Adca Training. Part 2
|
|
- Amberly Marcia Osborne
- 6 years ago
- Views:
Transcription
1 Adca Training Part 2 This presentation is only a guideline, that can only be completed by a trained personnel. (This document s total or partial use and/or reproduction is only allowed if the reference to the source is kept)
2 Part 2 The Boiler Equipment Used on Boilers Water Treatment Bottom Blow down TDS Control Energy Recovery Deaerators Part 4 Pressure Reduction Safety Relief Valves and Other Steam Valves Part 5 Control Valves Components of Control Valves Humidification Part 3 Pipeline Sizing Water Hammer Steam Trapping Condensate Removal
3 Steam Feedwater Feedtank Process Condensate Boiler
4 One can simply define heat generator as an equipment design to energy production through fuel combustion. Heat generators are mainly built of two distinct elements: Combustion chamber where the fuel is burned, producing hot gases that will act as fluid heater. Metallic body or generator itself closes the fluid to be heated, that will be the means of transportation for produced energy. Combustion chamber and main generator s project may vary according with type of boiler and fuel. In compliance with legislation in force generators are supplied with several auxiliary equipments appropriate to monitoring and assure generator s good functioning, such as: temperature and pressure indicators, safety valves, pressostats, thermostats, pumps, valves, instrumentation, etc.
5 By virtue of the huge variety of factors, heat generators classification is a very complex task. Here follows some examples: According to Fuel Fluid Produced Possibilities Solid, Liquid or Gas Hot or Superheated water, Steam, Diathermic oil, Hot air, Number of passes of combustion gases 1 to 4 Heating chamber Burners Pipes Inversion chamber Furnace, Fire tubes, Pressure jet, Rotary Cup, Fire tube or Water tube Wet, Dry back,
6 Feed Water Steam Burner Fuel
7 The hot gases from fuel combustion cross the main chamber (1 st pass) and the smoke tubes (2 nd pass), transfer the heat to the surrounding water. As far as the water reaches saturation temperature, steam start to be produced, being accumulated in the space above, ready to be delivery to the system. Burner
8 The hot gases from fuel combustion cross the main chamber (1 st pass) and the smoke tubes (2 nd and 3 rd pass), transfer the heat to the surrounding water. As far as the water reaches saturation temperature, steam start to be produced, being accumulated In the space above, ready to be delivery to the system.
9 Some typical control and safety equipment... Cocks and gauge glass for water level monitoring. The safety valve (s) function is to protect the boiler shell from overpressure and explosion.
10 For efficient and safe operation a steam boiler has also level controls and level alarms. Level control probes can be installed internally in the boiler shell or externally using appropriate level control chambers connected to the boiler shell. Alternatively, float control systems are still used by some manufacturers.
11 Water quality is extremely important on the exploration of a thermal power station. The use of hard water or poorly treated water may cause accidents or irreparable damages on the generator and piping, apart from decreased heat transmission. Water quality control must be done periodically. An effective treatment must keep it within the required parameters. Generally, water for a heat generator must be less hard as possible ( 1ºfH), be free of suspension solids, have alkaline Ph (8,5 minimum) and low in O2 ( 0,02mg/l) and CO2.
12 Most current process of reducing water hardness is through ion-exchange method: The raw water is guided through heavy-duty resin which has been enable by exchangeractive sets to exchange cations or anions. The calcium and magnesium ions are absorbed during the softening procedure while adequate amounts of sodium ions capable of exchange (Na+) are released into the water. The exchange resin has physically conditioned a limited capacity and is exhausted after a certain number of water throughputs. The regeneration of the water softening system is performed by means of a salt solution. Ph correction, which value is associated with CO2 content may be done through a controlled injection of chemicals for which is necessary adequate dosing instruments. O2 and CO2 can be eliminated by chemical or thermal process. The chemical process uses sometimes some products non-recommended in food industry,thus the thermal process offers more advantages as: O2 Elimination CO2 elimination And by consequence, Ph correction
13 The timing of regeneration can be selected manually or automatically. If the softener is electronically controlled by a timer, the regeneration has to be selected outside the operational use of steam boilers. The volumetric systems work in dependence on the flow volume. The duplex design is specially suitable for continuous operation, because the regeneration is performed alternatively without interruption of the soft water supply.
14 During the vaporisation process the suspended solids in the boiler water are collect in the bottom of the boiler in the form of sludge. Manual blowdown valves are specially designed for application on steam boilers removing the concentrations of solids (sludges) avoiding boiler damages, unstable water level control and other typical problems. VPA26S (Manual) The valves are provided with a manual handwheel. Valve aperture cycles depends from the boiler manufacturer specification or water treatment specialists.
15 During the vaporisation process the suspended solids in the boiler water are collect in the bottom of the boiler in the form of sludge. Automatic blowdown valve are specially designed for application on steam boilers removing the concentrations of solids (sludges) avoiding boiler damages, unstable water level control and other typical problems. VPA26S (Automatic) The valves are provided with a diaphragm actuator suitable for compressed air motive fluid. The opening signal is supplied by an automatic intermittent control unit but they can also have alternative manual operation. Valve aperture depends from the boiler manufacturer specification or water treatment specialists.
16 Some impurities remains in the boiler water in the form of dissolved solids and so they cannot be eliminated trough the bottom blowdown. The concentration of this dissolved solids naturally increase with steam production. When this concentration is high, and in order to restore the right levels, some of the boiler contents must be purged. Lost water will be replaced by lower TDS concentration feedwater, replacing the correct parameters. A typical problem of excess TDS concentration is water foaming which origins bad boiler performance and wet steam.
17 When the TDS concentration reaches the set point measured by the conductive probe, a controller gives an open signal to the blowdown valve. Conductivity probe Blowdown controller Adcatrol Blowdown control valve To BEX for expansion and drain or flash vessel for energy recovery. Sample Cooler Boiler manufacturer and water treatment specialists usually indicates the maximum permissible concentration.
18 The blowdown and cooling units are used in the modern boiler houses to cool hot waste water and steam boiler blowdown before to discharge into a pit or drain to prevent thermal pollution and pipe system damages. The waste water is discharged into the unit which is at atmospheric pressure and the cooling water enters via a control valve controlled by a thermostat, mixing with the hot water. EH Exhaust Head If flash steam can not be recovered or discharged to atmosphere an additional condensing water spray system (optional) can be supplied. This one is fitted in the top of the unit and can be controlled directly either by another thermostat or the same command used for the automatic blowdown valve control. BEX Blowdown Expansion Vessel
19 Sample coolers prevent steam flashing-off from hot pressurised liquid samples, which can be dangerous and will result in an incorrect water sample. Basically they operate as a small heat exchanger. Hot Sample IN Hot Sample IN Cooling Water OUT Cold Sample OUT Cooling Water IN Cooling Water IN SC32 Cold Sample OUT SC32/F Cooling Water OUT
20 For high pressure boilers and continuous analysing, special execution is necessary. Clean steam systems also require a specific design and finishing surfaces. SC332 SC432 SC532 Ts= 550ºC Ps=245 bar SC32P Clean Steam Internal Finished to 0,5 micronsra
21 Flash steam One of typical applications for the use of flash vessel is precisely in recovering flash steam from the boiler blowdown. This energy recovery can be used for feedtank preheating, saving fuel. Flash steam produced can be condensate inside the vessel by using injectors submerged in the water or it can simply be used on the deaerator head. Blowdown from boiler Adca RV.../A Flash Vessel Contaminated water
22 Condensate Flash Steam Make up Water Flash Vessel ADG Atmospheric Thermal Deaerator with Dome Flash Steam Inlet Hot Water Heat Recover from Residual Blowdown Cold Water
23 Since many years ago it is common to recover condensate from steam systems to the boiler feed tank, saving water and energy, reducing water treatment chemicals, costs and consequently reducing CO2 emissions. In some systems, the amount of recovered condensate and correspondent temperature is so high that the water feed tank temperature rise to the boiling point. Thus, most of the recoverable energy is lost in the form of flash steam through the vessel vent pipe. Besides, boiler feed pumps can cavitate (see NPSH) and be damaged. FRECO Flash Steam Heat RECOvery, consider the energy recovery downstream of boiler feed pump. High pressure avoids the water boiling. (FRECO can be supplied as a skid mounting system for easy installation and commissioning). A raised of 6ºC in feed water temperature, corresponds to a saving of approximately 1% fuel.
24 Flash Steam Steam Condensate Hot Water Cold Water
25 A thermal deaerator is actually a deaerating feed water heater, which combines water heating, storage and deaeration capabilities. Water is stored in a under pressure vessel typically about 3 bar g in order to aloud it to be kept at a temperature above 100ºC. Thermal deaeration takes place in equipments especially designed for the job. There are existing two main kinds: Tray type deaerators Spray nozzle type deaerators Tray type is by far the most used doing to is simplicity, versatility and performance. Atmospheric deaerators also called partial deaeration systems or semi-deaerators are most times the economic choice for boiler capacities up to approximately 2000 Kg/h.
26 Atmospheric semi-deaerators are designed to heat boiler feed water and to reduce oxygen and carbon dioxide (oxygen values in the feed water of less than 1,6 mg/l, can be achieved). Remaining oxygen can be completely removed using oxygen scavenging chemicals. Basically the complete system consists of a storage vessel, a deaeration head section and a vent. Hot return condensate is injected in the bottom of the storage vessel using an adequate sparger pipe and softened make-up water is introduced in the deaerator head to be heated by a contact cascade flash steam heating system (counter-current flow) coming from the vessel. Part of dissolved gases are liberated from the water at this point and they are liberated to atmosphere trough the flash steam vent line. Condensate Recirculation Condensate Vent Make up Water Flash steam ADG Atmospheric Semi-Deaerator Dome The semi-deaerated water then falls to the storage vessel below, where a steam injection system will provide an additional deaeration.
27 Make up Water Complete unit supplied including all the necessary instrumentation for temperature and level control. ADG/V Complete unit
28 Thermal deaerators are designed to heat boiler feed water and to reduce oxygen and carbon dioxide (oxygen values in the feed water of less than 0,02 mg/l - 0,02 ppm, can be achieved). Remaining oxygen can be completely removed using oxygen scavenging chemicals. Basically the complete system consists of a storage vessel, a deaeration section and a vent. Return condensate and softened make-up water are introduced in the deaerator dome to be heated by a contact cascade steam heating system (counter-current flow). The majority of dissolved gases are liberated from the water at this point and they are liberated to atmosphere trough the flash steam vent line. The deaerated water then falls to the storage vessel below, where a steam blanket ensure that no gases are reabsorbed. A sparger pipe is installed inside the tank at the bottom level providing the necessary heating energy. A second low pressure steam supply can also be necessary (double stage). Condensate Steam Make up Water TDG Thermal Deaerator Dome Double Stage
29 Complete unit supplied including all the necessary instrumentation for temperature, pressure and level control. Condensate Make up Water TDG/V Complete unit
30 Find the energy required to heat up the tank content, from 5ºC to 65ºC in 1,5 hours 90. m x Cp x T x 60' Q 90' Kg x 1Kcal/Kg ºC x 60º x 60' Q 90' Q Kcal/h How much Steam? V = 18000Kg of Water T1=5ºC T2=65ºC Cp of Water=1 Kcal/Kg ºC ΔT = 65º-5º=60ºC Steam = 3bar g Steam is supplied at 3 bar. From steam tables we can see that at this pressure the total enthalpy of steam (hg) at this pressure is 654,6 Kcal/Kg. SI-115 Q MKg/h hg (T2 x Cp) M Kg/h ,6 (65ºC x 1Kcal/Kg ºC) M Kg/h 1221,2Kg/h SI-125
31 Using the same formulas it is possible to find the steam flow rate necessary to heat the tank material and depending from insulation, ambient temperature, vessel design, etc, it is also possible to determine the steam flow rate necessary to make up for the heat losses from radiation and water surface. Practical calculation may accept an allowance based in a percentage of around 10%. So, for our example we will consider 1221,2 Kg x 1,1 = 1343,4 Kg/h of steam. NOTE: The tank must have enough free volume for the mass of steam added during the heating process, 1343,4 Kg x 1,5 hr = 2015,10Kg. The final water volume will be than 18000Kg ,10Kg = 20015,10Kg. At 3 bar the SI 140 has a capacity of 800 Kg/h, so, for the application we need 1343, ,4 1,68 2 Steam Injectors SI 140 or 4,98 5 Steam Injectors SI The vessel design, dimensions and the particular application may recommend the use of one single big injector or more small units, with the equivalent total capacity.
32 Hot water (or other fluids) storage vessels for industrial purposes can be divided in two types: Accumulators Semi-instantaneous Any of these can be equipped with internal coils or external heat exchanger. ADCATHERM WAVE with external STSV Heat Exchanger In the first case there s a pre determined lack of time for heating a quantity of fluid that is ready to be used. In this case, coil or heat exchanger s regeneration capacity during consumption process is not particularly relevant. On the second case there s a combination between accumulated volume and capacity of instantaneous heating. These two parameters combined must assure the maximum consumption calculated.
33 Heavy fuel oils and other viscous fluids are stored in tanks heated by pipe coils or other alternative systems. This is necessary to provide the necessary temperature (viscosity) for pumping. Too high temperature can represent less viscosity and pump cavitation problems. So, temperature control and correct condensate drainage can be crucial. Heating Coils can also be used to heat water in closed or open vessels. Mainly on fuel oil systems and semiinstantaneous heaters the coil is frequently supplied with a sleeve, heating the oil locally as it is pumped out of the tank. BM20 The use of extruded low fin tube, has the advantage that it can improve the external surface and thermal performance (Adcatherm R- Coils).
34 Heat exchangers are equipments designed to transfer primary heat from one fluid to another. Shell and tube heat exchangers are very popular for steam to water heating since they can be designed for any temperature and has relatively low cost maintenance. Plate heat exchangers can also be used on steam applications under certain conditions, however, maintenance is more expensive doing to the high cost of gaskets. Ready to install packaged units including heat exchanger, control valve, steam trapping system and all the necessary accessories, are recommended since as a rule they save time installation, while guaranty the correct assembly of all critical components.
35 Heat Exchanger TUBE SIDE SHELL SIDE FLUID SATURATED STEAM WATER OPERATING PRESSURE bar bar INLET TEMPERATURE º C * º C OUTLET TEMPERATURE º C * º C FLOW RATE Kg/h * Kg/h or m3/h HEAT EXCHANGED (Option) KW or Kcal/h MODEL REQUIRED (Please select) STH (Horizontal) STV(Vertical) Remarks : * Not necessary in case of saturated steam. STH Horizontal installation ; STV Vertical installation. Before installing an instantaneous heat exchanger, one must certify that there s a sufficient steam flow or primary energy available for the effect. Storage vessels and semi-instantaneous systems can be inconvenient since they need more installation space. However, by balancing with initial heating time and the accumulation capacity it s possible to avoid undesired highs of energetic consumption. Storage Hot Water Vessels Closed Type TUBE SIDE VESSEL SIDE FLUID SATURATED STEAM WATER OPERATING PRESSURE bar bar INITIAL TEMPERATURE º C FINAL TEMPERATURE º C VESSEL CAPACITY Kg or m3 INITIAL HEATING TIME (In minutes) RECOVERY PERIOD (In minutes) HEAT EXCHANGED (Option) KW or Kcal/h VESSEL TYPE (Please select) HORIZONTAL VERTICAL AVAILABLE DIMENSIONS (Send a sketch) Straight length mm Diameter mm Remarks : A coil in a cylindrical vertical vessel should be as close to but not exceeding the diameter of the vessel as possible. A coil in a horizontal vessel is typically approximately 2/3 the length of the vessel Semi Instantaneous Hot Water Heater If the vessel is also operating as semi-instantaneous hot water heater, please confirm : HOT WATER CONSUMPTION m3 INCOMING COLD WATER TEMPERATURE º C DESIRED HOT WATER TEMPERATURE º C LENGTH OF TIME (IN MINUTES)
36 The steam/water Adcamix mixers provide cheap, instant source of low pressure hot water by utilising existing steam and cold water supplies. The mixer incorporates a safety device to ensure that live steam cannot accidentally be ejected, even if for some reason the cold water supply fail. The temperature of water at the outlet of the Adcamix is easily controlled by using water and steam valves fitted to the inlets.
37 Condensate Air heating of large industrial spaces can be made through multiples systems available nowadays (gas, electricity, hot water, steam, etc). High pressure Live steam A steam to air unit heater is composed by a coil and a fan, which forces air passage through the coil in order to heat it. Steam air heating batteries can also be used in central air conditioning units combined with filtration modules, direct steam humidification, etc. Steam to Air Unit Heater
38 From higher pressure plants where the condensate enters into the vessel, the flash steam is separated from the condensate. Through the top main connection of the flash vessel the flash steam is then supplied to the lower pressure steam network. The remaining condensate is discharged by an automatic float steam trap. (See Adca Training I). Flash Steam Installation of a flash vessel is particularly convenient when both high and low pressure steam equipments are present in the same plant since high pressure condensate can generate low pressure steam. To maximize the use of flash vessels, it is convenient to design them for the lowest possible pressure. Blowdown from boiler Model RV.../A ADCA Flash Vessel Remaining condensate Model RV.../L
39 Flash steam High pressure Live steam Low pressure Steam application Flash vessel RV /L Condensate
40
STEAM VALVE SUPPLY & SYSTEM DESIGN
TRAP SURVEYS SYSTEM AUDITS TECHNICAL SUPPORT AND MUCH MORE... STEAM VALVE SUPPLY & SYSTEM DESIGN ISIS Steam; bringing you the expertise and technical knowledge to represent, promote and service the extensive
More informationSteam Ancillary Equipment. Primary Steam System, Water Treatment and Auxiliary Steam System Equipment
Steam Ancillary Equipment Primary Steam System, Water Treatment and Auxiliary Steam System Equipment WITH ANCILLARY EQUIPMENT Steam Header with Accumulator Gas Train Assembly Single Point Gas Supply Trap
More informationCHAPTER 6. HEATING PRODUCTION EQUIPMENT AND SYSTEMS
CHAPTER 6. HEATING PRODUCTION EQUIPMENT AND SYSTEMS 6.1 Types of Heating Systems 6.2 Heating Energy Sources 6.3 Furnaces and Air Heaters 6.4 Boilers 6.5 District Heating 6.6 Selection of Medium- Steam
More informationMath & Physics. Complete combustion requires an Air-FuelRatio of 14.7 to 1 for combustion.
Plant OPS Math & Physics Complete combustion requires an Air-FuelRatio of 14.7 to 1 for combustion. Math & Physics Increasing oxygen levels by 9 to 15% improves boiler efficiency. Math & Physics Draft
More informationPresentation On Industrial Boiler Operation And Maintenance
Presentation On Industrial Boiler Operation And Maintenance Supervised By: Engr. Poresh Kanti Das GM-MAL RIP, Mulgoan, Kaligonj, Gajipur Boiler fundamental. Assessment On Heat recovery Boiler. Boiler Operation.
More informationVolume 10 Summer Understanding Terminology Key to Treatment Program Success
Volume 10 Summer 2003 Understanding Terminology Key to Treatment Program Success One of the keys to success of a boiler water treatment program is good communication between the water treatment professional
More informationSECTION Boiler Controls & Waste Heat Recovery
6 Boiler Controls & Waste Heat Recovery ARMSTRONG PRODUCT CATALOGUE 255 IGEMA BOILER LEVEL & TDS CONTROLS IGEMA offers boiler level and TDS control products of the highest quality standard, being certified
More informationBoiler Basics. Design and operation
Boiler Basics Design and operation A boiler is an enclosed vessel that provides a means for combustion heat to be transferred into water until it becomes heated water or steam. The hot water or steam under
More informationCondensate Recovery and Return System SDR A
Condensate Recovery and Return System SDR A Condensate tank of rectangular design type SDR A with high-pressure centrifugal pump(s) installed next to the tank Condensate tanks are used to collect the condensate
More informationTDS Conductivity Probe In-Line conductivity measurement
TDS Conductivity Probe In-Line conductivity measurement (Two-pole cells with ATC Pt 100) SPS-20 DESCRIPTION The TROL SPS-20 conductivity probe is used to measure the conductivity (TDS) of the superheated
More informationBasic information about quick steam generators/boilers System GEKA Heat Technology Gottfried Kneifel
Basic information about quick steam generators/boilers System GEKA Heat Technology Gottfried Kneifel 1. Definition The term quick steam generator or boiler is used in the TRD 001, point 4.4 (technical
More informationMetropolitan. Steam Boiler. Suitable for Pressure Jet or Rotary Cup burners Oil, gas or dual fuel firing. Outputs kg/h
Metropolitan Steam Boiler Suitable for Pressure Jet or Rotary Cup burners Oil, gas or dual fuel firing Outputs 1845-21 700 kg/h 1 Metropolitan - Steam Boiler The Metropolitan is a range of high pressure
More information9707 Key West Avenue, Suite 100 Rockville, MD Phone: Fax:
9707 Key West Avenue, Suite 100 Rockville, MD 20850 Phone: 301-740-1421 Fax: 301-990-9771 E-Mail: awt@awt.org Part of the recertification process is to obtain Continuing Education Units (CEUs). One way
More informationTHE PRESSURIZED CONDENSATE RECOVERY SYSTEM:
BEST PRACTICE NO. 51 THE PRESSURIZED CONDENSATE RECOVERY SYSTEM: the solution to increasing a steam system s thermal cycle efficiency Pressurized condensate systems can provide plants with a minimum of
More informationReactor-Boiler and Auxiliaries - Course 433 BOILER STEAM AND WATER SYSTEMS
Lesson 433.60-1 Reactor-Boiler and Auxiliaries - Course 433 BOILER STEAM AND WATER SYSTEMS It was noted in an earlier lesson, that the reactor is a source of heat, and serves the purpose of a "furnace"
More information.03 ATMOSPHERIC DEAERATOR
.03 ATMOSPHERIC DEAERATOR SPECIFICATION SHEET NO. 3200 OCTOBER 1, 2007 GENERAL DESCRIPTION The Sellers atmospheric.03 deaerators condition make-up water and condensate returns to convert them into more
More informationChapter 2.3: Steam System
Part I: Objective type Questions and Answers Chapter 2.3: Steam System 1. For industrial process heating, the best quality of steam is: a) dry saturated steam b) superheated steam c) wet steam d) high
More information3.1 Deaerator Systems
3.1 Deaerator Systems 3.1.1 Design & Operational Considerations System Overview The primary function of a deaerator system is to protect the boiler and condensate system from corrosion by removing oxygen
More information.005 ATMOSPHERIC DEAERATOR
.005 ATMOSPHERIC DEAERATOR OCTOBER 1, 2007 GENERAL DESCRIPTION The Sellers atmospheric.005 deaerators condition make-up water and condensate returns to convert them into more desirable boiler feedwater.
More informationUNFIRED STEAM GENERATORS STANDARD EQUIPMENT
CEMLINE Unfired Steam Generators are designed to produce clean steam with steam or high temperature hot water as an energy source for use where there is a need to produce clean steam from boiler steam
More informationDEAERATORS .005 ATMOSPHERIC DEAERATOR
918 W WALNUT ST, DANVILLE, KENTUCKY 40422-0048 PHONE (859) 236-3181 www.sellersmfg.com SPECIFICATION SHEET NO. 3300 DEAERATORS.005 ATMOSPHERIC DEAERATOR GENERAL DESCRIPTION The Sellers atmospheric.005
More informationTray ST5. Tray Type Deaerator Pressurized.005 cc/liter. industrialsteam.com
Tray ST5 Pressurized and Atmospheric Deaerators Tray Type Deaerator Pressurized.005 cc/liter COUNTER FLOW TRAY design provides guaranteed removal of all dissolved oxygen in excess of.005 cc/liter from
More informationOpen System Condensate receiver tank of cylindrical. design type SDR A with highpressure
GESTRA Condensate Recovery and Return Systems GESTRA : ++49 (0) 421-35 03 566 Condensate flowrate Condensate temperature Condensate pressure Tank design: Cylindrical Rectangular Horizontal Vertical Condensate
More informationBOILER SYSTEM CHEMICAL TREATMENT 101
BOILER SYSTEM CHEMICAL TREATMENT 101 The primary function of a boiler is to transfer heat from hot gases generated by the combustion of fuel into water until it becomes hot or turns to steam. The steam
More informationBoiler Condensate Return Basics. Presented by Steve Connor February 24, 2016
Boiler Condensate Return Basics Presented by Steve Connor February 24, 2016 What We Are Covering Today? Brief review of the total steam system Why a proper condensate return system is so important Condensate
More informationEfficient Steam System Design
Efficient Steam System Design The word Efficient is often used to describe the general performance of a system. However it is important to distinguish between efficiency and effectiveness. Efficiency is
More informationClearFire Economizer Model ECF Integral or External. Addendum to manuals CFH and CFV
ClearFire Economizer Model ECF Integral or External Addendum to manuals 750-295 CFH and 750-269 CFV CB-8466 08/2011 1-GENERAL The Model ECF economizer is a stainless steel coil tube arrangement using
More informationBASIC BOILERS NAME :- DATE :-
BASIC BOILERS NAME :- DATE :- This examination was conducted under conditions that allowed a fair and honest test of the candidate s knowledge and ability. Exam supervisor C:\Tassie Steam\N01basicboiler
More informationspiraxsarco.com/uk Condensate recovery in industrial steam systems
Condensate recovery in industrial steam systems c o n d e n s a t e r e c o v e r y Contents 1.0 Executive Summary 2.0 Rising pressures of using natural resources 3.0 The importance of effective condensate
More information!!! Sample Written Program For Your Company. For BOILER SAFETY. Provided By:!!!
Sample Written Program For Your Company For BOILER SAFETY Provided By: P.O. Box 2136 Slidell, LA 70458 Phone: 985-781-1444 Fax: 985-781-1446 Email: info@se-safety.com Purpose Boiler Safety Program The
More informationSavile Plus. Steam Boiler. Suitable for Pressure Jet burners Oil, gas or dual fuel firing. Outputs kg/h
Savile Plus Steam Boiler Suitable for Pressure Jet burners Oil, gas or dual fuel firing Outputs 380-5425 kg/h 1 Savile Plus - Steam Boiler The Savile Plus is a range of three pass wet back reverse flame
More informationTECHNICAL MANUAL ASGX
TECHNICAL MANUAL ASGX MEDIUM/HIGH PRESSURE HOT WATER BOILER INDEX 1 TECHNICAL CHARACTERISTICS... 2 1.1 GENERAL... 2 1.2 TECHNICAL DATA... 2 2 ACCESSORIES... 3 2.1 PRESSURE... 3 Pressure gauge... 3 Operation
More informationProblem Cause Remedial action. Gauge glass There was excess chemical dosage The normal ph recommended was 9.5 to See photo 3 & 4.
CASE STUDIES OF STEAM SYSTEM AUDIT IN SOME PLANTS By K.K.Parthiban, Venus Energy Audit System Introduction This article outlines the outcome of auditing of steam system conducted in process Industries.
More informationWELCOME TO THE AWT REGIONAL TRAINING PROGRAM
WELCOME TO THE AWT REGIONAL TRAINING PROGRAM 2014 Las Vegas and Indianapolis 2 Course Schedule Day 2 8:00 a.m. Time & Relationship Management 9:00 a.m. Filtration & Pretreatment 10:00 a.m. BREAK 10:15
More informationBOILER HOUSE PRODUCTS GMS
GMS BOILER HOUSE PRODUCTS Contents Page 2 Introduction 3 Condensate Pumpsets 6 Blowdown Vessels 8 Boiler Feed Tanks Page 10 Chemical Dosing Pots 11 Vent Heads 11 De-Aerator Heads Introduction to Boiler
More informationBoiler. Fire tube Boiler:
Boiler What is Boiler? A closed metallic vessel in which the water is heated beyond the boiling temperature by the application of heat by the combustion of fuels to convert it into steam. The function
More informationCHAPTER 3 BASIC STEAM CYCLE
CHAPTER 3 BASIC STEAM CYCLE To understand steam generation, you must know what happens to the steam after it leaves the boiler. A good way to learn the steam plant on your ship is to trace the path of
More informationPrepared by Technical Team
Prepared by Technical Team Summary Vacuum degassing (VD) and vacuum oxygen de-carburisation (VOD) are the main processes in secondary steel making. The large volumes of dissolved contaminant gases arising
More informationFEEDWATER TANK WITH DEAERATOR DATASHEET. Capacity 1000 to lt Operating Pressure 0,5 bar
DATASHEET FEEDWATER TANK WITH DEAERATOR Capacity 1000 to 20000 lt Operating Pressure 0,5 bar Steam boiler feedwater tank with stainless steel Deaerator Oxygen Removal - Water Preheating and Storage DSEN001-01
More information1 of 127. Unicron Engineering ULTRASONIC TRAP TESTER UTT 100 CONDENSATE DRAIN VALVES CDV 32
Unicron Engineering ULTRASONIC TRAP TESTER UTT 100 The UTT- Ultrasonic Trap Tester is a battery powered instrument that gives visible and audible indication of ultrasonic frequencies. It provides easy,
More informationTYPE.005 DA-2C. Deaerating Boiler Feed Pumps. SHIPCO Deaerators can save you money!!! BULLETIN 149 Revised 8/09
SHIPPENSBURG PUMP CO., INC. P.O. BOX 279, SHIPPENSBURG, PA 17257 PHONE 717-532-7321 FAX 717-532-7704 WWW.SHIPCOPUMPS.COM BULLETIN 149 Revised 8/09 TYPE.005 DA-2C Deaerating Boiler Feed Pumps SHIPCO Deaerators
More informationLet us first understand how costs / savings are calculated. We know that, Boiler Efficiency ( η ) =
Economics The study of Economics with respect to steam will cover the direct and indirect cost of steam and savings accrued from Condensate and Flash recovery. Heat saving calculation Cost of steam Cost
More informationSteam and air don't mix. Chemical dosing of feedwater
is the study of matter and the changes that take place inside that matter. Our matter here is steam and the boiler. Wet steam, steam and air, feed water and air, combustion - these are some of the topics
More informationTHE ALLIANCE FOR BANGLADESH WORKER SAFETY BOILER SAFETY
THE ALLIANCE FOR BANGLADESH WORKER SAFETY BOILER SAFETY 1 Boiler Room Hazards A Risk Of Explosion Exists High Pressure steam Combustion Gases Chemicals Moving Machinery Hot Surfaces www.bangladeshworkersafety.org
More informationThermal Fluid Heaters
Thermal Fluid Heaters Vertical Coil, Vertical Tubeless, Electric and Horizontal Sizes from 75,000 to 40,000,000 BTU/HR The heat transfer innovators. THERMAL FLUID FEATURES AND BENEFITS KEY FEATURES No
More informationStrategies in Optimizing Condensate Return
Strategies in Optimizing Condensate Return By D. Bloom, Sr. Consultant, Ondeo Nalco Company, Naperville, IL Optimizing condensate return for reuse as boiler feedwater is often a viable means of reducing
More informationINDUSTRIAL RANGE ACCESSORIES AND COMPONENTS
AND COMPONENTS 199 INDUSTRIAL AUTOMATIC PURGING SYSTEMO FOR BX RANGE GENERATORS The automatic bottom blow down unit prevents unnecessary purging duplication or verifiable omission with the manual system.
More informationWater Treatment Improves Your Bottom Line DAVE PICOU WATER CARE SERVICES DIVISION JOHN SCHULTZ TEXTILE CARE DIVISON
Water Treatment Improves Your Bottom Line DAVE PICOU WATER CARE SERVICES DIVISION JOHN SCHULTZ TEXTILE CARE DIVISON Agenda Ecolab Summary Boiler Operating Costs Gas versus Electric Costs to Make Steam
More informationSteam Fundamentals. (in heating & processing applications)
Steam Fundamentals (in heating & processing applications) Introduction Common Heat Energy conveyers: Thermal Oil Hot water Steam Electrical Electric Heaters Electrodes (High Current) Steam Fundamentals
More informationProtective Chemistry for Steam Boiler Wet Layup posted to DPS client area on:
Protective Chemistry for Steam Boiler Wet Layup posted to DPS client area on: May 29, 2014 Richard Kunz, DPS Consulting Chemist s treatment recommendation: sulfite = 100 ppm P alkalinity = 400 ppm 0.2
More informationDiocese of Cleveland Facilities Services Corporation
Diocese of Cleveland Facilities Services Corporation BOILER MAINTENANCE and SERVICING SEASONAL MAINTENANCE - to be performed by trained boiler technician or boiler contractor only: 1. Disassemble the low
More informationFuel-Fired Vertical Tubeless Boilers
Fuel-Fired Vertical Tubeless Boilers Fulton Classic (4-60P), The EDGE (6-30P) orizontal and Vertical Feedwater / Condensate Return Systems and Blow-down Separators FULTON FUEL-FIRED VERTICAL TUBELESS BOILERS
More informationFUEL-FIRED VERTICAL TUBELESS BOILERS
FUEL-FIRED VERTICAL TUBELESS BOILERS 4 60 P orizontal and Vertical Feedwater / Condensate Return Systems and Blow-down Tanks FULTON FUEL-FIRED VERTICAL TUBELESS BOILERS FULTON: AN INDUSTRY LEADER SINCE
More informationDeaerators for Industrial Applications
Deaerators for Industrial Applications Combined Cycle Power Plant Deaera Deaerator - a device that is widely used for the removal of oxygen and other dissolved gases from the feedwater to steam-generating
More informationAttention is drawn to the following places, which may be of interest for search:
CPC - F22B - 2017.02 F22B METHODS OF STEAM GENERATION; STEAM BOILERS (steam engine plants where engine aspects predominate F01K; domestic central-heating systems using steam F24D; heat exchange or heat
More informationS. P. THERMAL SYSTEMS INC.
S. P. THERMAL SYSTEMS INC. 4504 Green Meadow Blvd. Beamsville Ontario L0R1B5 Canada Phone: 905 563 8651 Fax: 905 563 6234 BOILER & WATER TREATMENT REVIEW NOTE: This article is provided as a Guide Only.
More informationVICTRIX 90 VICTRIX 115 Wall-hung condensing boilers for high power
VICTRIX 90 VICTRIX 115 Wall-hung condensing boilers for high power VICTRIX 90 is the new wall-hung condensing boiler for room heating only, set-up for independent functioning and for that in cascade mode
More informationA hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes.
Introduction to Hydronics A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes. Hydronic heating systems use hot water or steam to deliver the
More informationProducts Solutions Services. Energy Solutions. Food & Beverage industry. Slide 2
Products Solutions Services Food & Beverage industry Slide 2 Why is energy management an important topic? Energy prices influence production costs, End-consumer looks for sustainable products, companies
More informationModule 3: Liquid Fossil Fuel (Petroleum) Lecture 25: Refinery Equipments
1 P age Module 3: Liquid Fossil Fuel (Petroleum) Lecture 25: Refinery Equipments 2 P age Keywords: Pipe still heater, heat exchangers, distillation tower, pumps Refinery equipments Introduction In refinery,
More informationSilhouette. Feedwater Heater. Boiler Feedwater
Roth Roth Low Low Silhouette Silhouette TRAY DEAERATORS Boiler Boiler Feedwater Feedwater Heater Heater Capacities Capacities to to 50,000 50,000 lb/hr lb/hr Model RDTV-150-5-1-2 vertical tray type deaerator
More informationTMCI Padovan Evaporators
TMCI Padovan Evaporators Evaporators Our range includes 4 types of evaporators: Forced Circulation Falling Film Evaporators Plates Thin Film Concentration systems Evaporator choosing criteria: product
More informationSpectrum TM. Installation, Service & Operation Manual O FLO. SoftH 2. Water Softener. Table of Contents
Installation, Service & Operation Manual SoftH 2 O FLO Water Softener Table of Contents 1. Description & Equipment Adjustments p.2 2. Components, Features & Functions p.3 3. Valve User Interface p.4 4.
More informationGESTRA Special Equipment and Vessels for Heat Recovery. For every application the optimally coordinated system
GESTRA Special Equipment and Vessels for Heat Recovery For every application the optimally coordinated system Steam and condensate systems with one-stop sophistication Pressure-reducing and cooling system
More informationTHERMODYNAMICS STEAM P7690 AND STEAM BENCHES CUSSONS TECHNOLOGY LABORATORY RECOMMENDATION
cussons TECHNOLOGY THERMODYNAMICS STEAM P7690 AND STEAM BENCHES CUSSONS TECHNOLOGY LABORATORY RECOMMENDATION Thermodynamics is a branch of physical science concerned with the inter-relationship and inter-conversion
More informationTypical damages to Boilers & Economizers
Typical damages to Boilers & Economizers A guide how to discover and prevent. Most commonly seen damages Boiler water side - Damages caused by : Contamination with oil Scales and Sludge Oxygen Corrosion
More informationAttention is drawn to the following places, which may be of interest for search:
CPC - F22D - 2016.11 F22D PREHEATING, OR ACCUMULATING PREHEATED, FEED-WATER; FEED- WATER SUPPLY; CONTROLLING WATER LEVEL; AUXILIARY DEVICES FOR PROMOTING WATER CIRCULATION WITHIN BOILERS (chemical treatment
More informationBoiler Mountings. Engr. Omar Sadath, Maritme Lecturer & Trainer, Bangladesh
Boiler Mountings Engr. Omar Sadath, Maritme Lecturer & Trainer, Bangladesh overview Mountings are crucial without which the operation of boilers is unsafe. Proper maintenance and care of the mountings
More informationOPTIMISE VACUUM TO IMPROVE PLANT PERFORMNCE
OPTIMISE VACUUM TO IMPROVE PLANT PERFORMNCE Vacuum Pumps and systems are widely used in the chemical process industry for various applications such as drying, solvent recovery, distillation, short path
More informationGAS FIRED ATMOSPHERIC ELECTRONIC VERSION kw
GAS FIRED ATMOSPHERIC ELECTRONIC VERSION 51-102 kw GENERAL DESCRIPTION 900 D a3 1000 762 672 E 222 The PEGASUS F2 range of atmospheric natural gas-fired boilers are constructed of cast iron finned sections
More informationPIPING SYSTEM EQUIPMENTS
PIPING SYSTEM EQUIPMENTS Introduction Equipments are devices that provide power, process and store materials. Equipments in piping systems depend on the specific industries using them. Specialized equipment
More informationCRU-S Series Stainless Steel Condensate Recovery Unit
IM-UK-CRU-S UK Issue 1 CRU-S Series Stainless Steel Condensate Recovery Unit 1. Safety information 2. General product information 3. Installation 4. Commissioning 5. Storage, shutdown and equipment protection
More informationPUROTAP easy. Installation Function Operation Service. fast efficient safe. Demineralised heating water perfect for every system
EN Demineralised heating water perfect for every system PUROTAP easy Installation Function Operation Service fast efficient safe Minerals and salts in technical water circulations lead to corrosion and
More informationSystem Solutions. Efficient energy use, effective flash steam utilisation, and tailor-made customer solutions CHEMICAL THE STEAM SPECIALIST.
THE STEAM SPECIALIST. System Solutions Efficient energy use, effective flash steam utilisation, and tailor-made customer solutions > Condensate drainage > Flash steam usage > Heating systems > Special
More information1. Know your process. The following guidelines will help you navigate what can be a challenging and time consuming task.
Many processes today require an indirect method of heating, which implies the use of a heat transfer medium, instead of circulating the process directly into a heater. Thermal oil, water, glycol mixtures,
More informationwww.greenspower.com.sg 1company profile G reens Power have been at the forefront of Waste Heat Recovery Technology since Edward Green first patented the Fuel Economiser in 1845. The business developed
More informationIN THE PULP AND PAPER INDUSTRY
H E A T E X C H A N G E R S BULLETIN NO. TIS-105A PRIME SURFACE PLATE & FRAME ALL-WELDED PLATE IN THE PULP AND PAPER INDUSTRY THE heat transfer people H E A T E X C H A N G E R S 2 TRANTER BRINGS EFFICIENCY
More informationSteam and Gas Power Systems Prof Ravi Kumar Department of Mechanical and Industrial Engineering Indian Institute of Technology - Roorkee
Steam and Gas Power Systems Prof Ravi Kumar Department of Mechanical and Industrial Engineering Indian Institute of Technology - Roorkee Module No # 02 Lecture No # 09 Boilers Mountings and Accessories
More information100 years of boiler technology leadership.
100 years of boiler technology leadership. TM A subsidiary of Burnham Holdings Compact Boiler Feed Systems Capacities from 20 to 80 boiler HP 15 through 150 PSI boilers The Bryan compact boiler feed system
More informationBuildingName The Description of the Project P DOCUMENTS
ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION
More information9. Cooling Water System
9.1 Water quality The fresh water in the cooling water system of the engine must fulfil the following requirements: ph... Hardness... Chlorides... Sulphates... min. 6.5...8.5 max. 10 dh max. 80 mg/l max.
More informationUnderstanding Process Vacuum for Process Improvement
Understanding Process Vacuum for Process Improvement Through this article we wish to give practical tips to boost process capacity, increase product quality and reduce cycle time in batch or continuous
More informationPamphlet M2404. Mechanical Pump & Pump/ Trap. GP Series GT Series
Pamphlet M2404 Mechanical Pump & Pump/ Trap GP Series GT Series Effective Processing Improves Plant Efficiency Increased productivity and product quality, plus reduced energy consumption and water treatment
More informationGas Plant Training Module 4 TEG Dehydration Systems
Module 4 TEG Dehydration Systems Table of Contents Introduction...2 Objectives...2 Glycol Dehydration...3 Dehydration System Process Control...4 Contactor C301...6 Glycol Regenerator...7 Flash Separator
More informationPamphlet U2404. Mechanical Pump & Pump/ Trap. GP Series GT Series
Pamphlet U2404 Mechanical Pump & Pump/ Trap GP Series GT Series Effective Processing Improves Plant Efficiency Increased productivity and product quality, plus reduced energy consumption and water treatment
More informationWhen you complete this module you will be able to: Describe various watertube boiler designs, including large generating units.
Watertube Boilers Learning Outcome When you complete this module you will be able to: Describe various watertube boiler designs, including large generating units. Learning Objectives Here is what you will
More informationGRUNDFOS IndustrY ENGINEERING MANUAL. Industrial Boilers
GRUNDFOS IndustrY ENGINEERING MANUAL Industrial Boilers 1 ENGINEERING MANUAL Copyright 2009 GRUNDFOS Management A/S. All rights reserved. Copyright law and international treaties protect this material.
More informationInstallation, Operation and Maintenance Guide. Steam Coil Installation, Operation and Maintenance. steam coils
Installation, Operation and Maintenance Guide Steam Coil Installation, Operation and Maintenance Guidelines for the installation, operation and maintenance of the Heatcraft brand of steam heating coils
More informationVIESMANN VITOROND 100. Datasheet Part numbers and prices: see pricelist VITOROND 100. Cast iron low temperature oil and gas fired boiler.
VIESMANN VITOROND 100 Cast iron low temperature oil and gas fired boiler 40 to 100 kw Datasheet Part numbers and prices: see pricelist File in: Vitotec folder, register 1 VITOROND 100 Type VR2B Cast iron
More informationMoss MOSS TRAY DEAERATOR ECONOMICAL INDUSTRIAL DEAERATOR SYSTEMS
Moss MOSS TRAY DEAERATOR ECONOMICAL INDUSTRIAL DEAERATOR SYSTEMS MOSS TRAY DEAERATOR DESIGNS WHY DEAERATE? Removal of corrosive oxygen and carbon dioxide from boiler feedwater Reduction in the use of oxygen
More informationDivacondens D Plus Atmospheric condensation wall-mounted boilers, with instant domestic hot water production
Divacondens D Plus Atmospheric condensation wall-mounted boilers, with instant domestic hot water production THE SIMPLEST SOLUTION FOR A CONDENSING BOILER DIVACONDENS D PLUS is the generator of condensation
More informationEvaporation The process in which a liquid dissipates or emits vapor, fumes, or invisible minute particles.
35 Evaporation of waste wash water occurs during normal operation of the pressure, steam or automatic vehicle wash system. It is generally assumed that 10-30% of wash water is lost to evaporation. Accelerated
More informationProduct overview. the optimum components for every application
For further information, please contact Distributor : Energy Technology Co., Ltd. 46 Soi On-Nuch 9, Sukhumvit Rd., Suanluang, Bangkok 020 Tel : (66) 0-272-860 Fax : (66) 0-272-869 E-mail : sales@energytechnology.co.th
More informationTYPE.005 DA-STP TYPE.005 DA-STP-2T. Spray Tray Deaerating Pressurized Boiler Feed Pumps. and. when separate surge tank is utilized
SHIPPENSBURG PUMP CO., INC. P.O. BOX 279, SHIPPENSBURG, PA 17257 PHONE 717-532-7321 FAX 717-532-7704 WWW.SHIPCOPUMPS.COM BULLETIN 147 Revised 7/09 TYPE.005 DA-STP Spray Tray Deaerating Pressurized Boiler
More informationOzone & UV & AOP Solutions ADVANCED TECHNOLOGIES
OZONE GENERATING SKID PACKAGES FOR BOTTLING & RINSING & HIGH PURITY PLANTS EC-OZ/SS & EC-ST/SS series 3 to 60 g/h EC- ST/SS SERIES EC-OZ/SS SERIES The skid mounted ozone generator systems are specifically
More informationClyde Alkon 90. Floor standing condensing boilers. Natural Gas. 90 kw. LP Gas. 90 kw
90 kw Clyde Alkon 90 LP Gas Floor standing condensing boilers Natural Gas 90 kw Contents General information Dimensions and Data Installation requirements Boiler wiring diagram Hydraulic systems Page Fully
More informationInstruction Manual STR MODEL RESISTO-FLO ELECTRIC BOILER
Page 1 of 18 Instruction Manual STR MODEL RESISTO-FLO ELECTRIC BOILER Page 2 of 18 FOREWORD The STR Resisto-Flo Electric Steam Boiler is designed to provide a compact packaged unit requiring a minimum
More informationMECHANICAL SCIENCE Module 2 Heat Exchangers
Department of Energy Fundamentals Handbook MECHANICAL SCIENCE Module 2 Heat Exchangers Heat Exchangers DOE-HDBK-1018/1-93 TABLE OF CONTENTS TABLE OF CONTENTS LIST OF FIGURES... ii LIST OF TABLES... iii
More informationMFP14 Automatic pumps for condensate and other industrial fluids
MFP14 Automatic pumps for condensate and other industrial fluids Effective condensate management... an essential part of any steam plant If energy requirements are to be kept to a minimum, then efficient
More informationANNEX 6. Refinery No. 1 New Area. Problems Existing in the Current Condensate Return System of the New Area of Refinery No.1
ANNEX 6 In FP the project was divided in two phases, but due to financial difficulties, Phase II is still not implemented. Below is what happened in Phase I of the Project, which will be replicated in
More information