QHD-125, QHD-200, QHD-250, QHD-325, QHD-400, QHD-500, QHD-650, QHD-750

Size: px
Start display at page:

Download "QHD-125, QHD-200, QHD-250, QHD-325, QHD-400, QHD-500, QHD-650, QHD-750"

Transcription

1

2 Quincy Compressor QHD Series Heatless Regenerative Dryers QHD-125, QHD-200, QHD-250, QHD-325, QHD-400, QHD-500, QHD-650, QHD-750 Instruction book Original instructions Copyright Notice Any unauthorized use or copying of the contents or any part thereof is prohibited. This applies in particular to trademarks, model denominations, part numbers and drawings quincycompressor.com

3 Table of Contents 1 Safety Precautions SAFETY ICONS SAFETY PRECAUTIONS, GENERAL SAFETY PRECAUTIONS DURING INSTALLATION SAFETY PRECAUTIONS DURING OPERATION SAFETY PRECAUTIONS DURING MAINTENANCE OR REPAIR General Description INTRODUCTION AIR CIRCUIT DESCRIPTION SHIFTING TOWERS Controller OPERATION Electric diagram Installation DIMENSION DRAWINGS INSTALLATION PROPOSAL ELECTRICAL CONNECTIONS Operating instructions Maintenance MAINTENANCE RESETTING THE SERVICE COUNTER

4 7.3 DISPOSAL OF USED MATERIAL AIRLOGIC2 Graphic controller AIRLOGIC2 GRAPHIC CONTROLLER CONTROL PANEL ICONS USED MAIN SCREEN CALLING UP MENUS INPUTS MENU OUTPUTS MENU COUNTERS EVENT HISTORY MENU TEST MENU SERVICE MENU PROTECTIONS MENU WEEK TIMER MENU INFO MENU MODIFYING SETTINGS EXTRA MENU WEB SERVER PROGRAMMABLE SETTINGS Problem solving Technical data REFERENCE CONDITIONS LIMITATIONS FOR OPERATION SPECIFIC DATA INSTRUCTIONS FOR USE Guidelines for inspection Pressure equipment directives

5

6 1 Safety Precautions 1.1 Safety Icons Explanation Danger for life Warning Important note 1.2 Safety Precautions, General General precautions 1. The dryers are designed for normal indoor use. 2. The operator must employ safe working practices and observe all related work safety requirements and regulations. 3. If any of the following statements does not comply with the applicable legislation, the stricter of the two shall apply. 4. Installation, operation, maintenance and repair work must only be performed by authorized, trained, specialized personnel. 5. The dryer is not considered capable of producing air of breathing quality. For air of breathing quality, the compressed air must be adequately purified according to the applicable legislation and standards. 6. Before any maintenance, repair work, adjustment or any other non-routine checks, stop the dryer, press the emergency stop button, switch off the voltage and depressurize the dryer. In addition, the power isolating switch must be opened and locked. 7. Never play with compressed air. Do not apply the air to your skin or direct an air stream at people. Never use the air to clean dirt from your clothes. When using the air to clean equipment, do so with extreme caution and wear eye protection. 8. The owner is responsible for maintaining the unit in safe operating condition. Parts and accessories shall be replaced if unsuitable for safe operation. 9. It is not allowed to walk or stand on the dryer components

7 1.3 Safety Precautions during Installation All responsibility for any damage or injury resulting from neglecting these precautions, or non-observence of the normal cautio and care required for installation, operation, maintenance and repair, even if not expressly stated, will be disclaimed by manufacturer. Precautions during installation 1. The machine must only be lifted using suitable equipment in accordance with the applicable safety regulations. Loose or pivoting parts must be securely fastened before lifting. It is strictly forbidden to dwell or stay in the risk zone under a lifted load. Lifting acceleration and deceleration must be kept within safe limits. Wear a safety helmet when working in the area of overhead or lifting equipment. 2. Install the dryer as level as possible and fix it firmly to the floor. 3. Place the machine where the ambient air is as cool and clean as possible. If necessary, install a suction duct. Never obstruct the air inlet. Care must be taken to minimize the entry of moisture at the inlet air. 4. Any blanking flanges, plugs, caps and desiccant bags must be removed before connecting the pipes. 5. Air hoses must be of correct size and suitable for the working pressure. Never use frayed, damaged or worn hoses. Distribution pipes and connections must be of the correct size and suitable for the working pressure. 6. The aspirated air must be free of flammable fumes, vapors and particles, e.g. paint solvents, that can lead to internal fire or explosion. 7. Arrange the air intake so that loose clothing worn by people cannot be sucked in. 8. No external force may be exerted on the air outlet valve; the connected pipe must be free of strain. 9. If remote control is installed, the machine must bear a clear sign stating: DANGER: This machine is remotely controlled and may start without warning. The operator has to make sure that the machine is stopped and that the isolating switch is open and locked before any maintenance or repair. As a further safeguard, persons switching on remotely controlled machines shall take adequate precautions to ensure that there is no one checking or working on the machine. To this end, a suitable notice shall be affixed to the start equipment. 10. Air-cooled machines must be installed in such a way that an adequate flow of cooling air is available and that the exhausted air does not recirculate to the compressor air inlet or cooling air inlet. 11. The electrical connections must correspond to the applicable codes. The machines must be earthed and protected against short circuits by fuses in all phases. A lockable power isolating switch must be installed near the compressor. 12. On machines with automatic start/stop system or if the automatic restart function after voltage failure is activated, a sign stating "This machine may start without warning" must be affixed near the instrument panel. 13. Never remove or tamper with the safety devices, guards or insulation fitted on the machine. Every pressure vessel or auxiliary installed outside the machine to contain air above atmospheric pressure must be protected by a pressure-relieving device or devices as required. 14. Piping or other parts with a temperature in excess of 176 F (80 C) and which may be accidentally touched by personnel in normal operation must be guarded or insulated. Other high-temperature piping must be clearly marked

8 15. For water-cooled machines, the cooling water system installed outside the machine has to be protected by a safety device with set pressure according to the maximum cooling water inlet pressure. 16. If the ground is not level or can be subject to variable inclination, consult the manufacturer. 17. Make sure that all piping is installed stress-free. If the maximum pressure of the compressor is higher than the design pressure of the dryer, a full flow safety valve must be installed between the compressor and the dryer in order to blow-off the excessive pressure in case the safety valve of the dryer should be out of order or blocked Also consult following safety precautions: Safety precautions during operation and Safety precautions during maintenance. These precautions apply to machinery processing or consuming air or inert gas. Processing of any other gas requires additional safety precautions typical to the application which are not included herein. Some precautions are general and cover several machine types and equipment; hence some statements may not apply to your machine 1.4 Safety Precautions During Operation All responsibility for any damage or injury resulting from neglecting these precautions, or nonobservance of the normal caution and care required for installation, operation, maintenance and repair, even if not expressly stated, will be disclaimed by the manufacturer. Precautions during operation 1. Never touch any piping or components of the compressor during operation. 2. Use only the correct type and size of hose end fittings and connections. When blowing through a hose or air line, ensure that the open end is held securely. A free end will whip and may cause injury. Make sure that a hose is fully depressurized before disconnecting it. 3. Persons switching on remotely controlled machines shall take adequate precautions to ensure that there is no one checking or working on the machine. To this end, a suitable notice shall be affixed to the remote start equipment. 4. Never operate the machine when there is a possibility of taking in flammable or toxic fumes, vapors or particles as indicated on the principal data sheet. 5. Never operate the machine below or in excess of its limit ratings. 6. Keep all bodywork doors shut during operation. The doors may be opened for short periods only, e.g. to carry out routine checks. Wear ear protectors when opening a door. 7. People staying in environments or rooms where the sound pressure level reaches or exceeds 90 db(a) shall wear hearing protection. 8. Periodically check that: All guards are in place and securely fastened All hoses and/or pipes inside the machine are in good condition, secure and not rubbing There are no leaks All fasteners are tight All electrical leads are secure and in good order

9 Safety valves and other pressure-relief devices are not obstructed by dirt or paint Air outlet valve and air net, i.e. pipes, couplings, manifolds, valves, hoses, etc. are in good repair, free of wear or abuse 9. If warm cooling air from compressors is used in air heating systems, e.g. to warm up a workroom, take precautions against air pollution and possible contamination of the breathing air. 10. Never operate the machine when there is a risk of taking inflammable or toxic fumes, vapors or particles. 11. Do not remove any of, or tamper with, the sound-damping material. 12. Never remove or tamper with the safety devices, guards or insulations fitted on the machine. Every pressure vessel or auxiliary installed outside the machine to contain air above atmospheric pressure shall be protected by a pressure-relieving device or devices as required. Also consult following safety precautions: Safety precautions during operation and Safety precautions during maintenance. These precautions apply to machinery processing or consuming air or inert gas. Processing of any other gas requires additional safety precautions typical to the application which are not included herein. Some precautions are general and cover several machine types and equipment; hence some statements may not apply to your machine All responsibility for any damage or injury resulting from neglecting these precautions, or nonobservance of the normal caution and care required for installation, operation, maintenance and repair, even if not expressly stated, will be disclaimed by the manufacturer

10 1.5 Safety Precautions During Maintenance or Repair Precautions during maintenance or repair 1. Always use the correct safety equipment (such as safety glasses, gloves, safety shoes, etc.). 2. Use only the correct tools for maintenance and repair work. 3. Use only genuine spare parts. 4. All maintenance work shall only be undertaken when the machine has cooled down. 5. A warning sign bearing a legend such as "work in progress; do not start" shall be attached to the starting equipment. 6. Persons switching on remotely controlled machines shall take adequate precautions to ensure that there is no one checking or working on the machine. To this end, a suitable notice shall be affixed to the remote start equipment. 7. Before removing any pressurized component, effectively isolate the machine from all sources of pressure and relieve the entire system of pressure. 8. Never use flammable solvents or carbon tetrachloride for cleaning parts. Take safety precautions against toxic vapors of cleaning liquids. 9. Scrupulously observe cleanliness during maintenance and repair. Keep dirt away by covering the parts and exposed openings with a clean cloth, paper or tape. 10. Never weld on, or in any way modify, pressure vessels. 11. Whenever there is an indication or any suspicion that an internal part of a machine is overheated, the machine shall be stopped but no inspection covers shall be opened before sufficient cooling time has elapsed; this to avoid the risk of spontaneous ignition of the oil vapor when air is admitted. 12. Never use a light source with open flame for inspecting the interior of a machine, pressure vessel, etc. 13. Make sure that no tools, loose parts or rags are left in or on the machine. 14. All regulating and safety devices shall be maintained with due care to ensure that they function properly. They may not be put out of action. 15. Before clearing the machine for use after maintenance or overhaul, check that operating pressures, temperatures and time settings are correct. Check that all control and shutdown devices are fitted and that they function correctly. If removed, check that the coupling guard of the compressor drive shaft has been reinstalled. 16. Never use caustic solvents which can damage materials of the air net, e.g. polycarbonate bowls. 17. The following safety precautions are stressed when handling desiccant: Take precautions not to inhale desiccant dust. Check that the working area is adequately ventilated; if required, use breathing protection. Do not overfill the dryer when replacing desiccant

11 Also consult following safety precautions: Safety precautions during installation and Safety precautions during operation. These precautions apply to machinery processing or consuming air or inert gas. Processing of any other gas requires additional safety precautions typical to the application which are not included herein. Some precautions are general and cover several machine types and equipment; hence some statements may not apply to your machine. After maintenance or repair, a functional test with depressurized vessels must be performed to check the correct operation of the dryer

12 2 General Description 2.1 Introduction General description The dryers are built to remove moisture from compressed air for industrial purposes. All units are designed for indoor use. Front view, QHD

13 Rear view, QHD

14 Front view, QHD-250 to QHD

15 Rear view, QHD-250 to QHD-750 Reference: Description A Tower A AI Air inlet AO Air outlet B Tower B C Non-return valves T Time card Controller PA Pneumatic actuator PDP Pressure dewpoint sensor (Optional) V Pneumatic valves 1 Purge lines

16 Automatic control of the dryer The controller maintains the pressure dewpoint between programmable limits automatically by defining the switching time. A number of time-based automatic start/stop commands may be programmed (see section Programming clock functions). Take into account that a start command will be executed (if programmed and activated), even after manually stopping the dryer. Protecting the dryer Service warning A number of service operations are grouped in plans (called Service plans A, B and C). Each Service plan has a programmed time interval. If a time interval is exceeded, a message will appear on the display to warn the operator to carry out the service actions belonging to that plan. Warning A warning message also appears if: The pressure dewpoint exceeds a programmed value. Automatic restart after voltage failure For dryers leaving the factory, this function is made inactive. If desired, the function can be activated. Consult Quincy Compressors

17 2.2 Air circuit Flow diagram Reference: Description 4 Open B V1/V2 Closed Inlet valve vessel A/B

18 Reference: V3/V4 V11/V12 V21 V22 Y1A Y2A PI01 PI02 Description Reg. valve vessel A/B Outlet valve vessel A/B Safety valve Safety valve Electrical signal regenerate vessel A Electrical signal regenerate vessel B Pressure indicator vessel A Pressure indicator vessel B 100 Manual valve 101 Pilot air filter 103 Filter + drain 104 Pressure regulator (optional) 107 3/2 Spoolvalve monostable 108 5/2 Namur valve monostable 109 Silencer 112 Adjustable restriction 114 Orifice PS IF1 OF1 DPI PDP01 Pressure switch Inlet filter Outlet filter Differential pressure indicator Pressure dewpoint

19 Description Wet compressed air enters the system and flows to the bottom of one of the towers (A or B) via valve (V1) or (V2). After passing through the desiccant, which adsorbs the moisture contained in the inlet air, the dry compressed air leaves the dryer via outlet valve (V11 or V12). The moisture in the drying tower is removed during regeneration Regeneration Circuit Flow Diagram Please refer the Flow diagram from Air circuit section 2.3 Description The wet desiccant beads are dried in the regeneration stage. The tower is depressurized via blow- off valve (V3orV4). A small portion of the dried air flows via nozzle (114) to the tower to be regenerated. The air is expanded to atmospheric pressure and flows downwards through the desiccant beads. The regenerating air is released via the exhaust valve (V3 or V4) and the silencers (109). 2.4 Shifting Towers Flow diagram Please refer the Flow diagram from Air circuit section Description The operation cycle of the dryers is repetitive and is controlled by the controller. While the desiccant in the first tower dries the compressed air, the desiccant in the second tower is being regenerated and vice versa. Regeneration of the desiccant is achieved by means of purge air from the dryer outlet. A small portion of the dried air flows via the control air valve to the solenoid valves which are controlled by the controller. The air leaving the solenoid valves (when energized) is used to control the pneumatic actuator and the pneumatic valves. After a certain period, the cycle will restart. The fully regenerated tower will be pressurized. Later, the inlet air switches tower and the wet tower is depressurized via the silencers. Then regeneration starts and the purge air flows through the vessel and a silencer. Then the regenerated tower will start drying the compressed air and the other tower will be regenerated

20 3 Controller Control panel 1 LED <Power On> 8 LED <Service alarm> 2 LED <In Operation> 9 Timer countdown 3 LED < Left tower drying> 10 Air inlet 4 LED <Left tower regenerating> 11 Air outlet 5 LED <Right tower drying> 12 Outlet non return valves 6 LED <Right tower 13 Inlet valves regenerating> 7 LED <Service warning> 14 Blow off valves 3.1 Operation The construction of the air dryer is simple, reliable and easy to service. The dryer has two towers, containing the adsorbing material or desiccant. The desiccant is a very porous grain material which can adsorb large amounts of water vapor. The operation cycle of the dryer is repetitive and is controlled by a factory-set timer, located inside the cubicle (3)

21 The compressed air entering the dryer is led to one of the towers by means of the inlet valves (IV), which are controlled by a pneumatic actuator (PA). As the air flows upwards through the tower, the desiccant adsorbs the water vapor and the compressed air is dried. The dry air leaves the dryer via the outlet, connected to the top of the tower. While the desiccant in the first tower dries the compressed air, the desiccant in the second tower is being regenerated. Regeneration of the desiccant is achieved by means of purge air from the drying tower: a small portion of the dried air passes a nozzle (N), expands to atmospheric pressure and flows downwards through the other tower, regenerating the desiccant. The regenerating air is released via the corresponding exhaust valve (PV) and the silencer (S). A second small portion of the dried air flows via the control air valve (CA), a small air filter (AF) and the pressure regulator (PR - only used on 232 psi (16bar) versions) to the solenoid valves (SV). The air leaving the solenoid valves (when energized) is used to control the pneumatic actuator (PA) and the pneumatic valves (PV). The solenoid valves are controlled by the timer. After a pre-set time period, the cycle will restart. The fully regenerated tower will now dry the air while the desiccant in the other tower will be regenerated. Freeze mode By default, the regeneration timer will be reset in case of a power failure during operation or in case the on/ off switch was put in position 0. However, in case the input of remote control connector X3 (also referred to as P4 - freeze contact, see section Electric diagram) was short-circuited, the dryer will switch to <freeze> mode: purge air flow stops, both solenoid valves are closed. When the contact, connected to connector X3 is opened again, the dryer will resume its cycle from where it was stopped and will continue the drying cycle. This feature can prevent loss of compressed air (purge air) when the compressor is not continuously running loaded. On compressors with load/unload regulation, X3 can be connected to a voltage free contact of the compressor (contact closed when the compressor runs unloaded). If no free contact is available, an additional voltage free contact should be installed on the load/unload contactor of the compressor to use this feature. See Electrical connections for more details. Operating principle: during unload operation of the compressor, the regeneration valve of the regenerating tower is closed. That way, the pressure in this tower will increase up to net pressure. From that moment on, purge air is no longer consumed. During load, the regeneration valve is opened and both towers resume their cycle

22 Do not connect X3 when an air receiver is installed before the dryer. X3 should only be connected when the air receiver is installed after the dryer Flow diagram Please refer the Flow diagram from Air circuit section

23 4 Electric diagram The complete service diagram is available inside the electric cabinet

24 Reference Explanation (1) Customer's installation (2) Alarm relay (3) Warning relay (a) Maximum fuses with regard to circuit protection. Cable section may impose fuses of smaller value (b) To connect supply voltage to the transformer: see transformer data plate (c) Connection for remote control (X3): to NO contact of compressor (f) Time setting solenoid valves Reference Designation Reference Designation E1 Controller card E2 LED/Display card K01 Alarm relay K02 Warning relay K03 Solenoid relay, left tower K04 Solenoid relay, right tower Y1 Solenoid valve(s) left tower Y2 Solenoid valve(s) right tower S1 On/Off switch PDP Pressure Dewpoint Sensor (optional) X1 Input PDP X2 Input On/Off contact X3 Input Freeze contact X4 Input Ext1 contact X5 Input Ext2 contact X8 CAN-Bus X9 Supply connections X11 Output alarm relay X12 Output warning relay X13 Output solenoid (left tower) X15 Output solenoid (right tower) T1 Transformer F1 Fuses B1 Opto Coupler

25 5 Installation 5.1 Dimension drawings QHD

26 QHD

27 QHD

28 QHD

29 QHD

30 QHD

31 QHD

32 QHD

33 5.2 Installation proposal Piping Make sure that all pipes, filters, valves, etc. are clean and that they are installed correctly with or without bypass system. Make sure that the piping is installed stress-free. For more information concerning air nets, cooling systems etc. refer to the compressor installation manual. To ensure correct operation of the dryer, it has to be fitted properly into the compressed air circuit, consisting of the compressor, the dryer and the application. Depending from the fact if the remote control connector X3 is used or not (see also section Operation), there are two possibilities: Installation in case X3 is not used If the freeze contact X3 is not used, the correct order of installation is compressor air receiver dryer. For information on the <freeze> contact, consult section Electrical connections. Installation proposal if the freeze contact (X3) is not used

34 COMP AR D Compressor Air receiver Dryer EIV External inlet valve (not shown) To cut off the air supply towards the dryer EOV External outlet valve (not shown) To cut off the air supply towards the air consumer BV Bypass valves (not shown on the drawings) Together with the external inlet valve and the external outlet valve, the bypass valves allow the dryer and the filters to be serviced while nondried air flows through the bypass system. Moisture Separator Moisture separator (optional) To prevent free water from entering the dryer. 1 The drain pipes to the drain collector must not dip into the water. For draining of pure condensate water, install an oil/water separator. 2 Minimum free area to be reserved for the dryer installation 3 Compressed air prefilter for general purpose filtration, particle removal down to 1 micron, maximum oil carry-over 0.5 ppm This filter provides extra protection of the dryer and extends the lifetime of the high efficiency filter cartridge (4). 4 High efficiency filter, particle removal down to 0.01 micron, maximum oil carry-over 0.01 ppm To remove remaining impurities. 5 Dust filter, particle removal down to 1 micron To remove dust particles originating from the desiccant. Positioning in case X3 is used If X3 connection is used, the correct order of installation is compressor dryer-air receiver

35 Installation with use of the X3 connection with the compressor General recommendations Keep the following in mind when installing the dryer: Place the dryer at a location where the temperature never exceeds the limits, see Technical Data. The dryer does not require extra ventilation. Fix the dryer as level as possible to the floor. Make sure the fixating bolts are tightened firmly and that the floor is suitable for taking the weight of the dryer. Provide enough space around the unit to install and service the filter elements. A minimum free space of 800 to 1000 mm (approx. 2.6 to 3.2 ft) is recommended - see the installation proposal drawings. Provide sufficient space under the filter elements in order to be able to replace the filter cartridges without the need having to disassemble the piping. Always install a high efficiency filter (4) at the inlet of the dryer. A prefilter (3) is recommended to extend the lifetime of the high efficiency filter. The drain pipes (1) of the water separator and the filters must not dip into the water. Use a dust filter (5) at the outlet of the dryer. Should oil vapour and odours be undesirable, a carbon filter can be installed downstream the dust filter. If the compressor has no built-in water separator, a moisture separator has to be installed before the dryer in order to prevent free water from entering the dryer, as free water can damage the desiccant. If the condensate contains oil, install an oil/water separator for draining of pure condensate water

36 It is recommended to install bypass pipes with ball valves over the filters in order to isolate the filters during service operations without disturbing the compressed air delivery. It is required to install pressure relief valves on each vessel of the dryer when ball valves are installed at the inlet and the outlet of the dryer to isolate the dryer from the air net Never overload the dryer as a too high air speed will damage the desiccant. It may be recommended to install the air dryer upstream of the air receiver to prevent overload (e.g. after extending the dry air circuit). Consult your supplier if in doubt. See also section Operating instructions for the correct operation procedure. 5.3 Electrical connections The electrical wiring must comply with the local regulations. The air dryer must be earthed and protected by fuses against short-circuiting Electrical wiring Below image shows the connection terminals of the timer card: Timer card

37 Supply connection (X9) Connect the supply voltage to terminals 1X0 (L1 - L2) and 1X3 (earth). Install a power switch and fuses in the supply line. See also section Electric diagram. X3 (freeze contact - P4) If you want to use the feature to freeze the regeneration cycle when the compressor runs unloaded, connect pin 1 and 2 of connector X3 with the potential free contact of the compressor (contact closed = freeze). CAN-Bus connection The timer card can be interconnected in a Local Area Network (LAN) with AirConnect (e.g.combox-e). Application: data communication between timer card and AirConnect (e.g. Combox-E). Addressing and CAN protocols used are the same as for the Advanced controllers. Because the timer card has no programming features however, the exchanged information is pre-configured and cannot be redefined Pin Function Pin Function Pin Function 1 reserved 4 reserved 7 CAN_HIGH 2 CAN_LOW 5 reserved 8 reserved 3 CAN_GND 6 CAN_GND 9 reserved

38 Output alarm relay (X11) These terminals are connected to a relay that switches when the alarm conditions are reached, i.e. when the operating hours counter has reached 8000 hours. Pin designations: Pin Label Description 1 NO2 Alarm contact - Normally Open 2 COM2 Alarm contact - Common 3 NC2 Alarm contact - Normally Closed Output warning relay (X12) These terminals are connected to a relay that switches when the warning conditions are reached, i.e. when the operating hours counter has reached 7750 hours. Pin designations: Pin Label Description 1 NO1 Warning contact - Normally Open 2 COM1 Warning contact - Common 3 NC1 Warning contact - Normally Closed Configuration dip switch settings The dip switch settings are factory set and should not be altered unless the timer card is replaced or an option is fitted. Dip switch number Function 1,2 Cycle time selection 11 bar version: Sw 1,2= Off, On: T1=145 s, T2=35 s 16 bar version: Sw 1,2= On, Off: T1= 195 s, T2= 55 s (Sw 1,2= On, On: not valid) 3 Not configured / used 4 Not configured / used 5 Not configured / used

39 Dip switch number Function 6,7 Control mode selection Sw 6,7=Off,Off: local control enabled Sw 6,7=On,Off: external input control enabled Sw 6,7=Off,On: LAN control enabled (Sw 6,7=On,On: not valid) 8 Not used CANbus address dip switch Dip switch number Function 1,2,3 (reserved) Normally Off Used for diagnostic purposes 4,5,6,7,8 Binary address selector (valid values= 1 to 31) bit 4, bit 3, bit 2, bit 1, bit 0) On = 1, Off = 0 Example of address selection: For CANbus node address 1, the dip switch configuration is: Before switching on the main power supply, check the voltage requirements in the technical specifications or on the dryer s data plate. PDP sensor connector (X1) A PDP sensor can be obtained as an option. With the PDP sensor, the pressure dewpoint (PDP) can be read from the display and the warning LED and alarm LED become active if the PDP set point is not reached. The connections are as follows: Pin Label Description 1 V V out / 50 ma max 2 P ma input (40 ma max) 3 GND Ground

40 See configuration dip switch settings. Dip switch number Function 1,2 Cycle time selection Sw 1,2=off, OFF:T1=95 s, T2=25 s 3 Off=PDP sensor not configured / disabled On=PDP sensor enabled (optional) 4 Off=PDP -40 F version enabled On=PDP -94 F version enabled Do not change the settings without change of desiccant! 5 Off=PDP temperature indication in C On=PDP temperature indication in F 6,7 Control mode selection Sw 6,7=Off,Off: local control enabled Sw 6,7=On,Off: external input control enabled Sw 6,7=Off,On: LAN control enabled Sw 6,7=On,On: not valid 8 Not used

41 6 Operating instructions In your own safety interest, always observe all relevant safety instructions. Initial start-up To start up the dryer for the first time or after a long period of standstill, proceed as follows: 1. If installed, open the bypass valves of the dryer. 2. Close off the air supply from the compressor towards the dryer by closing the external inlet valve (if installed). 3. If installed, close the external outlet valve. 4. Remove the silencers to prevent the silencers from getting clogged by the desiccant and wear a dust mask, safety glasses and ear protection. (This is only required at initial start-up or after the desiccant was replaced). 5. Start the compressor and wait for pressure. 6. Slowly open the external inlet valve. 7. Check the connections of the dryer for air leaks and remedy if necessary. 8. Switch the dryer on by putting main switch S1 in position I. 9. Let the dryer operate for several hours with the external outlet valve closed. 10. In case the silencers were removed, refit the silencers. 11. Gradually open the external outlet valve. 12. If applicable, close the bypass valves of the dryer Normal start If the application allows air that is not completely dry, the valve towards the dry air consumer may be opened even before the optimal PDP is reached. In this case however it will take more time for the desiccant to dry completely. At initial start-up, and specially when the dryer is loaded from the beginning, it can take a long time before the dewpoint is reached. For a dewpoint of -70 C (-94 F), it can take up to more than 10 days before this value is reached If the dryer has not been used for more than 3 months, refer to section Initial start-up. In all other cases proceed as follows: 1. Cut off the air supply from the compressor towards the dryer by closing the external inlet valve. 2. If installed, close the external outlet valve between the dryer and the dry air consumer. 3. Start compressor and slowly open the external inlet valve. 4. Switch the dryer on by putting main switch S1 in position I. 5. Gradually open the air outlet valve. 6. If applicable, close the bypass valves of the dryer

42 Close the external inlet valve in case the compressor needs to be restarted. The high air speed in the start-up phase of the compressor may damage the desiccant. To prevent this, a sonic nozzle (Please consult Quincy Compressors distributor for the sonic nozzles) can be installed During operation At regular intervals, check the status of the LED s on the control panel. Refer to section Problem solving. Stopping To stop the dryer, proceed as follows: 1. If installed and if necessary, open the bypass valves of the dryer so that the application will still receive compressed air. 2. Close the external inlet valve between the compressor and the dryer and the external outlet valve between the dryer and the dry air consumer. 3. Let the dryer operate for a period without consumption, to depressurize the vessels. 4. Switch off the dryer by putting main switch S1 to position 0. If the dryer is stopped for a longer period, keep the external inlet and outlet valve closed to avoid moisture from entering the dryer. Under no circumstances must compressed air be allowed to flow through the dryer when the electrical power is switched off. This will result in terminal failure of the desiccant material, causing regeneration will no longer be possible

43 7 Maintenance 7.1 Maintenance General recommendations and precautions The dryer does not need any specific maintenance. Nevertheless, before carrying out any maintenance or corrective activity read the following recommendations and safety precautions and act accordingly: Switch off the dryer by putting main switch S1 to position 0. Disconnect all pressure sources and vent the internal pressure of the system before dismantling any pressurized component. Use genuine Quincy Compressors spare parts only. Consult the Spare Parts List for part numbers. For preventive maintenance, dedicated Service kits are available. Check for correct operation after maintenance Filters and valves installed between the compressor, the dryer and the air consumer may need other maintenance activities than those mentioned below (e.g. draining the filters and replacing the filter elements). Refer to the appropriate manual for more information. Preventive maintenance schedule Frequency Service plan Activity Daily Every 6 months or every 4000 hours of operation (1) Every year or every 8000 hours of operation (1) A B Check the display panel for information and service messages. Check for damaged wiring or loose connections. Check for air leaks. Replace the in- and outlet filter cartridges. Replace the silencers. Clean or replace the silencer If a PDP sensor is installed, replace its filter cartridge and have sensor re-calibrated. Measure the dewpoint Have the condition of the desiccant checked Inspect the seats of check valve; replace it if necessary

44 Frequency Service plan Activity Every 3 years or C Service plan C every Replace desiccant hours (1) Revision of inlet valves and actuator Replace the check valves Always replace all o-rings, seals and nylon washers that come free when executing the scheduled maintenance. (1) Whichever comes first In normal working conditions, the lifetime of the desiccant is approximately three years. It is recommended to have the desiccant replaced by a qualified Quincy Compressors service technician. After each 8000 hours service interval, the timer card needs to be reset with a magnetic key, see section Resetting the service counter or the instruction, delivered with the service kits. Reset the service timer after a maintenance intervention. See section Resetting the service counter. All spare parts required for scheduled maintenance are included in specific service kits. Consult the spare parts list for part number information. 7.2 Resetting the service counter Timer card resetting procedure To reset the timer card, continue as follows:

45 Close off the dryer as describe in the stopping procedure, see section Operating instructions. Switch off the dryer by putting switch to Off position. LED (2) (dryer operating) will extinguish. Perform the service plan as scheduled. If the service warning LED (9) is already alight, go directly to the next step. If maintenance is being carried out before the service alarm appears (every 8000 hours), the reset procedure needs to be activated before the service counter can be reset to 0. This can be done by placing the service magnet during 3 seconds over the indicated area (A) of the control panel, in the middle of the left tower. As an indication that the reset procedure is activated, the service warning LED (9) will light up. Reset the timer card by putting the service magnet over the indicated area (A) of the control panel during 5 s. The service alarm LED extinguishes. The service counter has now been reset to 0. Also the counter to switch towers will be reset to 0 (only visible in case of timer control). Restart the dryer by switching switch to On. The service counter will restart, the dryer operating LED (2) is alight, and the drying and regeneration LED s indicate the status of the dryer operating cycle. The timer card is now reset and normal operation continues. The service counter has been reset to 0 and will appear again after 8000 hours 7.3 Disposal of used material Used filters or any other used material (e.g. desiccant, lubricants, cleaning rags, machine parts, etc.) must be disposed of in an environmentally friendly and safe manner, and in line with the local recommendations and environmental legislation

46 8 AIRLOGIC2 Graphic controller 8.1 AIRLOGIC2 Graphic controller Control panel General description The AIRLOGIC2 controller automatically controls and protects the dryer, i.e.: keeping the pressure dew-point stable monitoring pressures, temperatures and digital switches to ensure safe operation, and stopping the dryer whenever necessary restarting the dryer when required In order to control the dryer and to read and modify programmable parameters, the controller has a control panel provided with: LEDs indicating the status of the dryer a display indicating the operating conditions or a fault keys to control the dryer and to access the data collected by the controller buttons to manually start and stop the dryer Automatic restart after voltage failure The controller has a built-in function to automatically restart the dryer if the voltage is restored after voltage failure. For dryers leaving the factory, this function is not activated. If desired, the function can be activated. Consult the Quincy Compressors Customer Care

47 Provided the controller was in the automatic operation mode, the dryer will automatically restart if the supply voltage to the module is restored within a programmed time period. The power recovery time (the period within which the voltage must be restored to have an automatic restart) can be set between 15 and 3600 seconds or to Infinite. If the power recovery time is set to Infinite, the dryer will always restart after a voltage failure, no matter how long it takes to restore the voltage. A restart delay can also be programmed, allowing for example the dryer and the compressors to be restarted one after the other. 8.2 Control Panel Advanced controller Parts and functions Reference Designation Function 1 Display Shows the dryer operating condition and a number of icons to navigate through the 2 Pictograph Automatic operation 3 Pictograph General alarm 4 General alarm LED Flashes if a shut-down warning condition 5 Pictograph Service 6 Service LED Lights up if service is needed

48 Reference Designation Function 7 Automatic operation LED Indicates that the controller is automatically controlling the dryer. 8 Voltage on LED Indicates that the voltage is switched on. 9 Pictograph Voltage on 10 Enter key Key to activate the selected menu or to modify the selected parameter. 11 Escape key To go to previous screen or to end the current action 12 Scroll keys Keys to scroll through the menu. 13 Stop button Button to stop the dryer. LED (7) goes out. 14 Start button Button to start the dryer. LED (7) lights up indicating that the Advanced 8.3 Icons used Animation Animation Description Idle Relief tower B

49 Animation Description Purge heating tower B Purging tower B Equalize tower B Standby tower B Relief tower A Purge heating tower A

50 Animation Description Purging tower A Equalize tower A Standby tower A Split Flow Cooling Shifting: Activate tower A Shifting: Activate tower B Isolate tower A Isolate tower B

51 Status icons Name Icon Description Stopped / Running When the dryer is stopped, the icon stands still. When the dryer is running, the icon is rotating. Machine control mode Local start / stop Remote start / stop Network control Automatic restart after voltage failure Automatic restart after voltage failure is active Week timer Week timer is active Shutdown Warning Service Service required Input icons Icon Description Pressure

52 Temperature Digital input Special protection System icons Icon Description Dryer Drain Filter Failure expansion module Network problem General alarm Menu icons Icon Description Inputs Outputs

53 Alarms (Warnings, shutdowns) Counters Icon Description Test Settings Service Event history (saved data) Access key / User password Network Setpoint Info Navigation arrows Icon Description Up Down

54 8.4 Main screen Control panel (1) Scroll keys (2) Enter key (3) Escape key Function The Main screen shows the status of the dryer operation and is the gateway to all functions implemented in the controller. The Main screen is shown automatically when the voltage is switched on and one of the keys is pushed. It is switched off automatically after a few minutes when no keys are pushed Text on figures

55 (1) Pressure equalization (2) Menu Section A shows information regarding the dryer operation (e.g. the Pressure in vessels A and B, the Dryer Pressure Dewpoint, the Dryer Inlet temperature). Section B shows Status icons. Following icon types are shown in this field: Fixed icons These icons are always shown in the main screen (e.g. Dryer stopped or running, Dryer status). Optional icons These icons are only shown if their corresponding function is activated (e.g. week timer, automatic restart after voltage failure, etc.) Pop up icons These icons pop up if an abnormal condition occurs (warnings, shutdowns, service,...) To call up more information about the icons shown, select the icon using the scroll keys and press the enter key. Section C is called the Status bar This bar shows the text that corresponds to the selected icon. When the menu button is selected, this text shows the operational state of the dryer. Section D shows the Action buttons. These buttons are used: to call-up or program settings to reset a service message to have access to all data collected by the controller The function of the buttons depends on the displayed menu. The most common functions are: Designation Menu Modify Reset Function To go to the menu To modify programmable settings To reset a timer or message To activate an action button, highlight the button by using the Scroll keys and press the Enter key. To go back to the previous menu, press the Escape key

56 8.5 Calling up menus Control panel Control panel (1) Scroll keys (2) Enter key (3) Escape key Description When the voltage is switched on, the main screen is shown automatically (see section Main screen):

57 To go to the Menu screen, highlight the Menu button (2), using the Scroll keys. Press the Enter key to select the menu. Following screen appears The screen shows a number of icons. Each icon indicates a menu item. By default, the Inputs icon is selected. The status bar shows the name of the menu that corresponds with the selected icon. Use the Scroll keys to select an icon. Press the Enter key (2) to open the menu or press the Escape key (3) to return to the Main screen. 8.6 Inputs menu Control panel

58 (1) Scroll keys (2) Enter key (3) Escape key Menu icon, Inputs Function To call up information regarding the actually measured data and the status of some inputs such as the Vessel Pressure. Procedure Starting from the main screen (see Main screen), Move the cursor to the action button Menu and press the Enter key. Following screen appears: Press the Enter key. A screen similar to the one below appears:

59 Text on figure (1) Inputs (2) Pressure vessel A (3) Pressure vessel B (4) Blower pressure (see note*) (5) Inlet dryer *: only applicable to PE/PB dryers (not applicable to QHD dryers) The screen shows the first items of a list of all inputs with their corresponding icons and readings. Use the scroll button to see the other items in the list. If an input is in warning or shutdown, the original icon is replaced by the warning or shutdown icon respectively

60 8.7 Outputs menu Control panel (1) Scroll keys (2) Enter key (3) Escape key Menu icon, Outputs Function To call up information regarding the actual status of some outputs such as the Dryer motor, PDP alarm, General shut-down, etc. Procedure Starting from the Main screen (see Main screen), Move the cursor to the action button Menu and press the Enter key. Following screen appears:

61 Move the cursor to the Outputs icon using the Scroll keys. Press the Enter key. A screen similar to the one below appears: (1) Outputs (2) Dryer motor (means the dryer is operating) (3) PDP alarm (4) General shut-down (5) General warning (6) Yes (7) Not triggered (8) Triggered The screen shows the first items of a list of all outputs with their corresponding icons and readings. Use the scroll button to see the other items in the list

62 8.8 Counters Control panel (1) Scroll keys (2) Enter key (3) Escape key Menu icon, Counters Function To call up: The running hours The number of dryer starts The number of hours that the controller has been powered The operational state timers Procedure Starting from the Main screen (see Main screen),

63 Move the cursor to the action button Menu and press the Enter key. Following screen appears: Using the Scroll keys, move the cursor to the Counters icon (see above, section Menu icon) Press the Enter key. Following screen appears: Text on figure (1) Counters (2) Running hours dryer (3) Loaded hours dryer (4) Actual state time (5) Programmed state time (6) Reset The screen shows a list of all counters with their actual readings. A number of counters keep track of the state of the dryer: Running hours: counts the operation hours of the dryer

64 Loaded hours: the same as running hours, but shows to which time interval the energy counters refer to; this counter is also reset when the energy counters are reset. Actual state time: shows how long the dryer s current state has been active. Programmed state time: shows how long (at most) the current state should be active. Actual half cycle time: shows how long the adsorbing vessel has been adsorbing (since last vessel shift). Programmed half cycle time: shows how long the half cycle should take; minimum value if PDP control is not active, maximum value if PDP is active. Regeneration cycles vessel A: integer that counts how many cycles vessel A has performed. Regeneration cycles vessel B: integer that counts how many cycles vessel B has performed. Standby time: shows how long the dryer has been in standby mode since the last reset of the energy counters. This counter will not be reset when the standby state has ended and a vessel switch is performed. The next time the dryer is in the standby state, it resumes at the previous value. The counter is automatically reset when the energy counters are reset. Energy saving PDP sensor: shows how much energy is saved (in %) by having the PDP sensor since the energy counters have been reset, so it equals StandbyTime/LoadedTime. Module hours: shows how long the Advanced graphic controller has been active. This timer cannot be reset, not even when downloading new software. 8.9 Event history menu Control panel

65 (1) Scroll keys (2) Enter key (3) Escape key Menu icon, Event History Function To call up the last shut-down and last emergency stop data. Procedure Starting from the Main screen (see Main screen), Move the cursor to the action button Menu and press the Enter key. Following screen appears: Using the Scroll keys, move the cursor to the Event History icon (see above, section Menu icon). The list of last shut-down and emergency stop cases is shown. Scroll through the items to select the desired shut-down or emergency stop event. Press the Enter key to find the date, time and other data reflecting the status of the dryer when that shut- down or emergency stop occurred

66 8.10 Test menu Control panel Menu icon, Test Function The vessels can only be depressurized when the dryer is stopped (off state). The test procedure will be stopped as soon as another menu is selected on the controller Procedure Starting from the Main screen (see Main screen): Move the cursor to the action button Menu and press the enter key (2); following screen appears:

67 Using the scroll keys (1), move the cursor to the test icon (see above, section Menu icon). Press the enter key (2); following screen appears: Text on figure (1) Test (2) Depressurize vessels A red selection bar is covering the item Depressurize vessels; press the enter key to depressurize the vessels

68 8.11 Service menu Control panel (1) Scroll keys (2) Enter key (3) Escape key Menu icon, Service Function To reset the service plans which are carried out. To check when the next service plans are to be carried out. To find out which service plans were carried out in the past. To modify the programmed service intervals

69 Procedure Starting from the Main screen (see Main screen), Move the cursor to the action button Menu and press the Enter key. Following screen appears: Using the Scroll keys, move the cursor to the Service icon (see above, section Menu icon). Press the Enter key. Following screen appears: Text on figure (1) Service (2) Overview (3) Service plan (4) Next service (5) History

70 Scroll through the items to select the desired item and press the Enter key to see the details as explained below. Overview Text on figure (1) Overview (2) Running Hours (green) (3) Real Time hours (blue) Example for service level (A): The figures at the left are the programmed service intervals. For Service interval A, the programmed number of running hours is 4000 hours (upper row, green) and the programmed number of real time hours is 4380 hours, which corresponds to six months (second row, blue). This means that the controller will launch a service warning when either 4000 running hours or 4380 real hours are reached, whichever comes first. Note that the real time hours counter keeps counting, also when the controller is not powered. The figures within the bars are the number of hours to go till the next service intervention. In the example above, the dryer was just started up, which means it still has 4000 running hours or 4337 hours to go before the next Service intervention. Service plans A number of service operations are grouped (called Level A, Level B, etc...). Each level stands for a number of service actions to be carried out at the time intervals programmed in the Advanced graphic controller. When a service plan interval is reached, a message will appear on the screen

71 After carrying out the service actions related to the indicated levels, the timers must be reset. From the Service menu above, select Service plan (3) and press Enter. Following screen appears: Text on figure (1) Service plan (2) Level (3) Running hours (4) Real time Next Service Text on figure (1) Next service (2) Level (3) Running hours (4) Actual

72 In the example above, the A Service level is programmed at 4000 running hours, of which 8 hours have passed History The History screen shows a list of all service actions done in the past, sorted by date. The date at the top is the most recent service action. To see the details of a completed service action (e.g. Service level, Running hours or Real time hours), use the Scroll keys to select the desired action and press the Enter key Protections menu Control panel Menu icon, Protections Function To call-up the protections. Procedure Starting from the Main screen (see Main screen): Move the cursor to the action button Menu and press the enter key (2)

73 Following screen appears: Using the scroll keys (1), move the cursor to the protections icon (see above, section Menu icon). Press the enter key (2). Following screen appears: The screen shows a list of all shut-down and shut-down warning settings and the actual reading. Active alarms are highlighted in yellow. In case of a shutdown, the protection can be reset after remedying

74 8.13 Week timer menu Control panel (1) Scroll keys (2) Enter key (3) Escape key Menu icon, Week timer Function To program time-based start/stop commands for the dryer. To program time-based change-over commands for the net pressure band. Four different week schemes can be programmed. A week cycle can be programmed; a week cycle is a sequence of 10 weeks. For each week in the cycle, one of the four programmed week schemes can be chosen. Procedure Starting from the Main screen (see Main screen), Move the cursor to the action button Menu and press the Enter key. Use the Scroll buttons to select the Timer icon

75 Press the Enter key on the controller. Following screen appears: (1) Week Timer (2) Week Action Schemes (3) Week Cycle (4) Status (5) Week 1 (6) Remaining Running Time The first item in this list is highlighted in red. Select the item requested and press the Enter key on the controller to modify. Programming week schemes Select Week action schemes and press Enter. A new window opens. The first item in the list is highlighted in red. Press the Enter key on the controller to modify Week Action Scheme

76 (1) Week Action Schemes (2) Week Action Scheme 1 (3) Week Action Scheme 2 (4) Week Action Scheme 3 (5) Week Action Scheme 4 A weekly list is shown. Monday is automatically selected and highlighted in red. Press the Enter key on the controller to set an action for this day. (1) Week Action Scheme 1 (2) Monday (3) Tuesday (4) Wednesday (5) Thursday (6) Friday

77 (7) Saturday (8) Sunday A new window opens. The Modify action button is selected. Press the enter button on the controller to create an action. (1) Monday (2) Modify A new pop-up window opens. Select an action from this list by using the Scroll keys on the controller. When ready press the Enter key to confirm

78 (1) Monday (2) Actions (3) Remove (4) Start (5) Stop (6) Pressure Setpoint 1 (7) Modify A new window opens. The action is now visible in the first day of the week. (1) Monday (2) Start (3) Save (4) Modify To adjust the time, use the Scroll keys on the controller and press the Enter key to confirm

79 (1) Monday (2) Start (3) Save (4) Modify A pop-up window opens. Use the or key of Scroll keys to modify the values of the hours. Use the or Scroll keys to modify the minutes. (1) Monday (2) Time (3) Save (4) Modify

80 Press the Escape key on the controller. The action button Modify is selected. Use the Scroll keys to select the action Save. (1) Monday (2) Start (3) Save (4) Modify A new pop-up window opens. Use the Scroll keys on the controller to select the correct actions. Press the Enter key to confirm. (1) Monday

81 (3) Are you sure? (4) No (5) Yes (6) Save (7) Modify Press the Escape key to leave this window. The action is shown below the day the action is planned. (1) Week Action Scheme (2) Monday - Start (3) Tuesday (4) Wednesday (5) Thursday (6) Friday (7) Saturday (8) Sunday Press the Escape key on the controller to leave this screen. Programming the week cycle A week cycle is a sequence of 10 weeks. For each week in the cycle, one of the four programmed week schemes can be chosen

82 Select Week Cycle from the main Week Timer menu list. (1) Week Timer (2) Week Action Schemes (3) Week Cycle (4) Status (5) Week Timer Inactive (6) Remaining Running Time A list of 10 weeks is shown. (1) Week Cycle (2) Week

83 (3) Week 2 (4) Week 3 (5) Week 4 (6) Modify Press twice the Enter key on the controller to modify the first week. A new window opens. Select the action, example: Week Action Scheme 1 (1) Week Cycle (2) Week 1 (3) Week Action Scheme 1 (4) Week Action Scheme 2 (5) Week Action Scheme 3 (6) Modify Check the status of the Week Timer Use the Escape key on the controller to go back to the main Week Timer menu. Select the status of the Week Timer

84 (1) Week Timer (2) Week Action Schemes (3) Week Cycle (4) Status (5) Week Timer Inactive (6) Remaining Running Time A new window opens. Select Week 1 to set the Week Timer active. 1 is active. (1) Week Timer (2) Week Action Schemes (3) Week Cycle (4) Status

85 (5) Remaining Running Time Press the Escape key on the controller to go to the main Week Timer menu. Select Remaining Running Time from the list and press the Enter key on the controller to Modify. (1) Week Timer (2) Week Action Schemes (3) Week Cycle (4) Status (5) Remaining Running Time This timer is used when the week timer is set and for certain reasons the dryer must

86 (1) Week Timer (2) Week (3) Week Timer Inactive (4) Week 1 Press the Escape key on the controller to leave this window. The status shows that week continue working. The remaining running time, for example 1 hour, can be set in this screen. This timer is prior to the Week Timer action (1) Week Timer (2) Week action schemes (3) Remaining Running Time

87 8.14 Info menu Control panel (1) Scroll keys (2) Enter key (3) Escape key Menu icon, Info Function To show the Quincy Compressors internet address. Procedure Starting from the Main screen (see Main screen) Move the cursor to the action button Menu and press the Enter key. Following screen appears:

88 Using the Scroll keys, move the cursor to the Info icon (see above, section Menu icon). Press the Enter key. The Quincy Compressors internet address appears on the screen Modifying settings Control panel (1) Scroll keys (2) Enter key (3) Escape key

89 Menu icon, Settings Function To display and modify a number of settings (e.g. Time, Date, Date format, Language, units...) Procedure Starting from the Main screen (see Main screen), Move the cursor to the action button Menu and press the Enter key. Following screen appears: Using the Scroll keys, move the cursor to the Settings icon (see above, section menu icon). Press the Enter key. Following screen appears: The screen shows a number of icons:

90 Icon Function Network settings General settings Regulation settings Automatic restart after voltage failure settings Access key User password Move the cursor to the icon of the function to be modified and press the Enter key. Modifying network settings Select the network settings icon as described above and press the Enter button (2). Following screen appears: Text on figure (1) Network

91 (2) Ethernet (3) CAN A red selection bar is covering the first item (Ethernet). Use the t key of the Scroll keys to select the setting to be modified and press the Enter key. Following screen appears: Screen for Ethernet settings Screen for Ethernet CAN settings Press the Enter button; a red selection bar is covering the first item (Ethernet). Using the Scroll keys, move the cursor to the setting to be modified (e.g. Ethernet) and press the Enter button (2). A pop-up screen appears. Use the t or t key to select the required parameter and press the Enter key to confirm. General settings Select the General settings icon as described above and press the Enter button (2). Following screen appears:

92 Text on figure (1) General (2) Language in use (3) Time (4) Date (5) Date format The screen shows the first items of a list of all settings. Use the scroll button the see the other items in the list Press the Enter button (2); a red selection bar is covering the first item (Language in use). Use the key of the Scroll keys to select the setting to be modified and press the Enter key. A pop-up screen appears. Use the or key to select the required parameter and press the Enter key to confirm. Regulation settings Select the Regulation icon as described above and press the Enter button (2). Following screen appears:

93 Text on figure (1) Regulation (2) PDP extended cycle (3) Activated (4) PDP switching temperature (5) PDP alarm offset (6) Heatless backup mode (see note *) (7) Not activated (8) Modify *: only applicable to PE/PB dryers (not applicable to QHD dryers) The screen shows the list of all settings. Press the Enter button (2); a red selection bar is covering the first item (PDP extended cycle). Use the t key of the Scroll keys to select the setting to be modified and press the Enter key. A pop-up screen appears. Use the t or t key to select the required parameter and press the Enter key to confirm. Regulation settings: PDP extended cycle: the cycle is lengthened by putting the vessel in waiting mode (standby) if PDP is low enough after regeneration and cooling. PDP switching temperature: the PDP should not increase to this setting before the vessels are switched when the dryer is in standby mode. PDP alarm offset: the PDP alarm is active when: PDP > PDP_switching_temperature + PDP_alarm_offset. In that way, the alarm threshold can be set independently of the switching threshold. Automatic restart Select the Automatic restart settings icon as described above and press the Enter button (2). Following screen appears:

94 Text on figure (1) Automatic restart (2) Maximum power down time (3) Restart delay (4) Modify The screen shows the list of all settings. Press the Enter button (1); a red selection bar is covering the first item (Automatic restart). Use the key of the Scroll keys to select the setting to be modified and press the Enter key. A pop-up screen appears. Use the or key to select the required parameter and press the Enter key to confirm. Access key Different security levels are programmed in the controller (e.g. user, service technician, etc). This menu item is used to change the security level. Scroll to the correct icon using the scroll key. Press the enter button. Press the enter button again to modify the security level. Press the enter button again, a pop-up menu appears. Use the scroll keys to enter the password of the new security level. Press the enter key to confirm the change

95 User password If the password option is activated, it is impossible for not authorized persons to modify any setting. Using the Scroll keys, move the cursor to the Password icon. Press the Enter key Extra menu Select the Modify button using the Scroll keys and press the Enter key. Next, modify the password as required. Control panel Menu icon, Test Function To call-up the actual readings for the pressure dewpoint, the relative humidity and the LAT setpoint

96 Procedure Starting from the Main screen (see Main screen): Move the cursor to the action button Menu and press the enter key (2). Following screen appears: Using the scroll keys (1), move the cursor to the Extra icon (see above, section Menu icon) Press the enter key (2). A screen showing the actual readings for the pressure dewpoint, the relative humidity and the LAT setpoint appears Web server All Advanced graphic controllers have a built-in web server that allows direct connection to the company network or to a dedicated PC via a local area network (LAN). This allows to consult certain data and settings via a PC instead of via the display of the controller

97 Getting started Make sure you are logged in as administrator. Use the internal network card from your computer or a USB to LAN adapter (see picture below). USB to LAN adaptor Use a UTP cable (CAT 5e) to connect to the controller (see picture below). Configuration of the network card Go to My Network places (1)

98 Click on View Network connections (1). Select the Local Area connection (1), which is connected to the controller. Click with the right button and select properties (1). Use the checkbox Internet Protocol (TCP/IP) (1) (see picture). To avoid conflicts, deselect other properties if they are selected. After selecting TCP/IP, click on the Properties button (2) to change the settings

99 Use the following settings: IP Address Subnetmask Click OK and close network connections Configuration of the web server The internal web server is designed and tested for Microsoft Internet Explorer 6, 7 and 8. Other web browser like Opera, and Firefox do not support this internal web server. When using Opera or Firefox, a redirect page opens. Click on the hyperlink to connect to the download server from Microsoft to download the latest version of Internet Explorer, and install this software. When using internet explorer: Open Internet Explorer and click on Tools - Internet options (2)

100 Click on the Connections tab (1) and then click on the LAN settings button (2) In the Proxy server Group box, click on the Advanced button (1)

101 In the Exceptions Group box, enter the IP address of your controller. Multiple IP addresses can be given but they must be separated with semicolons (;). Example: Suppose that you already added two IP addresses ( and ). Now you add and separate the 3 IP addresses by putting semicolons between them (1) (see picture). Click OK (2) to close the window. Viewing the controller data Open your browser and type the IP address of the controller you want to view in your browser (in this example The interface opens:

102 Navigation and options The banner shows the dryer type and the language selector. In this example, three languages are installed on the controller. On the left side of the interface you can find the navigation menu (see picture below). If a license for ESi is foreseen, the menu contains 3 buttons. dryer: shows all dryer settings. Es: shows the ESi status (if a license is provided). Preferences: allows to change temperature and pressure unit

103 Dryer settings All dryer settings can be hidden or shown. Put a mark for each setting. Only the machine status is fixed and can not be removed from the main screen. Analog inputs (The units of measure can be changed in the preference button from the navigation menu). Counters Counters give an overview of all actual counters from controller and dryer. Info status Machine status is always shown on the web interface. Digital inputs Gives an overview of all Digital inputs and status

104 Digital outputs Shows a list of all digital outputs and their status. Special protections Give an overview of all special protections of the dryer. Service plan Shows all levels of the service plan and status. This screen only shows the running hours. It is also possible to show the actual status of the service interval

105 ES screen controller If an ESi license is provided, the button ES is shown in the navigation menu. At the left all dryers in the ES and at the right the ES status are shown Programmable settings Description The regulation and safety devices are factory-adjusted to obtain optimum performance of the dryer. No adjustments are required

1 Safety precautions General description Installation Operating instructions Maintenance... 30

1 Safety precautions General description Installation Operating instructions Maintenance... 30 2 0 1 2 2 0 0 0 1 6 Table of contents 1 Safety precautions... 4 1.1 HSAFETY ICONSH... 4 1.2 SAFETY PRECAUTIONS, GENERAL... 4 1.3 SAFETY PRECAUTIONS DURING INSTALLATION... 5 1.4 SAFETY PRECAUTIONS DURING

More information

INSTRUCTION AND MAINTENANCE MANUAL. Refrigerant Compressed Air Dryers QED 650, QED 850, QED 1050

INSTRUCTION AND MAINTENANCE MANUAL. Refrigerant Compressed Air Dryers QED 650, QED 850, QED 1050 INSTRUCTION AND MAINTENANCE MANUAL Refrigerant Compressed Air Dryers QED 650, QED 850, QED 1050 READ THIS MANUAL CAREFULLY BEFORE CARRYING OUT ANY OPERATIONS ON THE DRYER. QUINCY QED 650, QED 850, QED

More information

Atlas Copco Refrigerant compressed air dryers

Atlas Copco Refrigerant compressed air dryers Atlas Copco Refrigerant compressed air dryers FXe 1, FXe 2, FXe 3, FXe 4, FXe 5 Instruction book Atlas Copco Refrigerant compressed air dryers FXe 1, FXe 2, FXe 3, FXe 4, FXe 5 From following serial No.

More information

INSTRUCTION BOOK OIL-FREE SCROLL COMPRESSORS SF 8+, SF 11+

INSTRUCTION BOOK OIL-FREE SCROLL COMPRESSORS SF 8+, SF 11+ INSTRUCTION BOOK OIL-FREE SCROLL COMPRESSORS SF 8+, SF 11+ Atlas Copco Oil-free scroll compressors SF 8+, SF 11+ From following serial No. onwards: API 770 000 Instruction book Original instructions COPYRIGHT

More information

Atlas Copco Oil-injected rotary screw compressors

Atlas Copco Oil-injected rotary screw compressors Atlas Copco Oil-injected rotary screw compressors GA 18 VSD+, GA 22 VSD+, GA 26 VSD+, GA 30 VSD+, GA 37 VSD+ Instruction book Atlas Copco Oil-injected rotary screw compressors GA 18 VSD+, GA 22 VSD+,

More information

Atlas Copco Oil-injected rotary screw compressors

Atlas Copco Oil-injected rotary screw compressors Atlas Copco Oil-injected rotary screw compressors GA 15, GA 18, GA 22, GA 26 Instruction book Atlas Copco Oil-injected rotary screw compressors GA 15, GA 18, GA 22, GA 26 From following serial No. onwards:

More information

Atlas Copco Oil-injected rotary screw compressors

Atlas Copco Oil-injected rotary screw compressors Atlas Copco Oil-injected rotary screw compressors GA 30+, GA 37+, GA 37, GA 45+, GA 45 Instruction book Atlas Copco Oil-injected rotary screw compressors GA 30+, GA 37+, GA 37, GA 45+, GA 45 From following

More information

Atlas Copco Oil-injected rotary screw compressors

Atlas Copco Oil-injected rotary screw compressors Atlas Copco Oil-injected rotary screw compressors GX 2 EP, GX 3 EP, GX 4 EP, GX 5 EP, GX 7 EP Instruction book Atlas Copco Oil-injected rotary screw compressors GX 2 EP, GX 3 EP, GX 4 EP, GX 5 EP, GX

More information

Oil-injected rotary screw compressors

Oil-injected rotary screw compressors Oil-injected rotary screw compressors People. Passion. Performance. QRS 10, QRS 15, QRSM 20 Instruction book Chicago Pneumatic Oil-injected rotary screw compressors QRS 10, QRS 15, QRSM 20 From following

More information

Instruction Manual Dry spell HFH INSTALLATION, OPERATION, MAINTENANCE. Regenerative Type Heatless Desiccant Dryer

Instruction Manual Dry spell HFH INSTALLATION, OPERATION, MAINTENANCE. Regenerative Type Heatless Desiccant Dryer Adsorption dryer Instruction Manual Dry spell HFH INSTALLATION, OPERATION, MAINTENANCE Regenerative Type Heatless Desiccant Dryer WE REDEFINE COMPRESSED AIR TREATMENT SYSTEMS 5/232 KNG Pudur road, Somayampalayam

More information

HTD. High Temperature Non-Cycling Refrigerated Compressed Air Dryers. Operation & Maintenance Manual. MODELS HTD 21 thru HTD 100

HTD. High Temperature Non-Cycling Refrigerated Compressed Air Dryers. Operation & Maintenance Manual. MODELS HTD 21 thru HTD 100 HTD High Temperature Non-Cycling Refrigerated Compressed Air Dryers Operation & Maintenance Manual MODELS HTD 21 thru HTD 100 - TABLE OF CONTENTS - 1.0 GENERAL 2 1.1 How to use this manual 1.2 Symbols

More information

NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL

NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL DATE OF PURCHASE: MODEL: SERIAL NO.: Record above information from nameplate. Retain this information for future reference.

More information

HEATLESS REGENERATIVE DRYERS

HEATLESS REGENERATIVE DRYERS HEATLESS REGENERATIVE DRYERS PHL SERIES Pioneer Air Systems Inc. 210, Flatfork Road, Wartburg, TN - 37887 Tel. : (423) 346-6693 Fax : (423) 346-3865, (423) 346-7522 Email : sales@pioneerair.com Internet

More information

MANUAL. Dryspell INSTALLATION OPERATION MAINTENANCE. Regenerative Type Heatless Desiccant Dryer

MANUAL. Dryspell INSTALLATION OPERATION MAINTENANCE. Regenerative Type Heatless Desiccant Dryer MANUAL INSTALLATION OPERATION MAINTENANCE Regenerative Type Heatless Desiccant Dryer Dryspell Contents 1. Introduction 2 1.1 Design 1.2 Relevant Units 1.3 Statement of Conformity 1.4 Description 1.5 Adsorbant

More information

HEATLESS DESICCANT AIR DRYER INSTRUCTION & MAINTENANCE MANUAL

HEATLESS DESICCANT AIR DRYER INSTRUCTION & MAINTENANCE MANUAL HEATLESS DESICCANT AIR DRYER INSTRUCTION & MAINTENANCE MANUAL H-Series & 203 THRU 223 SERIES ARROW PNEUMATICS, INC. REGENERATIVE DRYER DIVISION 2111 WEST 21ST STREET BROADVIEW, IL 60155 708-343-9595 708-343-1907

More information

GENERAL 2004 HVAC SYSTEMS. Manual HVAC System - Sorento SPECIFICATIONS. Fig. 1: Air Conditioner Specifications Courtesy of KIA MOTORS AMERICA, INC.

GENERAL 2004 HVAC SYSTEMS. Manual HVAC System - Sorento SPECIFICATIONS. Fig. 1: Air Conditioner Specifications Courtesy of KIA MOTORS AMERICA, INC. Fig. 2: Blower & Evaporator Unit Specifications 2004 HVAC SYSTEMS Manual HVAC System - Sorento GENERAL SPECIFICATIONS AIR CONDITIONER Fig. 1: Air Conditioner Specifications BLOWER AND EVAPORATOR UNIT HEATER

More information

SECTION AIR COMPRESSORS AND ACCESSORIES

SECTION AIR COMPRESSORS AND ACCESSORIES PART 1 GENERAL 1.01 WORK INCLUDED SECTION 11370 AIR COMPRESSORS AND ACCESSORIES A. This specification includes air compressors with air dryers. B. Furnish, install, start-up, and test air compressors and

More information

Moduflex. Desiccant Air Dryer P3TJA13A1AN - P3TJA13A7AN. USER GUIDE (Original Language) Dry Air System NL DE FR FI SV NO DA EL ES PT IT PL SK CS ET HU

Moduflex. Desiccant Air Dryer P3TJA13A1AN - P3TJA13A7AN. USER GUIDE (Original Language) Dry Air System NL DE FR FI SV NO DA EL ES PT IT PL SK CS ET HU Moduflex Dry Air System Desiccant Air P3TJA13A1AN - P3TJA13A7AN EN USER GUIDE (Original Language) NL DE FR FI SV NO DA EL ES PT IT PL SK CS ET HU LV LT RU SL TR MT CONTENTS 1 Safety Information...2 1.1

More information

Indirect gas-fired air heater

Indirect gas-fired air heater Indirect gas-fired air heater SERIES HD INSTALLATION AND SERVICE MANUAL MANUFACTURED BY : BROTHERS LIMITED WARNING Improper installation, modification, adjustment or maintenance may cause damage, injury

More information

DHW Series INSTRUCTION MANUAL. Pressure Swing Desiccant Compressed Air Dryer Models 7 through 50 scfm

DHW Series INSTRUCTION MANUAL. Pressure Swing Desiccant Compressed Air Dryer Models 7 through 50 scfm INSTRUCTION MANUAL DHW Series Pressure Swing Desiccant Compressed Air Dryer Models 7 through 50 scfm FORM NO.: 3215738 REVISION: 07/2014 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING

More information

Desiccant Dryers. Desiccant Dryers. Heatless Heated Purge Blower Purge Modular

Desiccant Dryers. Desiccant Dryers. Heatless Heated Purge Blower Purge Modular Desiccant Dryers Desiccant Dryers Heatless Heated Purge Blower Purge Modular Desiccant Air Dryers Quincy desiccant air dryers purify compressed air by adsorbing water vapor. Pressure dewpoints of -40 F

More information

GA5 - GA7 Pack and Full-feature GA5 - GA7 - GA10 Standard Pack

GA5 - GA7 Pack and Full-feature GA5 - GA7 - GA10 Standard Pack Instruction book for compressors GA5 - GA7 Pack and Full-feature GA5 - GA7 - GA10 Standard Pack Important This book applies exclusively: 1. To GA5 - GA7 equipped with an electronic regulator as shown on

More information

Fred C. Gilbert Co. 106 Norris Road Bakersfield, Ca fax

Fred C. Gilbert Co. 106 Norris Road Bakersfield, Ca fax A R R O W P N E U M A T I C S Fred C. Gilbert Co. 106 Norris Road Bakersfield, Ca. 93308 661-399-9569 fax 661-393-9654 F I L T E R S R E G U L A T O R S L U B R I C A T O R S A C C E S S O R I E S H E

More information

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY Bousquet Technologies Inc. 2121, Nobel, Ste Julie, Quebec, Canada, J3E1Z9 SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL Oil-Fired air heater for industrial and commercial use. FOR YOUR SAFETY Do not

More information

Laboratory Enclosed Scroll Air Compressor System with Premium NFPA Controls

Laboratory Enclosed Scroll Air Compressor System with Premium NFPA Controls Laboratory Enclosed Scroll Air Compressor System with Premium NFPA Controls Specification General The Powerex Laboratory Scroll Enclosed Air Compressor System is designed to provide clean, dry air for

More information

Operation and Maintenance Manual. Dryer Package. Model Number: Job Number: Date Shipped: Date Started Up: Electrical: 120 V single phase - AC

Operation and Maintenance Manual. Dryer Package. Model Number: Job Number: Date Shipped: Date Started Up: Electrical: 120 V single phase - AC Operation and Maintenance Manual Dryer Package Model Number: Job Number: Date Shipped: Date Started Up: Electrical: 120 V single phase - AC w w w. a m i c o. c o m Introduction For further technical assistance,

More information

* * SF1 - SF2 - SF4 - SF6T - SF8T. Instruction book for Stationary Compressors. Industrial Air Division - B-2610 Wilrijk - Belgium

* * SF1 - SF2 - SF4 - SF6T - SF8T. Instruction book for Stationary Compressors. Industrial Air Division - B-2610 Wilrijk - Belgium Instruction book for Stationary Compressors SF1 - SF2 - SF4 - SF6T - SF8T Registration code Collection: APC SF Tab: 38 Sequence: 990 This instruction book meets the requirements for instructions specified

More information

Instruction book for Air dryers

Instruction book for Air dryers Instruction book for Air dryers FD7, FD16, FD30, FD40, FD60, FD80, FD100, FD120, FD160 and FD210 From following serial numbers onwards: FD7/16: AIQ 108 800 FD30/40/60: AIQ 114 800 FD80: AIQ 105 000 FD100:

More information

DESICCANT AIR DRYERS. BD + CD + CD series

DESICCANT AIR DRYERS. BD + CD + CD series DESICCANT AIR DRYERS BD + CD + CD series AIR TREATMENT, A CRUCIAL INVESTMENT WHY YOU NEED QUALITY AIR Compressed air contains oil, solid particles and water vapors. Together, they form an abrasive, often

More information

Desiccant Air Dryers. ABP Series. Blower Purge Desiccant Air Dryer 70-8,000 scfm

Desiccant Air Dryers. ABP Series. Blower Purge Desiccant Air Dryer 70-8,000 scfm Desiccant Air Dryers ABP Series Blower Purge Desiccant Air Dryer 70-8,000 scfm Since 1994, Aircel has been delivering quality, industry leading compressed air dryers and accessories for production lines

More information

DESICCANT DRYER USER MANUAL

DESICCANT DRYER USER MANUAL DESICCANT DRYER USER MANUAL AHLD Series Heatless Regenerative 70-4,000 scfm WARRANTY NOTICE Failure to follow the instructions and procedures in this manual, or misuse of this equipment, will void its

More information

FINO Kältetrockner. Original FINO

FINO Kältetrockner. Original FINO Original FINO Germany FINO Kältetrockner 9146 Kältetrockner refrigeration dryer sécheur frigorifique secador frigorífico essiccatore a refrigerazione vriesdroger kondenzační sušič tlakového vzduchu Kyltork

More information

Adsorption dryer PDAD. (en) Operating instructions g [ ]

Adsorption dryer PDAD. (en) Operating instructions g [ ] Adsorption dryer PDAD (en) Operating instructions 8068814 1701g [8068816] Original instructions Installation and commissioning are to be carried out only by qualified personnel in accordance with the operating

More information

Refrigerated air dryers

Refrigerated air dryers Refrigerated air dryers OPERATING AND MAINTENANCE MANUAL Original instructions 38178800319 OPERATING AND MAINTENANCE MANUAL - Contents 1 CONTENTS CONTENTS... 1 Chapter 1 IDRY ELECTRONIC CONTROLLER...

More information

EXHAUST PURGE DESICCANT AIR DRYER INSTRUCTION & MAINTENANCE MANUAL MODEL RE-231 THROUGH RE-252

EXHAUST PURGE DESICCANT AIR DRYER INSTRUCTION & MAINTENANCE MANUAL MODEL RE-231 THROUGH RE-252 EXHAUST PURGE DESICCANT AIR DRYER INSTRUCTION & MAINTENANCE MANUAL MODEL RE-231 THROUGH RE-252 ARROW PNEUMATICS, INC. REGENERATIVE DRYER DIVISION 500 NORTH OAKWOOD RD LAKE ZURICH, IL,60047 PHONE # (847)

More information

DESICCANT AIR DRYERS. BD + CD + CD series

DESICCANT AIR DRYERS. BD + CD + CD series DESICCANT AIR DRYERS BD + CD + CD series AIR TREATMENT, A CRUCIAL INVESTMENT WHY YOU NEED QUALITY AIR Compressed air contains oil, solid particles and water vapors. Together, they form an abrasive, often

More information

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas User s Manual TIGER S EYE E-Series Mark V Jockey TIGERFLOW Systems, Inc. 4034 Mint Way Dallas, Texas 75237 214-337-8780 www.tigerflow.com TABLE OF CONTENTS Introduction... 4 Sequence of Operation... 5

More information

Heatless Regenerative Compressed Air Dryers. Compressed Air System Products. Made in America

Heatless Regenerative Compressed Air Dryers. Compressed Air System Products. Made in America Heatless Regenerative Compressed Air Dryers Compressed Air System Products Made in America 22 AIR/TAK Heatless Regenerative Air Dryers Compressed Air System Products That Save Energy & Improve Operations.

More information

Adsorption Air Dryers

Adsorption Air Dryers Adsorption Air Dryers ADS 1 to 215 Clean and dry air. Prevent the risks, enjoy the benefits. AVAILABILITY PARTNERSHIP SERVICEABILITY TECHNOLOGY YOU CAN TRUST RELIABILITY SIMPLICITY AVAILABILITY PARTNERSHIP

More information

P6500W Air Dryer User s Guide

P6500W Air Dryer User s Guide P6500W Air Dryer User s Guide 1. Welcome & Congratulations Congratulations on your purchase of a new PUREGAS P6500W Air Dryer! We here at PUREGAS are very proud of our products and we are committed to

More information

ADSORPTION DRYING: WHY?

ADSORPTION DRYING: WHY? ADSORPTION DRYERDB ADSORPTION DRYING: WHY? Modern industries require compressed air that is increasingly filtered with low dew point and condensate. Today, the equipment is more sophisticated as there

More information

EN Installation and Operation Manual

EN Installation and Operation Manual EN Installation and Operation Manual Heatless Regenerated Dryer DRYPOINT XC Premium Series XCp models 80 to 800 with BEKOTOUCH Controller READ MANUAL FIRST BEFORE INSTALLATION AND OPERATION Contents 1.

More information

CHESNEY S. Bio-Ethanol Installation & User Manual. model: EFB750. Issue 01

CHESNEY S. Bio-Ethanol Installation & User Manual. model: EFB750. Issue 01 CHESNEY S Bio-Ethanol Installation & User Manual model: EFB750 Issue 01 1 2 Thank you for choosing this Chesney s Bio-Ethanol fire. Please read this information guide carefully to be able to safely install,

More information

Heated Desiccant Air Dryer

Heated Desiccant Air Dryer OWNERS MANUAL F-0073 HEATED DESICCANT AIR DRYER Heated Desiccant Air Dryer MODELS RE231-RE250 ARROW PNEUMATICS Table of Contents Unpacking/Application/Analysis 3 Specifications 4 Dimensional Drawings 5-6

More information

INSTRUCTION AND MAINTENANCE MANUAL DRYERS A 11 - A 12 - A 13 - A 14 (R410A)

INSTRUCTION AND MAINTENANCE MANUAL DRYERS A 11 - A 12 - A 13 - A 14 (R410A) Code 007806 0 Edit. 0/04 INSTRUCTION AND MAINTENANCE MANUAL DRYERS A - A - A - A 4 (R40A) READ THIS MANUAL CAREFULLY BEFORE CARRYING OUT ANY OPERATIONS ON THE DRYER. Cod. 007806 0 - Edition 0/04 - CONTENTS

More information

Installation, Operation, and Maintenance Instructions. Heatless Regenerative Air Dryers and HLD-PAK Dryer/Filter Packages HLD-25 through HLD-6250

Installation, Operation, and Maintenance Instructions. Heatless Regenerative Air Dryers and HLD-PAK Dryer/Filter Packages HLD-25 through HLD-6250 107 W. Main Street, Worthington, PA 16262 Phone: 724-297-3416 Fax: 724-297-5189 URL: http://www.airtak.com e-mail: airtak@airtak.com Installation, Operation, and Maintenance Instructions Heatless Regenerative

More information

150-3,000 scfm AEHD Series. Desiccant Air Dryers AEHD Series. Externally Heated Desiccant Air Dryer 150-3,000 scfm. Front Page

150-3,000 scfm AEHD Series. Desiccant Air Dryers AEHD Series. Externally Heated Desiccant Air Dryer 150-3,000 scfm. Front Page 150-3,000 scfm AEHD Series Desiccant Air Dryers AEHD Series Externally Heated Desiccant Air Dryer 150-3,000 scfm Front Page 1 AEHD Series Heated Dryer Externally Heated Desiccant Dryer 150-3,000 scfm Since

More information

Dryer Controller M720

Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 2.00 Software version 2.00 Manual M720 Dryer controller Page 1 of 60 Document history Preliminary version: - Created in April, 2009 Hardware Version 2.00,

More information

INGERSOLLrAND AIR COMPRESSORS CAUTION: HMD SERIES AIR DRYERS MODELS 18 THROUGH 385 OPERATORS/ INSTRUCTION MANUAL REPLACEMENT PARTS

INGERSOLLrAND AIR COMPRESSORS CAUTION: HMD SERIES AIR DRYERS MODELS 18 THROUGH 385 OPERATORS/ INSTRUCTION MANUAL REPLACEMENT PARTS INGERSOLLrAND AIR COMPRESSORS HMD SERIES AIR DRYERS MODELS 18 THROUGH 385 OPERATORS/ INSTRUCTION MANUAL REPLACEMENT PARTS CAUTION: For HMD Models 84 Through 385 ONLY 1. Remove Dryer Chambers And Protective

More information

USER S INFORMATION MANUAL

USER S INFORMATION MANUAL USER S INFORMATION MANUAL HOT WATER HEATING BOILERS DOMESTIC WATER HEATERS 150,000-300,000 Btu/hr MODELS EB-EWU-02 IMPORTANT INSTALLER - AFFIX INSTALLATION MANUAL ADJACENT TO THE BOILER CONSUMER - RETAIN

More information

P4200PM / P5000PM Remote Air Dryer User s Guide

P4200PM / P5000PM Remote Air Dryer User s Guide P4200PM / P5000PM Remote Air Dryer User s Guide 1. Welcome & Congratulations Congratulations on your purchase of a new PUREGAS P4200PM / P5000PM Air Dryer! We here at PUREGAS are very proud of our products

More information

domnick hunter PNEUDRI DME012-RX - DME080-RX USER GUIDE Original Language

domnick hunter PNEUDRI DME012-RX - DME080-RX USER GUIDE Original Language dh domnick hunter PNEUDRI DME012-RX - DME080-RX USER GUIDE Original Language EN Contents 1. Safety Information 4 1.1 Markings and symbols 5 1.2 Hazardous Substances 5 2. Description 6 2.1 Technical Specification

More information

Heatless Regenerative Air Dryers

Heatless Regenerative Air Dryers Heatless Regenerative Air Dryers CPAD Series / CPADM Series Owner s Manual Jan. 2009 DATE OF PURCHASE MODEL SERIAL NO. Record above information from nameplate. Retain this information for future reference.

More information

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE Release January 2001 CONTENTS 1.0 GENERAL CHARACTERISTICS... 4 1.1 MAIN CHARACTERIS TICS... 4 2.0 USER INTERFACE (CODE C5121230)... 5 2.1 DISPLAY... 5 2.2 MEANING OF THE LEDS...

More information

MDX. Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain. Operation & Maintenance Manual MODELS MDX

MDX. Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain. Operation & Maintenance Manual MODELS MDX MDX Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain Operation & Maintenance Manual MODELS MDX 800 1000 1200 TABLE OF CONTENTS HOW TO USE THIS MANUAL 2 SYMBOLS 2 WARRANTY 2 1.0

More information

MDX. Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain Drain Trap. Operation & Maintenance Manual MDX MODELS 18 THRU 250

MDX. Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain Drain Trap. Operation & Maintenance Manual MDX MODELS 18 THRU 250 MDX Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain Drain Trap Operation & Maintenance Manual MDX MODELS 18 THRU 250 TABLE OF CONTENTS HOW TO USE THIS MANUAL 2 SYMBOLS 2 WARRANTY

More information

SECTION air supply system + WARNING: + NOTE: GENERAL DESCRIPTION COMPRESSED AIR RESERVOIRS / 1.

SECTION air supply system + WARNING: + NOTE: GENERAL DESCRIPTION COMPRESSED AIR RESERVOIRS / 1. 08-000.02/ 1 2011JA14 SECTION 08-000.02 GENERAL DESCRIPTION See Figure 1 for a schematic diagram of the. See the Nova LFS parts manual for a detailed schematic of the. The function of the vehicle s is

More information

INSTRUCTION AND MAINTENANCE MANUAL

INSTRUCTION AND MAINTENANCE MANUAL Code 007758 0 Edit. 0/009 INSTRUCTION AND MAINTENANCE MANUAL DRYERS A A A A READ THIS MANUAL CAREFULLY BEFORE CARRYING OUT ANY OPERATIONS ON THE DRYER. Cod. 007758 0 - Edition 0/009 - CONTENTS PART A:

More information

Adsorption Dryers for Compressed Air

Adsorption Dryers for Compressed Air Adsorption Dryers for Compressed Air ADS 1 to 215 Clean and dry air. Prevent the risks, enjoy the benefits. AVAILABILITY PARTNERSHIP SERVICEABILITY TECHNOLOGY YOU CAN TRUST RELIABILITY SIMPLICITY AVAILABILITY

More information

OPERATING MANUAL MODEL AIR 1500TM AIR DRYER

OPERATING MANUAL MODEL AIR 1500TM AIR DRYER OPERATING MANUAL MODEL AIR 500TM AIR DRYER Puregas, LLC 226-A Commerce St. Tel: 800-52-535 Broomfield, Colorado Fax: 303-657-2205 P/N P0255 REV A, 02/9/4 TABLE OF CONTENTS.0 GENERAL... 3 2.0 SPECIFICATIONS...

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

User Manual. Dryer Controller M720

User Manual. Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 1.00 Software version 1.00 Preliminary version Manual M720 Dryer controller Page 1 of 42 Document history Preliminary version: - Created in April, 2009

More information

Polar Air Dryer. Instructions Manual PDRCF PDRCF R E F R I G E R A T E D T Y P E C O M P R E S S E D A I R D R Y E R S

Polar Air Dryer. Instructions Manual PDRCF PDRCF R E F R I G E R A T E D T Y P E C O M P R E S S E D A I R D R Y E R S Polar Air Dryer R E F R I G E R A T E D T Y P E C O M P R E S S E D A I R D R Y E R S PDRCF1150029 PDRCF4602000 Instructions Manual TABLE OF CONTENTS 1. Important safety notes - Please read... 1 1.1. Transportation...

More information

ECLIPSE DESICCANT DRYERS ZHA HEATED PURGE MODELS

ECLIPSE DESICCANT DRYERS ZHA HEATED PURGE MODELS COMPRESSED AIR SOLUTIONS TECHNICAL MANUAL ECLIPSE DESICCANT DRYERS ZHA HEATED PURGE MODELS TABLE OF CONTENTS PAGE 1. INTRODUCTION 1 2. ABBREVIATED WARRANTY 1 3. NOMENCLATURE 2 4. RECEIVING AND INSPECTION

More information

CE Unit is suitable for material transport. The transported gas may be up to 80 C.

CE Unit is suitable for material transport. The transported gas may be up to 80 C. The manual contains: 1 Safety regulations 1.1 Electrical 1.2 Crush risk 1.3 Hazardous dust 1.4 Suction injuries 1.5 Noise 1.6 Pneumatic 1.7 Other equipment 2 Machine Operation 3 Installation Directions

More information

Hydrogen Generator Model HPNM 1. Instruction manual. 166 Keystone Drive Montgomeryville, PA Phone: Fax:

Hydrogen Generator Model HPNM 1. Instruction manual. 166 Keystone Drive Montgomeryville, PA Phone: Fax: Hydrogen Generator Model HPNM 1 Instruction manual 166 Keystone Drive Montgomeryville, PA 18936 Phone: 215-641-2700 Fax: 215-641-2714 Introduction Index INDEX... 2 INTRODUCTION... 3 SCOPE OF THE MANUAL...

More information

MDX. Non-Cycling Refrigerated Compressed Air Dryers with Intellidrain Condensate Drain Trap. Operation & Maintenance Manual

MDX. Non-Cycling Refrigerated Compressed Air Dryers with Intellidrain Condensate Drain Trap. Operation & Maintenance Manual MDX Non-Cycling Refrigerated Compressed Air Dryers with Intellidrain Condensate Drain Trap Operation & Maintenance Manual MODELS MDX 1500 1800 2400 3000 TABLE OF CONTENTS 1.0 GENERAL 2 1.1 How to use this

More information

INSTRUCTION AND MAINTENANCE MANUAL DRYERS A5 - A6 - A7 - A7,5 - A8 - A9 - A10

INSTRUCTION AND MAINTENANCE MANUAL DRYERS A5 - A6 - A7 - A7,5 - A8 - A9 - A10 Code 00773 04 Edit. 03/0 INSTRUCTION AND MAINTENANCE MANUAL DRYERS A5 - A6 - A7 - A7,5 - A8 - A9 - A0 READ THIS MANUAL CAREFULLY BEFORE CARRYING OUT ANY OPERATIONS ON THE DRYER. Cod. 00773 04 - Edition

More information

Page 1 of 18. Part# /5/2013

Page 1 of 18. Part# /5/2013 Part# 1002655-06 8/5/2013 This manual contains important information concerning the installation and operation of the gun washers listed above. Read manual thoroughly and keep for future reference INSTRUCTIONS

More information

(PD[ $LU 'U\HU 5 ( ) 5, * ( 5 $ 7 ( ' 7 < 3 ( & ( 6 6 ( ' $, 5 ' 5 < ( 5 6 ('5&) ದ ('5&) Instructions Manual

(PD[ $LU 'U\HU 5 ( ) 5, * ( 5 $ 7 ( ' 7 < 3 ( & ( 6 6 ( ' $, 5 ' 5 < ( 5 6 ('5&) ದ ('5&) Instructions Manual Instructions Manual 1. Important safety notes - Please read... 1 1.1. Transportation... 1 1.2 Positioning... 1 1.3 Installation... 1 1.4 Before operating... 1 1.5 Maintenance by an engineer... 1 1.6 Maintenance

More information

MODEL MW200 MODEL MW600 AIR DRYER

MODEL MW200 MODEL MW600 AIR DRYER OPERATING MANUAL MODEL MW200 MODEL MW600 AIR DRYER Mail Address: 226A Commerce St. Tel: 303-465-3063 Broomfield, CO 80020 Fax: 303-465-9294 TABLE OF CONTENTS 1.0 GENERAL...3 2.0 SPECIFICATIONS...3 3.0

More information

Trident Breathing Air System

Trident Breathing Air System Trident Breathing Air System INSTALLATION, OPERATION, MAINTENANCE PSA Type Breathing Air Dryer Dealer: This manual MUST be given to the end user. User: BEFORE using this product, read this manual and preserve

More information

Service package PDAD- -SP (en) Assembly instructions d [ ]

Service package PDAD- -SP (en) Assembly instructions d [ ] Service package PDAD- -SP-12000 (en) Assembly instructions 8068819 1701d [8068821] Original instructions Installation and commissioning are to be carried out only by qualified personnel in accordance with

More information

Installer Manual KNX Touchscreen Thermostat

Installer Manual KNX Touchscreen Thermostat Installer Manual 02952 KNX Touchscreen Thermostat Index GENERAL FEATURES AND FUNCTIONALITY from page 5 ETS PARAMETERS AND COMMUNICATION OBJECTS from page 7 COMMUNICATION OBJECTS GENERAL FEATURES AND FUNCTIONALITY

More information

347002K/177002K/34900

347002K/177002K/34900 Service Manual Models: 347002K/177002K 34900/347012K Manifold Block Style Recovery/Recycling/Recharging Unit For R-12 or R-134a Only TABLE OF CONTENTS: Theory of Operation and Safety Precautions... 2 Depressurizing

More information

P4200W2 Series Air Dryer

P4200W2 Series Air Dryer P4200W2 Series Air Dryer User s Guide Models covered: P4200W2 P4200W2LP P4202W2 P4202W2LP P4202W2H 1. Welcome & Congratulations Congratulations on your purchase of a new PUREGAS P4200W2 Series Air Dryer!

More information

Rust, corrosion and leakages threaten even the best network. Only Quality Air Solutions. in optimal shape. air distribution

Rust, corrosion and leakages threaten even the best network. Only Quality Air Solutions. in optimal shape. air distribution Rust, corrosion and leakages threaten even the best distribution network Only Quality Air Solutions keep your air distribution in optimal shape Improve your business productivity, Why? Customer benefits

More information

CPF PRODUCT DESCRIPTION

CPF PRODUCT DESCRIPTION CPF 175 340 PRODUCT DESCRIPTION The CHICAGO PNEUMATIC CPF 175-340 compressor is a quiet, complete and ready-for-use unit for the production of compressed air in industrial applications. OVERVIEW The CHICAGO

More information

P550W Series Air Dryers

P550W Series Air Dryers P550W Series Air Dryers User s Guide Models covered: P550W P550WH P550WLP P552W P552WH P552WLP 1. Welcome & Congratulations Congratulations on your purchase of a new PUREGAS P550W Series Air Dryer! We

More information

Adsorption Dryers. AD 7 to 1300

Adsorption Dryers. AD 7 to 1300 D dsorption Dryers D 7 to 300 LUP Driven by technology. Designed by experience. lup Kompressoren has over 85 years of industrial experience. It is our ambition to offer compressed air solutions that ensure

More information

ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL

ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER 2001829 OPERATIONS AND MAINTENANCE MANUAL Prepared by: 860 Douglas Way PO Box 530 Natural Bridge Station, VA 24579 1.0 SCOPE: This Operations and Maintenance

More information

Instruction Manual EN CP COMPRESSOR. Model CPD CPD 75

Instruction Manual EN CP COMPRESSOR. Model CPD CPD 75 Instruction Manual EN CP COMPRESSOR Model CPD 75-00 62 305 8 65 CPD 75 TECHNICAL DATA STANDARD MACHINES CPD MODEL 75 00 Nominal pressure at full flow PSI 00 25 50 75 00 25 50 75 Actual flow * (as per ISO

More information

Laboratory Open Scroll Air Compressor System with Premium NFPA Controls

Laboratory Open Scroll Air Compressor System with Premium NFPA Controls Laboratory Open Scroll Air Compressor System with Premium NFPA Controls Specification General The Powerex Laboratory Open Scroll Air Compressor System is designed to provide clean, dry air for applications

More information

WILKERSON MODELS DE3, DE4 AND DE5 COMPACT HEATLESS AIR DRYERS

WILKERSON MODELS DE3, DE4 AND DE5 COMPACT HEATLESS AIR DRYERS INSTRUCTION MANUAL FOR WILKERSON MODELS DE3, DE4 AND DE5 COMPACT HEATLESS AIR DRYERS DE3 - DE5 OPERATIONS GENERAL This instruction manual covers the installation, operation, maintenance and troubleshooting

More information

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER 2001927 Prepared by: 860 Douglas Way PO Box 530 Natural Bridge Station, VA 24579 1 1.0 SCOPE: This

More information

LABORATORY ULTRA ZERO AIR GENERATOR. ZAC-ULT Series USER MANUAL

LABORATORY ULTRA ZERO AIR GENERATOR. ZAC-ULT Series USER MANUAL LABORATORY ULTRA ZERO AIR GENERATOR ZAC-ULT Series USER MANUAL 166 Keystone Drive Montgomeryville, PA 18936 Telephone: 215-641-2700 Fax: 215-641-2714 Email: mtgmmville@matheson-trigas.com INT-0261-XX rev

More information

Tempered Water Logic Control OPERATION l TROUBLE SHOOTING

Tempered Water Logic Control OPERATION l TROUBLE SHOOTING Tempered Water Logic Control OPERATION l TROUBLE SHOOTING English For MPE Multiple Chiller Units Control Panel TEMPERED WATER SYSTEMS L-2199 Rev. 20080223 Revision: L-2199 20101104 *** IMPORTANT NOTICE

More information

SERIES HC Heat-of-Compression Compressed Air Dryer

SERIES HC Heat-of-Compression Compressed Air Dryer SERIES HC Heat-of-Compression Compressed Air Dryer Models HC-3 HC-239 Information When making inquiries, please provide the following information: 1) Equipment Model Number 2) Equipment Serial Number 3)

More information

ultra-high purity compressed air dryers flow capacity: scfm ( Nm 3 /hr)

ultra-high purity compressed air dryers flow capacity: scfm ( Nm 3 /hr) snowstorm filled ultra-high purity compressed air dryers flow capacity: 3-1110 scfm (5-1900 Nm 3 /hr) D 1 2 3 ultra-high purity compressed air dryers flow capacity: 3-1110 scfm (5-1900 Nm 3 /hr) D 1 2

More information

ENGLISH (Original instructions) INSTRUCTION MANUAL. Power Mixer UT2204 DOUBLE INSULATION. IMPORTANT: Read Before Using.

ENGLISH (Original instructions) INSTRUCTION MANUAL. Power Mixer UT2204 DOUBLE INSULATION. IMPORTANT: Read Before Using. ENGLISH (Original instructions) INSTRUCTION MANUAL Power Mixer UT04 0078 DOUBLE INSULATION IMPORTANT: Read Before Using. ENGLISH (Original instructions) SPECIFICATIONS Model UT04 No load speed (min - )

More information

1998 Expedition/Navigator Workshop Manual

1998 Expedition/Navigator Workshop Manual Page 1 of 8 SECTION 412-00: Climate Control System - General Information 1998 Expedition/Navigator Workshop Manual DESCRIPTION AND OPERATION Procedure revision date: 02/11/2000 Climate Control System WARNING:

More information

AirCel. Heated Regenerative Desiccant Dryers. AEHD Externally Heated, HRE Blower Purge, and HRS-L Zero Purge Series

AirCel. Heated Regenerative Desiccant Dryers. AEHD Externally Heated, HRE Blower Purge, and HRS-L Zero Purge Series AirCel Heated Regenerative Desiccant Dryers AEHD Externally Heated, HRE Blower Purge, and HRS-L Zero Purge Series ié~çáåö=íüé=t~ó=áå=^áê=mìêáñáå~íáçå As one of the world s leading manufacturers of compressed

More information

CPVS PRODUCT DESCRIPTION

CPVS PRODUCT DESCRIPTION CPVS 20 30 PRODUCT DESCRIPTION The CHICAGO PNEUMATIC CPVS 20-30 compressor is a quiet, complete and ready-for-use unit for the production of compressed air for light and medium industrial applications.

More information

AIR COMPRESSOR TC UTC TC UTC125502

AIR COMPRESSOR TC UTC TC UTC125502 AIR COMPRESSOR TC120242 UTC120242 TC125502 UTC125502 Warning! When using compressors, basic safety precautions should always be followed to reduce the risk of fire, electric shock and personal injury.

More information

SIEMENS SIMATIC HMI TOUCH SCREEN BLOWER PURGE DESICCANT AIR DRYER HMI USER MANUAL V4

SIEMENS SIMATIC HMI TOUCH SCREEN BLOWER PURGE DESICCANT AIR DRYER HMI USER MANUAL V4 SIEMENS SIMATIC HMI TOUCH SCREEN BLOWER PURGE DESICCANT AIR DRYER HMI USER MANUAL V4 1- ELECTRICAL CONTROL PANEL OF THE DRYER Picture 1 2- FIRST START OF THE DRYER Picture 2 At the first start of the dryer

More information

CPX MEDICAL AIR PLANT INSTALLATION, OPERATIONS & MAINTENANCE MANUAL

CPX MEDICAL AIR PLANT INSTALLATION, OPERATIONS & MAINTENANCE MANUAL CPX MEDICAL AIR PLANT INSTALLATION, OPERATIONS & MAINTENANCE MANUAL Company Registered Office: Crown House, Stockport, Cheshire, SK13RB No. 850 Registered in England and Wales No. 05058855 VAT VERSION

More information

Digital Refrigerant System Analyzer. MAXMIN Psi kpa Bar MPa C F R TIME P T UNITS

Digital Refrigerant System Analyzer. MAXMIN Psi kpa Bar MPa C F R TIME P T UNITS Digital Refrigerant System Analyzer INSTRUCTION MANUAL ENGLISH LOW START PRS T-LOW SUPERHEAT MAXMIN kpa Bar MPa R TIME P T HIGH END PRS T-HIGH SUBCOOL VAC 1-800-547-5740 Fax: (503) 643-6322 www.ueitest.com

More information

Climate Control System

Climate Control System Page 1 of 13 SECTION 412-00: Climate Control System General Information DESCRIPTION AND OPERATION 1998 Mark VIII Workshop Manual Climate Control System Cautions and Warnings WARNING: To avoid accidental

More information

DESICCANT DRYER USER MANUAL

DESICCANT DRYER USER MANUAL DESICCANT DRYER USER MANUAL ABP Series Blower Purge 800-10,000 scfm WARRANTY NOTICE Failure to follow the instructions and procedures in this manual, or misuse of this equipment, will void its warranty.

More information

HEATLESS REGENERATIVE COMPRESSED AIR DRYER models THL-200 through THL- 5000

HEATLESS REGENERATIVE COMPRESSED AIR DRYER models THL-200 through THL- 5000 P.O Box 879 50 W. 6th Ave. - unit P Broomfield, CO 8008 Phone:0-65-06 Order Entry Fax: 0-65-99 www.airdryers.com INSTALLATION, OPERATION & MAINTENANCE MANUAL FOR HEATLESS REGENERATIVE COMPRESSED AIR DRYER

More information