Committee on NFPA 15

Similar documents
First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM

The distances in shall be reduced to 130 ft (39.7 m) when manual dry standpipes are installed in open parking garages.

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

M E M O R A N D U M. NFPA Technical Committee on Water Spray Fixed Systems

Report on First Revision November 2013 NFPA 750

Second Revision No. 3-NFPA [ Section No. 2.3 ]

Committee on NFPA 85

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

NFPA 15. Standard for. Water Spray Fixed Systems for Fire Protection Edition

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

Adobe Connect - Invitation to NFPA 385 Second Draft Web Conference

Committee on NFPA 51A

MEMORANDUM. NFPA 51 First Draft Technical Committee FINAL Ballot Results (A2017 Cycle)

GASEOUS HYDROGEN SYSTEMS

MSC Guidelines for Automatic Sprinkler Systems


First Revision No. 15-NFPA [ Chapter 2 ]

NFPA 14. Standard for the. Installation of Standpipe and Hose Systems Edition

FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

First Revision No. 1-NFPA [ Chapter 2 ]

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Construction and Demolition

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

TECHNICAL COMMITTEE ON FIRE CODE

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

NFPA 14. Standard for the. Installation of Standpipe and Hose Systems Edition

Public Comment No. 16-NFPA 13D-2014 [ Section No ]

PLAN REVIEW CHECKLIST

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ]

First Revision No. 20-NFPA [ Section No ]

Review of Residential Fire Sprinkler Systems for One- and Two-Family Dwellings

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

1 of /3/ :03 PM. Public Input No. 1-NFPA 13D-2015 [ Chapter 2 ]

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ]

Fire Pump Specification

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement

Report on First Revision June 2014 NFPA 5000

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] Submitter Information Verification. Committee Statement 11/18/2016 2:25 PM

Change all instances of "flame resistant (hypobaric)" to "Limited-Combustible (material)" in all instances in the document.

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

M E M O R A N D U M. Please do not vote negatively because of editorial errors. However, please bring such errors to my attention for action.

Location of Requirements Listed Category I appliances Type B gas vent 12.7 Listed appliances equipped with. Chimney Single wall metal pipe 12.

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Revise the metric values throughout the standard to follow the soft conversions provided by the metric task group

Public Input No. 3-NFPA [ Chapter 2 ]

The Technical Committee on Commissioning and Integrated Testing

Second Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

FIXED PROTECTION FOR OIL AND CHEMICAL PLANTS

Above Ground Fuel Tank Requirements

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD


SECTION DRY-PIPE SPRINKLER SYSTEMS

2018 National Fuel Gas Code Summary List of Revisions Updated: 7/27/17

SECTION AUTOMATIC SPRINKLER PIPING

SPRINKLERS TABLE OF CONTENTS

Committee on NFPA 30A

Public Comment No. 20-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

FACT SHEET 2018 National Fuel Gas Code Summary List of Revisions rev

CITY OF MADISON FIRE DEPARTMENT (MFD) FIRE PROTECTION SYSTEM PLANS

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

SECTION WET-PIPE SPRINKLER SYSTEMS

Remove the "Exception" text to be consistent with direction provided in the MOS.

Public Comment No. 2-NFPA [ Section No ]

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

Copyright 2016 AIA MasterSpec Full Length 09/16 PRODUCT MASTERSPEC LICENSED BY AVITRU, LLC TO VICTAULIC COMPANY.

esfr dry pendent sprinkler Vk501 (k14.0)

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

Committee on NFPA 85

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

TECHNICAL DATA OBSOLETE

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing

TECHNICAL DATA. 319a. January 27, 2012

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

UFGS (August 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.

Report on Proposals F2007 Copyright, NFPA NFPA 499 Report of the Committee on

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri

Report on First Revisions with Statement June 2014 NFPA 101

Transcription:

Committee on NFPA 15 M E M O R A N D U M TO: FROM: NFPA Technical Committee on Water Spray Fixed Systems Jeanne Moreau-Correia DATE: February 8, 2010 SUBJECT: NFPA 15 A11 ROP Letter Ballot The ROP letter ballot for NFPA 15 is attached. The ballot is for formally voting on whether or not you concur with the committee s actions on the proposals. Reasons must accompany all negative and abstention ballots. Please do not vote negatively because of editorial errors. However, please bring such errors to my attention for action. Please complete and return your ballot as soon as possible but no later than Monday, February 22, 2010. As noted on the ballot form, please submit the ballot to Jeanne Moreau-Correia, e-mail to jmoreaucorreia@nfpa.org or fax to 617-984-7110. The return of ballots is required by the Regulations Governing Committee Projects. Attachment: Proposals

15-1 Log #CP2 Technical Committee on Water Spray Fixed Systems, Review entire document to: 1) Update any extracted material by preparing separate proposals to do so, and 2) review and update references to other organizations documents, by preparing proposal(s) as required. To conform to the NFPA Regulations Governing Committee Projects. See Committee Proposal CP8 for the updating of references. The Extracts did not require any update. 15-2 Log #3 Robert M. Gagnon, Gagnon Engineering Revise text as follows: Para. 1.2 says standard is based on "sound engineering principles". Para. 1.3.2(1) "Gaseous and liquid flammable materials. Section 6.5.2.7 "Flammable Gas Detectors". These paragraphs do not relate to Chapter 7 (Design Objectives). Per attached CSB Report, the Commitee should provide advice for VA for hazards or delineate the limitations of water spray for vapor mitigation. NFPA 15 provides no advice for mitigation of gaseous hazards. The Committee should address the limitations of water spray with respect to vapor mitigation, and should indicate that flammable gas detectors are for pre-alarm only and may not be effective for release of vapor mitigation systems using water spray. Perhaps the Committee should defer to NFPA 18-A. Note: Supporting material is available for review at NFPA Headquarters. Do not revise Paragraph 1.2. Do not revise Paragraph 1.3.2(1) Add a new 1.3.2(5) Vapor Mitigation Do Not Change Section 6.5.2.7. There are principles of engineering involved in portions of spray system design. Gaseous flammables are protected by spray systems and the new provisions for Vapor Mitigation are being added so they should be added to 1.3.2(5) and as a result 6.5.2.7 does not need to be retitled. 1

15-3 Log #CP8 Technical Committee on Water Spray Fixed Systems, Revise Chapter 2 as follows: ****INCLUDE 15_LCP8_Rec HERE**** Update of Chapter to include the most recent editions of referenced standards. 15-4 Log #5 David R. Hague, Liberty Mutual Property A liquid that has a closed-cup flash point at or above 100 F (37.8 C). [30, 2003] A liquid that has a closed-cup flashpoint at or above 100 F (37.8 C) and below 140 F (60 C). [30, 2003] A liquid that has a closed-cup flash point at or above 140 F (60 C), but below 200 F (93 C). [30, 2003] A liquid that has a closed-cup flash point below 200 F (93 C). [30, 2003] A liquid that has a closed-cup flash point that is below 100 F (37.8 C) and a maximum vapor pressure of 40 psia (2068.6 mm Hg) at 100 F (37.8 C). [30, 2003] A liquid that has a closed-cup flash point below 100 F (37.8 C) and a Reid vapor pressure not exceeding 40 psia (2068.6 mm Hg) at 100 F (37.8 C). [30, 2003] A liquid that has a closed-cup flash point below 73 F (22.8 C) and a boiling point below 100 F (37.8 C). [30, 2003] A liquid that has a closed-cup flash point below 73 F (22.8 C) and a boiling point at or above 100 F (37.8 C). [30, 2003] A liquid that has a closed-cup flash point at or above 73 F (22.8 C) but below 100 F (37.8 C). Coordinates definitions with the NFPA Glossary of Terms. Accept defined terms 3.3.2 and 3.3.10. Move Section 3.3.2.1 to Annex 3.3.2 Move Section 3.3.10.1 to Annex for 3.3.10 And renumber definitions accordingly. The definitions are extracted from NFPA 30 and the Annex language further explains the terms. 2

2.2 NFPA Publications. National Fire Protection Association,1 Batterymarch Park, Quincy, MA 02169-7471. NFPA13, Standard for the Installation of Sprinkler Systems, 2007 2010 edition. NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection, 2007 2010 edition. NFPA 22, Standard for Water Tanks for Private Fire Protection, 2003 2008 edition. NFPA 24, Standard for the Installation of Private Fire Service Mains and Their Appurtenances, 2007 2010 edition. NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, 2002 2011 edition. NFPA 51B, Standard for Fire Prevention During Welding, Cutting, and Other Hot Work, 2003 2009 edition. NFPA 70, National Electrical Code, 2005 2011 edition. NFPA 72, National Fire Alarm Code, 2007 2010 edition. NFPA 1963, Standard for Fire Hose Connections, 2003 2009 edition. 2.3 Other Publications. 2.3.1 ANSI Publications. American National Standards Institute, Inc., 25 West 43rd Street, 4th Floor, New York, NY 10036. ANSI/ASME B1.20.1, Pipe Threads, General Purpose, 19832006. ANSI B16.1, Cast Iron Pipe Flanges and Flanged Fittings, 19982005. ANSI B16.3, Malleable Iron Threaded Fittings, 19982006. ANSI B16.4, Gray Iron Threaded Fittings, 19982006. ANSI B16.5, Pipe Flanges and Flanged Fittings, 20032006. ANSI B16.9, Factory-Made Wrought Steel Buttwelding Fittings, 20032007. ANSI B16.11, Forged Fittings, Socket-Welding and Threaded, 20012009. ANSI B16.18, Cast Copper Alloy Solder Joint Pressure Fittings, 2001. ANSI B16.22, Wrought Copper and Copper Alloy Solder Joint Pressure Fittings, 2001. ANSI B16.25, Buttwelding Ends, 1997. ANSI B36.10M, Welded and Seamless Wrought Steel Pipe, 20002004. ANSI B36.19M, Stainless Steel Pipe, 19852002. ANSI C2, National Electrical Safety Code, 20022007. 2.3.2 ASME Publication. American Society of Mechanical Engineers, Three Park Avenue, New York, NY 10016-5990. ASME Boiler & Pressure Vessel Code (BPVC) Section IX, Welding and Brazing Qualifications, 20032010. 2.3.3 ASTM Publications. ASTM International, 100 Barr Harbor Drive, Box C700,West Conshohocken, PA19428-2959. ASTM A 53, Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless, 20042007. ASTM A 135, Standard Specification for Electric-Resistance-Welded Steel Pipe, 20012009. ASTM A 182, Standard Specification for Forged or Rolled Alloy-Steel Pipe Flanges, Forged Fittings, and Valves and Parts for High-Temperature Service, 20042009. NFPA 15_Log #CP8_Rec A2011 ROP 1

ASTM A 234, Standard Specification for Piping Fittings of Wrought Carbon Steel and Alloy Steel for Moderate and High Temperature Service, 20042007. ASTM A 312, Standard Specification for Seamless Welded and Heavily Cold Worked Austenitic Stainless Steel Pipes, 20042009. ASTM A 536, Standard Specification for Ductile Iron Castings, 19842009. ASTM A 795, Standard Specification for Black and Hot-Dipped Zinc-Coated (Galvanized)Welded and Seamless Steel Pipe for Fire Protection Use, 20042008. ASTM B 75, Standard Specification for Seamless CopperTube, 2002. ASTM B 88, Standard Specification for Seamless Copper Water Tube, 20032009. ASTM B 251, Standard Specification for General Requirements for Wrought Seamless Copper and Copper-Alloy Tube, 2002. 2.3.4 AWS Publications. AmericanWelding Society, 550 N.W. LeJeune Road, Miami, FL 33126. AWS A5.8, Specification for Filler Metals for Brazing and Braze Welding, 2004. AWS B2.1, Specification forwelding Procedures and Performance Qualification, 20052009. AWS B2.2, Standard for Brazing Procedure and Performance Qualification, 1991. 2.3.5 IEEE Publication. Institute of Electrical and Electronics Engineers, Three Park Avenue, 17th Floor, New York, NY 10016-5997. IEEE/ASTM-SI-10, Standard Practice for Use of the International System of Units (SI): The Modern Metric System, 2002. 2.3.6 Other Publications. Merriam-Webster s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003. 2.4 References for Extracts in Mandatory Sections. NFPA13, Standard for the Installation of Sprinkler Systems, 2007 2010 edition. NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, 2002 2011 edition. NFPA 15_Log #CP8_Rec A2011 ROP 2

15-5 Log #13 Salvatore DiCristina, Rutgers University / Rep. NFPA Building Code Development Committee (BCDC) Revise text as follows: 3.3.9* Fire Area. For the purpose of this standard, Aan area that is physically separated from other areas by space, barriers, walls, or other means in order to contain fire within that area. Note: This proposal was developed by the proponent as a member of NFPA s Building Code Development Committee (BCDC) with the committee's endorsement. NFPA 15 uses the term fire area with a definition that is slightly different than the definition of fire area in NFPA 101 and NFPA 5000. Although it is not required to use identical language and/or meaning throughout all of the NFPA codes and standards, it would be better to be certain that the definitions are not intended to be the same. This proposal suggests using the phrase For the purposes of this code (or standard) at the beginning of the definition. Doing so is consistent with other NFPA documents. For example: NFPA 92A defines Smoke Barrier as follows: 3.3.9* Smoke Barrier. For the purposes of this standard, a continuous membrane, either vertical or horizontal, such as a wall, floor, or ceiling assembly, that is designed and constructed to restrict the movement of smoke in conjunction with a smoke-control system. This definition in NFPA 92A is different than the definition of Smoke Barrier in NFPA 5000, which reads : 3.3.47.2* Smoke Barrier. A continuous membrane, or a membrane with discontinuities created by protected openings, where such membrane is designed and constructed to restrict the movement of smoke. So, this proposal is consistent with other NFPA documents. 15-6 Log #11 Jeffrey W. Sutton, Global Risk Consultants New text to read as follows: Insert a new definition of 3.3.16 as follows: A type of automatic water spray system where water spray is applied in 500 milliseconds or less to protect specific hazards where deflagrations are anticipated. Renumber all other definitions accordingly. In the ammunition, propellant and explosives industries and in the U.S. Military, there is a very clear difference recognized between Ultra High Speed Deluge Systems and High Speed Deluge Systems, which is the amount of time required from detection of an event to water application. An Ultra High Speed Deluge System requires application of water within 100 milliseconds or less while a High Speed Deluge System requires application of water within 500 milliseconds or less. As currently written, NFPA 15 only applies to Ultra High Speed Deluge Systems, not High Speed Deluge Systems and it should apply to both. Several changes are needed to correct this situation, and this proposal is one of three being submitted to correct it. Introduction of a 500 millisecond response time could be confusing for users and lessen the level of protection in plants where rapidly spreading flame fronts are present. 3

15-7 Log #10 Jeffrey W. Sutton, Global Risk Consultants Revise the definition in 3.3.17 as follows: A type of automatic water spray system where water spray is rapidly applied in 100 milliseconds or less to protect specific hazards where deflagrations are anticipated. In the ammunition, propellant and explosives industries and in the U.S. Military, there is a very clear difference recognized between Ultra High Speed Deluge Systems and High Speed Deluge Systems, which is the amount of time required from detection of an event to water application. An Ultra High Speed Deluge System requires application of water within 100 milliseconds or less while a High Speed Deluge System requires application of water within 500 milliseconds or less. As currently written, NFPA 15 only applies to Ultra High Speed Deluge Systems, not High Speed Deluge Systems and it should apply to both. Several changes are needed to correct this situation, and this proposal is one of three being submitted to correct it. See Committee Action/Statement on 15- (Log #11) and 15- (Log #12). 15-8 Log #4 Raul Bustos Carrillo, ICA Fluor Daniel Revise and delete text to read as follows: Where steel pipe listed in Table 5.3.1 is joined by threaded fittings or by fittings used with pipe having cut grooves, the minimum wall thickness shall be in accordance with Schedule 30 [in pipe sizes 8 in. (203 mm) and larger] or Schedule 40 [in pipe sizes less than 8 in. (203 mm)] for pressures up to 300 psi (20.7 bar). "Screwed unions shall not be used on pipe larger than 2 in. (50 mm)." Due to the fact that both paragraphs seam to be against each other, it would be desirable to delete paragraph 5.4.8.1. Paragraph 5.3.3 does not limit threaded fittings. There is not a technical limitation to limit the use of threaded connections, because low working pressure, besides that are acceptable for small sizes. The language of 5.3.3 is already in the current edition of NFPA 15 and will remain. Screwed unions must be limited because of their lack of removability when required. 15-9 Log #CP3 Technical Committee on Water Spray Fixed Systems, Delete the current 5.3.10.1 and replace with the following: All pipe, including specially listed pipe allowed by 5.3.5, shall be marked continuously along its length by the manufacturer in such a way as to properly identify the type of pipe. 5.3.10.1 All pipe, including specially listed pipe allowed by 5.3.5, shall be marked along its length by the manufacturer in such a way as to properly identify the type of pipe. 5.3.10.2 The marking shall be visible on every piece of pipe over 2 ft (610 mm) long. A.5.3.10.1 Where approved, the pipe identification can be covered with paint or other protective coatings before installation. The proposal correlates to the requirements that were revised in the 2010 edition of NFPA 13 Section 6.3.8.1, 6.3.8.1 and A.6.3.8.1. 4

15-10 Log #CP6 Technical Committee on Water Spray Fixed Systems, Replace language of current 5.5.3 with the language on Grooved Joining Methods (6.5.3) from the 2010 edition of NFPA 13 as follows: Pipe joined with grooved fittings shall be joined by a listed combination of fittings, gaskets, and grooves. Grooves cut or rolled on pipe shall be dimensionally compatible with the fittings. Pipe joined with grooved couplings shall be joined by a listed combination of couplings, gaskets, and groove dimensions. Grooved connections of fittings and valves, and grooves cut or rolled on pipe shall be dimensionally compatible with the couplings. Grooved couplings, including gaskets used on preaction and deluge systems, shall be listed for dry pipe service. It is not the intent to require a listed combination of couplings, fittings, or valves. Material strength and pressure rating should be considered when determining compatibility. Correlation with revisions in NFPA 13, 2010 edition. 15-11 Log #CP4 Technical Committee on Water Spray Fixed Systems, Delete the current 5.11.4 and replace with the following: Piping to the water-motor-operated devices shall have corrosion resistance equal to or better than galvanized ferrous pipe and fittings and shall be of a size not less than 3/4 in. (20 mm). All piping to water motor-operated devices shall be galvanized steel, brass, copper, or other approved metallic corrosion-resistant material of not less than 3 / 4 in. (20 mm) nominal pipe size. Piping between the water spray system and a pressure actuated alarm-initiating device shall be galvanized steel, brass, copper, or other approved metallic corrosion-resistant material of not less than 3 / 8 in. (10 mm) nominal pipe size. Renumber remaining sections. The proposal correlates to the requirements that were revised in the 2010 edition of NFPA 13 Sections 6.9.3.3, and 6.9.3.4. 5

15-12 Log #14 E. Parks Moore, S & S Sprinkler Company, LLC Revise text to read as follows: ***Insert 15_L14_Table6.3.2.2.1_R*** The current table s information is limited and does not provide adequate guidance for support or larger diameter piping that is often encountered on larger fixed spray systems. This requires the need for involvement of a professional engineer to provide hanger designs and calculations for what should be a simple pre-engineered solution. The attached proposed table expands the allowable pipe stand diameter to include 4 and 6 pipe. It also includes guidelines for supporting 6 and 8 system piping. The values provided account for allowable compression stress and buckling load utilizing 5 X the maximum weight of water filled pipe plus 250 pounds. The committee realizes that larger pipe sizes are not addressed. The substantiation is not sufficient for the information that has been proposed. A task group has been formed to explore this issue and develop a comment for the committees consideration with appropriate substantiation for the revision. 15-13 Log #8 David R. Hague, Liberty Mutual Property Revise text as follows: Remote manual actuation devices shall be located so as to be conspicuous, unobstructed and accessible during an emergency. Provides guidance for the proper location of remote manual actuation devices. 15-14 Log #9 David R. Hague, Liberty Mutual Property Add new text as follows: The operable part of each remote manual actuation device shall be not less than 3 1 / 2 ft. (1.1m) and not more than 4 1 / 2 ft. (1.37m) above grade or floor level. Provides guidance for the proper location of remote manual actuation devices. 6

Table 6.3.2.2.1 Maximum Pipe Stand Height Pipe Stand Diameter Diam. Of Pipe 1 1 / 2 2 2 1 / 2 3 4 6 1 1 / 2 10 14 18 28 30 30 2 8 12 16 26 30 30 2 1 / 2 6 10 14 24 30 30 3 4 8 12 22 30 30 >3 in. 4 8 12 18 10 28 30 6 6 8 12 20 30 8 4 6 10 16 30 15_L14_Tbl6.3.2.2.1_R

15-15 Log #2 Robert M. Gagnon, Gagnon Engineering Revise text as follows: Emulsification is undefined in NFPA 15. The Committee should defer to NFPA 18-A. Dilution is undefined in NFPA 15. "Other Factors" is unclear and unenforceable. The Committee should define emulsification (an emulsion is "a suspension of small globules of one liquid in a second liquid with which the first will not mix"). Dilution defined is: "The process of making weaker or less concentrated". Other Factors: Delete or define. The submitter has not provided specific definitions or the necessity for the terms so the default at this time would be to use the dictionary term. 7

15-16 Log #CP5 Technical Committee on Water Spray Fixed Systems, Revise Section 7.5 Prevention of Fire to read as follows: Water spray systems designed for extinguishment, exposure protection, or control of burning can disperse flammable gases for fire prevention. When designing water spray systems primarily for dispersion of flammable gases (for fire prevention), the following should be considered: (1) Spray nozzles should be of the size and type to discharge a dense spray into the area of possible flammable vapor release at sufficient velocity to rapidly dilute the flammable vapors to a level below the lower flammable limit. (2) Spray nozzles should be positioned to provide coverage of potential leak sources such as flanges, flexible connections, pumps, valves, vessels, containers, and so forth. (3) The physical properties of the chemicals involved (including water solubility) in the hazard should also be considered. (4) Personnel should be notified upon vapor release. (5) Impairment procedures in accordance with NFPA 25 should be used for all water spray systems. A fire risk analysis shall be conducted. The following are some of the factors that shall be considered in determining the extent and method of fire protection required for vapor mitigation: (1) Importance to continuity of operation (2) Size, type, location and construction of equipment (3) Physical properties of the chemicals involved (4) Water supply (5) Value of equipment (6) Climate (7) Water delivery time (8) Environment (9) Access for firefighting (10) Projected flammable liquid or material spill pattern (11) Potential for flammable vapor release (12) Proximity of personnel to hazard area (13) Protection of system actuation valve from fire and explosion (14) Blast containment and pressure relief (15) Protection of electrical circuits, including explosion proof equipment (16) Potential for fire spread beyond hazard area (17) Required replacement time for process equipment (18) Potential for business interruption (19) Notification of personnel upon vapor detection Due to the unique characteristics of each fire risk, this standard does not provide comprehensive design criteria for vapor mitigation in all types of hazardous locations. Technology in this area is under constant development. The user of this standard should recognize the complexity of fire protection requirements for hazardous locations. The designer is responsible for demonstrating the validity of the design approach. The system shall be designed to operate as intended within the necessary time and shall discharge water for the duration needed time necessary to dissolve, dilute, disperse, or cool flammable vapor, gases, or hazardous materials. The duration of release of the flammable materials shall be included in the determination of the water spray duration time. The minimum net rate of application shall be based upon field experience with the product or upon actual test data. Flammable gas detection shall be accomplished with detectors in accordance with Section 6.5.2.7. Personnel shall be notified upon receipt of any detection signal in accordance with NFPA 72. This proposal is in response to recommendation 04-10-IL-R5 from the report of the Formosa Plastics Vinyl Chloride Monomer Explosion of April 23, 2004 in Illiopolis, IL published by the U.S. Chemical Safety and Hazard Investigation Board (attached). The recommendation as found on p. 49 of the report, reads as follows: 8

"04-10-I-IL-R5 Revise NFPA 15, Standard for Water Spray Fixed Systems for Fire Protection, to provide additional design guidance for deluge systems designed to prevent or mitigate fires and explosions. Include information concerning the limitations of using deluge systems for this purpose." The revised language for Section 7.5 is intended to provide the user with additional guidance on the application of water spray systems specifically intended for vapor mitigation and also provides guidance on the approach needed to conduct a fire risk analysis for such applications. 15-17 Log #7 David R. Hague, Liberty Mutual Property Add the word "friction" to Section 8.5.3.5 as follows: The friction loss of all fittings shall be calculated where a change in direction of the flow occurs, as follows: (1) The friction loss for a tee or a cross shall be calculated where the flow direction change occurs, based upon the equivalent pipe length for the smaller size of the tee or cross in the path of the turn. Friction Loss for that portion of the flow that passes straight through the run of a tee or a cross shall not be included. (2) The friction loss of reducing elbows shall be calculated based upon the equivalent length value in feet of the smallest outlet. (3) Friction loss shall be excluded for tapered reducers and for the fitting directly supplying the spray nozzle. Provides consistent wording - editorial. 9

15-18 Log #6 David R. Hague, Liberty Mutual Property. The contractor shall prepare and submit a set of as-built drawings and hydraulic calculations of the system, and maintenance and instruction bulletins., and the applicable parts of the The installing contractor shall complete the following: (1) Notify the authority having jurisdiction and the property owner or the property owner's authorized representative of the time and date that testing will be performed (2) Perform all required acceptance tests as required by this chapter (3) Complete and sign the contractor's material and test certificate(s) as indicted in Figures 10.1.2 (A) & (B) contractor's material and test certificates covering material and tests certifying that the work has been completed and tested in accordance with approved plans and specifications. *****Insert Figure 10.1.2(A) Here " "***** *****Insert Figure 10.1.2(B) Here " 13)***** " (from NFPA *****Insert Figures 10.1.2(A)and(B) here 15_L6_Fig10.1.2(A)and(B)_R.doc***** Clarifies commissioning requirements for water spray systems and coordinates these requirements with that of other systems standards such as NFPA 13 & 24. Remove the term Dry anywhere it appears in the form and add Ultra High Speed in those sections. Dry systems are not used for water spray systems and Ultra High Speed is and should be included in the form. 10

Contractor's material and Test Certificate for Water Spray System Property Information Building Name Building Address Owner's Name Owner's Address Owner's Phone/ Fax / E-mail System Designer / Contractor Company Name Address Contact Person Designer Qualifications Owner's Phone / Fax / E-mail Submittal Date: Log No.: File No.: Plan Examiner: Approval Date: Permit No.: General Building Type: New Existing Renovation Area: Construction Type: Fire Resistive Non-Combustible Ordinary Heavy Timber Wood Frame Mixed Occupancy Classification: Water Spray System Type Wet Dry Preaction Deluge Spray Sprinkler/nozzle Omitted in any areas? Yes No Spare sprinklers/nozzles provided? Yes No Sprinkler/nozzle wrench provided? Yes No Area of Coverage: Total Partial Special Hazard Other 15/L6/Figures10.1.2(A)and(B)/A2011/ROP

Contractor's material and Test Certificate for Water Spray System Fire Pump Fire Pump Provided? Yes No If yes, rated capacity: gpm @ psi Type of pump: Electric Diesel Steam Hydrostatic Test All piping tested at psi for hours Dry piping pneumatically tested? Yes No Equipment operates properly? Yes No Do you certify as the installing contractor that additives and corrosive chemicals, sodium silicate, brine or other corrosive chemicals were not used for testing systems or stopping leaks? Yes No Main Drain Test Static pressure psi Residual Pressure psi Alarm Valve or Flow Indicator Minimum Time to Operate Alarm Device Through Test Connection Type Make Model Minutes Seconds Dry Pipe Operating Test Dry Valve Make Model Serial No. Q.O.D. Make Model Serial No. Time to Trip Through Test Connection Water Pressure Air Pressure Trip Point Air Pressure Time Water Reached Test Outlet Alarm Operated Properly Minutes Seconds psi psi psi Minutes Sec Yes No Without Q.O.D. With Q.O.D. 15/L6/Figures10.1.2(A)and(B)/A2011/ROP

Contractor's material and Test Certificate for Water Spray System Deluge and Preaction Valves Operation Pneumatic Electric Hydraulic Piping Supervised? Yes No Detecting Media Supervised? Yes No Does valve operate from the manual trip, remote, or both control actions? Yes No Is there an accessible facility If no, explain. in each circuit for testing? Yes No Make Model Does Each Circuit Operate Does each circuit Maximum time to Supervision Loss Alarm? operate valve release? operate release? Yes No Yes No Min Sec Hydraulic Nameplate provided Data Nameplate Yes No Date left in service with all control valves open: If no, explain Tests Witnessed by Owner / Authorized Agent Title Date Owner / Authorized Agent Title Date Additional explanations / notes 15/L6/Figures10.1.2(A)and(B)/A2011/ROP

15-19 Log #12 Jeffrey W. Sutton, Global Risk Consultants Revise Chapter 12 as follows: This standard deals with fixed piped high speed and ultra high speed water spray systems. There are specialized self-contained ultra high speed deluge systems, which are outside the scope of this standard. The supervised systems can be used alone or with the high speed or ultra high speed systems discussed in this standard, which ever is applicable. Nonsupervised systems should not be used without fixed pipe high speed or ultra high speed backup as described in this standard, which ever is applicable. The following (no change to remainder of paragraph) High Speed and Ultra High Speed (no change to remainder of paragraph) Extinguishment of fires using high speed or ultra high speed water spray systems is accomplished by surface cooling, by dispersion or dilution of the combustible material, by cooling the expanding flame front, or by a combination of these factors. Examples of facilities where such systems are advantageous include rocket fuel manufacturing or processing, solid propellant manufacturing or handling, ammunition manufacturing, pyrotechnics manufacturing, and the manufacture or handling of other volatile solids, chemicals, dusts or gases. Other facilities where the very rapid application of water spray is desirable can be considered. Where used to protect process equipment, these systems will not prevent overpressures. This equipment should be protected in accordance with NFPA 68,, or NFPA 69.. High Speed and Ultra High Speed (no change to remainder of paragraph) (No Change) High Speed and Ultra High Speed (no change to remainder of paragraph) High Speed and Ultra High Speed (no change to remainder of paragraph) (No Change) (New) High Speed water spray systems shall be designed to have a response time of not more than 500 milliseconds. (Old 12.2.2) Ultra High Speed water spray systems shall be designed to have a response time of not more than 100 milliseconds. (Old 12.2.3) Faster response times than indicated in 12.2.2.3 shall be provided where required by the properties of the hazard being protected. (Old 12.2.4) In order to meet the response time criteria, high speed and ultra high speed water spray systems shall utilize water filled piping. close to the point of ignition as possible. Change figure title to read: such that the minimum density is applied uniformly over the entire hazard area. Change figure title to read: Nozzle(s) shall be placed as Nozzle(s) shall be spaced Change figure title to read: Where protection of personnel is required, coverage by the high speed or ultra high speed water spray system shall include locations where personnel are expected to be within the hazard area and their immediate means of egress. For additional information, refer to U.S. Department of Defense standards DOD 6055.09-STD,, and/or DOD 4145.26-M,. To protect personnel, the process equipment should be interlocked to shut down upon activation of the high speed or 11

ultra high speed water spray system... The minimum design density shall be 0.50 gpm/ft 2 [2 (L/min)/m 2 ] of area covered by the high speed or ultra high speed water spray system. As speed is a strong function of volumetric capacity, it is recommended that high speed and ultra high speed water spray systems be kept as small as possible. Tests have shown that systems having a capacity in excess of 500 gallons (1893 liters) are less likely to be capable of delivering water to the nozzles within the required 500 milliseconds for high speed water spray systems and 100 milliseconds for ultra high speed water spray systems. The capacities of various sizes of pipe are given in Table A.12.3.4 for convenience in calculating system capacity. System capacity shall be permitted to exceed 500 gallons (1893 liters) if the system design is such that the system response time required by 12.2.2 or 12.2.3, which ever is applicable, is met. speed water spray system. Hose connections shall not be permitted to be supplied by the high speed or ultra high The water supply pressure for a properly functioning high speed or ultra high speed water spray system shall be maintained such that it is available at the time a system functions. Initial pressure to a high speed or ultra high speed water spray system is ordinarily obtained from an elevated tank, a pressure tank, or an excess pressure pump. A fire pump can be used to provide the required flow and pressure after the system has started to operate. Change figure titles to read: Piping used in high speed or ultra high speed water spray systems shall comply with the requirements of Chapter 5. Trapped air in a high speed or ultra high speed water spray system dramatically increases system response time. Piping systems must be sufficiently sloped to allow removal of all trapped air. 12

High Speed and Ultra High Speed water spray systems shall be maintained in accordance with NFPA 25,, and NFPA 72,. In the ammunition, propellant and explosives industries and in the U.S. Military, there is a very clear difference recognized between Ultra High Speed Deluge Systems and High Speed Deluge Systems, which is the amount of time required from detection of an event to water application. An Ultra High Speed Deluge System requires application of water within 100 milliseconds or less while a High Speed Deluge System requires application of water within 500 milliseconds or less. As currently written, NFPA 15 only applies to Ultra High Speed Deluge Systems, not High Speed Deluge Systems and it should apply to both. Several changes are needed to correct this situation, and this proposal is one of three being submitted to correct it. Introduction of a 500 millisecond response time could be confusing for users and lessen the level of protection in plants where rapidly spreading flame fronts are present. 15-20 Log #CP7 Technical Committee on Water Spray Fixed Systems, Add a new sentence to the end of A.1.1.2 as follows: This standard does not provide specific design guidance for dry pipe or double interlock preaction systems. It is not the committees intent to prescribe a specific type of system and while dry pipe or double interlock preaction systems are not specifically addressed there is no prohibition against their potential use. 13

15-21 Log #1 KWANG-HOON KO, POSCO E&C Code 15, Annex B, figure 8.2(m) Hydraulic Calculation sheet At the point of nozzle identification & location F, the note is described as q=381.6(109.2/64.4)^1/2, Would you please check a numeral of 381.6? It is not clear to using some numeral. Change the following in Figure B.2(b) Pt = 64.4 gpm to psi Pt = 25.4 gpm to psi Pt = 28.5 gpm to psi. It appears that the reference to GPM should be PSI and perhaps that is what caused the confusion on the part of the submitter. The figure is used to illustrate pressure differential for velocity analysis at a specific junction in the system. 14