60,000 12 (3.7) 3 7 (2.1) 48 (14.6) 46 (14.0) 41 (12.) 40 (12.2) 38 (11.6) 01 to 8000 (2134 to 2438) 80,000 0,000 2Pipeor3-in 3 (76) 3 (76) 3 (76) no 36 (11.0) 66 (.1) 2 (7.6) 63 (19.2) 31 (9.4) 6 (19.8) 17 (.2) 8 (17.7) 13 (4.0) 19 (.8) 63 (19.2) 8 (2.4) 3 7 (2.1) 14 (4.3) 62 (18.9) 7 (2.1) 48 (14.6) 12 (3.7) 60 (18.3) 43 (13.1) 9 (18.0) 38 (11.6) 1,000 3 (76) 4 (2) no 4 (2) no 46 (14.0) 61 (18.6) 6 (17.1) 43 (13.1) 1 (1.) 41 (12.) 46 (14.0) 40 (12.2) 41 (12.) 38 (11.6) 36 (11.0) 140,000 ALTITUDE (BTUH) DIRECT VENT (2-PIPE) ONLY NON-DIRECT VENT (1-PIPE) ONLY NUMBER OF 90 ELBOWS TERMITION TYPE 1 2 3 4 6 40,000 46 (14.0) 62 (18.9) 41 (12.) 60 (18.3) 36 (11.0) 8 (17.7) 31 (9.4) 6 (17.1) 29 (8.8) (16.8) 24 (7.3) 3 60,000 11 (3.4) 6 (1.8) 42 (12.8) 37 (11.3) 3 (.7) 34 (.4) 8001 to 9000 (2438 to 2743) 80,000 33 (.1) 62 (18.9) 28 (8.) 60 (18.3) 17 (.2) 8 (17.7) 12 (3.7) 6 (17.1) (16.8) 3 0,000 2Pipeor3-in 3 (76) 3 (76) 23 (7.0) 9 (18.0) 1 (4.6) 4 (16.) 7 (2.1) (1.) 39 (11.9) 34 (.4) 3 (76) no 1,000 3 (76) 4 (2) no 4 no 43 (13.1) 3 (.7) 41 (12.) 30 (9.1) 39 (11.9) 2 (7.6) 37 (11.3) 3 (.7) 1 (4.6) 34 (.4) 140,000 See notes at end of table.

MAXIMUM ALLOWABLE PIPE LENGTH - ALTITUDE 9001 to,000 (2743 to 3048) (BTUH) 40,000 60,000 80,000 0,000 1,000 DIRECT VENT (2-PIPE) ONLY TERMITION TYPE 2Pipeor3-in NON-DIRECT VENT (1-PIPE) ONLY 3 (76) 3 (76) 3 (76) 4 (2) no 4 (2) no 140,000 NUMBER OF 90 ELBOWS 1 2 3 4 6 42 (12.8) 7 4 (13.7) 30 (9.1) 7 21 (6.4) 4 (16.) 39 (11.9) 37 (11.3) (16.8) 40 (12.2) 2 (7.6) (16.8) 13 (4.0) 37 (11.3) (1.) 32 (9.8) 3 38 (11.6) 14 (4.3) 3 (1.) 3 (.7) 27 (8.2) 1 (1.) 33 (.1) 9 (2.7) 1 (1.) 2 (7.6) 31 (9.4) 7 (2.1) 47 (14.3) 29 (8.8) 47 (14.3) 39 (11.9) 33 (.1) 34 (.4) 31 (9.4) 29 (8.8) 29 (8.8) * Disk usage-unless otherwise specified, use perforated assembly (factory-supplied in loose parts bag). # If one is stated, separate 2 halves of perforated assembly and use shouldered half. When using shouldered half, install screen side toward inlet box. Wide radius elbow. Vent sizing for Canadian installations over 400 ft. (1372 M) above sea level are subject to acceptance by the local authorities having jurisdiction. -Not Allowed; pressure switch will not make. 1. Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur. 2. Size both the combustion-air and vent pipe independently, then use the larger diameter for both pipes. 3. Assume two 4 elbows equal one 90 elbow. Wide radius elbows are desirable and may be required in some cases. 4. Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.. The minimum pipe length is ft (1. M) for all applications. 6. Use 3-in. (76 mm) diameter vent termination kit for installations requiring 4-in (2 mm) diameter pipe. VENT LENGTH FOR OUTLET RESTRICTOR USAGE (60,000 BTU MODEL ONLY) } ALTITUDE --- 0 --- 00 (0 --- 6) 01 --- 3000 (6 --- 914)* 3001 --- 4000 (914 --- 1219) 4001 --- 000 (1219 --- 124) 001 --- 6000 (124 --- 1829) 6001 --- 00 (1829 --- 2134) 01 --- 8000 (2134 --- 2438) 8001 --- 9000 (2438 --- 2743) 9001 --- 000 (2743 --- 3048) *Canada 60,000 DIRECT VENT (2---PIPE). (IN / mm) NON --- DIRECT VENT (1---PIPE ONLY). (IN / mm) 2 --- in. (1) 2 --- in. (1) 2 --- in. (1) 2 --- in. (1) 2 --- in. (1) 2 --- in. (1) 2 --- in. (1) 2 --- in. (1) 2 --- in. (1) 2 --- in. (1) 2 --- in. (1) 2 --- in. (1) 2 --- in. (1) 2 --- in. (1) 2 --- in. (1) 2 --- in. (1) 2 --- in. (1) 2 --- in. (1) NO. OF 90_ ELBOWS 1 2 3 4 28 (8.) 24 (7.3) 21 (6.4) 17 (.1) 14 (4.2) (3) 6 (1.8) (6) 17 (.1) 13 (3.9) (3) 6 (1.8) 1 (4.2) 12 (3.6) 8 (2.4) (1.) (3) 7 (2.1) }Discard outlet restrictor if vent lengths or elbows exceed the above table Discard restrictor if using 11/2---in. (38mm) diameter pipe. Refer to installation instructions for outlet restrictor installation guidelines. 11

MAXIMUM ALLOWABLE EXPOSED VENT PIPE LENGTH (FT/M) WITH AND WITHOUT INSULATION IN WINTER DESIGN TEMPERATURE AMBIENT* FURCE SIZE 040 060 080 0 1 140 WINTER DESIGN TEMPERATURE F C) MAX PIPE DIAMETER IN (mm) WITHOUT INSULATION WITH 3/8 IN. ( mm) OR THICKER INSULATION (--- 7) 1. (38) 1 (16) (21) 0 ( --- 18) 1. (38) 28 (9) (21) --- ( --- 29) 1. (38) 16 () (21) (---7) 2 (1) 4 (14) (21) 0 ( --- 18) 2 (1) 22 (7) (21) --- ( --- 29) 2 (1) (3) 8 (18) (---7) 2 (1) 6 () (21) 0 ( --- 18) 2 (1) 3 (11) (21) --- ( --- 29) 2 (1) (6) (21) (---7) 2 (1) (17) (17) 0 ( --- 18) 2 (1) 48 (1) (17) --- ( --- 29) 2 (1) 30 (9) (17) (--- 7) 2. (64) (21) (21) 0 ( --- 18) 2. (64) 47 (14) (21) --- ( --- 29) 2. (64) 28 (9) (21) (--- 7) 2. (64) 40 (12) 40 (12) 0 ( --- 18) 2. (64) 40 (12) 40 (12) --- ( --- 29) 2. (64) 38 (12) 40 (12) (---7) 3 (76) (21) (21) 0 ( --- 18) 3 (76) 0 (1) (21) --- ( --- 29) 3 (76) 28 (9) (21) (---7) 3 (76) (21) (21) 0 ( --- 18) 3 (76) 61 (19) (21) --- ( --- 29) 3 (76) 37 (11) (21) (--- 7) 4 (2) (21) (21) 0 ( --- 18) 4 (2) 48 (1) (21) --- ( --- 29) 4 (2) 23 (7) (21) (---7) 3 (76) 60 (18) 60 (18) 0 ( --- 18) 3 (76) 60 (18) 60 (18) --- ( --- 29) 3 (76) (13) 60 (18) (--- 7) 4 (2) (21) (21) 0 ( --- 18) 4 (2) 7 (17) (21) --- ( --- 29) 4 (2) 30 (9) (21) * Pipe length (Ft. / M) specified for maximum pipe lengths located in unconditioned spaces. Pipes located in unconditioned space cannot exceed total allowable pipe length as specified in the Maximum Allowable Pipe Length chart. Insulation thickness based on R value of 3. per in. 12

CONDENSATE TRAP BLOWER SHELF CONDENSATE TRAP (INSIDE) FURCE DOOR CONDENSATE TRAP FURCE SIDE FURCE DOOR FURCE SIDE 4 7 8 124 mm 4 2 mm 3 4 146 mm 3 4 146 mm 4 ALTERTE DRAIN TUBE LOCATION CONDENSATE TRAP DRAIN TUBE LOCATION UPFLOW APPLICATIONS FIELD DRAIN CONN 1 26 667 mm 26 1 4 1 1 2 FIELD 4 667 mm 38 mm DRAIN CONN 3 4 19 mm SIDE VIEW FRONT VIEW END VIEW FRONT VIEW DOWNFLOW AND ALTERTE EXTERL UPFLOW APPLICATIONS HORIZONTAL APPLICATIONS 19 mm 3 4 SLOT FOR SCREW HORIZONTAL APPLICATION (OPTIOL) 1 1 2 38 mm WIRE TIE GUIDES (WHEN USED) 1 3 4 4 mm 7 1 8 181 mm 7 8 22 mm 2 1 4 7 mm 1 /4 OD COLLECTOR BOX TO TRAP RELIEF PORT 1 /2 OD INDUCER HOUSING DRAIN CONNECTION /8 OD COLLECTOR BOX DRAIN CONNECTION SCREW HOLE FOR UPFLOW OR DOWN- FLOW APPLICATIONS (OPTIOL) 1 /2-IN. PVC OR CPVC FRONT VIEW SIDE VIEW A93026 13

CONCENTRIC VENT FOR DIRECT VENT (2 -PIPE) APPLICATION (ALL MODEL SIZES) B IN. (MM) DIA PVC VENT/EXHAUST F COMBUSTION -AIR PIPE FOR NON -DIRECT VENT (1 -PIPE) APPLICATION (SIZES 040 THRU 1 ONLY) FIELD-SUPPLIED 2-IN. (1 mm) DIA. PVC 90 ELBOW FIELD-SUPPLIED 2-IN. (1 mm) DIA. PVC PIPE E 1 3 /16 (30 mm) C IN. (MM) DIA A 11/2 (38 mm) D A B IN. (MM) DIA PVC INTAKE/COMBUSTION AIR A971 PART NO. A* B C D{ E F KGAVT01CVT 33---3/8 (848) KGAVT0801CVT 38---7/8 (987) 2 (1) 3 (76) 3 --- 1/2 (89) 4 --- 1/2 (114) 16---/8 (422) 21---1/8 (37) 6 --- 1/4 (19) 7 --- 3/8 (187) --- 3/4 (146) 6 --- 1/2 (16) * Dimension A will change accordingly as dimension D is lengthened or shortened. {Dimension D may be lengthened to 60 in. (124 mm) maximum. Dimension D may also be shortened by cutting the pipes provided in the kit to 12 in. (30 mm) minimum. NOTE: See furnace Installation Instructions when venting multiple furnaces near each other. COMBUSTION-AIR DISC (FACTORY-SUPPLIED IN LOOSE PARTS BAG) CASING WIDTH IN (mm) 17--- 1/2 () 21 (33) 24--- 1/2 (622) A IN (mm) 8-1/2 ± 1/2 (216 ± 13) -1/2 ± 1/2 (267 ± 13) 12 ± 1/2 (30 ± 13) A96211 SIDE FILTER RACK 1 1 / 4 (TYP) (32 mm) 3 / 1 8 ( mm) / 2 TABS (13 mm) 2 3 / 8 (60 mm) 1 1 / 4 (32 mm) 2 1 / 8 (638 mm) 3 / 4 (19 mm) 17 1 / 8 23 1 / 8 (87 mm) 16 1 / 8 (4 mm) (43 mm) OPENING 14 1 /2 (368 mm) OPENING A80199 14

ACCESSORY DOWNFLOW SUBBASE LOCATING TAB 1 1 / 4-in. ( mm) TYP B PLENUM OPENING D 1 2 3 4 A LOCATING TAB 4 3 2 1 FACTORY-SUPPLIED FIELD-INSTALLED INSULATION C Disassembled A887 Assembled A97427 FURCE CASING WIDTH IN (mm) FURCE IN DOWNFLOW APPLICATION PLENUM OPENING* IN (MM) A FLOOR OPENING IN (MM) B C D HOLE NO. FOR WIDTH ADJUSTMENT 17---1/2 ( mm) 21 (33 mm) 24---1/2 (622 mm) Furnace with or without Cased Coil Assembly or Coil Box Furnace with or without Cased Coil Assembly or Coil Box Furnace with or without Cased Coil Assembly or Coil Box 1---1/8 (384 mm) 18---/8 (473 mm) 22---1/8 (62 mm) 19 (483 mm) 19 (483 mm) 19 (483 mm) 16---3/4 (426 mm) ---1/4 (14 mm) 23---3/4 (603 mm) *The plenum should be constructed 1/4 in. (6 mm) smaller in width and depth than the plenum dimensions shown above. ---3/8 (18 mm) ---3/8 (18 mm) ---3/8 (18 mm) 3 2 1 1

AIR DELIVERY -CFM (WITH FILTER)* 024040 036040 024060 036060 048060 036080 048080 060080 0480 0600 0601 060140 RETURN-AIR SUPPLY 1 side or 1 side or 1 side or 1 side or 1 side or 1 side or 1 side or 1 side or both sides or 1 side and 1 side or 1 side or both sides or 1 side and only both sides or 1 side and 1 side only only both sides or 1 side and 1 side only SPEED Med- Med- Med- Med- Med- Med- Med- Med- Med- Med- Med- Med- Med- Med- Med- Med- EXTERL STATIC PRESSURE (In. wc) 0.1 0.2 0.3 0.4 0. 0.6 0.7 0.8 7 40 99 94 89 840 760 6 80 82 780 740 68 63 60 480 740 0 60 6 6 1 4 38 14 131 112 930 10 890 74 1430 12 91 100 132 1 13 139 10 40 170 1 13 113 20 181 160 2360 196 1740 100 1340 119 220 172 10 2360 1960 230 17 14 243 40 22 198 228 167 1460 23 197 2140 1930 141 1280 11 92 6 86 7 137 1260 89 169 146 129 11 14 130 117 168 14 1260 1 217 2 1760 1 2280 192 1 14 131 117 217 190 1690 1480 231 1940 220 1 17 1 2360 00 2190 1930 22 19 160 1 22 194 80 180 1400 123 8 9 0 8 6 132 121 4 88 1640 143 126 114 140 1300 112 990 163 140 122 7 8 194 17 11 22 18 1660 1 1300 116 90 1900 1660 1460 226 1930 2160 19 167 146 228 190 211 1890 2140 19 16 1430 218 1900 2 1800 128 1180 4 80 94 76 62 127 1160 1 86 180 138 1230 11 1330 122 6 960 17 13 11 40 2 186 16 1460 2130 1830 161 14 12 1130 1840 1630 10 20 1900 187 16 141 22 190 4 1840 6 18 190 1400 21 1860 194 1740 * A filter is required for each return-air supply. For horizontal and downflow applications, use 1 side or or only as airflow reference. 121 111 990 830 900 6 10 1 97 840 14 13 1190 80 124 11 30 9 12 130 112 99 192 178 16 143 3 1760 1 137 123 10 1930 1790 17 1380 2130 180 00 18 17 136 2130 183 196 1780 1990 180 160 13 4 183 187 172 11 3 91 7 80 6 0 113 3 9 800 140 1300 110 3 1160 80 9 860 1 120 9 99 18 10 1390 1960 17 100 1330 10 18 17 1 1340 1800 188 17 11 132 0 1790 1890 17 19 1730 1 13 196 177 179 1660 99 930 830 730 40 42 40 90 80 7 1380 120 1 990 6 98 890 78 1380 118 40 9 173 16 1480 1340 187 16 142 1280 1140 30 1760 1640 1460 129 196 1740 1790 160 140 126 196 172 1800 164 1830 1660 140 127 1880 17 172 180 890 82 740 63 6 47 360 93 80 70 60 13 118 0 90 93 880 780 680 13 11 980 860 163 140 140 12 1790 17 13 12 9 97 16 14 13 1230 1890 1660 163 140 136 118 187 160 17 160 174 190 1390 1230 1800 1640 162 1 16

TYPICAL INSTALLATIONS OUTDOOR UNIT COMBUSTION AIR PIPE (DIRECT VENT/2-PIPE APPLICATION) A/C COIL VENT PIPE HUMIDIFIER COMBUSTION AIR INLET (NON-DIRECT 1-PIPE APPLICATION) ELECTRONIC AIR CLEANER GAS-FIRED WATER HEATER AIRFLOW FRONT OF FURCE Basement - Upflow Application A0064 ELECTRONIC AIR CLEANER VENT COMBUSTION AIR INLET (NON-DIRECT VENT/ 1-PIPE APPLICATION HUMIDIFIER COMBUSTION AIR (DIRECT VENT/ 2 PIPE APPLICATION OUTDOOR UNIT A/C COIL FRONT OF FURCE Closet- Downflow Application AIRFLOW A006 17

TYPICAL INSTALLATIONS (CONTINUED) COMBUSTION-AIR INLET (NON-DIRECT VENT/1-PIPE APPLICATION) VENT PIPE COMBUSTION AIR PIPE DIRECT VENT/2-PIPE APPLICATION) ELECTRONIC AIR CLEANER FRONT OF FURCE FURCE CONDENSATE DRAIN AIRFLOW REFRIGERATION PIPING AIR CONDITIONING COIL Attic - Horizontal Application A0066 COMBUSTION - AIR INLET (NON-DIRECT VENT/ 1-PIPE APPLICATION) COMBUSTION AIR PIPE (DIRECT VENT/2-PIPE APPLICATION) VENT PIPE REFRIGERATION PIPING AIR CONDITIONING COIL AIRFLOW FURCE CONDENSATE DRAIN FRONT OF FURCE ELECTRONIC AIR CLEANER Crawlspace - Horizontal Application A0067 18

GUIDE SPECIFICATIONS GENERAL System Description Furnish a (4 -way multipoise) fixed capacity gas-fired condensing furnace for use with natural gas or propane (factory authorized conversion kit required for propane); furnish cold air return plenum; furnish side (external) filter rack. Quality Assurance Unit will be designed, tested and constructed to the current ANSI Z21.47/CSA 2.3 design standard for gas -fired central furnaces. Unit will be 3rd party certified by CSA to the current ANSI Z21.47/CSA 2.3 design standard for gas -fired central furnaces. Unit will carry the CSA Blue StarR and Blue FlameR labels. Unit efficiency testing will be performed per the current DOE test procedure as listed in the Federal Register. Unit will be certified for capacity and efficiency and listed in the latest AHRI Consumer s Directory of Certified Efficiency Ratings. Unit will carry the current Federal Trade Commission Energy Guide efficiency label. Delivery, Storage, and Handling Unit will be shipped as single package only and is stored and handled per unit manufacturer s recommendations. Warranty (for inclusion by specifying engineer) U.S. and Canada only. Warranty certificate available upon request. PRODUCTS Equipment Components shall include: slow -opening gas valve to reduce ignition noise, regulate gas flow, with electric switch gas shut -off; flame proving sensor, hot surface igniter, pressure switch assembly verifies inducer operation; flame rollout switch, drain tubing and installed condensate drain trap, blower and inducer assembly, 40va transformer; low -voltage (heating) (heating/ cooling) thermostat. Blower Wheel and Blower Motor Galvanized blower wheel shall be centrifugal type, statically and dynamically balanced. Blower motor of PSC type shall be permanently lubricated with sealed bearings, of hp, and shall be multiple -speed direct drive. Blower motor shall be soft mounted to the blower scroll to reduce vibration transmission. Filters Furnace shall have reusable -type filters. Filter shall be in. (mm) x in. (mm). Casing Casing shall be of.030 in. (.76 mm) thickness minimum, pre -painted galvanized steel. Inducer Motor Inducer motor shall be soft mounted to reduce vibration transmission. Primary Heat Exchangers Primary Heat exchangers shall be 3 -Pass gauge corrosion resistant aluminized steel of fold -and -crimp sectional design, which operates under negative pressure. Secondary Heat Exchangers Secondary Heat exchangers shall be of a flow -through design having a patented interior laminate coating of polypropylene for greater corrosion resistance with fold -and -crimp design, which operates under negative pressure. Controls Controls shall include a microprocessor based integrated electronic control board with at least 11 service troubleshooting codes displayed via diagnostic flashing LED light on the control, has ability to store fault codes, when activated a self -test feature checks all major functions of the furnace within one minute, and a replaceable automotive -type circuit protection fuse. Multiple operational settings available including separate blower speeds. Cooling airflow will be selectable between 30 or 400 CFM per ton of air conditioning. Operating Characteristics Heating Capacity shall be Btuh input; Btuh output capacity. Fuel Gas Efficiency shall be 92% AFUE. Air delivery shall be cfm minimum at 0.0 in. wg. external static pressure. Dimensions shall be: depth in. (mm); width in. (mm); height in. (mm) (casing only). Height shall be in. (mm) with A/C coil and in. (mm) overall with plenum. Electrical Requirements Electrical supply shall be 11 volts, 60 Hz, single-phase (nominal). Minimum wire size shall be AWG; maximum fuse size or HACR -type, designated circuit breaker shall be Amps. Special Features Refer to section of the product data sheet identifying accessories and descriptions for specific features and available enhancements. 19

E Bryant Heating & Cooling Systems D 73 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 11/ Catalog No. PDS340A.40.8 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Replaces: PDS340A.40.7