1 AIR HANDLING PART 1: GENERAL 1.01 RELATED SECTIONS A. Section Clean Steam Generation B. Section Building Automation and Control System Guidelines C. Section Air Cleaning Devices and Filters D. Section Coils 1.02 SUMMARY COMMENTS A. Air handling units over 5,000 CFM shall be custom units with a guaranteed maximum leakage rate of less than 1/2% at 1-1/2 times the design static pressure. AMCA certified air handlers below 5,000 CFM shall typically be Factory Package (modular) units unless function and/or physical constraints require the use of a custom unit. B. With the advent of better digital controls, improved preventive maintenance and enhanced air handling system designs, it is now recommended to have all chilled water cooling coils protected against freezing without having to seasonally drain and refill cooling coils. The consultant shall carefully design the air handling system to avoid stratification in mixed-air systems, provide glycol preheat coils and adequate controls to monitor and prevent coil freezing. C. To reduce freeze-stat trips due to partial load-induced cold spots on preheat coils, circulation pump shall be provided at the coil. D. The potential for moisture carry-over shall be carefully considered for all air handling units provided with a cooling coil. Consultant shall design the equipment for a maximum coil face velocity of 475 fpm. E. Consultant shall size all air handler condensate traps (based on worst-case static pressure) and include a trap schedule in the construction documents. In addition, air handlers need to incorporate enough base rail height to allow for proper trap depth, or, the design needs to include a supplemental structural steel base rail under the air handler. F. Unit performance shall be certified in accordance with ANSI/AHRI Standard 430, Performance Rating of Central Station Air-Handling Units. DATE: 3/2/17 DATE: 3/2/17 Page 1 of 6

2 G. Air performance of all moving devices shall be rated in accordance with ANSI/AMCA 210, Laboratory Methods of Testing Fans for Aerodynamic Performance Rating and in accordance with AMCA 301 for sound, and shall be licensed to bear the AMCA certified rating. H. Engineer shall make it a priority to minimize air handler noise and vibration when designing an air handling system. Sound management features including (but not limited to) adequately sized cabinets (incorporating future anticipated capacity), large, lower speed, spring-isolated fans, minimal coil and filter static pressures, application of proper internal attenuation, and maximizing unit mass and stiffness all contribute to a quieter air handler. These features need to be analyzed critically by the consultant. I. The Consultant shall include in the specifications a requirement for equipment leakage testing by the air handling unit manufacturer once assembled on site with all penetrations in place and properly sealed. That means the leak test shall be performed only after all controls work has been completed. Providing any unit penetrations after the leak test will result in a re-test. This test shall also be witnessed by representatives from Cornell University and the Project Engineer of Record. PART 2: PRODUCTS 2.01 PREFERRED MANUFACTURERS A. Custom Air Handling Unit (aluminum) 1. Air Enterprise 2. Buffalo Air Handling 3. Environmental Air Systems B. Custom Air Handling Unit (Galvanized) 1. Buffalo Air Handling 2. HAAKON 3. MAFNA 4. SEMCO 5. Temtrol 6. TMI 7. Trane Custom 8. Ventrol C. Factory Package Air Handling Unit 1. AAON 2. Carrier DATE: 3/2/17 DATE: 3/2/17 Page 2 of 6

3 3. McQuay 4. Trane D. Deviations from these manufacturers will require approval by Facilities Engineering. Please be aware that in order to obtain approval for an air handler manufacturer not on the preferred list, the consultant will be responsible for providing Facilities Engineering with access to an installed unit (that s been in operation for at least five years) and to the facilities personnel responsible for maintaining the unit CONSTRUCTION A. The following criteria applies to both custom and factory package air handlers. B. Fan Section: 1. General: The fan, motor, and drive shall be internally spring isolated on a structural steel base complete with flex connections and lateral restraint. Direct drive self-supported fans (with variable speed drives {VSDs}) shall be provided in lieu of belt drive fans. The fan section shall have full size access door and adjacent removable panel for maintenance access. Fan sections typically have perforated inner walls for sound attenuation. Provide rigging beam for motor removal and maintenance purposes. 2. Draw-thru: Draw-thru units are preferred for most applications. The use of plenum fans negate system effect associated with insufficient discharge duct development length (typically associated with centrifugal utility set fans). 3. Blow-thru: The use of plenum fans in blow-thru applications promote a more even velocity profile across the coil face. Blow-thru units are also very effective at de-stratifying mixed air streams before the air enters the downstream preheat and cooling coils. This mixing effect eliminates the occurrence of a stratification-induced freeze-stat trips. Blow-thru air handlers shall not be specified when final filtration is required, due to the possibility of moisture coalescing on the filters. C. Fan Motors: An Electrically Commutated Motor (ECM or EC motor) is preferred because its use eliminates the need for a VSD and is more efficient at part-load than an AC induction motor with a VSD. Where an air handler application requires a motor size that isn t available in ECM, an AC motor with VSD is acceptable. DATE: 3/2/17 DATE: 3/2/17 Page 3 of 6

4 D. Base Construction: 1. General: Floors shall be double bottom construction with a minimum R-12 (indoor unit) or R-24 (outdoor unit) closed-cell foam insulation between. The base frame assembly shall have a minimum of four lifting lugs per shipped section. The structural base frame shall be fitted with cross-members to prevent floor oil-canning and to support all interior components. Floor material shall have safety-tread surface, and shall have continuously-welded seams. All unit base service openings shall be framed with a minimum 2-inch high water dam continuously welded to the floor. All pipe and electric conduit chases with openings to building or elements shall be covered with thin gage aluminum or 304 stainless steel. Refer to Section 1.02.E for condensate trap requirements. 2. Aluminum Construction: Base frame assembly shall be fabricated from a minimum of 3/16-inch thick aluminum plate welded at all joints and to structural members, designed for a minimum live load of 100 pounds per square foot. 3. Galvanized Construction: Base frame assembly shall be fabricated from a minimum of 8 ga. galvanized steel. The floor shall employ a 16 ga. galvanized steel outer panel, and a 3/16-inch thick aluminum or 10 ga. stainless steel inner panel. E. Cabinet Construction: 1. General: Roof and walls shall be double wall with a minimum R-12 (indoor unit) or R-24 (outdoor unit) insulation between. The panels shall be unitized in such a manner as not to disturb the insulation if panels are removed. Unit construction shall incorporate thermal breaks between the inner and outer wall panels, as well as between the walls and structure. Perforated inner walls are acceptable for use in all sections except in outside air intake, cooling coil, humidifier sections and any sections after the humidifier. Both galvanized and aluminum constructions are acceptable. Panel deflection shall not exceed a maximum of 1/200 of any span at 1-1/2 times the design positive or negative pressure (plus snow and wind loading for outside units). 2. Aluminum Construction: The outer panels shall be fabricated of minimum inch thick aluminum. Inner panels shall be fabricated of inch thick aluminum. Interior finish shall be smooth mill. 3. Galvanized Construction: The outer panels shall be fabricated of 16 ga. steel. Inner panels shall be fabricated of 16 ga. galvanized steel. DATE: 3/2/17 DATE: 3/2/17 Page 4 of 6

5 F. Cabinet Insulation: Use of closed cell polyisocyanurate foam insulation is preferred. Insulation shall be ASTM-84 and UL 723 fire and smoke rated to a fire hazard classification of 25/50. Insulation shall meet or exceed a 3.0 pounds per cubic foot (pcf) density material rating. The insulation shall meet the erosion requirement of UL 181 facing the air stream. G. Humidifier Section: Humidifier section shall incorporate stainless steel or aluminum inner panels, structural components and hardware. Carbon steel is not acceptable. See Section for specifics related to the humidification system. H. Coil Sections: Coil sections shall be separated by a minimum space of 18-inches. Each coil section shall have a full size access door. Coil casings shall be fabricated from 16 ga. 304 stainless steel. Removable panels shall be located on both sides of the air handler unit, not just on the coil removal side. See Section for more specifics on coil construction. I. Drain Pans: Double-pitched drain pans shall be fabricated from 18 ga. 304 stainless steel and shall extend the entire length of the coil section, and extend as far as possible in the direction of airflow, far enough to catch condensate at the maximum recommended coil air velocity. Each tier of coils in a stacked configuration shall employ a dedicated drain pan. Intermediate drain pans shall extend at least 3-inches upstream and at least 12-inches downstream of the coil face. Each drain pan shall be individually piped down to the bottom pan; lower drain pan to be provided with a drain connection of sufficient size to remove condensate, and extended to the unit exterior for connection by others. Drain pans recessed into the floor shall be insulated. J. Access Doors: Access doors shall be included between each air handler component, and shall be of the same construction as the panels described above. The doors shall have two continuous neoprene gasket seals around the entire periphery of the door. Each access door shall have a minimum of two non-corrosive securing latches which are also operable from inside the unit. Provide 1-inch dia. test ports with screwed caps on casing upstream and downstream of all coils and filters for pressure and temperature measurement. Positively pressurized sections shall have inwardly swinging doors, while negatively pressurized doors shall swing outward. Doors shall incorporate thermopane safety glass windows for every section. K. Lights: Water-tight marine lights with LED lamps and wire guards shall be provided in each section that provides service access. A single externally wall-mounted switch shall be provided to control all interior lights. Switch shall have pilot light in handle. DATE: 3/2/17 DATE: 3/2/17 Page 5 of 6

6 L. Filter Section: Filter sections shall be deep enough to allow for deep-pocket or cartridge filters (See Section for acceptable filtration applications). Filter sections shall also be equipped with access doors of adequate size to remove and replace the filters. Filter frames shall employ factory-applied gaskets between frame and filter. For filters installed upstream or downstream of the fan, the filter frame shall allow filters to be installed only on the upstream side of the frame. This configuration will help push the filter against the filter frame, thus providing a better seal between the filter and frame. The use of slide filter frames should only be considered as a last-resort. Two access doors are required for slide filter applications. A Dwyer Photohelic gauge shall be mounted on the outside of the cabinet with copper probes measuring the pressure drop across the filter section. The purpose of the analogue output is for filter load trending over the life of the filter. M. Controls: Generally, controls shall be field mounted. See Section for specifics on recommended building and automated controls systems required for air handling units EXECUTION A. Shipping: Air handlers shall be properly protected during shipment. Units shipped on unprotected flat-bed trailers shall be made all-weather-tight. B. Storage: If air handlers need to be stored on site before installation within an enclosed building, all-weather-tight protection shall be maintained until the units are within an enclosed space. DATE: 3/2/17 DATE: 3/2/17 Page 6 of 6

1.1 This section applies to air handling units for HVAC Systems.

1.1 This section applies to air handling units for HVAC Systems. AIR HANDLING UNITS GENERAL INFORMATION 1.1 This section applies to air handling units for HVAC Systems. DESIGN REQUIREMENTS 2.1 Design Criteria a. The decision to use modular central station air handling

More information

SECTION AIR HANDLING UNITS WITH COILS. 1. Central Station Air Handling Units. 1. Section Basic Mechanical Requirements.

SECTION AIR HANDLING UNITS WITH COILS. 1. Central Station Air Handling Units. 1. Section Basic Mechanical Requirements. SECTION 15855 AIR HANDLING UNITS WITH COILS PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Central Station Air Handling Units. B. Related Sections: 1.02 REFERENCES 1. Section 15010 - Basic Mechanical

More information

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup.

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup. SECTION 23 70 00- CENTRAL HVAC EQUIPMENT PART 1: GENERAL 1.1 PURPOSE: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design.

More information

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett

More information

AIR HANDLERS. Central Station (CS3) Roof Mounted (RT) (Modular AL Frame AHU)

AIR HANDLERS. Central Station (CS3) Roof Mounted (RT) (Modular AL Frame AHU) AIR HANDLERS Central Station (CS3) (Modular AL Frame AHU) Roof Mounted (RT) CONTENTS 1. CS3 Modular Aluminium Frame AHU : Unit Types 2. Casing Structure 3. Blowers and Drives 4. Coils 5. Options and Accessory

More information

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES SECTION 15856 MODULAR AIR HANDLING UNITS PART 1 DESIGN DIRECTIVES 1.1 QUALITY ASSURANCE A. NFPA Compliance: Modular air handling units and components shall be designed, fabricated, and installed in compliance

More information

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems.

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems. 15855 AIR HANDLING UNITS SPECIFIER: CSI MasterFormat 2004 number: 237313 PART 1 GENERAL 1.1 SUMMARY A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution

More information

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems 233100 AIR DISTRIBUTION PART 1: GENERAL 1.01 RELATED SECTIONS A. Section 230700 HVAC Insulation B. Section 237300 Air Handling C. Section 230900 Building Automation and Control System Guidelines D. Section

More information

University of Delaware

University of Delaware University Contact: Energy & Engineering Group (302) 831-1744 SECTION 23 73 00_AIR HANDLING UNITS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Modular custom & semi-custom built indoor air handling

More information

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork.

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork. SECTION 15855 AIR HANDLING UNITS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15885 - Air Filtration Equipment. 3. 15890 - Ductwork. 1.02 REFERENCES A. Air Moving

More information

Bulletin C6200 MAY Buffalo. Big Buffalo. Air Handling. Custom Applications

Bulletin C6200 MAY Buffalo. Big Buffalo. Air Handling. Custom Applications Bulletin C6200 MAY 20 3 Buffalo Air Handling Big Buffalo Custom Applications Buffalo Air Handling Big Buffalo The historic strength of Buffalo Air Handling is the custom designed air handling equipment

More information

3.0 Factory packaged or modular constructed AHUs, when approved for use, shall conform to the following criteria:

3.0 Factory packaged or modular constructed AHUs, when approved for use, shall conform to the following criteria: SECTION 237300 - AIR HANDLING UNITS 1.0 The type and construction quality of AHUs shall be based on several factors, such as size, system features, building types, site restrictions, etc. The Project Engineer

More information

UNIVERSITY OF ROCHESTER DESIGN STANDARDS NOVEMBER 1, 2013

UNIVERSITY OF ROCHESTER DESIGN STANDARDS NOVEMBER 1, 2013 SECTION 15800 - AIR HANDLING EQUIPMENT 1.1 GENERAL A. All air handlers installed shall conform to the University of Rochester specification Guideline for Semi-Custom and Pre-Engineered Air Handling Units.

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise Modular Climate Changer Full Spec. Prepared by: Phone Number: Prepared for:

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise Modular Climate Changer Full Spec. Prepared by: Phone Number: Prepared for: Date: 05/21/2001 Time: 08:50:16 AM Job Name: EarthWise Modular Climate Changer Full Spec Location: Any Town, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SUBMITTALS Submittals

More information

SECTION CUSTOM INDOOR CENTRAL-STATION AIR-HANDLING UNITS For large systems, 50,000 cfm or more.

SECTION CUSTOM INDOOR CENTRAL-STATION AIR-HANDLING UNITS For large systems, 50,000 cfm or more. Page 237323-1 SECTION 237323 - For large systems, 50,000 cfm or more. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters.

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters. Section 15 _ Energy Recovery Air Handling System Part 1: GENERAL 1.1 Section Includes: A. Energy Recovery Air Handler B. Controls (most by Others) C. Equipment Schedule 1.2 Related Sections: A. Section

More information

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March GENERAL: 1. This section provides criteria for the design and installation of air handling units. DESIGN GUIDELINES: Design General 1. Location 1.1. For new construction, and existing buildings where possible,

More information

A. This Section includes air-handling units with coils for indoor installations.

A. This Section includes air-handling units with coils for indoor installations. SECTION 237313 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes air-handling units with coils for indoor installations. 1.2 SUBMITTALS A. Product Data: For each type of indoor air-handling unit

More information

Complete HVAC Capability. Central Station Air Handling Units. Publication No. WT-CSX-0616A

Complete HVAC Capability. Central Station Air Handling Units. Publication No. WT-CSX-0616A Publication No. WT-CSX-0616A Central Station Air Handling Units Complete HVAC Capability Horizontal Draw-Thru to Size 65 Vertical Draw-Thru to Size 50 1000 to 60,000 CFM Forward Curved or Airfoil Wheels

More information

Centeral Station Air Handling Unit

Centeral Station Air Handling Unit Centeral Station Air Handling Unit CA Series www.windind.com www.windind.com The product range includes double skinned Air Handling Units, double skinned Fan Coil Units, and custom designed packaged roof

More information

SECTION AIR HANDLING UNIT

SECTION AIR HANDLING UNIT SECTION 15800 - AIR HANDLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR

More information

DIVISION 15 MECHANICAL

DIVISION 15 MECHANICAL DIVISION 15 MECHANICAL A. GENERAL DESIGN CONDITIONS 1. Design occupied spaces to maintain 72 F and a space dew point temperature not to exceed 55 F. 2. Design classroom and office space buildings with

More information

AIR HANDLER SPECIFICATION

AIR HANDLER SPECIFICATION AIR HANDLER SPECIFICATION Air Handlers AH-1 through 5 The following air handlers will be supplied: AH-1 FX15-4842 Series 5700 CFM AH-2 FX15-4236 Series 3990 CFM AH-3 FX15-3633 Series 2570 CFM AH-4 FX15-3330

More information

Modular Supply Make-Up Air Unit

Modular Supply Make-Up Air Unit Modular Supply Make-Up Air Unit Model MSX Flexible Design Factory Assembled Heating Options Hot Water Steam Electric Cooling Options Evaporative Direct Expansion Chilled Water November 2009 Product Features

More information

Plenum Fans. Model HPA. Direct Drive

Plenum Fans. Model HPA. Direct Drive Plenum Fans Model HPA Direct Drive October 2012 Quiet & Efficient HPA Plenum Fans Greenheck s modular plenum fan, model HPA, is designed and engineered to provide superior performance and reliability in

More information

Copyright 2003 and 2005 by The American Institute of Architects (AIA) Modified by MSU Physical Plant / Engineering and Architectural Services

Copyright 2003 and 2005 by The American Institute of Architects (AIA) Modified by MSU Physical Plant / Engineering and Architectural Services Page 238216-1 Copyright 2003 and 2005 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified by MSU Physical

More information

ALL PRODUCTS BROCHURE

ALL PRODUCTS BROCHURE ALL PRODUCTS BROCHURE www.aaon.com d e d i c at i o n t o cust o m e r service since the founding of aaon in 1988, we have maintained our commitment to design, develop, manufacture and deliver heating

More information

Series PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS. Features:

Series PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS. Features: RZ PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS Features: Air-cooled condenser, water-cooled condenser, or evaporative-cooled condenser packaged rooftop units from 55-240 tons Water-source

More information

AIRSIDE COMPONENTS AND SYSTEMS

AIRSIDE COMPONENTS AND SYSTEMS Ventilation: Outdoor air (OA) ventilation shall be introduced into each occupied building space in compliance with ASHRAE Standard 62. Adequate additional OA capability is needed to keep buildings under

More information

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

Internal ridged board 1 x 1.5 foil face installation shall be installed on roof, walls and base of casing. A-D WITH MPU SPECIFICATION WRITTEN SPECIFICATION Description A Modular Packaged Heating, Cooling and ventilating unit(s), as indicated on the drawings shall be furnished. Direct Fired Gas Unit(s) shall

More information

Series. Packaged Rooftop Units, heat pumps and Outdoor air handling Units. Features:

Series. Packaged Rooftop Units, heat pumps and Outdoor air handling Units. Features: RL Packaged Rooftop Units, heat pumps and Outdoor air handling Units Features: Air-cooled condenser, water-cooled condenser, or patented AAON evaporative-cooled condenser, with capacities from 45-240 tons

More information

TYPICAL CPA SPECIFICATIONS

TYPICAL CPA SPECIFICATIONS TYPICAL CPA SPECIFICATIONS 4/10/2017 UNIT CONSTRUCTION: Casing: The exterior casing of the unit shall be constructed of 18-gauge, G235 galvanized steel (optional stainless steel or aluminum), unpainted.

More information

Advance Release September 2009

Advance Release September 2009 Vertical Air Cooled DSV Series R 410A Model DSV096 DSV120 DSV144 DSV180 Nominal Cooling (Tons) 8 10 12 15 Refrigerant R 410A R 410A R 410A R 410A Cooling Performance Gross Cooling Capacity(Btu/h) 95,000*

More information

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc.

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc. System Components with ` Emphasis on Packaged Rooftop Application and Installation Jerry Cohen President Jacco & Assoc. Agenda Define and relate in practical terms the following components: System Effect

More information

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED (491) SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU, K3EU & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION These completely assembled units include a well-insulated cabinet, a DX cooling coil with copper tubes

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 233423 - HVAC POWER VENTILATORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 PERFORMANCE REQUIREMENTS A. Operating

More information

Direct Fired Heater Model AD Specification

Direct Fired Heater Model AD Specification Direct Fired Heater Model AD Specification Description A Direct-fired gas heating and ventilating unit(s), as indicated on the drawings shall be furnished. Unit(s) shall be tested in accordance with ANSI

More information

SECTION AIR COILS

SECTION AIR COILS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

SECTION CUSTOM FAN WALL AIR HANDLING UNITS

SECTION CUSTOM FAN WALL AIR HANDLING UNITS SECTION 23 73 24 CUSTOM FAN WALL AIR HANDLING UNITS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004)

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004) High Plume Blowers Suggested Specification Section 15500 (Master Format 1996) Suggested Specification Section 23 38 16 (Master Format 2004) PART 1 GENERAL 1.01 WORK INCLUDED High Plume Laboratory Exhaust

More information

Rosemex Products 96 VENTILATION CLIMATAIR COMPARTMENT AIR HANDLING UNITS

Rosemex Products 96 VENTILATION CLIMATAIR COMPARTMENT AIR HANDLING UNITS 10 Rosemex Products 96 VENTILATION CLIMATAIR COMPARTMENT AIR HANDLING UNITS 2 INDEX Page Description - Introduction -Application - Data... 2 Typical Installation... 3 Sound performance... 3-6 Dimensional

More information

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS SECTION 237413 - PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, outdoor, central-station air-handling units (rooftop units) with the

More information

SECTION DUCTWORK

SECTION DUCTWORK SECTION 15890 DUCTWORK PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 07270 - Firestopping and Fire and Smoke Barrier Caulking. 2. 15260 - Vibration Isolation. 3. 15280 - Thermal Insulation (HVAC).

More information

A. Section Common Motor Requirements for HVAC Equipment: Fan motors.

A. Section Common Motor Requirements for HVAC Equipment: Fan motors. SECTION 233516 - ENGINE EXHAUST SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Exhaust fans. B. Ductwork and duct fittings. C. Inlet fittings. D. Accessories. E. Carbon monoxide detectors. 1.2 RELATED

More information

MLR SERIES MODULAR AIR HANDLING UNITS

MLR SERIES MODULAR AIR HANDLING UNITS MODULAR AIR HANDLING UNITS General Information MAINSTREAM About Mainstream Mainstream offers a diverse line of custom air handling units, as well as heat transfer coils and other components required for

More information

Energy Labs Energy Labs Energy Labs Energy Lab

Energy Labs Energy Labs Energy Labs Energy Lab Energy Labs was before was cool Customers Customers For the past 20 years Energy Labs products have been part of many industrial and commercial projects. We have a diversified clientele including hospitals,

More information

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components. Page 238126-1 SECTION 238126 - This Section includes requirements for the LEED Rating System. However, equipment specified in this Section may not qualify for LEED Rating System prerequisites and credits.

More information

Heat Pumps SA SERIES. Vertical Self-Contained Unit Water-Source Heat Pumps (23-70 tons) Features:

Heat Pumps SA SERIES. Vertical Self-Contained Unit Water-Source Heat Pumps (23-70 tons) Features: Heat Pumps SA SERIES SA Series Vertical Self-Contained Unit Water-Source Heat Pumps (23-70 tons) Features: Vertical self-contained units with capacities from 23 70 tons Direct drive backward curved plenum

More information

Turning Air Into Solutions. TUBEAXIAL PAINT SPRAY BOOTH EXHAUST FANS. Model TCBS

Turning Air Into Solutions. TUBEAXIAL PAINT SPRAY BOOTH EXHAUST FANS. Model TCBS Turning Air Into Solutions. TUBEAXIAL PAINT SPRAY BOOTH EXHAUST S Model TCBS CATALOG AX220 May 2013 TubeaxialFans Model TCBS The Twin City Fan & Blower model TCBS is a belt driven tubeaxial fan that is

More information

Contents INDEX. TDM Series Indirect Fired Heaters

Contents INDEX. TDM Series Indirect Fired Heaters Contents Typical Indoor Installations................... 000 Indoor Unit Dimensions (Vertical).............. 000 Indoor Unit Dimensions (Horizontal)............ 000 Outdoor Unit Dimensions.....................

More information

FEATURES AND BENEFITS

FEATURES AND BENEFITS FEATURES AND BENEFITS Product Features and Benefits Full Product Line Offering Feature All models are 80% thermally efficient Blower performance up to 3.0 W.C. DX or chilled water section with factory

More information

Vision and Skyline Semi-custom Air Handlers

Vision and Skyline Semi-custom Air Handlers Vision and Skyline Semi-custom Air Handlers Flexible design solutions to match building applications Skyline Outdoor Air Handler 900 to 65,000 cfm Vision Indoor Air Handler 900 to 100,000 cfm Custom solutions

More information

SECTION DUCTWORK

SECTION DUCTWORK PART 1 GENERAL 1.1 REFERENCES SECTION 23 31 00 DUCTWORK A. ASHRAE - Handbook, Duct Design B. ASHRAE - Handbook, Duct Construction C. ASTM A90/A90M - Standard Test Method for Weight (Mass) of Coating on

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM SECTION 23 81 06 - PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. This Section includes equipment types that contain all the components of the refrigeration process within

More information

Hood Depot Internatioonal, Inc., Phone S. Powerline Road, Deerfield Beach, FL

Hood Depot Internatioonal, Inc., Phone S. Powerline Road, Deerfield Beach, FL The Kitchen Cool by Hood Depot is a conditioned make up air unit design with flexibility, form and function kept in mind. Our unit offers a variety of configurations that allow the customer to customize

More information

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters.

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters. SECTION 15622 DIRECT GAS-FIRED BURNER & MANIFOLD SYSTEM PART 1: GENERAL 1.1 Section includes: A. Direct gas-fired heater modules B. Controls C. Equipment schedule 1.2 Related Sections A. Section 01655:

More information

ENGINEERING & SERVICE

ENGINEERING & SERVICE CUSTOM AIR HANDLERS ENGINEERING & SERVICE Alliance Air Products has brought together an engineering team focused on practical solutions to all aspects of air handling unit design. Our engineers are leaders

More information

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog H3/V3 Series Horizontal and Vertical Indoor Air Handling Units Engineering Catalog Table of Contents AAON H3/V3 Series Features and Options Introduction... 6 H3/V3 Base Model Description... 7 Unit Size...

More information

Cleveland Clinic Design Standards MECHANICAL SYSTEMS DESIGN GUIDELINES HVAC AIR DISTRIBUTION PART I - GENERAL 1.1 SUMMARY

Cleveland Clinic Design Standards MECHANICAL SYSTEMS DESIGN GUIDELINES HVAC AIR DISTRIBUTION PART I - GENERAL 1.1 SUMMARY PART I - GENERAL 1.1 SUMMARY A. This section addresses the general requirements for air handling distribution systems, including air handlers, ductwork, ductwork accessories, terminal units, air devices,

More information

Indirect Gas-Fired Make-Up Air

Indirect Gas-Fired Make-Up Air Indirect Gas-Fired Make-Up Air Model IG 800 to 7,000 cfm Up to 400,000 Btu/hr Multiple Furnace Control Options Optional Evaporative Cooling May 20041 Product Features Model IG Indirect Gas-Fired Make-Up

More information

EHH SERIES DRAW THROUGH FAN COILS CFM

EHH SERIES DRAW THROUGH FAN COILS CFM EHH SERIES DRAW THROUGH FAN COILS 400-5000 CFM TABLE OF CONTENTS TABLE OF CONTENTS 2 INTRODUCTION 3 GUIDE SPECIFICATIONS 4 UNIT OVERVIEW 6 TECHNICAL DATA 8 DIMENSIONS 10 COMPUTER SELECTION 11 GEMCOOL PROFILE

More information

SECTION AIR DOORS

SECTION AIR DOORS SECTION 23 34 33 AIR DOORS Berner Series VSA air doors are designed for openings up to 12 ft for environmental separation and up to 10 ft for insect control. Berner Series VSB air doors are designed for

More information

SECTION AIR DUCT ACCESSORIES

SECTION AIR DUCT ACCESSORIES SECTION 23 33 00 AIR DUCT ACCESSORIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes back-draft dampers, combination fire-and-smoke dampers, duct access doors, fire dampers, smoke dampers, volume control

More information

Air Handling Units. Ranging from 15 to 2,000+ tons and 500 to 400,000+ CFM

Air Handling Units. Ranging from 15 to 2,000+ tons and 500 to 400,000+ CFM Air Handling Units Ranging from 15 to 2,000+ tons and 500 to 400,000+ CFM THE NORTEK AIR SOLUTIONS AIR HANDLER ADVANTAGE Nortek Air Solutions is the largest custom HVAC manufacturer in North America, with

More information

B. Unit shall be shipped as a single package unless the unit is too large to fit on a standard tractor-trailer.

B. Unit shall be shipped as a single package unless the unit is too large to fit on a standard tractor-trailer. SECTION 23 72 23 ENERGY RECOVERY UNITS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Modular Air Handling Unit

Modular Air Handling Unit MAHUs are modular so that they have the flexibility to add components as required. The 3rd generation Midea MAHU adapts unitary structure design, more outstanding cold-bridge free performance, lower air

More information

CxA to Answer this Section

CxA to Answer this Section EXHIBIT 01 91 13-3, SAMPLE Construction checklist items are to be completed as part of initial checkout and subsequent startup, preparatory to Functional testing. This checklist does not take the place

More information

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 15371 KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM A. Section Includes: A complete wet chemical automatic fire suppression system for the exhaust hood, including necessary

More information

COMMERCIAL HVAC AIR-HANDLING EQUIPMENT. Central Station Air Handlers

COMMERCIAL HVAC AIR-HANDLING EQUIPMENT. Central Station Air Handlers COMMERCIAL HVAC AIR-HANDLING EQUIPMENT Central Station Air Handlers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application

More information

CLIMATAIR PENTHOUSE AIR HANDLING SYSTEMS

CLIMATAIR PENTHOUSE AIR HANDLING SYSTEMS 7 Rosemex Products 97 VENTILATION CLIMATAIR PENTHOUSE AIR HANDLING SYSTEMS 2 INTRODUCTION Rosemex "Penthouse" units are essentially outdoor mechanical rooms. They group in one compact weather proof outdoor

More information

KIC Air Curtains. Technical Guide

KIC Air Curtains. Technical Guide TGKIC-3 KIC Air Curtains Technical Guide AIR PERFORMANCE AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC. King certifies that the air curtains shown herein are licensed to bear the AMCA seal. The

More information

TO: PLANS AND SPECIFICATIONS FOR: Western District Court of Appeals Air Handling Unit 02 Replacement Kansas City, MO Project No:

TO: PLANS AND SPECIFICATIONS FOR: Western District Court of Appeals Air Handling Unit 02 Replacement Kansas City, MO Project No: Addendum No. 1 TO: PLANS AND SPECIFICATIONS FOR: Western District Court of Appeals Air Handling Unit 02 Replacement Kansas City, MO Project No: 01507-01 Bids Due: Second Submittal: Unchanged: Unchanged:

More information

PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION

PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION ENERGY EFFICIENT DEHUMIDIFICATION PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM Provides a very high degree of latent cooling using only a minimal amount of conventional cooling input Substantial energy

More information

AIR HANDLING UNITS. Revision AG 16-07

AIR HANDLING UNITS. Revision AG 16-07 AIR HANDLING UNITS UNIC sal is equipped to produce a wide range of COOLER Air conditioning and Refrigeration units, conforming to the international standards and works continually to improve its products

More information

CS 2. Central Station Air Handlers Double Wall & Single Wall Installation, Operation & Maintenance Manual. Form No. 6120A

CS 2. Central Station Air Handlers Double Wall & Single Wall Installation, Operation & Maintenance Manual. Form No. 6120A CS 2 Central Station Air Handlers Double Wall & Single Wall Installation, Operation & Maintenance Manual Form No. 6120A TABLE OF CONTENTS Page Inspection... 2 Shipment of Units... 2 Handling... 2 Installation...

More information

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section.

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section. SECTION 15855 GAS FURNACE/DX COOLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of contract including General and Supplementary Conditions of Division 1 of Specification

More information

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Construction Standards Page 233423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

NEW FAN COILS BLOWER COILS AIR HANDLERS NEW PRODUCT OFFERING.

NEW FAN COILS BLOWER COILS AIR HANDLERS NEW PRODUCT OFFERING. NEW FAN COILS BLOWER COILS AIR HANDLERS NEW PRODUCT OFFERING Continuing Excellence Since the 1980s, Superior Rex has manufactured/sold an extensive range of fan coils and air handlers in the global marketplace.

More information

Our energy efficient experts and engineers have made ground breaking innovations in this field.

Our energy efficient experts and engineers have made ground breaking innovations in this field. Company Profile Introduction: We are pleased to introduce ourselves as MAFNA Air Technologies Inc., established in 1999. MAFNA Air Technologies Inc, is Canada's leading manufacturer and supplier of Air

More information

RTU. Roof Top Units 8 30 Ton. Maxi-Kool.

RTU. Roof Top Units 8 30 Ton. Maxi-Kool. Maxi-Kool RTU Roof Top Units 8 30 Ton www.compu-aire.com MK A-3 034 -RTU Maxi-Kool Type Air Cooled - A Chilled Water Cooled - C Glycol Cooled - G Water Cooled - W Nominal Tonnage 8 30 Ton Voltage 2-208

More information

AcoustiFlo Fans: Retrofit Solutions and Beyond

AcoustiFlo Fans: Retrofit Solutions and Beyond AcoustiFlo Fans: Retrofit Solutions and Beyond The Most Energy Efficient Plenum Fan in the World! The AcoustiFLO Modular Fan RETROFITS Ideal for fan replacement inside any air handling unit Module is 35

More information

PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE / GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNTS. RQ Series.

PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE / GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNTS. RQ Series. RN/RQ Series PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE / GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNTS RQ Series Features: Air-cooled or water-cooled condenser, with unit capacities

More information

DESIGN GUIDELINES SECTION HVAC

DESIGN GUIDELINES SECTION HVAC 3/15/17 Cooling Methodology Chiller Plants Configurations monitoring Preferred DESIGN GUIDELINES SECTION 15700 HVAC Air-cooled chillers < or = 300 tons; water-cooled chillers > 300 tons Variable volume

More information

DACC Health Sciences Building Air Handler Assessment/Study

DACC Health Sciences Building Air Handler Assessment/Study DACC Health Sciences Building Air Handler Assessment/Study NMSU Facilities and Services Department P.O. Box 30001 Las Cruces, NM 88003-8001 June 14, 2016 Final Submittal 1065 S. Main St., Bldg. D, Ste.

More information

Industrial Space Heating Direct Gas-Fired Heating. Greenheat 50/50 Recirculation

Industrial Space Heating Direct Gas-Fired Heating. Greenheat 50/50 Recirculation Industrial Space Heating Direct Gas-Fired Heating Greenheat 00% Outdoor Air Greenheat 50/50 Recirculation 80/0 Recirculation March 008 Product Overview Industrial Space Heating Greenheck s space heating

More information

Modular Heating & Ventilating Unit Model IGX-HV

Modular Heating & Ventilating Unit Model IGX-HV Modular Heating & Ventilating Unit Model IGX-HV Indirect Gas-Fired Heating Evaporative Chilled Water DX Cooling October 2008 Product Features Model IGX-HV Indirect Gas-Fired Heating and Ventilating Unit

More information

A. Codes and Standards that are Standard at the University:

A. Codes and Standards that are Standard at the University: PART 1: GENERAL 1.01 Purpose: 1.02 References: 1.03 Requirements: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The

More information

SECTION (15820) - AIR DUCT ACCESSORIES

SECTION (15820) - AIR DUCT ACCESSORIES PART 1 GENERAL 1.01 SUMMARY A. Section includes: SECTION 23 33 00 (15820) - AIR DUCT ACCESSORIES 1. Manual-Volume Dampers 2. Fire Dampers 3. Turning Vanes 4. Duct-Mounted Access Doors 5. Flexible Connectors

More information

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS SECTION 238126 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

Easdale International INFINITY

Easdale International INFINITY Easdale International INFINITY Air flow from 800 to 0.000 m 3 /h APPLIED SYSTEM AIR HANDLING UNITS AHU N : 0.0.502 Range: Easdale International www.eurovent-certification.com www.certiflash.com Engineered

More information

Large Capacity Fan Coil Units Catalog Belt-Drive and Direct-Drive Cabinet and Hideaway Models

Large Capacity Fan Coil Units Catalog Belt-Drive and Direct-Drive Cabinet and Hideaway Models Large Capacity Fan Coil Units Catalog 735-12 Belt-Drive and Direct-Drive Cabinet and Hideaway Models Table of Contents Agency Listing and Nomenclature... 3 Overview....................................

More information

Submittal Transmittal

Submittal Transmittal Submittal Transmittal Standard St. Joe's - Sonntag Pavillion St. Joseph s Hospital 350 W. Thomas Road Phoenix, AZ 85013 Project # 5690A Tel: Fax: Kitchell Contractors Inc of AZ Date: 9/16/2011 Reference

More information

Double Skin Casing Air Handling Units

Double Skin Casing Air Handling Units Double Skin Casing Air Handling Units Double wall with 25 mm insulation Modular design for clean process application flexibility all the requirements 2,000 40,000 CFM AUTUMN Air Handling Units incorporate

More information

SECTION CENTRAL HVAC EQUIPMENT

SECTION CENTRAL HVAC EQUIPMENT SECTION 23 70 00 CENTRAL HVAC EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Packaged and Custom Air Handling Units 1.2 RELATED WORK A. Provide temporary heating, cooling, and ventilating as needed. 1.3 REFERENCES

More information

SSL & SBS Engineering Guide

SSL & SBS Engineering Guide REDUCED-FOOTPRINT VERTICAL BLOWER COIL UNITS SSL & SBS Engineering Guide SO TOUGH, WE GUARANTEE IT. SSL SBS Table of Contents Features and Benefits... 3 Construction Features... 4 Features and Options...

More information

HVAC BASIC MATERIAL AND METHODS 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS

HVAC BASIC MATERIAL AND METHODS 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS 230500 HVAC BASIC MATERIAL AND METHODS PART 1 GENERAL 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS A. Section 230000 Basic HVAC Requirements B. Section 230523 Valves C. Section 230510 Chilled

More information

Double Skin Air Handling Units

Double Skin Air Handling Units Double Skin Air Handling Units With Screwless Cabinets Engineered to Deliver High Indoor Air Quality Double Skin Air Handling Units from the Experts Blue Star has over six decades of experience in offering

More information

Technical Development Program

Technical Development Program Technical Development Program PRESENTED BY: James Parker Insert your logo here AIR HANDLERS Coils: Direct Expansion Chilled Water and Heating Menu Section 1 Introduction Section 2 Typical Coil Applications

More information