Fume cupboards and microbiological safety cabinets

Size: px
Start display at page:

Download "Fume cupboards and microbiological safety cabinets"

Transcription

1 Fume cupboards and microbiological safety cabinets Aesthetic To be agreed. Functional requirements General Fume cupboard Employers Requirements: BS/EN14175 All general fume cupboard installations must be designed in accordance with BS/EN All fume cupboards must be connected to dedicated fume extract systems via a fully seam welded PVC/Polypropylene/Stainless steel ducting system, or other types as appropriate to suit use of system. Where exposure to ultra-violet degradation is experienced, ductwork, fan housing and motor assembly must be treated to avoid degradation from sunlight and weather. Fume cupboard airflow types: All new fume cupboards to be designed to a face velocity design to be no greater 0.3 m/s average face velocity at 500mm sash height, using purpose designed low flow type fume cupboards only. (0.5m/s face velocity designed fume cupboard with a reduced flow will not be permitted) All general fume cupboard system designs must incorporate the ability to run the 0.3 m/s fume cupboard at a face velocity in a range of 0.2 m/s to 0.5m/s regardless of type of cupboard. All cupboards will be commissioned to their correct velocities by use of variable speed devices (invertors) and not by damper adjustments. Dampers to be provided for fine tuning only (e.g. < +/ 5%) Where multiple fumes cupboards are connected to a common extract duct (not recommended) balancing dampers will be provided for fine-tune balancing only. 1All velocity/volume control to be via VSD s. Under-bench Solvent cabinets must have separate extract systems (one per room) and not be part of individual fume cupboard installations. Use of supported face flow technology must be adopted to ensure ventilation systems are not compromised. Should supportive flow not be used, then a full non-linear 3D modelling exercise must be carried out for supply air distribution into the fume cupboard areas. Full laminar flow supply grilles must be adopted and use of ceiling voids as plenums will NOT be permitted. Where risk assessment of processes precludes low flow cupboards, the Chair of Fume cupboard Working Group and an Estates Maintenance Engineering Services representative

2 must give written authority for designers to use of higher flow rates after the appropriate consultation with Head(s) of department(s) concerned. An appropriate request form for this action will be required to be completed. This will account for both Safety and Energy issues associated with higher flow rate cupboards. A charge may be made for the additional energy use over and above 0.3 m/s, based upon actual flow rates and hours of use. Containment, Spillage and Robustness Fume cupboard minimum containment factors must be at least 2.1 x 10 3 for all new installations. The minimum containment factor of 2.1 x 10 3 will be expected at both 0.5m/s and at 0.3 m/s face velocities at 500mm sash height and at 900mm full face sash opening height. These will be ratified once commissioned by an independent assessor. Spillage testing to BS/EN must be carried out and results must show that there is less than 0.01ppm spillage of SF 6 at all test positions at 0.3m/s AND 0.5m/s at sash heights of 500mm, 900mm and with the horizontal sash slid fully sideways open and vertical sash fully closed position On-site robustness tests in accordance with EN shall be included for all new and recommissioned fume cupboards. Type-testing will be provided as a supplementary certificate but alone will not be sufficient without the on-site testing. Controls All fume cupboards to be complete with auxiliary no-volt relays for Run, start and fault signals and these must be connected back to the University Building Energy Management Systems. All fume cupboards to be complete with energy saving auto-sash closing devices and 0-10v control signalling to the VSD BeMS controller to maximise energy savings when the fume cupboard is unattended and left running. All sashes shall be vertically opening types and in addition will have a 50:50 split horizontally opening sash ability for the entire sash height. Fume cupboard fans must NOT be fed from HVAC or BeMS control panels but must have their own dedicated supplies to ensure maintenance on HVAC/BeMS panels can be carried out without compromising the fume cupboard supplies. Fume cupboard enable signalling cable must be directly wired to each corresponding motor and reliance upon comm s must not be used. Roof Ductwork All ductwork to have protection against mechanical damage. Any positions where ductwork traverses roof must have purpose made bridge walkways to prevent personnel stepping on ductwork. Ductwork is to be dedicated for fume cupboards and should not incorporate general extract.

3 No fire dampers will be fitted in fume cupboard extract ducts. 1 hour rated intumescent fire protection wrap and collars will be used where ducts pass through fire barrier/ fire zoned areas. Flexible ductwork connection to fan must be chemically resistant to the same specification as the ductwork. Lightning arrestor tape to be fitted to each outlet terminal to terminate within 150mm of top of outlet. Outlets to terminate a minimum of 5 metres above finished floor level. Removal cap air test points to be provided within the ductwork on the suction and discharge side of fan, each within 1 metre of the fan. Terminal outlet to be fitted with concentric cone reducing piece on top of the terminal to ensure a minimum face velocity of 10m/s is maintained. Specialist cupboards that require different ductwork materials and design must be separately approved by the fume cupboard working group and via individual risk assessment. (e.g. radioisotope and very high risk containment) Fume cupboard extract Motor Class IE3 (EFF0) high efficiency three phase motor to BSEN to a minimum of IP65X with Variable Speed Device (VSD) and mains combined Electro-Magnetic Interference (EMI)/ Radio Frequency Interference (RFI) filter for each and every VSD. Or IE4 Synchronous permanent magnet motors Motor to be installed on anti-vibration mounts. All motors to be sited in such a way to be immediately adjacent to the outlet and keeping positive pressure ductwork in atmosphere wherever possible. Fan Direct drive to motor via coupled connection to avoid the need to remove impellor. Belt drive connections between motor and fan not permitted. In-line fans will not be generally used. Where no other option is available and approved by the fume cupboard working group, bifurcated fans will be used. Fume cupboard to be connected to an individual dedicated extract system and not shared system wherever possible. VSD manufacturer to be used will be Trend or ABB. Notes: IE1 (EFF2), IE2 (EFF1) (to BSEN ) or lesser standard motors are not permitted and must be removed and replaced at the contractors cost if found on site. Maximum length of run from VSD device to motor must be indicated. All cabling from VSD to motor must be screened for EMI/RFI. VSD to be located within plant space and not on roof or adjacent to its own fume cupboard in a dedicated ventilated enclosure provided cable runs between VSD and motor does not exceed 20 metres.

4 Fans and motor sizes must match to ensure motor is correctly rated to run between 30% and 100% full load speed rating. Motor Isolation All poles to be isolated with lockable isolator to a minimum of IP65X immediately adjacent to each motor. Isolator to be provided to VSD Labelling: An identical unique fume cupboard number must be allocated by Estates Division. Each fume cupboard number will be labelled on both the fume cupboard itself and on the motor isolator on the roof. Labels must be permanently fixed and not self adhesive. All mains and control cables will be fully labelled both on outer sheathing and on individual cores to detail location, panel, way No and cable marker number. Fume cupboard sizes Range of sizes to be in 300mm modular format and will include 1200mm, 1500mm, 1800mm and 2100mm Low headroom versions required Make-up Air The entire supply and extract systems must be designed to provide the correct volumes and airflow patterns to suite the fume cupboard requirements. Air supply air grilles in fume cupboard areas must be of the laminar flow type with a maximum face velocity not exceeding 0.5 m/s and must not be within 1.5 metre zone of the face of any fume cupboard installation Ceiling void for plenum usage must be avoided wherever possible and fully ducted systems are preferred. Where ceiling void plenums cannot be avoided, the plenum must not traverse over the top of the fume cupboards and should not be within 1.5metre of any fume cupboard installation footprint. Make-up air design must be agreed in writing with the potential fume cupboard manufacturer(s) prior to going out to tender. Fume cupboard Construction Construction of frame must adequately show contrasting colours to ensure visually impaired personnel can distinguish frame from handles, etc. Colours: White - sikkens Colormap 439 A1 - Carcasses - Front panels

5 - Parts of panels - aluminium parts - Fume cupboard panel, top - Special storage units Grey - Sikkens Colormap 498 C3 Platine grey - RAL Worktops Construction: - Handles - Sash frames Panel external carcasses -Steel or Aluminium -10mm minimum Water resistant Medium Density Particle board lined with 6mm solid laminate and all edges sealed. Internal fume cupboard compartment bases (dependant upon Fume cupboard useage): 10mm minimum raised edge on all sides Thickness minimum 33mm Types available - Stoneware - Solid ceramic base - Solid Laminate (Trespa) - Polypropylene grade stainless steel Regardless of base type, all drainage outlets must be located in the bases and must be recessed with at least 1mm recess from lowest part of base to prevent any liquids from being retained from spillages/wash-down processes. Side panel services spines Each side panel services spine shall be capable of housing a minimum of 4 No single socket outlets, 6 No mechanical valve outlets, 1 No 75mm double-grommetted, fully ducted service hole (into each respective internal side of the fume cupboard) and indicators as necessary. Internal fume cupboard compartment sides (dependant upon Fume cupboard useage): Types available - Stoneware

6 - Glazed walling - 6mm minimum thickness solid laminate - 12mm minimum thickness polypropylene grade stainless steel Note: Faced particle board of any type will not be permitted. Sash Glass All to be Kite marked tempered safety glass (TSG) clear in all cases. 1 front frame with fixed pane of tempered safety glass (TSG) 1 vertical, weight-relieving sash with double anti-slip device and two horizontal sliding panes of tempered safety glass (TSG) Hydrofluoric acid usage circumstances may require special sash materials. Fume cupboard electrical supply Each fume cupboard shall be supplied via a dedicated 32A supply from a local fume cupboard fuseboard. This supply shall terminate of the front of each fume cupboard top valance to the main isolator of the fuseboard which must be located in an accessible position without the need to remove any panels. The fume cupboard manufacturer shall supply and install an eight module single phase and neutral metalclad flush mounted fuseboard complete with M9 rated miniature circuit breakers. The fuseboard will be manufactured by one of the following: TBC, all complete with integral isolators. The outgoing ways shall be provided for the following:- Module No s 1 & 2 63A double pole isolator Module No s 3 & 4 16A 30mA RCBO outlet feeding 1 No fume cupboard radial circuit to RHS of cupboard with 4 No 13A single high integrity earth double pole switched socket outlets installed in the RHS side services spine only. Module No s 5 & 6 16A 30mA RCBO outlet feeding 1 No fume cupboard radial circuit to LHS of cupboard with 4 No 13A single high integrity earth double pole switched socket outlets installed in the LHS side services spine only. Module No 7 10A MCB feeding fume cupboard controller Module No 8 6A MCB feeding fume cupboard lighting. Socket outlets radial circuit: From each 16A RCBO, the fume cupboard manufacturer shall connect a TBC corrugated PVC-U conduit complete with nylon adaptors to supply a dedicated LSF/PVC/Cu 6491Y singles in conduit installation using 2.5mm 2 radial circuit + 2.5mm 2 dual earthing conductors to BS7671 latest edition. All socket outlets will be of the TBC series high integrity earth double pole switched 1 gang type. Sockets must be installed in side pillars and not in the front of the open hood area to prevent back-wash turbulence from users. Flexible cables will not be permitted.

7 Fume cupboard Lighting Cabling from fume cupboard fuseboard will be wired in 1.5mm 2 LSF/PVC/Cu singles (Brown live phase, Blue neutral phase, green/yellow earth) in TBC corrugated PVC-U conduit from 6A outgoing MCB. Flexible cables will not be permitted. Luminaires to be of the high frequency electronic type or LED dimmable only. Linear fittings will be used throughout with T5 triphosphor tubes only. LED lighting may be considered as an option. PL, PLC or 2D lamps will not be permitted. Tube/fitting changes must be possible without accessing internal working space of fume cupboard to avoid the need for decontamination processes. Lighting level of 500 Lux with uniformity in excess of 0.95 and low glare factor required. Luminaires not installed to this specification will cause the fume cupboard installation to be rejected. Any other wiring will be LSF/PVC/Cu singles (Brown live phase, Blue neutral phase, green/yellow earth) in TBC corrugated PVC-U conduit. Fume cupboard controllers to incorporate:-on/off switch c/w on LED indicator. Sash high LED indicator and audible alarm (min 60dB(A) at 1 metre). Low flow/flow failure LED indicator and audible alarm (min 60dB(A) at 1 metre. Timed Sash mute button with LED indicator to show mute in operation. (Timer to be engineer adjustable from 5 seconds to 10 minutes) Audible alarm when in operation must be non-mutable except on dedicated mute button. Note: - Alarm outlet must not be able to be blocked with any form of compound e.g. plasticine, Blue-tak or similar. Fume cupboard mechanical supplies All mechanical services to each cupboard must have individual, easily accessible lockable isolation devices provided at the point of intake to each cupboard. All piped services connections from mains to cupboards will be installed in non-flexible pipework, suitable bracketed to British standards/en swater services installation must comply with the WRaS approval scheme with all fittings kite-marked and tested to the WRaS scheme requirements. Flexible hose of any type will not be permitted. All pipework will be end-feed soldered or brazed only. Compression or push-fit joints will not be permitted. Water services outlets must be directly over drain outlets to avoid flooding of the fume cupboards. All internal pipework in fume cupboards will also be installed in non-flexible pipework throughout. Mechanical services outlets will be installed in positions not to interfere with the operations of the fume cupboard and will not be installed over access points.

8 A List of approved Fume cupboard manufacturers will be supplied by the University of Bath. Testing/Commissioning Independent testing and commissioning will follow the manufacturer s own set-up testing commissioning and must be witnessed by the University of Bath L.E.V. group representatives. Inclusion for face velocity tests, and on-site robustness tests in accordance with EN shall be included for all new and recommissioned fume cupboards. Type-testing alone will not be sufficient. Where new cupboards or material alterations are made in existing laboratories, all fume cupboards in that laboratory must be recommissioned. No fume cupboard can be put into service unless signed off in writing by the chair or nominated representative of the University LEV group. Fire Conditions Under fire alarm activation the fume cupboard extract system will continue to operate. The makeup air into the space will be deactivated. A fireman's override switch (Normal/Off) is to be provided at the main reception adjacent to any fire alarm panel to enable them to switch off the fume cupboard extract, if required. Switch to be clearly labelled "Fire Switch", "Fume Cupboard Extract System Shut off". Lifecycle Minimum of 15 years. Approved manufacturers Microbiological Safety Cabinets: TBC Fume Cupboards: TBC Fume Cupboard Controls: TBC

9 Accessories: TBC Spares No requirements.

Technical Catalogue laboratory furniture system

Technical Catalogue laboratory furniture system Technical Catalogue laboratory furniture system Technical Catalogue The new design of our SCALA range of laboratory furniture will set the trend for future laboratory design. But only if design and functionality

More information

Technical Catalog laboratory furniture system

Technical Catalog laboratory furniture system Technical Catalog laboratory furniture system Technical Catalog The new design of our SCALA range of laboratory furniture will set the trend for future laboratory design. But only if design and functionality

More information

If a peak space temperature to about 28ºC is acceptable to the occupants then a naturally ventilated solution is a viable option.

If a peak space temperature to about 28ºC is acceptable to the occupants then a naturally ventilated solution is a viable option. Air handling units Aesthetic Not to add significantly to the existing ambient noise levels. Functional requirements If a peak space temperature to about 28ºC is acceptable to the occupants then a naturally

More information

Technical Catalog laboratory furniture system

Technical Catalog laboratory furniture system Technical Catalog laboratory furniture system Technical Catalog The new design of our SCALA laboratory furniture program is creating the laboratory of the future. Only when design and functionality effectively

More information

INSTALL AN ELECTRIC SHOWER

INSTALL AN ELECTRIC SHOWER INSTALL AN ELECTRIC SHOWER The plumbing and wiring involved in installing an electric shower requires sound basic skills in both areas of expertise. Ensure that wiring and plumbing are properly installed.

More information

Fire detection and alarm

Fire detection and alarm Fire detection and alarm Aesthetic Install all cabling and cable containment neatly and unobtrusively, meeting the highest electrical industry installation standards. Neatly lay and securely fix cables.

More information

SOUTH DUBLIN COUNTY COUNCIL Traffic Management Centre Roads (Traffic and Transportation) Department

SOUTH DUBLIN COUNTY COUNCIL Traffic Management Centre Roads (Traffic and Transportation) Department SOUTH DUBLIN COUNTY COUNCIL Roads (Traffic and Transportation) Department TECHNICAL SPECIFICATION 4 SDCC-TS-04 SIGNAL INSTALLATION REQUIREMENTS REQUIREMENTS FOR THE DESIGN AND INSTALLATION OF TRAFFIC CONTROL

More information

Advanced Air. Hard Wired Damper Control Panels. Systems 10, 11, & 12. Hard-Wired Systems. Bespoke Systems Available. Value Engineered Solutions

Advanced Air. Hard Wired Damper Control Panels. Systems 10, 11, & 12. Hard-Wired Systems. Bespoke Systems Available. Value Engineered Solutions ISSUE A, MAY 2008 Hard Wired Damper Control Panels Systems 10, 11, & 12 Hard-Wired Systems Bespoke Systems Available Value Engineered Solutions Overview The Hard-Wired Control Panels On a number of projects

More information

Technical Catalog laboratory furniture system

Technical Catalog laboratory furniture system Technical Catalog laboratory furniture system Technical Catalog The new design of our SCALA laboratory furniture program is creating the laboratory of the future. Only when design and functionality effectively

More information

Technical Catalogue laboratory furniture system

Technical Catalogue laboratory furniture system Technical Catalogue laboratory furniture system Technical Catalogue The design of our SCALA range of laboratory furniture will set the trend for future laboratory design. But only if design and functionality

More information

DWYER INSTRUMENTS, INC. P.O. BOX 373 MICHIGAN CITY, INDIANA 46360, U.S.A. Series 670 Hood Monitor. Bulletin AV-670

DWYER INSTRUMENTS, INC. P.O. BOX 373 MICHIGAN CITY, INDIANA 46360, U.S.A. Series 670 Hood Monitor. Bulletin AV-670 Bulletin AV-670 Series 670 Hood Monitor Specifications - Installation and Operating Instructions DWYER INSTRUMENTS, INC. P.O. BOX 373 MICHIGAN CITY, INDIANA 46360, U.S.A. Phone: 219/879-8000 Fax: 219/872-9057

More information

INSTALLATION AND USER S MANUAL COOKER HOOD RS-600/A-S

INSTALLATION AND USER S MANUAL COOKER HOOD RS-600/A-S INSTALLATION AND USER S MANUAL COOKER HOOD RS-600/A-S RS-600 (CHS60SS)-GB-05.indd 1 6/8/2010 9:30:59 AM TABLE OF CONTENTS 1. Introduction 2 2. Safety precaution 2 3. Intended use 3 4. Parts supplied 3

More information

Class II ECO Generation 8 Microbiological Safety Cabinet

Class II ECO Generation 8 Microbiological Safety Cabinet Class II ECO Generation 8 Microbiological Safety Cabinet Class II ECO Generation 8 Microbiological Safety Cabinet Our Design Philosophy A Microbiological Safety cabinet is a safety product first and foremost.

More information

FUME CUPBOARDS DESIGN FEATURES GENERAL ARRANGEMENT FACE VELOCITIES EXTRACTION SYSTEMS AIRFLOW CHARACTERISTICS

FUME CUPBOARDS DESIGN FEATURES GENERAL ARRANGEMENT FACE VELOCITIES EXTRACTION SYSTEMS AIRFLOW CHARACTERISTICS DESIGN FEATURES 1233 1233 mm mm 150 150 335 335 mm mm 150 150 HEIGHT HEIGHT TO TO EXTRACT EXTRACT APERTURE APERTURE FILTER FILTER 315 1000 mm SECTION 590 mm GENERAL ARRANGEMENT 150 FACE VELOCITIES 25 265

More information

ORION. Safety Class 2 100% exhaust. ALMOST Rocket Science

ORION. Safety Class 2 100% exhaust. ALMOST Rocket Science LaboGene SCANdinavian by design. ORION ALMOST Rocket Science Safety Class 2 100% exhaust Probably the best Class 2 with 100% exhaust for work with animal handling or high concentrations of organic solvents

More information

LABORATORY CABINETS 103

LABORATORY CABINETS 103 LABORATORY CABINETS 103 MINIFLO DUE - TYPE 60 COMPACT VERTICAL LAMINAR FLOW CABINET DESIGNED FOR MICROBIOLOGICAL AND PCR PROCEDURES A very compact size (footprint 73x61 cm), for small laboratory or dedicated

More information

Laboratory Fume Cupboards

Laboratory Fume Cupboards Laboratory Fume Cupboards 2006 (d)irene/ /Fumecupboards 4Jun07.doc.doc The University of Hong Kong Safety Office Laboratory Fume Cupboards Table of Content 1. Introduction 2. Components of a Fume Extraction

More information

5.0 Installation Instructions

5.0 Installation Instructions 5.0 Installation Instructions 5.1 Location Within the laboratory, pharmacy, etc., the ideal location of the biological safety cabinet is away from personnel traffic lanes, air vents (in or out), doors

More information

User Information Sheet 008 : 2010

User Information Sheet 008 : 2010 User Information Sheet 008 : 2010 Formerly UIS008, July 2009 ELECTRICAL INSTALLATIONS ASSOCIATED WITH BULK LPG INSTALLATIONS 1. Introduction This Information Sheet describes some of the principles and

More information

Centair CMEV.4 / CMEV.4e / CMEV.4eHT Mechanical Extract Ventilation (MEV) System Installation Instructions

Centair CMEV.4 / CMEV.4e / CMEV.4eHT Mechanical Extract Ventilation (MEV) System Installation Instructions Centair CMEV.4 / CMEV.4e / CMEV.4eHT Mechanical Extract Ventilation (MEV) System Installation Instructions Commissioning Data: To be completed by the Commissioning Engineer. Refer to User/Homeowner Guide

More information

CHEMICAL FUME HOOD PROGRAM

CHEMICAL FUME HOOD PROGRAM Reed College 3203 Southeast Woodstock Blvd. Portland Oregon 97202-8199 CHEMICAL FUME HOOD PROGRAM Last Reviewed: 3/20/17 I. PURPOSE... 1 II. SCOPE... 1 III. REFERENCES... 2 IV. PROGRAM RESPONSIBILITIES...

More information

Phenomena up close. Demonstration fume cupboards. Special features

Phenomena up close. Demonstration fume cupboards. Special features FUME CUPBOARDS Demonstration fume cupboards The mobile fume cupboard AeroEM will fascinate audiences in the room. Position your experiments behind safety glass and supply them with gas, water or electricity.

More information

Fire and Smoke Control Systems

Fire and Smoke Control Systems Control Systems Electrical Mechanical Standard Panel Modular design for control and monitoring Premier Panel Customised design for control and monitoring Fully Addressable Fully programmable data wired

More information

WHHR Midi & Midi Lite

WHHR Midi & Midi Lite WHHR Midi & Midi Lite Residential Whole House Heat Recovery Units with Low Energy EC Motors Optional - Integral LCD Installation, Operating and Maintenance Instructions Image of model with LCD screen Page

More information

Division 11 - Equipment

Division 11 - Equipment Division 11 - Equipment 11 40 00 Food Service Equipment 1. Prepare specifications for food service equipment in close coordination with University food service personnel. 2. Specify that the Contractor

More information

MRXBOX95B-LOFT. Mechanical Ventilation Unit with Heat Recovery & Summer Bypass for Loft Mounting. Installation and Maintenance

MRXBOX95B-LOFT. Mechanical Ventilation Unit with Heat Recovery & Summer Bypass for Loft Mounting. Installation and Maintenance MRXBOX95B-LOFT Mechanical Ventilation Unit with Heat Recovery & Summer Bypass for Loft Mounting Installation and Maintenance The EMC Directive 2004/108/EC The Low Voltage directive 2006/95/EC 1.0 Introduction

More information

Smoothflow Student Fume Cupboard Installation Instructions

Smoothflow Student Fume Cupboard Installation Instructions Calibre Solutions Ltd 37 Manurere Rise, RD1 Matakohe 0593 Freephone: 0800 422 542 Phone: +64 21 684 273 Fax: +64 9 813 1319 Smoothflow Student Fume Cupboard Installation Instructions Refer Numbered Installation

More information

RV Products Division INSTALLATION INSTRUCTIONS FOR SERIES PACKAGE AIR CONDITIONER

RV Products Division INSTALLATION INSTRUCTIONS FOR SERIES PACKAGE AIR CONDITIONER RV Products Division INSTALLATION INSTRUCTIONS FOR 46413 SERIES PACKAGE AIR CONDITIONER 1. WARNINGS IMPORTANT NOTICE These instructions are for the use of qualified individuals specially trained and experienced

More information

Snifter. User Manual. Distributor

Snifter. User Manual. Distributor Snifter User Manual Distributor Version 1.3 08/09/2009 1 Table of Contents 1. INTRODUCTION... 3 1.1 Safety... 3 1.2 Product overview... 3 1.3 How does it work?... 3 2. INSTALLATION... 4 2.1 Selecting the

More information

Requirements for Electrical Installations

Requirements for Electrical Installations BRITISH STANDARD BS 7671:2018 Corrigendum (December 2018) Requirements for Electrical Installations IET Wiring Regulations Eighteenth Edition The Institution of Engineering and Technology and BSI NO COPYING

More information

Ceiling swirl diffusers

Ceiling swirl diffusers X X testregistrierung Ceiling swirl diffusers Type Plenum box with damper blade and square diffuser face Horizontal swirling air discharge For comfort zones, with fixed air control blades Circular and

More information

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

ELIX 1003 IPX4. Energy Efficient Centrifugal Fan with EC Motor Installation and Operating Instructions

ELIX 1003 IPX4. Energy Efficient Centrifugal Fan with EC Motor Installation and Operating Instructions ELIX 1003 Energy Efficient Centrifugal Fan with EC Motor Installation and Operating Instructions 3 speed continuous running SAP Appendix Q Eligible 3 models: - standard - timer - humidity control for all

More information

LV100 Standard LV100PC Pull Cord LV100T Timer LV100H Humidistat LV100HP Humidistat and Pull Cord LV100PIR

LV100 Standard LV100PC Pull Cord LV100T Timer LV100H Humidistat LV100HP Humidistat and Pull Cord LV100PIR Installation and operating instructions LV100 Standard LV100PC Pull Cord LV100T Timer LV100H Humidistat LV100HP Humidistat and Pull Cord Safety extra low voltage toilet/bathroom 100mm fan range Integral

More information

Secuflow laboratory fume cupboards

Secuflow laboratory fume cupboards laboratory fume cupboards More safety, economy and comfort than ever: Our fume cupboards We are continuously working to improve laboratory equipment because being the leader in innovation is no accident.

More information

Ceiling swirl diffusers

Ceiling swirl diffusers X X testregistrierung Ceiling swirl diffusers Type Plenum box with damper blade (optional) Horizontal swirling air discharge With very low sound power level for comfort zones, with fixed air control blades

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5 Construction Standards Page 1 of 5.1 General Description.1 The University requires that all new fire alarm system control panel, components, and devices, as required for the project, be Secutron 2900 Series

More information

Secuflow laboratory fume cupboards

Secuflow laboratory fume cupboards Secuflow laboratory fume cupboards More safety, economy and comfort than ever: Our Secuflow fume cupboards We are continuously working to improve laboratory equipment because being the leader in innovation

More information

SECTION BIOLOGICAL SAFETY CABINETS AND LAMINAR AIRFLOW WORK STATIONS

SECTION BIOLOGICAL SAFETY CABINETS AND LAMINAR AIRFLOW WORK STATIONS SECTION 11 53 53 BIOLOGICAL SAFETY CABINETS AND LAMINAR AIRFLOW WORK STATIONS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. 2. Delete other items or paragraphs in the section

More information

WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED

WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED EQV R-407C WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED Size Cooling Heating [kw] [kw] 5 1,9 2,2 7 2,4 2,5 9 2,6 2,5 15 3,3 3,2 17 3,7 3,7 REPLACE: BT02E008GB-01 The Versatemp EQV units

More information

INCREASE YOUR LAB EFFICIENCY

INCREASE YOUR LAB EFFICIENCY INCREASE YOUR LAB EFFICIENCY Mars Pro Class 2 Ultra-Safe Triple Filters Microbiological Safety Cabinets Scandinavian by Design Mars Pro, the ideal choice for your laboratory, wherever personal, environment,

More information

U tube models PTU 09, 12, 15, 25, 30, 35, 40, 45. single linear tube models PTS 09, 12, 15, 25, 30, 35, 40, 45

U tube models PTU 09, 12, 15, 25, 30, 35, 40, 45. single linear tube models PTS 09, 12, 15, 25, 30, 35, 40, 45 U tube models PTU 09, 2, 5, 25, 30, 35, 40, 45 & single linear tube models PTS 09, 2, 5, 25, 30, 35, 40, 45 installation, servicing & operating instructions INSTALLATION, SERVICING AND OPERATING INSTRUCTIONS

More information

ELEGANCE IPX4 IPX7. Low Carbon Fan with EC Motor Installation and Operating Instructions. 6 models:

ELEGANCE IPX4 IPX7. Low Carbon Fan with EC Motor Installation and Operating Instructions. 6 models: ELEGANCE Low Carbon Fan with EC Motor Installation and Operating Instructions 6 models: - SAP Appendix Q Eligible 3 speed continuous running - timer - humidity control - SELV - low voltage for all domestic

More information

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module FIRE ALARM CONTROL EQUIPMENT Addendum October 2006 Instructions for new style EN54-4 Power supply unit module MXLK-05 Issue 2.0 June 2007 INSTALLATION Safety Suppliers of articles for use at work are required

More information

Safegard V4 Bespoke Intelligent Damper Control and Monitoring System

Safegard V4 Bespoke Intelligent Damper Control and Monitoring System August 2016 Range and Features All system wide activity is logged and viewable for diagnostics and preventative maintenance Safegard V4 Bespoke Intelligent Damper Control and Monitoring System Devices

More information

Under Desk Power.

Under Desk Power. Rotasoc is widely considered to be the industry standard for customisable under desk power as it includes a comprehensive selection of multi-socket power and data modules with 360 rotatable socket outlets,

More information

CBC - Active Chilled Beam. Halton CBC. Active Chilled Beam

CBC - Active Chilled Beam. Halton CBC. Active Chilled Beam Halton CBC Active Chilled Beam Combined cooling, heating, and supply air unit for flush installation within a suspended ceiling Well suited for spaces with high cooling loads and low humidity load Ideal

More information

IVF/ART Series Laminar Flow Cabinets

IVF/ART Series Laminar Flow Cabinets IVF/ART Series Laminar Flow Cabinets Applications IVF/ART procedures for human and animal reproduction require a controlled work environment. Ultra-clean conditions are required to minimise microbial contamination

More information

ALMOST Rocket Science FORTUNA. Clean Air Cabinet. Vertical Laminar Flow Cabinet

ALMOST Rocket Science FORTUNA. Clean Air Cabinet. Vertical Laminar Flow Cabinet ALMOST Rocket Science FORTUNA Clean Air Cabinet Vertical Laminar Flow Cabinet FORTUNA ALMOST Rocket Science Advanced design for a clean working environment In your daily work with the Fortuna, you will

More information

Installation and Maintenance

Installation and Maintenance 1.0 INTRODUCTION MRXBOXAB-ECO-LP1SW (Standard Unit) MRXBOXAB-ECO-LP1-OHSW (Opposite Hand Unit) Mechanical Ventilation Unit with Heat Recovery for Ceiling Void Mounting Installation and Maintenance The

More information

Loadstar AC/DC Systems

Loadstar AC/DC Systems WARRANTY W A R R A N T Y YEAR The Loadstar range of AC/DC central battery units comply with the latest relevant European and British standards. High quality, cost effective units provide secure sources

More information

INCREASE YOUR LAB EFFICIENCY

INCREASE YOUR LAB EFFICIENCY 1 INCREASE YOUR LAB EFFICIENCY Titan Small Portable Vertical Laminar Flow Clean Air Cabinets Scandinavian by Design 2 We have the cabin et for you for w hatever k ind of protectio n you req uire! Compact

More information

Catalogue. ActionpacEMSStandard. Electro Mechanical Control & Monitoring System.

Catalogue. ActionpacEMSStandard. Electro Mechanical Control & Monitoring System. Catalogue ActionpacEMSStandard Electro Mechanical Control & Monitoring System www.actionair.co.uk sales@actionair.co.uk Actionair Actionpac EMS Standard Electro- Mechanical Control and Monitoring System

More information

Installation and Maintenance

Installation and Maintenance 1.0 Introduction MRXBOX-ECO2 (Standard Unit) MRXBOX-ECO2-OH (Opposite hand Unit) MRXBOXAB-ECO2 (Standard Unit) MRXBOXAB-ECO2-OH (Opposite hand Unit) Mechanical Ventilation Units with Heat Recovery for

More information

Prescriptive Requirement for Smoke Control

Prescriptive Requirement for Smoke Control HKIE CPD Training Course (II) 7July 2009 Organization by The Hong Kong Institution of Engineers Fire Division Co-organized by the Association of Registered Fire Services Installation contractors of Hong

More information

Snifter ATEX22 VERSION. User Manual. Distributor

Snifter ATEX22 VERSION. User Manual. Distributor Snifter ATEX22 VERSION User Manual Distributor Version 1.4 09/09/2009 Table of Contents 1. INTRODUCTION... 3 1.1. Safety... 3 1.2. Product overview... 4 1.3. How does it work?... 4 2. INSTALLATION... 5

More information

Faster UltraSafe Class II Microbiological Safety Cabinets. Protection, safety, reliability. And more.

Faster UltraSafe Class II Microbiological Safety Cabinets. Protection, safety, reliability. And more. Faster UltraSafe Class II Microbiological Safety Cabinets Protection, safety, reliability. And more. BEYOND MINIMUM SAFETY REQUIREMENTS FASTER UltraSafe ULTRA FEATURES Faster UltraSafe Microbiological

More information

SECTION AIR COILS

SECTION AIR COILS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

Installation and Maintenance

Installation and Maintenance 1.0 INTRODUCTION MRXBOXAB-ECO-LP1 (Standard Unit) MRXBOXAB-ECO-LP1-OH (Opposite Hand Unit) Mechanical Ventilation Unit with Heat Recovery for Ceiling Void Mounting Installation and Maintenance The LP1

More information

Royal Wolfson Foundation Laboratory Refurbishment Grants Scheme Final Report: University of Glasgow, Prof Lee Cronin

Royal Wolfson Foundation Laboratory Refurbishment Grants Scheme Final Report: University of Glasgow, Prof Lee Cronin Royal Wolfson Foundation Laboratory Refurbishment Grants Scheme Final Report: University of Glasgow, Prof Lee Cronin Background In January 2011, the Royal Society Wolfson Laboratory Refurbishment Scheme

More information

Technical Specification

Technical Specification Technical Specification Surface Area Valve Service Unit Module Semi Flush Area Valve Service Unit Module Product Description The CPX AVSU Module is used in conjunction with area valve service units (AVSU).

More information

TC MODULE (FFD) (with Gas Hob)

TC MODULE (FFD) (with Gas Hob) TC MODULE (FFD) (with Gas Hob) Installation Instructions REMEMBER: when replacing a part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification

More information

Laboratory Automation & Robotic System Enclosures

Laboratory Automation & Robotic System Enclosures LA Product Range Laboratory Automation & Robotic System Enclosures A World Class Manufacturer of Enclosures Innovative Solutions for Advancing your Research Bigneat manufacturing a smarter range of enclosures

More information

Ceiling air diffuser INDULTHERM INDULTHERM-e

Ceiling air diffuser INDULTHERM INDULTHERM-e Technical Information Ceiling air diffuser INDULTHERM INDULTHERM-e Effective cooling and heating with a diffuser Thermomechanical or electrical switching Draught-free air distribution for cooling down

More information

DX AIR CURTAIN. SensAir

DX AIR CURTAIN. SensAir DX AIR CURTAIN SensAir Biddle and Daikin Complete climate system Since 2006 Biddle and Daikin have joined forces to provide a complete climate system for shops and public buildings. By combining Biddle

More information

PANEL. Cableflow International Limited

PANEL. Cableflow International Limited Cableflow International Limited PANEL TM The PANEL, a simple yet understated name for this extremely flexible medical supply unit, embodies our experience and innovative approach to bedhead services attained

More information

FHHT 18 3 PHASE /32A / 400V ELECTRIC HEATER PRODUCT MANUAL P

FHHT 18 3 PHASE /32A / 400V ELECTRIC HEATER PRODUCT MANUAL P FHHT 18 3 PHASE /32A / 400V ELECTRIC HEATER PRODUCT MANUAL P 1 of 13 These instructions should be read by: The specifying engineer. The installation engineer. The user. The service engineer. WARNINGS Failure

More information

Type TDF-SilentAIR WITH VERY LOW SOUND POWER LEVEL FOR COMFORT ZONES, WITH FIXED AIR CONTROL BLADES

Type TDF-SilentAIR WITH VERY LOW SOUND POWER LEVEL FOR COMFORT ZONES, WITH FIXED AIR CONTROL BLADES Homepage > Products > Air Diffusers > Ceiling diffusers > Ceiling swirl diffusers > Type TDF-SilentAIR Type TDF-SilentAIR WITH VERY LOW SOUND POWER LEVEL FOR COMFORT ZONES, WITH FIXED AIR CONTROL BLADES

More information

THE IMPACT OF FACILITY HVAC SYSTEMS ON BIOLOGICAL SAFETY CABINETS

THE IMPACT OF FACILITY HVAC SYSTEMS ON BIOLOGICAL SAFETY CABINETS THE IMPACT OF FACILITY HVAC SYSTEMS ON BIOLOGICAL SAFETY CABINETS Prepared for the: RPIC/SLCan Sustainable Labs Regional Workshop Presented by: THE IMPACT OF FACILITY HVAC SYSTEMS ON BIOLOGICAL SAFETY

More information

Adv. 8.4 Guidelines for Biosafety Cabinets Rev

Adv. 8.4 Guidelines for Biosafety Cabinets Rev UNIVERSITY OF CINCINNATI Environmental University Health Services 556-4968 Health and Safety ADVISORY NO. 8.4: GUIDELINES FOR THE SELECTION, INSTALLATION AND USE OF BIOSAFETY CABINETS (INCLUDING ISSUES

More information

Installation Instructions

Installation Instructions Installation Instructions 30" ELECTRIC Downdraft Cooktop Modules selected at time of purchase IMPORTANT: Read and save these instructions. Part No. 208040 A 438589 Quick Reference Table of Contents: Pages

More information

INFRARED IP55 HEATER INSTRUCTIONS FOR: MODEL:- QZWP45N 1. SAFETY INSTRUCTIONS

INFRARED IP55 HEATER INSTRUCTIONS FOR: MODEL:- QZWP45N 1. SAFETY INSTRUCTIONS INSTRUCTIONS FOR: INFRARED IP55 HEATER MODEL:- QZWP45N Thank you for purchasing a Consort Claudgen product. Manufactured to a high standard this product will, if used according to these instructions and

More information

EXTRACTOR HOOD. Please read all the instructions carefully before starting the installation. 230 / 240V 50Hz

EXTRACTOR HOOD. Please read all the instructions carefully before starting the installation. 230 / 240V 50Hz abc EXTRACTOR HOOD Please read all the instructions carefully before starting the installation Model Stock Ref Napoli 120812 Napoli Plus (white) 436083 Napoli Plus (Silver) 436084 230 / 240V 50Hz PLEASE

More information

Under Desk Power. 60

Under Desk Power. 60 Rotasoc is widely considered to be the industry standard for customisable under desk power as it includes a comprehensive selection of multi-socket power and data modules with 360 rotatable socket outlets,

More information

POWER SHOWERS Models 4500M 5002M 4500T 5002T

POWER SHOWERS Models 4500M 5002M 4500T 5002T II POWER SHOWERS Models 4500M 5002M 4500T 5002T Performance Shower Products CUSTOMER SERVICE HELPLINE: 01883 730339 CONTENTS PLEASE READ THESE INSTRUCTIONS CAREFULLY: This booklet covers all models in

More information

Carbon Film Installation Instructions

Carbon Film Installation Instructions Contents Page 2 Page 3 Page 4 Page 5 Page 8 Product Overview Pre-Installation & Electrical Provision Depron Underlay Installation Carbon Film Installation - Under Wood/Laminate Flooring Notes & Trouble

More information

SECTION LABORATORY EQUIPMENT CONSTRUCTION STANDARD PART 1: GENERAL Scope of Standard

SECTION LABORATORY EQUIPMENT CONSTRUCTION STANDARD PART 1: GENERAL Scope of Standard PART 1: GENERAL 1.01 Scope of Standard A. This standard provides general guidance concerning the specific preferences of the University of Texas at Austin for safety equipment used in or in support of

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

Microbiological Safety Cabinets ENVAIR eco safe Comfort Plus

Microbiological Safety Cabinets ENVAIR eco safe Comfort Plus Microbiological Safety Cabinets ENVAIR eco safe Comfort Plus Class II Microbiological Safety Cabinet Standard EN 12469 Width (m) 1.2 / 1.5 1.8 Clean technology for a clean environment ENVAIR eco safe Comfort

More information

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems 233100 AIR DISTRIBUTION PART 1: GENERAL 1.01 RELATED SECTIONS A. Section 230700 HVAC Insulation B. Section 237300 Air Handling C. Section 230900 Building Automation and Control System Guidelines D. Section

More information

"WHHR125DC" Whole House Heat Recovery Unit with Low Energy DC Motor. Installation, Operating and Maintenance Instructions domestic and commercial use

WHHR125DC Whole House Heat Recovery Unit with Low Energy DC Motor. Installation, Operating and Maintenance Instructions domestic and commercial use "WHHR125DC" Whole House Heat Recovery Unit with Low Energy DC Motor Installation, Operating and Maintenance Instructions domestic and commercial use Page 2 Contents Section Page Number Introduction 3 How

More information

MINI BENCH TOP CHAMBER MODEL: MI-80-A-H

MINI BENCH TOP CHAMBER MODEL: MI-80-A-H MINI BENCH TOP CHAMBER MODEL: MI-80-A-H Introduction: The Mini Bench top chambers are compact sized humidity chambers which can be placed on a work bench or on the optional stand provided. These chambers

More information

Air Comfort. Installation instructions (English) A

Air Comfort. Installation instructions (English) A Air Comfort Installation instructions (English) WWW.BRINKAIRFORLIFE.NL 614788-A This appliance may be used by children as of 8 years of age, persons of reduced mental or physical capacities and those of

More information

Installation and Maintenance

Installation and Maintenance MRXBOX95B-LP1 (Standard Unit) MRXBOX95B-LP1-OH (Opposite Hand Unit) Mechanical Ventilation Unit with Heat Recovery & Summer Bypass for Ceiling Void Mounting Installation and Maintenance The EMC Directive

More information

PHYSICAL FACILITIES Consultant s Handbook Division 01 General Special Requirements for Laboratories. Page 1 of 6

PHYSICAL FACILITIES Consultant s Handbook Division 01 General Special Requirements for Laboratories. Page 1 of 6 1 Applicable Industry Design Guidelines, Standards, and References: 1.1 ANSI/AIHA Z9.5-2012 (or latest version), American Industrial Hygiene Association 1.2 2011 ASHRAE Handbook (or latest version), HVAC

More information

Duct Heaters volts/1 phase volts/3 phase volts/3 phases volts/3 phases. Flange Type Duct Heater.

Duct Heaters volts/1 phase volts/3 phase volts/3 phases volts/3 phases. Flange Type Duct Heater. Duct Heaters Synheat duct heaters come in various sizes and dimensions to fit any compartment. There are three types of duct heaters available: open coil, tubular element or finned tubular heating elements

More information

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply

More information

Laboratory Airflow Monitors & Controls TYPE C STANDARD & NIGHT SETBACK LED & DIGITAL - VAV SYSTEMS

Laboratory Airflow Monitors & Controls TYPE C STANDARD & NIGHT SETBACK LED & DIGITAL - VAV SYSTEMS TYPE C STANDARD & NIGHT SETBACK S Specifications and Owner s Manual PLASTEC VENTILATION, INC. TYPE C STANDARD & NIGHT SETBACK General Description BENEFITS Safety: air flow is maintained at required speed

More information

UC DAVIS Campus Design Guide DIVISION 11 - EQUIPMENT

UC DAVIS Campus Design Guide DIVISION 11 - EQUIPMENT DIVISION 11 - EQUIPMENT LABORATORY FUME HOODS 11 53 13 A. General Fume Hood Requirements 1. Quality Assurance - Published specifications, standards, tests or recommended methods of trade, industry or governmental

More information

INTEGRA PLUS ABC. 230V~ 50Hz. Stock Ref. N. Installation and Wiring Instructions IPX2

INTEGRA PLUS ABC. 230V~ 50Hz. Stock Ref. N. Installation and Wiring Instructions IPX2 INTEGRA PLUS Installation and Wiring Instructions Stock Ref. N INTEGRA PLUS 437666 230V~ 50Hz ABC PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS. PLEASE SAVE THESE INSTRUCTIONS. IPX2 VENT-AXIA

More information

PANTHER. Condensate removal pump Installation and operating guide

PANTHER. Condensate removal pump Installation and operating guide PANTHER Condensate removal pump Installation and operating guide The PANTHER is a self-contained condensate removal system for use directly inside trunking and highwall-mount air conditioners.the small

More information

DC Heat Recovery Unit MVHR Wholehouse heat recovery unit

DC Heat Recovery Unit MVHR Wholehouse heat recovery unit DC Heat Recovery Unit MVHR Wholehouse heat recovery unit Stock Ref. N DC Heat Recovery Unit MVHR 443423 Installation, Maintenance & Users Instructions PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS.

More information

MICRO-KJELDAHL EQUIPMENT ( MM SERIES ) OPERATING AND SAFETY INSTRUCTIONS

MICRO-KJELDAHL EQUIPMENT ( MM SERIES ) OPERATING AND SAFETY INSTRUCTIONS MICRO-KJELDAHL EQUIPMENT ( MM SERIES ) OPERATING AND SAFETY INSTRUCTIONS MICRO-KJELDAHL EQUIPMENT ( MM SERIES ) OPERATING AND SAFETY INSTRUCTIONS CONTENTS PAGE 1 INTRODUCTION... 1 2 SAFETY INFORMATION...

More information

ACCESS SECURITY SYSTEMS (ELECTRONIC LOCKING) & ACCESSIBLE DOOR OPENING DEVICES ON MEANS OF ESCAPE

ACCESS SECURITY SYSTEMS (ELECTRONIC LOCKING) & ACCESSIBLE DOOR OPENING DEVICES ON MEANS OF ESCAPE Fire Safety Technical Note ACCESS SECURITY SYSTEMS (ELECTRONIC LOCKING) & ACCESSIBLE DOOR OPENING DEVICES ON MEANS OF ESCAPE Access Security & Accessible Door Opening Systems - what you need to know: Access

More information

Installation, Operation & Maintenance Instructions Document Ref:

Installation, Operation & Maintenance Instructions Document Ref: Series AM Fan Convectors Installation, Operation & Maintenance Instructions Document Ref: Dunham-Bush Ltd, Downley Road, Havant, Hants PO9 2JD 023 9247 7700 info@dunham-bush.co.uk 121-000-001-A UK:www.dunham-bush.co.uk

More information

CLEAN AIR SYSTEM.

CLEAN AIR SYSTEM. AIISHIL" AIR CURTAINS : JCA-01 : Invisible air door, keeps interior of a clean room dust-free, stops entry of insects, serves as temperature barrier and isolates heating, cooling & humidity. Fabricated

More information

VPC Gas Cabinet Heater Range

VPC Gas Cabinet Heater Range VPC Gas Cabinet Heater Range Industrial & Commercial Heating Systems. www.powrmatic.co.uk HEATING // VENTIATION // AIR CONDITIONING // OEM PRODUCTS VPC Overview Models Available VPC UF - Upright Freeblowing

More information

Consumer Units for Domestic Household (and other) Premises. Amendment No. 3 BS 7671

Consumer Units for Domestic Household (and other) Premises. Amendment No. 3 BS 7671 Consumer Units for Domestic Household (and other) Premises Amendment No. 3 BS 7671 ALL METAL CONSUMER UNITS FOR USE IN DOMESTIC HOUSEHOLD PREMISES 17th Edition Wiring Regulations Incorporating Amendment

More information

LC3000 Level Controller Installation and Maintenance Instructions

LC3000 Level Controller Installation and Maintenance Instructions 4025550/12 IM-P402-36 AB Issue 12 LC3000 Level Controller Installation and Maintenance Instructions 1. General safety information LC3000 NORM ALARM TEST 2. General product information 3. Installation 4.

More information