SELF CONTAINED HORIZONTAL UNITS WATER COOLED CONDENSER (COAXIAL REFRIGERANT-WATER HEAT EXCHANGER ) HEAT PUMP. WCHBZ COOLING ONLY. WCHZ SERIES: WCHBZ - Heat Pump MODELS: 201, 251, 271, 351, 401, 501 COOLING CAPACITIES from 6,0 kw to 16,5 kw SERIES: WCHZ - Cooling only MODELS: 201, 251, 271, 351, 401, 501, 701, 721, 751 COOLING CAPACITIES from 6,4 kw to 25,1 kw
CATALOGUES SUMMARY - WCHBZ Pages 3-18 - WCHZ Pages 19-42
WATER TO AIR HEAT PUMPS TUBE IN TUBE COAXIAL HEAT EXCHANGER WCHBZ SERIES. WATER TO AIR HEAT PUMPS (TUBE IN TUBE COAXIAL HEAT EXCHANGER) SERIES: WCHBZ MODELS: 201, 251, 351, 401, 501 COOLING CAPACITIES OF: 6,0 TO 16,0 kw 01.09 Ref. 88323 (En) Rev. 103 1
WATER TO AIR HEAT PUMPS TUBE IN TUBE COAXIAL HEAT EXCHANGER WCHBZ SERIES. 2 01.09 Ref. 88323 (En) Rev. 103
WATER TO AIR HEAT PUMPS TUBE IN TUBE COAXIAL HEAT EXCHANGER WCHBZ SERIES. CONTENTS Page Description...4 Construction. Dimensions...5, 6 Technical Specifications...7 Cooling capacities...8, 9 Heating capacities... 10 Water volumes...11 to 13 Water pressure drop... 13 Airflows. Static pressures...14 Accessories...15, 16 01.09 Ref. 88323 (En) Rev. 103 3
WATER TO AIR HEAT PUMPS TUBE IN TUBE COAXIAL HEAT EXCHANGER WCHBZ SERIES. DESCRIPTION General The WCHBZ series are packaged horizontal ductable, water to air heat pumps, with coaxial tube in tube all copper water/ refrigerant exchanger. Suitable to be fitted to an air duct distribution system. Units are delivered totally finished after a complete final run test, ready to be installed (air distribution, duct system, electric supply, control system, water supply, drain). Units are supplied with R407c refrigerant operating charge. Design and lay-out provide great versatility for any installation as well as easy access for future maintenance. Application mostly for shopping malls. Cabinet Made of high quality galvanized steel plate, finished with electrostatically applied and oven-polymerized polyester powder for optimum resistance against corrosion. The assembly is internally lined with thermo-acoustic insulation. Refrigerant Circuit Made of high grade refrigerant copper tubing, clean and dehydrated. Schrader Valves on high and low sides. Filter drier suction accumulator, reversing valve, etc. Brazing is made with silver alloy under inert atmosphere. Compressors Hermetic, reciprocating. Compressors incorporate internal inherent protection, oil charge and crankcase heater. All compressors are mounted on the unit base on vibration eliminators. Indoor coil Made of aluminium fins and 3/8 seamless copper tubing, mechanically expanded. Water / refrigerant heat exchanger Tube in tube type (co-axial), all copper, counterflow, water refrigerant heat exchanger. Fans Centrifugal fan that allows for air distribution duct system. Up to model 401 are direct drive motor (230.1.50). Model 501 incorporates a 230/400V.3.50 motor. Transmission is made through pulleys and belt for airflow, static pressure regulation. Fans are of reduced sound level, incorporated pre-lubricated bearings and are statically and dynamically balanced. Expansion Device Calibrated capillaries up to model 401. Restrictor (calibrated piston) on model 501. Air filter Made of polyurethane foam, washable. Fire class M1. Operation and control - Room thermostat. - Contactors for compressor and fan motor. - Overloads for three-phase fan motor. - High pressure switch (manual reset) and low pressure switch (automatic reset). - Terminal block for supply and controller Options - Electric heaters - Water regulating valve - Compressor jacket - Etc. Electric Supply Models 201 and 251: 230V 1Ph and 400V 3Ph 50Hz Models 351, 401 and 501: 400V. 3Ph. +N, 50Hz Some models available at 230V 3Ph 50 (to be consulted) OPERATION LIMITS COOLING Water inlet Indoor Air temperature Dry Bulb Wet Bulb Standard 30 C 27 C 19 C Minimum 15 C 21 C 15 C Maximum 40 C 32 C 23 C HEATING Water inlet Indoor Air temperature Dry Bulb Wet Bulb Standard 16 C 20 C Minimum 10 C 20 C Maximum 24 C 26 C 4 01.09 Ref. 88323 (En) Rev. 103
WATER TO AIR HEAT PUMPS TUBE IN TUBE COAXIAL HEAT EXCHANGER WCHBZ SERIES. DIMENSIONS. CONSTRUCTION MOD. 201, 251, 351, 401 J L F G Detail A I K C D E 10 11 12 H 2 3 2 8 1 7 A B 9 4 5 Detail A Water outlet Water inlet Water inlet M N O P Q R S CONSTRUCTION DETAILS 1. Electric panel 2. 3/4" Drainage (male) 3. Air filter 4. Fan motor 5. Fan 6. Electric heater (optional) 7. Indoor coil 8. Water refrigerant heat exchanger 9. Compressor 10. Power supply 11. Water outlet 12. Water inlet 6 DIMENSIONS (mm) MODEL A B C D E F G H I J K L M N O P Q R S 201 657 1080 484 430 25 552 40 617 264 234 82 140 50 50 60 80 75 70 70 251, 351 750 1200 484 430 25 615 40 678 264 302 82 170 70 44 60 75 80 67 40 401 850 1280 542 488 25 670 60 756 291 333 87 133 98 44 60 120 110 50 40 WATER CONNECTIONS MODEL 201 251 351 401 Size (male) 1/2" 1/2" 1/2" 3/4" APPROXIMATE WEIGHT (kg) MODEL 201 251 351 401 Net weight 104 130 130 160 Packed weight 121 148 148 180 01.09 Ref. 88323 (En) Rev. 103 5
WATER TO AIR HEAT PUMPS TUBE IN TUBE COAXIAL HEAT EXCHANGER WCHBZ SERIES. DIMENSIONS. CONSTRUCTION MOD. 501 Detail A Detail A Water outlet Water outlet Water inlet WATER CONNECTIONS MODEL 501 Size (male) 3/4" APPROXIMATE WEIGHT (kg) MODEL 501 Net weight 166 Packed weight 186 CONSTRUCTION DETAILS 1. Water refrigerant heat exchanger 2. Electric panel 3. Indoor coil 4. Electric heater (option) 5. Fan 6. Fan motor 7. Compressor 8. 3/4" drainage (male) 9. Air filter 10. 3/4 drainage (male) 11. Water outlet (male) 12. Water inlet (male) 13. Power supply 6 01.09 Ref. 88323 (En) Rev. 103
WATER TO AIR HEAT PUMPS TUBE IN TUBE COAXIAL HEAT EXCHANGER WCHBZ SERIES. TECHNICAL SPECIFICATIONS MODEL WCHBZ 201 251 351 401 501 Cooling capacity kw 6,0 8,1 11,1 13,0 16,5 Heating capacity kw 6,9 9,1 12,6 16,0 19,6 COMPRESSOR Type Reciprocating Voltage (50Hz~) V 230.I 230.I 400.III 230.I 230.III 400.III 230.III 400.III 230.III 400.III Input power (Cooling) kw 1,62 2,12 2,73 3,48 4,24 Input current (Cooling) A 8,3 10,8 3,6 13,9 8,1 4,6 10,3 5,9 12,5 7,2 Input power (Heating) kw 1,37 1,73 2,32 3,08 4,04 Input current (Heating) A 7,0 8,8 2,9 11,9 6,9 3,9 9,1 5,2 11,9 6,9 INDOOR COIL Type Copper tubing coil and aluminium fins Front face area m 3 0,188 0,252 0,252 0,252 0,350 Fin spacing - tube Ø mm - (") 2,1 3/8 2,1 3/8 2,1 3/8 2,1 3/8 2,1 3/8 WATER-REFRIGERANT HEAT EXCHANGER Type Tube in tube, co-axial, all copper Water connections (") 1/2 1/2 1/2 3/4 3/4 INDOOR FAN Type Centrifugal Model 9/7 DD 9/9 DD 9/9 DD 10/10 DD 10/10 SS Motor power kw 0,125 0,125 0,250 0,250 0,550 Voltage (50Hz~) V 230.I 230.III 400.III Input current A 1,2 1,2 2,3 2,3 2,8 1,7 REFRIGERANT R407C - operating charge kg 1,30 1,50 1,60 1,70 2,75 GENERAL SPECIFICATIONS FOR ELECTRIC INSTALLATION Voltage (50Hz~) V 230.I 230.I 400.III 230.I 230.III 400.III 230.III 400.III 230.III 400.III Total input power (Cooling) (1) kw 1,90 2,60 3,50 4,25 5,10 Total Input current (Cooling) (1) A 9,7 13,3 4,4 17,9 10,3 6,0 12,6 7,2 15,1 8,7 Max. Input power (Cooling) (2) kw 2,27 3,11 4,19 5,08 6,10 Max. Input current (Cooling) (2) A 11,6 15,9 5,3 21,4 12,4 7,1 15,0 8,6 18,0 10,4 Total Input power (Heating) (3) kw 18,0 2,50 3,30 4,15 4,95 Total Input current (Heating) (3) A 19,2 12,8 4,3 16,9 9,8 5,6 12,3 7,1 14,6 8,4 Max. Input Power (Heating) (4) kw 2,02 2,81 3,70 4,66 5,55 Max Input current (Heating) (4) A 10,3 14,4 4,8 18,9 10,9 6,3 13,8 7,9 16,4 9,4 Starting current A 58 78 39 106 51 48 105 64 131 70 SOUND PRESSURE LEVEL (at 2 meters) Unit db (A) 62 64 64 64 65 (1) COOLING (Standard): condensing temperature 40ºC; 27ºC/19ºC DB/WB indoor air. (2) COOLING (Maximum): Condensing temperature 50ºC; 31ºC/21ºC DB/ WB indoor air. (3) HEATING (Standard): Entering water temperature 16ºC; indoor air temperature 21ºC. (4) HEATING (Maximum): Entering water temperature to condenser 24ºC; indoor air temperature 26ºC. 01.09 Ref. 88323 (En) Rev. 103 7
WATER TO AIR HEAT PUMPS TUBE IN TUBE COAXIAL HEAT EXCHANGER WCHBZ SERIES. COOLING CAPACITIES Model WCHBZ201 WCHBZ251 WCHBZ351 Evap. Airflow l/s 417 555 639 Condensing temp. C 35 40 45 50 35 40 45 50 35 40 45 50 INDOOR AIR. ENTERING WET BULB TEMPerature 15 C Total capacity kw 5,35 5,13 4,89 4,65 7,22 6,93 6,61 6,27 9,90 9,50 9,05 8,60 Power input kw 1,66 1,82 1,99 2,16 2,28 2,49 2,72 2,96 3,06 3,36 3,66 3,98 Sensible 19 C 3,83 3,68 3,54 3,39 5,17 4,97 4,78 4,58 7,09 6,81 6,55 6,27 Capacity E.D.B.T. 21 C 4,40 4,24 4,09 3,95 5,93 5,72 5,53 5,33 8,13 7,84 7,57 7,30 kw 23 C 4,96 4,81 4,66 4,52 6,69 6,49 6,30 6,10 9,17 8,90 8,63 8,36 25 C 5,35 5,13 4,89 4,65 7,22 6,93 6,61 6,27 9,90 9,50 9,05 8,60 INDOOR AIR. ENTERING WET BULB TEMPerature 17 C Total capacity kw 5,79 5,57 5,33 5,08 7,82 7,52 7,20 6,86 10,71 10,31 9,86 9,41 Power input kw 1,70 1,86 2,02 2,20 2,33 2,55 2,77 3,01 3,13 3,43 3,73 4,05 Sensible 21 C 3,83 3,68 3,53 3,38 5,16 4,96 4,76 4,57 7,08 6,80 6,52 6,26 Capacity E.D.B.T. 23 C 4,39 4,24 4,09 3,95 5,93 5,72 5,52 5,33 8,12 7,84 7,57 7,30 kw 25 C 4,95 4,80 4,65 4,51 6,68 6,48 6,28 6,09 9,16 8,88 8,61 8,35 27 C 5,52 5,37 5,22 5,08 7,45 7,25 7,04 6,86 10,21 9,93 9,65 9,40 INDOOR AIR. ENTERING WET BULB TEMPerature 19 C Total capacity kw 6,22 6,00 5,77 5,52 8,40 8,10 7,79 7,45 11,51 11,10 10,67 10,21 Power input kw 1,75 1,90 2,06 2,24 2,40 2,60 2,82 3,06 3,22 3,50 3,80 4,12 Sensible 23 C 3,82 3,67 3,52 3,38 5,16 4,96 4,76 4,57 7,07 6,80 6,52 6,26 Capacity E.D.B.T. 25 C 4,38 4,24 4,09 3,95 5,92 5,72 5,52 5,33 8,11 7,84 7,57 7,30 kw 27 C 4,95 4,80 4,65 4,51 6,68 6,48 6,28 6,09 9,15 8,88 8,60 8,34 29 C 5,52 5,37 5,22 5,08 7,45 7,25 7,05 6,86 10,21 9,93 9,66 9,39 INDOOR AIR. ENTERING WET BULB TEMPerature 21 C Total capacity kw 6,66 6,44 6,21 5,95 8,99 8,69 8,38 8,03 12,32 11,91 11,48 11,00 Power input kw 1,79 1,94 2,10 2,27 2,45 2,65 2,87 3,11 3,30 3,57 3,86 4,19 Sensible 25 C 3,79 3,65 3,50 3,36 5,12 4,92 4,73 4,54 7,02 6,75 6,48 6,22 Capacity E.D.B.T. 27 C 4,38 4,23 4,08 3,94 5,91 5,71 5,51 5,32 8,10 7,82 7,54 7,28 kw 29 C 4,94 4,79 4,64 4,50 6,66 6,47 6,26 6,07 9,13 8,86 8,58 8,32 31 C 5,51 5,36 5,21 5,07 7,44 7,24 7,03 6,84 10,19 9,91 9,64 9,38 NOTES: 1. Capacities are net after deduction of indoor fan motor heat. 2. E.D.B.T. Indoor air. Entering dry bulb temperature. CORRECTION FACTORS % Airflow 80 90 110 120 Total Heat 0,95 0,97 1,03 1,05 Sensible Heat 0,92 0,96 1,04 1,08 Input power 0,96 0,98 1,02 1,03 8 01.09 Ref. 88323 (En) Rev. 103
WATER TO AIR HEAT PUMPS TUBE IN TUBE COAXIAL HEAT EXCHANGER WCHBZ SERIES. COOLING CAPACITIES Model WCHBZ401 WCHBZ501 Evap. Airflow l/s 666 972 Condensing temperature C 35 40 45 50 35 40 45 50 INDOOR AIR. ENTERING WET BULB TEMPerature 15 C Total capacity kw 11,60 11,12 10,60 10,07 14,72 14,11 13,46 12,78 Power input kw 3,72 4,08 4,44 4,83 4,46 4,89 5,33 5,80 Sensible 19 C 8,30 7,98 7,67 7,35 10,54 10,13 9,73 9,32 Capacity E.D.B.T. 21 C 9,52 9,18 8,87 8,55 12,09 11,66 11,26 10,85 kw 23 C 10,74 10,42 10,11 9,80 13,63 13,23 12,83 12,43 25 C 11,60 11,12 10,60 10,07 14,72 14,11 13,46 12,78 INDOOR AIR. ENTERING WET BULB TEMPerature 17 C Total capacity kw 12,54 12,07 11,55 11,02 15,92 15,32 14,66 13,98 Power input kw 3,80 4,16 4,53 4,92 4,56 4,99 5,43 5,90 Sensible 19 C 8,29 7,96 7,64 7,33 10,52 10,11 9,70 9,30 Capacity E.D.B.T. 21 C 9,51 9,19 8,86 8,55 12,07 11,66 11,25 10,86 kw 23 C 10,73 10,40 10,08 9,78 13,62 13,21 12,79 12,41 25 C 11,96 11,63 11,30 11,00 15,18 14,77 14,34 13,97 INDOOR AIR. ENTERING WET BULB TEMPerature 19 C Total capacity kw 13,47 13,00 12,50 11,96 17,10 16,50 15,86 15,18 Power input kw 3,92 4,25 4,62 5,00 4,70 5,10 5,54 6,00 Sensible 19 C 8,28 7,96 7,64 7,33 10,51 10,10 9,69 9,30 Capacity E.D.B.T. 21 C 9,50 9,18 8,86 8,55 12,05 11,66 11,25 10,85 kw 23 C 10,72 10,40 10,08 9,77 13,61 13,20 12,79 12,40 25 C 11,95 11,63 11,31 11,00 15,17 14,77 14,36 13,96 INDOOR AIR. ENTERING WET BULB TEMPerature 21 C Total capacity kw 14,43 13,95 13,45 12,88 18,32 17,71 17,07 16,35 Power input kw 4,01 4,33 4,69 5,08 4,81 5,20 5,63 6,10 Sensible 19 C 8,22 7,90 7,59 7,28 10,43 10,03 9,64 9,24 Capacity E.D.B.T. 21 C 9,48 9,16 8,84 8,53 12,04 11,63 11,22 10,83 kw 23 C 10,69 10,38 10,05 9,75 13,57 13,17 12,76 12,37 25 C 11,93 11,61 11,29 10,98 15,15 14,74 14,33 13,94 NOTES: 1. Capacities are net after deduction of indoor fan motor heat. 2. E.D.B.T. Indoor air. Entering dry bulb temperature. CORRECTION FACTORS % Airflow 80 90 110 120 Total Heat 0,95 0,97 1,03 1,05 Sensible Heat 0,92 0,96 1,04 1,08 Input power 0,96 0,98 1,02 1,03 01.09 Ref. 88323 (En) Rev. 103 9
WATER TO AIR HEAT PUMPS TUBE IN TUBE COAXIAL HEAT EXCHANGER WCHBZ SERIES. HEATING CAPACITIES Indoor dry bulb ºC Water inlet temperature ºC 10 12 14 16 18 20 22 24 MOD. WCHBZ 201. INDOOR AIRFLOW 417 l/s. 18 Pot. kw 6,17 6,46 6,75 7,04 7,30 7,49 7,70 7,92 C.O.P. 3,85 3,91 3,97 4,03 4,07 4,11 4,14 4,18 21 Pot. kw 6,00 6,33 6,61 6,90 7,16 7,37 7,59 7,81 C.O.P. 3,64 3,71 3,78 3,83 3,88 3,92 3,95 3,99 24 Pot. kw 5,86 6,17 6,47 6,74 7,01 7,23 7,45 7,68 C.O.P. 3,42 3,49 3,55 3,63 3,68 3,72 3,76 3,80 MOD. WCHBZ 251. INDOOR AIRFLOW 555 l/s. 18 Pot. kw 8,14 8,53 8,90 9,28 9,62 9,88 10,16 10,45 C.O.P. 3,66 3,72 3,77 3,83 3,87 3,90 3,94 3,97 21 Pot. kw 7,92 8,34 8,72 9,10 9,45 9,72 10,01 10,29 C.O.P. 3,46 3,53 3,59 3,64 3,69 3,73 3,75 3,79 24 Pot. kw 7,73 8,14 8,53 8,88 9,24 9,53 9,82 10,13 C.O.P. 3,25 3,32 3,38 3,45 3,49 3,54 3,57 3,61 MOD. WCHBZ 351. INDOOR AIRFLOW 639 l/s. 18 Pot. kw 11,26 11,80 12,33 12,85 13,32 13,68 14,07 14,46 C.O.P. 3,84 3,90 3,96 4,02 4,06 4,10 4,13 4,17 21 Pot. kw 10,96 11,55 12,08 12,60 13,08 13,46 13,86 14,25 C.O.P. 3,63 3,70 3,77 3,82 3,87 3,91 3,94 3,98 24 Pot. kw 10,70 11,27 11,81 12,30 12,79 13,19 13,60 14,03 C.O.P. 3,41 3,48 3,54 3,62 3,67 3,71 3,75 3,79 MOD. WCHBZ 401. INDOOR AIRFLOW 666 l/s. 18 Pot. kw 14,30 14,99 15,65 16,32 16,92 17,37 17,87 18,37 C.O.P. 3,87 3,93 3,99 4,05 4,09 4,13 4,17 4,20 21 Pot. kw 13,92 14,67 15,33 16,00 16,61 17,10 17,60 18,10 C.O.P. 3,66 3,73 3,80 3,85 3,90 3,94 3,97 4,01 24 Pot. kw 13,59 14,31 15,00 15,62 16,25 16,75 17,27 17,82 C.O.P. 3,44 3,51 3,57 3,65 3,70 3,74 3,78 3,82 MOD. WCHBZ 501. INDOOR AIRFLOW 972 l/s. 18 Pot. kw 17,52 18,36 19,18 19,99 20,72 21,27 21,89 22,50 C.O.P. 3,98 4,04 4,11 4,17 4,21 4,25 4,28 4,32 21 Pot. kw 17,05 17,97 18,78 19,60 20,35 20,94 21,56 22,17 C.O.P. 3,77 3,84 3,90 3,96 4,01 4,05 4,08 4,12 24 Pot. kw 16,65 17,53 18,37 19,13 19,90 20,52 21,15 21,83 C.O.P. 3,54 3,61 3,67 3,75 3,80 3,85 3,89 3,93 NOTES: 1. Heat capacities and COP are for standard airflow and motor. For others, please use correction factor. Factors correction % Airflow 80 90 110 120 Capacity 0,95 0,98 1,02 1,04 COP 0,93 0,97 1,03 1,05 10 01.09 Ref. 88323 (En) Rev. 103
WATER TO AIR HEAT PUMPS TUBE IN TUBE COAXIAL HEAT EXCHANGER WCHBZ SERIES. WATER FLOWS Water inlet temperatura ºC 15 20 25 30 35 Model Condensing EWBT Cooling LWT WT LWT WT LWT WT LWT WT LWT WT Temp. ºC C Capacity C l/s C l/s C l/s C l/s C l/s 15 5,35 28,19 0,13 28,80 0,19 29,40 0,38 17 5,79 29,10 0,13 29,40 0,19 29,70 0,38 35 19 6,22 30,00 0,13 30,00 0,19 30,00 0,38 21 6,66 30,90 0,13 30,60 0,19 30,30 0,38 15 5,13 32,59 0,09 33,20 0,13 33,80 0,19 34,40 0,38 17 5,57 33,81 0,09 34,11 0,13 34,41 0,19 34,70 0,38 40 19 6,00 35,00 0,09 35,00 0,13 35,00 0,19 35,00 0,38 WCHBZ 21 6,44 36,22 0,09 35,91 0,13 35,61 0,19 35,30 0,38 201 15 4,89 36,97 0,07 37,57 0,09 38,18 0,12 38,79 0,19 39,39 0,37 17 5,33 38,47 0,07 38,77 0,09 39,08 0,12 39,39 0,19 39,69 0,37 45 19 5,77 40,00 0,07 40,00 0,09 40,00 0,12 40,00 0,19 40,00 0,37 21 6,21 41,53 0,07 41,23 0,09 40,92 0,12 40,61 0,19 40,31 0,37 15 4,65 41,33 0,06 41,94 0,07 42,55 0,09 43,16 0,12 43,78 0,19 17 5,08 43,14 0,06 43,45 0,07 43,76 0,09 44,07 0,12 44,38 0,19 50 19 5,52 45,00 0,06 45,00 0,07 45,00 0,09 45,00 0,12 45,00 0,19 21 5,95 46,78 0,06 46,48 0,07 46,19 0,09 45,89 0,12 45,59 0,19 15 7,22 28,19 0,17 28,80 0,26 29,40 0,52 17 7,82 29,10 0,17 29,40 0,26 29,70 0,52 35 19 8,40 30,00 0,17 30,00 0,26 30,00 0,52 21 8,99 30,89 0,17 30,59 0,26 30,30 0,52 15 6,93 32,61 0,13 33,21 0,17 33,80 0,26 34,40 0,51 17 7,52 33,82 0,13 34,12 0,17 34,41 0,26 34,71 0,51 40 19 8,10 35,00 0,13 35,00 0,17 35,00 0,26 35,00 0,51 WCHBZ 21 8,69 36,20 0,13 35,90 0,17 35,60 0,26 35,30 0,51 251 15 6,61 36,98 0,10 37,59 0,13 38,19 0,17 38,79 0,25 39,40 0,51 17 7,20 38,49 0,10 38,79 0,13 39,10 0,17 39,40 0,25 39,70 0,51 45 19 7,79 40,00 0,10 40,00 0,13 40,00 0,17 40,00 0,25 40,00 0,51 21 8,38 41,51 0,10 41,21 0,13 40,90 0,17 40,60 0,25 40,30 0,51 15 6,27 41,35 0,08 41,96 0,10 42,56 0,13 43,17 0,17 43,78 0,25 17 6,86 43,17 0,08 43,48 0,10 43,78 0,13 44,09 0,17 44,39 0,25 50 19 7,45 45,00 0,08 45,00 0,10 45,00 0,13 45,00 0,17 45,00 0,25 21 8,03 46,80 0,08 46,50 0,10 46,20 0,13 45,90 0,17 45,60 0,25 NOTES: EWBT: Entering wet bulb temperature ºC LWT: Water outlet temperature WT: Water flow (l/s) 01.09 Ref. 88323 (En) Rev. 103 11
WATER TO AIR HEAT PUMPS TUBE IN TUBE COAXIAL HEAT EXCHANGER WCHBZ SERIES. WATER FLOWS Water inlet temperatura ºC 15 20 25 30 35 Model Condensing EWBT Cooling LWT WT LWT WT LWT WT LWT WT LWT WT Temp. ºC C Capacity C l/s C l/s C l/s C l/s C l/s 35 15 9,90 28,20 0,23 28,80 0,35 29,40 0,70 17 10,71 29,09 0,23 29,40 0,35 29,70 0,70 19 11,51 30,00 0,23 30,00 0,35 30,00 0,70 21 12,32 30,91 0,23 30,60 0,35 30,30 0,70 40 15 9,50 32,62 0,17 33,21 0,23 33,81 0,35 34,40 0,70 17 10,31 33,82 0,17 34,12 0,23 34,41 0,35 34,71 0,70 19 11,10 35,00 0,17 35,00 0,23 35,00 0,35 35,00 0,70 WCHBZ 21 11,91 36,21 0,17 35,90 0,23 35,60 0,35 35,30 0,70 351 45 15 9,05 36,96 0,14 37,57 0,17 38,18 0,23 38,78 0,35 39,39 0,69 17 9,86 38,48 0,14 38,78 0,17 39,09 0,23 39,39 0,35 39,70 0,69 19 10,67 40,00 0,14 40,00 0,17 40,00 0,23 40,00 0,35 40,00 0,69 21 11,48 41,50 0,14 41,20 0,17 40,90 0,23 40,60 0,35 40,30 0,69 50 15 8,60 41,34 0,11 41,95 0,14 42,56 0,17 43,17 0,23 43,78 0,34 17 9,41 43,18 0,11 43,48 0,14 43,79 0,17 44,09 0,23 44,39 0,34 19 10,21 45,00 0,11 45,00 0,14 45,00 0,17 45,00 0,23 45,00 0,34 21 11,00 46,80 0,11 46,50 0,14 46,20 0,17 45,90 0,23 45,60 0,34 15 11,60 28,21 0,28 28,81 0,42 29,40 0,83 17 12,54 29,09 0,28 29,40 0,42 29,70 0,83 35 19 13,47 30,00 0,28 30,00 0,42 30,00 0,83 21 14,43 30,91 0,28 30,60 0,42 30,30 0,83 15 11,12 32,62 0,21 33,22 0,27 33,81 0,41 34,41 0,82 17 12,07 33,82 0,21 34,11 0,27 34,41 0,41 34,70 0,82 40 19 13,00 35,00 0,21 35,00 0,27 35,00 0,41 35,00 0,82 WCHBZ 21 13,95 36,19 0,21 35,90 0,27 35,60 0,41 35,30 0,82 401 15 10,60 36,96 0,16 37,57 0,20 38,18 0,27 38,79 0,41 39,39 0,82 17 11,55 38,48 0,16 38,79 0,20 39,09 0,27 39,39 0,41 39,70 0,82 45 19 12,50 40,00 0,16 40,00 0,20 40,00 0,27 40,00 0,41 40,00 0,82 21 13,45 41,49 0,16 41,19 0,20 40,89 0,27 40,60 0,41 40,30 0,82 15 10,07 41,36 0,14 41,96 0,16 42,57 0,20 43,18 0,27 43,79 0,41 17 11,02 43,20 0,14 43,50 0,16 43,80 0,20 44,10 0,27 44,40 0,41 50 19 11,96 45,00 0,14 45,00 0,16 45,00 0,20 45,00 0,27 45,00 0,41 21 12,88 46,77 0,14 46,47 0,16 46,18 0,20 45,88 0,27 45,59 0,41 NOTES: EWBT: Entering wet bulb temperature ºC LWT: Water outlet temperature WT: Water flow (l/s) 12 01.09 Ref. 88323 (En) Rev. 103
WATER TO AIR HEAT PUMPS TUBE IN TUBE COAXIAL HEAT EXCHANGER WCHBZ SERIES. WATER FLOWS Water inlet temperatura ºC 15 20 25 30 35 Model Condensing EWBT Cooling LWT WT LWT WT LWT WT LWT WT LWT WT Temp. ºC C Capacity C l/s C l/s C l/s C l/s C l/s 15 14,72 28,20 0,35 28,80 0,52 29,40 1,04 17 15,92 29,09 0,35 29,39 0,52 29,70 1,04 35 19 17,10 30,00 0,35 30,00 0,52 30,00 1,04 21 18,32 30,92 0,35 30,61 0,52 30,31 1,04 15 14,11 32,59 0,26 33,19 0,34 33,80 0,52 34,40 1,03 17 15,32 33,81 0,26 34,10 0,34 34,40 0,52 34,70 1,03 40 19 16,50 35,00 0,26 35,00 0,34 35,00 0,52 35,00 1,03 WCHBZ 21 17,71 36,21 0,26 35,91 0,34 35,61 0,52 35,30 1,03 501 15 13,46 36,95 0,20 37,56 0,26 38,17 0,34 38,78 0,51 39,39 1,02 17 14,66 38,47 0,20 38,78 0,26 39,08 0,34 39,39 0,51 39,69 1,02 45 19 15,86 40,00 0,20 40,00 0,26 40,00 0,34 40,00 0,51 40,00 1,02 21 17,07 41,52 0,20 41,21 0,26 40,91 0,34 40,61 0,51 40,30 1,02 15 5,80 41,32 0,17 41,93 0,20 42,54 0,25 43,16 0,34 38,77 0,51 17 13,98 43,16 0,17 43,47 0,20 43,77 0,25 44,08 0,34 44,39 0,51 50 19 15,18 45,00 0,17 45,00 0,20 45,00 0,25 45,00 0,34 45,00 0,51 21 16,35 46,80 0,17 46,50 0,20 46,20 0,25 45,90 0,34 45,60 0,51 NOTES: EWBT: Entering wet bulb temperature ºC LWT: Water outlet temperature WT: Water flow (l/s) PRESSURE DROP ON COAXIAL HEAT EXCHANGER (kpa) Water flow MODEL l/s 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 WCHBZ m 3 /h 0,4 0,7 1,1 1,4 1,8 2,2 2,5 2,9 3,2 3,6 4,0 4,3 4,7 201 2,5 5,8 10,5 18,5 24,0 33,0 251 2,5 5,8 10,5 18,5 24,0 33,0 351 1,5 2,5 4,0 8,0 11,0 15,0 20,0 26,0 32,0 401 1,5 2,5 4,0 8,0 11,0 15,0 20,0 26,0 32,0 501 2,0 3,7 7,0 8,5 12,0 16,0 21,0 25,0 28,0 33,0 37,5 42,0 01.09 Ref. 88323 (En) Rev. 103 13
WATER TO AIR HEAT PUMPS TUBE IN TUBE COAXIAL HEAT EXCHANGER WCHBZ SERIES. AIRFLOW STATIC PRESSURE MODEL WCHBz ADJ. PULLEY TURNS OPEN AIRFLOW m3/h 1100 1200 1300 1400 1500 1600 1700 201 l/s 306 333 361 389 417 444 472 (1500) Pa 125 110 95 80 58 30 0 W 220 225 230 238 250 260 280 m3/h 1600 1700 1800 1900 2000 2100 2200 2300 2400 251 l/s 444 472 500 528 555 583 611 639 666 (2000) Pa 85 80 74 65 55 40 24 10 0 W 370 373 376 379 383 388 404 412 420 m3/h 1900 2000 2100 2200 2300 2400 2500 2600 2700 351 l/s 528 555 583 611 639 666 694 722 750 (2300) Pa 130 121 110 100 86 75 58 40 23 W 435 441 448 455 462 468 477 483 492 m3/h 1850 2000 2150 2300 2400 2450 2600 2750 2900 401 l/s 514 555 597 639 666 680 722 764 778 (2400) Pa 147 136 120 105 94 86 64 41 20 W 392 406 420 439 450 455 474 495 515 501 (3500) 1 vuelta m3/h 2800 3000 3200 3400 3500 3600 3800 4000 4200 l/s 778 833 889 944 972 1000 1055 1111 1166 0 Pa 118 112 103 92 85 79 65 52 35 W 505 535 560 580 595 610 635 660 692 1 Pa 105 98 87 75 70 65 50 35 20 W 430 470 478 500 510 525 552 580 610 2 Pa 80 73 65 52 45 39 26 12 W 390 410 430 450 465 475 500 525 NOTES: Airflow m 3 /h or l/s; Static pressure: Pa 14 01.09 Ref. 88323 (En) Rev. 103
WATER TO AIR HEAT PUMPS TUBE IN TUBE COAXIAL HEAT EXCHANGER WCHBZ SERIES. ACCESSORIES ROOM THERMOSTAT All models include room thermostat to control equipment operation. Mod 201 through 501: One stage Cooling/one stage Heating. KLR-E Type Option: Room sensor and duct sensor, DSL type. C O N T H E A T F A N F A N A U T O C O O L 3 4 1 2 I O 1 5 1 0 2 5 5 3 0 C KLRE 7035 1. On/Off 2. Temp. selection 3. Ventilation 4. Cool/Heat Selection 1 2 5 DSL type (Option) 1. Mode. 2. Ventilation. 3. Temperature decrease. 4. Temperature increase. 5. Alternative setpoint. 3 4 ARIA CONTROLLER (Option) ARIA is a microprocessor electronic controller consisting of two elements: a terminal to be located in the room and a board located in the electric panel. Connection is made with only two wires. Parameters are configurated in the factory. BOARD Terminal max. 150 m LC Display MODE: cooling, heating, auto, fan, off FAN: selects fan operation, manual or auto SET: adjust of setpoints: comfort CLOCK: option with clock (programmable) RESUME: reset of alarms, etc Front buttons: allow for modification of setpoints Options - Remote sensor - Terminal with programmer clock Applications 1. STANDARD ALONE: one controller per unit 2. LAN: Local Area Network. To control up to 30 units. All information is centralized and controlled by means of a pco terminal. 3. Supervision & telemainenance 01.09 Ref. 88323 (En) Rev. 103 15
WATER TO AIR HEAT PUMPS TUBE IN TUBE COAXIAL HEAT EXCHANGER WCHBZ SERIES. ACCESSORIES ELECTRIC HEATERS Made of nickel-chrome wire, mounted in a frame, incorporating thermal protection, contactor and terminal boards. Inside a plenum, ready to be fitted on the air supply. 400 3 1 330 2 371 DETAILS 1. Contactor 2. Connection terminals 3. Thermal protector 250 440 120 MODEL 201-251 251-351 351-401 351-401 - 501 501 Power kw 4 6 7,5 9,0 12 Voltage (50Hz~) V 230.I 230.III 400.III 230.I 230.III 400.III 230.I 230.III 400.III 230.I 230.III 400.III 230.III 400.III Input current A 17,4 10 5,8 26 15,1 8,7 32,6 18,8 10,8 39,1 22,8 13,1 30,1 17,3 WATER REGULATING VALVE Two way, pressure actuated water regulating valve, allowing water to flow to the heat exchanger to provide correct refrigerant head pressures. On heating operation, maximum waterflow is required; therefore, regulating valve has to be bypassed by means of a Solenoid valve. MODEL 201 251 351 401 501 Quantity 1 1 1 1 1 Size (") 3/8 3/8 1/2 1/2 3/4 OTHER OPTIONS Clogged filter indication Smoke detector Compressor jacket Base support VARIATIONS ON STANDARD PRODUCTION (to be consulted) Precoated coils Uprated indoor fan Special filters Fault indications Other power supplies Inverted air supply & return Other possible variations on request (to be consulted) Specifications subject to change without previous notice. 01.09 Ref. 88323 (En) Rev. 103 D.L.: B-30.316-99 Gràfiques Ferpala s.l. Eduard Toldrà, 111 08800 01.09 Vilanova Ref. 88323 i la Geltrú (En) Tel. 93 Rev. 893 70 103 11 16
SELF CONTAINED HORIZONTAL AIR CONDITIONERS WATER COOLED CONDENSER (COAXIAL REFRIGERANT-WATER HEAT EXCHANGER) SERIES: WCHZ MODELS: 201, 251, 271, 351, 401, 501, 701, 721, 751 COOLING CAPACITIES OF: 6,4 TO 25,1 kw 1
2
CONTENTS Page Description... 4 Construction. Dimensions... 5 to 7 Technical Specifications... 8, 9 Cooling capacities... 10 to 12 Water volumes... 13 to 17 Pressure drops... 17 Airflow. Static pressure - Consumo motor...18, 19 Accessories... 20 to 22 Hitecsa Aire Acondicionado, S.L.Unipersonal 3
DESCRIPTION Description The WCHZ series are packaged horizontal ductable airconditioners with co-axial water cooled condenser, suitable to be fitted to an air duct distribution system. Units are delivered totally finished after a complete final run test, ready to be installed (air distribution duct, electric supply, control system, drain). Units contain an operation charge of R407c refrigerant. Design and lay-out provide great versatility for any installation as well as easy access for future maintenance. Cabinet Made of high quality galvanized steel plate, finished with electrostatically applied and oven-polymerized polyester powder for optimum resistance against corrosion. The assembly is internally lined with thermo-acoustic insulation. Refrigerant Circuit Made of copper tube, refrigeration quality, clean and dehydrated. Filter drier and Schrader Valves on high and low side are included. Brazing is made with silver alloy under inert atmosphere (nitrogen). Compressors Hermetic, reciprocating or Scroll depending upon models. Compressors incorporate internal inherent protection, oil charge and crankcase heater. All compressors are mounted on the unit base on vibration eliminators. Expansion Device Models up to 501 use a restrictor (piston with calibrated orifice). Rest of models use a thermostatic expansion valve. Air filter Made of polyurethane foam, washable. Fire class M1. Operation and control Room thermostat. Contactors for compressor and fan motor. Overloads for three-phase fan motor. High pressure switch (manual reset) and low pressure switch (automatic reset). Terminal block for supply and controller. Main switch. Options Electric heaters. Hot water heating coils. Water regulating valve. Compressor jacket. Etc. Electric Supply Models 201 to 351: 230V 1Ph 50 Hz~. Models 201 to 751: 400V. 3Ph. +N, 50 Hz~. Some models available at 230V 3Ph 50 (to be consulted). Evaporator coil Made of aluminium fins and 3/8 seamless copper tubing, mechanically expanded. Condenser Tube in tube type (co-axial), all copper, counterflow, water cooled. Fans Centrifugal fan that allows for air distribution duct system. Up to model 401 are direct drive motor (230.1.50). Rest of models incorporate a 230/400V.3.50 motor. Transmission is made through pulleys and belt for airflow, static pressure regulation. Fans are of reduced sound level, incorporate prelubricated bearings and are statically and dynamically balanced. OPERATION LIMITS Indoor Air COOLING Water Inlet Temp. DB. WB. Standard 30 C 27 C 19 C Min. 15 C 21 C 15 C Max. 40 C 32 C 23 C 4
CONSTRUCTION. DIMENSIONS MOD. 201, 251, 271, 351, 401 J L F G I K E 11 C D 12 2 H 3 13 14 N 9 1 7 8 A B 10 4 5 6 CONSTRUCTION DETAILS 1. Electric panel 2. Drainage 3/4" male 3. Air filter 4. Fan motor 5. Fan 6. Electric heater (option) 7. Evaporator coil 8. Hot water coil (option) 9. Condenser 10. Compressor 11. Electric supply 12. Water outlet 13. Water intlet 14. Pressostat Water outlet Water intlet M O P Q R DIMENSIONS (mm) MODEL A B C D E F G H I J K L M N O P Q R 201 520 990 425 377 25 522 40 554 264 234 25 95 50 50 140 75 70 70 251 657 1080 484 430 25 552 40 617 264 234 82 140 50 50 140 75 70 70 271 750 1200 484 430 25 615 40 678 264 302 82 170 70 44 135 80 67 40 351 750 1200 484 430 25 615 40 678 293 337 28 91 70 44 135 80 67 40 401 850 1280 542 488 25 670 60 756 293 337 87 133 72 44 167 125 50 40 WATER CONNECTIONS MODEL 201 251 271 351 401 Size (male) 1/2" 1/2" 1/2" 1/2" 3/4" APPROXIMATE WEIGHT (kg) MODEL 201 251 271 351 401 Net weight 87 104 123 130 135 Packed weight 104 121 140 148 155 5
CONSTRUCTION. DIMENSIONS MOD. 501 333 133 752 60 291 87 542 25 488 13 12 817 10 11 1 44 2 40 9 3 4 1400 8 Water outlet Water inlet 180 110 50 5 7 100 900 6 APPROXIMATE WEIGHT (kg) MODEL 501 Net weight 160 Packed weight 180 WATER CONNECTIONS MODEL 501 Size (male) 3/4" CONSTRUCTION DETAILS 1. Pressostat 2. Condenser 3. Electric panel 4. Evaporator coil 5. Hot water coil (option) 6. Electric heater (option) 7. Fan 8. Fan motor 9. Compressor 10. Drainage 3/4" male 11. Air filter 12. Water connections 13. Power supply 6
CONSTRUCTION. DIMENSIONS MOD. 701, 721 y 751 311 184 952 90 62 343 600 546 25 11 30 9 1071 10 40 65 907 ø 15 25 100 12 55 1 2 3 1500 1550 8 110 110 Water outlet model 751 Water outlet model 721 Water inlet 4 7 6 198 50 1000 5 APPROXIMATE WEIGHT (kg) MODEL 701 721 751 Net weight 240 259 259 Packed weight 260 279 279 CONSTRUCTION DETAILS 1. Electric panel 2. Compressor 3. Evaporator coil 4. Hot water coil (option) 5. Electric heater (option) 6. Fan 7. Fan motor 8. Condenser 9. Drainage 3/4" male 10. Air filter 11. Power supply 12. Pressostat WATER CONNECTIONS MODEL 701 721 751 Size (male) 1" 1" 1" 7
TECHNICAL SPECIFICATIONS MODELO WCHZ 201 251 271 351 401 Rated cooling capacity kw 6,4 8,1 9,0 11,3 13,4 COMPRESSOR Type Hermetic, reciprocating Voltage (50 Hz~) V 230.I 230.I 230.I 400.III 230.I 230.III 400.III 230.III 400.III Input power kw 1,62 2,12 2,22 2,83 3,64 Input current A 8,3 10,8 11,3 3,8 14,5 8,4 4,8 10,8 6,2 EVAPORATOR COIL Type Copper tubing coil and aluminium fins Front face area m 3 0,188 0,225 0,252 0,252 0,310 Fin spacing - tube Ø mm - (") 2,1 3/8 2,1 3/8 2,1 3/8 2,1 3/8 2,1 3/8 CONDENSER Type Tube in tube, co-axial, all copper Water connections Ø (") 1/2 1/2 1/2 1/2 1/2 EVAPORATOR FAN Type Centrifugal Model 9/7 DD 9/7 DD 9/9 DD 10/10 DD 10/10 DD Motor power kw 0,125 0,125 0,250 0,250 0,250 Voltage (50 Hz~) V 230.I Input current A 1,4 1,5 2,1 2,3 2,3 REFRIGERANT R407c - operating charge kg 1,10 1,30 1,30 1,40 2,40 GENERAL DATA FOR ELECTRIC INSTALLATION Voltage (50 Hz~) V 230.I 230.I 230.I 400.III 230.I 230.III 400.III 230.III 400.III Total input power (1) kw 2,10 2,70 2,80 3,30 4,40 Total input current (1) A 10,7 13,8 14,3 4,8 16,9 9,8 5,6 13,0 7,5 Max. input power (2) kw 2,51 3,23 3,35 3,95 5,26 Max. input current (2) A 12,8 16,5 17,1 5,7 20,2 11,7 6,7 15,6 8,9 Starting current A 58 78 82 43 106 51 48 105 64 SOUND PRESSURE LEVEL (at 2 meters) Unit db (A) 62 63 64 64 64 1. COOLING (Standard): condensing temperature 40 C; 27 C DB / 19 C. WB indoor temperature. 2. COOLING (Max.): condensing temperature 50 C. 8
TECHNICAL SPECIFICATIONS MODELO WCHZ 501 701 721 751 Rated cooling capacity kw 16,0 20,6 22,2 25,1 COMPRESSOR Type Hermetic, reciprocat. SCROLL Voltage (50 Hz~) V 230.III 400.III 400.III 230.III 400.III 230.III 400.III Input power kw 4,10 4,10 5,60 4,45 4,45 7,20 7,20 Input current A 12,1 7,0 7,4 15,7 9,1 21,4 12,2 EVAPORATOR COIL Type Copper tubing coil and aluminium fins Front face area m 3 0,350 0,473 0,473 0,495 Fin spacing - tube Ø mm - (") 2,1-3/8 2,1-3/8 2,1-3/8 2,1-3/8 CONDENSER Type Tube in tube, co-axial, all copper Water connections Ø (") 3/4 1 1 1 EVAPORATOR FAN Type Centrifugal Model 10/10 SS 12/9 SS 12/9 SS 12/9 SS Motor power kw 0,550 0,750 0,750 0,750 Voltage (50 Hz~) V 230.III 400.III 400.III 230.III 400.III 230.III 400.III Input current A 2,8 1,7 2,0 3,5 2,0 3,5 2,0 REFRIGERANT R407c - operating charge kg 2,70 2,80 2,80 3,90 GENERAL DATA FOR ELECTRIC INSTALLATION Voltage (50 Hz~) V 230.III 400.III 400.III 230.III 400.III 230.III 400.III Total input power (1) kw 5,20 6,55 6,20 7,70 Total input current (1) A 15,4 8,8 11,1 18,3 10,5 22,8 13,1 Max. input power (2) kw 6,22 7,83 7,41 9,23 Max. input current (2) A 18,4 10,6 13,3 21,9 12,6 27,3 15,7 Starting current A 131 70 78 185 105 204 105 SOUND PRESSURE LEVEL (at 2 meters) Unit db (A) 65 68 68 68 1. COOLING (Standard): condensing temperature 40 C; 27 C DB / 19 C. WB indoor temperature. 2. COOLING (Max.): condensing temperature 50 C. 9
COOLING CAPACITIES MODEL WCHZ201 WCHZ251 WCHZ271 Indoor airflow l/s 417 444 555 Condensing temp. C 35 40 45 50 35 40 45 50 35 40 45 50 INDOOR AIR. ENTERING WET BULB TEMPERATURE 15 C Total capacity kw 5,71 5,47 5,22 4,96 7,22 6,93 6,61 6,27 8,03 7,70 7,34 6,97 Input power kw 1,84 2,01 2,20 2,39 2,36 2,59 2,82 3,07 2,45 2,69 2,93 3,18 19 C 4,09 3,93 3,77 3,62 5,17 4,97 4,78 4,58 5,75 5,53 5,31 5,09 Sensible Heat E.D.B.T. 21 C 4,69 4,52 4,37 4,21 5,93 5,72 5,53 5,33 6,59 6,36 6,14 5,92 kw 23 C 5,29 5,13 4,98 4,82 6,69 6,49 6,30 6,10 7,44 7,21 7,00 6,78 25 C 5,71 5,47 5,22 4,96 7,22 6,93 6,61 6,27 8,03 7,70 7,34 6,97 INDOOR AIR. ENTERING WET BULB TEMPERATURE 17 C Total capacity kw 6,18 5,94 5,69 5,42 7,82 7,52 7,20 6,86 8,68 8,36 7,99 7,63 Input power kw 1,88 2,06 2,24 2,43 2,42 2,64 2,88 3,12 2,50 2,74 2,98 3,24 21 C 4,08 3,92 3,76 3,61 5,16 4,96 4,76 4,57 5,74 5,51 5,29 5,07 Sensible Heat E.D.B.T. 23 C 4,68 4,52 4,36 4,21 5,93 5,72 5,52 5,33 6,58 6,36 6,14 5,92 kw 25 C 5,28 5,12 4,96 4,81 6,68 6,48 6,28 6,09 7,43 7,20 6,98 6,77 27 C 5,89 5,73 5,56 5,42 7,45 7,25 7,04 6,86 8,28 8,05 7,82 7,62 INDOOR AIR. ENTERING WET BULB TEMPERATURE 19 C Total capacity kw 6,63 6,40 6,15 5,89 8,40 8,10 7,79 7,45 9,33 9,00 8,65 8,28 Input power kw 1,93 2,10 2,28 2,47 2,49 2,70 2,93 3,18 2,58 2,80 3,04 3,30 23 C 4,08 3,92 3,76 3,61 5,16 4,96 4,76 4,57 5,73 5,51 5,29 5,07 Sensible Heat E.D.B.T. 25 C 4,67 4,52 4,36 4,21 5,92 5,72 5,52 5,33 6,57 6,36 6,13 5,92 kw 27 C 5,28 5,12 4,96 4,81 6,68 6,48 6,28 6,09 7,42 7,20 6,98 6,76 29 C 5,89 5,73 5,57 5,42 7,45 7,25 7,05 6,86 8,28 8,05 7,83 7,62 INDOOR AIR. ENTERING WET BULB TEMPERATURE 21 C Total capacity kw 7,11 6,87 6,62 6,34 8,99 8,69 8,38 8,03 9,99 9,66 9,31 8,92 Input power kw 1,98 2,14 2,32 2,51 2,55 2,75 2,98 3,23 2,64 2,85 3,09 3,35 25 C 4,04 3,89 3,74 3,58 5,12 4,92 4,73 4,54 5,69 5,47 5,26 5,04 Sensible Heat E.D.B.T. 27 C 4,67 4,51 4,35 4,20 5,91 5,71 5,51 5,32 6,57 6,34 6,12 5,91 kw 29 C 5,26 5,11 4,95 4,80 6,66 6,47 6,26 6,07 7,40 7,18 6,96 6,75 31 C 5,88 5,72 5,56 5,41 7,44 7,24 7,03 6,84 8,26 8,04 7,81 7,60 NOTES: 1. Capacities are net after deduction of indoor fan motor heat. 2. E. D.B.T. indoor entering air dry bulb temperature ( C). CORRECTION FACTORS % Airflow 80 90 110 120 Total capacity 0,95 0,97 1,03 1,05 Sensible capacity 0,92 0,96 1,04 1,07 Input power 0,96 0,98 1,02 1,03 10
COOLING CAPACITIES MODEL WCHZ351 WCHZ401 WCHZ501 Indoor airflow l/s 639 666 972 Condensing temp. C 35 40 45 50 35 40 45 50 35 40 45 50 INDOOR AIR. ENTERING WET BULB TEMPERATURE 15 C Total capacity kw 10,08 9,67 9,22 8,75 11,95 11,46 10,93 10,38 14,27 13,69 13,05 12,39 Input power kw 2,89 3,17 3,45 3,75 3,85 4,22 4,60 5,00 4,55 4,99 5,44 5,91 19 C 7,22 6,94 6,66 6,39 8,56 8,23 7,90 7,57 10,54 10,13 9,73 9,32 Sensible Heat E.D.B.T. 21 C 8,28 7,98 7,71 7,43 9,82 9,47 9,14 8,82 12,09 11,66 11,26 10,85 kw 23 C 9,34 9,06 8,78 8,51 11,07 10,74 10,42 10,10 13,63 13,23 12,83 12,39 25 C 10,08 9,67 9,22 8,75 11,95 11,46 10,93 10,38 14,27 13,69 13,05 12,39 INDOOR AIR. ENTERING WET BULB TEMPERATURE 17 C Total capacity kw 10,90 10,49 10,04 9,57 12,93 12,44 11,90 11,35 15,44 14,85 14,21 13,56 Input power kw 2,95 3,23 3,52 3,82 3,94 4,31 4,69 5,09 4,65 5,09 5,54 6,02 21 C 7,20 6,92 6,64 6,37 8,54 8,21 7,87 7,56 10,52 10,11 9,70 9,30 Sensible Heat E.D.B.T. 23 C 8,27 7,99 7,70 7,43 9,80 9,47 9,13 8,82 12,07 11,66 11,25 10,86 kw 25 C 9,33 9,04 8,76 8,50 11,06 10,72 10,39 10,08 13,62 13,21 12,79 12,4 27 C 10,40 10,11 9,82 9,57 12,33 11,99 11,65 11,34 15,18 14,77 14,21 13,56 INDOOR AIR. ENTERING WET BULB TEMPERATURE 19 C Total capacity kw 11,71 11,30 10,86 10,40 13,89 13,40 12,88 12,33 16,58 16,00 15,38 14,72 Input power kw 3,04 3,30 3,58 3,89 4,05 4,40 4,78 5,18 4,79 5,20 5,65 6,12 23 C 7,20 6,92 6,64 6,37 8,53 8,20 7,87 7,55 10,51 10,10 9,69 9,30 Sensible Heat E.D.B.T. 25 C 8,25 7,98 7,70 7,43 9,79 9,47 9,13 8,81 12,05 11,66 11,25 10,85 kw 27 C 9,32 9,04 8,76 8,49 11,05 10,72 10,39 10,07 13,61 13,20 12,79 12,40 29 C 10,39 10,11 9,83 9,56 12,32 11,99 11,66 11,34 15,17 14,77 14,36 13,96 INDOOR AIR. ENTERING WET BULB TEMPERATURE 21 C Total capacity kw 12,55 12,13 11,69 11,20 14,88 14,38 13,86 13,28 17,77 17,17 16,55 15,86 Input power kw 3,11 3,36 3,64 3,95 4,15 4,49 4,85 5,26 4,90 5,30 5,74 6,22 25 C 7,14 6,87 6,60 6,33 8,47 8,15 7,83 7,50 10,43 10,03 9,64 9,24 Sensible Heat E.D.B.T. 27 C 8,24 7,96 7,68 7,42 9,77 9,44 9,11 8,79 12,04 11,63 11,22 10,83 kw 29 C 9,30 9,02 8,74 8,47 11,02 10,70 10,36 10,05 13,57 13,17 12,76 12,37 31 C 10,37 10,09 9,81 9,55 12,30 11,97 11,63 11,32 15,15 14,74 14,33 13,94 NOTES: 1. Capacities are net after deduction of indoor fan motor heat. 2. E. D.B.T. indoor entering air dry bulb temperature ( C). CORRECTION FACTORS % Airflow 80 90 110 120 Total capacity 0,95 0,97 1,03 1,05 Sensible capacity 0,92 0,96 1,04 1,07 Input power 0,96 0,98 1,02 1,03 11
COOLING CAPACITIES MODEL WCHZ701 WCHZ721 WCHZ751 Indoor airflow l/s 1194 1250 1278 Condensing temp. C 35 40 45 50 35 40 45 50 35 40 45 50 INDOOR AIR. ENTERING WET BULB TEMPERATURE 15 C Total capacity kw 18,37 17,62 16,80 15,95 19,80 18,99 18,11 17,19 22,39 21,47 20,48 19,44 Input power kw 5,73 6,28 6,85 7,45 5,43 5,95 6,48 7,05 6,74 7,39 8,05 8,76 19 C 13,15 12,65 12,15 11,64 14,17 13,63 13,09 12,55 16,03 15,41 14,80 14,19 Sensible Heat E.D.B.T. 21 C 15,09 14,55 14,06 13,55 16,26 15,68 15,15 14,60 18,39 17,73 17,13 16,51 kw 23 C 17,02 16,51 16,01 15,52 18,34 17,80 17,26 16,73 20,74 20,12 19,51 18,91 25 C 18,37 17,62 16,80 15,95 19,80 18,99 18,11 17,19 22,39 21,47 20,48 19,44 INDOOR AIR. ENTERING WET BULB TEMPERATURE 17 C Total capacity kw 19,88 19,12 18,30 17,46 21,42 20,61 19,72 18,81 24,22 23,30 22,30 21,27 Input power kw 5,86 6,41 6,98 7,58 5,55 6,07 6,60 7,17 6,89 7,54 8,20 8,91 21 C 13,13 12,62 12,10 11,61 14,15 13,60 13,04 12,52 16,00 15,38 14,75 14,15 Sensible Heat E.D.B.T. 23 C 15,07 14,56 14,04 13,55 16,24 15,69 15,13 14,61 18,36 17,74 17,11 16,51 kw 25 C 17,00 16,49 15,97 15,50 18,32 17,77 17,21 16,70 20,71 20,09 19,46 18,88 27 C 18,96 18,43 17,91 17,44 20,43 19,87 19,30 18,79 23,10 22,46 21,82 21,25 INDOOR AIR. ENTERING WET BULB TEMPERATURE 19 C Total capacity kw 21,35 20,60 19,80 18,95 23,01 22,20 21,34 20,43 26,02 25,10 24,13 23,10 Input power kw 6,03 6,55 7,11 7,71 5,71 6,20 6,73 7,30 7,09 7,70 8,36 9,07 23 C 13,12 12,61 12,10 11,61 14,14 13,59 13,04 12,51 15,99 15,37 14,75 14,15 Sensible Heat E.D.B.T. 25 C 15,05 14,55 14,04 13,55 16,21 15,68 15,13 14,60 18,33 17,73 17,11 16,51 kw 27 C 16,99 16,48 15,97 15,48 18,31 17,76 17,21 16,68 20,70 20,08 19,46 18,86 29 C 18,94 18,44 17,92 17,43 20,41 19,87 19,32 18,79 23,08 22,46 21,84 21,24 INDOOR AIR. ENTERING WET BULB TEMPERATURE 21 C Total capacity kw 22,87 22,11 21,31 20,41 24,65 23,82 22,97 22,00 27,87 26,93 25,97 24,87 Input power kw 6,18 6,68 7,22 7,83 5,85 6,32 6,84 7,41 7,26 7,85 8,49 9,21 25 C 13,02 12,52 12,03 11,54 14,03 13,50 12,96 12,43 15,86 15,26 14,66 14,06 Sensible Heat E.D.B.T. 27 C 15,03 14,52 14,00 13,52 16,19 15,64 15,09 14,57 18,31 17,69 17,06 16,47 kw 29 C 16,95 16,44 15,93 15,45 18,26 17,72 17,17 16,65 20,65 20,04 19,41 18,82 31 C 18,91 18,40 17,89 17,40 20,38 19,83 19,28 18,76 23,04 22,42 21,79 21,21 NOTES: 1. Capacities are net after deduction of indoor fan motor heat. 2. E. D.B.T. indoor entering air dry bulb temperature ( C). CORRECTION FACTORS % Airflow 80 90 110 120 Total capacity 0,95 0,97 1,03 1,05 Sensible capacity 0,92 0,96 1,04 1,07 Input power 0,96 0,98 1,02 1,03 12
CONDENSER WATER FLOW Water inlet temperatur C 15 20 25 30 35 MODEL Condensing EWBT Cooling LWT WT LWT WT LWT WT LWT WT LWT WT temp. C C cap. C l/s C l/s C l/s C l/s C l/s 15 5,71 28,23 0,14 28,82 0,20 29,41 0,41 17 6,18 29,12 0,14 29,42 0,20 29,71 0,41 35 19 6,63 30,00 0,14 30,00 0,20 30,00 0,41 21 7,11 30,93 0,14 30,62 0,20 30,31 0,41 15 5,47 32,60 0,10 33,20 0,14 33,80 0,20 34,40 0,41 17 5,94 33,82 0,10 34,12 0,14 34,41 0,20 34,71 0,41 40 19 6,40 35,00 0,10 35,00 0,14 35,00 0,20 35,00 0,41 WCHZ 21 6,87 36,20 0,10 35,90 0,14 35,60 0,20 35,30 0,41 201 15 5,22 37,00 0,08 37,60 0,10 38,20 0,13 38,80 0,20 39,40 0,40 17 5,69 38,52 0,08 38,81 0,10 39,11 0,13 39,41 0,20 39,70 0,40 45 19 6,15 40,00 0,08 40,00 0,10 40,00 0,13 40,00 0,20 40,00 0,40 21 6,62 41,51 0,08 41,21 0,10 40,91 0,13 40,60 0,20 40,30 0,40 15 4,96 41,38 0,07 41,98 0,08 42,58 0,10 43,19 0,13 43,79 0,20 17 5,42 43,17 0,07 43,47 0,08 43,78 0,10 44,08 0,13 44,39 0,20 50 19 5,89 45,00 0,07 45,00 0,08 45,00 0,10 45,00 0,13 45,00 0,20 21 6,34 46,76 0,07 46,47 0,08 46,17 0,10 45,88 0,13 45,59 0,20 15 7,22 28,20 0,17 28,80 0,26 29,40 0,52 17 7,82 29,10 0,17 29,40 0,26 29,70 0,52 35 19 8,40 30,00 0,17 30,00 0,26 30,00 0,52 21 8,99 30,90 0,17 30,60 0,26 30,30 0,52 15 6,93 32,63 0,13 33,22 0,17 33,81 0,26 34,41 0,52 17 7,52 33,81 0,13 34,11 0,17 34,41 0,26 34,70 0,52 40 19 8,10 35,00 0,13 35,00 0,17 35,00 0,26 35,00 0,52 WCHZ 21 8,69 36,19 0,13 35,89 0,17 35,59 0,26 35,30 0,52 251 15 6,61 36,99 0,10 37,59 0,13 38,19 0,17 38,80 0,26 39,40 0,51 17 7,20 38,51 0,10 38,81 0,13 39,10 0,17 39,40 0,26 39,70 0,51 45 19 7,79 40,00 0,10 40,00 0,13 40,00 0,17 40,00 0,26 40,00 0,51 21 8,38 41,49 0,10 41,19 0,13 40,90 0,17 40,60 0,26 40,30 0,51 15 6,27 41,36 0,08 41,97 0,10 42,57 0,13 43,18 0,17 43,79 0,25 17 6,86 43,17 0,08 43,47 0,10 43,78 0,13 44,08 0,17 44,39 0,25 50 19 7,45 45,00 0,08 45,00 0,10 45,00 0,13 45,00 0,17 45,00 0,25 21 8,03 46,78 0,08 46,48 0,10 46,19 0,13 45,89 0,17 45,59 0,25 NOTES: EWBT= indoor air entering wet bulb temperature ºC. LWT= leaving water temperature ºC. WT= water flow l/s. 13
CONDENSER WATER FLOW Water inlet temperatur C 15 20 25 30 35 MODEL Condensing EWBT Cooling LWT WT LWT WT LWT WT LWT WT LWT WT temp. C C cap. C l/s C l/s C l/s C l/s C l/s 15 8,03 28,20 0,19 28,80 0,28 29,40 0,57 17 8,68 29,08 0,19 29,39 0,28 29,69 0,57 35 19 9,33 30,00 0,19 30,00 0,28 30,00 0,57 21 9,99 30,91 0,19 30,60 0,28 30,30 0,57 15 7,70 32,61 0,14 33,21 0,19 33,81 0,28 34,40 0,56 17 8,36 33,81 0,14 34,11 0,19 34,41 0,28 34,70 0,56 40 19 9,00 35,00 0,14 35,00 0,19 35,00 0,28 35,00 0,56 WCHZ 21 9,66 36,20 0,14 35,90 0,19 35,60 0,28 35,30 0,56 271 15 7,34 36,96 0,11 37,57 0,14 38,18 0,19 38,79 0,28 39,39 0,56 17 7,99 38,46 0,11 38,77 0,14 39,08 0,19 39,38 0,28 39,69 0,56 45 19 8,65 40,00 0,11 40,00 0,14 40,00 0,19 40,00 0,28 40,00 0,56 21 9,31 41,52 0,11 41,21 0,14 40,91 0,19 40,61 0,28 40,30 0,56 15 3,18 41,30 0,09 41,91 0,11 42,53 0,14 43,15 0,18 43,77 0,28 17 7,63 43,16 0,09 43,47 0,11 43,77 0,14 44,08 0,18 44,39 0,28 50 19 8,28 45,00 0,09 45,00 0,11 45,00 0,14 45,00 0,18 45,00 0,28 21 8,92 46,79 0,09 46,49 0,11 46,19 0,14 45,89 0,18 45,60 0,28 15 10,08 28,19 0,23 28,79 0,35 29,40 0,70 17 10,90 29,08 0,23 29,39 0,35 29,69 0,70 35 19 11,71 30,00 0,23 30,00 0,35 30,00 0,70 21 12,55 30,93 0,23 30,62 0,35 30,31 0,70 15 9,67 32,59 0,17 33,19 0,23 33,79 0,35 34,40 0,70 17 10,49 33,79 0,17 34,10 0,23 34,40 0,35 34,70 0,70 40 19 11,30 35,00 0,17 35,00 0,23 35,00 0,35 35,00 0,70 WCHZ 21 12,13 36,22 0,17 35,91 0,23 35,61 0,35 35,30 0,70 351 15 9,22 36,94 0,14 37,55 0,17 38,16 0,23 38,77 0,34 39,39 0,69 17 10,04 38,48 0,14 38,78 0,17 39,09 0,23 39,39 0,34 39,70 0,69 45 19 10,86 40,00 0,14 40,00 0,17 40,00 0,23 40,00 0,34 40,00 0,69 21 11,69 41,54 0,14 41,23 0,17 40,92 0,23 40,62 0,34 40,31 0,69 15 8,75 41,24 0,11 41,87 0,14 42,49 0,17 43,12 0,23 43,75 0,34 17 9,57 43,11 0,11 43,43 0,14 43,74 0,17 44,06 0,23 44,37 0,34 50 19 10,40 45,00 0,11 45,00 0,14 45,00 0,17 45,00 0,23 45,00 0,34 21 11,20 46,81 0,11 46,50 0,14 46,20 0,17 45,90 0,23 45,60 0,34 NOTES: EWBT= indoor air entering wet bulb temperature ºC. LWT= leaving water temperature ºC. WT= water flow l/s. 14
CONDENSER WATER FLOW Water inlet temperatur C 15 20 25 30 35 MODEL Condensing EWBT Cooling LWT WT LWT WT LWT WT LWT WT LWT WT temp. C C cap. C l/s C l/s C l/s C l/s C l/s 35 15 11,95 28,21 0,29 28,81 0,43 29,40 0,86 17 12,93 29,11 0,29 29,40 0,43 29,70 0,86 19 13,89 30,00 0,29 30,00 0,43 30,00 0,86 21 14,88 30,91 0,29 30,61 0,43 30,30 0,86 40 15 11,46 32,62 0,21 33,21 0,28 33,81 0,43 34,40 0,85 17 12,44 33,82 0,21 34,12 0,28 34,41 0,43 34,71 0,85 19 13,40 35,00 0,21 35,00 0,28 35,00 0,43 35,00 0,85 WCHZ 21 14,38 36,20 0,21 35,90 0,28 35,60 0,43 35,30 0,85 401 45 15 10,93 36,98 0,17 37,59 0,21 38,19 0,28 38,79 0,42 39,40 0,84 17 11,90 38,49 0,17 38,79 0,21 39,09 0,28 39,39 0,42 39,70 0,84 19 12,88 40,00 0,17 40,00 0,21 40,00 0,28 40,00 0,42 40,00 0,84 21 13,86 41,49 0,17 41,19 0,21 40,89 0,28 40,59 0,42 40,30 0,84 50 15 10,38 41,35 0,14 41,96 0,17 42,57 0,21 43,18 0,28 43,78 0,42 17 11,35 43,17 0,14 43,47 0,17 43,78 0,21 44,08 0,28 44,39 0,42 19 12,33 45,00 0,14 45,00 0,17 45,00 0,21 45,00 0,28 45,00 0,42 21 13,28 46,76 0,14 46,47 0,17 46,18 0,21 45,88 0,28 45,59 0,42 15 14,27 28,21 0,34 28,81 0,51 29,40 1,02 17 15,44 29,10 0,34 29,40 0,51 29,70 1,02 35 19 16,58 30,00 0,34 30,00 0,51 30,00 1,02 21 17,77 30,91 0,34 30,61 0,51 30,30 1,02 15 13,69 32,62 0,25 33,22 0,34 33,81 0,51 34,41 1,01 17 14,85 33,81 0,25 34,11 0,34 34,41 0,51 34,70 1,01 40 19 16,00 35,00 0,25 35,00 0,34 35,00 0,51 35,00 1,01 WCHZ 21 17,17 36,20 0,25 35,90 0,34 35,60 0,51 35,30 1,01 501 15 13,05 36,98 0,20 37,58 0,25 38,19 0,33 38,79 0,50 39,40 1,00 17 14,21 38,48 0,20 38,78 0,25 39,09 0,33 39,39 0,50 39,70 1,00 45 19 15,38 40,00 0,20 40,00 0,25 40,00 0,33 40,00 0,50 40,00 1,00 21 16,55 41,50 0,20 41,20 0,25 40,90 0,33 40,60 0,50 40,30 1,00 15 5,91 41,34 0,17 41,95 0,20 42,56 0,25 43,17 0,33 43,78 0,50 17 13,56 43,19 0,17 43,49 0,20 43,79 0,25 44,09 0,33 44,40 0,50 50 19 14,72 45,00 0,17 45,00 0,20 45,00 0,25 45,00 0,33 45,00 0,50 21 15,86 46,79 0,17 46,49 0,20 46,19 0,25 45,89 0,33 45,60 0,50 NOTES: EWBT= indoor air entering wet bulb temperature ºC. LWT= leaving water temperature ºC. WT= water flow l/s. 15
CONDENSER WATER FLOW Water inlet temperatur C 15 20 25 30 35 MODEL Temperatura de EWBT Potencia LWT WT LWT WT LWT WT LWT WT LWT WT condensación C C frigorífica C l/s C l/s C l/s C l/s C l/s 15 18,37 28,20 0,44 28,80 0,65 29,40 1,31 17 19,88 29,10 0,44 29,40 0,65 29,70 1,31 35 19 21,35 30,00 0,44 30,00 0,65 30,00 1,31 21 22,87 30,91 0,44 30,61 0,65 30,30 1,31 15 17,62 32,61 0,32 33,20 0,43 33,80 0,65 34,40 1,30 17 19,12 33,81 0,32 34,10 0,43 34,40 0,65 34,70 1,30 40 19 20,60 35,00 0,32 35,00 0,43 35,00 0,65 35,00 1,30 WCHZ 21 22,11 36,21 0,32 35,91 0,43 35,60 0,65 35,30 1,30 701 15 16,80 36,97 0,26 37,58 0,32 38,18 0,43 38,79 0,64 39,39 1,29 17 18,30 38,49 0,26 38,79 0,32 39,09 0,43 39,39 0,64 39,70 1,29 45 19 19,80 40,00 0,26 40,00 0,32 40,00 0,43 40,00 0,64 40,00 1,29 21 21,31 41,51 0,26 41,20 0,32 40,90 0,43 40,60 0,64 40,30 1,29 15 15,95 41,33 0,21 41,94 0,25 42,55 0,32 43,17 0,42 43,78 0,64 17 17,46 43,18 0,21 43,48 0,25 43,78 0,32 44,09 0,42 44,39 0,64 50 19 18,95 45,00 0,21 45,00 0,25 45,00 0,32 45,00 0,42 45,00 0,64 21 20,41 46,78 0,21 46,48 0,25 46,19 0,32 45,89 0,42 45,59 0,64 15 19,80 28,18 0,46 28,78 0,69 29,39 1,37 17 21,42 29,09 0,46 29,39 0,69 29,70 1,37 35 19 23,01 30,00 0,46 30,00 0,69 30,00 1,37 21 24,65 30,93 0,46 30,62 0,69 30,31 1,37 15 18,99 32,56 0,34 33,17 0,45 33,78 0,68 34,39 1,36 17 20,61 33,79 0,34 34,09 0,45 34,39 0,68 34,70 1,36 40 19 22,20 35,00 0,34 35,00 0,45 35,00 0,68 35,00 1,36 WCHZ 21 23,82 36,23 0,34 35,92 0,45 35,61 0,68 35,31 1,36 721 15 18,11 36,90 0,27 37,52 0,34 38,14 0,45 38,76 0,67 39,38 1,34 17 19,72 38,44 0,27 38,75 0,34 39,06 0,45 39,38 0,67 39,69 1,34 45 19 21,34 40,00 0,27 40,00 0,34 40,00 0,45 40,00 0,67 40,00 1,34 21 22,97 41,55 0,27 41,24 0,34 40,93 0,45 40,62 0,67 40,31 1,34 15 17,19 41,22 0,22 41,85 0,26 42,48 0,33 43,11 0,44 43,74 0,66 17 18,81 43,11 0,22 43,42 0,26 43,74 0,33 44,05 0,44 44,37 0,66 50 19 20,43 45,00 0,22 45,00 0,26 45,00 0,33 45,00 0,44 45,00 0,66 21 22,00 46,82 0,22 46,51 0,26 46,21 0,33 45,91 0,44 45,61 0,66 NOTES: EWBT= indoor air entering wet bulb temperature ºC. LWT= leaving water temperature ºC. WT= water flow l/s. 16
CONDENSER WATER FLOW. PRESSURE DROPS Water inlet temperatur C 15 20 25 30 35 MODEL Condensing EWBT Cooling LWT WT LWT WT LWT WT LWT WT LWT WT temp. C C cap. C l/s C l/s C l/s C l/s C l/s 15 22,39 28,20 0,53 28,80 0,79 29,40 1,58 17 24,22 29,09 0,53 29,40 0,79 29,70 1,58 35 19 26,02 30,00 0,53 30,00 0,79 30,00 1,58 21 27,87 30,92 0,53 30,61 0,79 30,31 1,58 15 21,47 32,60 0,39 33,20 0,52 33,80 0,78 34,40 1,57 17 23,30 33,80 0,39 34,10 0,52 34,40 0,78 34,70 1,57 40 19 25,10 35,00 0,39 35,00 0,52 35,00 0,78 35,00 1,57 WCHZ 21 26,93 36,21 0,39 35,91 0,52 35,60 0,78 35,30 1,57 751 15 20,48 36,95 0,31 37,56 0,39 38,17 0,52 38,78 0,78 39,39 1,55 17 22,30 38,47 0,31 38,78 0,39 39,08 0,52 39,39 0,78 39,69 1,55 45 19 24,13 40,00 0,31 40,00 0,39 40,00 0,52 40,00 0,78 40,00 1,55 21 25,97 41,52 0,31 41,21 0,39 40,91 0,52 40,61 0,78 40,30 1,55 15 8,76 41,30 0,26 41,91 0,31 42,53 0,38 43,15 0,51 43,77 0,77 17 21,27 43,14 0,26 43,45 0,31 43,76 0,38 44,07 0,51 44,38 0,77 50 19 23,10 45,00 0,26 45,00 0,31 45,00 0,38 45,00 0,51 45,00 0,77 21 24,87 46,78 0,26 46,48 0,31 46,19 0,38 45,89 0,51 45,59 0,77 NOTES: EWBT= indoor air entering wet bulb temperature ºC. LWT= leaving water temperature ºC. WT= water flow l/s. PRESSURE DROP ON CONDENSER (KPA) WATER FLOW MODEL l/s 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6 WCHZ m 3 /h 0,4 0,7 1,1 1,4 1,8 2,2 2,5 2,9 3,2 3,6 4,0 4,3 4,7 5,0 5,4 5,8 201 2,5 5,8 10,5 18,5 24,0 33,0 251 2,5 5,8 10,5 18,5 24,0 33,0 271 2,5 5,8 10,5 18,5 24,0 33,0 351 1,5 2,5 4,0 8,0 11,0 15,0 20,0 26,0 32,0 401 1,5 2,5 4,0 8,0 11,0 15,0 20,0 26,0 32,0 501 2,0 3,7 7,0 8,5 12,0 16,0 21,0 25,0 28,0 33,0 37,5 42,0 701 2,0 3,7 7,0 8,5 12,0 16,0 21,0 25,0 28,0 33,0 37,5 42,0 721 2,0 3,7 7,0 8,5 12,0 16,0 21,0 25,0 28,0 33,0 37,5 42,0 45,0 751 1,0 2,0 3,0 6,0 7,0 8,3 10,0 13,0 17,0 21,0 26,0 35,0 40,0 50,0 55,0 17