A Liquid Desiccant System for Solar Cooling and Dehumidification

Size: px
Start display at page:

Download "A Liquid Desiccant System for Solar Cooling and Dehumidification"

Transcription

1 A Liquid Desiccant System for Solar Cooling and Dehumidification K. Gommed G. Grossman Faculty of Mechanical Engineering, Technion, Israel Institute of Technology, Haifa 32000, Israel The growing demand for air conditioning, particularly in hot and humid climates has caused a significant increase in demand for energy resources. A promising solar technology with potential to alleviate the problem is an open absorption system, where humidity is absorbed directly from the air to be treated by direct contact with the absorbent. The absorbent is then regenerated, again in direct contact with an external air stream, at relatively low temperatures of the heat source. The paper describes a study of a liquid desiccant cooling system designed to air-condition a group of offices on the top floor of a building in the Mediterranean city of Haifa, Israel. The system is capable of using as its source of power low-grade solar heat, of the type obtainable from low-cost flat plate collectors, and has a potential to provide both cooling and dehumidification in variable ratios, as required by the load. Several cycle variations have been considered, corresponding to different design options. A parametric study shows that entrance conditions of the ambient air significantly affect the heat and mass transfer occurring during the dehumidification process. The temperatures and flow rates of the heating and cooling water and the flow rates of solution through the dehumidifier and regenerator affect the humidity of the supply air delivered to the conditioned space, and show an optimum in certain cases. DOI: / Keywords: Dehumidifier, Evaporator, Regenerator, Absorber, Cooling, Dehumidification, Air Conditioning Contributed by the Solar Energy Division of THE AMERICAN SOCIETY OF ME- CHANICAL ENGINEERS for publication in the ASME JOURNAL OF SOLAR ENERGY ENGINEERING. Manuscript received by the ASME Solar Energy Division May 2003; final revision, December Associate Editor: M. Krarti. Introduction The growing demand for air conditioning, particularly in hot and humid climates such as in Mediterranean countries, has caused a significant increase in demand for energy resources. Electric utilities have their peak loads in hot summer days, and are often barely capable of meeting the demand, with brown-out situations. With suitable technology, solar cooling can help alleviate, if not eliminate the problem. It is a good application for solar energy due to the fact that the greatest demand for air conditioning occurs during times of highest insolation 1,2. Conventional closed-cycle absorption chillers require heat source temperatures that are significantly higher than the temperatures of corresponding heat sinks. Thus, they have to be operated with high-grade heat extracted from natural gas, steam, concentrating solar collectors and the like. A promising alternative is the use of an open absorption system, where humidity is absorbed directly from the air to be treated by direct contact with the absorbent. The absorbent is then regenerated, again in direct contact with an external air stream, at relatively low temperatures of the heat source. The entire operation takes place at atmospheric pressure, thus eliminating vacuum vessels and the like. Earlier work has been conducted on liquid desiccant systems for cooling and dehumidification, using solar energy for regeneration. In several cases, direct regeneration of the solution in the sun has been considered, using a special type of collector. Wood and co-workers at Arizona State University 3 6 have constructed and tested a full-scale liquid desiccant system, employing aqueous LiCl as well as an aqueous mixture of LiCl and CaCl 2 as liquid sorbents. Kessling 7 studied a LiCl-water system operating at a large concentration difference between the strong and weak desiccant, to facilitate cold storage by means of a regenerated solution. Kababaev et al report on the operation of a large scale air-conditioning system employing LiCl-water, where both direct regeneration in open collectors and cold storage in the form of regenerated solution have been attempted. Noteworthy are also the liquid desiccant system analyses of Collier 11, Haim et al. 12, and Gandihdasan and Al-Farayedhi 13. This project is concerned with an open absorption solar air conditioning system based on controlled evaporation and dehumidification using liquid desiccants. It is designed to air-condition a group of offices in a typical building and will serve as a prototype for larger systems, to be constructed at a later stage. The system is capable of using as its source of power low-grade solar heat, of the type obtainable from low-cost flat plate collectors and has the potential to provide both cooling and dehumidification in variable ratios, as required by the load. The objective of this work has been to perform an analysis in order to choose the best potential configuration of the solar air conditioning system. Desiccant systems are quite efficient in dealing with the latent load, but considerably less so with regard to the sensible load. A good solution is for the solar-powered desiccant cooling system to deal with the latent heat while an electricpowered heat pump deals with the remaining sensible heat. Under such conditions, the electric heat pump can operate at evaporator temperatures considerably higher than normal as it is not required to cool the air below its dew point in order to dehumidify it, and hence with greater efficiency. The significance of this work lies in the potential to provide solar-powered cooling, dehumidification and air conditioning for residential or commercial applications. The required low-grade heat can be obtained from low-cost flat plate solar collectors, which do not require sun tracking and in some cases can be incorporated in the roof structure of the building. The use of hygroscopic salts in direct contact with moist air provides an attractive alternative to conventional cooling systems employing ozone- Journal of Solar Energy Engineering Copyright 2004 by ASME AUGUST 2004, Vol. 126 Õ 879

2 depleting CFCs. The possibility of using low-grade energy goes a long way toward the elimination of pollution and utilizing renewable and environmentally-safe energy sources. Project Description The system under consideration is designed to air-condition a group of offices total floor area of 35 m 2 ) on the top floor of the Energy Research Center building at the Technion Israel Institute of Technology Haifa, Israel. The city of Haifa is an ideal site to test such a system. Located on the Mediterranean coast at 33 degrees north latitude, it has the typical climate of Mediterranean cities. Outside summer conditions typical for design are 30 C and 70% relative humidity. Room design conditions have been selected at 24 C and 50% relative humidity. A load calculation for the three typically staffed and equipped offices shows about 4.2 kw with a room sensible heat factor RSHF of At 30 cfm (51 m 3 /hr) of fresh air per occupant ASHRAE air quality recommendations, the additional fresh air associated load is about 3.0 kw, most of which 2.4 kw is latent. Thus, the total cooling capacity required is 7.2 kw, with a grand sensible heat factor GSHF of The total supply air circulation needed based on 12 air changes per hour is 0.4 kg/sec 720 cfm. The desired conditions of the supply air are 14.7 C and 86% relative humidity. In considering the liquid desiccant system for performing the air conditioning task, two cooling options are available. Under option A, ambient air mixed with return air is dried in the dehumidifier absorber, to be described in detail in the next section. Leaving the dehumidifier, the air is cooled first in a heat exchanger by cooling water or exhaust air, then cooled further in an auxiliary chiller e.g. electrically-powered vapor compression heat pump and still further in an evaporative cooler before being supplied to the conditioned space. In this option, the desiccant part of the system treats the total supply air the return air together with the fresh air and deals with the latent heat together with part of the sensible heat. The auxiliary chiller deals with the remaining part of the sensible load. In option B, the fresh make-up air, accounting for most of the latent load, is treated separately by the desiccant system while an auxiliary heat pump deals with the sensible load of the rest of the air. Under this option, the fresh air is dried in the dehumidifier, then cooled by heat exchange with the exhaust air in an air-to air heat exchanger, and supplied to the conditioned space. Calculations show that option A has a thermodynamic advantage only when exercising the option of employing an auxiliary chiller with an evaporator temperature considerably higher than normal not requiring to cool the air below its dew point for dehumidification and hence operating at a higher efficiency. Otherwise, option B is preferable, providing a simpler way for controlling the complete system and for incorporating the auxiliary heat pump. Option B also requires considerably less pumping and fan power in the desiccant system than option A. In the final system design, Option B of handling only the fresh air part by the desiccant system was chosen. The desiccant solution is regenerated by solar heat, supplied by flat-plate solar collectors of conventional design, of the type widely employed in Israel for domestic water heating, but with better than average quality to enable higher efficiency at high temperatures. Solar-heated water serves as the heat carrier. The option of heating the regenerated solution directly, by exposing it to the sun and to ambient air simultaneously, had been explored but found to be somewhat problematic. The advantages of the current option are simpler construction technology, simpler storage capability, dirt control and simpler ability for using an air-toair heat exchanger for heat recovery. With the total latent heat load of 2.75 kw, the solar energy demand was calculated to be 4.77 kw. Assuming ten hours of continuous operation daily, and taking a small safety factor, the solar collector area was selected at 20 m 2. Solution storage in the amount of 120 liters of LiCl solution at 43% concentration and a 1000 liter hot water tank added to the system make it possible to operate for a total of four hours with no insolation a typical situation in the summer during the morning hours. Description of the Liquid Desiccant System The liquid desiccant system is designed to serve as an opencycle absorption system that can operate with low-grade solar heat. A detailed description of the desiccant cycle, design considerations that led to the various choices and an experimental investigation of this system is given elsewhere 14. A schematic description of the final design version of the system is given in Fig. 1. The system consists of six major components: an air dehumidifier or absorber, a solution regenerator or desorber, two water-tosolution heat exchangers, a solution-to-solution heat exchanger, and an air-to-air heat exchanger. Arabic numerals indicate working fluids state points at specific locations. Air flow is represented by thick solid lines, solution flow by thin solid lines and water flow by dashed lines. The dehumidifier absorber consists of a packed tower and operates in an adiabatic mode. Ambient air at state 14 entering the bottom of the absorber packed section is brought into contact with a concentrated absorbent solution entering the unit at state 11. Water vapor is removed from the air stream by being absorbed into the solution stream. The dehumidified warm air leaving the absorber at state 15 passes through the blower and leaves the system toward the air-conditioned space for some further treatment under options A or B see the previous section at state 16. The blower controls the flow of air, while raising its temperature slightly. Solution is pumped from the absorber pool at the bottom of the tower into the plate heat exchanger state 10, where it is cooled by water from a cooling tower. The solution leaving the heat exchanger state 11 then proceeds to the distributor at the top of the packing, from where it trickles down in counter-flow to the air stream and collects in the pool. A controlled solution stream is transferred from the absorber pool to the regenerator, as shown state 10c. The return pumped stream from the regenerator 1c goes directly into the pool. As evident, the regenerator desorber device is very similar to the dehumidifier, and so are the flow system and associated components. The solution is heated in the liquid-to-liquid heat exchanger by solar-heated water states 3-4. Ambient air at state 5 is pre-heated in the air-to-air heat exchanger by recovering heat from the exhaust air leaving the desorber state 8. After preheating, the air stream state 6 enters the desorber where it serves to re-concentrate the solution state 2. The exhaust air leaves the desorber state 7, passing through the blower, then pre-heats the entering air stream and is rejected to the environment. The solution-to-solution heat exchanger facilitates pre-heating of the weak solution leaving the dehumidifier states 10c to 10h and recovers heat from the hot strong solution leaving the regenerator states 1h to 1c. The above brief description of the system already reveals a number of advantages of this system over conventional absorption heat pump cycles: 1 The number of main components is reduced by one by transferring condensation of the refrigerant from a condenser to the environment. 2 Capital-intensive pressure-sealed units are avoided as the whole system operates at atmospheric pressure. 3 The amount of refrigerant water evaporated in the regenerator is independent of an evaporator, providing greater flexibility. 4 Efficient utilization of very low heat source temperatures is possible. In the overall setup, the liquid desiccant system is connected in a flow arrangement allowing storage of concentrated solution and a capability to work in three different modes. The first is a manual mode used for testing individual components of the system. The other two modes are automatic, as may be selected by the user. One automatic mode is for full operation of the system FOP and the second is for regeneration only REG. In the automatic FOP mode, all system components operate, including the solution stor- 880 Õ Vol. 126, AUGUST 2004 Transactions of the ASME

3 Fig. 1 Schematic description of the open-cycle desiccant system age circuit, if required. In this case, the absorber solution pump may supply the dehumidifier with solution from both the absorber pool and from the solution storage tank, in parallel. Thus, dehumidification can continue independent of regeneration. If the solar collectors cannot supply water at sufficiently high temperature, or if the concentration of the solution in the storage tank and/or the regenerator pool rises above a set limit, the regeneration side of the system will shut down for a certain time. In the REG mode, only the regenerator desorber side of the system operates. The system shuts down automatically when the concentration of the solution in the storage tank reaches a certain high value or when the temperature of the hot water drops below a certain limit. At the end of days of high insolation, when a large amount of solar heat has been collected, the user can set the system to operate in the automatic REG mode before leaving the site. Practical aspects pertaining to the design, construction and operation have been discussed in the paper by Gommed, Grossman and Ziegler 14, which describes an experimental investigation of the liquid desiccant system. One concern in this type of opencycle system is the prevention of solution carryover. Our experiments have shown that the LiCl solution should not be sprayed, but rather dripped over the packing, with the drops large enough not to be carried away by the air stream. In addition, mist eliminators were incorporated in each of the packed towers, above the solution distributors, as shown in Fig. 1. These two measures were found to eliminate carryover almost completely. It should be noted that LiCl, while somewhat corrosive, is not a toxic material, and does not pose any health hazards; in fact, it possesses bacteriostatic qualities. Anther issue is the cost of such a system; while still in the proof-of-concept stage, it is already clear that the ultimate cost will be dominated by the solar part collector and storage and the ability to employ low-cost flat plate collectors could make this system cost-competitive with other solar air conditioning systems. Parametric Study The lack of reliable data on heat and mass transfer coefficients in the absorption and desorption processes has been a serious impediment in earlier simulation studies to obtaining a good prediction of the system s performance. Particularly critical are the performances of the dehumidifier absorber and regenerator desorber, forming the two key components of the liquid desiccant system. Such data has now been obtained through the experimental work described by Gommed, Grossman and Ziegler, 14. This makes it possible to conduct an extensive parametric study of the overall system behavior. The computer code ABSIM 15,16, developed specifically for simulation of absorption systems in flexible and modular form, was employed in this study. The modular structure of ABSIM makes it possible to simulate a variety of absorption systems in varying cycle configurations and with different working fluids. The code is based on unit subroutines containing the governing equations for the system s components. The components are linked together by a main program, which calls the unit subroutines according to the user s specifications to form the complete cycle. When all the equations for the entire cycle have been established, a mathematical solver routine is employed to solve them simultaneously. Property subroutines contained in a separate database serve to provide thermodynamic properties of the differ- Journal of Solar Energy Engineering AUGUST 2004, Vol. 126 Õ 881

4 Table 1 System parameters for reference case Room air conditions: Temperature, T R 24 C Humidity ratio, R 9.5 g/kg Ambient air conditions: Temperature, T o 30 C Humidity ratio, o 19.0 g/kg Heating water temperature, T HW 65 C Heating water flow rate, F HW 0.25 kg/sec Cooling water temperature, T CW 29.5 C Cooling water flow rate, F CW 0.25 kg/sec Air flow rate through desorber, F DA 0.16 kg/sec Air flow rate through absorber, F AA 0.16 kg/sec Desorber solution pump flow rate, F DS 0.5 kg/sec Absorber solution pump flow rate, F AS 0.5 kg/sec Heat transfer coefficients: desorber heat exchanger, UA DS 1.3 kw/ C absorber heat exchanger, UA AS 1.3 kw/ C solution-solution heat exchanger, UA DAS 1.3 kw/ C desorber air-to-air heat exchanger, UA DA 0.5 kw/ C absorber air-to-air heat exchanger, UA AA 0.5 kw/ C Mass transfer coefficients: desorber solution-interface, KA DS 0.36 kg/sec desorber air-interface, KA DA 1.00 kg/sec absorber solution-interface, KA AS 0.36 kg/sec absorber air-interface, KA AA 1.00 kg/sec ent working fluids. The property subroutine for LiCl-water, the particular working fluid employed in this study, contains correlations derived from the work of Uemura 17. The computer simulation yields the temperature and humidity of the air at the system outlets as well as heat duties of the various system components as functions of the specified conditions at inlets and other operating conditions. The behavior is quite complex and depends on many input parameters. In conducting the simulation, a design reference case has been selected, and the values of the relevant parameters were varied around it. The values of the various parameters influencing the problem for the reference case are listed in Table 1. When conducting the following parametric study, only one parameter from those listed in Table 1 was varied at a time, while all others remained fixed at their design value. The reference condition is indicated on each curve by a dot. Figure 2 describes the humidity ratio water content of the supply air to the conditioned space, which has been dehumidified by the desiccant system state 16 in Fig. 1, as a function of the inlet conditions of the ambient air supplied to the dehumidifier state 14 in Fig. 1. Three curves are shown representing the temperature, humidity ratio and flow rate of the ambient air. As expected, the absorption rate dehumidification performance of the desiccant system increases as each of these quantities decreases. The slope of the flow rate curve tends to become flat at the higher air flow rates. A similar behavior is exhibited by the regenerator heat duty as a function of the flow rate of ambient air being dehumidified not shown here. This behavior is due to the limited heat and mass transfer capacity area and coefficient, causing the driving force to diminish at the high flow rates. A heat duty of 6.13 kw is found to be required for regeneration at the reference condition, where the flow rate of ambient air supplied is 0.16 kg/sec. Figure 2 further indicates that the water content and flow rate of the ambient air supplied to the absorber have a more significant effect on the system performance than the temperature. Figure 3 describes the effect of the temperature of the hot water produced by the solar collectors on the strong solution concentration reached at the regenerator outlet. Clearly, the higher the heating temperature-the higher the solution concentration. At a hot water temperature of 70 C the solution concentration is about 43%, which is the preferred working concentration. It is high enough to produce a good degree of dehumidification in the absorber, while staying safely away from the crystallization limit of the solution. Fig. 2 Humidity ratio of supply air as function of inlet conditions of ambient air to dehumidifier Figure 4 describes the humidity ratio water content of the supply air to the conditioned space as a function of the conditions of the heating and cooling water supplied to the two water/ solution heat exchangers state points 3 and 12, respectively, in Fig. 1. Four curves are shown representing the heating water and cooling water temperature and flow rate. It is evident that the higher the heating water temperature and the lower the cooling water temperature-the better the dehumidification. A cooling water temperature of 29.5 C, selected for the reference condition, is a high-probability upper limit for the weather conditions of Haifa. During many summer days, lower cooling water temperatures can be produced by the cooling tower and therefore better performance. The humidity ratio tends toward a constant value as the heating and cooling water flow rates increase. This is again due to the limited heat transfer capacity in the solution/water heat exchangers, resulting in diminishing driving force at the high water Fig. 3 Effect of heating water temperature on strong solution concentration at regenerator outlet 882 Õ Vol. 126, AUGUST 2004 Transactions of the ASME

5 Fig. 6 Humidity ratio of supply air as a function of solution flow rate in the dehumidifier and split ratio in the regenerator Fig. 4 Humidity ratio of supply air as a function of heating and cooling water conditions flow rates. Keeping pumping power in mind, it is preferable to select the heating and cooling water flow rates in the range between 0.2 to 0.4 kg/sec 0.25 kg/sec for the reference condition. Figure 5 describes the effect of desiccant solution flow rate in the regenerator on several performance parameters. Three curves are shown representing the solution concentration at the desorber outlet, the supply air humidity ratio and the desorber heat duty. Here an optimum humidity ratio is reached when the solution flow rate is in the range between 0.4 to 0.6 kg/sec 0.5 kg/sec is the reference condition. The explanation for this is as follows: When the solution flow rate in the regenerator is low, the flow rate of strong solution reaching the absorber is low too. Then, the resulting low solution concentration in the absorber causes a reduction in absorber performance, and leads to higher water content in the supply air. Increasing solution flow rate in the regenerator, on the other hand, increases the system circulation losses due to the transfer of solution from the hot desorber to the cold absorber through a non-ideal solution-to-solution heat exchanger. The same considerations explain the existence of a maximum in the solution concentration at the desorber outlet: The reduction of the concentration from the maximum value at high solution flow rates is due to increased circulation losses. At low flow rates, a low equilibrium temperature of the solution during adiabatic regeneration leads to low solution concentrations. The regenerator heat duty curve shows a rapid increase in slope at low flow rates due to intensive dehumidification in the absorber. Beyond a solution flow rate of 0.4 kg/sec, the desorber heat duty increases more gradually due to increasing circulation losses. Figure 6 describes the humidity ratio of the supply air to the conditioned space as a function of two parameters: The split ratio in the desorber and the solution flow rate in the absorber. At the desorber outlet the solution is split into two streams, as shown in Fig. 1. The main stream state point 1 flows to the desorber inlet at the top, passing through the hot water heat exchanger. The second, smaller stream state point 1h flows to the absorber, passing through the solution-to-solution heat exchanger. The Split ratio is defined as the flow rate of the main stream to the total desorber flow rate. Figure 6 shows a seemingly unexpected behavior of increasing water content in the supply air with increasing desiccant solution flow rate in the absorber. A high solution flow rate has the advan- Fig. 5 Effect of desiccant solution flow rate in the regenerator on supply air humidity, solution concentration at regenerator outlet and regenerator heat duty Journal of Solar Energy Engineering AUGUST 2004, Vol. 126 Õ 883

6 tage of reduced sensitivity to the temperature increase due to the heat of absorption released during the dehumidification process, together with good wetting of the transfer surfaces. However, lowering the temperature of this solution stream in the heat exchanger by the cooling water becomes increasingly difficult with increasing solution flow rate. A higher solution temperature at the absorber inlet leads to higher equilibrium water content of the supply air. Lowering the split ratio increases the amount of strong solution transferred from the desorber to absorber. On one hand this leads to increased solution concentration in the absorber and hence to improved dehumidification. On the other hand, increasing solution flow rate between desorber and absorber increases the associated circulation losses. These two mechanisms working against each other are responsible for the behavior shown in Fig. 6. Increased dehumidification together with increased circulation losses related to a higher split ratio, both lead to an increased desorber heat duty. Figure 7 describes the system s coefficient of performance COP as a function of the heating water temperature for three different cooling water temperatures. The COP is defined here as the ratio of the useful dehumidification energy to the heat spent in the desorber. The useful dehumidification energy is the product of the change in humidity ratio of the process air, times the mass flow rate of the process air, times the latent heat of evaporation of the water. It was mentioned already in connection with Fig. 3 that an operating temperature of 70 C yields regenerated solution at 43%, which gives it good hygroscopic behavior while staying safely away from crystallization. Figure 7 indicates that for steady state operation at higher temperatures the COP decreases; this is due to increased desorber heat duty, resulting from increased circulation losses associated with the imperfect heat transfer between the weak and strong solution streams and mixing losses associated with the increased solution concentration. On the other hand, at very low heating temperatures, close to that of the heat sink, the system continues to operate and the COP is high, approaching unity. However, under such conditions the dehumidification process is very weak and the change in humidity ratio of the process air is extremely low. These simulation results are obtained assuming steady state operation; in practice, one can operate for short periods of time in batch mode, without reaching steady state, or in regeneration mode where the regenerator operates alone, without circulation to the absorber. Under these conditions, the circulation and mixing losses can be reduced and a high overall COP around 0.8 can be achieved with high regeneration temperatures, when available. In fact, the regeneration mode is preferred and often used at times of high insolation, to concentrate and store regenerated solution for operation at times of no sun. Results of measurements while operating in this mode, conducted during a five-months monitoring period over the summer of 2003, will be reported in a later paper 18. Fig. 7 Coefficient of performance COP as a function of heating water temperature for three different cooling water temperatures refä29.5 C, per Table 1 Conclusion Several cycle configurations of the desiccant cooling system have been considered. Option B was found to be the most suitable for the current application, as it utilizes best the strong points of the desiccant system. Under this option, the solar powered desiccant system deals with the latent heat load, due mainly to the fresh air, while an auxiliary electric-powered heat pump deals with the remaining sensible load. A parametric study was conducted to investigate the effect of the various design parameters on performance. It was shown that entrance conditions of the ambient air humidity and flow rate significantly affect the heat and mass transfer occurring during the dehumidification process. The effect of the ambient air temperature is rather low. The temperatures and flow rates of the heating and cooling water and the flow rates of solution through the dehumidifier and regenerator affect the humidity of the supply air delivered to the conditioned space, and show an optimum in certain cases. The computer simulation supported by experiments has affirmed the system s capability to produce a high degree of dehumidification. The system designed and simulated for the current application contains a margin for future applicability to other system loads or configurations. Acknowledgment The support provided for this work under EU contract NNE ASODECO is gratefully acknowledged. References 1 Grossman, G., and Johannsen, A., 1981, Solar Cooling and Air Conditioning, Prog. Energy Combust. Sci., 7, pp Grossman, G., 2002, Solar-powered Systems for Cooling, Dehumidification and Air-conditioning, Sol. Energy, 72, pp Ameel, T. A., Gee, K. G., and Wood, B. D., 1995, Performance Predictions of Alternative, Low Cost Absorbents for Open-Cycle Absorption Solar Cooling, Sol. Energy, 54, pp Nelson, D. J., and Wood, B. D., 1989, Combined Heat and Mass Transfer Natural Convection Between Vertical Parallel Plates, Int. J. Heat Mass Transfer, 32, pp Nelson, D. J., and Wood, B. D., 1989, Fully Developed Combined Heat and Mass Transfer Natural Convection Between Parallel Plates with Asymmetric Boundary, Int. J. Heat Mass Transfer, 32, pp Nelson, D. J., and Wood, B. D., 1989, Evaporation Rate Model for a Natural Convection Glazed Collector/Regenerator, ASME J. Sol. Energy Eng., 112, pp Kessling, W., 1997, Luftentfeuchtung und Energiespeicherung mit Salzlösungen in offenen Systemen, Fortschritt-Bericht 509, VDI Verlag, Düsseldorf, Germany. 8 Kakabaev, A., Khandurdyev, A., Klyshchaeva, O., and Kurbanov, N., 1976, A Large Scale Solar Air-Conditioning Pilot Plant and its Test Results, Int. Chem. Eng., 16, pp Kakabaev, A., Klyshchaeva, O., Khandurdyev, A., and Kurbanov, N., 1977, Experience in Operation a Solar Absorption Cooling Plant with Open Solution Regenerator, Geliotekhika, 13, pp Kakabaev, A., Kurbanov, N., Klyshchaeva, O., and Redzhepov, G., 1981, Storage of Cold in an Open-cycle Solar Absorption Cooling System, Geliotekhika, 17, pp Collier, R. K., 1979, The Analysis and Simulation of an Open Cycle Absorption Refrigeration System, Sol. Energy, 23, pp Haim, I., Grossman, G., and Shavit, A., 1992, Simulation and Analysis of Open Cycle Absorption Systems for Solar Cooling, Sol. Energy, 49, pp Gandihdasan, P., and Al-Farayedhi, A., 1995, Thermal Performance Analysis of a Partly Closed-Open Solar Regenerator, ASME J. Sol. Energy Eng., 117, pp Gommed, K., Grossman, G., and Ziegler, F., 2002, Experimental Investigation of a LiCl-Water Open Absorption System for Cooling and Dehumidification, Proceedings, the 7th International Sorption Heat Pump Conference, Shanghai, China, September 24 27, pp Also ASME Journal of Solar Energy Engineering, May 2004 In Press. 884 Õ Vol. 126, AUGUST 2004 Transactions of the ASME

7 15 Grossman, G., and Wilk, M., 1994, Advanced Modular Simulation of Absorption Systems, Int. J. Refrig., 17, pp Grossman, G., and Zaltash, A., 2001, ABSIM Modular Simulation of Advanced Absorption Systems, Int. J. Refrig., 24, pp Uemura, T., 1967, Studies on the LiCl-Water Absorption Refrigeration Machine, Technology Reports of the Kansai University, Osaka, Japan, 9, pp Gommed, K., and Grossman, G., 2004, Experimental Study of a Liquid Desiccant System for Solar Cooling and Dehumidification, Presented at EuroSun 2004, Freiburg, Germany, June Journal of Solar Energy Engineering AUGUST 2004, Vol. 126 Õ 885

Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations

Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations 43rd ANZSES Conference Solar 24, Denedin (NZ), 28.11.-3.11.5, CD Abstract Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations M., W. Saman, K. Vajen* Sustainable

More information

Theoretical Performance Analysis of a Liquid Desiccant Air- Conditioning System for Air Heating and Cooling

Theoretical Performance Analysis of a Liquid Desiccant Air- Conditioning System for Air Heating and Cooling Proc. 2nd International Confirence Solar Air-Conditioning, Tarragona (ES), 18.-19.10.07, CD Theoretical Performance Analysis of a Liquid Desiccant Air- Conditioning System for Air Heating and Cooling R.

More information

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant Proceedings of the World Congress on Momentum, Heat and Mass Transfer (MHMT 16) Prague, Czech Republic April 4 5, 216 Paper No. ENFHT 111 DOI: 1.11159/enfht16.111 Experimental Investigation of a Multi

More information

Regenerator Design for Open Cycle Liquid Desiccant Systems Theoretical and Experimental Investigations

Regenerator Design for Open Cycle Liquid Desiccant Systems Theoretical and Experimental Investigations Proc. International Conference Air-Conditioning, Staffelstein (DE), 6.-7.10.2005, pp. 236-240 Design for Open Cycle Liquid Desiccant Systems Theoretical and Experimental Investigations M. Krause, W. Saman,

More information

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement International Conference Passive and Low Energy Cooling 651 Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

More information

Experimental study on mass transfer comparison of two liquid desiccants aqueous solutions

Experimental study on mass transfer comparison of two liquid desiccants aqueous solutions International Conference on Renewable Energies and Power Quality (ICREPQ ) Cordoba (Spain), th to th April, 0 exçxãtuäx XÇxÜzç tçw céãxü dâtä àç ]ÉâÜÇtÄ (RE&PQJ) ISSN 1-03 X, No., April 0 Experimental

More information

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System Feasibility of a Liquid Desiccant Application in an Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, S.K.Han 1, S.Y. Cho 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang

More information

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System 4 th International Conference On Building Energy Environment Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System J Y Park H W

More information

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area MMS DEZFOULI, SOHIF MAT, K.SOPIAN Solar Energy Research Institute (SERI, Universiti

More information

solution, due to the partial vapor pressure difference between the air and the desiccant solution. Then, the moisture from the diluted solution is rem

solution, due to the partial vapor pressure difference between the air and the desiccant solution. Then, the moisture from the diluted solution is rem A Simplified model for estimating the regeneration effectiveness of a counter flow regenerator for a liquid desiccant system M.H. Kim 1, H.J. Cho 1, and J.W. Jeong 1* 1 Division of Architectural Engineering,

More information

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, J.Y.Park 1, E.J.Lee 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang University,

More information

Experimental Performance of Solar Collector cum Regenerator for Coupling with a Liquid Desiccant Cooling System

Experimental Performance of Solar Collector cum Regenerator for Coupling with a Liquid Desiccant Cooling System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Experimental Performance of Solar Collector cum Regenerator for Coupling

More information

Modelling the Performance of a Diffusion Absorption Refrigeration System

Modelling the Performance of a Diffusion Absorption Refrigeration System Modelling the Performance of a Diffusion Absorption Refrigeration System Noman Yousuf 1, Etienne Biteau 2, Timothy Anderson 1, Michael Gschwendtner 1 and Roy Nates 1 1 School of Engineering, Auckland University

More information

Recent Advances in Energy, Environment and Economic Development

Recent Advances in Energy, Environment and Economic Development Experimental Investigation of Solar Hybrid Desiccant Cooling System in Hot and Humid Weather of Malaysia MM SALEHI DEZFOULI, Z HASHIM, MH RUSLAN, B BAKHTYAR, K SOPIAN, A ZAHARIM, S MAT, A RACHMAN, Solar

More information

Conditioning of outdoor air using rotating disk type liquid desiccant-air contacting device

Conditioning of outdoor air using rotating disk type liquid desiccant-air contacting device Conditioning of outdoor air using rotating disk type liquid desiccant-air contacting device J R Mehta 1, A A Sujela 2 1 Department of Mechanical Engineering, Faculty of Technology and Engineering,The Maharaja

More information

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering July 2018 Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to

More information

Optimization of Moisture condensation rate of Liquid Desiccant Dehumidifier through Genetic Algorithm

Optimization of Moisture condensation rate of Liquid Desiccant Dehumidifier through Genetic Algorithm International Journal of ChemTech Research CODEN (USA): IJCRGG ISSN: 0974-4290 Vol.7, No.01, pp 400-407, 2014-2015 Optimization of Moisture condensation rate of Liquid Desiccant Dehumidifier through Genetic

More information

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015) 4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015) Multi-stage Series Heat Pump Drying System with Dehumidification Simulation and Experiment Verification Chao

More information

COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM

COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM Suhail Ahmad Khan Department of Mechanical Engineering, Aligarh Muslim University, Aligarh (India) ABSTRACT Energy analysis

More information

Desiccant Cooling with Solar Energy

Desiccant Cooling with Solar Energy Desiccant Cooling with Solar Energy Gerrit Höfker 1,2, Ursula Eicker 2, Kevin Lomas 1, Herbert Eppel 1 1 De Montfort University Leicester, Institute of Energy and Sustainable Development 2 Hochschule für

More information

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump IOP Conference Series: Earth and Environmental Science PAPER OPEN ACCESS Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump To cite this article: Yefeng Liu et al 2018 IOP

More information

Experimental Investigation of a Hybrid Evacuated Tube Solar Collector

Experimental Investigation of a Hybrid Evacuated Tube Solar Collector International Conference on Mechanical, Industrial and Materials Engineering 2015 (ICMIME2015) 11-13 December, 2015, RUET, Rajshahi, Bangladesh Paper ID: ET-46 Experimental Investigation of a Hybrid Evacuated

More information

Performance analysis of a liquid desiccant evaporative cooling airconditioning system powered by solar energy

Performance analysis of a liquid desiccant evaporative cooling airconditioning system powered by solar energy Performance analysis of a liquid desiccant evaporative cooling airconditioning system powered by solar energy F. Zhang 1, Y. Yin 1,2* and X. Zhang 1,2 1 School of Energy and Environment Southeast University,

More information

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING V. Vakiloroaya*, J.G. Zhu, and Q.P. Ha School of Electrical, Mechanical and Mechatronic Systems,

More information

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE Journal of Sustainability Science and Management Volume 9 Number 1, June 2014: 150-155 ISSN: 1823-8556 Penerbit UMT PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE ARFIDIAN

More information

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance #1 Jaydev S. Bade, #2 Dr. Nitin U. Korde 1 Department of Mechanical Engineering, Savitribai Phule

More information

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Abstract Shoeb J. Inamdar 1 H.S. Farkade 2 M. Tech student. (Thermal Engineering) 1, Asst. Professor 2 Department of Mechanical

More information

Adsorption refrigeration system using waste heat

Adsorption refrigeration system using waste heat Adsorption refrigeration system using waste heat 1 RISHI SREEKUMAR, 2 SANJEEV SINGH, 3 HIMANSHU SHEKHAR, 4 RAUSHAN KUMAR, 5 Dr. R. S. BINDU 1,2,3,4 BE Students, 5 Professor Mechanical Engineering Department

More information

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology IJIRST International Journal for Innovative Research in Science & Technology Volume 1 Issue 11 April 2015 ISSN (online): 2349-6010 CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

More information

Impact of indirect evaporative air cooler type on the performance of desiccant systems

Impact of indirect evaporative air cooler type on the performance of desiccant systems Impact of indirect evaporative air cooler type on the performance of desiccant systems Anna Pacak 1,*, Aleksandra Cichoń 1, Demis Pandelidis 1, and Sergey Anisimov 1 1 Wrocław University of Science and

More information

Potential and Simulation of Open-Cycle Solar-Assisted Climatisation-Plants in Single-Family-Houses

Potential and Simulation of Open-Cycle Solar-Assisted Climatisation-Plants in Single-Family-Houses Proc. International Conference Solar Air-Conditioning, Staffelstein (DE), 6.-7.10.2005, pp. 236-240 Potential and Simulation of Open-Cycle Solar-Assisted Climatisation-Plants in Single-Family-Houses R.Heinzen,

More information

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY Xiaoyun Xie, Yidan Tang, Xiaoqin Yi, Shuanqiang Liu,Yi Jiang Department of Building Science and Technology,

More information

STUDY ON HYBRID SYSTEM OF SOLAR POWERED WATER HEATER AND ADSORPTION ICE MAKER

STUDY ON HYBRID SYSTEM OF SOLAR POWERED WATER HEATER AND ADSORPTION ICE MAKER , Volume 6, Number 4, p.168-172, 2005 STUDY ON HYBRID SYSTEM OF SOLAR POWERED WATER HEATER AND ADSORPTION ICE MAKER Zhaohui Qi School of Energy Science and Engineering, Centralsouth University, Changsha,

More information

Performance of solid desiccant-based evaporative cooling system under the climatic zones of India

Performance of solid desiccant-based evaporative cooling system under the climatic zones of India *Corresponding author: hemant_parmar1@ rediffmail.com Performance of solid desiccant-based evaporative cooling system under the climatic zones of India... H. Parmar 1 * and D.A. Hindoliya 2 1 Department

More information

INSTITUTE FOR ENVIRONMENTAL RESEARCH & SUSTAINABLE DEVELOPMENT NATIONAL OBSERVATORY OF ATHENS (NOA)

INSTITUTE FOR ENVIRONMENTAL RESEARCH & SUSTAINABLE DEVELOPMENT NATIONAL OBSERVATORY OF ATHENS (NOA) 1 SOLAR COOLING An Overview of European Applications & Design Guidelines Costas Balaras, Ph.D. Member ASHRAE, Mechanical Engineer, Research Director GRoup Energy Conservation (GR.E.C.) INSTITUTE FOR ENVIRONMENTAL

More information

GSJ: VOLUME 6, ISSUE 6, JUNE GSJ: Volume 6, Issue 6, June 2018, Online: ISSN

GSJ: VOLUME 6, ISSUE 6, JUNE GSJ: Volume 6, Issue 6, June 2018, Online: ISSN GSJ: VOLUME 6, ISSUE 6, JUNE 2018 189 GSJ: Volume 6, Issue 6, June 2018, Online: ISSN 2320-9186 ANALYSIS OF A VAPOUR ABSORPTION REFRIGERATION CYCLE POWERED BY A SOLAR SYSTEM Taiwo O. Oni Department of

More information

Experimental Investigation of the Padding Tower 1. for Air Dehumidifier

Experimental Investigation of the Padding Tower 1. for Air Dehumidifier Experimental Investigation of the Padding Tower 1 for Air Dehumidifier Jin Wang Jianhua Liu Cunnan Li Guangli Zhang Shouchao An Associate Associate graduate Engineer Prelector Professor Professor Student

More information

Using the Open Source SorpSim for Simulation of Sorption Water Heating Applications

Using the Open Source SorpSim for Simulation of Sorption Water Heating Applications Using the Open Source SorpSim for Simulation of Sorption Water Heating Applications Zhiyao Yang Dr. Ming Qu Dr. Kyle R. Gluesenkamp Dr. Omar Abdelaziz 2/28/2017 ACEEE Hot Water Forum, Portland OR ORNL

More information

ANALYSIS OF DESICCANT COOLING SYSTEM

ANALYSIS OF DESICCANT COOLING SYSTEM Int. J. Mech. Eng. & Rob. Res. 2012 Gaurav Pundir and S N Mishra, 2012 Research Paper ISSN 2278 0149 www.ijmerr.com Vol. 1, No. 3, October 2012 2012 IJMERR. All Rights Reserved ANALYSIS OF DESICCANT COOLING

More information

Performance evaluation of a liquid desiccant solar air conditioning system

Performance evaluation of a liquid desiccant solar air conditioning system Available online at www.sciencedirect.com Energy Procedia 3 (212 ) 542 55 SHC 212 Performance evaluation of a liquid desiccant solar air conditioning system Lisa Crofoot a, Stephen Harrison b a,b McLaughlin

More information

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road 517583 AUTONOMOUS QUESTION BANK (DESCRIPTIVE) Subject with Code : Refrigeration and Air Conditioning (16ME8806) Course & Branch:

More information

K.F. Fong *, C.K. Lee, T.T. Chow

K.F. Fong *, C.K. Lee, T.T. Chow Investigation on radiative load ratio of chilled beams on performances of solar hybrid adsorption refrigeration system for radiant cooling in subtropical city K.F. Fong *, C.K. Lee, T.T. Chow Building

More information

Dynamic performance of a novel dew point air conditioning for the UK buildings

Dynamic performance of a novel dew point air conditioning for the UK buildings *Corresponding author: xudongzhao@nottingham. ac.uk Dynamic performance of a novel dew point air conditioning for the UK buildings... Xudong Zhao *, Zhiyin Duan, Changhong Zhan and Saffa B. Riffat School

More information

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible

More information

Performance of the Cross Flow Regenerator Used in Liquid Desiccant Dehumidification.

Performance of the Cross Flow Regenerator Used in Liquid Desiccant Dehumidification. Performance of the Cross Flow Regenerator Used in Liquid Desiccant Dehumidification. Archit Kumar Vias 1, Rakesh Thakur 2 1,2 Research scholar, Punjab Technical University, Kapurthala, Punjab, India. Abstract-The

More information

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger International Journal of ChemTech Research CODEN( USA) IJCRGG ISSN 0974-4290 Vol.5, No.2, pp 925-934, April-June 2013 ICGSEE-2013[14th 16th March 2013] International Conference on Global Scenario in Environment

More information

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former A study on reducing the energy demand of a liquid desiccant dehumidifier with a radiant panel system Tae Ha Leigh, 1 Dae Uk Shin, 1 Goo Sang Joe, 1 Min Gi Kim, 1 Myoung Souk Yeo, 2 and Kwang Woo Kim 2,*

More information

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning Available online at www.sciencedirect.com Systems Engineering Procedia () 6 International Conference on Risk and Engineering Management (REM) Thermodynamic analysis of air cycle refrigeration system for

More information

Performance of solar-assisted hybrid air-conditioning liquid desiccant system in Beirut

Performance of solar-assisted hybrid air-conditioning liquid desiccant system in Beirut Performance of solar-assisted hybrid air-conditioning liquid desiccant system in Beirut N. Ghaddarl, K. Ghali2 & A. ~ajm' I American University of Beirut, Faculty of Engineering and Architecture, Beirut

More information

SIMULATION OF A NEW TYPE GAS-FIRED AIR-COOLED AIR-CONDITIONER. Lin Wang, Xing Xu, Aihua Ma, Yonghui Guo and Xiwen Zhou

SIMULATION OF A NEW TYPE GAS-FIRED AIR-COOLED AIR-CONDITIONER. Lin Wang, Xing Xu, Aihua Ma, Yonghui Guo and Xiwen Zhou SIMULATION OF A NEW TYPE GAS-FIRED AIR-COOLED AIR-CONDITIONER Lin Wang, Xing Xu, Aihua Ma, Yonghui Guo and Xiwen Zhou College of Civil Engineering and Architecture Henan University of Science and Technology,

More information

Impact of TXV and Compressor in the Stability of a High-End Computer Refrigeration System

Impact of TXV and Compressor in the Stability of a High-End Computer Refrigeration System Yasin Makwana Dereje Agonafer Fellow ASME Mechanical and Aerospace Engineering Department, University of Texas at Arlington, Box 19018, Arlington, TX 76019 Dan Manole Tecumseh Products Company, Tecumseh,

More information

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER University of Maiduguri Faculty of Engineering Seminar Series Volume 6, december 5 ASSESSMENT OF REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R34A REFRIGERANT IN LARGE CAPACITY FREEZER S. Shodiya*, M.B. Oumarou

More information

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM 111 CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM 7.1 INTRODUCTION Energy is the primary component to run any system in the world. According to

More information

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA Ninth International IBPSA Conference Montréal, Canada August 15-18, 25 SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS Chaoqin Zhai 1, Xiaohong

More information

Heat pump and energy recovery systems

Heat pump and energy recovery systems SBS5311 HVACR II http://ibse.hk/sbs5311/ Heat pump and energy recovery systems Ir. Dr. Sam C. M. Hui Faculty of Science and Technology E-mail: cmhui@vtc.edu.hk Oct 2017 Contents Basic concepts Air-to-air

More information

EFFECT OF DIVERSE STREAM PATTERNS ON THE PERFORMANCE OF SOLAR AIR HEATER

EFFECT OF DIVERSE STREAM PATTERNS ON THE PERFORMANCE OF SOLAR AIR HEATER Int. J. Mech. Eng. & Rob. Res. 2013 P Velmurugan and R Kalaivanan, 2013 Research Paper ISSN 2278 0149 www.ijmerr.com Vol. 2, No. 1, January 2013 2013 IJMERR. All Rights Reserved EFFECT OF DIVERSE STREAM

More information

Development of a Sorption Assisted Air Conditioning System Driven by a Solar Air Collector

Development of a Sorption Assisted Air Conditioning System Driven by a Solar Air Collector Development of a Sorption Assisted Air Conditioning System Driven by a Solar Air Collector Gunther M. Munz, C. Bongs, A. Morgenstern, Y. Tiedtke, H. Kummer, H.-M. Henning and Stefan K. Henninger Fraunhofer

More information

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length HEIMO WALTER Institute for Thermodynamics and Energy Conversion Vienna University

More information

Experimental Investigation of a Heat Pump Assisted Fluidized Bed Dryer

Experimental Investigation of a Heat Pump Assisted Fluidized Bed Dryer GRD Journals- Global Research and Development Journal for Engineering Volume 2 Issue 6 May 2017 ISSN: 2455-5703 Experimental Investigation of a Heat Pump Assisted Fluidized Bed Dryer Gokul G Nair Dr. Jeoju

More information

Computerized Simulation of Automotive Air-Conditioning System: A Parametric Study

Computerized Simulation of Automotive Air-Conditioning System: A Parametric Study www.ijcsi.org 787 Computerized Simulation of Automotive Air-Conditioning System: A Parametric Study Haslinda Mohamed Kamar 1, Nazri Kamsah 2 and Mohd Yusoff Senawi 3 1 Department of Thermo-Fluid, Universiti

More information

EVALUATION OF A LIQUID DESICCANT AIR CONDITIONING SYSTEM WITH SOLAR THERMAL REGENERATION

EVALUATION OF A LIQUID DESICCANT AIR CONDITIONING SYSTEM WITH SOLAR THERMAL REGENERATION EVALUATION OF A LIQUID DESICCANT AIR CONDITIONING SYSTEM WITH SOLAR THERMAL REGENERATION Stephen J. Harrison, Ph.D., P.Eng. Solar Calorimetry Laboratory Queen s University Kingston, Canada Overview Main

More information

So far, we have covered the basic concepts of heat transfer and properties.

So far, we have covered the basic concepts of heat transfer and properties. ET3034TUx - 6.2.2 - Solar thermal energy 2 - Solar thermal heating So far, we have covered the basic concepts of heat transfer and properties. Now we are going to discuss the applications of these concepts

More information

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant M. Honma, T. Tamura, Y. Yakumaru and F. Nishiwaki Matsushita Electric Industrial Co., Ltd. Living Environment

More information

System Modeling of Gas Engine Driven Heat Pump

System Modeling of Gas Engine Driven Heat Pump Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 01 System Modeling of Gas Engine Driven Heat Pump Isaac Mahderekal shenb@ornl.gov

More information

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid Simulation Analysis of Compression Refrigeration Cycle with Different Refrigerants P.Thangavel, Dr.P.Somasundaram, T.Sivakumar, C.Selva Kumar, G.Vetriselvan Abstract --- In this analysis, the performance

More information

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers e-issn 2455 1392 Volume 2 Issue 5, May 2016 pp. 108-116 Scientific Journal Impact Factor : 3.468 http://www.ijcter.com Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl

More information

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 1. OBJECTIVE The objective of this experiment is to observe four basic psychrometric processes

More information

EVALUATION OF HEAT REJECTION STRATEGIES FOR LIQUID DESICCANT AIR-CONDITIONING SYSTEMS

EVALUATION OF HEAT REJECTION STRATEGIES FOR LIQUID DESICCANT AIR-CONDITIONING SYSTEMS EVALUATION OF HEAT REJECTION STRATEGIES FOR LIQUID DESICCANT AIR-CONDITIONING SYSTEMS by Danial Salimizad A thesis submitted to the Department of Mechanical and Materials Engineering in conformity with

More information

COMPACT ADSORPTION CHILLERS WITH COATED ADSORBER HEAT EXCHANGERS

COMPACT ADSORPTION CHILLERS WITH COATED ADSORBER HEAT EXCHANGERS - 1 - COMPACT ADSORPTION CHILLERS WITH COATED ADSORBER HEAT EXCHANGERS W. Mittelbach, Managing Director, SorTech AG, Weinbergweg 23, 06120 Halle, Germany T. Büttner, Head of R&D / production, SorTech AG,

More information

Desiccant-enhanced evaporative (DEVap) cooler system introduction and its comparison with direct expansion (DX) system

Desiccant-enhanced evaporative (DEVap) cooler system introduction and its comparison with direct expansion (DX) system Applied Science Reports www.pscipub.com/asr E-ISSN: 2310-9440 / P-ISSN: 2311-0139 DOI: 10.15192/PSCP.ASR.2015.11.1.1621 App. Sci. Report. 11 (1), 2015: 16-21 PSCI Publications Desiccant-enhanced evaporative

More information

FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE

FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE HEFAT2012 9 th International nference on Heat Transfer, Fluid Mechanics and Thermodynamics 16 18 July 2012 Malta FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE Kim K.,

More information

Performance Of The Dehumidification Cycle Of A 3-Fluid Liquid Desiccant Membrane Air-Conditioning System

Performance Of The Dehumidification Cycle Of A 3-Fluid Liquid Desiccant Membrane Air-Conditioning System Performance Of The Dehumidification Cycle Of A 3-Fluid Liquid Desiccant Membrane Air-Conditioning System Devin Storle 1, Mohamed R.H. Abdel-Salam 2, Nader Pourmahmoud 3, Carey J. Simonson 4 1 MSc, University

More information

EFFECT OF WATER RADIATOR ON AIR HEATING SOLAR COLLECTOR EFFICIENCY

EFFECT OF WATER RADIATOR ON AIR HEATING SOLAR COLLECTOR EFFICIENCY EFFECT OF WATER RADIATOR ON AIR HEATING SOLAR COLLECTOR EFFICIENCY Aivars Aboltins, Janis Palabinskis Latvia University of Agriculture aivars.aboltins@inbox.lv Abstract. The paper describes the results

More information

Development of simulation modules for liquid desiccant systems in SorpSim

Development of simulation modules for liquid desiccant systems in SorpSim Purdue University Purdue e-pubs Open Access Theses Theses and Dissertations Spring 2015 Development of simulation modules for liquid desiccant systems in SorpSim Zhiyao Yang Purdue University Follow this

More information

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

Available online at   Energy Procedia 6 (2011) MEDGREEN 2011-LB Available online at www.sciencedirect.com Energy Procedia 6 (2011) 759 768 MEDGREEN 2011-LB Comparison of two methods of improving dehumidification in air conditioning systems: hybrid system (refrigeration

More information

The Use Of Attic Space For Cooling and Dehumidification

The Use Of Attic Space For Cooling and Dehumidification Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2002 The Use Of Attic Space For Cooling and Dehumidification H. F. Abaza Virginia

More information

Adsorption Chillers Energysmart Green Cooling

Adsorption Chillers Energysmart Green Cooling Adsorption Chillers Energysmart Green Cooling New Partners in innovation Leaders in Dehumidification... Worldwide Power Partner Inc USA www.bryair.com Recover Low Grade Process Waste Heat For Energy Smart

More information

Experimental Study of Direct Contact Condensation of Steam on Water Droplets

Experimental Study of Direct Contact Condensation of Steam on Water Droplets , July 1-3, 2015, London, U.K. Experimental Study of Direct Contact Condensation of Steam on Water Droplets Semra GUMRUK, Murat K. AKTAS Abstract Air or water cooled condensers are used to reduce the moisture

More information

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler International Journal of Thermal Technologies E-ISSN 2277 4114 2015 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijtt/ Research Article Effect of Operating Parameters on the

More information

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air Anna Pacak 1,*, Andrzej Jedlikowski 1, Demis Pandelidis 1, and Sergey Anisimov 1 1 Wrocław University of

More information

Vapour Compression-Absorption Cascade Refrigeration System- Thermodynamic Analysis

Vapour Compression-Absorption Cascade Refrigeration System- Thermodynamic Analysis Vapour Compression-Absorption Cascade Refrigeration System- Thermodynamic Analysis PARBHUBHAI R.TAILOR Department of Mechanical Engineering Sardar Vallabhbhai National Institute of Technology Surat,Gujarat-395007,INDIA

More information

A study of tea leaves drying using dehumidification process and regeneration of liquid desiccant in a closed-cycle dehumidification-humidification

A study of tea leaves drying using dehumidification process and regeneration of liquid desiccant in a closed-cycle dehumidification-humidification A study of tea leaves drying using dehumidification process and regeneration of liquid desiccant in a closed-cycle dehumidification-humidification Eflita Yohana 1,*, Mohammad Endy Yulianto 2, Shofwan Bahar

More information

Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System

Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System 1 Avnish Chandra Pandey, 2 M. Akash Rao, 3 Sabyasachi Sahoo, 4 Narendra Kumar Students, Department of Mechanical

More information

CASE STUDIES OF THERMALLY DRIVEN HEAT PUMP ASSISTED DRYING. Minh Cuong Tran, Jamy Logie, Bruno Vanslambrouck, Martijn van den Broek

CASE STUDIES OF THERMALLY DRIVEN HEAT PUMP ASSISTED DRYING. Minh Cuong Tran, Jamy Logie, Bruno Vanslambrouck, Martijn van den Broek CASE STUDIES OF THERMALLY DRIVEN HEAT PUMP ASSISTED DRYING Minh Cuong Tran, Jamy Logie, Bruno Vanslambrouck, Martijn van den Broek Department of Flow, Heat and Combustion Mechanics, Ghent University UGent,

More information

Ultra Efficient Desiccant Based Evaporative Cooling for Air- Conditioning

Ultra Efficient Desiccant Based Evaporative Cooling for Air- Conditioning Ultra Efficient Desiccant Based Evaporative Cooling for Air- Conditioning Ranga Vamshi and Anurag Bajpai GreenTree Building Energy (P) Ltd., B 67, Sector 67, Noida, UP, India. Problem Statement: Air-conditioning

More information

Numerical study of heat pipe application in heat recovery systems

Numerical study of heat pipe application in heat recovery systems Numerical study of heat pipe application in heat recovery systems *Song Lin, John Broadbent, Ryan McGlen Thermacore Europe, 12 Wansbeck Business Park Ashington, Northumberland NE3 QW, UK E-mail: song.lin@thermacore.com

More information

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM Sachin Kumar 1, Vicky Ranga 2 1Assistant Professor, Department of Mechanical Engineering, Jagan Nath University Jhajjar, Haryana, India. 2Scholar.

More information

Study on an Air-Side Heating Source Liquid Desiccant Regeneration Model

Study on an Air-Side Heating Source Liquid Desiccant Regeneration Model Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Study on an Air-Side Heating Source Liquid Desiccant Regeneration Model

More information

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview International Journal of Research in Engineering and Innovation Vol-2, Issue-1 (2018), 21-28 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com

More information

Global Journal of Engineering Science and Research Management

Global Journal of Engineering Science and Research Management EXPERIMENTAL AND THEORETICAL STUDY OF MINIATURE VAPOR COMPRESSION CYCLE USING MICROCHANNEL CONDENSER Issam M. Ali Aljubury*, Ahmed Q. Mohammed, Marwa S. Neama * Mechanical Eng. Dept. College of Engineering,

More information

Experimental Investigation of Hot water Fired R134A-DMAC VARS System at Various Heat Source Temperatures

Experimental Investigation of Hot water Fired R134A-DMAC VARS System at Various Heat Source Temperatures Journal of Energy Research and Environmental Technology pp. 20-25 Krishi Sanskriti Publications http://www.krishisanskriti.org/jeret.html Experimental Investigation of Hot water Fired R134A-DMAC VARS System

More information

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Available online at   ScienceDirect. Procedia Engineering 121 (2015 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 121 (2015 ) 1222 1229 9th International Symposium on Heating, Ventilation and Air Conditioning (ISHVAC) and the 3rd International

More information

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential

More information

CHAPTER 1 INTRODUCTION

CHAPTER 1 INTRODUCTION 1 CHAPTER 1 INTRODUCTION 1.1 Background The science which deals with creating a controlled climate in indoor space is called air conditioning. Earlier days the air-conditioning was treated as a luxury,

More information

Chapter 10. Refrigeration and Heat Pump Systems

Chapter 10. Refrigeration and Heat Pump Systems Chapter 10 Refrigeration and Heat Pump Systems Learning Outcomes Demonstrate understanding of basic vaporcompression refrigeration and heat pump systems. Develop and analyze thermodynamic models of vapor-compression

More information

SOLAR PARABOLIC COLLECTOR ASSISTED EVAPORATIVE COOLING SYSTEM

SOLAR PARABOLIC COLLECTOR ASSISTED EVAPORATIVE COOLING SYSTEM 2 nd International Conference on Energy Systems and Technologies 18 21 Feb. 2013, Cairo, Egypt SOLAR PARABOLIC COLLECTOR ASSISTED EVAPORATIVE COOLING SYSTEM Tanuja Sheorey 1 +, Vandana Arora 1 1 PDPM Indian

More information

SOLAR WATER DISTILLATION BY USING WATER IN THE INNER GLASS EVACUATED TUBES

SOLAR WATER DISTILLATION BY USING WATER IN THE INNER GLASS EVACUATED TUBES Third Southern African Solar Energy Conference 11 13 May 2015 Kruger National Park, South Africa SOLAR WATER DISTILLATION BY USING WATER IN THE INNER GLASS EVACUATED TUBES Shahmohamadi M., Shafii, M.B.and

More information

UNIT 1 AIR CONDITIONING 1. Write the various psychometric processes? Explain any four processes with neat sketches?

UNIT 1 AIR CONDITIONING 1. Write the various psychometric processes? Explain any four processes with neat sketches? SIDDHARTH INSTITUTE OF ENGINEERING & TECHNOLOGY :: PUTTUR (AUTONOMOUS) (Approved by AICTE, New Delhi & Affiliated to JNTUA, Anantapuramu) (Accredited by NBA & Accredited by NAAC with A Grade) (An ISO 9001:2008

More information

Air Conditioning Clinic. Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN

Air Conditioning Clinic. Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN Air Conditioning Clinic Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN Absorption Water Chillers One of the Equipment Series A publication of The Trane Company Worldwide Applied Systems

More information

Energy Performance of a Desiccant and Evaporative Cooling-assisted Airconditioning System under Various Climatic Conditions in China

Energy Performance of a Desiccant and Evaporative Cooling-assisted Airconditioning System under Various Climatic Conditions in China Energy Performance of a Desiccant and Evaporative Cooling-assisted Airconditioning System under Various Climatic Conditions in China S. Y. Li 1, H. S. Lim 1, J. H. Shin 1, M. S. Jo 1, and J. W. Jeong 1

More information