39HQM Central Station Air Handling Units AiroVison Guide Specifications

Size: px
Start display at page:

Download "39HQM Central Station Air Handling Units AiroVison Guide Specifications"

Transcription

1 39HQM Central Station Air Handling Units AiroVison Guide Specifications Page 1

2 AiroVision Guide specifications 39HQM Central Station Air Handler Units Size Range: 936 to 81,360 Nominal m3/h 64 different standard sizes Non-standard model sizes (please contact factory) Insulation types for indoor, outdoor, vertical and ceiling mounting and stacked. Part 1 General 1.1 Quality Assurance A. Certification of our processes according to the international quality standard ISO 9001:2000 is customer guarantee for the quality of the Carrier product offering and the services provided B. The characteristic of the casing wall construction must be established in accordance with EN 1886, based on measurements carried out on a model box Mechanical Strength Class D1 Casing Air Leakage Class L1 Filter By-Pass Leakage Class F8 Thermal Transmittance Class T2 Thermal Bridging Class TB2 Acoustics Insulation HZ db C. CFC-Free Polyurethane insulation D. Airtight seal material meets NFPA 90A requirements for flame spread and smoke generation E. Casing sheet metal to withstand 500 hours salt spray exceeding ASTM B117 F. Air filters performance according to ASHRAE Standard or EUROVENT Standard 5/6 G. Electric Heater Heating Elements manufactured accordance to NEC and UL Space Heating Standard No 1996 H. Fan performance tested and certified to DIN and AMCA Standard. I. Standard IE1 fan motor manufactured to conform IEC Standard (optional IE2 & IE3 motors with UL listed) J. ARI 1060 and Eurovent Certified Energy Recovery Wheels 1-2 Delivery, Storage and Protection A. All units shall be completely shrink-wrapped from the factory for protection during shipment. B. All units shall be using transport brackets in fan section, tighten spring bolt and fan discharge cover for protection during shipment C. All units shall be delivered with factory installed shipping skids and lifting holes. D. Inspect for transportation damage and store in clean dry place and protect from weather and construction traffic. Handle carefully to avoid damage to components, enclosures, and finish. Part 2 Product Overview 2-1 General Description Units shall ship in the number of sections necessary to meet project requirements and shall ship in as many splits as specified in selection software. Unit shall include all specified components installed at the factory, the air-handling unit may consist of the following Standard Heating, Cooling and Energy Recovery Cooling & Dehumidification Chilled water coil and direct expansion coil. Sensible Heating Heating coil, Electric heater and steam coil. Pre-cooled & Re-heat. Heat pipe and run around coil. Heat Recovering Heat plate exchanger, heat recovery wheel and heat recovery heat pipe. Heating & Humidification Steam Humidifier Standard Air Management Indoor Air Quality Double Skin Casing, Sand Trap Louver, standard Air Filter & Humidifiers and Energy Recovery Heat Exchanger. Pre-filtering up to HEPA-filtering MERV1 up to MERV18 2 & 3-Way Air Mixing Plenum. Sound Attenuator Standard Air Movement Double inlet double width fans. Forward, backward and aerofoil and plug fan Variable Air Volume Variable Frequency Drive and Variable pitch pulley. Totally Enclosed Fan Cooled, IP55 Fan Motor Drive package. Fixed Pulleys and Wedge Belts Rubber & Spring Vibration Isolators 2-2 Casing Construction The construction of the AiroVision air handling units consists of a frame and panels. Profiled 1-mm thick casing sides of galvanized and coated steel plates ensure a rigid and light weight frame. Page 2

3 The frame holds a 60-mm double-skin casing wall with panels, doors, inspection hatches and removable center posts Unit shall be constructed of a complete frame with easily removable panels. Removal of any panel shall not affect the structural integrity of the unit, thereby facilitating maintenance work Unit shall be thermally broken to minimize the conduction path from the inside of the casing to the outside. The construction should reducing machine noise, absorbing vibration and avoiding air leakage Mechanical performances tested and conformed to Eurovent Standard EN 1886 Mechanical Strength Class D1 Casing Air Leakage Class L1 Filter By-Pass Leakage Class F8 Thermal Transmittance Class T2 Thermal Bridging Class TB2 Acoustics Insulation HZ db Profile Frame Heavy-duty profile frame made from galvanized steel, fully welded and hermetically sealed at the ends, profile is more robust and can be repeatedly disassembled. Profile is coating according to ASTM A 653/A 653 M Profile frames are painted with highly durable heat hardened polyester based powder paint RAL 7035 with 50 microns film thickness Double Skin Panel Modular panel is design to be rigid and sturdy. Made of durable galvanized sheet steel treated with a weather and scratch-resistant coating on both sides, Base color grey (RAL-7035) The standard casing wall construction consists of 0.8 mm internal and external skin with injected polyurethane, fire retardant according to DIN 4102 class B2, 40kg/m3 density, 0-19 W/M ºC K value The doors and the panels shall be formed by bending the panel external sheet metal over the internal sheet metal so that closed panel structure resistant to water and steam will be obtained. Bended external sheet metal structure of the panel (preventing the formation of sharp edges) also reduces the risk of any possible injuries during mounting and maintenance Tested for strength at ± 1000 Pascal with deflection < 1 mm/m and without permanent deflection at ± 2500 Pascal, confirmed to EN 1886 Class D Thermal and Weather Protection Panels are manufactured from steel sheets treated with weather and scratch-resistant coating on both sides RAL 7035, frames and roof are painted with highly durable heat hardened polyester based powder paint RAL 7035 with 50 microns film thickness The paint shall conform to ASTM D-2201 and ASTM D-2092 for gloss, adhesion, impact resistance, withstand up to 1000 hours salt spray resistance test, exceeding 500 hours ASTM B Thermal Transmittance, U-value tested at 1- W/m2K conformed to Eurovent EN 1886 Class T Thermal Bridging Factor kb 0.62 conformed to Eurovent EN 1886 Class TB Fasteners are zinc coated comply with 400 hours salt spray resistance test ASTM B Profile and Panel Seal Panels and profile frames shall be assembled with a closed cell self-adhesive polyethylene seal installed in between them to prevent air leakage, reduce vibration noise and minimized thermal losses A closed cell self-adhesive polyethylene seal shall avoid external water from penetrate inside the unit and shall block heat infiltration and avoid external contamination into the conditioned space area inside the unit Casing Air Leakage The construction of panels to the profile frames shall provide minimum air leakage Class L1. Casing leakage tested and conformed to Eurovent Standard EN Doors and Access Panels Hinge type with handle and lock can only be opened with a special key, access door panel equipped with metal hinges with plastic cover. EPDM rubber sealed at door perimeter provides an effective airtight and protection from heat gain Access door type shall be at the Fan Section, filter section and the Mixing Box Section. View port can be added (optional). View port shall have double skin (there shall be glass on both interior and exterior surfaces of the viewing glass) Safety Access Panels hinged access door type accessible internally and externally Removable Access Panels - the fixing of panel to the profile frames with bolts provide additional access to ease mobility for major service work on large and heavy component such as coil, fan and motor. Page 3

4 2-2-8 Roof (optional) Roof prevents water penetration on top surfaces of the AHU when installed outdoor. Silicone shall be applied to the profile joints on the outer surface of the unit, increasing insulation against water Heavy gauge (G16) galvanized steel grade G90 and powder painted RAL7035, 50 microns thick Roof Curb (Base Frame) A base shall be provided under the unit to avoid contact of the bottom surface of the unit with the others surfaces during transportation and installation, and to ensure required body strength. The height of the base shall be 62 mm, 160 mm base frame is available as an option Roof curb profiles, where the unit will be carried, shall be of closed section, high welded w and thus risk of its deformation during transportation shall be minimized Supplied with multiples holes to suit optimum hoisting stability Roof curb shall be from heavy gauge (2mm) galvanized steel, longitudinally welded with the profile, connected with 3 mm crossbar to form strong and rigid structure. Part-3 Air Mixing Section 3-1 General Description Dampers construction are made from heavy gauge galvanized steel for sturdy and rigid structure Nylon or bronze bushing, metal side linkages enable damper blades to operate within low torque. 3-2 Damper Construction Damper s blades shall be with a single skin laminar type, made from galvanized steel, operate in parallel or oppose blades position Standard class IV air leakage, 0.5% leakage rate at 100 Pascal P per square meter damper area, according to UL555S Side and blade seal damper with Class II air leakage, 0.2% leakage rate at 100 Pascal P per square meter damper area, (optional) Shafts are with 12 mm diameter, seated on noncorrosive bronzed or nylon bushing for less resistance, free maintenance and lowest torque Extended shaft length is provided for provision to electrical motor actuator to regulate damper s blades opening and closing Frames are made from galvanized steel, reinforced at every 1200-mm and flanged at both ends to facilitate external ductwork or sand trap louvers connection Metal linkage made from steel pushrods is installed for dampers with top-rear position to allow damper to inter connected at open and closed position Damper blade s quadrant shall be assembled to guide blades opening and closing position Hinged type access door is assemble at Mixing Box Section Damper torque is printable from AiroVision selections for dampers, 2-Way Mixing Box and 3-Way- Mixing Box. Part-4 Air Filters 4-1 Preliminary Filters Preliminary filter shall be made from synthetics media, in flat form or pleated form, shall be with galvanized steel frames, cleanable and washable Aluminum filter (Metallic) shall be from wire mesh form, shall be with galvanized steel frames, cleanable and washable. 4-2 Secondary Filters Soft bag filters is up to 500 mm depth synthetics bag media and supported with galvanized steel frames Built from strong, robust materials they display excellent abrasional resistance and perform well up to 100% relative humidity and in high airflow and heavy dust loading conditions. 4-3 HEPA/Absolute Filter Absolute filter is up to 630-mm depth synthetics or glass fiber bag media and supported with galvanized steel or aluminum frames Absolute air filter DOP-efficiency ranged from 95% up to 99.99% equivalent to EU10 up to EU Filter Mounting Frame Mounting frame is made from galvanized steel and filter can be accessed on to the mounting frame from front (front or rear access or existing frame mounting) or slide (side mounting) type Frame mounting or Slide rails should be sealed for a minimal air leak Class F8 according to EN Part-5 Coil Constructions 5-1 General Description Coils shall be of the cartridge type, mounted on a condensate drain pan with a slide in-out coil track so that the complete assembly is wholly removable for easy maintenance Coils fabricated and tested in accordance with ASHRAE/ANSI 15 Safety Code for Mechanical Refrigeration (latest edition). Page 4

5 5-2 Coil Construction Standard coil fins material shall be aluminum or copper or pre-coated aluminum. Aluminum coated steel fin is standard for steam coil Standard fin thickness is 0.12 mm, Fin s density can be from 8 FPI up to 14 FPI Fins shall be a collar type, assembled with 12.7 mm OD copper tubes (steel fins and steel tube for steam coils) and mechanically bonded to copper tube for greater heat transfer coefficient Standard copper tube 12.7 OD with 0.41 mm wall thickness Coil Frames are made from galvanized steel and painted for additional protection. Stainless steel SS 304 coil frames are available (optional) Coil assembly shall sit within coil section face area and seal to the casing wall to avoid air by-pass, plate by-pass of removable type for easy access to header section Water coil headers are made from black steel barrel and connection with threaded end (11 TPI) steel stub, seamless copper barrel is available (option) Water coil header s connection of copper, sweat type is available as an option DX coil headers shall be all copper tubes with sweat connection type Header s connections are sealed internally and externally with rubber seal to avoid air leaking through gap at coil panels Coils shall be counter flow and equipped with vent and drain (drain and vent - water coil only) Coils shall be tested at 300-psig submerged under water, designed to operate up to 230 psig (16 Bar) at 200 F (93 C) Extended header connections outside the coil section shall be protected with metal shield to avoid any damage during transportation. 5-3 Condensate Drain Pan Single skin drain pan insulated with 60 mm panels from all sides Drain pan shall be mounted in slanted angle at one side for complete and positive drainage, drain connection shall be at one side. 5-4 High Efficiency Moisture Eliminator Mineral reinforced PVC eliminator profile, highly efficient to trap moisture molecules at much higher velocity 4- m/s Eliminator shall be installed at downstream of the coil whenever face velocity approaching 2.5 m/s (2.3 m/s for fresh air coil at highly humid condition). 5-5 Coil Section Access Panel Removable panel shall be assembled at both left and right side of coil section Coil panels shall be bolted externally, air tight sealed, easy removal and quick reassemble to facilitate access for service and maintenance. Part-6 Electric Heater Section 6-1 General Description Electric heater shall be of the cartridge type Heaters shall be framed with a slide in-out track so that the complete assembly is removable. 6-2 Standard Electric Heater Closed Tubular Finned Type Standard electric heater shall be from Closed Tubular Finned Type, composition 80% Ni and 20% Cr Heating component is according to AISI 321 and AISI Assembly of the heating element is secured inside the stainless steel spherical sheathed fins copper tube (except for heater for 460 volt heater without spherical fins) Heater assembly, the basic components shall be a airflow switch, power terminal board, grounding lug and primary & secondary over load temperature sensor Components are assembled inside terminal box integrated with heating elements frame assembly Frames shall be from a heavy gauge (G16) galvanized steel frame. 6-3 Electric Heater Section Access Panel Removable panel shall be assembled at electric heater section Panels shall be bolted externally, air tight sealed, easy removal and quick reassemble to facilitate access for service and maintenance Standard drain pan made of galvanized steel and powder painted. Stainless steel SS304 drain pan available as a standard option. Page 5

6 Part-7 Fan and Drive Section 7-1 DIN and AMCA DIDW Fans Fan shall be forward, backward and airfoil curved, double inlet and double width (DIDW) centrifugal type Direct Drive DIDW Aerofoil fans and plug fans are available (optional) Forward and backward fans are AMCA-200 air performance accredited Forward and backward fans are sound power level measurement according to AMCA 300 & Airfoil fans are accredited for AMCA 300 & 301 Sound power and AMCA for Air Performance Sound power level measured values have been converted to other operating speeds with a calculation procedure described in the BS 848 Part 2 standard, Outlet side sound power levels according to ISO 5136, DIN Part 9, BS 848 Part 2 Chapter 6 or AMCA DIDW Fan Construction Blades of the fans shall be from galvanized steel Backward and airfoil fan s blades shall be treated with polyester powder coat RAL Fan scroll from hot dip galvanized steel JIS G3302 Grade SGCC No electrical spot welding is used as the scroll back is joined to the side plates with the Pittsbourgh lock forming system. This prevents any oxidation starting from the welding spots Light-construction side frames of the R versions are made with cold-formed, galvanized steel Sendzimir type EN Heavy-duty side frames of the K, K1, K2, versions are made with hot-rolled steel sections welded and coated with alchidic-melamminic paint RAL Wheel shall be statically and dynamically balance within fan operating speed in compliance to DIN ISO Standard 1940 with grade G Fan shafts made from C45 carbon steel bars, All the shafts are coated, after assembly, with a clearly distinguishable, bright yellow protective paint. Stainless steel shafts can be provided on request (option) Shaft diameters are selected to achieve a safety factor for critical speed 1.25 higher than the maximum operating speed Standard fan bearings R versions are eccentric clamp bearing type, single row ball bearing, mounted in pressed steel housing, pre-lubricated and sealed for life Reinforced fan bearings K versions are self-aligning single row ball bearing, mounted inside cast iron pillow blocks, with grease nipples, bolted to the side-frames K1 versions reinforced single row, sealed ball bearings, locked on the shaft with a conical sleeve, mounted inside cast iron pillow blocks, with grease nipples, bolted to the side-frames K2 versions, Sealed heavy-duty bearings. For fan size 500 single row ball bearings with conical sleeve inside cast iron pillow blocks. For fan size 560,630,710 and 800 Double-row ball bearings with conical sleeve inside split block housings. For fan size 900 & 1000 Double row, self-aligning roller bearings inside single piece pillow blocks All the pillow blocks shall have grease nipples for lubrication and shall be bolted to specially reinforced side-frames Bearing s nominal life expectancy shall be 40,000 L10 operating hours (according to DIN ISO 281 Section 1). 7-3 IEC TEFC Fan Motor Design and performance shall be according to IEC Standards Fan motor shall be suitable to operate with Variable Frequency Drive (VFD) or Frequency Inverter (FI) application Fan motor shall able to operate at maximum 50% of rated speed. At 50% of rated speed, the fan motor shall deliver 80% of rated torque and 40% of rated power Standard fan s motor shall be a Totally Enclosed Fan Cooled type (TEFC) Motor s frame shall be from aluminum up to frame size or cast iron Index of Protection shall be with IP 55, motor shall be protected against dust and protected against jets of water from all direction Insulation Class F (T max 155 ºC) and Temperature Rise Class B ( T 80K) Motor shall able to operate at 50 C operating temperature Motor shall have a thermal reserve to spare for overheating when induced by voltage fluctuation at ±10%, compliance to IEC Page 6

7 Thermal Overload Protection Normally Closed Thermostat (PTO) shall be a standard accessory. Note: PTO shall provide general surveillance for nontransient overload. Bi-metallic strip with normally closed contact is indirectly heated when line current passes through the strip and shall shut down or restores supply circuits as necessary. PTO connection shall be mounted to control circuit and suitable for manual or automatic reset Positive Temperature Coefficient thermistor (PTC) shall provide general surveillance for transient overload and shall be mounted and connected to a relay in control circuit (option). 7-4 Highest Efficiency Vibration Isolation Fan and motor assemble on a common base, FMB, fabricated from heavy gauge galvanized steel or cast iron steel Motor rail shall be a slide rail type for flexible belt tensioning Fan and motor assembly are totally isolated from AHU casing structure by isolators and flexible canvas Rubber isolators capable to achieve standard vibration isolation efficiency E80 up to E Spring isolator, 250 micron powder paint, 50 mm free deflection capable to achieve critical vibration isolation efficiency E95 up to E Fan shall be isolated to discharge panel with fire retardant fan flexible connection. 7-5 Pulleys and Belts Fan drive package shall consist of fan and motor pulleys and assembled with Wedge belts Variable pitch pulley shall be available at motor drive up to 15 HP (11 kw) - option Standard belt Service Factor designed at minimum SF1.1 and flexible to reach up to SF1.5. Part-8 Energy Recovery Wheels 8-1 General Description Highly efficient heat recovery above 80% efficiency Recover both sensible and latent energy The wheel shall have purge mechanism to provide definite separation of airflow minimizing the carryover of bacteria, dust and pollutants from the exhaust air to the supply air Cross contamination protection devices with non-contact synthetic brush seal and fixed and adjustable purge sector Very low wheel speed < 25 RPM Wheel housing made of galvanized steel, cartridge type, slide-in and slide-out installation into heat wheel section. 8-2 Sorption, molecular sieve desiccant wheel, Eurovent certified Rotor to recover sensible heat and latent heat to a high degree The sorptive coating of the enthalpy rotor provides an expanded capacity in transferring humidity Storage matrix made of standard aluminium foil set up of alternating layers of flat and corrugated foils. Surface is coated with a special molecular sieve to achieve very good sorptive properties Foil layers are stabilized together by means of interior radial spokes, fixed at hub and rim in special design for long term form stability (rotor Ø>800mm). Winded up to rotor Ø 2600mm. 8-3 Sorption, molecular sieve 3Å desiccant wheel, AHRI and Eurovent certified Rotor to recover sensible heat and latent heat to a very high degree The sorptive coating of the enthalpy rotor provides an expanded capacity in transferring humidity Storage matrix made of standard aluminium foil set up of alternating layers of flat and corrugated foils. Surface is coated with a special molecular sieve to achieve excellent sorptive properties Foil layers are stabilized together by means of interior radial spokes, fixed at hub and rim in special design for long term form stability (rotor Ø>800mm). Winded up to rotor Ø 2600mm 8-4 Hygroscopic Aluminum wheel, Eurovent certified Hygroscopic Rotor is a cost-efficient solution to recover sensible heat and transfer latent heat. It is suitable for standard applications in comfort ventilation Humidity is transferred in cases when the dew point of one of the air streams is reached (e.g. winter) and, to a fair degree, during the rest of the year Storage matrix made of standard aluminum foil set up of alternating layers of flat and corrugated foils. 8-5 Desiccant Aluminum Wheel 3Å ARI Certified (Optional) Desiccant coated on to Aluminum based wheel for total energy recovery Excellent corrosion protection Highest recovery for latent energy. Best recovery operation for tropical weather Wheel edge hardened suit for marine and coastal application. Page 7

8 8-6 Desiccant Synthetic Wheel ARI Certified (optional) Desiccant wheel effectively moisture from air via a process called sorption Desiccant coated on to Synthetic based wheel material for highest heat transfer and best corrosion protection Non-metal wheel, best corrosion protection for marine and coastal application. Part-9 Plate Heat Recovery 9-1 Static Aluminum plates, recover sensible energy. Standard crosss flow energy transfer efficiency performance up to 75%. Part-11 Run Around Coils 11-1 Provide solution for Pre-Cooling,, Re-Heating and Energy Recovery Water based mediumm within Cu/Al and Cu/Cuu coil construction Water circulated c byy pump. Pump and external piping accessories are field supply and field install Lower efficiency at 25% 10-5 No contamination - totally separate flow for Fresh Air and Return Air for Recovery application Free energy for Pre- Cooling and Re-Heating. R 9-2 Exhaust and Supply flow are separated by special seal of flat plate with swirl control. 9-3 Superb seal minimize cross contamination from Exhaust Air into Supply Air. Extremely low leak 0.2% of nominal airflow at 200 Pascal P. 9-4 Anti-corrosion and non-inflammability material. construction made of Aluminum 9-5 Potential latent energy recovery and condensation occurrence whenever Fresh Air temperatures lower than Exhaust Air dew point. Part-10 Heat Pipe System (optional) Provide solution for Pre-Cooling, Re-Heating and Energy Recovery Refrigerant based medium within Cu/Al and Cu/Cu coil construction Natural refrigerant flow - no motor and no pump minimize maintenance Up to 40% efficiency No contamination - totally separate flow for Fresh Air and Return Air for Recovery application Free energy for Pre-Cooling and Re-Heating. Manufacturer reserves the rights to discontinue, or change at any time, specificationss or designs without notice and without incurring obligations Supersedes Version: N/A Effective Date: Page 8 Version: 39HQMSG-01

AIR HANDLERS. Central Station (CS3) Roof Mounted (RT) (Modular AL Frame AHU)

AIR HANDLERS. Central Station (CS3) Roof Mounted (RT) (Modular AL Frame AHU) AIR HANDLERS Central Station (CS3) (Modular AL Frame AHU) Roof Mounted (RT) CONTENTS 1. CS3 Modular Aluminium Frame AHU : Unit Types 2. Casing Structure 3. Blowers and Drives 4. Coils 5. Options and Accessory

More information

Indoor Air Quality. For assured. Double Skin Air Handling Units

Indoor Air Quality. For assured. Double Skin Air Handling Units Double Skin Air Handling Units INTL-31-OCT 06-R0 CI680512 For assured Indoor Air Quality. For more information, please contact BLUE STAR LIMITED, International Division, Band Box House, 4th Floor, Dr.

More information

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup.

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup. SECTION 23 70 00- CENTRAL HVAC EQUIPMENT PART 1: GENERAL 1.1 PURPOSE: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design.

More information

1.1 This section applies to air handling units for HVAC Systems.

1.1 This section applies to air handling units for HVAC Systems. AIR HANDLING UNITS GENERAL INFORMATION 1.1 This section applies to air handling units for HVAC Systems. DESIGN REQUIREMENTS 2.1 Design Criteria a. The decision to use modular central station air handling

More information

UNIVERSITY OF ROCHESTER DESIGN STANDARDS NOVEMBER 1, 2013

UNIVERSITY OF ROCHESTER DESIGN STANDARDS NOVEMBER 1, 2013 SECTION 15800 - AIR HANDLING EQUIPMENT 1.1 GENERAL A. All air handlers installed shall conform to the University of Rochester specification Guideline for Semi-Custom and Pre-Engineered Air Handling Units.

More information

GUIDE SPECIFICATIONS FOR AIR HANDLING UNITS VENTILATION UNITS & HEAT RECOVERY UNITS

GUIDE SPECIFICATIONS FOR AIR HANDLING UNITS VENTILATION UNITS & HEAT RECOVERY UNITS S FOR AIR HANDLING UNITS VENTILATION UNITS & HEAT RECOVERY UNITS VAYHAN AIR CONTROLS PVT. LTD. G-1, Park View Residency, Patwari Enclave Gandhi Nagar (IDPL), Hyderabad 500 037. INDIA Phone: +91-40-2372

More information

SECTION AIR HANDLING UNIT

SECTION AIR HANDLING UNIT SECTION 15800 - AIR HANDLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR

More information

13 HYGENIC AIR HANDLING UNITS

13 HYGENIC AIR HANDLING UNITS 39HQM INDEX 1 GENERAL 3 2 STANDARDS 4 2.1 Mechanical Strength 4 2.2 Casing air leakage 4 2.3 Filter bypass leakage 5 2.4 Thermal transmission 5 2.5 Thermal bridges 6 2.6 Acoustic casing insulation 6 3

More information

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems.

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems. 15855 AIR HANDLING UNITS SPECIFIER: CSI MasterFormat 2004 number: 237313 PART 1 GENERAL 1.1 SUMMARY A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution

More information

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork.

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork. SECTION 15855 AIR HANDLING UNITS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15885 - Air Filtration Equipment. 3. 15890 - Ductwork. 1.02 REFERENCES A. Air Moving

More information

Complete HVAC Capability. Central Station Air Handling Units. Publication No. WT-CSX-0616A

Complete HVAC Capability. Central Station Air Handling Units. Publication No. WT-CSX-0616A Publication No. WT-CSX-0616A Central Station Air Handling Units Complete HVAC Capability Horizontal Draw-Thru to Size 65 Vertical Draw-Thru to Size 50 1000 to 60,000 CFM Forward Curved or Airfoil Wheels

More information

Double Skin Casing Air Handling Units

Double Skin Casing Air Handling Units Double Skin Casing Air Handling Units Double wall with 25 mm insulation Modular design for clean process application flexibility all the requirements 2,000 40,000 CFM AUTUMN Air Handling Units incorporate

More information

Centeral Station Air Handling Unit

Centeral Station Air Handling Unit Centeral Station Air Handling Unit CA Series www.windind.com www.windind.com The product range includes double skinned Air Handling Units, double skinned Fan Coil Units, and custom designed packaged roof

More information

Double Skin Air Handling Units

Double Skin Air Handling Units Double Skin Air Handling Units With Screwless Cabinets Engineered to Deliver High Indoor Air Quality Double Skin Air Handling Units from the Experts Blue Star has over six decades of experience in offering

More information

A. Codes and Standards that are Standard at the University:

A. Codes and Standards that are Standard at the University: PART 1: GENERAL 1.01 Purpose: 1.02 References: 1.03 Requirements: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The

More information

EHH SERIES DRAW THROUGH FAN COILS CFM

EHH SERIES DRAW THROUGH FAN COILS CFM EHH SERIES DRAW THROUGH FAN COILS 400-5000 CFM TABLE OF CONTENTS TABLE OF CONTENTS 2 INTRODUCTION 3 GUIDE SPECIFICATIONS 4 UNIT OVERVIEW 6 TECHNICAL DATA 8 DIMENSIONS 10 COMPUTER SELECTION 11 GEMCOOL PROFILE

More information

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett

More information

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004)

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004) High Plume Blowers Suggested Specification Section 15500 (Master Format 1996) Suggested Specification Section 23 38 16 (Master Format 2004) PART 1 GENERAL 1.01 WORK INCLUDED High Plume Laboratory Exhaust

More information

A. This Section includes air-handling units with coils for indoor installations.

A. This Section includes air-handling units with coils for indoor installations. SECTION 237313 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes air-handling units with coils for indoor installations. 1.2 SUBMITTALS A. Product Data: For each type of indoor air-handling unit

More information

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March GENERAL: 1. This section provides criteria for the design and installation of air handling units. DESIGN GUIDELINES: Design General 1. Location 1.1. For new construction, and existing buildings where possible,

More information

TYPICAL CPA SPECIFICATIONS

TYPICAL CPA SPECIFICATIONS TYPICAL CPA SPECIFICATIONS 4/10/2017 UNIT CONSTRUCTION: Casing: The exterior casing of the unit shall be constructed of 18-gauge, G235 galvanized steel (optional stainless steel or aluminum), unpainted.

More information

Submittal Data Performance Data Electrical Data

Submittal Data Performance Data Electrical Data ERMS Series Submittal Data Submittal Data Unit Designation: Job name: Architect: Engineer: Contractor: Performance Data Revision: 07/01/11 Cooling Capacity: EER: Heating Capacity: COP: Ambient Air Temp:

More information

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

Internal ridged board 1 x 1.5 foil face installation shall be installed on roof, walls and base of casing. A-D WITH MPU SPECIFICATION WRITTEN SPECIFICATION Description A Modular Packaged Heating, Cooling and ventilating unit(s), as indicated on the drawings shall be furnished. Direct Fired Gas Unit(s) shall

More information

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES SECTION 15856 MODULAR AIR HANDLING UNITS PART 1 DESIGN DIRECTIVES 1.1 QUALITY ASSURANCE A. NFPA Compliance: Modular air handling units and components shall be designed, fabricated, and installed in compliance

More information

Direct Fired Heater Model AD Specification

Direct Fired Heater Model AD Specification Direct Fired Heater Model AD Specification Description A Direct-fired gas heating and ventilating unit(s), as indicated on the drawings shall be furnished. Unit(s) shall be tested in accordance with ANSI

More information

AIR HANDLING UNITS. Revision AG 16-07

AIR HANDLING UNITS. Revision AG 16-07 AIR HANDLING UNITS UNIC sal is equipped to produce a wide range of COOLER Air conditioning and Refrigeration units, conforming to the international standards and works continually to improve its products

More information

AIR HANDLER SPECIFICATION

AIR HANDLER SPECIFICATION AIR HANDLER SPECIFICATION Air Handlers AH-1 through 5 The following air handlers will be supplied: AH-1 FX15-4842 Series 5700 CFM AH-2 FX15-4236 Series 3990 CFM AH-3 FX15-3633 Series 2570 CFM AH-4 FX15-3330

More information

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS SECTION 23 34 16 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Drawings and general provisions of the contract, including General and Special Conditions and Division 01 Specification

More information

Modular Air Handling Unit

Modular Air Handling Unit MAHUs are modular so that they have the flexibility to add components as required. The 3rd generation Midea MAHU adapts unitary structure design, more outstanding cold-bridge free performance, lower air

More information

WE ARE PLEASED TO PROVIDE THE ENCLOSED SUBMITTAL FOR YOUR REVIEW AND APPROVAL

WE ARE PLEASED TO PROVIDE THE ENCLOSED SUBMITTAL FOR YOUR REVIEW AND APPROVAL PREPARED FOR: DATE: JOB NAME: WE ARE PLEASED TO PROVIDE THE ENCLOSED SUBMITTAL FOR YOUR REVIEW AND APPROVAL EQUIPMENT DETAILS ITEM TAG DESCRIPTION MODEL NUMBER 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 EQUIPMENT

More information

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters.

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters. Section 15 _ Energy Recovery Air Handling System Part 1: GENERAL 1.1 Section Includes: A. Energy Recovery Air Handler B. Controls (most by Others) C. Equipment Schedule 1.2 Related Sections: A. Section

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM SECTION 23 81 06 - PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. This Section includes equipment types that contain all the components of the refrigeration process within

More information

SSL / SBS Sales Guide BLOWER-COILS REDUCED-FOOTPRINT, VERTICAL

SSL / SBS Sales Guide BLOWER-COILS REDUCED-FOOTPRINT, VERTICAL SO TOUGH, WE GUARANTEE IT. SSL / SBS Sales Guide BLOWER-COILS REDUCED-FOOTPRINT, VERTICAL SSL SBS www.superiorrex.com SSL / SBS Series: BIG ON FEATURES; SMALL IN SIZE Contractors All SSL/SBS model blower-coil

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

Double Skin Air Handling Units

Double Skin Air Handling Units Double Skin Air Handling Units With Screwless Cabinets Engineered to Deliver High Indoor Air Quality Double Skin Air Handling Units from the Experts Blue Star has over six decades of experience in offering

More information

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise Modular Climate Changer Full Spec. Prepared by: Phone Number: Prepared for:

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise Modular Climate Changer Full Spec. Prepared by: Phone Number: Prepared for: Date: 05/21/2001 Time: 08:50:16 AM Job Name: EarthWise Modular Climate Changer Full Spec Location: Any Town, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SUBMITTALS Submittals

More information

Chilled Water DOAS Fan Powered Terminal Units

Chilled Water DOAS Fan Powered Terminal Units Chilled Water DOAS Fan Powered Terminal Units CHILLED WATER DOAS FAN POWERED TERMINAL UNITS DOAS TERMINAL UNITS FEATURES AND BENEFITS MINIMUM VENTILATION CONTROL The DOAS unit provides the Designer, Owner

More information

MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH

MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH 318 MHNCCX NOMENCLATURE BREAKDOWN 4-Pipe Heat/Cool Ceiling Concealed Fan Coil MHNCCW- XX - XX Ceiling Concealed

More information

Double Skin Air Handling Units

Double Skin Air Handling Units Double Skin Air Handling Units With Screwless Cabinets Engineered to Deliver High Indoor Air Quality Double Skin Air Handling Units from the Experts Blue Star has over six decades of experience in offering

More information

A. Section Common Motor Requirements for HVAC Equipment: Fan motors.

A. Section Common Motor Requirements for HVAC Equipment: Fan motors. SECTION 233516 - ENGINE EXHAUST SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Exhaust fans. B. Ductwork and duct fittings. C. Inlet fittings. D. Accessories. E. Carbon monoxide detectors. 1.2 RELATED

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof

More information

HIGH EFFICIENCY POOL DEHUMIDIFIER AND CONDITIONER WITH HIGH HEAT RECOVERY RATES. Air treatment unit. Swimming pool waste air 28 C-65%

HIGH EFFICIENCY POOL DEHUMIDIFIER AND CONDITIONER WITH HIGH HEAT RECOVERY RATES. Air treatment unit. Swimming pool waste air 28 C-65% Dry HIGH EFFICIENCY POOL DEHUMIDIFIER AND CONDITIONER WITH HIGH HEAT RECOVERY RATES Calculation of savings (for illustrative purposes) Operating scheme Note: power rates refer to 10,000 m 3 /h of air and

More information

DUCTED SPLIT AIR CONDITIONERS GCUN-A/GDS-A SERIES

DUCTED SPLIT AIR CONDITIONERS GCUN-A/GDS-A SERIES DUCTED SPLIT AIR CONDITIONERS GCUN-A/GDS-A SERIES Range 3.6 To 36.5 Tons 50Hz R22 TABLE OF CONTENT General features Page 3 Components features Pages 3 to 5 Compressors Condensers Condenser fans Evaporators

More information

DIVISION 15 MECHANICAL

DIVISION 15 MECHANICAL DIVISION 15 MECHANICAL A. GENERAL DESIGN CONDITIONS 1. Design occupied spaces to maintain 72 F and a space dew point temperature not to exceed 55 F. 2. Design classroom and office space buildings with

More information

RetroAire Model Number: 9,000 to 36,000 Btuh (2.6 to 10.5 kw)

RetroAire Model Number: 9,000 to 36,000 Btuh (2.6 to 10.5 kw) Indoor Single Package Vertical, Air-Cooled Heat Pump Unit RetroAire Model Number: Capacity Range: VPRH 9,000 to 36,000 Btuh (2.6 to 10.5 kw) Part 1 General 1.01 UNIT DESCRIPTION A. Indoor, single package

More information

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Construction Standards Page 233423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified

More information

Modular Supply Make-Up Air Unit

Modular Supply Make-Up Air Unit Modular Supply Make-Up Air Unit Model MSX Flexible Design Factory Assembled Heating Options Hot Water Steam Electric Cooling Options Evaporative Direct Expansion Chilled Water November 2009 Product Features

More information

SECTION AIR COILS

SECTION AIR COILS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

Bulletin C6200 MAY Buffalo. Big Buffalo. Air Handling. Custom Applications

Bulletin C6200 MAY Buffalo. Big Buffalo. Air Handling. Custom Applications Bulletin C6200 MAY 20 3 Buffalo Air Handling Big Buffalo Custom Applications Buffalo Air Handling Big Buffalo The historic strength of Buffalo Air Handling is the custom designed air handling equipment

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION EXHAUST FANS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION EXHAUST FANS PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Placement within a mechanical room is required for all major mechanical equipment. Only small units may be roof-mounted, and shall be made as inconspicuous

More information

Easdale International INFINITY

Easdale International INFINITY Easdale International INFINITY Air flow from 800 to 0.000 m 3 /h APPLIED SYSTEM AIR HANDLING UNITS AHU N : 0.0.502 Range: Easdale International www.eurovent-certification.com www.certiflash.com Engineered

More information

DUCTED SPLIT AIR CONDITIONERS 50Hz GCUN/GDS SERIES R 407C

DUCTED SPLIT AIR CONDITIONERS 50Hz GCUN/GDS SERIES R 407C DUCTED SPLIT AIR CONDITIONERS 50Hz GCUN/GDS SERIES R 407C CONTENTS General features Page 3 Components features Pages 3 to 5 Compressors Condensers Condenser fans Evaporators Evaporator fan and drive Casing-Structure

More information

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components. Page 238126-1 SECTION 238126 - This Section includes requirements for the LEED Rating System. However, equipment specified in this Section may not qualify for LEED Rating System prerequisites and credits.

More information

University of Delaware

University of Delaware University Contact: Energy & Engineering Group (302) 831-1744 SECTION 23 73 00_AIR HANDLING UNITS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Modular custom & semi-custom built indoor air handling

More information

SSL & SBS Engineering Guide

SSL & SBS Engineering Guide REDUCED-FOOTPRINT VERTICAL BLOWER COIL UNITS SSL & SBS Engineering Guide SO TOUGH, WE GUARANTEE IT. SSL SBS Table of Contents Features and Benefits... 3 Construction Features... 4 Features and Options...

More information

High Ambient / High Efficiency Series. R - 410a. 50Hz. Ducted Split Air Conditioners (5.0 kw kw)

High Ambient / High Efficiency Series. R - 410a. 50Hz. Ducted Split Air Conditioners (5.0 kw kw) High Ambient / High Efficiency Series R - 410a 50Hz Ducted Split Air Conditioners (5.0 kw - 17.5 kw) ISO 9001 : 2008 ISO 14001 : 2004 ISO 18001 : 2007 R - 410a 50Hz Introduction: Established in the year

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703 TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.

More information

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section.

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section. SECTION 15855 GAS FURNACE/DX COOLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of contract including General and Supplementary Conditions of Division 1 of Specification

More information

FCC Fan-Coil Units High-Performance, Vertical

FCC Fan-Coil Units High-Performance, Vertical FCC Fan-Coil s High-Performance, Vertical Model FCC construction features Piping and supply-duct connections are from top of unit, eliminating the need for side or back access Right or left-hand configurations

More information

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes). Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage

More information

Advance Product Data. Features/Benefits. 42WKN Hydronic Fan Coil Units

Advance Product Data. Features/Benefits. 42WKN Hydronic Fan Coil Units Advance Product Data 42WKN Hydronic Fan Coil Units 3 4 to 2 1 2 Tons UNIT SIZES 004-010 UNIT SIZES 016,020 The new Carrier Hydronic Cassette offers a modern solution for a wide variety of small and medium

More information

SECTION AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS

SECTION AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS SECTION 23 62 13 - AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements",

More information

SECTION WATER-SOURCE UNITARY HEAT PUMPS

SECTION WATER-SOURCE UNITARY HEAT PUMPS SECTION 23 81 46 WATER-SOURCE UNITARY HEAT PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification

More information

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH MHCCW-10-05 Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH Rev. 1.21 HVAC Guide Specifications Chilled Water Fan Coil with Electric Heat 2-Pipe Nominal Size:

More information

MODULAR AIR HANDLING UNIT. Models: FAC / FMC / FBC

MODULAR AIR HANDLING UNIT. Models: FAC / FMC / FBC MODUAR AIR HANDING UNIT Models: FAC / FMC / FBC Contents Product Nomenclature... 2 Features... 4 Engineering Specifications... 13 Cooling Coil Performance Chart... 13 Heating Coil Performance Chart...

More information

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH MHCCW-06-00 Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH Rev. 1.21 HVAC Guide Specifications Chilled or Hot Water Fan Coil 2-Pipe Nominal Size: 18,000 BTUH

More information

Air flow m3/h

Air flow m3/h Air-Handling Unit 9XT Air flow 000 00000m/h *EUROVENT Certification *50mm double skins *Excellent casing insulation and strength *Flexible selection *Excellent Cooling Performance *Quiet Operation *Reliable

More information

SECTION CUSTOM INDOOR CENTRAL-STATION AIR-HANDLING UNITS For large systems, 50,000 cfm or more.

SECTION CUSTOM INDOOR CENTRAL-STATION AIR-HANDLING UNITS For large systems, 50,000 cfm or more. Page 237323-1 SECTION 237323 - For large systems, 50,000 cfm or more. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

XeteX, Inc. All Rights Reserved.

XeteX, Inc. All Rights Reserved. Model DXH Custom, packaged, roof mounted or indoor mounted unit with cooling (DX or Chilled Water) and an air-to-air aluminum flat plate exchanger designed to provide pre-cooling and reheat. The DXH is

More information

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS SECTION 237413 - PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, outdoor, central-station air-handling units (rooftop units) with the

More information

Hi-Pres. Self Contained A/C Unit HI-PRES MARINE & OFFSHORE

Hi-Pres. Self Contained A/C Unit HI-PRES MARINE & OFFSHORE Hi-Pres Self Contained A/C Unit TYPE SCU-C & SCU-W Product specifications HI-PRES MARINE & OFFSHORE Contents Introduction..................... 2 Type SCU-W.......................... 2 Type SCU-C...........................

More information

B. Unit shall be shipped as a single package unless the unit is too large to fit on a standard tractor-trailer.

B. Unit shall be shipped as a single package unless the unit is too large to fit on a standard tractor-trailer. SECTION 23 72 23 ENERGY RECOVERY UNITS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Product Specifications. Vertical Floor Consoles By First Co.

Product Specifications. Vertical Floor Consoles By First Co. NOW WITH 18 GAUGE CABINET AND FACTORY INSTALLED SERVICE SWITCH Product Specifications VFB Series VSB Series VCB Series Vertical Console Fan Coils 300-00 CFM Vertical Floor Consoles By First Co. VFB Series

More information

Guide Specifications PART 1 GENERAL 1.01 SUMMARY

Guide Specifications PART 1 GENERAL 1.01 SUMMARY Guide Specifications PART 1 GENERAL 1.01 SUMMARY A The environmental control system shall be designed specifically for precision temperature control applications. It will automatically monitor and control

More information

THE ULTIMATE ROOFTOP SOLUTION

THE ULTIMATE ROOFTOP SOLUTION Configured Packaged Rooftop Solutions Specializing in Dedicated Outdoor Air Systems (DOAS) Capacities from 6 to 90 Tons Available in 208, 230, 460 and 575 Volts THE ULTIMATE ROOFTOP SOLUTION Service Friendly

More information

39G Air Handling Unit

39G Air Handling Unit 39G Air Handling Unit Air flow: 2000 ~ 60000 m³/h The Manufacturer reserves the right to change any produt specifications without prior notices Version: Supersede: Effective Date: CAT_39G_E-1307_02 CAT_39G_E-1205_01

More information

SECTION (15833) - HVAC POWER VENTILATORS

SECTION (15833) - HVAC POWER VENTILATORS PART 1 GENERAL 1.01 SUMMARY SECTION 23 34 23 (15833) - HVAC POWER VENTILATORS A. Section Includes: 1. Centrifugal Roof Ventilators. 2. Up-blast Roof Exhaust Fans (Kitchen Hood Exhaust). 3. Ceiling-Mounted

More information

SECTION AIR HANDLING UNITS WITH COILS. 1. Central Station Air Handling Units. 1. Section Basic Mechanical Requirements.

SECTION AIR HANDLING UNITS WITH COILS. 1. Central Station Air Handling Units. 1. Section Basic Mechanical Requirements. SECTION 15855 AIR HANDLING UNITS WITH COILS PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Central Station Air Handling Units. B. Related Sections: 1.02 REFERENCES 1. Section 15010 - Basic Mechanical

More information

MHNCCW (4-Pipe) Chilled/Hot Water Ceiling Concealed 208/230V 4-Pipe Heating & Cooling Fan Coil 12,000 BTUH

MHNCCW (4-Pipe) Chilled/Hot Water Ceiling Concealed 208/230V 4-Pipe Heating & Cooling Fan Coil 12,000 BTUH MHNCCW-04-01 (4-Pipe) Chilled/Hot Water Ceiling Concealed 208/230V 4-Pipe Heating & Cooling Fan Coil 12,000 BTUH Rev. 1.2 HVAC Guide Specifications Chilled and Hot Water Fan Coil 4-Pipe Nominal Size: 12,000

More information

ETA ACCU 90% HIGHEST EFFICIENCY AIR HANDLING UNIT

ETA ACCU 90% HIGHEST EFFICIENCY AIR HANDLING UNIT 90% EFFICIENCY HIGHEST EFFICIENCY AIR HANDLING UNIT Packaged energy recovery solutions for Green Buildings Integrated Accumulator, controls and DX Cooling System CLEAN AIR SINCE 1963 Euroclima is a company

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 233423 - HVAC POWER VENTILATORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 PERFORMANCE REQUIREMENTS A. Operating

More information

Air handling units KLASIK. Unique solutions available Flexible performance & economy Reliable, stable & efficient Tight casing & perfect insulation

Air handling units KLASIK. Unique solutions available Flexible performance & economy Reliable, stable & efficient Tight casing & perfect insulation Air handling units KLASIK Unique solutions available Flexible performance & economy Reliable, stable & efficient Tight casing & perfect insulation KLASIK air handling units Customer oriented and unique

More information

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS AutoZone R Model Single Package Rooftop Gas Heating/Electric Cooling Unit Size 07 with Puronr (R---410A) Refrigerant Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION

More information

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS SECTION 23 81 26 SPLIT-SYSTEM AIR-CONDITIONERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

More information

we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size)

we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size) we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size) www.blowtech.in we make air move Blowtech Air Devices Pvt. Ltd. was founded in 1988 and quickly established

More information

SECTION AIR DUCT ACCESSORIES

SECTION AIR DUCT ACCESSORIES SECTION 23 33 00 AIR DUCT ACCESSORIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes back-draft dampers, combination fire-and-smoke dampers, duct access doors, fire dampers, smoke dampers, volume control

More information

KAP Horizontal Product Coolers

KAP Horizontal Product Coolers PRODUCT DATA & INSTALLATION Bulletin K80-KAP-PDI-6 Part # 1097718 PRODUCT SUPPORT web: k-rp.com/kap email: ahu@k-rp.com call: 1-844-893-3222 x527 scan: KAP Horizontal Product Coolers Air Defrost for Applications

More information

Air handling units KLASIK. Unique solutions available Flexible performance & economy Reliable, stable & efficient Tight casing & perfect insulation

Air handling units KLASIK. Unique solutions available Flexible performance & economy Reliable, stable & efficient Tight casing & perfect insulation Air handling units KLASIK Unique solutions available Flexible performance & economy Reliable, stable & efficient Tight casing & perfect insulation KLASIK air handling units Customer oriented and unique

More information

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories. Page 238219-1 SECTION 238219 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Series. Packaged Rooftop Units, heat pumps and Outdoor air handling Units. Features:

Series. Packaged Rooftop Units, heat pumps and Outdoor air handling Units. Features: RL Packaged Rooftop Units, heat pumps and Outdoor air handling Units Features: Air-cooled condenser, water-cooled condenser, or patented AAON evaporative-cooled condenser, with capacities from 45-240 tons

More information

Product Data. Features/Benefits. 39FX Central Station Air Handling Units 1000 m3/hr to 160,000 m3/hr Nominal Air Flow

Product Data. Features/Benefits. 39FX Central Station Air Handling Units 1000 m3/hr to 160,000 m3/hr Nominal Air Flow Central Station Air Handling Units 1000 m3/hr to 160,000 m3/hr Nominal Air Flow Product Data Series Central Station Air Handling Units are designed based on Carrier Moduflex Series. The design of the Central

More information

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT Carrier International Sdn. Bhd. Malaysia INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT 40LM 120-200 50Hz CONTENTS: Physical Data & Dimension 1-3 Safety Considerations 4 Rigging

More information

TECAM S.A. harmony. 5PZA Direct Expansion. Air Conditioning Equipment Manufacturer. R-410A PRECISION UNIT 2 Ton 6 Ton / 60 Hz. Tecnología Ambiental

TECAM S.A. harmony. 5PZA Direct Expansion. Air Conditioning Equipment Manufacturer. R-410A PRECISION UNIT 2 Ton 6 Ton / 60 Hz. Tecnología Ambiental TECAM S.A. Tecnología Ambiental R-410A PRECISION UNIT 2 Ton 6 Ton / 60 Hz harmony 5PZA Direct Expansion Registration No.: SC 4696-1 Registration No.: CO-SC 4696-1 Air Conditioning Equipment Manufacturer

More information

AIR HANDLING. B. Section Building Automation and Control System Guidelines. C. Section Air Cleaning Devices and Filters

AIR HANDLING. B. Section Building Automation and Control System Guidelines. C. Section Air Cleaning Devices and Filters 237300 AIR HANDLING PART 1: GENERAL 1.01 RELATED SECTIONS A. Section 230530 Clean Steam Generation B. Section 230900 Building Automation and Control System Guidelines C. Section 234100 Air Cleaning Devices

More information

CLIMACIAT AIRTOP. Air handling units. Very short delivery time Double wall with 50 mm insulation. Complete range meeting all the tertiary requirements

CLIMACIAT AIRTOP. Air handling units. Very short delivery time Double wall with 50 mm insulation. Complete range meeting all the tertiary requirements Excellent quality / price ratio Very short delivery time Double wall 50 mm insulation Complete range meeting all the tertiary requirements Air flow : 000 to 7 000 m 3 /h DESCRIPTION Casing Double wall

More information

Series PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS. Features:

Series PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS. Features: RZ PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS Features: Air-cooled condenser, water-cooled condenser, or evaporative-cooled condenser packaged rooftop units from 55-240 tons Water-source

More information

PRODUCT CATALOG BLOWER COILS.

PRODUCT CATALOG BLOWER COILS. 2016 PRODUCT CATALOG BLOWER COILS www.superiorrex.com SBH / SBV Series Design Features DESIGNED FOR MAXIMUM FLEXIBILITY Both Horizontal and Vertical Belt Drive Blower Coils are designed to maximize flexibility

More information

SKYPAK II, 3 Ton Series, gives you a

SKYPAK II, 3 Ton Series, gives you a SKYPAK II 3 ton Heating And Cooling self-contained Package SKYPAK II, 3 Ton Series, gives you a complete air-conditioning and heating system as an all in one package unit. Designed for convenient through-the-wall

More information

CR A-F-A-E-HQQE 3x400/ HZ

CR A-F-A-E-HQQE 3x400/ HZ GRUNDFOS DATA BOOKLET CR45-12-2 A-F-A-E-HQQE 3x4/69 5 HZ Grundfos Pump 96122818 Thank you for your interest in our products Please contact us for more information, or visit our website http://www.lenntech.com/grundfos/crfam/96122818/cr-45-12-2-a-f-a-e-hqqe.html

More information

SKYPAK II, 3 Ton Series, gives you a

SKYPAK II, 3 Ton Series, gives you a SKYPAK II 3 ton Heating And Cooling self-contained Package SKYPAK II, 3 Ton Series, gives you a complete air-conditioning and heating system as an all in one package unit. Designed for convenient through-the-wall

More information