INSTALLATION ADJUSTMENT SERVICE TYPE TM-15, TM-20* (As furnished with models TM-554, TM-356, TM-356-W/HA Valve is ASSE 1017 listed

Similar documents
INSTALLATION ADJUSTMENT SERVICE TYPE TM-15, TM-20, TM-20-LF (As furnished with models TM-554, TM-356, TM-356-W/HA)

INSTALLATION ADJUSTMENT SERVICE

OUTLET HOT INLET COLD INLET INSTALLATION

INSTALLATION SETUP AND OPERATING INSTRUCTIONS THERMOSTATIC WATER MIXING VALVE SYSTEM * TM-500A, TM-550A

INSTALLATION SETUP AND OPERATING INSTRUCTIONS THERMOSTATIC WATER MIXING VALVE SYSTEM TM-500, TM-550

INSTALLATION ADJUSTMENT SERVICE TYPE TM-15, TM-20 (As furnished with models TM-554, TM-356, TM-356-W/HA, TM PRV, 8015, 12520, 15020)

MODEL TA. TA-SB 117.5mm mm HOT INLET. TA mm mm mm mm

TA-300, TA-300-LF, TA-350, TA-350-LF

MEGATRON MODEL 2, 3, 4, and 5

INSTALLATION ADJUSTMENT SERVICE NEXT-GENERATION MANIFOLD SYSTEMS TM-520B-LF, TM-820B-LF, TM-920B-LF, TM-1520B-LF

DOMESTIC OUTLET. kg/cm 2 11 psi LEONARD LEONARD -10 C F LEONARD R THERMOSTATIC LEONARD LEONARD C F C F 60 COLD INLET HOT INLET

INSTALLATION ADJUSTMENT SERVICE

INSTALLATION ADJUSTMENT SERVICE HIGHLOW THERMOSTATIC WATER MIXING VALVE SERIES XL-32, XL-82

Installation, Operation and Maintenance Guide G3600 Series Thermostatic Mixing Valves

INSTALLATION ADJUSTMENT SERVICE THERMOSTATIC WATER MIXING VALVE SERIES LV-981 & LV-982

INSTALLATION ADJUSTMENT SERVICE THERMOSTATIC WATER MIXING VALVE TM-200 (NEW STYLE) TMS-200 (VALVE ONLY)

30 R -10 C F H C INSTALLATION. Maximum Operating Pressure 125PSI (860 KPA) for Hot and Cold Water. CAUTION

Installation, Operation and Maintenance Guide AP3900 Series Thermostatic Mixing Valves

INSTALLATION 125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE

Note: Please provide valve serial number (stamped on cover of valve) when ordering parts. Tempered Water Outlet. Hot Water Inlet.

INSTALLATION 125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE

INSTALLATION ADJUSTMENT SERVICE TM-1520A-DT, TM-2020A-DT PARALLEL SYSTEMS

INSTALLATION ADJUSTMENT SERVICE HIGH-LOW MANIFOLD SYSTEMS TM-520, TM-820, TM-920, TM-1520A TM-520-LF TM-820-LF, TM-920-LF, TM-1520A-LF

INSTALLATION 125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE

INSTALLATION 125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE

INSTALLATION 125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE

INSTALLATION 125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE

INSTALLATION ADJUSTMENT SERVICE HIGH-LOW MANIFOLD TM-2020B

OUTLET LEONARDH THERMOSTATIC INSTALLATION

Note: Please provide valve serial number (stamped on cover of valve) when ordering parts. Thermometer. Hot Water Inlet. Cold Water Inlet G3600LF

SS-7600 THERMOSTATIC MODEL INSTALLATION INSTRUCTIONS

INSTALLATION 125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE

INSTALLATION 125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE

INSTALLATION ADJUSTMENT SERVICE HIGH-LOW MANIFOLD SYSTEMS TM-420A Valve assemblies are ASSE 1017 listed

INSTALLATION ADJUSTMENT SERVICE HIGH-LOW MANIFOLD SYSTEMS TM-420A Valve assemblies are ASSE 1017 listed

INSTALLATION ADJUSTMENT SERVICE HIGH-LOW MANIFOLD TM-2020B, TM-2020B-LF

INSTALLATION ADJUSTMENT SERVICE HIGH-LOW MANIFOLD TM-2020B, TM-2020B-LF

MODEL 210, 210-LF THERMOSTATIC WATER MIXING VALVES INSTALLATION SETUP AND OPERATING INSTRUCTIONS

HOT INLET COLD INLET INSTALLATION

INSTALLATION ADJUSTMENT SERVICE HIGH-LOW MANIFOLD TM-2020B, TM-2020B-LF

INSTALLATION SETUP AND OPERATING INSTRUCTIONS THERMOSTATIC WATER MIXING VALVE SYSTEMS TYPE *TM-600, TM-650, *TM-800, *TM-850, TM-5100, TM-5125

INSTALLATION ADJUSTMENT SERVICE 2P TM-2020B-2P, TM2020B-2P-LF PARALLEL SYSTEMS

INSTALLATION ADJUSTMENT SERVICE MEGATRON MODEL 8N-LF. Valve assemblies are ASSE 1017 listed

INSTALLATION ADJUSTMENT SERVICE TM-1520A-2P, TM-1520A-2P-LF TM-2020B-2P, TM2020B-2P-LF PARALLEL SYSTEMS

INSTALLATION ADJUSTMENT SERVICE 2PS TM-2020B-2P, TM2020B-2PS-LF PARALLEL SYSTEMS

MEGATRON MODEL 2NB-LF, 3NB-LF, 4NB-LF, 5NB-LF NEXT GENERATION MANIFOLD SYSTEMS TM-520B-LF, 820B-LF, 920B-LF, 1520B-LF

OUTLET LEONARD THERMOSTATIC INSTALLATION

MEGATRON MODEL TA, TA-LF

LEONARD -10 LEONARD VALVE CO. CRANSTON RI USA. TYP TM US. P aten ts 2.970, 3,06 1, , " Maximum Operating Pressure 125PSI (8.6 Bar).

MEGATRON MODEL 2N, 3N, 4N, 5N HIGH-LOW MANIFOLD SYSTEMS TM-520, TM-820, TM-920, TM-1520A TM-520-LF, TM-820-LF, TM-920-LF, TM-1520A-LF

Installation S

Installation S

Installation S

Installation S

Installation S

Installation S HL2X2 High Capacity Manifold System. Table of Contents Rev. B; ECN Bradley Page 1 of 8 11/10/2014

ECO-MIX COMPLETE WATER TEMPERATURE CONTROL STATION

Installation Instructions / Warranty

Installation Instructions / Warranty. Metris 31060XX XX XX1

ECO-MIX COMPLETE WATER TEMPERATURE CONTROL STATION

Installation Instructions / Warranty. PuraVida 15775XX1

TWIN-FLOIII HEATER INSPECT THE SHIPMENT IMMEDIATELY WHEN RECEIVED TO DETERMINE IF ANY DAMAGE HAS OCCURRED DURING SHIPMENT.

Installation Instructions PP-AS20 Anti-Scale System

ECO-MIX COMPLETE WATER TEMPERATURE CONTROL STATION

Installation Instructions / Warranty. Massaud

installation, operation & Maintenance manual Floor-mounted Induction units acb 30/35

CLASSIC HIGH LOW MANIFOLD SYSTEMS

WATER TEMPERATURE CONTROL SYSTEMS

Submittal S-NV-150-LF-M November, 2018 MEGATRON MODEL NV-150-LF DIGITAL TEMPERATURE CONTROL STATION

ECO-MIX COMPLETE WATER TEMPERATURE CONTROL STATION MEGATRON MODEL 10NB-LF 4 HOT & COLD INLETS 4 MIXED OUTLET 2 RETURN PIPING

ECO-MIX COMPLETE WATER TEMPERATURE CONTROL STATION

SEISCO SUPERCHARGER EXTENDER/BOOSTER INSTALLATION GUIDE & OWNERS MANUAL

SAN RAPHAEL PRESSURE LITE VITREOUS CHINA SIPHON JET TOILET

Submittal S-NV-200-LF-M DIGITAL TEMPERATURE CONTROL STATION. Valve assembly is ASSE 1017 Certified. Valve assembly is cupc Certified

TRU-TEMP VALVE. Tru-Temp Pressure Balance 1/2" Rough-In Valve Owner's Manual 3001-RIV-PB-ORB 3001-RIV-PB-BN 3001-RIV-PB-CH 3003-RIV-PB-ORB

Installation, Operation, and Maintenance Manual

Instruction Manual. Cheese Warmer with Pump

installation, operation & Maintenance manual Floor-mounted Induction units

INTERMEDIATE GUIDE BRACKET

ECO-MIX COMPLETE WATER TEMPERATURE CONTROL STATION

Series 1140 and 1141 Temperature Regulators

Installation Manual. Models 99168, 99169, 99170

Installation S IMPORTANT! Bradley Thermostatic Mixing Valve for Individual Showers. Table of Contents

SEABREEZE. SeaBreeze Rain Shower System Model #1086-CH Owner's Manual

Installation Instructions / Warranty

TUB AND SHOWER FAUCET

Model TWBS.SHE Tempered Water Blending System

Installation & Operation Manual Models: SSS031, SSS041, SSS051, SSS081, & SSS119

installation, operation & Maintenance manual acb ceiling-mounted cassette models

TMV45 & TMV80 Standard Thermostatic Mixing Valves

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

Installation Instructions / Warranty. Starck 10111XX XX XX1

INSTALLATION INSTRUCTIONS

Models: FM FM WARNING

INSTRUCTION MANUAL HS-229G

A910.8A Remote Water Chiller, 8 GPH A A / A A-220V TECHNICAL ASSISTANCE TOLL FREE TELEPHONE NUMBER:

INSTRUCTION MANUAL. Keep this manual in a safe place for future reference TEMPERATURE CONTROL STEAM TRAP LEX3N-TZ LEX3N-TZ.

Storage Tanks. Instruction Manual. To the Installer: Please attach these instructions next to the water heater.

Electric Mini Tank Water Heaters ME10 ME25 ME40 ME60

BARRINGTON PRESSURE LITE VITREOUS CHINA SIPHON JET TOILET K-4327

Transcription:

ASSE 1017 INSTALLATION ADJUSTMENT SERVICE TYPE TM-15, TM-20* (As furnished with models TM-554, TM-356, TM-356-W/HA Valve is ASSE 1017 listed *Valve is CUPC listed IMPORTANT! Provide valve serial number when ordering parts!! TM15 serial # starting with TM1513839 TM20 serial # starting with TM2039272 BULLETIN P-15A March, 2012 OUTLET HOT INLET COLD INLET 1 1/2" 7" 7" INSTALLATION 1. Valve should be installed at a location where it 3. A shutoff valve must be installed on the outlet can easily be cleaned, adjusted or repaired. pipe. Type TM valves do not have a built-in 2. The inlets are clearly marked on the valve body shutoff. casting. Connect the hot water into the inlet 4. Use solder or pipe cement sparingly. Supply pipes marked "H" and cold water into the inlet marked should be flushed before the valve is connected. "C." Flush outlet pipe and valve as soon as it is connected. Maximum Operating Pressure 125PSI (860 KPA) for Hot and Cold Water. CAUTION All thermostatic water-mixing valves have limitations. They will not provide the desired accuracy outside of their flow capacity range. Consult the capacity chart on page 6. Minimum flow must be no less than as shown. REMEMBER! THIS IS A CONTROL DEVICE WHICH MUST BE CLEANED AND MAINTAINED ON A REGULAR BASIS (SEE MAINTENANCE GUIDE AND RECORD MGR-1000). 1360 Elmwood Avenue, Cranston, RI 02910 USA Phone: 401.461.1200 Fax: 401.941.5310 Email: info@leonardvalve.com Web Site: http://www.leonardvalve.com

1017 ASSE Leonard Type TM Thermostatic Water Mixing Valves are simple in design and may be easily cleaned, adjusted and repaired. If the installation is accessible, servicing may be completed without disconnecting the valve. POINTER SCREW POINTER STOP TO RESET ADJUSTABLE HIGH TEMPERATURE LIMIT STOP: HOT LTR SET SCREW COLD ADJUSTMENT AND SERVICE FINE ADJUSTMENT SCREW WEB (REST STOP AGAINST SCREW) 1. Loosen LTR SET SCREW, remove POINTER SCREW. 2. Adjust POINTER to maximum desired temperature. 3. Remove POINTER, replace POINTER on spline rod with STOP (which is cast into the underside on the pointer), resting against the BOTTOM side of the WEB on the FINE ADJUSTMENT SCREW. 4. If fine adjustment is needed, adjust FINE ADJUSTMENT SCREW on the cover, loosen for hotter or tighten for cooler temperature. 5. Replace POINTER and check temperature, if set to desired temperature replace POINTER SCREW, and tighten LTR SET SCREW. 6. The new maximum temperature has now been set. Test this temperature by holding a thermometer under the flow of water to be certain it is as desired. * LIMIT STOP MUST BE RESET AND RECHECKED EACH TIME HANDLE IS REMOVED. PACKINGS & S THERMOSTAT GROUP CHECKSTOPS TROUBLESHOOTING INSTRUCTIONS 1. Leak at pointer rod. 2. Leak between valve cover and base. 3. Valve delivers either all hot or all cold water, or will not mix consistently. 4. After cleaning or replacing port sleeve assembly, valve will not hold temperature. 5. Hot water bypass into cold line. 6. Supplies cannot be shut off completely. 7. Leak at checkstop bonnet. NOTE: Thermostatic Water Mixing Valves are REGULATING mechanisms, which must be regularly maintained to provide best performance. Frequency of cleaning depends on quality of local water conditions and usage. (See Maintenance Guide and Record MGR-1000). WARNING WARNING! This Thermostatic Mixing Valve has an adjustable high temperature limit stop which must be checked. If temperature is too high, the installer MUST RESET stop immediately. Always check the temperature of the mixed water when the lever handle is turned to full HOT. Excessively hot water is DANGEROUS AND MAY CAUSE SCALDING! The high temperature limit stop is factory set at approximately 120 F (49 C) with an incoming hot water supply temperatureof 150 F (65 C). If the incomingi hot water on the job is higher than 150 F, the valve when turned to full hot will deliver water in excess of 120 F and the high temperature limit stop MUST BE RESET BY THE INSTALLER. PARTS REQUIRED: REPAIR KIT 1/M20 (PACKINGS & S) REPAIR KIT R/M20 (REBUILDING KIT) OR M20-1-8B BRIDGE REPAIR KIT R/M20 (REBUILDING KIT) OR M20-G2 THERMOSTAT GROUP REPAIR KIT#4/M20 (CHECKSTOP KIT) SEE PAGE 5 FOR COMPLETE PARTS BREAKDOWN, PARTS KITS *Check for significant variations in outlet flow. Thermostatic valves will NOT provide the desired accuracy outside of their flow capacity range. Minimum flows must be no less than shown (see Flow Capacities, page 6). If installed on a circulated hot water system, make certain the valve is piped according to Leonard Required Methods of Piping (see page 3). REMEMBER! THIS IS A CONTROL DEVICE WHICH MUST BE CLEANED AND MAINTAINED ON A REGULAR BASIS. (SEE MAINTENANCE GUIDE AND RECORD, MGR-1000). 2

AS SE 1017 ASSE 1017 C F REQUIRED METHODS OF PIPING TM VALVES (RECIRCULATED HOT WATER SYSTEMS) VOLUME CONTROL AND SHUTOFF TEMPERED WATER TO FIXTURES CHECKSTOPS ON INLETS HOT SUPPLY COLD SUPPLY CIRCULATE HOT WATER FROM END OF LINE BACK TO TANK METHOD #1 Required when hot water in the 140 F (60 C) range is to be circulated to a master mixer or individual thermostatic mixing valves which are a substantial distance from the hot water source. It is used primarily in a building with several risers, with tempered water in each riser controlled by a separate master mixer. NOTE: The engineer must determine maximum distance which can be run, i.e. maximum allowable time for hot water to reach user with one shower head operating, based upon code requirements and/or good practice. (THIS PIPING IS NOT TO BE USED FOR AN ENTIRE BUILDING!) HOT WATER SOURCE THERMOMETER FROM HOT WATER SOURCE TRAP CHECK VALVE * BALL VALVE TO BALANCE SYSTEM FIXTURES VOLUME CONTROL AND SHUTOFF CIRCULATOR C CHECK VALVE 1/2" BY-PASS OF TEMPERED WATER PIPED TO BY-PASS INLET COLD SUPPLY INTO BUILDING FOR VALVES PIPED IN SERIES, THIS RETURN LINE MUST * BE TIED INTO THE OUTLET OF THE FIRST MIXING VALVE WHICH IS SUPPLYING THE SECOND MIXING VALVE. AQUASTAT T METHOD #2 Required when tempered water in the 120 F (49 C) range is to be circulated through the entire building, to maintain tempered water at each fixture. The function of the 1/2" by-pass is to allow the recirculated water to pass through the mixing valve during periods of no draw without entering the hot water source to avoid being reheated. The ball valve allows the system to be properly balanced. The secondary by-pass loop helps reduce the buildup of undesirable hot water in the primary system, and MUST NOT be omitted. See set-up instructions below. (THIS PIPING IS NOT TO BE USED FOR MORE THAN ONE BUILDING!) METHOD #2 SET-UP INSTRUCTIONS Before any attempt is made to adjust this system, be sure the temperature of the hot water at the source is properly set and maintained. 1. Be sure system is piped in accordance with Method #2. 2. Open enough showers/lavs to cover the minimum requirements of the mixing valve installed (see Flow Capacities, page 6). Note: The minimum flow requirements apply only to the mixing valve and not to the flow of the circulator. 3. Set mixing valve to the desired temperature, (note Warning Tag attached to the pointer of the valve). 4. Shut off all showers. Note: At this point, be sure NO water is being drawn through any fixture until the temperature in the recirculated line has been set. 5. Open the ball valve approximately 1/2 way and start the circulator. 6. Observe the temperature until it stabilizes. 7. Close the ball valve slightly if the temperature is too hot, or open if it is too cold and again let the temperature stabilize. Repeat until the desired recirculated temperature is set. Open the ball valve approximately 1/2 way and start the circulator. WARNING: THIS PIPING METHOD WILL NOT PERFORM EFFECTIVELY IF THE VALVE IS OVERSIZED. MINIMUM FLOWS ARE SHOWN ON FLOW CAPACITIES CHART, PAGE 6. FOR ESTIMATING MAXIMUM HOT WATER DEMAND, CONSULT LEONARD CASPAK PLUS SIZING PROGRAM. DO NOT CONFUSE THE MINIMUM FLOW REQUIREMENTS OF THE MIXING VALVE WITH PROPER SIZING OF THE CIRCULATOR. 3

INSTRUCTIONS FOR DISMANTLING VALVE (DWG. 1) 1. Loosen LTR set screw, remove pointer screw (handle)(7628). Shut off hot and cold supplies to valve (use screwdriver to shut checkstops). 2. Remove four Cover Screws M20-2C release entire thermostatic control assembly. (M20-1-12B) 1. M20-2C SCREWS WHEN RE-ASSEMBLING VALVE, insert Cover Gasket in base. Lubricate O'Rings before re-inserting assembly. After installing new parts, it will be necessary to reset high temperature limit. See instructions "TO RESET ADJUSTABLE HIGH TEMPERATURE LIMIT STOP" (page 2). TO REMOVE BRIDGE (DWG. 2) Remove MU-10B Pointer Rod Nut, remove M20-1-8B Bridge Assembly from pointer rod. Improper blending of the water may be caused by a sticking condition in the M20-G1 Port Sleeve Assembly. The Thimble should slide freely on the Port Sleeve. Clean with a NON-CORROSIVE CLEANING AGENT AND SOFT CLOTH. DO NOT USE ABRASIVES, then wash parts thoroughly. To reassemble, replace Bridge Assembly on pointer rod. M20-14B Driving stud MUST engage in thimble and hole in coil bracket. Replace pointer rod nut. DO NOT apply grease or lubricants to the M20-G1 Port Sleeve Assembly. TO DISASSEMBLE BRIDGE (DWG. 3) Remove M20-5B Holder Nuts using a screwdriver in the slots provided. Clean or replace M20-G1 Port Sleeve Assembly following instructions above. When reassembling, check M20-3B port sleeve packings and replace if necessary. MU-10B POINTER ROD NUT M20-1C(RF)(CP) MU-4C GLAND PACKING (2 REQD) 57-D RF GLAND NUT 2. HOLDER NUT O'RING THIMBLE PORT SLEEVE 3. M20-1-8B BRIDGE ASSY M20-14B DRIVING STUD M20-5B P.S. HOLDER NUT HOLDER NUT O'RING M20-1B BRIDGE COIL BRACKET MU-10B POINTER ROD NUT M20-4B P.S. HOLDER M20-G1 M20-3B P.S. PACKING M20-14B DRIVING STUD THIMBLE M20-G2 THERMOSTAT GROUP R DURA-trol TO CLEAN OR REPLACE THERMOSTAT GROUP Remove stop retaining ring and stop. Loosen gland nut. Push rod through cover. BE CAREFUL NOT TO PULL THERMOSTAT COIL OUT OF SHAPE. To clean, if a deposit has collected on the thermostat group, brush in a noncorrosive cleaning solution. Rinse in clean water and replace in cover with parts as shown. NOTE: AFTER INSTALLING NEW PARTS IT WILL BE NECESSARY TO RESET THE ADJUSTABLE HIGH TEMPERATURE LIMIT STOP (SEE PAGE 2). 4. M20-1-12B To replace entire Thermostatic Control Assembly specify M20-1-12B REMEMBER: THIS IS A CONTROL DEVICE WHICH MUST BE CLEANED ON A REGULAR BASIS (SEE MAINTENANCE GUIDE AND RECORD, MGR-1000). 4

TM-15/20 VALVE PARTS 7520 POINTER SCREW 6910 LTR SET SCREW 57-D(RF) GLAND NUT M20-1C(RF)(CP) M20-2C SCREWS 7628 POINTER M-20-1-8B BRIDGE MU-4C GLAND PACKING M20-5B P.S. HOLDER NUT HOLDER NUT O'RING M20-1B BRIDGE M20-G2 THERMOSTAT GROUP R DURA-trol MU-10B POINTER ROD NUT M20-4B P.S. HOLDER M20-G1 M20-3B P.S. PACKING M20-14B DRIVING STUD CHECKSTOP PARTS REPAIR KITS CHECKSTOPS M20-3A BONNET PACKING M20-9A CHECK SPRING M20-6A LOWER STEM & PACKING MU-4A UPPER STEM AND PACKING MU-5A UPPER STEM PKG. M20-2A RF/CP CHECK BONNET REPAIR KIT 1/M20 PACKINGS & S MU-4C GLAND PKG. M20-3A BONNET PKG. M20-9A SPRING M20-6A LOWER STEM & PKG. HOLDER NUT O'RING REPAIR KIT R/M20 REBUILDING KIT MU-5A O'RING REMEMBER! THIS IS A CONTROL DEVICE WHICH MUST BE CLEANED AND MAINTAINED ON A REGULAR BASIS (SEE MAINTENANCE GUIDE AND RECORD, MGR-1000). NOTE: AFTER INSTALLING NEW PARTS IT WILL BE NECESSARY TO RESET THE ADJUSTABLE HIGH TEMPERATURE LIMIT STOP ON EACH VALVE (SEE PAGE 2). REPAIR KIT 4/M20 REBUILDING KIT 2 EACH: M20-6A LOWER STEM & PACKING MU-5A UPPER STEM O'RING M20-9A SPRING M20-1-12B THERMOSTATIC CONTROL M20-3A BONNET PKG. REPAIR KIT 2/M20 KIT M20-3B P.S. PACKING M20-G1 PORT SLEEVE ASSY. HOLDER NUT 0'RING 7

FLOW CAPACITIES CAUTION! All thermostatic water mixing valves have limitations. They will not provide the desired accuracy outside of their flow capacity range. Consult the capacity chart and DO NOT OVERSIZE. Minimum flow must be no less than shown below. 57 57 REMEMBER! THIS IS A CONTROL DEVICE WHICH MUST BE CLEANED AND MAINTAINED ON A REGULAR BASIS. (SEE MAINTENANCE GUIDE AND RECORD MGR-1000) LIMITED WARRANTY Leonard Valve Company (hereinafter, Leonard ) warrants the original purchaser that products manufactured by Leonard will be free from defects in material or workmanship under normal conditions of use, when properly installed and maintained in accordance with Leonard s instructions, for a period of one year from the date of shipment. During this period, Leonard will at its option repair or replace any product, or part thereof, which shall be returned, freight prepaid, to the Leonard factory and determined by Leonard to be defective in materials or workmanship. Leonard provides no warranty, express or implied, which extends beyond the description contained herein. LEONARD SPECIFICALLY DISCLAIMS ANY AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY OR OF FITNESS FOR A PARTICULAR PURPOSE. Nonetheless, some jurisdictions may not allow the disclaimer of certain implied warranties, in which case Leonard hereby limits such implied warranties to the duration of the limited warranty period contained herein. Some jurisdictions may not allow limitations on how long an implied warranty lasts, so the foregoing durational limitation may not apply to you. In no event will Leonard be liable for labor or incidental or consequential damages. Any alteration or improper installation or use of this product will void this limited warranty. If any provision of this limited warranty is prohibited by law in the applicable jurisdiction, such provision shall be nulland void, but the remainder of this limited warranty shall continue in full force and effect. 2012 Leonard Valve Company Printed in USA 1360 Elmwood Avenue, Cranston, RI 02910 USA Phone: 401.461.1200 Fax: 401.941.5310 Email: info@leonardvalve.com Web Site: http://www.leonardvalve.com