S H R E V E P O R T, L O U I S I A N A File: ARCHIVE MAIN STORAGE 102 09 / 18 / 2018 REVISIONS BY SCHEMATIC DESIGN SET DESIGN DEVELOPMENT SET CONSTRUCTION DOCUMENT SET CLIENT REVIEW SET AS-BUILT DOCUMENT SET MEETING SET CHECK SET OFFICE SET FINAL PRINT REQUESTED PRINT Drawn: Job: 1820 Sheet M2.00 2 of 3M sheets
HEAT RECOVERY CONDENSING UNIT SCHEDULE MARK HRCU - 1 LOCATION NORTH EAST CORNER OF BLD SERVICE BUILDING NOMINAL TONS 22 (12+10) REFRIGERANT 410 A NO OF COMPRESSORS 4 CAPACITY CONTROL RANGE 5-100% MINIMUM IEER 21 HEATING COP @17F NON-DUCTED 2.4 COOLING AMBIENT TEMPERATURE F 95 RATED COOLING CAPACITY MBH 245.0 NOMINAL COOLING CAPACITY MBH 264.0 COOLING INPUT POWER KW 21.1 HEATING AMBIENT TEMPERATURE F 47 RATED HEATING CAPACITY MBH 276.0 NOMINAL HEATING CAPACITY MBH 297.0 HEATING INPUT POWER KW 21.8 ELECTRICAL ELECTRICAL CONNECTION TWO CIRCUITS VOLTS / PHASE 208 / 3 MCA AMPS (55 + 43) MOCP AMPS (70 + 50) APPROX DIMENSIONS (L X W X H) FT 2.5' X 8.2' X 5.5' APPROX WEIGHT LBS MANUFACTURER "DAIKIN" MODEL NO REYQ264TATJU REMARKS 1, 2, 3 1.PROVIDE DDC CONTROLS 2.MINIMUM ONE INVERTER COMPRESSOR AHU1 - INDOOR UNIT SCHEDULE - WITH HUMIDIFIER MARK OAU-2 TYPE HORIZONTAL UNIT WITH FILTER ACCESSORY SERVICE LOCATION CFM TOTAL CFM OUTSIDE AIR (INTO RA DUCT MAIN WITH DAMPER) ARCHIVE STORAGE AND CONFERENCE ROOM ARCHIVE STORAGE 2217 350 DX COOLING COOLING/HEATING (VRV SYSTEM) CONNECTED TO VRF SYSTEM VIA AHU CONTROL BOX EQUIVALENT TO DAIKIN EKEQMCBAV3-US MARK FCU-1A FCU-1B FCU-1C FCU-2 FCU-3 FCU-4 FCU-5 FCU-6 FCU-7 FCU-8A FCU-8B FCU-9 FCU-10 OAFCU-1 AHU1 SERVES TYPE ARCHIVE MAIN HALL 3' X 3' ARCHIVE MAIN HALL 3' X 3' ARCHIVE MAIN HALL RAMP 3' X 3' CORRIDOR CURATOR ASSIST DIR. OFFICE DIRECTOR OFFICE ACCT. OFFICE BREAKROOM MENS RESTROOM WOMENS RESTROOM SERVICE ENTRANCE 3' X 1' WALL MOUNTED ELECTRIC ROOM NON STORAGE AREA NOMINAL TONS 2.0 2.0 2.0 1.3 0.6 1.0 1.0 1.3 1.3 0.42 0.42 0.6 0.42 4.0 8.8 REFRIGERANT 410 A 410 A 410 A 410 A 410 A 410 A 410 A 410 A 410 A 410 A 410 A 410 A 410 A 410 A 410 A FAN AIRFLOW RANGE CFM 777/477 777/477 777/477 405/282 307/229 353/247 353/247 405/282 405/282 300/229 300/229 307/229 300/229 1377/988 COOLING EAT (DB / WB) F 74 / 62 74 / 62 74 / 62 74 / 62 74 / 62 74 / 62 74 / 62 74 / 62 74 / 62 74 / 62 74 / 62 74 / 62 74 / 62 80 / 67 TOTAL CAPACITY MBH 19.8 19.8 19.8 12.5 6.4 10.0 10.0 12.5 12.5 4.9 4.9 6.2 4.9 39.6 105.1 SENSIBLE CAPACITY MBH 16.9 16.9 16.9 9.4 5.1 6.9 6.9 9.4 9.4 4.3 4.3 5.5 4.3 30.6 HEATING EAT F 70 70 70 70 70 70 70 70 70 70 70 70 70 70 HEATING CAPACITY MBH 27.0 27.0 27.0 17.1 8.5 13.6 13.6 17.1 17.1 6.5 6.5 8.5 6.5 54.0 118.4 ELECTRICAL POWER SUPPLY (VOLT / PH) 208 / 1 208 / 1 208 / 1 208 / 1 208 / 1 208 / 1 208 / 1 208 / 1 208 / 1 208 / 1 208 / 1 208 / 1 208 / 1 208 / 1 MCA 0.7 0.7 0.7 0.4 0.3 0.4 0.4 0.4 0.4 0.3 0.3 0.3 0.3 3.4 MOPD 15 15 15 15 15 15 15 15 15 15 15 15 15 15 REFRIGERANT LIQUID IN 3/8" 3/8" 3/8" 1/4" 1/4" 1/4" 1/4" 1/4" 1/4" 1/4" 1/4" 1/4" 1/4" 3/8" REFRIGERANT GAS IN 5/8" 5/8" 5/8" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 5/8" CONDENSATE CONNECTION IN 1-1/4" 1-1/4" 1-1/4" 1" 1" 1" 1" 1" 1" 1" 1" 1" 1" 1-1/4" MANUFACTURER "DAIKIN" "DAIKIN" "DAIKIN" "DAIKIN" "DAIKIN" "DAIKIN" "DAIKIN" "DAIKIN" "DAIKIN" "DAIKIN" "DAIKIN" "DAIKIN" "DAIKIN" "DAIKIN" "DAIKIN" 4.6' X 2.1' DUCTED FCU ARCHIVE STOR. AND CONF. RM SEE SEPARATE AHU SCHEDULE MODEL NO FXFQ24TVJU FXFQ24TVJU FXFQ24TVJU FXZQ15TAVJU FXZQ07TAVJU FXZQ12TAVJU FXZQ12TAVJU FXZQ15TAVJU FXZQ15TAVJU FXZQ05TAVJU FXZQ05TAVJU FXAQ07PVJU FXZQ05TAVJU FXMQ48PBVJU EKEXV250-US REMARKS 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3 1,2,3, 4 1,2,3, 5 1. MANUFACTURER PROVIDED CONDENSATE PUMP AND LIQUID SENSOR 2. PROVIDE A 15 AMP 208V / 1PH CIRCUIT FOR BRANCH SELECTOR 3. PROVIDE LOCKING THERMOSTAT COVERS 4. AHU WITH DX COIL SERVED BY HRCU-1 REFRIGERANT SYSTEM, PROVIDE AHU KIT Z-CONTROL BOX 5. DUCTED VRF UNIT WITH 400 CFM OA. INDOOR UNIT SCHEDULE - HEAT RECOVERY CONDENSING UNIT HRCU - 1 ACCESS SECTION CAPACITY (BTU) 86,488 ENT:AIR-DB/WB (DEG.F.) 77.2/64.5 LAT:AIR-DB/WB (DEG.F.) 52.2/51/1 CAPACITY (BTU MIN) 30,872 ENT:AIR-DB (DEG.F.) 62.1 LAT:AIR-DB (DEG.F.) 75 RPM / RPM MAX 2803 / 3230 DISCHARGE DRIVE HORIZONTAL INTEGRATED MOTOR HP/MAX FAN RPM 4 / 3,910 VOLTAGE/PHASE REMARKS 208V / 3-PHASE AIRFOIL PREFILTER TYPE MERV 8 AIR P.D. (IN W.G.) 0.0 FILTER SIZE 2" FILTER TYPE MERV 14 AIR P.D. (IN W.G.) 1.0 FILTER SIZE 4" STAINLESS STEEL DRIP PAN CAPACITY (LBS/HR) 20 COMMENTS SECTION LENGTH CONDENSATE CONNECTION 2" MANUFACTURER MODEL NO COOLING HEATING SUPPLY FAN PANEL AND CARTRIDGE FILTER HUMIDIFIER / ACCESS SECTION "DAIKIN" CAH005GDCM REMARKS 1,2,3,4,5 1. MANUFACTURER PROVIDED CONDENSATE PUMP AND LIQUID SENSOR 2. PROVIDE A 15 AMP 208V / 1PH CIRCUIT FOR BRANCH SELECTOR 3. PROVIDE LOCKING THERMOSTAT COVERS 4. PROGRAM UNITS TO RUN ON TIMER WHEN BUILDING IS OCCUPIED, PER OWNER SCHEDULE 5. PROVIDE INSULATED AHU CASE EXT S.P./TOTAL S.P. WITH CLEAN FILTERS (W.G.) 1.00/4.08 File: S H R E V E P O R T, L O U I S I A N A 09 / 18 / 2018 REVISIONS BY SCHEMATIC DESIGN SET DESIGN DEVELOPMENT SET CONSTRUCTION DOCUMENT SET CLIENT REVIEW SET AS-BUILT DOCUMENT SET MEETING SET CHECK SET OFFICE SET FINAL PRINT REQUESTED PRINT Drawn: Job: 1820 Sheet M3.00 3 of 3M sheets