HALOGUARD TM IR MONITOR (OPTIONAL) FOUR or EIGHT POINT SCANNER INSTRUCTION MANUAL

Similar documents
HALOGUARD TM II/IR MULTI-GAS MULTI-SENSOR MONITOR INSTRUCTION MANUAL

HALOGUARD IR MULTI-POINT, COMPOUND SPECIFIC MONITOR INSTRUCTION MANUAL

HALOGUARD TM II MULTI-GAS MULTI-SENSOR MONITOR INSTRUCTION MANUAL

HALOGUARD REMOTE IR SENSOR MODULE

SPECIFICATION CHEMGARD INFRARED GAS MONITOR SERIES

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

Two-Channel Gas Controller

Pioneer-R16 Gas Monitor Operator s Manual

Controllers. Instruction Manual WARNING

THIS MANUAL MUST BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR USING, MAINTAINING OR SERVICING THIS PRODUCT.

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08

Oxygen (O2) Single-Point Gas Detection System

Carbon Monoxide Transmitter

Instruction Manual WARNING

Installation Operation Maintenance

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

Model OEM-2 INSTRUCTIONS FOR USE

Greentrol Automation, Inc.

Mark 25 Ultrapure Water Conductivity Analyzer

Analog Room Pressure Monitor RPC Series

Table of Contents SECTION PAGE SECTION 1 INTRODUCTION Description Features Models... SECTION 2 RS-232 COMMUNICATIONS...

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

MAINTENANCE & TROUBLESHOOTING GUIDE LEAK ALARM CHANNEL DRY OIL WATER AUX ALARM HIGH LOW CRITICAL WATER TANK LEVEL ALARM MODEL LDE-740 ADVANCE PAPER

Duct and Rough Service Carbon Monoxide Sensor

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

Installation & Operation

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

Sensor Interface Module Installation/Operation Instructions

INSTALLATION AND OPERATION MANUAL ENVIRONMENTAL SYSTEM IR-SNIF-MCD MODELS MCD-1, 4, 8 & 16

Safe T Net 210. Instruction Manual Part Number Mar2010

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

MODEL 4200-IR-2 (Up to 2 Sensors) MODEL 4200-IR-4 (Up to 4 Sensors) MODEL 4200-IR-6 (Up to 6 Sensors)

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Universal Gas Detector

HP727S. Single speed swimming pool heat pump controller Operation manual TABLE OF CONTENTS

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

Combustible Gas Detection and Control System

DESIGN MANUAL. The information in this doucment is applicable to sensors built in September, 2009 or later (Firmware 3.0)

Ammonia Leak Detector Manual

Model 9010 and 9020 Monitoring Systems

IT COULD FAIL TO PERFORM AS DESIGNED AND PERSONS WHO RELY ON THIS PRODUCT FOR THEIR SAFETY COULD SUSTAIN SEVERE PERSONAL INJURY OR DEATH.

CHILLGARD M-100. Refrigerant Sensor. Operating Manual. Order No.: /02

MODEL A-316 CARBON MONOXIDE (CO) MONITOR AND ALARM FOR COMPRESSED AIR TESTING

SECTION 1 (Page 2) Introduction, standard accessories and mounting specifications.

GLD-30 Gas Leak Detector

Series DCT1000DC Dust Collector Timer Controller Specifications Installation and Operating Instructions

Beacon 800 Gas Monitor Operator s Manual

Pump-Down Controller MODEL 4052

UNI-TRAN PREMIUM PLUS TOXIC GAS DETECTOR USER MANUAL UT-P+-STXXXX

ALTAIR 5X Multigas Detector Product Specification

RTD TEMPERATURE SENSING SYSTEM

Warranty Registration

Toxic and Explosive Smart Gas Monitor PN / Installation and User Manual

ACCURATE ELECTRONICS INC

ESSEX ENGINEERING CORPORATION

SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA)

NT DUAL CHANNEL DISPLAY. User Guide

MEGA. cal electronic gas alarm. Installation, Operation, and Maintenance Instructions. Part No Rev. D Pg.

MODEL 8144-RD CLOCK SELECTOR/DISTRIBUTION AMPLIFIER INSTRUCTION MANUAL. SPECTRACOM CORPORATION 95 Methodist Hill Drive, Suite 500 Rochester, NY 14623

Table of Contents SECTION PAGE

1040 Gas Monitor INSTALLATION AND OPERATING INSTRUCTIONS AMC-1040 WITH INTEGRAL ELECTROCHEMICAL SENSOR

Operating Instructions. For. Alarm Control Module. Model SSR 500

Model 9010 and 9020 Monitoring Systems

MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

DIGITAL METERS Large Display Temperature Meters Instruction Manual

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

Table of Contents. T538 Instruction Manual Rev # 6 June R6T538 June rtf E L Switchgear and Control Inc

WARRANT Y AND LIMITS OF LIABILIT Y Vulcain Inc. warrants to the original purchaser that its product, and the component parts thereof, will be free fro

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08

Model 4001 Series Single Channel Controller

GG-R REFRIGERANT SENSOR. Installation and Operation Manual

Using the MiniRAE 2000 & ppbrae PID

Rev B, 9/2/2009. Kodiak Chiller Overview

MST, INC. MODEL 2002 CARBON MONOXIDE MONITOR (AMBIENT-TYPE) OWNER S MANUAL

Warranty Registration

21-light Remote Annunciator. Owner s Manual

TMC. Installation and Operation Manual TMC. Temperature and Pressure Monitoring for Heating and Cooling Applications. Temperature Monitoring Control

GasScanner 1C. Single Channel Monitor. Operator s Manual. MINT-0278-XX Rev A

Carbon Monoxide Sample-Draw Detector Operator s Manual

MBUV-100D, MBUVS-100D MBIR-100D, MBFR-100D DIN RAIL MOUNT FLAMEWORX MODULES

Product Manual SZ1144

Sierra Series 900 Single & Dual Channel System. Instruction Manual

Software Version 2.01 LEVEL MONITOR MODEL 220

S304 and S305 Dust Emission Monitors. User Manual. Distributor

MX43. Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. Cost savings on wiring installation

Beacon 410A Gas Monitor Operator s Manual

Pump-Up Controller MODEL 4062

Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. Cost savings on wiring installation

SEC 2000 Millenium Infrared Gas Detector

Product Manual SZ1145

OVEN INDUSTRIES, INC.

Pre-March 2016 Design - Click to be redirected to newer SBS-H2 design SBS-H2. Hydrogen Gas Detector Kit

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

OPERATION & MAINTENANCE MANUAL GUARDIAN SPACE PRESSURE MONITOR WITH REMOTE AUXILLARY ALARM

HGM300/RDM800 PREVENTATIVE MAINTENANCE AND TECHNICAL SUPPORT. SECTION 1 HGM300 CPU reset, RDM800 CPU reset, WARM UP notes and HGM300 Self Test

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

Water Leak Detector - Four Zone with open/short-circuit detection. Product overview

CO2 RESPONDER Portable Carbon Dioxide Detector QUICK REFERENCE GUIDE

RCS Residential Control Systems Inc.

Transcription:

HALOGUARD TM IR MONITOR (OPTIONAL) FOUR or EIGHT POINT SCANNER INSTRUCTION MANUAL SE R IA L N O. M O D E L N O. Tem p. Range 1 - = > 60 o F 2 - = 40-60 o F 3 - = < 40 o F G as Type 1 - R-11 2 - R-12 3 - R-22 4 - R-134a 5-6 - 7 - R-123 M ount 1 - W all R ange 1-0 - 1000 ppm O utputs 11-4 x 3A Relays 12-0 - 5 VD C or 0-10 VD C 13-4 - 20m A O ptions/a ccessories A - Audible Alarm B - UPS E - Inlet/O utlet Extension L - Strobe Light S - Scanner T - TW A Integration 11285 Elkins Road Bldg. H-1 Roswell, GA 30076 TEL: 770-667-3865 FAX: 770-667-3857 www.thermalgas.com 1 Rev.2 1/26/98

IMPORTANT READ ENTIRE BOOKLET BEFORE INSTALLING OR OPERATING HALOGUARD TM IR MONITOR AND (OPTIONAL) SCANNER TABLE OF CONTENTS Page 1. Unpacking Instructions 3 2. Before Installation 3 3. Installation 7 4. Calibration 10 5. Testing 10 6. Trouble Shooting 10 7. Specifications 11 FIGURES Page 1. Dimension Drawing 4 2. Controller Upper Circuit Board 5 3. Controller Lower Circuit Board 5 4. Controller LCD Display Features 6 5. Infrared (IR) Module Circuit Boards 6 6. Sensor Cable Terminal Connection 9 7. Analog Output Jumper and Terminal Settings 7 8. Function Jumper Settings 8 9. Initial Factory Settings 11 10. Exposure Limits 11 11. Wiring Diagram 12 2 Rev.2 1/26/98

UNPACKING INSTRUCTIONS Haloguard TM monitors are carefully packed, inspected and delivered to the carrier in good condition. If damage occurs in transit it is the responsibility of the carrier. Carefully inspect the unit upon receipt. Any damage should be reported to the carrier and an inspection requested. After inspection by the carrier and your receipt of his acknowledgment as to the damage, contact us for return authorization (RMA). We cannot file claims for damaged goods on your behalf, but we will assist you in any way we can. In order to expedite our work, please provide serial number and purchase date when you call. WE CANNOT ACCEPT RETURNS WITHOUT PRIOR APPROVAL. BEFORE INSTALLATION 1. Remove Haloguard Controller and IR Sensor Module from carton. Check contents against packing list. If shipment is incomplete, contact us immediately. 2. The following tools and hardware are required for installation and calibration. a. Two standard & one philips screwdrivers; 1 - medium standard w/ long shaft, 1 - jewelers fine standard & 1 - medium philips. b. Needle-nosed electrician s pliers c. (8) No. 8 x 1 Screw (minimum) d. Digital VOM 3. Select a site for the installation: a. Power requirements: Provide a clean source of 115-230 VAC, 50/60 Hz, single phase circuit rated 15A minimum Haloguard Controller and IR Sensor Module. b. Infrared (IR) Sensor Module should be mounted near potential leaks in a quiet area or downstream from leak source in area with air movement. c. Infrared (IR) Sensor Module sample tube end should be located 18-24 above the floor. If using optional scanner, locate IR Module at a point central to chiller locations. Install inlet extension tube out to each remote sample location (up to 200 Ft. from IR module). Make sure each sample tube is equipped with an end of line filter. d. Make sure the area selected is not subject to flooding, potential impact or severe ambient temperature and humidity changes (i.e. boiler blow-down or near roll-up doors). e. Infrared detector is highly selective but may respond to the presence of other gases (i.e. paint thinner, cleaning fluids and other refrigerants) if interfering gas reaches a high concentration. For accurate refrigerant leak detection select a location free from above fumes or temporarily disable sensor when they are present. Contact TGS for specific interference s. 4. The wall mounted controller should be installed indoors, approximately five feet above the floor or at a location easily visible to operators, in an area with minimal vibration, and with temperature and humidity changes like sensor location. IMPORTANT CONSULT LOCAL AND NATIONAL ELECTRICAL CODES FOR ANY SPECIAL REQUIREMENTS OR RESTRICTIONS BEFORE INSTALLING HALOGUARD. 3 Rev.2 1/26/98

5. LED Indicators, Pushbuttons, LCD Displays, and Relays a. POWER LED- Green LED indicates Haloguard is receiving AC power. b. FAULT LED and Relay - Indicates malfunction. LCD indicates specific type of failure (See Figure 4). c. TEST Push-button - Energizes Alarm LED s & relays. Depress button five (5) times to sequence through each alarm level. d. Adjustable Alarm LEDs & Relays -Indicate Alarm 1&Alarm 2 - Factory set for particular refrigerant (See Figure 9). User adjustable as follows: 1 PPM 10 PPM RANGE INCREMENTS INCREMENTS 0-1000 ppm 10-100 100-1000 Note: Optional TWA Integration activates Alarm 1 LED and relay when installed. TLV-TWA Alarm is factory set and not user adjustable. e. OFFSCALE LED and Relay - Factory set at 1000ppm f. RESET Push-button - Silences alarm, disables relays, and resets instrument for 20 minutes. LCD displays *CAUTION* and RESET with 20 minute countdown. Alarms are automatically reactivated if alarm condition is not corrected. Reset is automatically initiated on start-up and after power failure (Except when optional UPS is provided.). 6. Optional Features:. TWA Integration - Haloguard calculates an 8 hr. Time Weighted Average (TLV-TWA), displays this value on LCD, activates Alarm 1 LED and relay if factory set PPM value is exceeded. Only used for gases with TLV-TWA less than 1000ppm. 5 1/2 4 6 1/2 9 HALOGUARD IR CONTROLLER 14 1/4 3/4 HALOGUARD IR MODULE Figure 1 - Dimensional Drawing (By 4 Deep) 4 Rev.2 1/26/98

LCD Brightness Adjustment Power LED ENTER DOWN UP RUN GAS ALARM ZERO SPAN J5 AUD Setup Jumpers Offscale LED Fault LED Alarm 2 LED Test Button Processor Chip Alarm 1 LED Scanner Connection Analog Trim Pot 0-5 or 0-10 VDC I C VOLT ma ANALOG RS-232 Reset Button Sensor Connection IR Trim Figure 2 - Controller Upper Circuit Board FAULT ALARM 1 ALARM 2 OFFSCALE 1 2 3 4 5 6 7 8 9 10 11 12 Figure 3 - Controller Lower Circuit Board 5 Rev.2 1/26/98

Channels 1-8 (Optional Scanner Only) Flashing cursor means Auto Scan Mode (Opt. Scanner Only) Gas Type (R-11, R-12, R-123, R-134, etc.) Fault Messages - Caution - Chopper Failure - Discontinuity - Lamp Failure - Scan Discontinuity - Low Temp - Pump Failure - Scan Stop - Concentration (ppm) 8 hr. TWA Concentration (R-123) Alarms - Alarm 1 - Alarm 2 - Fault - Latch ON - OFF Scale - Reset Set up Messages GAS - SET GAS TYPE ALARM - SET ALARM 1 (ppm) SET ALARM 2 (ppm) SET SCAN RATE (scanner only) Figure 4 - Controller LCD Display Features Scanner Circuit Board (Optional) 1.. 8 Connector for Digital Calibrator (Optional) Lower Circuit Board Cable to Controller (DO NOT REMOVE) Red White Black DO NOT ADJUST POTS Run Setup IR Module Run/ Setup Jumper Figure 5 - IR Module Circuit Boards Rev.1/26/98 6

INSTALLATION 1. Check power supply. (See Section Before Installation 3a ) 2. Disconnect power before beginning. 3. Installation of Haloguard Controller and IR Sensor Module a. To mount Haloguard Controller 1. Remove Plastic cover. 2. Install No. 8 x 1 screw (minimum) wall fastener through cover screw holes. 3. Replace cover. Refer to figures 2, 3, 4 and 5 before proceeding. b. To mount Haloguard IR Sensor Module 1. Mount IR Module in a VERTICAL position in a location not subject to vibration or extreme temperature or humidity fluctuation. Install sample tube to 18-24 above floor, install filter. 2. IR Module Inlet/Exhaust Extension (optional) sample tube may be extended up to 200FT with 0.125 OD x 0.093 ID nylon, copper or stainless steel tubing. When extending sample tubing: a. Keep sample lines as short as possible and free of kinks. b. 30 micron Inlet Filter should be attached at end of line. c. Exhaust to atmosphere. DO NOT install any device which might restrict the flow. c. Wiring Instructions: 1. Remove cover and face plate from Haloguard Controller and IR Sensor Module using screw driver. 2. Run cable from Haloguard Controller to IR Sensor Module location. Eight feet (8FT.) of cable with DIN connectors standard; optional extension cables are available (Follow instruction in Section 4, Page 9, when extension cables are used). 3. Relay Terminals - Connect alarm relays (NO or NC) (Figure 3 - Controller Lower Circuit Board) as required. **WARNING** analog output is a driven signal, do not connect any wire with voltage or current to analog output terminals 4. Analog Output (Optional) - Connect 18 ga. twisted shielded pair to Controller Upper Circuit Board (Figure 2) as follows: Analog Output Range Terminal Position 0-5VDC or 0-10VDC VDC and COM 4-20mA ma and COM Figure 7 - Analog Jumper and Terminal Settings 5. Uninteruptable Power Supply (Optional) - Connect Haloguard Controller and IR module to UPS, IR module must be within 10ft. of controller. d. On power-up, RESET and 20 minute count down will appear on LCD. For 20 minutes after power up all alarms and relays are automatically disabled. Whenever power is disrupted, RESET mode will be automatic (unless optional UPS is supplied) to protect against false alarms. Allow 1 hour for warm-up from cold start. Rev.1/26/98 7

e. Locate Setup jumpers on Figure 2 - Controller Upper Circuit Board. Select required settings from the following: JP FUNCTION RUN Select run for normal operation GAS Set Gas Type ALARM Alarm 1 and Alarm 2 Set Point Adjustment ZERO Factory Use Only SPAN Factory Use Only J5 Factory Use Only AUD Audible Alarm Disable Figure 8 - Function Jumper Settings 1. RUN - Remove jumper to initiate Set-Up Mode. Use jumper to initiate the following set-up modes. Replace jumper when finished. 2. GAS - Gas type will be pre-set at the factory (See Figure 9). 3. Alarm - Alarm levels will be pre-set at the factory. Scroll through menu to set up Alarm 1 and Alarm 2. Adjust alarm levels using UP/DOWN and ENTER push-buttons. 4. ZERO - Factory only. 5. SPAN - Factory only. 6. AUD - Local Audible Alarm (optional) is factory installed. To disable alarm remove AUD jumper. f. System Configuration: 1. Relay Setup - Factory setting is Unlatched Mode; e.g., the alarm LEDs and relays will return to a normal status when gas concentration goes below alarm setpoint. To select Latched Mode place jumper on ALARM setting (Figure 8). Press TEST button until LATCH ON appears on the LCD Display. (LATCH ON mode requires manual RESET of all alarms.) 2. Analog Output (optional) is factory set at 0-5 VDC or 4-20mA as ordered. Use Analog trim pot(figure 2) to adjust for up to 0-10VDC range 3. LCD display adjustment changes brightness - Adjust potentiometer (Figure 2). 4. Four or Eight Point Scanner - (Optional) Scanner is factory installed. Scanner automatically sequences through each port (1-4 or 1-8). A. Manual Scan - While in RUN Mode, 1. Press UP or DOWN button on controller. Each time the button is pressed, display will advance to next/previous sample point. Controller will return to automatic sequencing within 2 minutes. When changing set-up on scanner, turn power off before proceeding. B. Scanner Jumper Setup - Factory setting is for four (4)or eight (8) sample ports. If 1,2,3,5,6 or 7 sample ports are required, place jumper on corresponding positions located on Scanner Circuit Board(s) in IR Module (Figure 5). IR Module Scanner will sequence through the selected port settings. 5. Scan Rate - Scan rate is factory set at 4 seconds per point. Rate is adjustable from 0 to 10 seconds. To change scan display rate, from RUN mode at controller, press ENTER and then UP/DOWN to adjust. Press ENTER to return to RUN mode. Rev.1/26/98 8

4. Installation of Haloguard Controller and IR Sensor Module (Extended Cable Procedure) Refer to FIGURE 2 - Controller Upper Circuit Board before proceeding. DO NOT CUT SUPPLIED CABLE Maximum Extension wire 1000 Feet. a. Controller is provided with 18 cable with DIN Connector and sensor is provided with 6-1/2 cable. If cable extension is provided by customer, proceed as follows: We recommend 3 conductor 18 ga. cable with foil shield, Carol C2535 or equal. Use 3/4 conduit if required. b. To extend sensor beyond the provided length, remove 18 cable with DIN connector from controller Upper Circuit Board. Splice or solder extension cable to end of 18 cable. Reconnect extended sensor cable to terminal block in upper circuit board of controller. Terminal Provided Wire Color Extension Wire Color Function SCAN Red Red Scanner SIG White White Signal GND Blk./Blk Black Ground Note - SCAN Terminal is used with scanner Only. Figure 6 - Sensor Cable Terminal Connection To avoid nuisance alarms remove alarm jumper AUD before beginning. c. To compensate for line losses adjust signal voltage with a digital VOM as follows: 1. Open cover on Haloguard IR Module. Move Jumper from RUN to SETUP (See Figure 5). Wait approximately 1 minute before proceeding. 2. Open cover on Haloguard IR Controller and remove faceplate. 3. With VOM on 5 VDC scale, place VOM probe on SIG (+) and GND (-) Test points on Controller (see Figure 2). Adjust potentiometer I on Controller Upper Circuit Board, with screwdriver until it reads 4.975 +/-0.025 VDC. Display will show FAULT if out of range and SETUP, if trimmed to 4.975+/-0.025 VDC. 4. When done, replace IR Module jumper in RUN mode. 5. Replace AUD jumper to activate alarms circuit. Rev.1/26/98 9

CALIBRATION Haloguard IR monitors are factory calibrated to the gas of interest; field recalibration is not required for operation in typical machine room environments during the first twelve months of operation unless drift exceeds more than 5ppm in a 30 day period. For those who wish to check the factory calibration an optional Digital Calibrator and Span Gas Kit is available. Instructions for use are included with kit TESTING The Haloguard IR TM should be tested at start-up, after any changes to alarm protocol, and after each alarm level condition has been corrected. During Testing, display will indicate TEST MODE a. Alarm Test - Push TEST button five times to check all alarm levels sequentially. Alarm relays, lights, audible and remote alarms (if equipped) will activate. b. Reset Test - Push RESET/SILENCE button; alarm relays, audible and remote alarms (if equipped) will become inactive for 20 minutes. Display will read RESET and indicate minutes to completion of reset period. TROUBLESHOOTING The most frequent cause of nuisance alarms and faults is improper set-up, primarily due to: a. Failure to install in accordance with instructions. b. Not allowing sufficient warm-up time. c. Poor sensor location. To check Zero Calibration, fill a clean plastic trash bag with clean outside air, tie off with twist-tie, let sample stabilize inside for 15-20 minutes. Insert sample tube into bag. For models equipped with scanner allow up to 2.5 minutes per channel for clean air sample analysis. Observe LCD response, if dispalyed PPM value drops lower then Haloguard IR is detecting the presence of the gas of interest or another gas which absorbs IR light at the same frequency. Remove sample tube from bag and observe LCD response. If displayed PPM value moves higher, look for refrigerant leaks or possible sources of interfering gases (See Before Installation section 3e). and relocate sensor. Keep in mind that the Haloguard IR is much more sensitive than hand held leak detectors, it may detect a leak when hand held units show no response We wish to aid with any problems you might experience with the Haloguard IR. When contacting Thermal Gas Systems, Inc. Service Department, please have the following information ready 1. Model Number and Serial Number. 2. Description of problem. 3. Remove faceplate. Place jumper on Alarm setting function. and record settings. 4. Measure voltage between SIG and GND.(Fig. 2) in SETUP and RUN modes Write down values 5. Advise the condition of all LED s and all information displayed on the LCD. Rev.1/26/98 10

SPECIFICATIONS Technology: Photoacoustic Infrared Electrical Supply: 115-230 VAC, 50-60Hz Output Signal: Analog Output Alarm Outputs: Readout: Std. 4 x 3A Dry Contact Relays (either NO or NC) Opt. 0-5 VDC or 4-20mA Three Level Contact Closure Digital Meter, Displayed in PPM Gas Type, Range and Options Display accuracy: 1ppm 0-100 ppm Range 10ppm 100-1000 ppm Range Ranges: Response Time: 0-1000 ppm R-11,R- 12, R-22, R123, R-134a, < 1 Minute single point < 2.5 Minutes per point with optional scanner. Operating Conditions: IR Module +40 o F to +110 o F Non-condensing Controller 0 o F to +120 o F Non-condensing Fault Diagnostics: Indicator Light or LCD Readout for fault diagnostics See Figure 5) Materials: IR Module NEMA 4/12/13 IP 65 Design Controller NEMA 4/12/13, IP65 Design Weight: IR Module Controller: 10 lbs. 4 lbs Dimensions: IR Module 6-1/2 W x 14-1/4 H x 4 D Controller 5-1/2 W x 9 H x 4 D Initial factory settings are: Function Setting Gas Alarm 1 Alarm 2 Full Scale PPM TWA Alarm Level Figure 9 - Initial Factory Settings GAS TLV- TWA* CEIL PEL R-11 1000 R-12 1000 1000 R-22 1000 1000 R-123 50 R-134a 1000 1000 Other exposure limits are pending. TLV-TWA = 8hr./day, 40hr./wk. avg. Short term exposures should not exceed 3-5 times the TWA for more than 30 min./day. * ACGIH Trademark. Figure 10 - Exposure Limits Rev.1/26/98 11

S G +V S G (OPTIONAL) STROBE LIGHT HALOGUARD IR CONTROLLER Upper Circuit Board See Chart for Connection WARNING Analog output lines must not be connected to any kind of voltage or current source, serious damage will result. IR SENSOR MODULE GROUND AC COMMON AC HOT Green White Black G N L Lower Circuit Board Line Cord 115 VAC 50/60Hz. S Used only with Scanner (Optional) Rev. 1/26/98 FAULT Plug in DIN Connector ALARM 1 ALARM 2 1 2 3 4 5 6 7 8 9 10 11 12 ANALOG OUTPUTS TO BAS OR OTHER (3) Cable to IR Sensor Module OFFSCALE + A + L (OPTIONAL) AUDIBLE ALARM Notes: 1. Power Cord - Provided w/ wall plug connector and 8 Ft. 3 conductor wire. 2. Audible and Visual Alarm (Optional) factory wired. Remote Audible and Visual Alarms must be 120VAC and connected to terminal Strip on Lower Circuit Board. 3. Sensor Cable between Haloguard IR Controller and IR Sensor Module - Maximum Length 1000FT. Use, 3 conductor 18 or 20ga. w/ foil shield. 4. Analog Outputs (Optional) are either 0-5 to 10VDC, and 4-20mA. 5. If Optional scanner is installed, Red wire is connected to scanner terminal on upper circuit board. Figure 11 - Wiring 12 Diagram GROUND AC COMM Cable from Controller Green White AC HOT Black Line Cord 115 VAC 50/60Hz. G N L S G ALL WIRES COMING INTO IR SENSOR MODULE ARE HARD WIRED. Cable Color Code White - S Signal Black - G Ground Red - Scan Scanner(Only)