www. ElectricalPartManuals. com INSTRUCTIONS DRY TYPE TRANSFORMERS OPERATION AND MAINTENANCE OF

Size: px
Start display at page:

Download "www. ElectricalPartManuals. com INSTRUCTIONS DRY TYPE TRANSFORMERS OPERATION AND MAINTENANCE OF"

Transcription

1 I.L INSTRUCTIONS FIG. L Section of Three-Phase ASL Pcwer Center with Class B Insulation. OPERATION Tap Connections. In type ASL dry type trans formers changes in voltages are made by the changing of connector links on "stub taps", (see Fig. 2) which are brought out on the face of the coil. OPERATION AND MAINTENANCE OF DRY TYPE TRANSFORMERS The panel that must be removed, by removing all screws in that panel, is indicated by a nameplate located directly below the transformer's Instruction Plate. Type AVR transformers have the tap leads brought to a terminal board, (see Fig. 3) where connector links are used to connect the proper studs to obtain the desired voltage. The panel tha is to be removed will be indicated by a nameplate NEW INFORMATION Before changes are made the Instruction Plate should be consulted for the proper terminals to be connected to give the desired voltage. When tap connections are made the same numbered studs must be always connected in all phases. Caution: Transformer case panels should never be removed while transformer is energized. Effect of Humidity. As long as the transformer is energized, humidity conditions are unimportant. In the event that a dry type transformer is de-energized and allowed to cool to ambient temperature, consideration must be given to the possible effects of humidity. If the shutdown period occurs during low humidity conditions, no special precaution should be required before energizing the unit. Should a shutdown exceeding 12 hours occur during a period of high humidity, particularly if atmospheric conditions are such as to cause condensation within the housing, then precautions should be taken. Small strip heaters may be placed in the bottom of the unit shortly after shutdown to FIG. 2. Type ASL Transformer Stub Taps. JANUARY, 1952

2 DRY TYPE TRANSFORMERS -- DRY TYPE TRANSFORMERS --- The transformer should be located to allow free circulation of air through the coils from the bottom to the top of the case. One winding should be short circuited, and sufficient voltage at normal frequency should be applied to the other winding to circulate approximately normal current. The impedance of the transformer will normally be found on the Instruction Plate. If for any reason the impedance is not known it should be obtained from the Westinghouse Electric Corporation, Sharon, Pennsylvania. When inquiring, complete transformer data as given on the Instruction Plate should be included. It is recommended that the winding temperature not be allowed to exceed 100 C., as measured by resistance or by thermometers placed in the ducts between the windings. The thermometers used should be of the spirit type because mercury thermometers give erroneous readings due to the generation of heat in the mercury as a result of induced eddy currents. The end terminals of the windings (and not the taps) must be used in order to circulate current through the entire winding. Proper precautions should be taken to protect the operator from dangerous voltages. 3. Drying by External and Internal He t This is a combination of the two methods previously described, and is by far the quickest method. The transformer core and coil assembly should be placed in a non-flammable box, or kept in its own case if suitable, and external heat applied as described in the first method, and cwrent circulated through the windings as described in the second method. The current required will' be considerably less than when no external heating is used but should be sufficient to produce the desired temperature of the windings. It is recommended that the temperatures attained not exceed those stated in the foregoing. 4. Use of Insulation Resistance for Determining Drying Time. Drying time depends on the condition of the transformer, size, voltage, amount of moisture absorbed, and the method of drying used. The measurement of insulation resistance is of value in determining the status of drying. Measurements should be taken before starting the drying process and at two hour intervals during drying. The initial value, if taken at ordinary temperatures, may be high even though the insulation may not be dry. Because insulation resistance varies inversely with temperature, the transformer temperature should be kept approximately constant during the drying period to obtain comparative readings. As the transformer is heated, the presence of moisture will be evident by the rapid drop in resistance measurement. Following this period the insulation resistance will generally increase gradually until near the end of the drying period when it will increase more rapidly. Sometimes it will rise and fall through a short range before steadying because moisture in the interior of the insulation is working out through the initially dried portions. abscissa and resistance A curve with time as as ordinate should be plotted and the run should be continued until the resistance levels off and remains constant for from three to four hours. Insulation resistance measurements should be taken for each winding to ground with all windings grounded except the one being tested. Before taking insulation resistance measurements the current should be interrupted and the winding should be short circuited and grounded for at least one minute to drain off any static charge. All readings should be for the same time of application of the test voltage, preferably one minute. Caution: Constant attendance during the drying process is desirable. 9 WESTINGHOUSE ELECTRIC CORPORATION SHARON PLANT TRANSFORMER DIVISION SHARON, PA. (Rep, 6-58) Printed in U.S.A.

3 - FIG. l. I.L B INSTRUCTIONS Type ASL Distribution Transformer DESCRIPTION THE MODERN DRY TYPE TRANSFORM ER has been developed to supply the need for a safe transformer for indoor applications. DRY TYPE TRANSFORMERS It is designed to be essentially fireproof and explosion proof for economical installations without vaults near its load center. Explosion and fire, the hazards of liquid filled transformers, are greatly reduced in air cooled transformers because they are constructed with A.S.A. Class B and Class H materials and utilize the surrounding air for their cooling medium. Metal cases with suitable covered openings are used to encase air cooled transformers. The open ings, which are necessary for the free circulation SUPERSEDES I.L A of air within the transformer, are not weather tight and so limit these transformers to indoor installations. Dry type transformers are manufactured in two types, the "DT-3" and the ASL. The type "DT-3" consists of the smaller ratings and the type ASL the larger ratings. The normal kva limit of self-cooled dry type transformers is 5000 kva single-phase and 7500 kva three-phase. It is possible to increase these limits by the addition of air blast equipment (which must be provided for at the time of design} or by the paralleling or banking of two or more units mounted in a common case. The maximum voltage for which air cooled transformers are built is volts. Dry type transformers are supplied with provision for grounding the case and an instruction FIG. 2. Type DT -3 Power Center TraiU.Iformer OCTOBER, 1960

4 DRY TYPE TRANSFORMERS --- FIG. 3. Type ASL Power Transformer Crated for Export Shipment plate which gives the electrical connections and details of the transformer. Other accessories are supplied in accordance with the specific transformer and customer requirements. High and low voltage leads may be brought out of the case by several different methods. The most common are: porcelain bushings (see the Instruction Leaflet "Dry Type Transformer Bushings")1 terminal chambers with potheads or conduit connections1 and direct connection to switchgear/ switches or bus work. SHIPMENT Except for lightning arresters and LCB switches1 air cooled transformers are usually shipped ready for installation complete with bushings and accessories in place and connected for operation. They are completely covered with a weatherproof covering which should not be removed until the transformer is ready to be moved indoors and then1 only when there is no danger of exposing the transformer to dampness. Shipping braces and shims under the transformer feet with their respective bolts when provided should be removed after installation. The outline drawing will show which braces are to be removed. FIG. 4. Type ASL Power Center Transformer Loaded on a flat Car for Domestic Shipment For foreign shipment air cooled transformers are completely covered with a weather tight wrapping and crated with a sturdy wooden box and securely braced to take the extra handling and movement to which they are subjected while in transit. Aside from the crating, all details are the same as for domestic shipment. UNPACKING It is only necessary to remove the weather proof covering to completely unpack an air cooled transformer, however precautions to keep the transformer dry as outlined above must be followed. Occasionally bushings or other accessories are shipped separately. If this is done1 care must be taken when unpacking as items such as bushings are quite fragile. SERVICE Further information/ or renewal parts1 may be obtained by contacting the nearest Westinghouse office. The facilities of the Engineering and Service Departments may be obtained through the nearest Westinghouse office. WESTINGHOUSE ELECTRIC CORPORATION SHARON PLANT TRANSFORMER DIVISION SHARON, PA. Printed In U.S.A.

5 RECEIVING I. L INSTRUCTIONS New transformers should be inspected when received for damage during shipment. RECEIVING AND INSTALLATION OF DRY TYPE TRANSFORMERS Examination should be made before removing from cars or trucks and if any injury is evident or any indication of rough handling is visible, a claim should be filed with the carrier at once and the manufacturer should be notified. After the transformer has been placed indoors, the panels should be removed and an internal inspection made for injury or displacement of parts, loose or broken connections, cracked porcelain, dirt or foreign material and for the presence of free water or moisture. Any damaged condition should be reported at once to the nearest Westinghouse Office. If w:ater or moisture is evident see the Instruction Leaflet "Operation and Maintenance of Dry Type Transformers" for methods of testing for moisture and methods of drying out. HANDLING Lifting holes are provided on each side of the case for the insertion of hooks to lift the complete transformer. These holes should be closed with the steel cover provided, so as to prevent the entrance of foreign materials. For power centers and unit substations, eye nuts are provided for lifting the complete unit. After installation, these may be removed and the openings covered with cap provided. The base of these transformers is constructed so that the transformer can be moved on rollers in any horizontal direction. Under no circumstances should the transformer be moved with ropes or cables placed around the case. suitably designed for jacking. The transformer case is Jacks should be placed as indicated on the outline drawing. STORING Dry type transformers should be stored in a warm, dry location with a uniform temperature. Ventilating openings should be covered to keep out dust and foreign objects. If it is necessary to store a transformer outdoors it should be thoroughly protected SUPERSEDES ADVANCE I. L. 46-3Q0-2 to prevent moisture and foreign material from entering. Condensation and the absorption of moisture can be prevented or greatly reduced by the installation of space heaters or other small electric heaters. Testing of transformers that have been in storage as described in the Instruction Leaflet "Operation Maintenance" should be performed before the transformer is placed in service. INSTALLATION Factors which should be kept in mind in locating dry type transformers are accessibility, ventilation, and atmospheric conditions. Dry type transformers are normally designed for installation indoors in dry locations. They will operate successfully while energized where the humidity is high but under this condition it may be necessary FIG. 1-Normal Air Circulation in a Dry Type Transformer. JANUARY 1952

6 DRY TYPE TRANSFORMERS --- to take precautions to keep them dry if they are shut down for appreciable periods. Precautions should be taken to guard against accidental entrance of water, such as might be obtained from an open window, by a break in a water or steam line, from use of water near the transformer, or from constantly dripping water. Adequate ventilation is essential for the proper cooling of transformers. Clean, dry air is desirable. Filtered air may reduce maintenance if the location presents a particular problem. When transformers are installed in vaults or other restricted spaces, sufficient ventilation should be provided to hold the air temperature within established limits when measured near the transformer inlets. This usually will require approximately 100 cubic feet of air per minute per kilowatt of transformer loss. The area of ventilating opening required depends on the height of the vault, location of openings, and the maximum loads to be carried by the transformer. For selfcooled transformers, the required area will be at least one square foot each of inlet and outlet per 100 Kva of rated transformer capacity, after deduction of the area occupied by screens, gratings or louvers. Dry type transformers should be installed in locations free from unusual dust producing mediums or chemical fumes. Transformers should be located 12 to 36 inches away from walls or other obstructions that might prevent free circulation of air through and around each unit. The distance between adjacent transformers should not be less than this value. Also accessibility for maintenance should be taken into account in locating a transformer. If the transformer is to be located near combustible materials, the minimum separations established by the national electrical code should be maintained. The transformer case is designed to prevent the entrance of most small animals and foreign objects. However, in some locations, it may be necessary to give consideration to additional protection. WESTINGHOUSE ELECTRIC CORPORATION SHARON PLANT TRANSFORMER DIVISION SHARON, PA. (Rep. MIS) Printed in U.SA.

7 FIG. l. I.L B INSTRUCT IONS Type ASL Distribution Transformer DESCRIPTION THE MODERN DRY TYPE TRANSFORM ER has been developed to supply the need for a safe transformer for indoor applications. DRY TYPB TRANSFORMBRS It is designed to be essentially fireproof and explosion proof for economical installations without vaults near its load center. Explosion and fire, the hazards of liquid filled transformers, are greatly reduced in air cooled transformers because they are constructed wi.th A.S.A. Class B and Class H materials and utilize the surrounding air for their cooling medium. Metal cases with suitable covered openings are used to encase air cooled transformers. The openin9s, which are necessary for the free oircul;;dion SUPERSEDES LL. 46-3Q0..6-A of air within the transformer, are not weather tight and so limit these transformers to indoor installations. Dry type transformers are manufactured in two types, the "DT-3" and the ASL. The type "DT-3" consists of the smaller ratings and the type ASL the larger ratings. The normal kva limit of self-cooled dry type transformers is 5000 kva single-phase and 7500 kva three-phase. It is possible to increase these limits by the addition of air blast equipment (which must be provided for at the time of design) or by the paralleling or banking of two or more units mounted in a common case. The maximum voltage for which air cooled transformers are built is volts. Dry type transformers are supplied with provision for grounding the case and an instruction FIG. 2. Type DT-3 Power Center Transformer OCTOBER, 1960

8 DRY TYPE TRANSFORMERS -- FIG. 3. Type ASL Power Transformer Crated for Export Shipment plate which gives the electrical connections and details of the transformer. Other accessories are supplied in accordance with the specific transformer and customer requirements. High and low voltage leads may be brought out of the case by several different methods. The most common are: porcelain bushings (see the Instruction Leaflet "Dry Type Transformer Bushings"), terminal chambers with potheads or conduit connections, and direct connection to switchgear, switches or bus work. SHIPMENT Except for lightning arresters and LCB switches, air cooled transformers are usually shipped ready for installation complete with bushings and accessories in place and connected for operation. They are completely covered with a weatherproof covering which should not be removed until the transformer is ready to be moved indoors and then, only when there is no danger of exposing the transformer to dampness. Shipping braces and shims under the transformer feet with their respective bolts when provided should be removed after installation. The outline drawing will show which braces are to be removed. FIG. 4. Type ASL Power Center Transformer Loaded on a Flat Car for Domestic Shipment For foreign shipment air cooled transformers are completely covered with a weather tight wrapping and crated with a sturdy wooden box and securely braced to take the extra handling and movement to which they are subjected while in transit. Aside from the crating, all details are the same as for domestic shipment. UNPACKING It is only necessary to remove the weather proof covering to completely unpack an air cooled transformer, however precautions to keep the transformer dry as outlined above must be followed. Occasionally bushings or other accessories are shipped separately. If this is done, care must be taken when unpacking as items such as bushings are quite fragile. SERVICE Further information, or renewal parts, may be obtained by contacting the nearest Westinghouse office. The facilities of the Engineering and Service Departments may be obtained through the nearest Westinghouse office. WESTINGHOUSE ELECTRIC CORPORATION SHARON PLANT TRANSFORMER DIVISION SHARON, PA. Prillted in U.S.A. -

9 I. L INSTRUCTIONS RECEIVING New transformers should be inspected when received for damage during shipment. RECEIVING AND INSTALLATION OF DRY TYPE TRANSFORMERS Examination should be made before removing from cars or trucks and if any injury is evident or any indication of rough handling is visible, a claim should be filed with the carrier at once and the manufacturer should be notified. After the transformer has been placed indoors, the panels should be removed and an internal inspection made for injury or displacement of parts, loose or broken connections, cracked porcelain, dirt or foreign material and for the presence of free water or moisture. Any damaged condition should be reported at once to the nearest Westinghouse Office. If water or moisture is evident see the Instruction Leaflet "Operation and Maintenance of Dry Type Transformers" for methods of testing for moisture and methods of drying out. HANDLING Lifting holes are provided on each side of the case for the insertion of hooks to lift the complete transformer. These holes should be closed with the steel cover provided, so as to prevent the entrance of foreign materials. For power centers and unit substations, eye nuts are provided for lifting the complete unit. After installation, these may be removed and the openings covered with cap provided. The base of these transformers is constructed so that the transformer can be moved on rollers in any horizontal direction. Under no circumstances should the transformer be moved with ropes or cables placed around the case. suitably designed for jacking. The transformer case is Jacks should be placed as indicated on the outline drawing. STORING Dry type transformers should be stored in a warm, dry location with a uniform temperature. Ventilating openings should be covered to keep out dust and foreign objects. If it is necessary to store a transformer outdoors it should be thoroughly protected SUPERSEDES ADVANCE I. L to prevent moisture and foreign material from entering. Condensation and the absorption of moisture can be prevented or greatly reduced by the installation of space heaters or other small electric heaters. Testing of transformers that have been in storage as described in the Instruction Leaflet "Operation Maintenance" should be performed before the transformer is placed in service. INSTALLATION Factors which should be kept in mind in locating dry type transformers are accessibility, ventilation, and atmospheric conditions. Dry type transformers are normally designed for installation indoors in dry locations. They will operate successfully while energized where the humidity is high but under this condition it may be necessary FIG. 1-Normal Air Circulation in a Dry Type Transformer. JANUARY 1952

10 DRY TYPE TRANSFORMERS --- to take precautions to keep them dry if they are shut down for appreciable periods. Precautions should be taken to guard against accidental entrance of water, such as might be obtained from an open window, by a break in a water or steam line, from use of water near the transformer, or from constantly dripping water. Adequate ventilation is essential for the proper cooling of transformers. Clean, dry air is desirable. Filtered air may reduce maintenance if the location presents a particular problem. When transformers are installed in vaults or other restricted spaces, sufficient ventilation should be provided to hold the air temperature within established limits when measured near the transformer inlets. This usually will require approximately 100 cubic feet of air per minute per kilowatt of transformer loss. The area of ventilating opening required depends on the height of the vault, location of openings, and the maximum loads to be carried by the transformer. For selfcooled transformers, the required area will be at least one square foot each of inlet and outlet per 100 Kva of rated transformer capacity, after deduction of the area occupied by screens, gratings or louvers. Dry type transformers should be installed in locations free from unusual dust producing mediums or chemical fumes. Transformers should be located 12 to 36 inches away from walls or other obstructions that might prevent free circulation of air through and around each unit. The distance between adjacent transformers should not be less than this value. Also accessibility for maintenance should be taken into account in locating a transformer. If the transformer is to be located near combustible materials, the minimum separations established by the national electrical code should be maintained. The transformer case is designed to prevent the entrance of most small animals and foreign objects. However, in some locations, it may be necessary to give consideration to additional protection. WESTINGHOUSE ELECTRIC CORPORATION SHARON PLANT TRANSFORMER DIVISION SHARON, PA. (Rep. ll-60) Printed in U.S.A.

www. ElectricalPartManuals. com I N S T R u C T I 0 N S WESTINGHOUSE RADIATORS INSTALLATION MAINTENANCE

www. ElectricalPartManuals. com I N S T R u C T I 0 N S WESTINGHOUSE RADIATORS INSTALLATION MAINTENANCE FIG. 1. Westinghouse Single Radiators Mounted Perpendicular to the Wall of a Form-Fit Tank THE WESTINGHOUSE RADIATOR is a highly efficient cooling unit which is designed for use on large self-cooled transformers

More information

www. ElectricalPartManuals. com INSTRUCTIONS I I DETERMINATION OF DRYNESS and METHODS OF DRYING OUT Minimum Insulation Resistance in Oll at 20 C

www. ElectricalPartManuals. com INSTRUCTIONS I I DETERMINATION OF DRYNESS and METHODS OF DRYING OUT Minimum Insulation Resistance in Oll at 20 C I.L. 48-628-1 INSTRUCTIONS All transformers are dry when they leave the factory, but since they may absorb more or less moisture during shipment and storage, they should not be put into service until it

More information

www. ElectricalPartManuals. com \/' INSTRUCTIONS WESTINGHOUSE RADIATORS DESCRIPTION '- INSTALLATION MAINTENANCE

www. ElectricalPartManuals. com \/' INSTRUCTIONS WESTINGHOUSE RADIATORS DESCRIPTION '- INSTALLATION MAINTENANCE FIG. 1. Westinghouse Single Radiators Mounted Perpendicular to the Wall of a Rectangular Tank on a 6,000 KVA Transformer THE WESTINGHOUSE RADIATOR is a highly efficient cooling unit which is designed for

More information

ELECTRIC UNIT HEATER REGULAR DUTY

ELECTRIC UNIT HEATER REGULAR DUTY ELECTRIC UNIT HEATER REGULAR DUTY Installation Form RGM 428 (MI500 Revision 0) APPLIES TO: Model EGE INDEX (by page number) Clearance to Combustibles... 3 Dimensions... 4 Electrical... 4 Fan Motor... 4

More information

IN-7750 April Instruction Manual. Ventilated Dry-Type Transformers. Unit Substation Type and Other Transformers Above 600 Volts

IN-7750 April Instruction Manual. Ventilated Dry-Type Transformers. Unit Substation Type and Other Transformers Above 600 Volts Instruction Manual IN-7750 April 2017 Ventilated Dry-Type Transformers Unit Substation Type and Other Transformers Above 600 Volts Instructions for the Safe Handling, Installation, Operation and Maintenance

More information

VACUUM OVEN. Model: VPX9-2. Installation and Operation Manual

VACUUM OVEN. Model: VPX9-2. Installation and Operation Manual VACUUM OVEN Model: VPX9-2 Installation and Operation Manual Sheldon Manufacturing, Inc. P.O. Box 627, 300 N 26 th Avenue, Cornelius, Oregon 97113 EMAIL: tech @ Shellab.com; www.shellab.com 1-800-322-4897

More information

INSTALLATION AND OPERATIONS MANUAL

INSTALLATION AND OPERATIONS MANUAL email: info@uapc.com Main Office: Telephone: 757-461-0077 1140 Kingwood Ave, Norfolk, Virginia 23502 Telefax: 757-461-0808 Branch Offices: Telephone: 704-374-0600 4715 Stockholm Court, Charlotte, NC 28273

More information

Quartzone. Infrared Quartz Tube & Metal Sheathed Electric Heaters. Owner s Manual. File E COMFORT HEATERS for INDOOR* and OUTDOOR** USE

Quartzone. Infrared Quartz Tube & Metal Sheathed Electric Heaters. Owner s Manual. File E COMFORT HEATERS for INDOOR* and OUTDOOR** USE Quartzone Infrared Quartz Tube & Metal Sheathed Electric Heaters Owner s Manual File E97759 COMFORT S for INDOOR* and OUTDOOR** USE *Excluding Residences ** With Quartz Elements and when mounted Underneath

More information

RENEWAL PARTS IDENTIFICATION. Type TTUH and TTUH-CO URN Heaters. Dimensions (In.) Extends. Model Volts kw W/In 2 A B C D

RENEWAL PARTS IDENTIFICATION. Type TTUH and TTUH-CO URN Heaters. Dimensions (In.) Extends. Model Volts kw W/In 2 A B C D Chromalox Installation, Operation and RENEWAL PARTS IDENTIFICATION DIVISION DATE SALES REFERENCE (Supersedes PD00-1) OCTOBER, 000 SECTION TTUH PD00-15 161-0815-001 Type TTUH and TTUH-CO URN Heaters TTUH-0A

More information

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2 I&M NUMBER: 316-42-15-1 Page: 1 _ Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to

More information

SPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

SPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS SPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with

More information

MODELS 304GC, 304GCX, 314GC, and 314GCX

MODELS 304GC, 304GCX, 314GC, and 314GCX 2562109A REV. A1 0317 Printed in U.S.A. MODELS 304GC, 304GCX, 314GC, and 314GCX INSTALLATION AND SERVICE INSTRUCTIONS FOR SELECTONE Limited Warranty This product is subject to and covered by a limited

More information

Powerohm Resistors Digital HRG System

Powerohm Resistors Digital HRG System Installation and Operating Instructions Powerohm Resistors Digital HRG System This manual provides general information, installation, operation, maintenance, and system setup information for the Powerohm

More information

Installation & Maintenance Instructions

Installation & Maintenance Instructions B2451 & B2452 Series Wall Heaters SPECIFICATIONS MODEL VOLTS HZ AMPS WATTS BTUH B2451 120 60 12.5 1500 5120 B2452 240 60 8.3 2000 6826 208 60 7.2 1500 5120 DIMENSIONS OVERALL Height - 14 1/4 Width - 11

More information

Installation Instructions Type XPMC Air Heater for Hazardous Locations

Installation Instructions Type XPMC Air Heater for Hazardous Locations Installation Instructions Type XPMC Air for Hazardous Locations 1 PF500-1 161-302639-005 May 2017 XPMC Air for Hazardous Locations 12", 2 Heat Sinks with Fixed Thermostat 12", 2 Heat Sinks with Adjustable

More information

MODELS ASHP, ASHH, ASUP, and ASUH

MODELS ASHP, ASHH, ASUP, and ASUH 2562229A REV. A 1210 Printed in U.S.A. MODELS ASHP, ASHH, ASUP, and ASUH INSTALLATION AND SERVICE INSTRUCTIONS blank page INSTALLATION AND SERVICE INSTRUCTIONS FOR MODELS ASHP, ASHH, ASUP, AND ASUH SAFETY

More information

Enviro KES INSTALLATON MANUAL

Enviro KES INSTALLATON MANUAL Enviro KES INSTALLATON MANUAL Spring Air Systems Inc., Oakville, Ontario Phone (905) 338-2999, Fax (905) 338-0179, info@springairsystems.com www.springairsystems.com KES Installation Manual. This publication

More information

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL TUBE AXIAL FANS BTA, WTA, HTA, DDA The purpose of this manual is to aid in the proper installation and operation of the fans. These instructions are intended

More information

Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers

Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers Bulletin 1200/4 (Revised 5/12) Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers INNOVATORS IN HEAT TRANSFER I. INSTALLATION OF HEAT EXCHANGERS A. HEAT EXCHANGER SETTINGS 1)

More information

SWP. (Models SWP08 through SWP20) IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL

SWP. (Models SWP08 through SWP20) IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL SWP (Models SWP08 through SWP20) OPERATION & MAINTENANCE MANUAL IMPORTANT! Read before proceeding! Read carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

Installation Instructions U-RAD-LT Electric Radiant Heaters

Installation Instructions U-RAD-LT Electric Radiant Heaters Installation Instructions U-RAD-LT Electric Radiant Heaters 1 PG421-2 161-058006-001 May 2016 2 U-RAD-LT Electric Radiant Heaters The Safety Alert Symbol is used to indicate a risk of personal injury.

More information

INSTALLATION AND OPERATION MANUAL

INSTALLATION AND OPERATION MANUAL ECONOMY OVENS SMO1E SMO3E MODELS OBSOLETED AFTER MAY 31ST SMO1E-2, SMO3E-2, SMO5E, SOM5E-2 INSTALLATION AND OPERATION MANUAL Revised June 13, 2017 861659 Sheldon Manufacturing Inc. P.O. Box 627 Cornelius,

More information

B.C.S. Shop Heaters 26, 30 & 36 (36 shown)

B.C.S. Shop Heaters 26, 30 & 36 (36 shown) BIOMASS COMBUSTION SYSTEMS, INC. 67 MILLBROOK ST., SUITE 502 WORCESTER, MA 01606 508-798-5970 - FAX 508-798-5971 B.C.S. Shop Heaters 26, 30 & 36 (36 shown) INSTALLATION MANUAL HAND FIRED SYSTEMS 8-09 Biomass

More information

Fisher Scientific Isotemp Muffle Furnace 550 Series. Instruction Manual

Fisher Scientific Isotemp Muffle Furnace 550 Series. Instruction Manual Fisher Scientific Isotemp Muffle Furnace 550 Series Instruction Manual Model 14 Catalog No: 10-550-14 & 14A Model 58 Catalog No: 10-550-58 Model 126 Catalog No: 10-550-126 Service Division (Repairs):

More information

RCM-77. Instruction Manual. G-Series Cooler. U.S. Patent No. 8,215,125 RECHARGE COLD MERCHANDISER

RCM-77. Instruction Manual. G-Series Cooler. U.S. Patent No. 8,215,125 RECHARGE COLD MERCHANDISER G-Series Cooler RECHARGE COLD MERCHANDISER U.S. Patent No. 8,215,125 Instruction Manual FOR YOUR FUTURE REFERENCE This easy-to-use manual will guide you in getting the best use of your cooler. Remember

More information

Tooling Assistance Center

Tooling Assistance Center Safeguards are designed into this application equipment to protect operators and maintenance personnel from most hazards during equipment operation. However, certain safety precautions must be taken by

More information

WATLOW ELECTRIC MFG CO. WATROD Duct Heater (module only) I& M Manual I&M NUMBER: Page: 1 Date: 11/25/2013 Rev: 4.00

WATLOW ELECTRIC MFG CO. WATROD Duct Heater (module only) I& M Manual I&M NUMBER: Page: 1 Date: 11/25/2013 Rev: 4.00 I&M NUMBER: 316-42-16-1 Page: 1 Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to

More information

Watt-Muncher Load Bank Manual WATT-MUNCHER. Portable Load Bank. 6 June 2018 Simplex Service Page 1 of 13

Watt-Muncher Load Bank Manual WATT-MUNCHER. Portable Load Bank. 6 June 2018 Simplex Service Page 1 of 13 WATT-MUNCHER Portable Load Bank 6 June 2018 Simplex Service 800-637-8603 Page 1 of 13 This manual was last revised: 6 June 2018 For up-to-date information on this product or others, please contact Simplex

More information

DC Motor Blower Kit Frames DC180ATZ and C180ATZ thru C400ATZ Installation & Operating Manual

DC Motor Blower Kit Frames DC180ATZ and C180ATZ thru C400ATZ Installation & Operating Manual DC Motor Blower Kit Frames DC180ATZ and C180ATZ thru C400ATZ Installation & Operating Manual 10/11 Any trademarks used in this manual are the property of their respective owners. Important: Be sure to

More information

Chromalox. Installation, Operation. Portable Industrial Unit Blower Air Heater Types SDRA and SDRA-RG RENEWAL PARTS IDENTIFICATION

Chromalox. Installation, Operation. Portable Industrial Unit Blower Air Heater Types SDRA and SDRA-RG RENEWAL PARTS IDENTIFICATION Chromalox Installation, Operation and RENEWAL PARTS IDENTIFICATION DIVISION SALES REFERENCE DATE (Supersedes PF99-1) AUGUST, 2010 Portable Industrial Unit Blower Air Types SDRA and SDRA-RG SECTION SDRA

More information

M Series Fan Filter Units

M Series Fan Filter Units M Series Fan Filter Units Product Specifications... 2 Safety Instructions... 3 Receiving and Unpacking... 3 Pre-Installation Instructions... 3-4 Installation Instructions... 4 Electrical Installation Instructions...

More information

CIRCUIT BREAKER - GAS

CIRCUIT BREAKER - GAS CIRCUIT BREAKER - GAS Capabilities: In a large substation, circuit breakers are used to interrupt any short-circuits or overload currents that may occur on the network. A 345 kv, high voltage, three position/phase

More information

PARAFFIN/DIESEL HEATER

PARAFFIN/DIESEL HEATER PARAFFIN/DIESEL HEATER MODEL NO: XR60 PART NO: 6931002 OPERATION & MAINTENANCE INSTRUCTIONS LS0813 INTRODUCTION Thank you for purchasing this CLARKE product. Before attempting to use this product, please

More information

INSTALLATION MANUAL. '»'"',' ','"* Self-contained Ceiling Mount Electronic Air Cleaner.

INSTALLATION MANUAL. '»'',' ','* Self-contained Ceiling Mount Electronic Air Cleaner. . '»'"',' ','"* '^ Self-contained Ceiling Mount Electronic Air Cleaner. Fits T-Bardrop ceiling or mounts directly to standard ceiling. Quieter performance* Adjustable discharge louvers on 4 sides. Cleans

More information

Installation Instructions

Installation Instructions 50ES---A, 50EZ---A, 50VL---A, 50VG---A, 50VR---A, 50VT---A, 604D--- ---A, 607C--- ---A, 607E,--- ---A, 704D--- ---A, 707C--- ---A, 707E--- ---A PA3G --- --- A, PH3G --- --- A SMALL PACKAGED PRODUCTS Electric

More information

G-7s. Instruction Manual. G-Series Cooler COUNTERTOP COOLER. Part No.11IPA

G-7s. Instruction Manual. G-Series Cooler COUNTERTOP COOLER. Part No.11IPA G-Series Cooler COUNTERTOP COOLER Part No.11IPA-061000 Instruction Manual FOR YOUR FUTURE REFERENCE This easy-to-use manual will guide you in getting the best use of your cooler. Remember to record the

More information

MIRUS International Inc.

MIRUS International Inc. MIRUS International Inc. INSTALLATION, OPERATION AND MAINTENANCE GUIDE HARMONY Series Transformers Harmony Transformers HARMONY Owner's Manual H-M001-A2 HARMONY Warranty Seller warrants to the Ultimate

More information

Dr. Infrared Heater Elite Series

Dr. Infrared Heater Elite Series Dr. Infrared Heater Elite Series 1500 Watts with Two Heat Settings Built-In Humidifier Rotatable Air Outlet Automatic Thermostat Tip-Over Switch Overheat Thermal Cut-Off Protection Room Temperature LED

More information

Model: Ecostrad Thermostrip with Remote

Model: Ecostrad Thermostrip with Remote Model: Ecostrad Thermostrip with Remote Model no.: AH18NCPR 1800 W Ratings: 220 V 240 V; 50 Hz; Class I; IP65 Introduction The Ecostrad Thermostrip is a versatile infrared heater that provides radiant

More information

Installation Instructions

Installation Instructions EHNA Electric Heaters 5-20kW For 60 Hz Small Packaged Products MODELS: PAD3, PHD3, PAD4, PHD4, PAD5, PHD5, WPA3, WPH3 Installation Instructions NOTE: Read the entire instruction manual before starting

More information

AIR-COOLED CONDENSING UNIT UNITS PRODUCED AFTER JANUARY, 1996 INDEX SCHEMATIC DIAGRAM FIG. NO.

AIR-COOLED CONDENSING UNIT UNITS PRODUCED AFTER JANUARY, 1996 INDEX SCHEMATIC DIAGRAM FIG. NO. wiring diagrams AIR-COOLED CONDENSING UNIT 566D Sizes 120-240 Cancels: New WD 566D.120.1 11/15/96 UNITS PRODUCED AFTER JANUARY, 1996 INDEX UNIT 566D 120-240 ELECTRICAL CHARACTERISTICS (V-Ph-Hz) SCHEMATIC

More information

Fisher Scientific Model 281A Vacuum Oven. Installation and Operating Manual Rev. 0

Fisher Scientific Model 281A Vacuum Oven. Installation and Operating Manual Rev. 0 Fisher Scientific Model 281A Vacuum Oven Installation and Operating Manual 30979 Rev. 0 Preface Models covered in this manual: Catalog numbers Models numbers Voltage 13-262-50 6288 120V 13-262-51 6289

More information

Part No Revised January 30, 2007 SAFETY PRECAUTIONS

Part No Revised January 30, 2007 SAFETY PRECAUTIONS DUAL ZONE STAGING CABINET Instruction Manual Part No. 44406 Revised January 30, 2007 SAFETY PRECAUTIONS SAFETY PRECAUTIONS INTRODUCTION This manual covers the model #2856. The unit is designed to provide

More information

Horizontal/Side Discharge Condensing Units

Horizontal/Side Discharge Condensing Units INSTALLATION, OPERATION & MAINTENANCE MANUAL Horizontal/Side Discharge Condensing Units Models CMA12SD-0 CMA18SD-1 CMA24SD-1 CMA30SD-1 CMA36SD-1 CMA48SD-1 517.787.2100 www.marsdelivers.com Horizontal/Side

More information

Installation Manual CARBONATOR With Plain-Water Booster

Installation Manual CARBONATOR With Plain-Water Booster CORNELIUS INC One Cornelius Place Anoka, MN 55303-6234 Telephone (800) 238-3600 Facsimile (763) 422-3246 Installation Manual CARBONATOR With Plain-Water Booster IMPORTANT: It is the responsibility of the

More information

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check for any interior and exterior damage, and

More information

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check

More information

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check

More information

Breezex (BX) Heavy Duty Reversible Supply/Exhaust Fans with Reversing Switch. IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL

Breezex (BX) Heavy Duty Reversible Supply/Exhaust Fans with Reversing Switch. IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL Breezex (BX) Heavy Duty Reversible Supply/Exhaust Fans with Reversing Switch OPERATION & MAINTENANCE MANUAL IMPORTANT! Read before proceeding! Please read and save these instructions. Read carefully before

More information

FEB 15 Rev C

FEB 15 Rev C ORIGINAL INSTRUCTIONS Double-Action Hand Tool (DAHT) Lithium-Ion Battery-Powered Crimping Tool Kits 2217483-[ ] Customer Manual 409-32028 13 FEB 15 Rev C SAFETY PRES READ THIS FIRST!... 2 1. INTRODUCTION...

More information

Installation Operation Maintenance Instructions

Installation Operation Maintenance Instructions Installation Operation Maintenance Instructions Storage Recommendations Induction Motors Integral Horsepower TABLE OF CONTENTS INTRODUCTION............................. 3 SAFETY PROCEDURE.........................

More information

AVANI Grinding Booth

AVANI Grinding Booth AVANI Grinding Booth GB-6066-DD Customer: Kelly Walsh Customer PO#: 11305 AVANI SO#: Serial #: 153920-153921 Ship Date / Install Date: Tested By: Please read and save these instructions. Read carefully

More information

J120 STEAM BOOSTER INSTALLATION, OPERATION, AND SERVICE MANUAL J120 STEAM BOOSTER. J120 Steam Booster Manual D

J120 STEAM BOOSTER INSTALLATION, OPERATION, AND SERVICE MANUAL J120 STEAM BOOSTER. J120 Steam Booster Manual D INSTALLATION, OPERATION, AND SERVICE MANUAL J120 STEAM BOOSTER J120 STEAM BOOSTER J120 Steam Booster Manual REVISION HISTORY Revision Letter Revision Date Made by Applicable ECNs Details A 10-27-04 CBW

More information

KPHE24 SERIES WATER-TO-AIR HEAT EXCHANGER

KPHE24 SERIES WATER-TO-AIR HEAT EXCHANGER Keep This Manual With Heat Exchanger Find additional information on this model at kooltronic.com or use the Technical Documents QR code below. Technical Documents KPHE24 SERIES WATER-TO-AIR HEAT EXCHANGER

More information

Professional Warming Drawer and Warming Drawer Cabinet

Professional Warming Drawer and Warming Drawer Cabinet Professional Warming Drawer and Warming Drawer Cabinet Care & Use/Installation Instructions Models: (C)VQEWD5300SS (C)VQEWD5420SS IMPORTANT SAFETY INSTRUCTIONS WARNING: Read this manual carefully and completely

More information

WATLOW ELECTRIC MFG CO. FIREBAR Screw Plug Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 11/25/2013 Rev: 4.

WATLOW ELECTRIC MFG CO. FIREBAR Screw Plug Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 11/25/2013 Rev: 4. I&M NUMBER: 316-42-3-1 Page: 1 Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to elements

More information

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW INSTALLATION INSTRUCTIONS RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW 92-106595-01-00 TABLE OF CONTENTS Introduction.......................................

More information

Instruction Manual Item No.: V~, 60Hz

Instruction Manual Item No.: V~, 60Hz Energy- Saving Mode Portable AC 8,000 BTU Model: MW-O-08C Montgomery Ward Customer Service 1112 7th Avenue, Monroe, WI 53566 8:00 am to Midnight, Monday through Friday Wards.com 1 888 557 3848 Instruction

More information

G-10s. Instruction Manual. G-Series Cooler UPRIGHT COOLER. Part No.11IPA

G-10s. Instruction Manual. G-Series Cooler UPRIGHT COOLER. Part No.11IPA G-Series Cooler UPRIGHT COOLER Part No.11IPA-062800 Instruction Manual FOR YOUR FUTURE REFERENCE Thank you for using our product. This manual will guide you in getting the best use of your cooler. Remember

More information

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTION INSTALLATION INSTRUCTION MODULAR AIR HANDLER MODEL: N*AH CONTENTS GENERAL... 1 INSPECTION... 2 REFERENCE... 2 LIMITATIONS... 2 LOCATION... 2 BLOWER/COIL ASSEMBLY UPFLOW AND HORIZONTAL INSTALLATIONS...

More information

Installation & Maintenance Instructions

Installation & Maintenance Instructions Portable High Temperature Blower Attention: Do not operate this heater in explosive areas. Installation & Maintenance Instructions Dear Owner, Congratulations! Thank you for purchasing this new heater

More information

SPACESAVER INSTRUCTION MANUAL WARRANTY CERTIFICATE

SPACESAVER INSTRUCTION MANUAL WARRANTY CERTIFICATE SPACESAVER BY INSTRUCTION MANUAL WARRANTY CERTIFICATE Manual design and all elements of manual design are protected by U.S. Federal and/or State Law, including Patent, Trademark and/or Copyright laws.

More information

USER GUIDE. This manual covers the description, cautions, operation and maintenance of Super Vac confined space electric ventilators CONTENTS

USER GUIDE. This manual covers the description, cautions, operation and maintenance of Super Vac confined space electric ventilators CONTENTS VENTILATOR USER GUIDE MODEL HF124 USER GUIDE This manual covers the description, cautions, operation and maintenance of Super Vac confined space electric ventilators Please take the time to read this manual

More information

INSTALLATION, OPERATION & MAINTENANCE MANUAL FOR DRY PAK PACKAGED COMPRESSED AIR TREATMENT SYSTEM MODEL: DPP-150 WARNING

INSTALLATION, OPERATION & MAINTENANCE MANUAL FOR DRY PAK PACKAGED COMPRESSED AIR TREATMENT SYSTEM MODEL: DPP-150 WARNING January 207 80-572 Rev - 2950 Mechanic Street Lake City, PA 6423 USA Phone: -800-840-9906 Fax: 84-774-0778 Email: info@vanairsystems.com www.vanairsystems.com INSTALLATION, OPERATION & MAINTENANCE MANUAL

More information

Combination Cooling/Gas Heat Package Units

Combination Cooling/Gas Heat Package Units User s Manual Combination Cooling/Gas Heat Package Units YSC036E* YHC036E* YSC048E* YHC048E* YSC060E* YHC060E* YSC072E* YHC072E* YSC090E* YHC092E* YSC092E* YHC102E* YSC102E* YHC120E* YSC120E* July 2009

More information

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT Technical Data SD 4511A SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY 12586-2035 TYPE T14 & T14D TEMPERATURE PILOT PRINTED IN U.S.A. SD 4511A/9811 5 13 /16 D 4 7 /8 1 13 /16 T14 PILOT

More information

SERIES 500. Installation & Maintenance Instructions. Ceiling Mounted Fan Forced Heater WARNING SAVE THESE INSTRUCTIONS. Recessed Mount.

SERIES 500. Installation & Maintenance Instructions. Ceiling Mounted Fan Forced Heater WARNING SAVE THESE INSTRUCTIONS. Recessed Mount. Recessed Mount Ceiling Mounted Fan Forced SERIES 500 Surface Mount Installation & Maintenance Instructions Dear Owner, Congratulations Thank you for purchasing this new heater manufactured by Marley Engineered

More information

MLM. Multi-Layer Media for Regenerative Thermal Oxidizers. from Lantec Products Installation Manual

MLM. Multi-Layer Media for Regenerative Thermal Oxidizers. from Lantec Products Installation Manual MLM Multi-Layer Media for Regenerative Thermal Oxidizers from Lantec Products Installation Manual 1. Introduction Contents 1. Introduction 2. Safety First 3. Media Inspection on Arrival 4. Proper Handling

More information

WATLOW IND. WATROD Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2.00

WATLOW IND. WATROD Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2.00 I&M NUMBER: 316-42-8-1 Page: 1 _ Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to

More information

KPHE32 SERIES WATER-TO-AIR HEAT EXCHANGER

KPHE32 SERIES WATER-TO-AIR HEAT EXCHANGER Keep This Manual With Heat Exchanger Find additional information on this model at kooltronic.com or use the Technical Documents QR code below. Technical Documents KPHE32 SERIES WATER-TO-AIR HEAT EXCHANGER

More information

M-11 Series. Installation and Service Manual

M-11 Series. Installation and Service Manual M-11 Series Installation and Service Manual INTRODUCTION SPECIFICATIONS UNPACKING MOUNTING ELECTRICAL OPERATION MAINTENANCE REPLACEMENT PARTS TROUBLESHOOTING ***IMPORTANT*** THIS MANUAL CONTAINS PRECAUTIONARY

More information

KNHE30 SERIES WATER-TO-AIR HEAT EXCHANGER

KNHE30 SERIES WATER-TO-AIR HEAT EXCHANGER Keep This Manual With Heat Exchanger Find additional information on this model at kooltronic.com or use the Technical Documents QR code below. Technical Documents KNHE30 SERIES WATER-TO-AIR HEAT EXCHANGER

More information

www.whitakerbrothers.com The Challenge Machinery Company provides owner's manuals on its products solely as a courtesy to its customers. See the information below before using this manual. These manuals

More information

WATLOW IND. FIREBAR Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00

WATLOW IND. FIREBAR Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00 I&M NUMBER: 316-42-2-1 Page: 1 Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to elements

More information

Type 300 Series Bench Electrode Stabilization Ovens

Type 300 Series Bench Electrode Stabilization Ovens REPAIR PARTS INSTALLATION INSTRUCTIONS Type 300 Series Bench Electrode Stabilization Ovens *Please read all instructions, paying special attention to all cautions or warnings, before beginning any repairs.

More information

BK17 Heater. Read all instructions before using the heater. Contents

BK17 Heater. Read all instructions before using the heater. Contents Read all instructions before using the heater Contents 1) Components... 3 Total Assembly... 3 2) Specifications... 4 a) Power Specifications... 4 3) Receiving... 4 4) Safety... 5 a) Power connections...

More information

INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP

INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP RV Products A Division of Airxcel, Inc. P.O. Box 4020 Wichita, KS 67204 1976-360 (1-02) PP TABLE OF CONTENTS 1. Warnings......................................................

More information

Manual for MC91 SETUP INSTRUCTIONS

Manual for MC91 SETUP INSTRUCTIONS Manual for MC91 SETUP INSTRUCTIONS Evaporative cooling works on the principle of heat absorption by moisture evaporation. Simply put, heat is removed from the air as water evaporates. You feel this principle

More information

Garment Steamer Model SC620

Garment Steamer Model SC620 OWNER S MANUAL Garment Steamer Model SC620 For information or assistance: EURO-PRO Corporation 178 West Service Rd. Champlain, NY 12919 1-800-798-7398 www.euro-pro.com IMPORTANT SAFETY INSTRUCTIONS When

More information

Getting Started Quick Reference Guide

Getting Started Quick Reference Guide Getting Started Quick Reference Guide Electric Immersion Heater Installation and Operating Instructions Read and understand instructions before installing, operating or servicing equipment. Failure to

More information

Series 300 VTB. Installation Instructions

Series 300 VTB. Installation Instructions Series 300 VTB Installation Instructions Sizes 7 12 16 20 30 HP #2 Fuel Oil Gas (500 to 2500 BTU) Gas Light Oil Combination High Pressure Steam Sizes 7 thru 16 HP (125 PSI) Sizes 20 and 30 HP (150 PSI)

More information

CONSOLIDATED EDISON CO. OF NEW YORK INC. 4 IRVING PLACE NEW YORK, N.Y DISTRIBUTION ENGINEERING CABLE SYSTEMS

CONSOLIDATED EDISON CO. OF NEW YORK INC. 4 IRVING PLACE NEW YORK, N.Y DISTRIBUTION ENGINEERING CABLE SYSTEMS CONSOLIDATED EDISON CO. OF NEW YORK INC. 4 IRVING PLACE NEW YORK, N.Y. 10003 DISTRIBUTION ENGINEERING CABLE SYSTEMS SPECIFICATION EO-4082 REVISION 2 May, 1998 OPERATION AND MAINTENANCE OF CONDUIT SYSTEM,

More information

! The Caution Symbol (exclamation point) alerts you to a "CAUTION", a safety or

! The Caution Symbol (exclamation point) alerts you to a CAUTION, a safety or I&M NUMBER: 316-42-10-1 Page: 1 Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to

More information

VACUUM OVENS MODEL: 1410MS,1430MS, 1450MS INSTALLATION AND OPERATIONAL MANUAL

VACUUM OVENS MODEL: 1410MS,1430MS, 1450MS INSTALLATION AND OPERATIONAL MANUAL VACUUM OVENS MODEL: 1410MS,1430MS, 1450MS INSTALLATION AND OPERATIONAL MANUAL Sheldon Manufacturing Inc. P.O. Box 627 Cornelius, Oregon 97113 EMAIL: tech@shellab.com INTERNET: http://www.shellab.com/~shellab

More information

Operating Instructions & Parts Manual Models 99533, 99532

Operating Instructions & Parts Manual Models 99533, 99532 Operating Instructions & Parts Manual Models 99533, 99532 2 Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

MODEL: 1407, , 1408, & INSTALLATION AND INSTRUCTION MANUAL

MODEL: 1407, , 1408, & INSTALLATION AND INSTRUCTION MANUAL ECONOMY VACUUM OVEN MODEL: 1407, 1407-2, 1408, & 1408-2 INSTALLATION AND INSTRUCTION MANUAL Sheldon Manufacturing Inc. P.O. Box 627, Cornelius, Oregon 97113 EMAIL: tech@shellab.com INTERNET: http://www.shellab.com/~shellab

More information

USER GUIDE CONTENTS. Please take the time to read this manual before operating the ventilator. Save this guide for future reference.

USER GUIDE CONTENTS. Please take the time to read this manual before operating the ventilator. Save this guide for future reference. VENTILATOR USER GUIDE MODEL HF164E USER GUIDE This manual covers the description, cautions, operation and maintenance of Super Vac confined space electric ventilators with explosionproof motors. Please

More information

READ AND SAVE THESE INSTRUCTIONS. Air Boss Model T5200 Custom Packaged Electronic Air Cleaner. TRION

READ AND SAVE THESE INSTRUCTIONS. Air Boss Model T5200 Custom Packaged Electronic Air Cleaner. TRION READ AND SAVE THESE INSTRUCTIONS Air Boss Model T5200 Custom Packaged Electronic Air Cleaner TRION Installation, Operation, & Service Manual Electrostatic Precipitators for Commercial & Industrial Applications

More information

Manual No: Revision: E. Groundwater Sensor. Installation Guide

Manual No: Revision: E. Groundwater Sensor. Installation Guide Manual No: 576013-763 Revision: E Groundwater Sensor Installation Guide Notice Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties

More information

General Care and Safety Guide

General Care and Safety Guide GECO203 General Care and Safety Guide Thank you for choosing a ecosave Panel Heater. This ecosave heater has been designed and manufactured to high standards of engineering and with proper use and care,

More information

NOVALYNX CORPORATION

NOVALYNX CORPORATION NOVALYNX CORPORATION MINIMUM-MAXIMUM THERMOMETER SET NATIONAL WEATHER SERVICE TYPE INSTRUCTION MANUAL 210-4420 210-4421 210-4425 210-4426 210-4429 210-4430 EXTRACTED FROM THE NWS OBSERVING HANDBOOK NO.

More information

ELECTRIC COMPACT DECK OVEN INSTALLATION - OPERATION - MAINTENANCE

ELECTRIC COMPACT DECK OVEN INSTALLATION - OPERATION - MAINTENANCE 1415 ELECTRIC COMPACT DECK OVEN INSTALLATION - OPERATION - MAINTENANCE BLODGETT OVEN COMPANY www.blodgett.com 44 Lakeside Avenue, Burlington, Vermont 05401 USA Telephone: (802) 658-6600 Fax: (802)864-0183

More information

Part No Revised December 2002 DESIGNER SERIES NACHO CABINETS Instruction Manual Model #5510, 5511 AND 5512

Part No Revised December 2002 DESIGNER SERIES NACHO CABINETS Instruction Manual Model #5510, 5511 AND 5512 Part No. 74271 Revised December 2002 DESIGNER SERIES NACHO CABINETS Instruction Manual Model #5510, 5511 AND 5512 Safety Precautions 2 FORWARD This manual covers the all models #5510, #5511 and #5512 nacho

More information

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13 R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.

More information

Handling or using the product improperly and in disregard of the instructions with this mark might result in serious bodily injury or death.

Handling or using the product improperly and in disregard of the instructions with this mark might result in serious bodily injury or death. Please Read: Safety Precautions DC AC In order to ensure that this product is used safely, be sure that you read and understand the following precautions fully and use the product only as directed. Be

More information

DIESEL/PARAFFIN HEATERS

DIESEL/PARAFFIN HEATERS DIESEL/PARAFFIN HEATERS MODEL NO: XR80, XR110, XR160, XR210 PART NO: 6931004, 6931006, 6931008, 6931012 OPERATION & MAINTENANCE INSTRUCTIONS LS0814 INTRODUCTION Thank you for purchasing this CLARKE product.

More information

DUAL VOLTAGE ICE BOX CONVERSION SYSTEM 120 VOLTS A.C. & 12/24 VOLTS D.C. MODELS: SCQT-4408F-U1-L SCQT-4408F-U1-I OWNER'S GUIDE

DUAL VOLTAGE ICE BOX CONVERSION SYSTEM 120 VOLTS A.C. & 12/24 VOLTS D.C. MODELS: SCQT-4408F-U1-L SCQT-4408F-U1-I OWNER'S GUIDE DUAL VOLTAGE ICE BOX CONVERSION SYSTEM 120 VOLTS A.C. & 12/24 VOLTS D.C. MODELS: SCQT-4408F-U1-L SCQT-4408F-U1-I OWNER'S GUIDE SAWAFUJI ELECTRIC CO., LTD. GENERAL: This appliance is designed to convert

More information

POWER CUT Hedge Trimmer 46 Model No. 101HT450

POWER CUT Hedge Trimmer 46 Model No. 101HT450 POWER CUT Hedge Trimmer 46 Model No. 101HT450 Operator s Manual To reduce the risk of injury, the user must read and understand the Operator s Manual. Keep these instructions for future reference. Introduction

More information

BMW E36 Thermostat Removal And Coolant Flush

BMW E36 Thermostat Removal And Coolant Flush BMW E36 Thermostat Removal And Coolant Flush Disclaimer: The cooling system is critical to the proper operation of your car. Failure to properly install all of the components of the cooling system could

More information

Model No: Little Devil II (inc ss)

Model No: Little Devil II (inc ss) GAS HEATER Model No: Little Devil II (inc ss) PART NO: 6926020, 6926025 (SS) OPERATION & MAINTENANCE INSTRUCTIONS LS1213 INTRODUCTION Thank you for purchasing this CLARKE Gas Heater. Before attempting

More information