UMC 2012 (Chapter 9): Item # 86. gas utilization appliances having an operating temperature exceeding 500 F (260 C). [NFPA 54:9.1.8.

Size: px
Start display at page:

Download "UMC 2012 (Chapter 9): Item # 86. gas utilization appliances having an operating temperature exceeding 500 F (260 C). [NFPA 54:9.1.8."

Transcription

1 UMC 2012 (Chapter 9): Item # 86 Dave Levanger Chair, Technical Correlating Committee The following is recommended by the Technical Correlating Committee (see TCC Items of Discussion Report Chapter 9) Building Structural Members Gas Utilization Appliances (exceeding 500 F degrees). Structural members of a building shall not pass through gas utilization appliances having an operating temperature exceeding 500 F (260 C). [NFPA 54: ] Gas Utilization Appliances (equal to or less than 500 F degrees). Structural members passing through gas utilization appliances having an operating temperature of 500 F (260 C) or less shall be of noncombustible material. Building columns, girders, beams, or trusses shall not be installed within appliances, unless insulation and ventilation are provided to avoid deterioration in strength and linear expansion of the building structure in either a vertical or a horizontal direction. [NFPA 54: ] Support of Gas Utilization Appliances. Gas utilization appliances shall be furnished either with load-distributing bases or with an approved number of supports to prevent damage to either the building structure or appliance. [NFPA 54: ] Structural Capacity. At the locations selected for installation of the gas utilization appliance, the dynamic and static load-carrying capacities of the building structure shall be checked to determine whether they are adequate to carry the additional loads. The appliance shall be supported and shall be connected to the piping so as not to exert undue stress on the connections. [NFPA 54: ] Flammable Vapors. Gas appliances shall not be installed in areas where the open use, handling, or dispensing of flammable liquids occurs, unless the design, operation, or installation reduces the potential of ignition of the flammable vapors. Gas utilization appliances installed in accordance with Section or Section shall be considered to be in accordance with the intent of this provision. [NFPA 54:9.1.9] Access to Appliances on Roofs Appliances located on roofs or other elevated locations shall be accessible. [NFPA 54-09: ] Access to Equipment on Roofs General. Equipment and appliances located on roofs or other elevated locations shall be accessible. [NFPA 54: ] The technical correlating committee is submitting these proposals as part of their responsibility to resolve conflicts, achieve correlation between the UPC and UMC, along with correcting errors and omissions. For informational purposes the code language from the UPC is shown as follows based on action taken by the TCC: Building Structural Members Gas Utilization Appliances (exceeding 500 F degrees). Structural members of a building shall not pass through gas utilization appliances having an operating temperature exceeding 500 F (260 C). [NFPA 54: ] Gas Utilization Appliances (equal to or less than 500 F degrees). Structural members passing through gas utilization appliances having an operating temperature of 500 F (260 C) or less shall be of noncombustible material. Building columns, girders, beams, or trusses shall not be installed within appliances, unless insulation and ventilation are provided to avoid deterioration in strength and linear expansion of the building structure in either a vertical or a horizontal direction. [NFPA 54: ] 201

2 Support of Gas Utilization Appliances. Gas utilization appliances shall be furnished either with loaddistributing bases or with a sufficient an approved number of supports to prevent damage to either the building structure or appliance. [NFPA 54: ] Structural Capacity. At the locations selected for installation of the gas utilization appliance, the dynamic and static load-carrying capacities of the building structure shall be checked to determine whether they are adequate to carry the additional loads.the appliance shall be supported and shall be connected to the piping so as not to exert undue stress on the connections. [NFPA 54: ] Flammable Vapors. Gas appliances shall not be installed in areas where the open use, handling, or dispensing of flammable liquids occurs, unless the design, operation, or installation reduces the potential of ignition of the flammable vapors. Gas utilization appliances installed in compliance accordance with Sections , , or through Section shall be considered to comply be in accordance with the intent of this provision. [NFPA 54:9.1.9] Access to Appliances on Roofs Gas utilization aappliances located on roofs or other elevated locations shall be accessible. [NFPA 54: ] The TCC has the responsibility to resolve conflicts and achieve correlation among the recommendations of the TCs. The TCC shall have the authority to choose between alternative text recommended by the TC, but only as necessary for correlation, consistency, and the correction of errors and omissions in accordance with Section 3-4 of the Regulations Governing Committee Projects. Actions taken on UMC Item 86 for building structural members and UPC Items 80 and for building structural members resulted in a conflict between the codes. In order to correlate language the following Technical Correlating Committee proposed action to the UMC is shown as follows: Building Structural Members Gas Utilization Appliances (exceeding 500 F degrees). Structural members of a building shall not pass through gas utilization appliances having an operating temperature exceeding 500 F (260 C). [NFPA 54: ] Gas Utilization Appliances (equal to or less than 500 F degrees). Structural members passing through gas utilization appliances having an operating temperature of 500 F (260 C) or less shall be of noncombustible material. Building columns, girders, beams, or trusses shall not be installed within appliances, unless insulation and ventilation are provided to avoid deterioration in strength and linear expansion of the building structure in either a vertical or a horizontal direction. [NFPA 54: ] (renumber remaining sections) Flammable Vapors. Gas appliances shall not be installed in areas where the open use, handling, or dispensing of flammable liquids occurs, unless the design, operation, or installation reduces the potential of ignition of the flammable vapors. Gas utilization aappliances installed in accordance with Section or Section shall be considered to be in accordance with the intent of this provision. [NFPA 54:9.1.9] General. Equipment and aappliances located on roofs or other elevated locations shall be accessible. [NFPA 54: ] 202

3 TCC TCC COMMITTEE STATEMENT: The code language in Sections and of the UMC is being deleted to provide correlation with Sections and of the UPC. The term gas utilization is being deleted from Section of the UMC to correlate with Section of the UPC. The code language of Equipment and is being deleted from Section of the UMC to correlate with Section of the UPC. The following proposed action moves forward as approved by the TCC and supersedes the recommendation from the UMC TC for action taken on Section on Building Structural Members, Section on Flammable Vapors, and Section on general requirement for Access to Equipment on Roofs. 203

4 UMC 2012 (902.2): Item # UMC Technical Committee Proposal Type of Gas(es). It shall be determined whether the appliance has been designed for use with the gas to which it will be connected. The appliance shall be connected to the fuel gas for which it was designed. No attempt shall be made to convert the appliance from the gas specified on the rating plate for use with a different gas without consulting the installation instruction, the serving gas supplier, or the appliance manufacturer for complete instructions. [NFPA 54:9.1.3] This revision provides an enforceable code language that coordinates the UMC with NFPA

5 UMC 2012 (220.0, 903.3, 904.2, 903.5): Item # UMC Technical Committee Proposal ROOM LARGE IN COMPARISON WITH SIZE OF EQUIPMENT A room having a volume of at least twelve (12) times the total volume of a furnace or air-conditioning appliance and at least sixteen (16) times the total volume of a boiler. Total volume of the appliance is determined from exterior dimensions and includes fan compartments and burner vestibules when used. When the actual ceiling height of a room is greater than eight (8) feet (2,438 mm), the volume of the room is figured on the basis of a ceiling height of eight (8) feet (2,438 mm) (C) Where the room size in comparison with the size of the appliance is to be calculated, the total volume of the appliance is determined from exterior dimensions and is to include fan compartments and burner vestibules, where used. Where the actual ceiling height of a room is greater than eight (8) feet (2,438 mm), the volume of the room is figured on the basis of a ceiling height of eight (8) ft. (2,438 mm). [NFPA 54:10.1.3] Clearances for Indoor Installation. The installation of air-conditioning appliances shall comply with the following requirements: (A) Listed air-conditioning appliances installed in rooms that are large in comparison with the size of the appliance shall be installed with clearances per the terms of their listing and the manufacturer s instructions. (B) Air-conditioning appliances installed in rooms that are NOT large (such as alcoves and closets) in comparison with the size of the equipment shall be listed for such installations and installed in accordance with the manufacturer s instructions. Listed clearances shall not be reduced by the protection methods described in Table 5-3, regardless of whether the enclosure is of combustible or noncombustible material. (B)(C) Unlisted air-conditioning appliances shall be installed with clearances from combustible material of not less than eighteen (18) inches (457 mm) above the appliance and at the sides, front, rear, and nine (9) inches (229 mm) from the draft hood and in accordance with the manufacturer s installation instructions Clearance. (A) Listed central heating furnaces and low-pressure boilers installed in rooms that are large in comparison with the size of the appliance shall be installed with clearances per the terms of their listings and the manufacturer s instructions. (See Sections and for definition.) [NFPA 54: ] (B) Central-heating furnaces and low-pressure boilers installed in rooms that are NOT large (such as alcoves and closets) in comparison with the size of the appliance shall be listed for such installations. Listed clearances shall not be reduced by the protection methods described in Table 5-3 and illustrated in Figures 9-1(a) through 9-1(c), regardless of whether the enclosure is of combustible or noncombustible material. [NFPA 54: ] (B)(C) Unlisted central-heating furnaces and low pressure boilers installed in rooms that are large in comparison with the size of the appliance shall be installed with clearances from combustible material not less than those specified in Table 9-1 and such reduction is allowed by the manufacturer installation instructions. [NFPA 54: ] (C)(D) Listed and unlisted central-heating furnaces and low-pressure boilers (listed and unlisted) installed in rooms that are large in comparison with the size of the appliance shall be permitted to be installed with reduced clearances to combustible material provided that the combustible material or appliance is protected as described in Table 5-3. [NFPA 54: ] Furnace Plenums and Air Ducts. A furnace plenum supplied as a part of the air-conditioning appliance shall be installed in accordance with the manufacturer s instructions. Where a furnace plenum is not supplied with the appliance, any fabrication and installation instructions provided by the manufacturer shall be followed. The method of connecting supply and 205

6 return ducts shall facilitate proper circulation of air. Where the air conditioner is installed within an enclosure the installation shall comply with (D) [NFPA 54:10.2.5] Revise the title of Table 9-1 to read: Clearances to Combustible Material for Unlisted Furnaces, Boilers, and Air Conditioners Installed in Rooms That Are Large in Comparison with the Size of Appliances. [NFPA 54: Table (a)] The use of the term Room Large in Comparison with Size of Appliance originated for high input air-conditioning, boiler and furnaces were that were either unlisted or where designed in a world where today s federal energy efficiency laws were not enacted. Modern gas-fired HVAC equipment is more efficient and has much lower heat losses through their jackets. Therefore the code s current requirements for the size of the room in which they can be installed have also changed. The concept of room large in comparison with size of appliance has out lived its intended usage and is being misused to determine a closet size. The proposal will delete the term and coverage from the code. Unlisted appliances will not be allowed in such locations (1.4 Equivalency could still be used). Listed appliances would be required to be installed with clearances in accordance with the manufacturer s instructions. The code will continue to require the current minimum clearances for unlisted appliances. These revised code requirements are consistent with how the code treats all other types of appliances. Clearance to combustibles for listed appliances are revised to not be in conflict with the manufacturers installation instructions. VOTING RESULTS: AFFIRMATIVE: 16, NEGATIVE: 4, NOT RETURNED: 1 Nikravi EXPLANATION OF NEGATIVE: ADLER, MACELLAIO, MANN: These sections provide prescriptive direction that clarifies the intent of the code or more precisely states the intent. FEEHAN: These sections supply prescriptive direction that clarifies the intent of the code. The current language is necessary as the term Room Large in Comparison with Size of Appliance is used to provide requirements for appliances built on site that will not have manufacturer s installation instructions for clearances. Appliance built on site such as tile manufacturing kilns. 206

7 UMC 2012 (904.2): Item # UMC Technical Committee Proposal (H) Listed central heating furnaces shall have the clearance from supply ducts within three (3) feet (914 mm) of the furnace plenum be not less than that specified from the furnace plenum. No clearance is necessary beyond this distance. Supply air ducts connecting to listed central heating furnaces shall have the same minimum clearance to combustibles as required for the furnace supply plenum for a distance of not less than 3 ft from the supply plenum. Clearance is not required beyond the 3 ft distance [NFPA 54: ] (I) Unlisted central heating furnaces with temperature limit controls that cannot be set higher than 250ºF (121ºC) shall have the clearance from supply duct within six (6) feet (1,829 mm) of the furnace plenum be not less than six (6) inches (150 mm). No clearance is necessary beyond this distance. Supply air ducts connecting to unlisted central heating furnaces equipped with temperature limit controls with a maximum setting of 250 F shall have a minimum clearance to combustibles of 6 in. for a distance of not less than 6 ft from the furnace supply plenum. Clearance is not required beyond the 6 ft distance. [NFPA 54: ] The revision clarifies clearances to combustible materials for listed central heating furnaces and unlisted central heating furnaces. 207

8 UMC 2012 (904.8): Item # UMC Technical Committee Proposal Refrigeration Coils. The installation of refrigeration coils shall comply with the following requirements: [NFPA 54:10.3.8] (A) A refrigeration coil shall not be installed in conjunction with a forced-air furnace where circulation of cooled air is provided by the furnace blower, unless the blower has sufficient capacity to overcome the external static resistance imposed by the duct system and cooling refrigeration coil and at the air flow rate throughput necessary for heating or cooling, whichever is greater. [NFPA 54:10.3.8(1)] (B) Furnaces shall not be located upstream from cooling units refrigeration coils, unless the cooling unit refrigeration coil is designed or equipped so as not to develop excessive temperature or pressure. [NFPA 54:10.3.8(2)] (remaining text unchanged) The proposed text provides editorial revisions for clarity. The term refrigeration is substituted for cooling unit for consistency, and flow rate is substituted for throughput. 208

9 UMC 2012 ( ): Item # 87 Michael Giordano Clark County, Nevada Work Surface. A level working platform or grade surface not less than thirty (30) inches (760 mm) by thirty (30) inches (760 mm) shall be provided in front of the service side of the appliance. [NFPA 54:9.5.2] Exception: A working platform need not be provided where the furnace can be serviced from the required access opening. The furnace service side shall not exceed 12 inches (305 mm) from the access opening. The problem is furnaces are being installed approximately 6 inches to 24 inches from the access opening. When distances exceed 12 inches it is difficult to service depending on service technician and ladder size. In addition the 24 inches in front of the service side is being used to sit on when unable to service from ladder. Per Section , 30 inches is required in depth and width in front of the entire fire box side. If we require a maximum distance this would reduce any safety issues when servicing furnaces in attics off ladders. 209

10 UMC 2012 ( , ): Item # 88 Ted Lemoff NFPA Work Surface Platform. A level working platform or grade surface not less than thirty (30) inches (760 mm) by thirty (30) inches (760 mm) shall be provided in front of the service side of the appliance. [NFPA 54:9.5.2] Mounting on Combustible Floor. (B2) Floor-mounted food service appliances that is not listed for mounting on a combustible floor shall be mounted in accordance with Section or be mounted in accordance with one of the following: [NFPA 54: ] (1) Where the appliance is set on legs that provide not less than eighteen (18) in.ches (460 mm) open space under the base of the appliance or where it has no burners and no portion of any oven or broiler within eighteen (18) in.ches (460 mm) of the floor, it shall be permitted to be mounted on a combustible floor without special floor protection, provided there is at least not less than one sheet metal baffle between the burner and the floor. [NFPA 54: (1)] (portion of text not shown remains unchanged) Mounting Installation on Noncombustible Floor. Listed floor-mounted food service appliances that are designed and marked, For use only in non-combustible locations, shall be mounted installed on floors of noncombustible construction with noncombustible flooring and surface finish and with no combustible material against the underside thereof, or on noncombustible slabs or arches having no combustible material against the underside thereof. Such construction shall in all cases extend not less than twelve (12) inches (300 mm) beyond the appliance on all sides. [NFPA 54: ] This change provides consistency with NFPA and an editorial revision to use a more appropriate term for clarity. COMMITTEE ACTION: Accept as Amended by the TC Amend proposal as follows: Work Surface Platform. A level working platform or grade surface not less than 30 inches (760 mm) by 30 inches (760 mm) shall be provided in front of the service side of the appliance. [NFPA 54-06:9.5.2] COMMITTEE STATEMENT: The modification provides an option for an appliance that does not require a platform but it requires a work area. For example, appliances located under floor spaces. 210

11 UMC 2012 (910.1, 910.3): Item # 89 Ted Lemoff NFPA Revised text as follows: Application. Direct gas-fired industrial air heaters of the recirculating type shall be designed and certified to be in compliance with the Standard for Recirculating Direct Gas-Fired Industrial Air Heaters, ANSI Z Unlisted direct gas-fired industrial air heaters of the recirculating type shall not be installed. [NFPA 54:10.9.1] Installation. Installation of direct gas-fired industrial air heaters shall comply with the following requirements: [NFPA 54:10.9.3] (A1) Recirculating direct gas-fired industrial air heaters shall be installed in accordance with the manufacturer s instructions. [NFPA 54:10.9.3(1)] (B2) Recirculating direct gas-fired industrial air heaters shall be installed only in industrial or commercial occupancies. [NFPA 54:10.9.3(2)] (C) Recirculating direct gas-fired industrial air heaters shall be permitted to provide fresh air ventilation only for the amount that exceeds the minimum ventilation air specified on the heater s rating plate to maintain the combustion level created by the heater in the space being served by the heater below 25 ppm for carbon monoxide, 3 ppm for nitrogen dioxide, and 5000 ppm for carbon dioxide. Where gas-powered fork trucks or other fossil-fueled appliance are utilized in the conditioned space, additional ventilation requirements for the facility must be addressed separately. [NFPA 54:10.9.3(3)] (D) Recirculating direct gas-fired industrial air heaters shall be provided with access for removal of burners; replacement of motors, controls, filters, and other working parts; and for adjustment and lubrication of parts requiring maintenance. [NFPA 54:10.9.3(4)] This proposed change revises the coverage of recirculating direct gas-rired industrial air heaters to require all units to be listed, as was done in the 1996 edition of NFPA 54. Previously, requirement would have allowed unlisted units to be used if they met key safety criteria similar to the listing standard. As these units have a greater possibility of increased levels of carbon monoxide in building, only listed units should be used. 211

12 UMC 2012 (910.5, ): Item # 90 Ted Lemoff NFPA Air Supply. Ventilation air to the recirculating direct gas-fired industrial air heater shall be ducted directly from outdoors. Air to the recirculating direct gas-fired industrial air heater in excess of the minimum ventilation air specified on the heater s rating plate shall be taken from the building, ducted directly from outdoors, or a combination of both. Where outside outdoor air dampers or closing louvers are used, they shall be verified to be in the open position prior to main burner operation. [NFPA 54:10.9.5] Venting. (A) Line Gas Pressure Regulators. (1) An independent vent to the outside of the building, sized in accordance with the regulator manufacturer s instructions, shall be provided where the location of a regulator is such that a ruptured diaphragm will cause a hazard. Where there is more than one (1) regulator at a location, each regulator shall have a separate vent to the outside, or if approved by the Authority Having Jurisdiction, the vent lines shall be permitted to be manifolded in accordance with accepted engineering practices to minimize back pressure in the event of diaphragm failure. (See NFPA 54:5.9.7 for information on properly locating the vent.) Materials for vent piping shall be in accordance with Section Exception: A regulator and vent-limiting means combination listed as complying with CSA Z21.80, Standard for Line Pressure Regulators, shall be permitted to be used without a vent to the outdoors. The following references were extracted from NFPA 54: Vents. The discharge stacks, vents or outlet parts of all pressure-relieving and pressure-limiting devices shall be located so that gas is safely discharged into the outside atmosphere outdoors. Discharge stacks or vents shall be designed to prevent the entry of water, insects, or any other foreign material that could cause blockage. The discharge stack or vent line shall be at least not less than the same size as the outlet of the pressure-relieving device. (remaining text unchanged) This change provides consistency with NFPA and an editorial revision for clarity. 212

13 UMC 2012 (911.6): Item # 91 Ted Lemoff NFPA Duct Furnaces Used with Refrigeration Systems. (D4)Where a duct furnace is installed downstream of an evaporative cooler or air washer, the heat exchanger shall be constructed of corrosion-resistant materials. Stainless steel, ceramic-coated steel, and an aluminum-coated steel in which the bond between the steel and the aluminum is an iron-aluminum alloy are considered to be corrosion resistant. Air washers operating with chilled water that deliver air below the dew point of the ambient air at the equipment duct furnace are considered as refrigeration systems. [NFPA 54: ] (portions of text not shown remains unchanged) This change provides consistency with NFPA In the NFPA , the term equipment is reserved for anything that is not an appliance. 213

14 UMC 2012 (912.1, 916.1, 916.2, 922.2): Item # 92 Ted Lemoff NFPA Installation. The installation of floor furnaces shall comply with the following requirements: (A1) Listed floor furnaces shall be installed in accordance with their listing and the manufacturer s installation instructions. (remaining text unchanged) Floor-Mounted Units. (A1) Clearance from Combustible Material. The clearances specified as follows shall not interfere with combustion air, accessibility for operation, and servicing. (1a) Listed floor-mounted household cooking appliances, where installed on combustible floors, shall be set on their own bases or legs and shall be installed in accordance with their listing and the manufacturer s installation instructions. (3c) Listed household cooking appliances that include a solid or liquid fuel-burning section shall be spaced from combustible material and otherwise installed in accordance with the standards applying to manufacturer s installation instructions for the supplementary fuel section of the appliance. (portions of text not shown remain unchanged) Built-In Units. (A1)Installation. Listed built-in household cooking appliances shall be installed in accordance with their listing and the manufacturer s installation instructions. The installation shall not interfere with combustion air, accessibility for operation, and servicing. Unlisted built-in household cooking appliances shall not be installed in or adjacent to combustible material. [NFPA 54-09: ] (remaining text unchanged) Clearance. The installation of pool heaters shall comply with the following requirements: (B2) A listed pool heater shall be installed in accordance with its listing and the manufacturer s installation instructions. (portions of text not shown remain unchanged) The terms of the listing of specific appliances (i.e. household cooking appliance, floor furnace, and household pool heaters) are not available to the installer. The manufacturer s installation instructions contain the necessary installation provisions, and are reviewed by the listing agency. VOTING RESULTS: AFFIRMATIVE: 15, NEGATIVE: 5, NOT RETURNED: 1 Nikravi 214

15 EXPLANATION OF NEGATIVE: ADLER, MANN: The term of listing is critical for plan checking and inspection purposes. In order for the Authority Having Jurisdictions to properly check plans and issue the permit, the appliance listing must be provided. BERGER: The term listing should be left as written to require all available information to be submitted to the Authority Having Jurisdictions for review. The listing information is necessary to assist the Authority Having Jurisdictions in the decision making process. FEEHAN: Terms of their listing should not be removed. The manufacturers instructions may not have the information necessary for a proper installation. The listing is the only way to insure that appliances are installed correctly. The terms of the appliances listing are critical for plan checking and inspection purposes. MACELLAIO: The appliance listing must be submitted to the plan reviewer in order to properly review submitted plans. 215

16 UMC 2012 (1002.0, , Table 17-1): Item # 93 Erik S. Emblem 3E International Incorporated Add new text as follows: Standards General. Boilers shall be constructed and designed in accordance with ASME CSD-1 and one of the following standards: (1) ASME BPVC Section I (2) ASME BPVC Section IV (3) NFPA 85 (renumber existing sections) CHAPTER 17 STANDARDS TABLE 17-1 STANDARDS FOR EQUIPMENT AND MATERIALS STANDARD NUMBER STANDARD TITLE APPLICATION REFERENCED SECTION ASME BPVC Section I-2007 Power Boilers Boilers ASME BPVC Section IV-2007 Rules for Construction of Heating Boilers Boiler construction, Heating Boilers ASME CSD Controls and Safety Devices for Automatically Boilers, Controls Fired Boilers Note: ASME BPVC Section I-2007 and ASME CSD were not provided for review at the time of this monograph (portions of table not shown remain unchanged) This addition provides referenced standards for boilers in Chapter 10 of the UMC. Standards listed above are new and will be proposed as additions to Table ASME BPVC Section I provides requirements for all methods of construction of power, electric, and miniature boilers; high temperature water boilers used in stationary service; and power boilers used in locomotive, portable, and traction service. Superheaters, economizers, and other pressure parts connected directly to the boiler without intervening valves are considered as part of the scope of Section I. ASME BPVC Section IV provides requirements for design, fabrication, installation, and inspection of steam generating boilers, and hot water boilers intended for low pressure service that are directly fired by oil, gas, electricity, or coal. It contains appendices which cover approval of new material, methods of checking safety valve and safety relief valve capacity, examples of methods of checking safety valve and safety relief valve capacity, examples of methods of calculation and computation, definitions relating to boiler design and welding, and quality control systems. Rules pertaining to use of the H, HV, and HLW Code symbol stamps are also included. (look at companion change, Item # 94 and 95) 216

17 217

18 UMC 2012 ( , ): Item # 94 Erik S. Emblem 3 E International Incorporated Oil-Burning Boilers. Oil-burning boilers shall be in accordance with Section and Section Listing & Labeling. Oil-burning boilers shall be listed and labeled in accordance with UL Installation. Tanks, piping, and valves for oil-burning boilers shall be installed in accordance with NFPA 31. (renumber remaining sections) Fuel Piping, Tanks, and Valves. Tanks, piping, and valves for oil burning appliances shall be installed in accordance NFPA 31, Standard for the Installation of Oil-Burning Equipment. The design, installation and operation of single burner boilers, multiple burner boilers, stokers, and atmospheric fluidized-bed boilers with not less than a fuel input rating of 12.5 billion Btu/hr (3.7 MWt) to pulverized fuel systems, fired or unfired steam generators used to recover heat from combustion turbines and to other combustion turbine exhaust systems shall be in accordance with NFPA 85. That portion of the oil-burning system supplied on boilers and covered within the scope of NFPA 85 shall be installed in accordance with NFPA 85. This addition provides referenced standards for oil-fired boilers in Chapter 10 of the UMC. Because of the misconception of the referenced standard required, the applicable standard was added to provide the necessary information. In addition to provide a clarification, the scope of NFPA 85 has been inserted into section to assist the user. (look at companion change, Item # 93 and 95) 218

19 UMC 2012 (1002.3): Item # 95 Erik S. Emblem 3E International Incorporated Add new text as follows: Electric Boilers. Electric boilers shall be listed and labeled in accordance with UL 834. (renumber remaining sections) This addition provides cross-reference between Chapter 10 and Table 17-1 for UL 834 standard. (look at companion change, Item # 93 and 94) 219

20 UMC 2012 ( ): Item # 96 Erik Emblem Chair, UMC Standards Task Group The following is recommended by the Standards Task Group (see Standards Task Group Report Item 1) New and Reclaimed Refrigerants. The Purity of Nnew and reclaimed refrigerants shall meet the referenced standard for refrigerant specifications in Chapter 17 be in accordance with AHRI 700 or other approved standards. This change provides the correct reference standard for new and reclaimed refrigerants. AHRI 700 is the only known current standard available in the industry for new and reclaimed refrigerants. AHRI 700 specifies acceptable levels of contaminants (purity requirements) for fluorocarbon refrigerants regardless of source and lists acceptable test methods. Refrigerants listed in AHRI 700 are also referenced in ASHRAE Standard 34 which Table 11-1 of the UMC is extracted from. 220

21 UMC 2012 (1106.1): Item # 97 Jeff Henning Air Conditioning Contractors of America (ACCA) Human Comfort. Cooling systems used for human comfort shall comply be in accordance with the return-air and outside-air provisions for furnaces in Sections and Section of this code. Cooling equipment used for human comfort in dwelling units shall be selected sized to satisfy the calculated loads determined in accordance with the reference standards in Chapter 17 or other approved methods. Equipment is often selected based on the capacity rating from Air Conditioning, Heating, and Refrigeration Institutes (AHRI). This information is applicable to only an extremely small demographic (95 F outdoor temperature, and indoor conditions of 80 F / 50%RH). There are very few people who desire an 80 F indoor temperature and live in an area with an outdoor design temperature of 95 F. The country has many different climates and operating conditions. For example, a home with a 30,000 Btu load would nominally need a 2.5 ton unit however, that same home in: (1) Phoenix (hot and dry) might need 3.5 ton system running on high fan speed to deliver 30,000 Btu because the design outdoor temperature is 108 F, (2) Miami (hot and humid) might need a 3.0 ton system running on low fan speed to deliver 30,000 Btu and address the high latent heat load (moisture), (3) Seattle (mild and dry) might only need a 2.0 ton system running on medium fan speed because it rarely gets warmer than 80 F. Manual S (residential) and CS (commercial) explains the procedure of using the original manufacturer s expanded performance data to determine a cooling unit s capacity in different climates. Manual S / CS also address altitude correction factors, which can affect equipment capacity by an additional 10%. ACCA Manual J and Manual N are often referenced for sizing cooling equipment. However, these procedures provide guidance to estimate the cooling load that serves as the basis for the equipment size. They refer to ACCA Manual S / CS to address the equipment selection procedure. ANSI/ACCA Manual S (pending) is the ANSI standard for residential equipment sizing and selection. The International Association of Plumbing and Mechanical Officials reference standards for sizing and selecting residential equipment should be consistent with the official ANSI standard. 221

22 UMC 2012 ( ): Item # 98 Steve Taylor Taylor Engineering Delete text without substitution: An A1 system having an aggregate combined compressor horsepower of 100 (73.55 kw) or more is used. (renumber remaining sections) In rooms where there are multi-circuit chillers that would individually fall below the threshold of 100 hp, an accident scenario that would involve more than one circuit at a time is very unlikely. The current code requirement makes the design of such a room much more difficult to account for the possibility of a very unlikely scenario. COMMITTEE ACTION: Reject COMMITTEE STATEMENT: The proposed deletion reduces the requirement for safety. Based on the quantity and the safety group of refrigerant, a dedicated machinery room is necessary to be provided. VOTING RESULTS: AFFIRMATIVE: 19, NEGATIVE: 1, NOT RETURNED: 1 Nikravi EXPLANATION OF NEGATIVE: TAYLOR: The requirement for a refrigeration machinery room is based on the amount of refrigerant that would escape into the room in case of a leak from the largest refrigerant circuit. The code does not assume that an accident will occur from many circuits, just one. Therefore, this section is inconsistent with the rest of Chapter 11. There is no increase in risk of dangerous refrigerant levels in the room if it has 10 or 100 small circuits. This section is not in ASHRAE Standard 15 upon which most of Chapter 11 of the UMC is based. 222

23 UMC 2012 (1107.4, , , ): Item # 99 Steve Taylor Taylor Engineering Refrigerant-Vapor Alarms. Machinery rooms shall have approved refrigerant-vapor detectors located in an area sensing where refrigerant from a leak is likely to concentrate and that will activate visual and audible alarms inside the refrigerating machinery room, outside each entrance to the refrigerating machinery room and shall activate mechanical ventilation in accordance with Section Alarms shall be activated at a value not greater than one-half the immediately dangerous to life or health (IDLH), or measurement consistent therewith; the PEL, or measurement consistent therewith; or 25 percent of the LFL, whichever is less. The alarm shall be of the manual reset type with the reset located inside the refrigerating machinery room Emergency Control of the Ventilation Systems. Fans required by Section to provideing emergency purge ventilation for refrigerant escape shall be activated by a refrigerant detector in accordance with Section and by have a clearly identified switch of the break-glass type providing on only control located immediately adjacent to and outside of each refrigerant machinery room exit. For other than ammonia, purge fans shall also respond automatically to the refrigerant concentration detection system set to activate the ventilation system at no more than 25 percent of the LFL, or 50 percent of the IDLH, or a measure equivalent thereto, whichever is less. For ammonia, purge fans shall also respond automatically to the refrigerant concentration detection system set to activate the ventilation system at no more than 1,000 parts per million. An emergency purge control shall be provided with a manual reset only Central Control of Ventilation Systems. Mechanical ventilation systems shall have switches to control power to each fan. The switches shall be key operated or within a locked, glass-covered enclosure at an approved location adjacent to and outside of the principal entrance to the machinery room. Necessary keys shall be located in a single approved location. Switches controlling fans providing continuous ventilation shall be of the two-position, on-off type. Switches controlling fans providing intermittent or emergency ventilation shall be of the threeposition, automatic on-off type. Switches shall be labeled identifying both the function and the specific fan controlled. Two colored and labeled indicator lamps responding to the differential pressure across the purge fan or current through the fan motor created by airflow shall be provided for each switch. One lamp shall indicate flow; the other shall indicate no flow Emergency Control. A clearly identified switch of the break-glass type providing off -only control of electrically energized equipment and devices within the refrigeration machinery room shall be provided immediately adjacent to and outside of each refrigeration machinery room exit. In addition, emergency shutoff shall also be automatically activated when the concentration of refrigerant vapor exceeds 25 percent of the LFL by the refrigerant alarm in accordance with Section Sections and both address the same subject but have overlapping and sometimes competing requirements. Refrigerant alarm concentrations and limits are listed in three locations; they are not all the same. In this revision: 1. The refrigerant detector is addressed once in It is clearly indicated as the device that initiates alarm horns and lights as well as purge fans. 2. Alarm horns and lights are required to be in the room and outside each exit (in accordance with ASHRAE Standard 15). Previously the location was not specified. 3. The duplicated refrigerant concentration limits in these sections are eliminated and listed only in The redundant switches and alarm limits listed in section are eliminated. 5. Current switches are allowed in addition to differential pressure switches. The former are more reliable. The on/off lights are now required at each exit, not just the main exit. COMMITTEE ACTION: Accept as Amended by the TC Amend proposal as follows: 223

24 Emergency Control of the Ventilation Systems. Fans required by Section to provideing emergency purge ventilation for refrigerant escape shall be activated by a refrigerant detector in accordance with Section and by have a clearly identified switch of the break-glass type providing on only control located immediately adjacent to and outside of each refrigerant machinery room exit. For other than ammonia, purge fans shall also respond automatically to the refrigerant concentration detection system set to activate the ventilation system at no more than 25 percent of the LFL, or 50 percent of the IDLH, or a measure equivalent thereto, whichever is less. For ammonia, purge fans shall also respond automatically to the refrigerant concentration detection system set to activate the ventilation system at no more than parts per million. An emergency purge control shall be provided with a manual reset only Emergency Control. A clearly identified switch of the break-glass type providing off -only control of electrically energized equipment and devices within the refrigeration machinery room shall be provided immediately adjacent to and outside of each refrigeration machinery room exit. In addition, emergency shutoff shall also be automatically activated when the concentration of refrigerant vapor exceeds 25 percent of the LFL by the refrigerant alarm in accordance with Section COMMITTEE STATEMENT: The modification to Section permits alternative covers to a break-glass type that are acceptable to the Authority Having Jurisdiction. This modification correlates with action taken on Item #102. In addition, modification to Section correlates with action taken by the technical committee on Item #106. The proposed text in Item #106 revises the operational threshold for detectors to be lesser of 25% of LFL. 224

25 UMC 2012 ( ): Item # 100 Steve Taylor Taylor Engineering Refrigeration Machinery Room Ventilation General. Refrigeration machinery rooms shall be provided with a continuous source of outside air for ventilation and removal of rejected heat Refrigeration Machinery Rooms. Refrigeration machinery rooms shall be provided with dedicated mechanical exhaust systems. The exhaust systems shall have the capacity to achieve each of the following: Continuously maintain the refrigeration machinery room at 0.05 inch (12.44 Pa) water gauge negative relative to adjacent spaces calculated by: Q = 2610A e p (Equation 11-1) Exception: Refrigeration machinery rooms located in entirely detached structures and more than twenty (20) feet (6,096 mm) from property lines or openings into buildings Continuously provide 0.5 cubic foot per minute of airflow per gross square foot (2.54 L/s/m2) of floor area within the refrigeration machinery rooms as calculated by: Q = 0.5Agf (Equation 11-2) (renumber remaining sections) Continuous ventilation of refrigeration machinery rooms is not necessary and is a waste of energy. The requirements for exhaust airflow rates of refrigeration machinery rooms should be based on safety. The airflow rates as calculated by Sections and are sufficient to ensure safe levels of exhaust. If the refrigerant concentration is below the detector alarm level, the room is de facto safe so no ventilation is needed. If it rises above that concentration, the detector starts the fans which, if sized per , will render the room safe. So there is no need for continuous ventilation. In fact, a continuous exhaust can dilute a small leak such that the detector will not detect it, causing damage to the environment (ozone depletion, global warming). It also can cause a cooling or heating load in the room, increasing energy usage. 225

26 UMC 2012 ( ): Item # 101 Jeffrey Shapiro, P.E. International Code Consultants/Rep. International Institute of Ammonia Refrigeration Provide emergency purge of escaping refrigerant in accordance with IIAR 2 for ammonia, or for other refrigerants as calculated by: (remaining text unchanged) The proposed change will defer the required ventilation rate for ammonia refrigeration machinery rooms to IIAR 2, which is the ANSI accredited industry standard. IIAR 2 is in the process of being revised to change the basis of calculating required ventilation to an air changes per minute/hour basis. There is general agreement in the industry that the minimum ventilation rate for ammonia needs to be greater than the rate calculated using the current formula, and IIAR 2 is out for public comment so that a consensus rate that is unique based on the properties of ammonia can be established. It is anticipated that the public comment period for IIAR 2 will close prior to the ICC IAPMO hearing, and additional information on the new calculation approach will be presented at that time to support this proposal. COMMITTEE ACTION: Accept as Amended by the TC Amend proposal as follows: Provide emergency purge of escaping refrigerant at a rate of 30 air changes per hour in accordance with IIAR 2 for ammonia, or for other refrigerants as calculated by: (remaining text unchanged) COMMITTEE STATEMENT: The modification clarifies a specific rate for emergency purge of escaping refrigerant and provides clear and concise code language which is enforceable. 226

27 UMC 2012 (1108.5): Item # 102 Jeffrey Shapiro, P.E. International Code Consultants/Rep. International Institute of Ammonia Refrigeration Emergency Control of the Ventilation Systems. Fans providing emergency purge ventilation for refrigerant escape shall have a clearly identified switch of the break-glass type or protected by an approved tamper resistant cover. The switch shall provideing on only control and shall be located immediately adjacent to and outside of each the principal refrigerant machinery room exit. For other than ammonia, purge fans shall also respond automatically to the refrigerant concentration detection system set to activate the ventilation system at no more than 25 percent of the LFL, or 50 percent of the IDLH, or a measure equivalent thereto, whichever is less. For ammonia, purge fans shall also respond automatically to the refrigerant concentration detection system set to activate the ventilation system at no more than 1,000 parts per million. An emergency purge control shall be provided with a manual reset only. This change permits alternative covers to a break-glass type that are acceptable to the code official. It also revises the location of emergency ventilation control switches from every machinery room exit to only one. This change correlates with ASHRAE 8.12(i), and IFC 606.9, which only require a switch at one machinery room door. COMMITTEE ACTION: Accept as Amended by the TC Amend proposal as follows: Emergency Control of the Ventilation Systems. Fans required by Section to provideing emergency purge ventilation for refrigerant escape shall be activated by a refrigerant detector in accordance with Section and by have a clearly identified switch of the break-glass type, or protected by an approved tamper resistant cover. The switch shall, provideing on only control and shall be located immediately adjacent to and outside of each the principal refrigerant machinery room exit. For other than ammonia, purge fans shall also respond automatically to the refrigerant concentration detection system set to activate the ventilation system at no more than 25 percent of the LFL, or 50 percent of the IDLH, or a measure equivalent thereto, whichever is less. For ammonia, purge fans shall also respond automatically to the refrigerant concentration detection system set to activate the ventilation system at no more than 1,000 parts per million. An emergency purge control shall be provided with a manual reset only. COMMITTEE STATEMENT: The modification provides a reference to required refrigerant detector in accordance with Section Section currently permits sensor settings which initiate at minimum levels as PEL. In addition, the last portion of Section is retained to provide 1000 ppm threshold for ammonia ventilation. This requirement is consistent with ASHRAE 15, Section 8.12(h). 227

28 UMC 2012 (1106.4): Item # 103 Mona Casey United Parents to Restrict Open Access to Refrigerant (UPROAR) Add new text as follows: Refrigerant Port Protection. Air conditioning refrigerant circuit access ports located outdoors shall be protected from unauthorized access with locking-type tamper-resistant caps or in a manner approved by the Authority Having Jurisdiction. (renumber remaining sections) The Uniform Mechanical Code currently does not address the issue of securing refrigerant service ports that are accessible to the public. This proposal seeks to prevent illegal venting of refrigerant by unauthorized individuals. Refrigerant poses a serious threat to human life and safety. Huffing, the intentional inhalation of refrigerant and other inhalants affects over one million children per year. As a result, deaths and injuries resulting from exposure to refrigerant are rising at an alarming rate. In addition, refrigerant leaks and illegal venting of refrigerant are contributing to the greenhouse gases in our atmosphere. This is illustrated in Figure 1.1. The reasons for securing refrigerant are compelling. Refrigerant is classified as hazardous material by the U. S. Department of Labor Occupational Safety and Health Administration, the U. S Department of Transportation, the U. S. Department of Energy, and the U. S. Environmental Protection Agency. It is also listed in the European Waste Catalogue and Hazardous Waste List. Regulation (EC) No. 2037/2000 mandated by the Environmental Protection Agency classifies refrigerant as a controlled substance. According to Mike Opitz, Certification Manager, LEED for Existing Buildings, U.S. Green Building Council, chlorine in CFCs and HCFCs destroy the ozone and depletes the Earth s natural shield for incoming ultraviolet radiation and absorb outgoing infrared radiation from the earth, functioning as potent greenhouse gases. 228

X Article/Section 902.0(D) X X X X X X X X X X X

X Article/Section 902.0(D) X X X X X X X X X X X CALIFORNIA MECHANICAL CODE MATRIX ADOPTION TABLE CHAPTER 9 INSTALLATION OF SPECIFIC APPLIANCES Adopting Agency BSC SFM HCD DSA OSHPD 1 2 1/AC AC SS SS/CC 1 2 3 4 Adopt Entire Chapter X X X X X Adopt Entire

More information

IMC Significant Changes Summary Tier I

IMC Significant Changes Summary Tier I 2009-2015 IMC Significant Changes Summary Tier I 202 Environmental Air The definition of environmental air has been expanded through the addition of parking garage exhaust. 306.1 Access More than just

More information

SPECIFIC APPLIANCES CHAPTER 6

SPECIFIC APPLIANCES CHAPTER 6 CHAPTER 6 SPECIFIC APPLIANCES SECTION FGC 601 GENERAL 601.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and equipment

More information

SPECIFIC APPLIANCES CHAPTER 6

SPECIFIC APPLIANCES CHAPTER 6 CHAPTER 6 SPECIFIC APPLIANCES SECTION 601 GENERAL 601.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and equipment

More information

SPECIFIC APPLIANCES CHAPTER 6

SPECIFIC APPLIANCES CHAPTER 6 CHAPTER 6 SPECIFIC APPLIANCES SECTION 601 (IFGC) GENERAL 601.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and

More information

ICC CODE CORNER 2015 International Fire Code

ICC CODE CORNER 2015 International Fire Code SECTION 606 MECHANICAL REFRIGERATION [M] 606.1 Scope. Refrigeration systems shall be installed in Code. [M] 606.2 Refrigerants. The use and purity of new, recovered and reclaimed refrigerants shall be

More information

Safety Standard for Refrigeration Systems

Safety Standard for Refrigeration Systems BSR/ASHRAE Addendum a ANSI/ASHRAE Standard 15-2016 First Public Review Draft Safety Standard for Refrigeration Systems First Public Review (April 2017) (Draft shows Proposed Changes to Current Standard)

More information

CHAPTER 10 STEAM AND HOT WATER BOILERS

CHAPTER 10 STEAM AND HOT WATER BOILERS CHAPTER 10 STEAM AND HOT WATER BOILERS 1001.0 Purpose. The purpose of this chapter is to establish and provide minimum standards for the protection of public welfare, health, safety, and property by regulating

More information

2015 National Fuel Gas Code Summary List of Revisions Updated: 04/24/14

2015 National Fuel Gas Code Summary List of Revisions Updated: 04/24/14 The following list contains a summary of the significant revisions in the 2015 National Fuel Gas Code approved by the National Fuel Gas Code Committee, ANSI ASC Z223 and NFPA 54. PIPING Various Brass REVISED

More information

2012 INTERNATIONAL FUEL GAS CODE VENTS

2012 INTERNATIONAL FUEL GAS CODE VENTS 2012 INTERNATIONAL FUEL GAS CODE SECTION 502 (IFGC) VENTS 502.1 General. All vents, except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accordance with

More information

CHAPTER 5: EXHAUST SYSTEMS

CHAPTER 5: EXHAUST SYSTEMS MOTORS, FANS AND FILTERS 503.1 General. Motors and fans shall be sized to provide the required air movement. Motors in areas that contain flammable vapors or dusts shall be of a type approved for such

More information

2018 National Fuel Gas Code Summary List of Revisions Updated: 7/27/17

2018 National Fuel Gas Code Summary List of Revisions Updated: 7/27/17 The following list contains a summary of the significant revisions in the 2015 National Fuel Gas Code approved by the National Fuel Gas Code Committee, ANSI ASC Z223 and NFPA 54. 1.1.1.1 (B), (C), & (D)

More information

ATTACHMENT D #1 - HVAC (OIL) - SINGLE FAMILY DWELLINGS Category C: OIL

ATTACHMENT D #1 - HVAC (OIL) - SINGLE FAMILY DWELLINGS Category C: OIL LINE ITEM # ATTACHMENT D #1 - HVAC (OIL) - SINGLE FAMILY DWELLINGS Category C: OIL LINE ITEM DETAIL Labor Material FURNACE COMPONENTS 1 Furnish & Install Sight-Impaired Thermostat For Heating and Cooling

More information

Analysis of Changes for the 6 th Edition (2017) Florida Codes

Analysis of Changes for the 6 th Edition (2017) Florida Codes Analysis of Changes for the 6 th Edition (2017) Florida Codes Changes to the Florida Building Code, Mechanical This Analysis of Changes for the 6 th Edition (2017) of the Florida Codes is intended to provide

More information

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT SECTION 901 GENERAL 901.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration

More information

FACT SHEET 2018 National Fuel Gas Code Summary List of Revisions rev

FACT SHEET 2018 National Fuel Gas Code Summary List of Revisions rev This fact sheet provides an overview of the significant revisions in the 2015 National Fuel Gas Code approved by the National Fuel Gas Code Committee, ANSI ASC Z223 and NFPA 54. These revisions are published

More information

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT SECTION 901 GENERAL 901.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration

More information

Ammonia Refrigeration RAGAGEP

Ammonia Refrigeration RAGAGEP Providing Solutions. Simplifying Regulation. Ammonia Refrigeration RAGAGEP Peter Thomas, P.E., CSP Resource Compliance, Inc. Introduction Providing Solutions. Simplifying Regulation. Providing Solutions.

More information

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2012 EDITION

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2012 EDITION CHAPTER 23.20 LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2012 EDITION Sections 23.20.100 Local amendments to the International Mechanical Code, 2012 Edition.... 2 23.20.101.2 Scope.... 2 23.20.103-110

More information

Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016

Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016 Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016 Ohio Administrative Code Rule Number OMC Section IMC origin Reason for proposed 4101:2-2-01 Air, Makeup 2015 Modified definition Air,

More information

Item # 1 Comment Seq # 1 UMC 2012 (Chapters 1 15): Chair, UMC Correlation Task Group (Manual of Style)

Item # 1 Comment Seq # 1 UMC 2012 (Chapters 1 15): Chair, UMC Correlation Task Group (Manual of Style) Item # 1 Comment Seq # 1 UMC 2012 (Chapters 1 15): SUBMITTER: Martin Cooper Chair, UMC Correlation Task Group (Manual of Style) RECoMMEndaTIon: The following is recommended by the Correlation Task Group

More information

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2000 EDITION

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2000 EDITION CHAPTER 23.20 LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2000 EDITION SECTIONS 23.20.100 Local Amendments To The International Mechanical Code, 2000 Edition 23.20.202 Definitions 23.20.301.14

More information

CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL BURNING EQUIPMENT

CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL BURNING EQUIPMENT CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL BURNING EQUIPMENT SECTION 901 GENERAL 901.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance

More information

2015 & 2012 International Mechanical Code Significant Changes and the PA Uniform Construction Code

2015 & 2012 International Mechanical Code Significant Changes and the PA Uniform Construction Code 2015 & 2012 International Mechanical Code Significant Changes and the PA Uniform Construction Code Welcome! Shawn Strausbaugh Director PMG Technical Resources ICC Government Relations sstrausbaugh@iccsafe.org

More information

Subject: BSR Uniform Mechanical Code, 2015 Edition: Appeal on Proposal #333

Subject: BSR Uniform Mechanical Code, 2015 Edition: Appeal on Proposal #333 Paul Cabot Administrator National Fuel Gas Ms. Gabriella Davis Recording Secretary, IAPMO Standards Council International Association of Plumbing and Mechanical Officials (IAPMO) IAPMO Group World Headquarters

More information

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951) Riverside County Fire Department Office of the Fire Marshal 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4777 Fax (951) 955-4886 Technical Policy Title: Plant Processing and Extraction

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply

More information

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2006 EDITION

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2006 EDITION CHAPTER 23.20 LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2006 EDITION Sections 23.20.100 Local amendments to the International Mechanical Code, 2006 Edition... 2 23.20.101.2 Scope... 2 23.20.303.4

More information

CUMULATIVE ANALYSIS OF UNIFORM MECHANICAL CODE CHANGES to 2003

CUMULATIVE ANALYSIS OF UNIFORM MECHANICAL CODE CHANGES to 2003 CUMULATIVE ANALYSIS OF UNIFORM MECHANICAL CODE CHANGES 2000 to 2003 The following pages contain comments regarding the changes to the 2000 edition of the UNIFORM MECHANICAL CODE (UMC ) that were made to

More information

CHAPTER 6 SPECIFIC APPLIANCES

CHAPTER 6 SPECIFIC APPLIANCES CHAPTER SPECIFIC APPLIANCES SECTION 01 (IFGC) GENERAL 01.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and equipment

More information

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER PART 1 GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 American National Standard for Gas-Fired Low Pressure Steam and Hot Water Boilers B. ASME Section

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply with this chapter and the International

More information

Revitalize Building Mechanical Systems (4619)

Revitalize Building Mechanical Systems (4619) SECTION 235216 FIRE-TUBE CONDENSING BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

UNIFORM MECHANICAL CODE

UNIFORM MECHANICAL CODE INDEX Note: Content and section numbers will be updated before publishing. 2009 International Association of Plumbing and Mechanical Officials. All rights reserved. The copyright in this index is separate

More information

2012 ICC Code Development Hearings 2012 Code Development Cycle:

2012 ICC Code Development Hearings 2012 Code Development Cycle: 2012 ICC Code Development Hearings 2012 Code Development Cycle: The 2012 International Code Council (ICC), Code Development Hearings were held from April 29 thru May 8, 2012. The deadline for public comment

More information

UMC 2012 ( ): Item # 38

UMC 2012 ( ): Item # 38 UMC 2012 (504.3.1): Item # 38 Steve Taylor Taylor Engineering 504.3.1 Moisture Exhaust Ducts. Moisture exhaust ducts shall terminate on the outside of the building and shall be equipped with a back-draft

More information

NFPA 54 UPDATE. Paul Cabot American Gas Association

NFPA 54 UPDATE. Paul Cabot American Gas Association NFPA 54 UPDATE Paul Cabot American Gas Association PRESENTATION TOPICS Summary Listing Schedule Revisions Definitions/General Piping Appliances and Appliance Installation Venting 2015 Edition Revision

More information

AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER

AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER The 2016 Denver Building and Fire Code includes the following codes except as amendment herein. 2015 IBC (Building) 2015 IFC (Fire)

More information

Errata ANSI Z223.1 National Fuel Gas Code 2015 Edition

Errata ANSI Z223.1 National Fuel Gas Code 2015 Edition Errata ANSI Z223.1 National Fuel Gas Code 2015 Edition Reference: Various Errata Z223.1-2015-1 Issue Date: 3/10/16 National Fuel Gas Code user: The American Gas Association (AGA) notes the following errors

More information

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Solvent Extraction Plants

More information

NFPA 96, 2017 REVIEW SUMMARY

NFPA 96, 2017 REVIEW SUMMARY NFPA 96, 2017 REVIEW SUMMARY 1) NFPA 96 REVISION SUMMARY NFPA 96 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations The 2017 edition adds a new normative annex on mobile

More information

2015 MECHANICAL CODE REQUIREMENTS

2015 MECHANICAL CODE REQUIREMENTS 2015 MECHANICAL CODE REQUIREMENTS ANTRIM COUNTY BUILDING DEPARTMENT PO BOX 188 205 CAYUGA STREET BELLAIRE, MI 49615 (231) 533-8373 FAX (231) 533-6041 Mechanical requirements for residential buildings per

More information

COMcheck Software Version Review Mechanical Compliance Certificate

COMcheck Software Version Review Mechanical Compliance Certificate COMcheck Software Version 4.0.7.2 Review Mechanical Compliance Certificate Section 1: Project Information Energy Code: 2014 Oregon Energy Efficiency Specialty Code Project Title: Benton County Health Project

More information

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM 1 of 14 6/22/2016 3:15 PM Second Revision No. 1-NFPA 17A-2016 [ Section No. 4.3.3 ] 4.3.3 All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors,

More information

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The

More information

NFPA 37 Public Comment Responses Page 1 of 32

NFPA 37 Public Comment Responses Page 1 of 32 of 30 11/4/2016 3:05 PM Public Comment No. 6-NFPA 37-2016 [ New Section after 1.6 ] TITLE OF NEW CONTENT Type your content here... 1.7 Pressure Measurement. All pressures expressed in this document are

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR7040 SAF-MER (36.1.1.4) 36.1.1.4 The provisions of this chapter shall apply to life safety requirements for all new mercantile buildings. Specific requirements shall apply to suboccupancy groups,

More information

Uniform Mechanical Code

Uniform Mechanical Code Uniform Mechanical Code 2019 Technical Committee Meeting Monograph Denver, Colorado Sheraton Denver Downtown Hotel May 1 2, 2019 TABLE OF CONTENTS I II III Tentative Agenda Tentative Order of Discussion

More information

Department of Public Safety

Department of Public Safety Terry E. Branstad Governor Kim Reynolds Lt. Governor Department of Public Safety Roxann M. Ryan Commissioner Liquid Propane Informational guide to submitting plans Plans are to be submitted to: State Fire

More information

DIVISION FINNED WATER-TUBE BOILERS

DIVISION FINNED WATER-TUBE BOILERS MVB, TYPE H - MODELS 2503-4003 SUGGESTED SPECIFICATIONS Catalog No.: 2000.934A Effective: 04-01-14 Replaces: 06-01-13 DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section

More information

Completed Projects / Projets terminés

Completed Projects / Projets terminés Completed Projects / Projets terminés New Standards New Editions Special Publications Gas Technician Training 2 Module 10, 3rd edition Piping and Tubing Systems for Industrial and Commercial Applications...

More information

IFGC-2012 AMENDED IFGC-2015 IFGC-2018 CHAPTER 1 SCOPE AND

IFGC-2012 AMENDED IFGC-2015 IFGC-2018 CHAPTER 1 SCOPE AND CHAPTER 1 SCOPE AND CHAPTER 1 SCOPE AND ADMINISTRATION ADMINISTRATION 301.1.2 LP-Gas installations. Whenever there is a conflict between this code and NFPA 54 and B+NFOA 58 as adopted by the Nevada LP-Gas

More information

GASEOUS HYDROGEN SYSTEMS

GASEOUS HYDROGEN SYSTEMS CHAPTER 7 GASEOUS HYDROGEN SYSTEMS SECTION 701 GENERAL 701.1 Scope. The installation of gaseous hydrogen systems shall comply with this chapter and Chapters 30 and 35 of the Fire Compressed gases shall

More information

Introduction Service Pipe Application Important Terms Air Requirements... Appliance Location... Venting... Calculations...

Introduction Service Pipe Application Important Terms Air Requirements... Appliance Location... Venting... Calculations... Construction Guide Table of Contents Page Introduction... 2 Service Pipe Application... 4 Important Terms... 5 Air Requirements... Appliance Location... Venting... Calculations... 37 Gas Distribution System...

More information

DIVISION FINNED WATER-TUBE WATER HEATERS

DIVISION FINNED WATER-TUBE WATER HEATERS HI DELTA, TYPE WH - MODELS 992C-2342C SUGGESTED SPECIFICATIONS Catalog No.: 3500.932A Effective: 04-01-17 Replaces: 10-31-16 DIVISION 23 52 33.13 FINNED WATER-TUBE WATER HEATERS - GENERAL 1.1 SUMMARY A.

More information

Inspection Checklist Mechanical Rough in

Inspection Checklist Mechanical Rough in Property Owner Name: Property Address: Permit Number: Inspectors Name: Review Date: Permits and Plans 1. Job address is posted in a visible location. (R319.1) 2. Permit and approved plans are on site and

More information

DIVISION COMMERCIAL, GRID-TYPE, FINNED-TUBE, GAS DOMESTIC WATER HEATERS

DIVISION COMMERCIAL, GRID-TYPE, FINNED-TUBE, GAS DOMESTIC WATER HEATERS MVB, TYPE WH - MODELS 503A-2003A SUGGESTED SPECIFICATIONS Catalog No.: 3500.952C Effective: 06-25-15 Replaces: 12-22-09 DIVISION 23 34 36.29 COMMERCIAL, GRID-TYPE, FINNED-TUBE, GAS DOMESTIC WATER HEATERS

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply

More information

COMBUSTION APPLIANCE SAFETY INSPECTION FOR VENTED APPLIANCES*

COMBUSTION APPLIANCE SAFETY INSPECTION FOR VENTED APPLIANCES* COMBUSTION APPLIANCE SAFETY INSPECTION FOR VENTED APPLIANCES* *Vented appliances refer to natural draft appliances equipped with a barometric draft regulator or Category I appliances equipped with a draft

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof

More information

WATER-TUBE POOL HEATERS

WATER-TUBE POOL HEATERS XTHERM, TYPE P - MODELS 1005A-2005A SUGGESTED SPECIFICATIONS Catalog No.: 6000.63B Effective: 3-01-15 Replaces: 9-01-09 WATER-TUBE POOL HEATERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes condensing,

More information

DIVISION FINNED WATER-TUBE BOILERS

DIVISION FINNED WATER-TUBE BOILERS MVB, TYPE H - MODELS 503A-2003A SUGGESTED SPECIFICATIONS Catalog No.: 2000.932C Effective: 04-01-14 Replaces: 07-15-13 DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section

More information

DIVISION FINNED WATER-TUBE BOILERS

DIVISION FINNED WATER-TUBE BOILERS MVB, TYPE H - MODELS 504A-2004A SUGGESTED SPECIFICATIONS Catalog No.: 2000.933C Effective: 06-25-15 Replaces: 12-21-09 DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section

More information

AHRI Certification Program Scopes - COOLING

AHRI Certification Program Scopes - COOLING Air-to-Air Energy Recovery Ventilators (AHRI Std. 1060) Automatic Commercial Ice-Cube Machines and Ice Storage Bins (AHRI Stds. 810 & 820) Central Station Air-Handling Units (AHRI Std. 430) Commercial

More information

TABLE OF CONTENTS. Part I Administrative

TABLE OF CONTENTS. Part I Administrative Part I Administrative.......................... 1-1 CHAPTER 1 SCOPE AND ADMINISTRATION. 1-1 R101 General............................. 1-1 R102 Applicability......................... 1-2 R103 (Not adopted)........................

More information

NCEHSA Conference. Carbon Monoxide Detector Regulations for Lodging Establishments (S.L )

NCEHSA Conference. Carbon Monoxide Detector Regulations for Lodging Establishments (S.L ) NCEHSA Conference Carbon Monoxide Detector Regulations for Lodging Establishments (S.L. 2013-413) 1 Purpose of this session The purpose of this session is to review the provisions of Session Law 2013-413

More information

Conversion Instructions Logano G234X. Gas boiler. Please read carefully before installing and servicing. Gas boiler

Conversion Instructions Logano G234X. Gas boiler. Please read carefully before installing and servicing. Gas boiler Gas boiler UPON COMPLETION OF THE INSTALLATION THE INSTALLER MUST INSTRUCT THE OWNER AND OPERATOR ON THE FUNCTIONALITY AND THE PROPER OPERATION OF THE BOILER AND THE HEATING SYSTEM. INSTALLER MUST REVIEW

More information

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015

More information

Preliminary Agenda Technical Committee on Liquefied Petroleum Gas

Preliminary Agenda Technical Committee on Liquefied Petroleum Gas Preliminary Agenda Technical Committee on Liquefied Petroleum Gas Tuesday, March 10; All Day Wednesday, March 11; All Day DRURY PLAZA HOTEL San Antonio Riverwalk 0. Administrative. A. Meeting Schedule.

More information

WATER-TUBE POOL HEATERS

WATER-TUBE POOL HEATERS XTHERM, TYPE P - MODELS 2505-4005 SUGGESTED SPECIFICATIONS Catalog No.: 6000.70 Effective: 09-15-16 Replaces: NEW WATER-TUBE POOL HEATERS - GENERAL 1.1 SUMMARY A. Section includes condensing, gas-fired

More information

2009 Washington State Non-Residential Energy Code Scott Rushing, PE, LEED AP - Rushing Company Lisa Rosenow, CSBA, LEED AP NEEC

2009 Washington State Non-Residential Energy Code Scott Rushing, PE, LEED AP - Rushing Company Lisa Rosenow, CSBA, LEED AP NEEC 2009 Washington State Non-Residential Energy Code Scott Rushing, PE, LEED AP - Rushing Company Lisa Rosenow, CSBA, LEED AP NEEC Mechanical Systems Agenda Changes in NREC Chapter 11 Changes in NREC Chapter

More information

101 S. George St 116 E Gas Ave York, PA York, PA (717) (717)

101 S. George St 116 E Gas Ave York, PA York, PA (717) (717) City of York Qdot Engineering 101 S. George St 116 E Gas Ave York, PA 17405 York, PA 17405 (717) 849-2329 (717) 744-8315 INSPECTION CHECKLIST Residential Mechanical 2009 Codes This checklist is intended

More information

TABLE OF CONTENTS. Part I Administrative... 1

TABLE OF CONTENTS. Part I Administrative... 1 Part I Administrative............................ 1 CHAPTER 1 Deleted Part II Definitions.............................. 3 CHAPTER 2 DEFINITIONS.................... 3 R201 General..................................

More information

d. Portable water heaters used exclusively for underwater diving operations.

d. Portable water heaters used exclusively for underwater diving operations. RULE 360. BOILERS, WATER HEATERS, AND PROCESS HEATERS (0.075 2 MMBtu/hr) EMISSIONS OF OXIDES OF NITROGEN FROM LARGE WATER HEATERS AND SMALL BOILERS. (Adopted 10/17/2002, revised xx/xx/xxxx) A. Applicability

More information

CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS

CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS Presented to: Presented by: Sargon Ishaya, PE www.pragmaticprofessionalengineers.com Introduction Today s Agenda Overview Review

More information

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 43 10/20/2015 4:02 PM First Revision No. 2035-NFPA 101-2015 [ Global Input ] To 14.3.4.4.1, add an item (4) to read: (4) Carbon monoxide detectors shall be installed centrally located within occupiable

More information

RAGAGEP UPDATE. Douglas Reindl, Director, IRC 2016 IRC R&T Forum

RAGAGEP UPDATE. Douglas Reindl, Director, IRC 2016 IRC R&T Forum RAGAGEP UPDATE Douglas Reindl, Director, IRC 2016 IRC R&T Forum What s the point? Process safety information (d)(3)(ii) The employer shall document that equipment complies with recognized and generally

More information

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS SECTION 22 34 00 (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS System shall provide a complete hot water return throughout the entire system with balancing (flow control) valves not less than 10 feet from

More information

Flammable Liquid: A liquid whose flashpoint is greaterless than 100 F when tested by closed-cup test methods.

Flammable Liquid: A liquid whose flashpoint is greaterless than 100 F when tested by closed-cup test methods. ANSI/IIAR 2-2014 Addendum A Standard for Safe Design of Closed-Circuit Ammonia Refrigeration Systems Public Review Draft #3 Reviewers of Addendum A are welcome to comment on the changes in the standard,

More information

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement 1 of 7 3/4/2016 12:02 PM Second Revision No. 5-NFPA 56-2016 [ Section No. 1.1.2 ] 1.1.2 Nonapplication of Standard. This standard shall not apply to the following items: (1)* Piping systems covered by

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Hot Work Operations

More information

SECTION HEATING BOILERS

SECTION HEATING BOILERS SECTION 23 52 00 HEATING BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes boilers, controls and boiler trim, steam and condensate connections, hot water connections, fuel burning system and connections,

More information

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter

More information

FINNED WATER-TUBE POOL HEATERS

FINNED WATER-TUBE POOL HEATERS HI DELTA, TYPE P - MODELS 992C-2342C SUGGESTED SPECIFICATIONS Catalog No.: 6000.611 Effective: 10-31-16 Replaces: NEW FINNED WATER-TUBE POOL HEATERS - GENERAL 1.1 SUMMARY A. Section includes gas-fired,

More information

Section 2, Reference publications: Updated the referenced publications to the current editions.

Section 2, Reference publications: Updated the referenced publications to the current editions. Summary of Substantive Changes between the 2014 and the 2015 editions of ANSI Z21.10.3 CSA 4.3 Gas fired water heaters, volume III, storage water heaters with input ratings above 75,000 Btu per hour, circulating

More information

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY Fire Department HEADQUARTERS 4410 Cathedral Oaks Road Santa Barbara, CA 93110-1042 (805) 681-5500 FAX: (805) 681-5563 Michael W. Dyer Fire Chief County Fire Warden Eric Peterson Deputy Fire Chief CODE

More information

ACKNOWLEDGEMENT. IIAR expresses its deepest appreciation to these authors for their contributions for the betterment of the industry.

ACKNOWLEDGEMENT. IIAR expresses its deepest appreciation to these authors for their contributions for the betterment of the industry. t ACKNOWLEDGEMENT The success of the 15th Annual Meeting of the International Institute of Ammonia Refrigeration is due to the work of the authors whose technical papers appear in this book. IIAR expresses

More information

2012 International Mechanical Code Significant Changes. About the Significant Changes

2012 International Mechanical Code Significant Changes. About the Significant Changes Significant Changes to the International Mechanical Code and the International Fuel Gas Code With Louisiana Amendments Copyright Materials This presentation is protected by US and International Copyright

More information

ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005

ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005 ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005 Kenneth Kretchman, CIH, CSP Mgr, Industrial Hygiene NC State University Ken_Kretchman@ncsu.edu International Building

More information

Analysis of Changes for the 5 th Edition (2014) of the Florida Codes

Analysis of Changes for the 5 th Edition (2014) of the Florida Codes Analysis of Changes for the 5 th Edition (2014) of the Florida Codes Changes to the Florida Building Code, Fuel-Gas This Analysis of Changes for the 5 th Edition (2014) of the Florida Codes is intended

More information

DIVISION FINNED WATER-TUBE WATER HEATERS

DIVISION FINNED WATER-TUBE WATER HEATERS DELTA LIMITED, TYPE WH - MODELS 399B-899B SUGGESTED SPECIFICATIONS Catalog No.: 3500.97B Effective: 04-01-17 Replaces: 11-15-08 DIVISION 23 52 33.13 FINNED WATER-TUBE WATER HEATERS - GENERAL 1.1 SUMMARY

More information

SECTION GAS-FIRED RADIANT HEATERS

SECTION GAS-FIRED RADIANT HEATERS SECTION 23 55 23 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph

More information

Committee on NFPA 85

Committee on NFPA 85 Committee on NFPA 85 M E M O R A N D U M TO: FROM: NFPA Technical Committee on Single Burner Boilers Patti Mucci, Technical Assistant II DATE: August 5, 2009 SUBJECT: NFPA ROP Letter Ballot The ROP letter

More information

DIVISION WALL-HUNG STAINLESS STEEL HEATING BOILERS

DIVISION WALL-HUNG STAINLESS STEEL HEATING BOILERS XPAK FT TYPE H - MODELS 088AR-398A SUGGESTED SPECIFICATIONS Catalog No.: 2100.91 Effective: 05/01/15 Replaces: new DIVISION 23 52 33.13 WALL-HUNG STAINLESS STEEL HEATING BOILERS PART 1 - GENERAL 1.1 SUMMARY

More information

Gil Rossmiller. In the construction industry for over 30 years. ICC IRC Plumbing & Mechanical Code Development Committee

Gil Rossmiller. In the construction industry for over 30 years. ICC IRC Plumbing & Mechanical Code Development Committee Gil Rossmiller In the construction industry for over 30 years ICC IRC Plumbing & Mechanical Code Development Committee ICC- IECC Commercial Energy Code Development Committee Building Official Parker, Colorado

More information

Notable Changes in the Mechanical Codes

Notable Changes in the Mechanical Codes Notable Changes in the Mechanical Codes July 2004 The following are some of the changes between the 1997 Uniform Mechanical Code and the 2003 International Mechanical Code(M) and the 2003 International

More information

Report on First Revision June 2014 NFPA 5000

Report on First Revision June 2014 NFPA 5000 5000- Log #12 BLD-BSF Final Action: (55.2 (New) ) NOTE: This proposal appeared as Comment 5000-168 (Log #86) which was held from the A11 ROC on Proposal 5000-239. Submitter: Technical Correlating Committee

More information

Adopting Agency BSC SFM. Adopt Entire Chapter X X X X X X X X X X Adopt Entire Chapter as amended (amended sections listed below)

Adopting Agency BSC SFM. Adopt Entire Chapter X X X X X X X X X X Adopt Entire Chapter as amended (amended sections listed below) CALIFORNIA MECANICAL CODE MATRIX ADOPTION TABLE CAPTER CIMNEY AND VENTS Adopting Agency BSC SFM CD DSA OSPD 1 1/AC AC SS SS/CC 1 4 Adopt Entire Chapter X X X X X X X X X X Adopt Entire Chapter as amended

More information

CHAPTER 5 WATER HEATERS

CHAPTER 5 WATER HEATERS CAPTER WATER EATERS Part I 1. General. The regulations of this chapter shall govern the construction, location, and installation of fuelburning and other water heaters heating potable water, together with

More information