SUBMITTAL AG015KSVAJH/AA Samsung DVM Heat Pump Chiller. Submitted to Reference Approval Construction Unit Designation Schedule #

Similar documents
Increase your flexibility.

Submitted to Reference Approval Construction Unit Designation Schedule #

Submitted to Reference Approval Construction Unit Designation Schedule #

Samsung 360 Cassette, Single Zone, Split System

Well rounded. 360 CASSETTE. A truly circular cassette. Enjoy even airflow from a beautifully sleek design that fits into any setting.

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

MAC-120HE-03 Air-Cooled Chiller

MACH N-407 Heat Pump Air-Cooled Chiller

SUBMITTAL DATA - OUTDOOR UNIT VEP075N432G VRF HEAT PUMP

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC N-407 Air-Cooled Chiller

Submittal Data: LIVS09HP230V1B. Job Name Location Date. Submitted To. Cool Quiet Comfort & more 9,000 BTU/H (208/230V) Wall Mounted Heat Pump System

TECHNICAL SPECIFICATIONS

Submittal Data: VIR12HP230V1B. Job Name Location Date. Submitted To

Submittal Data: VIR09HP115V1B Job Name Location Date. Submitted To. Innovative Ductless solutions 9,000 BTU/H (115V) Wall Mounted Heat Pump System

Submittal Data: VIR24HP230V1B. Job Name Location Date. Submitted To

Submittal Data: UMAT48HP230V1AF. Job Name Location Date. Submitted To

15A 18-2 AWG / 300V THHN Cooling (Max) 118 F (48 C)

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES

NFZP Variable Refrigerant Flow Guide Specification

Innovative Ductless Mini Split Solution Submittal Data: GUHD24ND3FO/GKH24D3FI Job Name Location Date

Power Input (Max) 1,500 W Dehumidification 1.7 pt/hr HSPF 10.5 COP 4.2 Compressor Type DC Inverter Driven 2-Stage Rotary Heating at 17 F FLA 8.

15A Operating Range Communication Wire Size 18-2 AWG / 300V THHN Cooling (Max) 118 F (48 C)

18-2 AWG / 300V THHN Operating Range MCA 2.0A Cooling (Max) 118 F (48 C) MOCP/Breaker Size 15A (Min) 0 F (-18 C)

MHNCCW (4-Pipe) Chilled/Hot Water Ceiling Concealed 208/230V 4-Pipe Heating & Cooling Fan Coil 12,000 BTUH

A single answer for multiple zones.

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

High Ambient / High Efficiency Series. R - 410a. 50Hz. Ducted Split Air Conditioners (5.0 kw kw)

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Cold Remedies. SamsungHVAC.com. Product Registration Required Conditions Apply

CFFWA4P-08-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 24,000 BTUH

A single answer for multiple zones.

The ultimate fresh air solution.

Submittal. Date: September 04, Customer P.O. Number: Customer Project Number:

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH

Product Data INDUSTRY LEADING FEATURES / BENEFITS

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH

VARIABLE REFRIGERANT FLOW (VRF) FULL LINE CATALOG

UP to 14.5 SEER, PACKAGE AIR CONDITIONER UNIT, 2 to 5 TONS 208/230 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT

Call us today! (800)

RECORD SUBMITTAL COVER SHEET

Product Data. 50LJS/TJS Single- Package. Features / Benefits. Rooftop Units - 50 Hz 6 to 12 Nominal Tons

PAJ3. Product Specifications

Advance Product Data

13 SEER CONDENSING UNITS & AIR HANDLERS

CFFWA4P-16-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 48,000 BTUH

CFFWA4P-12-1-U Chilled/Hot Water Universal Mount Fan Coil (4-Pipe) 4-Pipe Heat / Cool Fan Coil 36,000 BTUH

SECTION VARIABLE REFRIGERANT VOLUME (VRV) HVAC SYSTEM

Advance Release September 2009

Advance Product Data

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz

Commercial High-Efficiency Condensing Units

VRF D4 PLUS System. Highlights. Digital Scroll Series. Dealer information. Commercial Air Conditioner Business Units Midea Group

Call us today! (800)

Commercial High-Efficiency Condensing Units

Unit Data - RCA 051 RATED IN ACCORDANCE TO AHRI STANDARD

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

CHS. Product Specifications COMMERCIAL SPLIT SYSTEMS HEAT PUMP UNITS R 410A, 6 10 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

Air-Cooled Condensing Units with Compact Screw Compressors

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/

LG VRF Systems. Air Conditioning Technologies

JOB NAME: LOCATION: PURCHASER: ENGINEER: SUBMITTED TO: FOR: REFERENCE [ ] APPROVAL [ ] CONSTRUCTION [ ] SUBMITTED BY: DATE:

PAR5. Product Specifications

WJH4 Product Specifications

Condensing Units & Air Handlers

Variable Refrigerant Flow

.2 Section Waste Management and Disposal.

SUBMITTAL M4MCW1509A-SUB-1C. Specifications 15 SERIES. Single Zone Mini-Split Inverter System M4MCW1509A1N0A M4TCS1509A11NA TAG:

SUBMITTAL M4MLW1809A-SUB-1A. Specifications 18 SERIES. Single Zone Mini-Split Inverter System M4MLW1809A1N0A M4TLS1809A11NA TAG:

NQ Series Portable Chillers

Call us today! (800)

Water-Cooled Modular Chillers. Product Data Catalog. Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X

SECTION AIR-SOURCE UNITARY HEAT PUMPS

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N

DAIKIN Modular Inverter Air Cooled Chiller

Design guide for DVM Chiller. Design guide for DVM Chiller

High Heat COP. High/Low Stage

SUBMITTAL M4MCW1509A-SUB-1B. Specifications 15 SERIES. Single Zone Mini-Split Inverter System M4MCW1509A1N0A M4TCS1509A11NA TAG:

R4H4. Product Specifications

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

Wicomico County Purchasing 125 N. Division St. Room B-3 Salisbury, MD Ph Fax Addendum # 1

For Modules: ASM002X, ASM003X, ASM005X, ASM008X, ASM010X, ASM015X, ASM020X, ASM030X. Air Cooled Medical Chiller Product Data Catalog

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

GREEN REFRIGERANT R-410A

BRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION. Ver. 1.01

Project ID: 9217 Project name: Fuller Lake Arena Address: Fuller Lake, BC V0R 1K5 Project Type: Sports Complex / Civic Center

MULTIPLO PF Multifunction chillers for indoor installation. Cooling Capacity: kw Heating Capacity: kw

Product Data. 38GJQ MULTI-ZONE DUCTLESS SYSTEM MATCHED WITH 40GRQ / 40GJB / 40GJC / 40GJD / 40GJF Indoor Units Sizes 18, 24, 30, 36, 42, 48 and 56

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

PACKAGED AIR COOLED Product Data Catalog

MHCFC4W Chilled/Hot Water Cassette Fan Coil

MHCFC4W Chilled/Hot Water Cassette Fan Coil

MHCFC4W Chilled/Hot Water Cassette Fan Coil

NH4H4. Product Specifications 14 SEER HORIZONTAL DISCHARGE HEAT PUMP FOR USE WITH DUCTED INDOOR UNIT

TECHNICAL NOTICE: Supplemental External Heat Control/Reduce Fan Operation Indoor Unit Firmware Version: (14/06/13) or newer

WCH5**4. Product Specifications

Transcription:

Job Name Location Purchaser Engineer Submitted to Reference Approval Construction Unit Designation Schedule # Page 1 of 7 Performance Power Compressor 95 F Ambient, Entering Temperature: 54 F, Leaving Temperature: 44 F 15 168,000 Leaving Temperature: 105 F 182,000 Leaving Temperature: 120 F 171,000 Leaving Temperature: 105 F 90,000 Leaving Temperature: 120 F 85,000 95 F Ambient, Entering Temperature: 54 F, Leaving Temperature: 44 F 25.25 Leaving Temperature: 105 F 22.40 Leaving Temperature: 120 F 25.77 Leaving Temperature: 105 F 17.72 Leaving Temperature: 120 F 19.31 10.10 Leaving Temperature: 105 F 12.00 Leaving Temperature: 120 F 9.80 Leaving Temperature: 105 F 7.50 Leaving Temperature: 120 F 6.50 18.80 Voltage (ø/v/hz) 3 / 460 / 60 Maximum Circuit Breaker (MCCB/ELB/ELCB) Minimum Circuit Ampacity (MCA) 50 40 SCCR ka 5 Inverter Driven Scroll X 2 A 16.0 Refrigerant R410A Factory Charge Lbs. 40 Water Side Heat Exchanger Condenser Fan Dimensions Quantity Water Flow (GPM) Minimum Water System Volume 50A Cut Groove Minimum (cooling / heating) 16.8 / 16.8 Nominal (cooling / heating) 33.6 / 33.6 Maximum (cooling / heating) 67.2 / 67.2 Gallons 100.8 2 Propeller X 2 Output (max.) CFM 12,855 BLDC Output W 630 X 2 FLA A 2.0 "WC 0.32 Inches 70 11/16 X 66 3/4 X 30 1/8 Net Lbs. 959 Shipping Lbs. 1,008 Sound Level Sound db (A) 62 Operating Water Temperature Range COP Operating Ambient Temperature Range Safety Certifications US Ton (nominal) Rated Capacity (Btu/h) Power Input (A) EER IPLV Type RLA Connection Type Fan Motor W X H X D Weight (Dry/Wet Bulb: 47/43 F) (Dry/Wet Bulb: 17/15 F) (Dry/Wet Bulb: 47/43 F) (Dry/Wet Bulb: 17/15 F) (Dry/Wet Bulb: 47/43 F) (Dry/Wet Bulb: 17/15 F) Type Type Max. External Static System Specifications Standard F 41-77 When Using Brine F 14-77 F 77-131 F 5-118 F -13-109 ETL (UL 1995) Intelligent logic to ensure proper operation within unit design limitations and operational parameters High pressure sensor, low pressure sensor, over-voltage protection, compressor over- current Protection Devices protection, current transformer, fan motor voltage protection, fan motor thermal protection, overheat protection, phase detection protection, high voltage fuses, water pressure sensors Inverter PCB cooling done with liquid refrigerant to maintain optimal and safe operating temperatures Construction The unit shall be EGI (electronic galvanized steel) with a baked on powder coated finish. Some brackets shall be GI (hot-dipped galvanized steel) Air Side Heat Exchanger The heat exchanger shall be mechanically bonded fin to copper tube. The aluminum fins of the heat exchanger shall have a protective coating. Salt spray test method: ASTM-B117, ISO 21207- the heat exchanger showed no unusual rust or corrosion development to 1,000 hours. Water Side Heat Exchanger The heat exchanger shall be brazed plate type (2) Controls The unit shall be operated via NASA Protocol with s provided by Samsung Can connect up to 16 X AG0**KSVA*H/AA DVM Chillers to a single DVM Chiller module ler (MCM-A00N) to provide various system operation configuration, setup, monitoring, status, and error notification (MCM-A00N is required for operation). The outdoor unit shall have a removable EEPROM that stores unit serial number, startup information, system settings, system tag/name, and other information. Optional FCU Kit (fan coil unit) available to and integrate fan coil units to Samsung central and local s (FCU Kit: MIM-F00N; FCU Kit Central Control Interface Module: MIM-F10N). Controls shall integrate with a BMS system without additional interface modules Control wiring shall be 16 AWG X 2 shielded wire (for communicating s connections). Refrigerant System The compressors shall be Samsung hermetically sealed, inverter driven, direct flash injected, DC scroll type with soft-start capability. The refrigerant system capacity shall modulate based on demand. Flash injected compressors provide advanced low ambient heating performance. Refrigerant flow shall be led by EEV (electronic expansion valve). Other Features Asymmetrical scroll design with rotating compressor operation/priority. Optional night quiet modes to reduce outdoor unit sound (default mode and levels 1-3) with automatic or manual activation. Advanced intelligent defrost logic to significantly reduce defrost cycle frequency by monitoring air resistance across the condenser coil during heating operation to determine defrost operation initiation to prevent unnecessary defrost cycles. In applications where 2-16 modules are configured and led as one system, only 30% or less of the total nominal capacity will enter defrost operation at a time (ex: 6 module system - only one module will defrost at a time; 8 module system - two modules may enter defrost at a time). Optional snow blowing logic to prevent snow accumulation on idle units (enabled by default, can be disabled at any time) Error reset with dry input at outdoor unit (refer to pages 4-5 for input/output details) Three operation patterns can be selected: Standard, Rotation, and Efficiency (refer to page 6 for details) Operation patterns can be adjusted at DVM Chiller unit or at lers (refer to page 7 for details) Energy savings options to reduce system energy consumption by configuring Water Law to automatically adjust leaving water set temperature based on ambient temperature or room temperature. Room temperature (heating and cooling, two points each), outdoor temperature (heating and cooling, two points each), and water temperature (heating and cooling, two points each) settings can be configured when using Water Law. Water Law can be based on outdoor temperature or indoor temperature. Water Law based on room temperature requires installation of PT1000 temperature sensor (field provided) in the space to monitor room temperature (refer to page 6 for details). Performance is certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Heat Pump Water- unit is certified when operating in cooling. Certified units may be found in the AHRI Directory at www.ahridirectory.org. Combined performance of multiple chillers are not AHRI Certified. DVM Chiller design software is available at www.dvmdownload.com. 2018 Samsung HVAC SHA-DVMS-10082018

Dimensional Drawing Page 2 of 7 70 11/16" 65 1/8" 35 5/16" 10" 70 11/16" 66 3/4" 30 1/8" 30 9/16" 7 9/16" 9 1/16" 19 1/16" 8 15/16" 65 1/8" 6" 30 9/16" 4 1/2" 7 1/16" No. Description No. Description 1 Water connections 5 Communication wiring conduit opening (side) 2 Power wiring conduit opening (front) 6 Anchor bolt hole 3 Power wiring conduit opening (side) 7 PCB monitoring window 4 Communication wiring conduit opening (front) 888-699-6067

Output Contacts Page 3 of 7 for individual DVM Chiller units A-T/B (terminal block: A) sing heat sile system ising s s ro s ressors s is enabled Not used Not used Refer to technical data book and installation manual for complete operation and details. in DVM Chiller details (not Samsung HVAC)

s SUBMITTAL AG015KSVAJH/AA Input Contacts Page 4 of 7 B-T/B (terminal block: B) 1 Not used Pump operation signal iis not on e 3) 5 4) mode 1 1 2 2 2 2 2 6) 6 6 6 1 over range of water outlet temperature 2 6) Note 1) (MCM-A00N) Note 2) Input types: - (switch). - Instant input: Operate when contact signal changes from OFF to ON / from ON to OFF (push button). 3 o 4 5 6 Refer to technical data book and installation manual for complete operation and details.

Input Contacts (continued) Page 5 of 7 C-T/B (terminal block: C) 9 iat 9 9 (error) error enabled 9 Not used Not used (N/A) (refer to page 6 for details) Not used Not used Not used Not used (N/A) temperature by external input 9 Refer to technical data book for more details and sensor information 2 Refer to technical data book for more details and sensor information 3 If operation pattern is not standard, standard temperature depends on external water outlet temperature sensor. External water outlet temperature sensor should be installed where it can represent the temperature of the water pipe system. Refer to technical data boook for full details. closed (short) Note 9) Input types: - (switch). - Instant input: Operate when contact signal changes from OFF to ON / from ON to OFF (push button). sare and install the appropriate sensor according to the usage. - Refer to technical data book and installation manual for complete operation and details.

Control Points SUBMITTAL AG015KSVAJH/AA Control Points, Water Law Details Page 6 of 7 Below DVM Chiller points are adjustable at the lers/point of noted below. Point of Control (X = supported) Control option Chiller module ler MCM-A00N DMS2.5 (MIM-D01AUN) Central gateway BACnet (MIM-B17BUN) LON (MIM-B18BUN) DVM Chiller dry contact Operation ON/OFF X X X X X Mode: cool, heat, cool storage, hot water X X X X X Operation pattern: standard, rotation, efficiency X X Enable/disable Water Law (adjustable temperature settings of Water Law) X 1 X X X 2 Enable/disable quiet mode (default mode and quiet mode levels 1-3 are selected during system commissioning) X 1 X X X 2 Forced fan mode X X X X Demand/maximum current of module chiller(s): limit current 50% - 100% of design current 1 The setting value is adjustable on MCM-A00N service mode. 2 Adjust the setting value on Hydro ler option setting on DVM Chiller unit X 1 X X X 2 Water Law Details Water Law standards can be configured for cooling and heating operating mode. Water law can be enabled to change the water outlet temperature based on demand load changes according to outdoor or indoor temperature. Water Law configuration according to outdoor temperature Tcool1 Tcool2 Theat1 Theat2 AirCool1 AirCool2 Outdoor temperature Cool Mode AirHeat1 AirHeat2 Outdoor temperature Heat Mode If the unit is not a low temperature water model, the set temperature decided by the Water law will not decrease below 41 F. Tcool1, Tcool2, AirCool1, AirCool2, AirHeat1, and AirHeat2 will be configured at the DVM Chiller unit during system commissioning or at lers noted above. Water Law configuration according to indoor temperature (when using an external temperature sensor) Tcool1 Tcool2 Theat1 Theat2 RoomCool1 RoomCool2 Indoor temperature Cool Mode RoomHeat1 RoomHeat2 Indoor temperature Heat Mode If the unit is not a low temperature water model, the set temperature decided by the Water law will not decrease below 41 F. Tcool1, Tcool2, RoomCool1, RoomCool2, RoomHeat1, and RoomHeat2 will be configured at the DVM Chiller unit during system commissioning or at lers noted above. Refer to technical data book and installation manual for complete operation and details.

Standard Control SUBMITTAL AG015KSVAJH/AA Operation Patterns All modules start operating at the same time, and each module operates in the operation pattern which set in the installation service mode. The default for each module is Standard. Page 7 of 7 Unit 1 Unit 2 Unit 1 Unit 2 Operation of all units Standard is suited for applications that always has a high cooling and heating load factor. Rotation Control DVM CHILLER s water outlet temperature is led according to the water outlet temperature average value of all operating units in a module. However, if you set Use for an external water temperature sensor, it s the water outlet temperature according to a temperature value from the sensor. Modules in a group operate in Standard. The module with the highest priority starts operating first, and if the module reaches full load, a module with the following priority will start operating. When the module with the lowest priority operates at the minimum capacity and the water outlet temperature reaches close to the set temperature, the compressors of the module stop. Module 1 Module 2 Module 1 Module 2 Unit 1 Unit 2 Unit 1 Unit 2 Start operating all units in the module Full load operation Start operating all units in the module Rotation is suited for applications that have lower capacities at load side while starting a DVM CHILLER and has small fluctuation in momentary load. Efficiency Control DVM CHILLER s water outlet temperature is led according to the water outlet temperature average value of all operating units in a module. However, if you set Use for an external water temperature sensor, it s the water outlet temperature according to a temperature value from the sensor. Only one unit with the highest priority operates, and if the unit operates with the optimum efficiency, a unit with the following priority will operate. When all units reach efficient operating condition, each unit operates at capacity between efficient operating condition and the maximum capacity condition. When all units reach efficient operating condition and the water outlet temperature reaches close to the set temperature, the unit with the lowest priority s decrease compressor operating capacity. Unit 1 Unit 2 Unit 1 Unit 2 Operation of 1 unit Operation with efficient Hz Off Efficient operating condition Efficiency is suited for applications that has both an operating section with the low load and a focused operating time. When all units operate with the optimum efficiency, they the pressure of their compressors in a range between higher than efficient Hz and lower than full load Hz separately. Efficient Hz means the most efficient Hz (speed) of inverter. Maximum capacity condition Efficient operating condition Unit 1 Unit 2 Refer to technical data book and installation manual for complete operation and details.