SERVICE MANUAL REFRIGERATED AIR DRYER DIGI-PRO CONTROLLER WARRANTY NOTICE

Similar documents
Label Displayed temperature Pb1 if the P4 parameter is set to 0, 1 or 2, room temperature if the P4 parameter is set to 3, incoming air temperature

DIMENS. MIN TYPICAL MAX A 71.0 (2.795) 71.0 (2.795) 71.8 (2.826) B 29.0 (1.141) 29.0 (1.141) 29.8 (1.173)

Refrigerated air dryers

User Guide ems25plus. Page 1. Normal operation. Product interface

EVF818 Installer manual ver. 1.0 Code 144F818E104 EVF818. Split execution controller for temperaturecontrolled

EVF815 Installer manual ver. 2.0 Code 144F815E204 EVF815

EasyTronic III MANUAL SERVICE

Dixell Installing and Operating Instructions release 7.0

Follett Performance Plus

Updated: 17/03/2010 ELECTROLUX. CAREL ir33. Quick reference Handbook. Ver. 1.1 Eng. Pag.1/12

WATER HEATER ELECTRONIC CONTROLLER USER MANUAL

SmarTemp Control fx 2.0

CAREL CONTROLLER. Programming Instructions HOW TO CHANGE LEVEL 1 CONTROL SETTINGS HOW TO CHANGE LEVEL 2 CONTROL SETTINGS

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB

User Manual. Dryer Controller M720

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

50110_HM-neoStat-2014_Layout 1 31/10/ :33 Page 1 neo

CAREL IR33+ CONTROLLER

Dryer Controller M720

User Manual Ichill 200 L/D (Firmware version 1.7)

SA-3841 User Manuel. 1U 4 Fans Unit with Thermostat Sensor. Version 1.1 Copyright All Rights Reserved

ST710-KHJV.03. Wiring diagram. Product description. Temperature controller. Order number

ST Wiring diagram. Product description. Four-stage controller. Order number

i.c³ User Guide For Helmer i.series Ultra-Low Freezers A/A

Table of Contents. Product Image Table of Contents What is a Programmable Room Thermostat? Installation Procedure

EXPERT TRI-STAR. Temperature controller. User s Manual

ST Wiring diagram. Product description. Standard temperature controller. Order number

REMOTE CONTROL FOR CHILLER MYCHILLER

Tempered Water Logic Control OPERATION l TROUBLE SHOOTING

Important information. Government Regulations and Safety information. Your Warranty. Replacement remote controls

Table of Contents. Product Image 1 Locking/Unlocking the neoair 24 Table of Contents 2 Frost Protection 25 What is a Programmable Room Thermostat?

EWCM 900/S rel. 5/2000 ing

INSTALLATION & USER MANUAL

Table of Contents. Model: Series. Available in : Sapphire Black and Glacier White. Product Image. 20 Table of Contents.

User Manual. Digi-Sense TC9500 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs

NO ONE DARES COME CLOSE O WNER S GUIDE 7756V

AC&R Controller RWR Basic Documentation VR2002 for water to water heat pump units

PONY 2/4 User Guide 2017

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Owner s Manual. Walk-in Monitoring System 100B. Cooler is Better! TM. Used in UL Listed Door Panel Assemblies

CONTROL PANEL INSTRUCTIONS RSQ-4

GSM Alarm System. User s Manual. Profile. MOBILE CALL GSM Alarm System

Model: Available in : Sapphire Black and Glacier White. 1 Series

EC 6-295P220S001. smart guide 2 OPERATION. 2.1 How to turn the instrument ON/OFF. If you have to turn the instrument ON/OFF:

Operating instructions Page 14

technical bulletin Control Link RSC Installation Instructions

OPERATING INSTRUCTIONS. G214 Software - Version 4

PF1000 CONTROLLER. for the. Heateflex Corporation 405 E. Santa Clara St. Arcadia, CA TEL: (626) ; FAX: (626)

Millennium Xtra. Millennium ATMA setup and configuration guide. May Millennium Group, Inc.

MODEL URS-1: FACTORY RETROFIT PROGRAM

Digital Marine Exhaust Temperature Alarm

User Manual. Digi-Sense TC9600 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs

URS-1 SERVICE AND PARTS MANUAL SERIAL NUMBERS: UP TO

Operating instructions Page 14. Refrigerator Read the operating instructions before switching on for the first time

Operating instructions Page 14. Freezer Read the operating instructions before switching on for the first time

DIGITAL TEMPERATURE RELAY TR-100

Operating instructions Page 14

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING

User manual CLIMATIC 200/400 - Controller. Providing indoor climate comfort

System. For a better understanding of this product, please read this user manual thoroughly before using it.

IN NOURISHING SECURITY.

Analog Room Pressure Monitor RPC Series

SCHMIDT LED Measured Value Display MD Instructions for Use

QUICK REFERENCE GUIDE SERIES IC100CX FW 1.8 (rel. 1.0)

USER S MANUAL. Profile. MOBILE CALL GSM Alarm System

12V. Model: Available in : Sapphire Black and Glacier White. 2 Series

INSTRUCTION MANUAL Portable Refrigerator Units MODEL 15-LITER Including the Standard Battery Backup System (BBS)

EXD-HP1/2 Stand-alone Superheat/Economizer Controller

PRODUCT BULLETIN. Rev. A Monitoring Station offering PN Rev. B as a direct replacement. OVERVIEW / DESCRIPTION

Model: 1 Series 12V. Available in: Sapphire Black and Glacier White

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

OPERATION AND MAINTENANCE MANUAL

Model: Available in: Sapphire Black and Glacier White. 1 Series

XC1008D -XC1011D- XC1015D and VGC810

ViewMatrix. Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels. Version: 2.0 Revision: 0.1

Toll Free: Tel: Fax:

Container Refrigeration

ELECTRONIC AIR CONDITIONING CONTROL

GMH 285 / GMH 285-BNC

Modular Standard HP Chiller 1/4 screw compressor with Carel driver

PL-1 Thermostat User s Guide

XWA11V. Walk-In Temp / Door /Alarm / Light Module

TDU Series LCD Thermostat For EFCB and EVCB Controllers. Models. Features. Functions. Onboard Sensors. Model # Temp RH CO2 Color.

Refrigeration and Air Conditioning Controls. User s manual. Degree Master Controller in AKC 55 Systems ADAP-KOOL REFRIGERATION AND AIR CONDITIONING

Networkable Fan Coil Controller Specification and Installation Instructions

WiFi Hints & Tips. Contents. WiFi Hints and Tips 1. Page No. Section No. Title

HTD. High Temperature Non-Cycling Refrigerated Compressed Air Dryers. Operation & Maintenance Manual. MODELS HTD 21 thru HTD 100

USB Multi Function Dataloggers. RHT30 Humidity/Temperature Datalogger. TH30 Dual Temperature Datalogger

Ver.04 IP 65 FRONT. Serial programming. Protection level FAST FREEZING (ON/OFF) ECONOMIC SETPOINT(ON/OFF) DEFROST (ON/OFF) FUNCTIONS LOCKDOWN

ELECTRONIC THERMOSTAT AND THERMOMETER With SPEED CONTROL

ECB Specification: Electric control box: W 300 * H 400 * D 150 (mm)

ER65-DRW Controller. Heating Applications. Product Bulletin. Heating Controller

SyringeHeater.com. Syringe Heater. Thermo-Kinetic Heat Clamping. Model: HEATER-KIT-1LG HEATER-KIT-5SP

Operating Manual UV Monitor UVT 18

ER65 - Mini Rack Controller Electronic Refrigeration Line

OPTIONAL SLIT TUBING RECOMMENDED (AVAILABLE AT MOST HARDWARE STORES) Violet Grey. +12v Dash Lighting (See Lighting Mode)

Electro-Sentry. Users Manual

Air Comfort. Installation instructions (English) A

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

XWA11V-KIT Walk-In Temp / Door /Alarm / Light Module with Mounting Box and Wiring

Transcription:

REFRIGERATED AIR DRYER SERVICE MANUAL DIGI-PRO CONTROLLER WARRANTY NOTICE Failure to follow the instructions and procedures in this manual or misuse of this equipment will VOID any warranty.

1. USER INTERFACE During normal operation the display shows the evaporation temperature. 1.1. Showing machine status 1. To disable the Key Lock: Press and hold SET for 4 seconds 2. Press and hold the DOWN arrow for 4 seconds: the display will show Pb1. 3. Press and release the UP or DOWN arrows to select the setting you want to view: - Pb1 heat exchanger probe - hse running hours for unit - rhs reset running hours for unit - hfi running hours for filter - rhf reset running hours for filter - rfi reset filter alarm 4. To reset the value, press and release SET, press and release the UP arrow to set 149 for rhf and rfi 171 for rhs Then press and release SET: the display will show - - - flashing for 4 seconds. 2. OPERATION During normal operation, the digital controller display shows the evaporation temperature. Picture 1 Digi Pro Controller View Using the Digi Pro controller as shown in the table below: Page 2

2.1 Menu Buttons PROGRAM POWER MENU MANUAL DRAIN To modify the parameters, press and release SET. This should be used by service team This button is used for starting and stopping the dryer. Press and hold for 4 seconds to start or stop. These buttons are used to navigate between screens and adjust values. This button is used for manual control of the drain output. Press and hold for 4 seconds to drain manually. Please contact service when an alarm/warning occurs. 2.2 Mode Display DRYER ACTIVE MODE This mark indicates that the dryer is in an active state and drying. AUTOMATIC DRAIN MODE Shows if the drain system is activated. ENERGY SAVING MODE CELSIUS UNIT MODE Shows if the energy saving mode is activated Indicates that Celsius temperature is selected. FAHRENHEIT UNIT MODE Indicates that Fahrenheit temperature is selected. COMPRESSOR STANDBY MODE This mode shows that the dryer is ready for drying operation. SERVICE MODE This mode shows that the dryer has reached service time. Page 3

2.3 Alarm Display Alarms / warnings are displayed on the digital screen. This means the dryer is not working under normal operating conditions or conditions which are outside the range of set values. Alarm Code Alarm Description Reason for Alarm tal Low Temperature Alarm Refrigerant line temperature is lower than specified set values tah High Temperature Alarm Refrigerant line temperature is higher than specified set values FIL Filter Change Alarm Filter element needs to be replaced SEr General Service Alarm General service time of the dryer HPr High Pressure Alarm Refrigerant line pressure is higher than specified set values Pr1 Temperature Probe Alarm Temperature sensor is faulty. hfi Running Hours Alarm The dryer running hours allowed has been reached. Please contact service if an alarm/warning occurs. 3. ALARMS 3.1 Alarm Output - if a low temperature alarm occurs ( the display shows the code tal ) - if a high temperature alarm occurs (the display shows the code tah ) - if the filter needs changed (the display shows the code FIL ) - if a high pressure alarm occurs (the display shows the code HP or HPr ) - if a compressor or fan condenser alarm occurs (the display shows the code COH or CSd ) - if the compressor exceeds the running hours allowed ( the display shows the code SEr and the service LED lights up.) - if the filter element exceeds the running hours allowed ( the display shows the code FIL and the service LED lights up.) 3.2 Device / Compressor Running Hours for SEr Parameter sets to record the device running hours or the compressor running hours. When the running hours overtakes the hours, the display shows the code SEr alternated to the temperature read by the heat exchanger, LED service is lit and the device works normally. To show/cancel the compressor running hours have a look at chapter 1 USER INTERFACE (labels hse and rhs). Page 4

3.3. Device/compressor runtime for FIL Parameter sets to record the device runtime or the compressor runtime. When the runtime reaches set limit, the display shows the code FIL replacing the temperature read by the heat exchanger, service LED is lit and the device works normally. To show/cancel the compressor runtime have a look at chapter 1 USER INTERFACE (labels hse and rhs). 3.4. Input change filter The activation of this input triggers the display showing the code FIL alternated to the temperature read by the heat exchanger, LED service is lit and the device works normally. Restoring the normal operation works the same way as cancelling the filter runtime (look for label rfi) 3.5. High Pressure alarm During this alarm the compressor is switched off. 3.6. Condenser Fan If one output is configured as condenser fan, parameters are relevant, as follows. If just one of the input terminal pairs, 11-10 or 9-10, is configured as fan activation, the input activation also activates the output. If the input terminal pair 11-10 is configured as condenser probe, the fan will be switched on when the compressor is switched on; as soon as the compressor switches off, the fan keeps in being switched on for the time F1, then it works according to temperature F0 (the fan switches off when the temperature falls below the temperature F0 and switches on when the temperature rises above F0 + 2 C/4 F. If the condenser probe is in error, the fan is switched on if the compressor is switched on and is switched off if the compressor is switched off (in this last case the fan is switched off with the delay F1 since the compressor switches off). If the input terminal pair 11-10 is configured as condenser fan and the input terminal pair 9-10 is configured as fan activation, input terminal pair 11-10 has priority over the input terminal pair 9-10. If no input is configured to manage the fan, this is switched on if the compressor is switched on, and switched off if the compressor is switched off (in this last case the fan is switched off with the delay F1 since the compressor switches off). In case of COH and CSd alarm the fan is switched on; the fan LED shows the status of the output. 3.7. Drain Test Press and hold button UP 4 s: the relay will be turned on as long the button is pressed. When the button is released the valve restores its cyclical operation. Page 5

Follow the steps below to reset the filter alarm: To reset the filter alarm, you need to enter the service domain and then access the rhf section. Please follow the steps carefully. Table 1 Steps to reset the filter alarm 1 Main page To disable the Key Lock: Press and hold the SET button for 4 sec 2 Key Lock Loc appears while holding the SET button for 4 sec 3 UnL appears when key lock is released 4 To access service menu (Pb1): Press and hold the menu button for 4 sec. 5 Pb1 appears when service menu is opened 6 To access rhf, use the menu keys 7 Press the SET button to password section after access the rhf section. 8 Enter 149 in the password field 9 The press and release button SET: the display will show - - - 4 sec flashing 10 The main page appears after this operation Page 6

Follow the steps below to reset the service alarm: To reset the service alarm, you need to enter the service domain and then access the rhs section. Please follow the steps carefully. Table 2 Steps to reset the service alarm 1 Main page To disable the Key Lock: Press and hold the SET button for 4 sec 2 Key Lock Loc appears while holding the SET button for 4 sec 3 UnL appears when key lock is released 4 To access service menu (Pb1): Press and hold the menu button for 4 sec. 5 Pb1 appears when service menu is opened. 6 To access rhs, use the menu keys 7 Press the SET button to password section after access the rhf section. 8 Enter 171 in the password field 9 The press and release button SET: the display will show - - - 4 sec flashing 10 The main page appears after this operation Page 7

4. PARAMETERS The controller includes parameters for controlling the dryer, such as temperature Set-points, time and operating hours. These parameters are used and changed only by the manufacturer. Please contact the manufacturer if you have a need to change these parameters. The manufacturer will provide a key to change the parameter settings if necessary. The programming key changes some of the parameter settings of the controller not otherwise allowed. The manufacturer reserves the right to deny access to some parameters. 4.1. Programming Key Description Table 3 Programming key function buttons Port Meaning 1 USB port 2 Not used 3 Enter Button 4 Clone Button 5 Signal LED 6 Connector 4.2. Use of the Programming Key The programming key can be used with the controllers in the DigiPro series; Which is called loading. The loading takes 5 s at most; If the LED signal is not a flashing, the procedure will not be completed (or the LED will not flash). The loading is allowed on the condition that the program on the key and that on the controller are the same; If this condition is not true, the programming key will signal that the procedure has not been completed successfully (or the LED is flashing to show red light for 1 s). The programming key does not have its own power supply and must be powered using the USB port; A USB / male Micro-B USB cable (referred to as USB cable ) is a USB port that can be plugged into a USB port. Page 8

Picture 3 Programming key USB connector Page 9

Warnings; make sure about that the device operating conditions, do not operate on the controller terminal blocks using electrical or pneumatic screw drivers, if the controller has fixed screw connection terminal blocks, never screw the screw connectors to connect the programming key, if the device was taken from a cold to a warm place, humidity could condense inside; wait for about an hour before powering it, for repairs and information regarding the device contact the EVCO sales network, Follow the Steps Below to Use Programming Key: 1. Make sure the controller is not powered. 2. If the controller has removable screw connection terminal blocks, unscrew at the maximum opening the screw connectors of the analog and digital inputs of the controller terminal block and remove possible cables previously wired. 3. Put to the bottom the connector of the programming key in the connectors of the analog and digital inputs of the controller terminal block paying attention the terminal on the left of the programming key connector coincides with the common terminal of the controller analog and digital inputs. 4. If the controller has removable screw connection terminal blocks, screw the screw connectors of the analog and digital inputs of the controller terminal block moderating the clamping the most possible. 5. Connect one end of the USB cable to the USB port of the programming key. 6. Connect the other end of the USB cable to the USB port of the Personal Computer (or to the USB port of the USB power supply; in this case also put the plug of the USB power supply in a socket). 7. press and release the programming button of the programming key: the signal LED shows red light flashing a few seconds, after which shows green light firmly 1 s. 8. Disconnect the ends of the USB cable. 9. If the controller has fixed screw connection terminal blocks, remove the programming key; if the controller has removable screw connection terminal blocks, remove the controller terminal block. 12 11 10 Page Picture 4 Digi Pro controller and programming key connection

Follow the steps below to change the Filter Alarm Parameters: For the filter alarm duration, you need to enter the parameter field and then access the A9 section. Please follow the steps carefully. When making these adjustments, be careful of the timing on the controller. The standard timing is 6000 hours. For this, the value that should be entered in A9 is 60. The controller evaluates the entered values by multiplying by 100. For example; 60 x 100 = 6000 h. Table 4 Steps to change the filter alarm parameter 1. Main page To disable the Key Lock: Press and hold the SET button for 4 sec. 2. Key Lock Loc appears while holding the SET button (4 sec) 3. UnL appears when key lock is released 4. To access parameters menu (PA): Press and hold the SET button for 4 sec. 5. PA appears when parameter menu is opened. Press the SET key to enter the password. 6. Enter 10 in the password field, use the menu keys. 7. After the password is confirmed, it is entered in the para meter section. 8. To access A9, use the menu keys. 9. Standard filter time appears on the screen. Note! 60 x 100 = 6000 h 10. Press the Set key after entering the new filter time. Use the menu keys. 11. After the process is complete, you can return to the main menu with the OFF button. Page 11

Follow the steps below to change the Drain Time Parameters: For the drain times it is necessary to enter the parameter field and then access the sections u2 and u3. Please follow the steps carefully. Note that when these values are changed, the time of evacuation closed time is in minutes and the time of evacuation opened time is in seconds. Table 5 Steps to change the Drain time parameters 1. Main page To disable the Key Lock: Press and hold the SET button for 4 sec. 2. Key Lock Loc appears while holding the SET button (4 sec) 3. UnL appears when key lock is released 4. To access parameters menu (PA): Press and hold the SET button for 4 sec. 5. PA appears when parameter menu is opened. Press the SET key to enter the password. 6. Enter 10 in the password field, use the menu keys. 7. After the password is confirmed, it is entered in the parameter section. 8. To access u2, use the menu keys. Press the SET button to enter the parameter. 9. This value is the drain system s on-time. Standard time is 5 seconds. Please enter the new time, then press the SET button. 10. To access u3, use the menu keys. Press the SET button to enter the parameter. Use the menu keys. 11. This value is the drain system s off-time. Standard time is 4 minutes. Please enter the new time, then press the SET button. 12. After the process is complete, you can return to the main menu with the off button. Page 10

5. ELECTRICAL CONNECTION EV3B23* and EV3B33* have the same electrical connection; EV3B23 relay K1 is rated 16 A, EV3B33 relay K1 is 30 A. Page 11