38LB/38LF AIR COOLED CONDENSING UNIT

Size: px
Start display at page:

Download "38LB/38LF AIR COOLED CONDENSING UNIT"

Transcription

1 WORLD LEADER IN AIR CONDITIONING AND HEATING TECHNOLOGY INSTALLATION, START-UP AND SERVICE INSTRUCTIONS 38LB/38LF AIR COOLED CONDENSING UNIT CONTENTS PAGE PHYSICAL DATA 2 PHYSICAL DATA 2 DIMENSION DATA 3 RIGGING&UNPACKING 4 CONFIGURATION 5 ELECTRICAL DATA 5 PIPING CONNECTIONS / PIPING 6 MAINTENANCE 7 WIRING DIAGRAM 8-9 ATTENTION BEFORE OPERATING

2 Physical Data 38LB Description Air Cooled Condensing Unit Product Model 38LB 048SC 060SC 007SC 009SC 012SC 015SC Nominal Cooling Capacity W 14,000 17,500 22,800 28,700 35,100 43,900 Btu/hr. 48,000 60,000 78,000 98, , ,000 Power Consumption W 4,200 5,240 6,170 9,370 10,830 14,330 Power Supply V/Ph/Hz 380/3/50 Operating Current Amp Compressor Type Scroll Compressor QTY RLA Amp LRA Amp Power Supply V/Ph/Hz 220/1/50 Power Input W Fan Motor RLA Amp Fan Type Propeller QTY Drive Type Direct Safety Device Hi-Pressure Switch psig / (Cut out / Cut in) - Auto Restart type Low-Pressure Switch psig / 60+15(Cut out / Cut in) - Auto Restart type Refrigerant Type R-22 Pre-Charging from Facto kg Piping Connections Liquid inch 3/8 (Flare) 1/2 (Flare) 5/8 (Flare) Suction inch 7/8 (Flare) 1-1/8 (Brazing) 1-3/8 (Brazing) Height mm Dimension Width mm Depth mm Weight kg * RATING CONDITION: OUTDOOR AMBIENT TEMPERATURE 95F, SATURATED SUCTION TEMPERATURE 45F ** UNIT SUPPLIED FROM FACTORY ONLY 4.5 LB FOR PRE-CHARGED 38LF Description Air Cooled Condensing Unit Product Model 38LF048 38LF060 38LF007 38LF009 38LF012 38LF015 Nominal Cooling Capacity Btu/hr. 48,000 60,000 78,000 98, , ,000 w Power Consumption w 4,470 5,380 6,270 9,320 10,880 14,380 Power Supply V/Ph./Hz 380/3/50 RLA Amp Operating Weight (Approx) kg Compressor Fully Hermetric Scroll Compressor Type HFC R-407C Refrigerant Pre-Charging from Factory Nitrogen Operation Charging kg Fan Motor Type Propeller Fan, Direct Drive Power Supply V/Ph/Hz 220/1/50 Safety Device Hi-Pressure Switch psig 395 / 275 (Cut out / Cut in) - Auto Restart type Low-Pressure Switch psig 30 / 60 (Cut out / Cut in) - Auto Restart type Piping Connections Liquid inch 3/8 1/2 5/8 5/8 Suction inch 7/8 1-1/8 1-1/8 1-3/8 Dimension Height mm Width mm Weigth kg * RATING CONDITION: OUTDOOR AMBIENT TEMPERATURE 95 F, SATURATED SUCTION TEMPPERATURE 45 F ** UNIT SUPPLIED FROM FACTORY ONRY NITROGEN - 2 -

3 Dimension Data 38LB Dimension (mm.) 38LF Dimension (mm.) - 3 -

4 Rigging & Unpacking Unit should not be removed from protective packaging until reaching final location. The 38LB Series should be handled and installed upright. Inspect the unit for shipping damage and file claim with transport agency if necessary. Confirm the nameplate voltage to ensure that it matches available power supply. Consult building and electrical codes as required in your area. Location Unit should be installed outdoors. Do not restrict service, wiring and piping areas. Also avoid positioning unit in manner restriction airflow or in areas where water will pour directly onto unit. Minimum recommended clearance space is shown in figure 1 to 4. Fig 1 Fig 2 Fig 3 Fig 4-4 -

5 Configuration Unit is shipped from factory in vertical discharge configuration as standard. However, converting to horizontal discharge as shown is simply effected without extra fittings or metal sheet work. To modify into horizontal discharge mode : 1. Ensure all electrical supply to the unit is disconnected and then loosen top and fan discharge panels by removing screws. 2. Release wires tie on fan motor wires in control box and ease wires out of hole for extra length for interchanging panels. 3. Assemble top panel on front of unit and secure with screws. 4. Final assembles fan discharge panel. Pull fans motor wires taut and retie extra length in control box. 5. Check fan for free rotation and observe that wiring has not been damaged or improperly strained. Electrical Data Voltage Range Compressor Fan Motor Recommended Unit Model Power Supply Min Max RLA LRA QTY RLA Power Wire(mm.2) Ground Wire (mm.2) Field CB (AT) 38LF V/3Ph/50Hz LF V/3Ph/50Hz LF V/3Ph/50Hz LF V/3Ph/50Hz LF V/3Ph/50Hz LF V/3Ph/50Hz

6 Piping Connections / Piping Refer to Physical Data Table for correct piping sizes. The length of refrigerant pipe depends on the unit placement and building structure attempt to run pipes as CONNECTION TO INDOOR PIPING (Flare) CONNECTION TO INDOOR PIPING (Brazing) SHUT-OFF PORT FACTORY-BRAZED TO CONDENSING UNIT SHUT-OFF PORT FACTORY-BRAZED TO CONDENSING UNIT SERVICE PORT (SCHRAEDER) SERVICE PORT (SCHRAEDER) Service Valve (Flare) Service Valve (Blazing) 1. Refrigerant tubing between sections may be made using accessory tubing packages or field-supplied tubing of refrigerant grade, correct size and condition. 2. Refrigerant suction tube must be insulated with closed-cell foam type insulation with a minimum wall thickness of 3/8 in. Failure to properly insulate refrigerant tubes adequately will degrade system performance and efficiency as well as permitting moisture or frost to form on the tubing surfaces during operation. 3. Run refrigerant tubes as directly as possible, avoiding unnecessary turns and bends. 4. If tube bending is necessary, use only copper cutter to cut the copper tube and shape tube with a tube bender so that the tube ends coincide with flare connections. 5. Carefully remove the flare nut fitting from indoor and outdoor sections tubing. 6. Thoroughly clean all tubing connection points to prevent foreign matter from entering the refrigerant circuit. 7. Thread the 2 fittings by hand, making sure the threads fit smoothly and the flare seats evenly against the union. 8. Tighten the 2 fittings securely. 9. Connect piping to the indoor and outdoor section. 10. Evacuate the system at lower 500-micron for at least 30 minutes. 11. Suspend refrigerant tubes so they do not damage insulation on liquid and vapor tubes and do not transmit vibration to structure. Also, when passing refrigerant tubes through walls, seal opening so vibration is not transmitted to structure. Leave some slack in refrigerant tubes between structure and units to absorb vibration. 12. After evacuating the system, turn on both valves at the condensing unit to flow the refrigerant into the system. Outdoor unit contains holding refrigerant charge to operate split system

7 Maintenance Warning! To avoid the possibility of electric shock, before performing any cleaning and maintenance operations always turn off power to the system. If the indoor unit is on a separate switch, be sure it is also disconnected. Ensure that tubing is cool. Beware of rotating fan and energized electrical components. Cleaning coil : Ensure power to unit is disconnected. Wire grilles may be removed simply be lifting grilles upwards so that grille legs clear holes in base pan and then pulling them towards you (Fig. 4). Clean coil with water from ordinary hose at a pressure high enough to clean efficiently. Coils are double row and may be separated carefully and sufficiently be loosening screws at one end of the coil so that dirt may be flushed out towards the outside of both coils. Avoid splashing mud on coil or water onto fan motor. Condensing fan adjustment : The fan should be adjusted by loosening the set screws and moving the fan blade up or down. The final position of the fan relative to the louvers should be as shown in Fig. 5. Condenser fan removal : Shut off power to unit. Open control box cover and remove fan motor wire leads from attached components. Remove fan deck and then the 3 mounting nuts between fan bracket and deck. Remove 3 nuts between motor bracket and motor

8 Wiring Diagram 38LB036SCG, 040SCG, 048SC, 060SC ( 380 ) 38LB(048SC, 060SC) / 38LF(048, 060SC) 38LB007SC (007SC,, 009SC,, 009SC-D, 012SC,,012SC 012SC-D), 38LF(007, 009, 012) ( 380 ) - 8 -

9 Wiring Diagram 38LB015SC ( 380 ) 38LB015SC / 38LF015SC TB N (NEUTRAL) YEL POWER SUPPLY 380V.3-? 50Hz.AC. R S T C YEL BLU T2 T1 IP T3 COMP. GRD CR 1 2 CR 3 4 CR 5 6 CONTROL SUPPLY 220V.50Hz.AC. LPS TB L LEGEND: COMP C CR CH HPS IP LPS OFMC OFM TC TM BLU TB 8 TB 1 2 TM LOGIC BLU OFM BRN WHT OFMC BLU RED RED A1 RED GRN TB 3 1 C BRN YEL YEL TB 4 CH TB 5 HPS GRD COMPRESSOR CONTACTOR CONTROL RELAY CRANKCASE HEATER HIGH PRESSURE SWITCH INTERNAL PROTECTOR LOW PRESSURE SWITCH OUTDOOR FAN MOTOR CAPACITOR OUTDOOR FAN MOTOR THERMOSTAT CONNECTOR SOLID STATE TIMER TERMINALS BLOCK (TB) FIELD WIRING TB 2 TC A B CR A2 YEL COMPONENT ARRANGEMENT CR OFMC 38LB015SC-D 38LB015SC-D ( 380 ) TB TM C L N 8 (PT300148) ITEM NO.39SX0038

10 Attention before operating 1. Please read this installation manual carefully. It contains further important instructions. 2. Do not anything block the air outlet and air inlet of the condensing unit. The refrigeration system may be broken down. 3. Due to temperature of outlet air is higher around degree C; it may be having an effect on environments especially tree, plant, or shrub etc. 4. Make sure that outlet air is moved out from installation area. It must not be return to air inlet. Do not be store until temperature above 42 degree C. The compressor or refrigeration system may be damaged. 5. For safety first, it should be turned off the breaker if the air conditioner does not be used for a long time. 6. If the condensing unit is installed on the ground, make sure that the location is not liable to flooding. 7. After a long use, check the unit fixing for damage. 8. Before cleaning, be sure to stop the operation and turn off the breaker. (As the fan is rotating at high speed, cleaning during operation may cause injury) 9. Do not place a vessel containing water or any object on the condensing unit and do not stand or sit on the condensing unit. 10. The condensing unit should not be installed where normal operation sounds may be objectionable. On either rooftop or ground level installations. Rubber padding can be applied between the base rails and their supports to lesson any transmission of vibration. 11. The fan of condensing unit is the propeller type. It is not suitable for use with duct work. 12. Make sure that the surrounding atmosphere does not contain noxious or dangerous substances such as oil vapors etc. Before inform our call center or inspect the air-conditioner, please check as following Case of Air-conditioner does not work, Disconnect the electrical? Turn off the breaker? Fuse is broken? Low level of the battery show on remote control? The timer function is set on remote control? Case of air-conditioner work but it can not cooling, Fan-coil is unclean? Open the door or the window? Pre-Filter is unclean? The position of louver is unsuitable? Low speed on fan-coil unit? The temperature setting is unsuitable set on remote control? / Carrier (Thailand) Ltd th.fl, 1858/63-74 Bangna-Trad Road Km. 4.5 Bangna Bangkok Tel Fax Carrier reserves the right to make changes in specifications 38LB/38LF_EN_11/2015

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703 TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.

More information

AIR-COOLED CONDENSING UNIT UNITS PRODUCED AFTER JANUARY, 1996 INDEX SCHEMATIC DIAGRAM FIG. NO.

AIR-COOLED CONDENSING UNIT UNITS PRODUCED AFTER JANUARY, 1996 INDEX SCHEMATIC DIAGRAM FIG. NO. wiring diagrams AIR-COOLED CONDENSING UNIT 566D Sizes 120-240 Cancels: New WD 566D.120.1 11/15/96 UNITS PRODUCED AFTER JANUARY, 1996 INDEX UNIT 566D 120-240 ELECTRICAL CHARACTERISTICS (V-Ph-Hz) SCHEMATIC

More information

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13 R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.

More information

38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT

38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT Concepcion Carrier Air conditioning Company Philippines INSTALLATION, START-UP AND SERVICE INSTRUCTIONS 38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT CONTENTS Safety Considerations 1 Complete

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz) DESCRIPTION These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of refrigerant-22 for storage

More information

Installation Instructions

Installation Instructions 24AHA4 Performance Series Air Conditioner with Puron Refrigerant 1-1/2 to 5 Nominal Tons Installation Instructions Fig. 1-24AHA4 A07532 SAFETY CONSIDERATIONS Improper installation, adjustment, alteration,

More information

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS SUNLINE 2000ô MODELS: H5CE090, H3CE120 & H1CE150 7-1/2, 10, & 12-1/2 NOMINAL TONS 9.0-9.5 EER DESCRIPTION These Sunline 2000ô units are completely

More information

WineZone Ceiling Mount Ductless Split 15

WineZone Ceiling Mount Ductless Split 15 WineZone Ceiling Mount Ductless Split 15 Requires an HVAC technician to install and charge with R-22 refrigerant. Easy to install. Unit plugs into wall outlet. Industrial grade unit for longer life. Indoor

More information

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS DLCLRA INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 Fig. 1 - Size 36 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 WIRING...

More information

MODELS E1FB180 & E1FB240

MODELS E1FB180 & E1FB240 SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS INSTALLATION INSTRUCTION Supersedes: 035-16192-000 (0601) 035-16192-001-A-1001 MODELS E1FB180 & E1FB240 GENERAL The outdoor units are completely piped and wired at

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin WCU_O&I 01 June 2003 Condensing Unit Installation and Operating Instructions WCU Air Cooled Condensing Unit Table of Contents Section 1. Section 2. Section 3. Section 4. Section 5. Section 6.

More information

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811 Description These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of Refrigerant R-410A for storage

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions Installation, Start-Up and Service Instructions 38HDF018-036 Duct Free Condensing Units 38HDR018-060 Ducted Condensing Units CONTENTS Page SAFETY CONSIDERATIONS...1 INSTALLATION... 1-10 Step 1 Complete

More information

CHAMPION SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: N4 (778) N4Y (492)

CHAMPION SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: N4 (778) N4Y (492) CHAMPION SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: 550.13-N4 (778) 550.13-N4Y (492) MODELS H2CA480 & 600 035-09563 GENERAL CHAMPION units are designed for outdoor

More information

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS 15 THROUGH 20 NOMINAL TON HB B-0804

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS 15 THROUGH 20 NOMINAL TON HB B-0804 INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS 15 THROUGH 20 NOMINAL TON CONTENTS GENERAL................................. 3 REFERENCE............................... 3 INSPECTION...............................

More information

Installation Instructions

Installation Instructions 38MHR Outdoor Unit Single Zone Ductless System Sizes 09 to 24 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. NOTE: Images are for illustration purposes

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS R 410A Ducted Horizontal Air Conditioner Product Family: HC4A3 Fig. 1 - HC4A3 NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE

More information

Hoshizaki America, Inc.

Hoshizaki America, Inc. Hoshizaki America, Inc. Modular Crescent Cuber Models KM-1340MAH KM-1340MWH KM-1340MRH A Superior Degree of Reliability INSTRUCTION MANUAL www.hoshizaki.com Issued: 8-11-2005 IMPORTANT Only qualified service

More information

PACKAGE AIR CONDITIONER

PACKAGE AIR CONDITIONER PACKAGE AIR CONDITIONER FORM NO. ATZ-206 TZAA- HIGH EFFICIENCY SERIES NOMINAL SIZE 10 TON [35.2 kw] 10 TON MODEL [35.2 kw] This product is shipped with a nitrogen holding charge that must be vented prior

More information

SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS. INSTALLATION INSTRUCTION Supersedes: N1Y (497) N1Y (998) MODELS E2FB090 & E1FB120 GENERAL

SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS. INSTALLATION INSTRUCTION Supersedes: N1Y (497) N1Y (998) MODELS E2FB090 & E1FB120 GENERAL SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS INSTALLATION INSTRUCTION Supersedes: 515.41-N1Y (497) 515.41-N1Y (998) MODELS E2FB090 & E1FB120 035-15410 EFB090 SHOWN 208/230/460 VOLT ONLY 208/230 VOLT ONLY GENERAL

More information

Concealed Ducted Split Series R-407C MBH

Concealed Ducted Split Series R-407C MBH Concealed Ducted Split Series R-407C 4-60 MBH Ducted Split with Hermetic Compressor Tropical 50 Hz For more technical information please visit Table of Contents INTRODUCTION NOMENCLATURE UNIT RATING SUMMARY

More information

SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS. INSTALLATION INSTRUCTION Supersedes: Nothing N1Y (692) MODELS E1FB090 & 120 (50 & 60 HZ) GENERAL

SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS. INSTALLATION INSTRUCTION Supersedes: Nothing N1Y (692) MODELS E1FB090 & 120 (50 & 60 HZ) GENERAL SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS INSTALLATION INSTRUCTION Supersedes: Nothing 515.41-N1Y (692) MODELS E1FB090 & 120 (50 & 60 HZ) 035-09648 EFB090 SHOWN GENERAL Renewal Parts: 208/230/460 VOLT ONLY

More information

Installation Instructions

Installation Instructions PREFERREDT SERIES AIR CONDITIONER WITH PURONR REFRIGERANT 1-1/2 TO 5 NOMINAL TONS Installation Instructions Fig. 1 --- 538A NOTE: Read the entire instruction manual before starting the installation. TABLE

More information

CHS. Product Specifications COMMERCIAL SPLIT SYSTEMS HEAT PUMP UNITS R 410A, 6 10 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

CHS. Product Specifications COMMERCIAL SPLIT SYSTEMS HEAT PUMP UNITS R 410A, 6 10 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE COMMERCIAL SPLIT SYSTEMS HT PUMP UNITS R 410A, 6 10 TONS BUILT TO LAST, SY TO INSTALL AND SERVICE Single stage cooling capacity control on all models All models utilize round copper tube, aluminum plate

More information

DLCSRA. INSTALLATION INSTRUCTIONS Outdoor Unit Ductless Split System Sizes 09 to 36 TABLE OF CONTENTS

DLCSRA. INSTALLATION INSTRUCTIONS Outdoor Unit Ductless Split System Sizes 09 to 36 TABLE OF CONTENTS DLCSRA INSTALLATION INSTRUCTIONS Outdoor Unit Ductless Split System Sizes 09 to 36 NOTES: Read the entire instruction manual before starting the installation. Images are for illustration purposes only.

More information

Installation Instructions

Installation Instructions 40MAQ High Wall Ductless Split System Sizes 09 to 36 Installation Instructions NOTE: Read the entire instruction manual before starting the installation TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS

More information

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS. HB 180 & thru 20 Nominal Tons NOTES, CAUTIONS AND WARNINGS

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS. HB 180 & thru 20 Nominal Tons NOTES, CAUTIONS AND WARNINGS INSTALLATION MANUAL TABLE OF CONTENTS GENERAL.................................... 3 REFERENCE................................. 3 INSPECTION.................................. 4 OPERATION.................................

More information

Installation Instruction

Installation Instruction 40QAC / 38HDR 40QAQ / 38QRR Ceiling---Suspended Duct Free Split System Sizes 018 to 060 Installation Instruction 40QAC, QAQ Unit 38HDR, QRR Unit the environmentally sound refrigerant NOTE: Read the entire

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 183A FILE NO. SA 183A REFERENCE NO. SM Destination Australia SA-183A

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 183A FILE NO. SA 183A REFERENCE NO. SM Destination Australia SA-183A TECHNICAL & SERVICE MANUAL SA 183A FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. SA-183A 1 851 006 96 Destination Australia SA 183A REFERENCE NO. SM700514 IMPORTANT! Please Read Before

More information

50BY, BL. Ÿà Õ µ µ Èß ËÕߪ Õ» å Single-Package Cooling Units 50BY, BL 50BY, BL

50BY, BL. Ÿà Õ µ µ Èß ËÕߪ Õ» å Single-Package Cooling Units 50BY, BL 50BY, BL 50BY, BL Ÿà Õ µ µ Èß ËÕߪ Õ» å Single-Package Cooling Units 50BY, BL 50BY, BL Contents Safety Considerations... 4 Danger... 4 Warning... 4 Installation... 5-6 Air Duct Connection... 6 Electrical Wiring...

More information

Wiring Diagrams. 38ARZ ARS ARD Air-Cooled Condensing Units 50/60 Hz

Wiring Diagrams. 38ARZ ARS ARD Air-Cooled Condensing Units 50/60 Hz Wiring Diagrams 38ARZ007-012 38ARS008-012 38ARD012-024 Air-Cooled Condensing Units 50/60 Hz UNIT 38AR DIAGRAM INDEX VOLTAGE-PHASE-HERTZ LABEL DIAGRAM FIGURE NO. 208/230-3-60 38AK540117 1 or 2* 400/460-3-50/60

More information

Installation Instructions

Installation Instructions 8GXM / 0GXM Multi---Split High---Wall Duct Free Split System 8GXM --- Size 18k, k, and 0k 0GXM --- Size 9k, 1k, and 18k Installation Instructions NOTE: Read the entire instruction manual before starting

More information

Installation Instructions

Installation Instructions Baset Series Heat Pumps with Puronr Refrigerant 1---1/2 To 5 Nominal Tons (Sizes 18 to 60) Installation Instructions NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS

More information

Commercial High-Efficiency Condensing Units

Commercial High-Efficiency Condensing Units FORM NO. A22-193 REV. 3 Supersedes Form No. A22-193 Rev. 2 Commercial High-Efficiency Condensing Units 15 & 20 TON MODEL [52.8 & 70.3 kw] 10 & 12.5 TON MODEL [35.2 & 44.0 kw] 10 THROUGH 20 NOMINAL TON

More information

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features.

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features. Spot Cooling Systems, Inc. 120 Century Drive Suite 00 Carrollton, TX 7006 00-6-776 Operation Manual SCT1B and SCT1B Warning! Improper installation, adjustment, alteration, service, or maintenance can cause

More information

Installation, Operation, and Maintenance Information

Installation, Operation, and Maintenance Information Installation, Operation, and Maintenance Information Air Cooled Condensers 8-2016 Rev 0 Table of Contents General Safety Information 2 Inspection 2 Installation 2 6 Rigging and Assembly 2 Unit Location

More information

TECHNICAL MANUAL CX(E) SPLIT SYSTEMS. Tel: Fax:

TECHNICAL MANUAL CX(E) SPLIT SYSTEMS. Tel: Fax: TECHNICAL MANUAL CX(E) SPLIT SYSTEMS CONTENTS INDEX PART NUMBERS, OPTIONS, UNIT COMBINATIONS, DIMENSIONS & WEIGHTS 3 PERFORMANCE DATA & AIR FLOW 4 SOUND POWER AND SOUND PRESSURE LEVELS 5 ELECTRICAL DATA

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 123A FILE NO. SA 123A REFERENCE NO. SM700513

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 123A FILE NO. SA 123A REFERENCE NO. SM700513 TECHNICAL & SERVICE MANUAL SA 123A FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-123A 1 851 006 95 Australia SA 123A REFERENCE NO. SM700513 IMPORTANT! Please Read Before

More information

Installation Instructions

Installation Instructions 40MBFQ Floor Console Ductless System Sizes 09 to 12 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 DIMENSIONS... 5 CLEARANCES... 5

More information

INSTALLATION MANUAL SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) HB Ton HB Ton HB Ton NOTES, CAUTIONS AND WARNINGS

INSTALLATION MANUAL SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) HB Ton HB Ton HB Ton NOTES, CAUTIONS AND WARNINGS INSTALLATION MANUAL SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) CONTENTS GENERAL................................... 5 SAFETY CONSIDERATIONS.................... 5 AGENCY APPROVALS.........................

More information

Hoshizaki America, Inc.

Hoshizaki America, Inc. Hoshizaki America, Inc. Modular Crescent Cuber Models KM-461MAH KM-461MWH KM-461MRH A Superior Degree of Reliability INSTRUCTION MANUAL www.hoshizaki.com Issued: 2-13-2006 Revised: 1-28-2008 IMPORTANT

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 128S5 FILE NO. SA 128S5 REFERENCE NO. SM700338

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 128S5 FILE NO. SA 128S5 REFERENCE NO. SM700338 TECHNICAL & SERVICE MANUAL SA 128S5 FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-128S5-A 1 851 004 09 General (50Hz) & Europe SA 128S5 REFERENCE NO. SM700338 IMPORTANT!

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS T CLASS TSA Series 6 to 20 Ton AIR CONDITIONERS 6 20 TONS 506147 01 06/11 Supersedes 3/11 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE IMPORTANT The Clean Air Act

More information

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS Concepcion Carrier Air conditioning Company Philippines INSTALLATION MANUAL, START-UP & SERVICE INSTRUCTIONS 38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS CONTENTS: Physical Data and Dimensions........

More information

Hoshizaki America, Inc.

Hoshizaki America, Inc. Hoshizaki America, Inc. Modular Crescent Cuber Serenity Series Model KMS-1400MLH Including Condensing Unit Model SRK-14H/3 A Superior Degree of Reliability INSTRUCTION MANUAL www.hoshizaki.com Issued:

More information

INSTALLER'S GUIDE. ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

INSTALLER'S GUIDE. ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES 11-AC11D2-5 INSTALLER'S GUIDE ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES Models: Condensing Units 2A7A5024-048, 2A7A4018-060, 2A7A2018-060 & 2A7A1018-060 IMPORTANT

More information

UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions

UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions INSPECTION When the equipment is received, all items should be carefully checked against the bill

More information

SELF-CONTAINED FLAKER

SELF-CONTAINED FLAKER Reliability is a beautiful thing TM SELF-CONTAINED FLAKER F-500BAF(-C) INSTRUCTION MANUAL ISSUED: April 13, 1998 REVISED: December 30, 2004 IMPORTANT Only qualified service technicians should attempt to

More information

Reliability is a beautiful thing TM MODULAR FLAKER F-800MAH(-C) F-800MWH(-C) INSTRUCTION MANUAL

Reliability is a beautiful thing TM MODULAR FLAKER F-800MAH(-C) F-800MWH(-C) INSTRUCTION MANUAL Reliability is a beautiful thing TM MODULAR FLAKER F-800MAH(-C) F-800MWH(-C) INSTRUCTION MANUAL ISSUED: FEB. 28, 2001 REVISED: DEC. 11, 2003 IMPORTANT Only qualified service technicians should attempt

More information

MODELS W1LC220, 260 AND 320 STYLE B

MODELS W1LC220, 260 AND 320 STYLE B LIQUID CHILLER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: 570.05-NY (494) 570.05-N3Y (495) MODELS WLC0, 60 AND 30 STYLE B 035-3053 Only -5 and -46 voltage codes GENERAL YORK s WLC Packaged Air-Cooled

More information

Installation Instructions

Installation Instructions 38MGQ Multi-Zone Ductless System Sizes 18, 27, 36 and 48 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

More information

Hoshizaki America, Inc.

Hoshizaki America, Inc. Hoshizaki America, Inc. Modular Crescent Cuber Models KM-501MAH KM-501MWH KM-501MRH A Superior Degree of Reliability INSTRUCTION MANUAL www.hoshizaki.com Issued: 2-13-2006 IMPORTANT Only qualified service

More information

Contour TM Screw Compressors

Contour TM Screw Compressors Contour TM Screw Compressors Semi-Hermetic Compact Operating Instruction SCH1 High Temp Compressors Form No. 99-77 1. Introduction This series of semi-hermetic compact screw compressors is designed for

More information

A/C-HEATER SYSTEM - MANUAL

A/C-HEATER SYSTEM - MANUAL A/C-HEATER SYSTEM - MANUAL 1986 Isuzu Trooper II 1986 A/C-HEATER SYSTEM Isuzu A/C-Heater Systems - Manual P UP, Trooper II * PLEASE READ THIS FIRST * CAUTION: When discharging air conditioning system,

More information

Room Air Conditioner Service and Parts Manual

Room Air Conditioner Service and Parts Manual Cool Dry Temp Mode Room Air Conditioner Service and Parts Manual F Fan Speed hr Timer 0n 0ff Money Saver Fan Only Auto Swing Power CP06 CP08 93011401_01 CONTENTS 1. PREFACE 1.1 SAFETY PRECAUTIONS...2 1.2

More information

Installation Instructions

Installation Instructions Performance Series Heat Pumps with PURONr Refrigerant 1 --- 1/2 to 5 Nominal Tons Installation Instructions Fig. 1 --- A07532 NOTE: Read the entire instruction manual before starting the installation.

More information

Hoshizaki America, Inc.

Hoshizaki America, Inc. Hoshizaki America, Inc. Stackable Crescent Cuber Models KM-1301SAJ/3, SWJ/3, SRJ/3 KM-1601SAJ/3, SWJ/3, SRJ/3 KM-1900SAJ/3, SWJ/3, SRJ/3 KM-2100SWJ3, SRJ3 KM-2500SWJ3, SRJ3 A Superior Degree of Reliability

More information

WCH5**4. Product Specifications

WCH5**4. Product Specifications HEAT PUMP HIGH EFFICIENCY 15 SEER 1-1/2 THRU 5 TONS SPLIT SYSTEM ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 208 / 230 Volt, 1- phase, 60 Hz This product has been designed and manufactured to meet ENERGY

More information

AHG**-0B Series Hydronic Air Handling Units

AHG**-0B Series Hydronic Air Handling Units HEAT CONTROLLER, INC. Installation, Operation and Maintenance Manual Installation, Operation and Maintenance Manual AHG**-0B Series Hydronic Air Handling Units HEAT CONTROLLER, INC. 1900 Wellworth Ave.,

More information

INSTALLATION MANUAL AFFINITY SERIES SINGLE PACKAGE AIR CONDITIONERS ELECTRIC/ELECTRIC, AIR-COOLED. MODELS: D1EB036 thru Thru 5 Ton (10 SEER)

INSTALLATION MANUAL AFFINITY SERIES SINGLE PACKAGE AIR CONDITIONERS ELECTRIC/ELECTRIC, AIR-COOLED. MODELS: D1EB036 thru Thru 5 Ton (10 SEER) INSTALLATION MANUAL CONTENTS GENERAL...................................... 3 INSPECTION.................................... 3 INSTALLATION.................................. 3 REFERENCE....................................

More information

INSTALLATION MANUAL - 50 Hz

INSTALLATION MANUAL - 50 Hz INSTALLATION MANUAL - 50 Hz SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) CONTENTS GENERAL................................... 5 SAFETY CONSIDERATIONS.................... 5 AGENCY APPROVALS.........................

More information

Installation and Start-Up Instructions

Installation and Start-Up Instructions 52VCR,VER,VQR,VWR09-24 Vertical Packaged Terminal Air Conditioners Cooling Only Units, Heat Pump Units, Electric Heat Units, and Hot Water Heat Units Installation and Start-Up Instructions CONTENTS Page

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 2016 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS Elite Series XC16 Units AIR CONDITIONER 507161-01 8/2016 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE General This

More information

INSTALLATION MANUAL R-22/R-407C OUTDOOR SPLIT-SYSTEM AIR CONDITIONING MODELS: GCGA SERIES 1.5 TO 6.3 TONS 1 & 3 PHASE LIST OF SECTIONS LIST OF FIGURES

INSTALLATION MANUAL R-22/R-407C OUTDOOR SPLIT-SYSTEM AIR CONDITIONING MODELS: GCGA SERIES 1.5 TO 6.3 TONS 1 & 3 PHASE LIST OF SECTIONS LIST OF FIGURES INSTALLATION MANUAL R-22/R-407C OUTDOOR SPLIT-SYSTEM AIR CONDITIONING MODELS: GCGA SERIES 1.5 TO 6.3 TONS 1 & 3 PHASE GENERAL..............................................1 SAFETY................................................1

More information

National Comfort Products 539 Dunksferry Road Bensalem, PA (215) Fax: (215)

National Comfort Products 539 Dunksferry Road Bensalem, PA (215) Fax: (215) National Comfort Products 539 Dunksferry Road Bensalem, PA 19020 (215) 244-1400 1-800-523-7138 Fax: (215) 244-9579 R410a SPLIT-SYSTEM CONDENSING UNIT INSTALLATION INSTRUCTIONS 1000 3000 4000 SERIES 1.

More information

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies Pakistan s Largest Manufacturers of Air-Conditioners PACKAGE TYPE UNIT FOR MOBILE APPLICATIONS Provides Turnkey Projects Conceptual Planning to Commissioning of HVACR Projects THE LARGEST MANUFACTURER

More information

40 RM/RMS Packaged Air-Handling Units

40 RM/RMS Packaged Air-Handling Units ConcepcionCarrier Air conditioning Company Philippines 40 RM/RMS 008034 Packaged AirHandling Units INSTALLATION MANUAL, STARTUP & SERVICE INSTRUCTIONS Contents Page Page Safety Considerations 1 40RM Physical

More information

15 SEER SINGLE- PACKAGED HEAT PUMP SYSTEM WITH PURON

15 SEER SINGLE- PACKAGED HEAT PUMP SYSTEM WITH PURON 7D- -A EVOLUTIONr 15 SEER SINGLE-PACKAGED HEAT PUMP SYSTEM WITH PURONr (R-410A) REFRIGERANT SINGLE PHASE 2-5 NOMINAL TONS (SIZES 24-) Fig. 1 - Unit 7D - -A Product Data A09032 Single-Packaged Products

More information

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with non authorized factory parts voids all warranty

More information

Installation Instructions

Installation Instructions 40MAQ / 38MAQ 619PB / 538PR High---Wall Ductless Split System Sizes 09 to 30 Installation Instructions TABLE OF CONTENTS PAGE PARTS LIST... 2 SAFETY CONSIDERATIONS... 3 SYSTEM REQUIREMENTS... 4 DIMENSIONS...

More information

High Ambient / High Efficiency Series. R - 410a. 50Hz. Ducted Split Air Conditioners (5.0 kw kw)

High Ambient / High Efficiency Series. R - 410a. 50Hz. Ducted Split Air Conditioners (5.0 kw kw) High Ambient / High Efficiency Series R - 410a 50Hz Ducted Split Air Conditioners (5.0 kw - 17.5 kw) ISO 9001 : 2008 ISO 14001 : 2004 ISO 18001 : 2007 R - 410a 50Hz Introduction: Established in the year

More information

Technical Data Ducted Three Phase Split System Air Conditioner

Technical Data Ducted Three Phase Split System Air Conditioner ENERGY EFFICIENT ISD / OSA 2 Technical Data Ducted Three Phase Split System Air Conditioner EXTRA LONG LIFE EPOXY COATED OUTDOOR COIL Nominal Cooling Capacity 26.5 kw (Total) JUNE 4 ISD / OSA 2 DUCTED

More information

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) CS*/CD*/CP* Series Air Cooled Condensing Units Operating and Installation Manual CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) TABLE OF CONTENTS I. Receipt of Equipment 2 II. Piping...4 III. System

More information

Horizontal/Side Discharge Condensing Units

Horizontal/Side Discharge Condensing Units INSTALLATION, OPERATION & MAINTENANCE MANUAL Horizontal/Side Discharge Condensing Units Models CMA12SD-0 CMA18SD-1 CMA24SD-1 CMA30SD-1 CMA36SD-1 CMA48SD-1 517.787.2100 www.marsdelivers.com Horizontal/Side

More information

Wiring Diagrams DIAGRAM INDEX

Wiring Diagrams DIAGRAM INDEX 50TFF004-014 Single Package Rooftop Electric Cooling Units Wiring Diagrams DIAGRAM INDEX UNIT LABEL DIAGRAM Unit 50TFF Voltage-Phase-Hertz Type Label Diagram Figure No. 208/230-1-60 Schematic/Component

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS R 410A Ducted Horizontal Heat Pump Product Family: HC4H3 Figure 1 - HC4H3 NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY

More information

Installation Instructions

Installation Instructions 40MBFQ Floor Console Ductless System Sizes 09 to 58 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 WIRING... 4 DIMENSIONS... 5 CLEARANCES...

More information

MODELS B1PA024, 030 AND 036

MODELS B1PA024, 030 AND 036 STELLAR 2000 SINGLE PACKAGE HEAT PUMPS INSTALLATION INSTRUCTION Supersedes: 511.26-N1Y (892) 511.26-N1Y (893) MODELS B1PA024, 030 AND 036 035-11622 GENERAL YORK Model B1PA units are factory assembled heat

More information

Installation Instructions

Installation Instructions 38MPRA Outdoor Unit Single Zone Ductless System Sizes 09 to 12 Installation Instructions NOTES: Read the entire instruction manual before starting the installation. Images are for illustration purposes

More information

installation, start-up and service instructions

installation, start-up and service instructions installation, start-up and service instructions MULTI-SPLIT, DUCT-FREE OUTDOOR COOLING UNITS Cancels: New 538S Sizes 024,048 2 and 4 Tons II 538S-24-1 2/15/96 IMPORTANT READ BEFORE INSTALLING 1. Read and

More information

Hoshizaki America, Inc.

Hoshizaki America, Inc. Hoshizaki America, Inc. Self-Contained Crescent Cuber Models KM-255BAH KM-255BWH A Superior Degree of Reliability INSTRUCTION MANUAL www.hoshizaki.com Issued: 10-4-2006 IMPORTANT Only qualified service

More information

Installation Instructions

Installation Instructions 25HHA4 Performance Series Heat Pump with Puron Refrigerant 1-1/2 to 5 Nominal Tons Installation Instructions Fig. 1-25HHA4 A07532 SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service,

More information

3 to 5 Tons. AIR CONDITIONERS 2scu13. Dry Charge Split System - 60 HZ PRODUCT SPECIFICATIONS. 2 scu 13 lc 1 36 t - 1 a MODEL NUMBER IDENTIFICATION

3 to 5 Tons. AIR CONDITIONERS 2scu13. Dry Charge Split System - 60 HZ PRODUCT SPECIFICATIONS. 2 scu 13 lc 1 36 t - 1 a MODEL NUMBER IDENTIFICATION AIR CONDITIONERS 2scu3 PRODUCT SPECIFICATIONS Dry Charge Split System - 60 HZ Bulletin No. 20644 May 204 Supersedes September 203 3 to 5 Tons MODEL NUMBER IDENTIFICATION 2 scu 3 lc 36 t - a Refrigerant

More information

MODULAR CRESCENT CUBER

MODULAR CRESCENT CUBER Reliability is a beautiful thing TM MODULAR CRESCENT CUBER KMD-700MAH KMD-700MWH KMD-700MRH KMD-900MAH KMD-900MWH KMD-900MRH INSTRUCTION MANUAL ISSUED: APRIL 24, 2003 REVISED: JAN. 3, 2008 IMPORTANT Only

More information

INSTALLATION AND OPERATING INSTRUCTIONS

INSTALLATION AND OPERATING INSTRUCTIONS INSTALLATION AND OPERATING INSTRUCTIONS HIGH-EFFICIENCY CONDENSING UNITS RAWD- 6 1 2 & 7 1 2 TON RAWE - 6 1 2 & 7 1 2 TON! RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION!! WARNING

More information

Hoshizaki America, Inc.

Hoshizaki America, Inc. Hoshizaki America, Inc. Modular Crescent Cuber Models KM-900MAH50 KM-900MRH50 A Superior Degree of Reliability INSTRUCTION MANUAL www.hoshizaki.com Issued: 6-25-2008 IMPORTANT Only qualified service technicians

More information

Refrigeration System with a Capillary Tube and a Thermostat

Refrigeration System with a Capillary Tube and a Thermostat Exercise 2-1 Refrigeration System with a Capillary Tube Part A: REFRIGERATION CIRCUIT OBJECTIVE When you have completed this part, a refrigeration circuit using a capillary tube as a metering device will

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin ACU_O&I 02 August 2016 Condensing Unit Installation and Operating Instructions ACU Air Cooled Condensers Table of Contents Section 1. General Information... 2 Section 2. Refrigeration Piping...

More information

Instruction Manual. Modular Crescent Cuber Serenity Series. Models KMS-2000MLH. Including Condensing Unit Models SRK-20H/3. hoshizakiamerica.

Instruction Manual. Modular Crescent Cuber Serenity Series. Models KMS-2000MLH. Including Condensing Unit Models SRK-20H/3. hoshizakiamerica. Instruction Manual Modular Crescent Cuber Serenity Series Models KMS-2000MLH Including Condensing Unit Models SRK-20H/3 hoshizakiamerica.com Issued: 4-29-2011 Revised: 8-15-2017 WARNING Only qualified

More information

Nominal Circuit Capacities: 9,000 12,000 18,000 & 24,000 Btuh units.

Nominal Circuit Capacities: 9,000 12,000 18,000 & 24,000 Btuh units. Nominal Circuit Capacities: 9,000 12,000 18,000 & 24,000 Btuh units. Enviromaster International LLC 5780 Success Dr. Rome, NY 13440 An ISO 9001-2000 Certified Company P/N# 240006458 Rev. 1.1 [04/07] EMI

More information

Instruction Manual. Modular Crescent Cuber Models KM-340MAH, MWH KM-515MAH, MWH, MRH KM-600MAH KM-650MAH, MWH, MRH KM-901MAH, MWH, MRH/3

Instruction Manual. Modular Crescent Cuber Models KM-340MAH, MWH KM-515MAH, MWH, MRH KM-600MAH KM-650MAH, MWH, MRH KM-901MAH, MWH, MRH/3 Instruction Manual Modular Crescent Cuber Models KM-340MAH, MWH KM-515MAH, MWH, MRH KM-600MAH KM-650MAH, MWH, MRH KM-901MAH, MWH, MRH/3 hoshizakiamerica.com Issued: 4-28-2015 Revised: 8-7-2017 WARNING

More information

R-410A MODELS: YD360 Thru Ton 60 Hertz

R-410A MODELS: YD360 Thru Ton 60 Hertz R-410A MODELS: YD360 Thru 600 30-50 Ton 60 Hertz Nomenclature..................................... 2 General.......................................... 2 Renewal Parts.....................................

More information

2 shp 13 lc 1 36 t - 1 a

2 shp 13 lc 1 36 t - 1 a HEAT PUMPs 2SHP3 PRODUCT SPECIFICATIONS Dry Charge Split System - 60 HZ Bulletin No. 20645 July 203 Supersedes June 202 3 to 5 Tons MODEL NUMBER IDENTIFICATION 2 shp 3 lc 36 t - a Refrigerant Type 2 =

More information

EarthLinked SW Series Compressor Unit R-410A Quik-Start Instructions

EarthLinked SW Series Compressor Unit R-410A Quik-Start Instructions EarthLinked SW Series Compressor Unit R-410A Quik-Start Instructions CONTENTS PAGE Pre-Installation 3 Placement & Mechanical Information 4 System Application Options 10 Antifreeze Protection 14 Electrical

More information

SINGLE-PACKAGE ROOFTOP HEAT PUMP UNITS INDEX. VOLTAGE (3 Ph, 60 Hz) ACCESSORIES

SINGLE-PACKAGE ROOFTOP HEAT PUMP UNITS INDEX. VOLTAGE (3 Ph, 60 Hz) ACCESSORIES wiring diagrams SINGLE-PACKAGE ROOFTOP HEAT PUMP UNITS Cancels: New 542J Sizes 150, 180 12-1/2 and 15 Tons WD 542J.150.1 7/15/96 UNIT 542J 150 180 LABEL DIAGRAM TYPE Component Arrangement Schematic Component

More information

INSTRUCTIONS! DO NOT DISCARD!

INSTRUCTIONS! DO NOT DISCARD! INSTRUCTIONS! DO NOT DISCARD! CAUTION! Do NOT install where injury might occur due to Moving parts, Sharp corners, Hot surfaces or electrical components d N0417 Page 1 of 10 INSTALLATION INSTRUCTIONS CAUTION

More information

INSTALLATION AND COMMISSIONING MANUAL. Neos 100S Integra 20X, 30S, 35X, 40X, 50X

INSTALLATION AND COMMISSIONING MANUAL. Neos 100S Integra 20X, 30S, 35X, 40X, 50X Installation Truck Refrigeration & Commissioning Manual: INSTALLATION AND COMMISSIONING MANUAL for Neos 100S Integra 20X, 30S, 35X, 40X, 50X Direct Drive Refrigeration Units 2017 Carrier Corporation Printed

More information

Air Conditioning Operation and Troubleshooting Matt Dunham

Air Conditioning Operation and Troubleshooting Matt Dunham Air Conditioning Operation and Troubleshooting Matt Dunham Major Components (10 Minutes) Compressor heart of the system, causes refrigerant to flow by increasing the pressure of the refrigerant Metering

More information

Product Data. Features/Benefits. 19XB Positive Pressure Storage System

Product Data. Features/Benefits. 19XB Positive Pressure Storage System Product Data 19XB Positive Pressure Storage System 19XB028 Copyright 1992 Carrier Corporation 19XB052 Carrier s Positive Pressure Storage (PPS) System ensures the critical conservation of refrigerants

More information

INSTALLATION INSTRUCTIONS FOR MOUNTING KIT

INSTALLATION INSTRUCTIONS FOR MOUNTING KIT RV Products Division INSTALLATION INSTRUCTIONS FOR 8330-5501 MOUNTING KIT 8330-752 CONTROL BOX KIT (12 VDC COOL ONLY) 9330B755 CONTROL BOX KIT (12 VDC HEAT/COOL) 8530-750 CONTROL BOX KIT (24 VAC COOL ONLY)

More information