SECTION (15833) - HVAC POWER VENTILATORS

Similar documents
Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION EXHAUST FANS

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

A. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:

A. Codes and Standards that are Standard at the University:

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004)

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

SECTION AXIAL FANS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

Construction Standards Page

SECTION (15900) - INSTRUMENTATION AND CONTROL FOR HVAC

Modular Supply Make-Up Air Unit

A. Section Common Motor Requirements for HVAC Equipment: Fan motors.

SECTION FAN COIL UNITS

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork.

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems.

HVAC REPAIR/REPLACEMENT 07/18/12 SECTION HVAC - MAJOR EQUIPMENT

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS

SECTION CUSTOM INDOOR CENTRAL-STATION AIR-HANDLING UNITS For large systems, 50,000 cfm or more.

Direct Fired Heater Model AD Specification

Direct Gas-Fired Make-Up Air

University of Houston Master Construction Specifications Insert Project Name

SECTION (15820) - AIR DUCT ACCESSORIES

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

SECTION AIR HANDLING UNIT

Indirect Gas-Fired Make-Up Air

UNIVERSITY OF ROCHESTER DESIGN STANDARDS NOVEMBER 1, 2013

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No

SECTION AIR DUCT ACCESSORIES

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

SECTION (15767) - UNIT HEATERS

Turning Air Into Solutions. TUBEAXIAL PAINT SPRAY BOOTH EXHAUST FANS. Model TCBS

Modular Heating & Ventilating Unit Model IGX-HV

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - "Systems and Equipment.

SECTION CONVECTION HEATING AND COOLING UNITS

SECTION AIR COILS

Selecting the Correct Fan

1.1 This section applies to air handling units for HVAC Systems.

JM Aerofoil Fans Bulletin JMA60-05

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

A. This Section includes air-handling units with coils for indoor installations.

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION COMPRESSED-AIR EQUIPMENT FOR LABORATORY FACILITIES

MXI Mixed Flow Inline Fan

Glossary of Terms Laboratory & Fume Exhaust Fans

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

SECTION DOMESTIC WATER PUMPS

SECTION (16460) - LOW-VOLTAGE TRANSFORMERS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

A. Operation and Maintenance Data: For pumps to include in emergency, operation, and maintenance manuals.

SECTION (13900) - FIRE SUPPRESSION SYSTEMS

SECTION AIR OUTLETS AND INLETS

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters.

A. Section includes factory-packaged units capable of supplying up to 100 percent outdoor air and providing cooling and heating.

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

SECTION AIR COOLED WATER CHILLERS

15900 HVAC INSTRUMENTATION AND CONTROLS

SECTION COMPUTER ROOM AIR CONDITIONING SYSTEMS

SECTION WATER-SOURCE UNITARY HEAT PUMPS

SECTION AIR DOORS

Industrial Fans & Blowers

Copyright 2003 and 2005 by The American Institute of Architects (AIA) Modified by MSU Physical Plant / Engineering and Architectural Services

C. Samples for Initial Selection: For units with factory-applied color finishes.

Contents INDEX. TDM Series Indirect Fired Heaters

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise Modular Climate Changer Full Spec. Prepared by: Phone Number: Prepared for:

SECTION (15530) - REFRIGERANT PIPING

A. Standards: Except where modified or exceeded by the requirements of this Specification, conform to the following standards:

SECTION (15733) - DEDICATED OUTDOOR AIR UNITS

SECTION SPRINKLER SYSTEMS

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION COOLING TOWERS

SECTION COOLING TOWERS

SECTION ELECTRIC-DRIVEN, FIRE PUMPS

Bulletin FH05 FUME EXHAUST

A. Section Common Motor Requirements for HVAC Equipment: Fan motors.

SECTION COMMERCIAL-KITCHEN HOODS

Belt Driven Mixed Flow Fans

SECTION AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS

B. Section Identification for Fire Suppression Piping and Equipment.

Plenum Fans. Model HPA. Direct Drive

SECTION ROOFTOP REPLACEMENT AIR UNITS

CONTENTS. B. System Design and Performance Requirements

D. NEMA Compliance: Provide electric motors and components which comply with NEMA standards.

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS

SECTION STEAM CONDENSATE PUMPS

SECTION ROTARY-SCREW WATER CHILLERS

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters.

SECTION DUCTWORK

Transcription:

PART 1 GENERAL 1.01 SUMMARY SECTION 23 34 23 (15833) - HVAC POWER VENTILATORS A. Section Includes: 1. Centrifugal Roof Ventilators. 2. Up-blast Roof Exhaust Fans (Kitchen Hood Exhaust). 3. Ceiling-Mounted Ventilators. 4. In-Line Centrifugal Fans. 5. Motors 6. Factory Finishes 7. Quality Control B. Related Sections: 1. Section 23 05 00 (15050) Common Work Results for HVAC 2. Section 23 05 48 (15070) - Mechanical Sound, Vibration and Seismic Control. 3. Section 23 05 53 (15075) Identification for HVAC Piping and Equipment 4. Section 23 05 13 (15090) Common Motor Requirements for HVAC Equipment 5. Section 23 05 93 (15950) - Testing, Adjusting, and Balancing for HVAC 6. Section 23 09 00 (15900) Instrumentation and Control for HVAC 7. Section 26 29 13 (16420) - Enclosed Controllers: For motor starters. 8. Section 26 51 00 (16510) Interior Lighting: Light Fixture Matrix For Guestroom Toilet Ceiling Mounted Ventilators. C. Products Supplied But Not Installed Under This Section: 1.02 REFERENCES 1. Roof curbs for roof-mounted exhaust fans. A. Air Movement & Control Association International, Inc. (AMCA) Publications: 1. 99 "Standards Handbook" (Revised 2003) 2. 210 "Laboratory Methods of Testing Fans for Aerodynamic Performance Rating" 3. 300 "Reverberant Room Method for Sound Testing of Fans" 4. 301 "Methods for Calculating Fan Sound Ratings from Laboratory Test Data" B. ASTM International (ASTM) Publications: (Former American Society for Testing and Materials) 1. B117 "Standard Practice for Operating Salt Spray (Fog) Apparatus" C. National Electrical Manufacturer s Association (NEMA) Standards Publications: 1. MG 1 Motors and Generators D. National Fire Protection Association (NFPA) Publications: 1. 70 "National Electric Code" E. Underwriter's Laboratories, Inc. (UL) Publications: PAGE 1 FILE: 23-233423-CFRST-HVAC Power Ventilators REVISED: 09/03/13 2013, Marriott International, Inc. CFRST SPECMSTR-NEW BUILD

REVISED: 09/03/13 1. 486A Standard For Wire Connectors and Soldering Lugs for Use With Copper Conductors 2. 486B Standard for Wire Connectors for Use With Aluminum Conductors 3. 705 Standard for Power Ventilators 1.03 PERFORMANCE REQUIREMENTS A. Project Altitude: Base air ratings on actual site elevations. B. Operating Limits: Classify according to AMCA 99. C. Fan Schedule: The following information is described in an equipment schedule on the Drawings. 1. Fan performance data including capacities, outlet velocities, static pressures, sound power characteristics, motor requirements, and electrical characteristics. 2. Fan arrangement including wheel configuration, inlet and discharge configurations, and required accessories. 1.04 QUALITY ASSURANCE A. Electrical Component Standard: Provide components that comply with NFPA 70 and that are listed and labeled by UL where available. B. Listing and Labeling: Provide electrically operated fixtures specified in this Section that are listed and labeled. 1. The Terms "Listed" and "Labeled": As defined in the National Electrical Code, Article 100. C. AMCA Compliance: Provide products that meet performance requirements and are licensed to use the AMCA Seal. D. NEMA Compliance: Provide components required as part of fans that comply with applicable NEMA standards. E. UL Standard: Provide power ventilators that comply with UL 705. 1.05 PROJECT CONDITIONS A. Field Measurements: Verify dimensions by field measurements. Verify clearances. B. Do not operate fans until ductwork is clean, filters are in place, bearings are lubricated, and fans have been commissioned. 1.06 COORDINATION AND SCHEDULING A. Coordinate the size and location of structural steel support members. B. Coordinate the installation of roof curbs, equipment supports, and roof penetrations. Roof specialties are specified in Division 07 Sections. 1.07 EXTRA MATERIALS A. Furnish extra materials described in Section 01 78 43 (01790) Spare Parts and Materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. PART 2 PRODUCTS 2.01 MANUFACTURERS A. Approved Manufacturers: PAGE 2 FILE: 23-233423-CFRST-HVAC Power Ventilators CFRST SPECMSTR-NEW BUILD 2013, Marriott International, Inc.

1. Centrifugal Roof Ventilators: 2. Up-blast Roof Exhaust Fans: 3. Ceiling-Mounted Ventilators: e. Broan-NuTone LLC (888-336-6151) f. Panasonic Corporation of North America (866-292-7292) 4. In-Line Centrifugal Fans: 5. Attic Ventilators: 2.02 CENTRIFUGAL ROOF VENTILATORS A. Description: Belt-driven or direct-drive centrifugal fans, as indicated, consisting of housing, wheel, fan shaft, bearings, motor and disconnect switch, drive assembly, curb base, and accessories. B. Housing: Removable, spun-aluminum, dome top and outlet baffle; square, one-piece, aluminum base with venturi inlet cone. C. Fan Wheels: Aluminum hub and wheel with backward-inclined blades. D. Belt-Driven Drive Assembly: Resiliently mounted to the housing, with the following features: 1. Fan Shaft: Turned, ground, and polished steel drive shaft keyed to wheel hub. 2. Shaft Bearings: Permanently lubricated, permanently sealed, self-aligning ball bearings. PAGE 3 FILE: 23-233423-CFRST-HVAC Power Ventilators REVISED: 09/03/13 2013, Marriott International, Inc. CFRST SPECMSTR-NEW BUILD

3. Pulleys: Cast-iron, adjustable-pitch motor pulley. 4. Fan and motor isolated from exhaust air stream. E. Accessories: The following items are required as indicated: 1. Variable-Speed Controller: Solid-state control to reduce speed from 100 percent to less than 50 percent. (Direct drive fans only). 2. Disconnect Switch: Nonfusible type, with thermal-overload protection mounted inside fan housing, factory wired through an internal aluminum conduit. 3. Bird Screens: Removable 1/2-inch mesh, aluminum or brass wire. 4. Dampers: Counterbalanced, parallel-blade, backdraft dampers mounted in curb base; factory set to close when fan stops. 5. Roof Curbs: Galvanized steel; mitered and welded corners; 2-inch- thick, rigid, fiberglass insulation adhered to inside walls; and 2-inch wood nailer. Size as required to suit roof opening and fan base. Built-in cant and mounting flange. a. Overall Height: 12 inches. Minimum. 2.03 UPBLAST ROOF EXHAUST A. Description: Belt-driven or direct-driven centrifugal fans consisting of housing, wheel, fan shaft, bearings, motor and disconnect switch, drive assembly, curb base, and accessories. B. Housing: Removable, spun-aluminum, square one-piece, aluminum base with venturi inlet cone. 1. Up-blast Units: Provide spun-aluminum discharge baffle to direct discharge air upward, with rain and snow drains and grease collector. C. Fan Wheels: Aluminum hub and wheel with backward-inclined blades. D. Belt-Driven Drive Assembly: Resiliently mounted to housing, with the following features: 1. Fan Shaft: Turned, ground, and polished steel; keyed to wheel hub. 2. Shaft Bearings: Permanently lubricated, permanently sealed, self-aligning ball bearings. 3. Pulleys: Cast-iron, adjustable-pitch motor pulley. 4. Fan and motor isolated from exhaust airstream. E. Accessories: 1. Disconnect Switch: Non-fusible type, with thermal-overload protection mounted inside fan housing, factory wired through an internal aluminum conduit. 2. Bird Screens: Removable, ½ inch(13-mm) mesh, aluminum or brass wire. 3. Motorized Dampers: Parallel-blade dampers mounted in curb base with electric actuator; wired to close when fan stops. F. Roof Curbs: Galvanized steel; mitered and welded corners; 1-1/2 inch thick, rigid, fiberglass insulation adhered to inside walls with galvanized steel metal liner; and 1-1/2 inch wood nailer. Size as required to suit roof opening and fan base. G. Coordinate control of kitchen hood exhaust fans with Melink Intelli-Hood system or CaptiveAire EMS system. REVISED: 09/03/13 PAGE 4 FILE: 23-233423-CFRST-HVAC Power Ventilators CFRST SPECMSTR-NEW BUILD 2013, Marriott International, Inc.

2.04 CEILING-MOUNTED VENTILATORS A. Description: Centrifugal fans designed for installing in ceiling or wall, or for concealed in-line applications. B. Housing: Galvanized steel lined with acoustical insulation. C. Fan Wheel: Centrifugal wheels directly mounted on motor shaft. Fan shrouds, motor, and fan wheel shall be removable for service. D. Grille: Aluminum, louvered grille or egg-crate with flange on intake and thumbscrew attachment to fan housing. E. Electrical Requirements: Junction box for electrical connection on housing and receptacle for motor plug-in. F. Variable-Speed Controller Mounted on Fan Housing: Solid-state control to reduce speed from 100 percent to less than 50 percent. G. Sound Level: Guestroom Toilets shall have a maximum of 0.3 Sones per HVI 915 Procedure for Loudness Rating of Residential Fan Products Refer to Light Fixture Matrix for approved manufacturers and models. H. Accessories: Manufacturer's standard roof jack or wall cap, and transition fittings. 2.05 IN-LINE CENTRIFUGAL FANS A. Description: In-line, belt-driven, or direct-drive centrifugal fans consisting of housing, wheel, outlet guide vanes, fan shaft, bearings, drive assembly, motor and disconnect switch, mounting brackets, and accessories. B. Housing: Split, spun-aluminum housing, with aluminum straightening vanes; inlet and outlet flanges; and support bracket adaptable to floor, side wall, or ceiling mounting. C. Direct-Drive Units: Motor encased in housing out of air stream, factory wired to disconnect located on outside of fan housing. D. Belt-Driven Units: Motor mounted on adjustable base, with adjustable sheaves, enclosure around belts within fan housing, and lubricating tubes from fan bearings extended to outside of fan housing. E. Fan Wheels: Aluminum, airfoil blades welded to aluminum hub. F. Accessories: The following accessories are required as indicated: 1. Volume-Control Damper: Manually operated with quadrant lock, located in fan outlet. 2. Companion Flanges: For inlet and outlet duct connections. 3. Fan Guards: Expanded metal in removable frame. Provide fan guards for units not connected to ductwork. 2.06 ATTIC VENTILATORS A. Description: Roof mounted, direct drive, propeller fan consisting of housing, wheel, motor drive, thermostat. B. Housing: Heavy gauge aluminum dome with insect screen, splash guard, heavy gauge aluminum flashing. C. Motor Drive: Thermally protected, permanently protected motor. D. Wheel: Aluminum propeller and hub construction. E. Thermostat: Single stage line voltage thermostat with 55 to 130 F. range, bimetal actuated. PAGE 5 FILE: 23-233423-CFRST-HVAC Power Ventilators REVISED: 09/03/13 2013, Marriott International, Inc. CFRST SPECMSTR-NEW BUILD

2.07 MOTORS A. Refer to Section 23 05 13 - "Common Motor Requirements for HVAC Equipment" for general requirements for factory-installed motors. B. Motor Construction: NEMA MG 1, general purpose, continuous duty, Design B. C. Enclosure Type: The following features are required as indicated: 1. Open dripproof motors where satisfactorily housed or remotely located during operation. 2.08 FACTORY FINISHES A. Sheet Metal Parts: Prime coat before final assembly. B. Exterior Surfaces: Baked-enamel finish coat after assembly. C. Aluminum Parts: No finish required. 2.09 SOURCE QUALITY CONTROL A. Testing Requirements: The following factory tests are required as indicated: 1. Sound Power Level Ratings: Comply with AMCA 301, "Methods for Calculating Fan Sound Ratings From Laboratory Test Data." Test fans according to AMCA 300, "Reverberant Room Method for Sound Testing of Fans." Label fans with the AMCA Seal. 2. Fan Performance Ratings: Establish flow rate, pressure, power, air density, speed of rotation, and efficiency by factory tests and ratings according to AMCA 210, "Laboratory Methods of Testing Fans for Rating." PART 3 EXECUTION 3.01 EXAMINATION A. Examine areas and conditions for compliance with requirements of installation tolerances and other conditions affecting performance of the power ventilators. Do not proceed with installation until unsatisfactory conditions have been corrected. 3.02 INSTALLATION A. Install power ventilators according to manufacturer's written instructions. B. Support units using the vibration-control devices indicated. Vibration-control devices are specified in Section 23 05 48 - "Vibration, and Seismic Control for HVAC Piping and Equipment." 1. Secure roof-mounted fans to roof curbs with cadmium-plated hardware. a. Installation of roof curbs is specified in Division 07 Sections. 2. Suspend units from structural steel support frame using threaded steel rods and vibration isolation springs. 3. Ceiling Units: Suspend units from structure using steel wire or metal straps. C. Install units with clearances for service and maintenance. D. Label units according to requirements specified in Section 23 05 53 "Identification for HVAC Piping and Equipment." REVISED: 09/03/13 PAGE 6 FILE: 23-233423-CFRST-HVAC Power Ventilators CFRST SPECMSTR-NEW BUILD 2013, Marriott International, Inc.

3.03 CONNECTIONS A. Duct installation and connection requirements are specified in other Division 15 Sections. Drawings indicate the general arrangement of ducts and duct accessories. Make final duct connections with flexible connectors. B. Electrical: Conform to applicable requirements in Division 26 Sections. C. Grounding: Ground equipment. Tighten electrical connectors and terminals, including grounding connections, according to manufacturer's published torque-tightening values. Where manufacturer's torque values are not indicated, use those specified in UL 486A and UL 486B. Note: Paragraph below is for use with Type I kitchen exhaust hoods.marriott Module 15 has the Melink Intelli-Hood or CaptiveAire EMS demand control ventilation system listed as a franchise option. D. Controls: Melink Intelli-Hood or CaptiveAire EMS ] System for kitchen hood exhaust fans. 3.04 FIELD QUALITY CONTROL A. Manufacturer's Field Service: Provide services of a factory-authorized service representative to supervise the field assembly of components and installation of fans, including duct and electrical connections, and to report results in writing. 3.05 ADJUSTING A. Adjust damper linkages for proper damper operation. B. Adjust belt tension. C. Lubricate bearings. 3.06 CLEANING A. After completing installation, inspect exposed finish. Remove burrs, dirt, and construction debris, and repair damaged finishes including chips, scratches, and abrasions. B. Clean fan interiors to remove foreign material and construction debris. Vacuum clean fan wheel and cabinet. 3.07 COMMISSIONING A. Final Checks before Startup: Perform the following operations and checks before startup: 1. Verify that shipping, blocking, and bracing are removed. 2. Verify that unit is secure on mountings and supporting devices and that connections for piping, ducts, and electrical components are complete. Verify that proper thermaloverload protection is installed in motors, starters, and disconnects. 3. Perform cleaning and adjusting specified in this Section. 4. Disconnect fan drive from motor, verify proper motor rotation direction, and verify fan wheel free rotation and smooth bearing operation. Reconnect fan drive system, align and adjust belts, and install belt guards. 5. Lubricate bearings, pulleys, belts, and other moving parts with factory-recommended lubricants. 6. Verify that manual and automatic volume control and fire and smoke dampers in connected ductwork systems are in the fully open position. 7. Disable automatic temperature-control operators. B. Starting procedures for fans are as follows: PAGE 7 FILE: 23-233423-CFRST-HVAC Power Ventilators REVISED: 09/03/13 2013, Marriott International, Inc. CFRST SPECMSTR-NEW BUILD

1. Energize motor; verify proper operation of motor, drive system, and fan wheel. Adjust fan to indicated RPM. 2. Measure and record motor voltage and amperage. 1. Test control integration of Melink Intelli-Hood or CaptiveAire EMS Plus System for kitchen hood exhaust fans. C. Shut unit down and reconnect automatic temperature-control operators. D. Refer to Section 23 05 93 "Testing, Adjusting, and Balancing for HVAC" for procedures for airhandling-system testing, adjusting, and balancing. E. Replace fan and motor pulleys as required to achieve design conditions. 3.08 DEMONSTRATION A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain units. 1. Conduct training as specified in Section 01 79 00 (01820) "Training. 2. Train Owner's maintenance personnel on procedures and schedules related to startup and shutdown, troubleshooting, servicing, and preventive. END OF SECTION REVISED: 09/03/13 PAGE 8 FILE: 23-233423-CFRST-HVAC Power Ventilators CFRST SPECMSTR-NEW BUILD 2013, Marriott International, Inc.