Major Fault Caused by Stator Winding Circuit Ring Failure

Similar documents
Contents. Preface. Chapter 2 Faults, types and effects The development of simple distribution systems Faults-types and their effects 7

Electrical Energy department

17 TH APRIL 2017 Switch Board Monitoring Protecting Switchboard. Courtesy of ABB. Paul Lee

SDG&E Feeder Protection Philosophy:

Multi-Technology Fault Identification

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS

ABB Medium Voltage Days MEA 2016 Proactive safety ABB medium-voltage switchgear

Transmission Line Protection End to End Testing

T22 - Arc Flash Hazards and Arc Resistant Equipment- Understanding the Standards

A three-pole dead-tank SF 6 circuit-breaker incorporating one interrupter per pole in single-pole enclosures with a common operating mechanism

Cat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE

Arc Fault Detection Devices (AFDDs) Protecting People and Property

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

The Generator Condition Monitor Explosion Proof Design. The GCM-X

Contents The IET Regulations, BS 7671, and this Guide 1.1 The need for this Electrician s Guide 1.2 The IET Regulations BS 7671

IEEE Transformer Committee PC Distribution Transformer Monitoring - User

Step by Step Detailed Procedure Expected Result Observations Verify power off at all loads on emergency power. Verify all loads have power.

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

FreezGard. Self-regulating crankcase heater. Product Overview

Description (Data Point Name) Unit Size

Development of standards for MV Switchgear for Arc Flash protection. ABB Group May 20, 2013 Slide 1

40 CDe ENCLOSURES AND DISTRIBUTION BOARDS FOR SPECIFIC STANDARDS

7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management

Heat Pump Defrost Board Replacement Kit

Series G Molded Case Circuit Breakers Amperes Technical Data and Specifications. NG-Frame. Product Description

AQ 100 Series. Arc Flash Protection System

Animals:Goats:Bleat.Calls,Warbling.Baa,Movements.Rubbing,Barn,Medium.Close,Interior,BG.Dog.Barks 01:21.618

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS

Environmental. Electrical Specifications at 25 O C TYPE HL E Output Constant Current. Output Voltage Range

AC Backward Curved Motorized Impellers

Commissioning the Fire Suppression System for 500/230 kv Transformers of EGAT s Nongchok Substation

Distribution Control Center Operator Training

Standard PRC Protection System Misoperation Identification and Correction

SEL Arc-Flash Solutions

Microgrid Fault Protection Based on Symmetrical and Differential Current Components

INSTALLATION INSTRUCTIONS AND OWNER S MANUAL FOR

Distributed Generation (greater than 10kW) Connecting to Vector s electricity network

ELECTRIC INSTANTANEOUS WATER HEATER INSTALLATION GUIDE AND OWNERS MANUAL THERMOSTATIC

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES

SEL Arc-Flash Solutions

SENTINEL D - Fault Passage Monitoring

FALCON SERIES 12 METAL CLAD

HNC-120BE-L/R-B HNC-150BE-L/R-B HNC-180BE-L/R-B HNC-210BE-L/R-B COUNTER SHOWCASE MODEL SERVICE MANUAL HOSHIZAKI

Metering systems 0548EN April 2014

NOTICE . SAFE SERVICING PRACTICES. Electric Wall Oven with Electronic Oven Control

Welcome! Today s topic: Small Home Repairs. November 14, 2015

US Navy Leading the Way in Switchboard Protection

CIRCUIT BREAKER FAIL PROTECTION

Motor Controller AC Semiconductor Motor Controller Type RSBS23..A2V.2C24..

Lloyd s Register Type Approval System Test Specification Number 3

FALCON SERIES 12 METAL CLAD

ASPEN CANADA. Available From:

Soft Starter AC Semiconductor Motor Controller Type RSBS23..A2V.2C24..

EE034: Electrical Maintenance for Engineers & Technicians

UPM I. Unit Protection Module. Installation and Operation Manual (2015/06)

KSUF CONTROL AND MONITORING UNIT. Description. Installation Designed for wall installation.

PD alarm system brings peace of mind in Malta

Environmental. Electrical Specifications at 25 O C TYPE HL E Output Constant Current

Smoke Detector Activation of any smoke detector shall start the alarm verification mode.

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

APPLICATION NOTE. Applying pressure sensing in arc flash protection applications with air magnetic circuit breakers

The CAB & DAB Air Curtains

FACILITY CONNECTION STANDARD

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

Guide Specification Model CTG Automatic Transfer Switch

CVGF. Water Cooled Centrifugal Chillers

Standard PRC Protection System Misoperation Identification and Correction

4. Applicability: 4.1. Functional Entities: 4.2. Facilities:

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING

3T/7T MRI FACILITY. SOP Number: Emergency Fire. Revision Chronology. Facility Manager Signature: Date: Version Number Date Changes

Call us today! (800)

CONTENTS AUTOMATIC TRANSFER SWITCHES

Fleck 5600 Carbon Filter Installation & Start Up Guide

MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack

VOLTAGE QUALITY MONITORING IMPACT OF VOLTAGE DISTURBANCES AND THE NEED OF VOLTAGE QUALITY MONITORING

5. CBS Alarms Responding to a CBS Alarm Understanding the Alarm Condition A-CBS-008 Circuit Breaker Sentinel Page 109 of 156

Welcome to Hager Presentation

Progressive Cavity Sewer Systems

PRIUX HOME D. High-efficiency double circulating pumps Heating Air conditioning 50 Hz OPERATING RANGE APPLICATIONS BENEFITS

REA 105 Arc Protection Module. Operator s Manual

Call us today! (800)

Table of Contents. Important Safety Instructions. WARNING: If the instructions contained in this manual are not followed

Compatibility between Smoke Alarms and Arc-Fault Circuit Interrupters

Intelligent Security & Fire Ltd

ARC MAPPING IN THE ADVENT OF AFCI, GFCI, AND GFEP CIRCUIT PROTECTION DEVICES

Electrical Safety Through Design. Mersen EP formerly Ferraz Shawmut

Clean Water Made Easy

Datasheet: K-22 LO Sensor

A CASE STUDY ON FAILURE OF DRY TYPE TRANSFORMERS IN DISTRIBUTION SYSTEM

SECTION AUTOMATIC TRANSFER SWITCHES

Freeze Protection Thermostat TRACON MODEL GPT 3 Installation and Operation Manual

38-SDMS-03 SPECIFICATIONS FOR LV DIGITAL PANEL METERS

RD:30 Specification No. TI/SPC/PSI/AUTOTR/0090 For 50U5/150 MVA, 220/132 kv Auto Transformer

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.

Hoshizaki America, Inc.

RENDERED TO. Radial Engineering Limited 1588 Kebet Way Port Coquitlam, B.C. V3C 5M5

Vacuum Interrupters. Outstanding vacuum-related manufacturing techniques of MEIDEN has

INSTRUCTION MANUAL T119 1MN0110 REV. 0. operates with ISO9001 certified quality system

GPS 140 NEC Requirements for Generators. Professional Development Seminar Series NEC Requirements for Generators

CARSON MANUFACTURING CO., INC NORTH RURAL STREET INDIANAPOLIS, IN (888) TECHNICAL BULLETIN

Transcription:

Case study Major Fault Caused by Stator Winding Circuit Ring Failure Joël Pedneault-Desroches, P. Eng.

Presentation Outline Introduction Inspection report Chronology of events Repair Conclusion 2

Introduction August 13, 2017 : 202 MVA, 13.8 kv generator failed and forced the evacuation of a power house 3

Presentation Outline Introduction Inspection report Chronology of events Repair Conclusion 4

Inspection report Main damages to the generator: Stator circuit ring (section of 6 feet) 18 Bottom bars seriously damaged Cable ducts and instruments 5

Inspection report: Stator circuit ring Circuit S2 (phase B) 60 cm Circuit E1 (phase A) Circuit ring insulation is burned and damaged around the fault 60 cm (3 feet) of S2 circuit ring is missing (copper pipe of 3 ½ inches and ¾ thickness) 6

Inspection report: Stator circuit ring (2) Golf ball hole in circuit E1 (phase A) Circuit E1 moved by a inch Support bloc opened by the force of the fault 7

Inspection report: Bottom bars Insulation of 18 bottom bars was seriously burned and covered by copper 8

Inspection report: Instrumentation Many cable ducts and instruments were burned Neutral cable, neutral CTs cables, RTDs cables 9

Inspection report: Generator circuit breaker Burned spots in the mobiles contacts Current fault: ~ 100 ka rms (~12 pu) 10

Presentation Outline Introduction Inspection report Chronology of events Repair Conclusion 11

Chronology of events: Protection 08:57:03: After being stopped for a part of the night, the group is started 1 min 08:58:03: The generator circuit breaker is closed 2 min 43 sec 09:00:46: Abnormal voltage of third harmonic at the neutral of the generator detected 1 sec 09:00:47: Smoke detected in the generator 19 sec 09:01:06: Current in reverse sequence detected 15 sec 09:01:21: Current in reverse sequence alarm 3 sec 09:01:24: First overvoltage in the neutral of the generator 3 sec 09:01:27: Tripping with complete stop by differential protection, fire protection activated 12

Chronology of events: Protection 08:57:03: After being stopped for a part of the night, the group is started 1 min 08:58:03: The generator circuit breaker is closed 2 min 43 sec 09:00:46: Abnormal voltage of third harmonic at the neutral of the generator detected 1 sec 09:00:47: Smoke detected in the generator 19 sec 09:01:06: Current in reverse sequence detected 15 sec 09:01:21: Current in reverse sequence alarm (400 ms) 3 sec 09:01:24: First overvoltage in the neutral of the generator (15-25 ms) 3 sec 09:01:27: Tripping with complete stop by differential protection, fire protection activated Duration of the fault 41 seconds Alarm Tripping alarm 13

Chronology of events: Summary of the event Fault started with a resistive contact that made circuit S2 (phase B; neutral end) rise in temperature and start an arc that caused : Smoke detection inside the generator; Intermittent ground fault not constant enough to shut down the unit by the operation of protections (lower voltage side); Damage the insulation of the circuit E1 (phase A; high voltage end). It ends by a phase-to-phase fault with E1 and S2 causing the unit to trip by differential protection. 14

Presentation Outline Introduction Inspection report Chronology of events Repair Conclusion 15

Repair: Stator bars Wave winding First bottom bar cost 20 top bars Bars replaced: 18 bottom and 37 top (55 total) Challenge: Work to be done with the rotor in place 16

Repair: Stator bars (2) 1 Removing the bars after debrazing and removing the wedges 17

Repair: Stator bars (3) 2 Replacing the bars after cleaning and painting the slots with semi-conductive paint (Hipot tests on spare bars before installation: 34 kvac, after insertion of the bottom bars: 32 kvac, after insertion of the top bars: 30 kvac) U packing with semi-conductive resin: Semi conductive paper (0.1 mm) Semi conductive resin Roebel Bar 18

Repair: Stator bars (4) 3 Final tests after the radial wedging with original wedges (ripple springs), brazing and attaching the bars - Final Hipot: 13.8 kvac - Winding resistance 19

Repair: Circuit ring Preparing and brazing the junction Original junction : New junction: 20

Repair: Final look 21

Presentation Outline Introduction Inspection report Chronology of events Repair Conclusion 22

Conclusion Bad junction in the circuit ring can be difficult to detect with conventional protection setting and can cause serious damages to the generator. Protection logic has to be revised to reduce the damages in case of failure (protection sensitivity, combining smoke detection with ground fault for tripping ). Other monitoring solutions such as permanent thermal imaging should be considered to enable early detection of such faults. The fault caused a down time of 3 months; repair was a success. 23

Questions? 24