4100U City and Relay Cards Installation Instructions

Similar documents
Panel Remote Annunciators Installation Instructions

/ XPS Interconnection Diagrams

/9308 External Battery Chargers Installation Instructions

Network Display Unit Installation Instructions

4009 Fiber Optic Link Option Installation Instructions

Class A and Expansion NAC Modules Installation Instructions

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

/5121/5122 TrueAlert Power Supply Installation Instructions

AU MX Digital Loop Card Installation Instructions

Panel Message Memory Expansion Cards Installation Instructions

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Booster Power Supply Manual

General Routing Interface

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

Specification/ Data Sheet

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

Independent Zone Control (I.Z.C.)

RMS/RPX Reader. User Manual

FCPS-24F FIRE ALARM FIELD CHARGER/POWER SUPPLY FOR FIRE PROTECTION/SIGNALING SERVICE FCPS-24F/FCPS-24FE. Field Charger/Power Supply

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description

IDP-Zone-6 Six Zone Interface Module

Doc. No Part No Rev. U * T*

LifeAlarm Fire Alarm Controls

Model 17A00 Expansion Enclosure

Addressable IDNet Isolator Installation Instructions

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description.

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

4010 Fire Alarm Parts List

FIRE FIRE. 4100U Fire Alarm. Operator's Manual. Technical Manuals Online! -

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION

FCPS-24F/FCPS-24FE. Field Charger/Power Supply D P/N 50079:D ECN Installation, Operation and Application Manual

Instruction Manual. CMP-12/24 Fire Alarm Control Panel. 12 Clintonville Road, Northford, CT DOCUMENT /11/96 REV: D1

Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES Rev. B

Addressable NAC Output Module D327A

Remote NAC Power Supply D7038

30.45 Electric Release PDRP-2001

MMF Six Zone Interface Module

RELEASE DEVICE CONTROLS

4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual

Installation Guide for models:

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

MS-2410BC. Conventional Fire Alarm Control Panel. Programming, Installation, Maintenance and Operating Instruction Manual

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

LED Driver Module. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment.

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

Public Safety DAS Annunciator Panel

Installation Guide for models:

TrueAlert Addressable Notification Appliances

Securitron Magnalock Corporation S. 51 st St., Ste. 102 Phoenix, AZ Phone: (800) MAGLOCK

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

FEC400 Series. Installation Manual

Duct smoke housings, 4-wire D341/D341P and D342/D342P

LifeAlarm Fire Alarm Control Panels

TECHNICAL DATA OBSOLETE

CZ-6A Six Zone Interface Module

Series. Access Power Controllers. Installation Guide

The TC-4F. Time Control Module C P/N 15972:C ECN For the Sensican 2000 Fire Alarm Control Panel

4010 Fire Alarm Front Panel Installing, Operating, and Programming Instructions

PSN-1000 & PSN 1000(E) Installation Manual

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

Installation, Operating and Maintenance Manual

Operation and Installation Guide. Fire Alarm Control Panel

EXTINGUISHING AGENT RELEASE MODULE

Functional Performance Test

1 UL 864 Compliance. 2 Product Overview. Network Communications Module NCM-W/F Product Installation Document. 1.1 Products Subject to AHJ Approval

SC-6 Six Supervised Control Module

TrueAlarm Analog Sensing

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

The ACM-8R Annunciator Control Module

Series SPB Audio Boosters Installation, Testing, Operation, and Maintenance Manual

Wiring Instructions. Single Doors 99 Checkmate Series Use one or Master Unit each door or one or Support unit each door

Conventional Fire Alarm Control Panel

Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual

MANUAL RESET ALARM RELEASE

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

CMP-2401B/CMP-2402B. Fire Alarm Control Panel. Installation, Maintenance and Operating Instruction Manual

CFP-2401B/CFP-2402B. Fire Alarm Control Panel. Installation, Maintenance and Operating Instruction Manual.

PDD-8PCI. Power Distribution Board With Supervised Interface. Installation and Specifications Manual

Notification Appliance Circuit Module

TrueAlarm Analog Sensing

Rev. B. TrueAlert Addressable Controller Application Manual

Release Control Fire Alarm Systems

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

GE Security. FP1200, FP2000 and KSA1200 series fire panels, repeaters and emulators Interconnection and wiring

Wiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector

Fire Control Panels. Multiple Signal Fiber Optic Modems and Accessories for 4120 Network. UL, ULC, CSFM Listed; FM Approved* Features

System Accessories, LCD Annunciators

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

SILENT KNIGHT. Model SK-2/E & SK-4/E. Installation and Operations Manual. Fire Alarm Control Panel. Part Number Rev. A ECN /08/05

FEC403EN Installation Manual

1 INTRODUCTION NOTICE WARNINGS AND CAUTIONS NATIONAL APPROVALS EMC COMPATIBILITY UNPACKING...

PN: 51883:D ECN Field Charger/Power Supply FCPS-24FS6 FCPS-24FS8. Document # /14/05 Revision: D

UNC100 Integra Manual

Fire Control Panels. Multiple Signal Fiber Optic Modems and Accessories for Panel and Remote Mounting. Features. Operation.

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

Harrington Signal HS-3100/3200 Fire Alarm Control Unit

Transcription:

4100U City and Relay Cards Installation Instructions Introduction This publication describes the installation procedure for the following: 4100-6031/6032 City Circuit Cards 4100-6033 Alarm Relay Card Inspecting Contents of Shipment Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify your local Simplex product supplier. In this Publication This publication discusses the following topics: Topic See Page Cautions, Warnings, and Regulatory Information 2 Introduction to the City and Relay Cards 3 Installing the City or Relay Card to the SPS 5 Configuring the Card 6 Field Wiring 7 2003 Tyco Safety Products Westminster, Westminster, MA 01441-0001 USA All specifications and other information shown were current as of document revision date and are subject to change without notice. Tyco, Simplex, and the Simplex logo are trademarks of Tyco International Services AG or its affiliates in the U.S. and/or other countries. 574-839 Rev. C

Cautions, Warnings, and Regulatory Information READ AND SAVE THESE INSTRUCTIONS. Follow the instructions in this installation manual. These instructions must be followed to avoid damage to this product and associated equipment. Product operation and reliability depends upon proper installation. DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking the product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify your local Simplex product supplier. ELECTRICAL HAZARD - Disconnect electrical field power when making any internal adjustments or repairs. All repairs should be performed by a representative or authorized agent of your local Simplex product supplier. STATIC HAZARD - Static electricity can damage components. Therefore, handle as follows: Ground yourself before opening or installing components (use the 553-484 Static Control Kit). Prior to installation, keep components wrapped in anti-static material at all times. EYE SAFETY HAZARD - Under certain fiber optic application conditions, the optical output of this device may exceed eye safety limits. Do not use magnification (such as a microscope or other focusing equipment) when viewing the output of this device. RADIO FREQUENCY ENERGY - This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area may cause interference in which case the user at his or her own expense will be required to take whatever measures may be required to correct the interference. SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES - To ensure proper system operation, this product must be tested in accordance with NFPA72-1999, Chapter 7 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions, known to be affected by a change, must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. 2

Introduction to the City and Relay Cards Overview This section describes the city and relay cards in turn, and lists their electrical specifications. The City Card The 4100-6031/6032 City Card is used to annunciate alarms and other urgent indications to remote facilities. When the 4100 goes into alarm, city card circuits are activated, and annunciation immediately occurs at the remote facility. Reverse polarity modules or local energy modules (for reaching the Public Service Fire Communications Center) receive annunciations at the remote site. Each city circuit module has two circuits, which are configurable for alarm, trouble, or supervisory reporting. In the event of a CPU failure, a city card configured for a trouble output sends a trouble to the city circuit. Note: Only one city card can be installed per system. ALARM/ TROUBLE/ SUPERVISORY JUMPER PORT (P6) P6 10-POSITION HEADER CONNECTOR TO SPS (P1) REVERSE POLARITY/ LOCAL ENERGY JUMPER PORT (for City Circuit 1) (P3) (P2) P1 CITY DISCONNECT SWITCHES (4100-6031 only) (SW2) (SW1) CITY CIRCUITS 1 AND 2 (TB1) SW1 CITY1+ P3 P5 P2 SW2 CITY1- CITY2+ CITY2- P4 REVERSE POLARITY/ LOCAL ENERGY JUMPER PORTS (for City Circuit 2) (P4) (P5) Figure 1. 4100-6031/6032 City Card Table 1 lists the city card s specifications. Table 1. Specifications Electrical Specifications Input voltage Current Output voltage Environmental Specifications 20 to 32 VDC 20 ma @ 24 VDC, nominal 36 ma @ 24 VDC, both relays on 5 V +/-5%, nominal Normal operating temperature 77 F (25 C) Operating temperature 32 to 120 F (0 to 49 C) Humidity 10% to 93% non-condensing @ 90 F (32 C) 3 Continued on next page

Introduction to the City and Relay Cards, Continued The Relay Card The 4100-6033 Relay Card is used to provide common unsupervised control functions or indications for devices such as fans and doors. Each relay module has three circuits: one each for alarm, trouble, and supervisory signals. Figure 2, below, is an illustration of the relay card. P6 ENERGIZED RELAY LEDS: for Trouble relay (LED1) for Supervisory relay (LED2) 10-POSITION HEADER CONNECTOR TO SPS (P4) P4 P3 LED1 P2 LED2 P1 LED3 for Alarm relay (LED3) NORMALLY CLOSED/ NORMALLY OPEN JUMPERS: for Alarm relay (P1) for Supervisory relay (P2) for Trouble relay (P3) RELAY CIRCUITS (TB1) TB1 TROUBLE SUPERVISORY ALARM Figure 2. 4100-6033 Relay Card Table 2 lists the relay card s electrical specifications. Table 2. Specifications Electrical Specifications Input voltage Input current Output voltage Output current Environmental Specifications 20 to 32 VDC 15 ma @ 24 VDC, nominal / standby 37 ma @ 24 VDC, all relays on 5 V +/-5%, nominal 6 ma, nominal / standby 12 ma, all relays on Normal operating temperature 77 F (25 C) Operating temperature 32 to 120 F (0 to 49 C) Humidity 10% to 93% non-condensing @ 90 F (32 C) LEDs LED1, LED2, and LED3 illuminate when relays are energized. LED1 corresponds to Relay K3, LED2 to Relay K2, and LED3 to Relay K1. 4

P1 SW1 CITY1+ P3 SW2 P2 CITY1- CITY2+ CITY2- P5 P4 P6 P4 P3 LED1 P2 LED2 TROUBLE SUPERVISORY ALARM P1 LED3 P6 TB1 Installing the City or Relay Card to the SPS or RPS Mounting The city and relay cards mount identically onto the system power supply (SPS). Use the following instructions and Figure 3 to mount either card. Note: The city card connects to the SPS only. The relay card connects to the SPS or RPS. 1. Disconnect battery and then AC power at the breaker from the FACP. 2. Secure the card to the SPS or RPS with the plastic standoffs as shown in Figure 3. 3. Use the supplied slotted torx screw (441-002) and plastic sleeve to secure the lower right corner of the module bracket to the SPS or RPS chassis. SPS CONNECTOR (P4 on Relay Card) (P1 on City Card) CITY CARD RELAY CARD SYSTEM POWER SUPPLY/ REMOTE POWER SUPPLY CITY CONNECTOR (P6) METAL STANDOFF SCREW WITH PLASTIC SLEEVE Figure 3. City Card Hardware Slot Communications/ Power Connection Each card comes with a 733-952 Power/Communication Harness used to interface the card with the SPS or RPS. (See Figure 4.) Use the harness to connect one end from P1 on the city card or P4 on the relay card to the connector labeled CITY on the SPS or RPS. Once this is done, you can apply AC power at the breaker and then battery power to the FACP. CITY CARD RELAY CARD Figure 4. City Card or Relay Card Connection to the SPS/RPS 5

Configuring the Card Overview Card configuration depends on the type of card used. This section describes how to configure all types of cards. 4100-6031/6032 City Cards Configuration For the 4100-6031/6032 City Cards, use the information in Table 3 and the bullets below to set the jumper positions for reverse polarity and local energy operations. Table 3. Jumper Positions for Reverse Polarity and Local Energy Reverse Polarity Jumper Positions Local Energy City Circuit 1 City Circuit 2 P3: 1-2, 3-4, 5-6 P2: 2-3 P5: 1-2, 3-4, 5-6 P4: 2-3 P3: 7-8, 9-10 P2: 1-2 P5: 7-8, 9-10 P4: 1-2 P6: You must select either supervisory or trouble operation for the second circuit by setting P6. To configure City 2 for supervisory activation, install jumpers on port P6 to positions 1 and 2, and another to positions 3 and 4. City 1 sends a trouble to the city by dropping circuit power when reverse polarity is selected. To configure City 2 for trouble activation, install a jumper on port P6 in positions 2 and 3. City 1 sends alarms only to the city. Disconnect Settings (4100-6031 City Card only) The 4100-6031 City Card has two disconnect switches (SW1 / City Circuit 1 and SW2 / City Circuit 2). Turn the switches to the ON position for normal operation and to the OFF position to test the system without transmitting alarms to the city. The 4100-6032 City Card does not have disconnect switches. 4100-6033 Relay Card Configuration Use the information in Table 4 to set the jumper positions for normally open (NO) and normally closed (NC) circuits for the 4100-6033 Relay Card. Table 4. Jumper Positions for NO and NC Circuits Alarm relay Supervisory relay Trouble relay Normally Open P1: 2-3 (jumper toward bottom) P2: 2-3 (jumper toward bottom) P3: 2-3 (jumper toward bottom) Jumper Positions Normally Closed P1: 1-2 (jumper toward top) P2: 1-2 (jumper toward top) P3: 1-2 (jumper toward top) Software Requirements The city and relay card options must be selected via the 4100U Programmer. Refer to Chapter 6 in the 4100U Fire Alarm PC Programmer Programming Manual (574-849). 6

Field Wiring Overview This section describes wiring and wiring guidelines for city and relay cards. City Card Guidelines Wiring is not power-limited. Wiring is supervised. Conductors must test free of all grounds before connecting to the system. All wiring that leaves the building requires overvoltage protection. Install the 2081-9044 Module inside a UL Listed electrical box wherever wire enters or exits the building. A maximum of four 2081-9044 Modules may be connected to one channel. Minimum wire size for reverse polarity is 20 AWG (0.5176 mm 2 ). Maximum wire size is 12 AWG (3.309 mm 2 ). Minimum wire size for local energy is 18 AWG (0.8231 mm 2 ). Maximum wire size is 12 AWG (3.309 mm 2 ). P3 on SPS: City/Relay Hardwired Trouble Jumper. Position 1-2 removes trouble monitoring on Relay 3 (default) of the 4100-6033 Alarm Relay Card; Position 2-3 activates the 4100-6031/6032 City Cards or the 4100-6033 Alarm Relay Card when the system microprocessor fails. Always use Position 2-3 for 4100-6031/6032 City Cards. Relay Card Guidelines All wiring is 18 AWG (0.8231 mm 2 ) to 12 AWG (3.309 mm 2 ). When relay power through auxiliary contacts is provided by the SPS or RPS, relay wiring is power-limited. Conductors must test free of all grounds before connecting to the system. Relay circuits are fused at 3 A. Replace with 208-163. Relay circuits are not supervised. The relay circuit is rated to switch 2 A at 30 VAC or 32 VDC, resistive load. Relay contacts are Normally Open or Normally Closed dry contacts. Suppression is provided to earth ground. Damage may result from switching voltages to a greater amount than that for which they are rated. Relay operation is under software control. If Relay 3 is not programmed as Trouble, move Jumper P3 on the SPS to Positions 1 and 2. P3 on SPS: City/Relay Hardwired Trouble Jumper. Position 1-2 removes trouble monitoring on Relay 3 (default) of the 4100-6033 Alarm Relay Card; Position 2-3 activates the trouble relay on the 4100-6033 Alarm Relay Card. Continued on next page 7

Field Wiring, Continued Relay Card Guidelines (continued) Auxiliary power only: Supervision must be provided if the auxiliary power circuit is to be wired as a power-limited circuit. In order to connect a circuit using power-limited wiring, the devices being powered must all be addressable, or a UL-Listed EOL relay must be used to supervise the circuit. Refer to the figure below for wiring directions for the EOL relay. TO AUX POWER Note: The 2098-9739 Relay is used as an example. Other UL-Listed EOL relays can be used, depending on the application. RED 2098-9739 END OF LINE RELAY BLACK YELLOW IDC LAST IDC DEVICE RESISTOR Figure 5. The EOL Relay City Card Wiring Use Figure 6 and the notes below to wire the city card for reverse polarity or to a local energy master box. All wiring is terminated at TB1 on the city card. Leave the 3.3 K Ω, ½ W resistor (part number 378-155; orange/orange/red), installed from the + to the - terminals of unused circuits on TB1. REVERSE POLARITY (See Note 1) TO CITY- TO CITY+ R+ R- TO CITY- TO CITY+ LOCAL ENERGY MASTER BOX (See Note 2) Notes: 15 ma MAX AT 24 VDC 24 VDC NOMINAL 4 ma SUPERVISION 500 ma MAX ALARM 1. Intended for connection to a polarity reversal circuit of a remote station receiving unit having compatible ratings. 19-32 VDC, 2 V p-p ripple maximum. 2. Intended for connection to 14.5 Ω trip coil. Figure 6. City Circuit Wiring Continued on next page 8

Field Wiring, Continued Relay Card Wiring Use Table 5, below, to wire the relay card. All wiring is terminated at TB1 on the relay card. Table 5. Relay Card Wiring Screw Terminal Signal Type Contact TB1-1 Alarm Selected contact (NO or NC) TB1-2 Alarm Center contact, fused at 3 A TB1-3 Supervisory Selected contact (NO or NC) TB1-4 Supervisory Center contact, fused at 3 A TB1-5 Trouble Selected contact (NO or NC) TB1-6 Trouble Center contact, fused at 3 A Each circuit is rated at 2 A (maximum) for 20 to 30 VDC. A 3 A fuse connects between the center arm of each relay and the field wiring. 9

574-839 Rev. C