65 MBH through 2890 MBH. LD16237a. June 18, 2015

Size: px
Start display at page:

Download "65 MBH through 2890 MBH. LD16237a. June 18, 2015"

Transcription

1 AIR-COOLED CONDENSER AND FLUID COOLER INSTALLATION, OPERATION, MAINTENANCE Supersedes: NM1 (413) Form NM1 (615) MODEL VDC Condenser and MODEL VDCF Fluid Cooler VDC 66 Models R-22, R-134A, R-404A, R-407C, R-410A, R-507A Nominal Heat Rejection Capacity 175 MBH through 2280 MBH VDCF 22 Models Water, Ethylene Glycol, Propylene Glycol Nominal Heat Rejection Capacity 65 MBH through 2890 MBH LD16237a Issue Date: June 18, 2015

2 IMPORTANT! READ BEFORE PROCEEDING! GENERAL SAFETY GUIDELINES FORM NM1 This equipment is a relatively complicated apparatus. During rigging, installation, operation, maintenance, or service, individuals may be exposed to certain components or conditions including, but not limited to: heavy objects, refrigerants, materials under pressure, rotating components, and both high and low voltage. Each of these items has the potential, if misused or handled improperly, to cause bodily injury or death. It is the obligation and responsibility of rigging, installation, and operating/service personnel to identify and recognize these inherent hazards, protect themselves, and proceed safely in completing their tasks. Failure to comply with any of these requirements could result in serious damage to the equipment and the property in which it is situated, as well as severe personal injury or death to themselves and people at the site. This document is intended for use by owner-authorized rigging, installation, and operating/service personnel. It is expected that these individuals possess independent training that will enable them to perform their assigned tasks properly and safely. It is essential that, prior to performing any task on this equipment, this individual shall have read and understood the on-product labels, this document and any referenced materials. This individual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in question. SAFETY SYMBOLS The following symbols are used in this document to alert the reader to specific situations: Indicates a possible hazardous situation which will result in death or serious injury if proper care is not taken. Identifies a hazard which could lead to damage to the machine, damage to other equipment and/or environmental pollution if proper care is not taken or instructions and are not followed. Indicates a potentially hazardous situation which will result in possible injuries or damage to equipment if proper care is not taken. Highlights additional information useful to the technician in completing the work being performed properly. External wiring, unless specified as an optional connection in the manufacturer s product line, is not to be connected inside the control cabinet. All wiring must be in accordance with Johnson Controls published specifications and must be performed only by a qualified electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper connections to the controls or application of improper control signals. Failure to follow this warning will void the manufacturer s warranty and cause serious damage to property or personal injury. 2 JOHNSON CONTROLS

3 CHANGEABILITY OF THIS DOCUMENT In complying with Johnson Controls policy for continuous product improvement, the information contained in this document is subject to change without notice. Johnson Controls makes no commitment to update or provide current information automatically to the manual or product owner. Updated manuals, if applicable, can be obtained by contacting the nearest Johnson Controls Service office or accessing the Johnson Controls QuickLIT website at johnsoncontrols.com. It is the responsibility of rigging, lifting, and operating/ service personnel to verify the applicability of these documents to the equipment. If there is any question regarding the applicability of these documents, rigging, lifting, and operating/service personnel should verify whether the equipment has been modified and if current literature is available from the owner of the equipment prior to performing any work on the chiller. Change Bars Revisions made to this document are indicated with a line along the left or right hand column in the area the revision was made. These revisions are to technical information and any other changes in spelling, grammar or formatting are not included. JOHNSON CONTROLS 3

4 CONDENSER AND FLUID COOLER NOMENCLATURE V D C D 6 0 X X X P G J BASE MODEL VDC = Vertical Up Airflow HDC = Horizontal Airflow DUTY = Condenser F = Fluid Cooler FANS WIDE 1 Single-Wide Model 2 Double-Wide Model FANS IN LINE 1 = 1 Fan Long (Single-Wide only) 2 = 2 Fans Long 3 = 3 Fans Long 4 = 4 Fans Long 5 = 5 Fans Long 6 = 6 Fans Long COIL ROWS DEEP 3 = 3 Rows (Condenser and 1-Fan Fluid Cooler) 4 = 4 Rows 6 = 6 Rows 8 = 8 Rows (Fluid Cooler only) COIL CONSTRUCTION B = 5/8 in. OD Tube (1- through 6-Fan, Single-Wide Fluid Coolers) (4-, 6-, 8-, 10- & 12-Fan, Double-Wide Fluid Coolers) C = 1/2 in. OD Tube (5- and 6-Fan, Single-Wide Condensers) (10- and 12-Fan, Double-Wide Condensers) D = 3/8 in. OD Tube (1- through 4-Fan, Single-Wide Condensers) (4-, 6- and 8-Fan, Double-Wide Condensers) MOTOR HORSEPOWER, FAN SPEED 1 = 1.0 HP, 840 RPM (60 Hz) 6 = 2.0 HP, 1150 RPM (60 Hz) 7 = 1.0 HP, 700 RPM (50 Hz) 9 = 2.0 HP, 950 RPM (50 Hz) FAN CONTROL TYPE W = Without Fan Cycling S = Temperature Controlled K = Temperature Controlled (VDCF only) J = Pressure Controlled I = VSD-Ready, Variable Speed Control Double-Wide Units, Individual Fan Banks U = Temperature Controlled L = Temperature Controlled (VDCF only) Z = Pressure Controlled MOTOR POWER AND TYPE TEAO with ATO, Inverter Duty Rated: A = 200/3/60 C = 230/3/60 H = 380/400/415/3/50 G = 460/3/60 J = 575/3/60 HOUSING P = Painted COIL CIRCUIT X = Condenser B = 4-Pass Fluid Cooler C = 6-Pass Fluid Cooler FIN MATERIAL X = Aluminum H = Holly Gold Coated Aluminum (3/8 in. OD tube only) C = Copper (3/8 in. OD tube only) COIL COAT X = Not Coated E = ElectroFin y Coated FINS PER INCH 8 = 8 FPI (Condensers only) 0 = 10 FPI (Standard) 2 = 12 FPI (3 and 4 row Condensers only) 4 = 14 FPI (3 and 4 row Condensers only) NOTE: TEAO Totally Enclosed Air Over ATO Automatic Thermal Overload (Integral) 4 JOHNSON CONTROLS

5 TABLE OF CONTENTS SECTION 1 - GENERAL INFORMATION...9 Mechanical Specifications...9 Overview...9 Legs...9 Coil...9 Headers...9 Housing...9 Fan Guards...9 Fans...9 Motors...9 Motor Mounts...10 Basic Factory Wiring (Standard)...10 Basic Motor Control (Standard)...10 Shipping...10 Lifting...10 SECTION 2 - PRODUCT DESCRIPTION Accessories and Options Special Coils Sealtite Conduit Manifold Kit Motor Wiring Options for Fan Control Fan Cycling Options SECTION 3 - HANDLING AND STORAGE...13 Preface...13 Shipping Inspection...13 Coil Inspection...13 Safety Requirements...13 SECTION 4 - INSTALLATION...15 Mounting...15 Crane Rigging Instructions...15 Location...16 Indoor Applications...16 Outdoor Applications...16 Wiring...17 Corrosive Environment...17 Electric Power Supply...17 Refrigerant Piping - Condenser...17 Refrigerant Line Sizing...17 Chiller Below Condenser...18 Condenser Below Chiller...18 Oil Traps...18 Refrigerant Piping Reference...18 R-410A Copper Line Sizing...18 YCRL Line Sizing Notes...18 Suggested Field Piping Arrangements...18 JOHNSON CONTROLS 5

6 TABLE OF CONTENTS (cont d) Recommended Refrigeration Line Sizes...19 Receiver Location (if Required for Refrigerant Storage)...21 Refrigerant Charge...22 SECTION 5 - TECHNICAL DATA...23 Dimensions - Condenser...23 Dimensions - Fluid Cooler...24 VDC Charge Calculation...25 Physical Data...26 Wiring Diagrams...48 SECTION 6 - COMMISSIONING...57 Unit Identification...57 Start-Up...57 SECTION 7 - UNIT OPERATION...59 Standard Fan Cycling...59 VDC Pressure Setting Guidelines...60 Two-stage units (2-fan single-wide, 4-fan double-wide VDC)...60 Three-stage units (3-fan single-wide, 6-fan double-wide VDC)...60 Four-stage units (4-fan single-wide, 8-fan double-wide VDC)...60 Low Ambient Operation...60 Low Ambient Control Options...60 Fan Cycling Control...60 A99 Temperature Sensor Description and Mounting...61 Description...61 Accessories...61 Operation...61 Temperature Sensor Mounting - VDC...62 Temperature Sensor Mounting - VDCF...62 Mounting Using an Immersion Well - VDCF...62 Temperature Sensor Replacement Parts...63 Pressure Transducers Mounting...63 VSD Inverter Wiring...64 VSD Inverter Installation Checklist...64 SECTION 8 - MAINTENANCE...65 General...65 Cleaning...65 Recommended Spare Parts JOHNSON CONTROLS

7 list of figures Figure 1 - Unit Components...10 Figure 2 - Rigging And Leg Mounting Drawing...15 Figure 3 - Condenser, Compressor And Receiver On Same Level...18 Figure 4 - Capacity Controlled Systems...19 Figure 5 - Condenser Higher Than Compressor And Receiver...19 Figure 6 - Two Or More Condensers Connected To One Compressor...19 Figure 7 - Typical Piping Arrangement - VDC...20 Figure 8 - Refrigerant Connections - VDC...21 Figure 9 - Liquid Connections - VDCF...22 Figure 10 - Basic Factory Wiring - Standard, 1-6 Fans Long - VDC and VDCF...48 Figure 11 - Temp-Controlled Fan Cycling, 2-6 Fans Long - VDC...49 Figure 12 - Temp-Controlled Fan Cycling, 2-6 Fans Long, Double-Wide, Fans Wired Individually - VDC Figure 13 - Temp-Controlled Fan Cycling, 2-6 Fans Long - VDCF...51 Figure 14 - Temp-Controlled Fan Cycling, 2-6 Fans Long, Double-Wide, Fans Wired Individually - VDCF Figure 15 - Pressure-Controlled Fan Cycling, 2-5 Fans Long - VDC...53 Figure 16 - Pressure-Controlled Fan Cycling, 6 Fans Long - VDC...54 Figure 17 - Pressure-Controlled Fan Cycling, 2-6 Fans Long, Double-Wide, Fans Wired Indivdualy - VDC Figure 18 - VSD-Controlled Fans, 2-6 Fans Long, Double-Wide Fans Wired in Pairs - VDC and VDCF Figure 19 - ID Plate Information, VDC - Monterrey, Mexico...57 Figure 20 - ID Plate Information, VDCF - Monterrey, Mexico...57 Figure 21 - ID Plate Information, VDC - San Antonio, TX...57 Figure 22 - ID Plate Information, VDCF - San Antonio, TX...57 Figure 23 - A99B Temperature Sensors...61 Figure 24 - A99B Sensor Accessories...61 Figure 25 - A99B Sensor Dimensions...61 Figure 26 - Installing The Immersion Well...62 Figure 27 - Insert Sensor, Spring And Bushing...62 Figure 28 - P499 Electronic Pressure Transducers...63 Figure 29 - Pressure Transducer Wiring...63 JOHNSON CONTROLS 7

8 list of tables Table 1 - Receiver And Heater Data...21 Table 2 - Unit Dimensions - Condensers...23 Table 3 - Unit Dimensions - Fluid Coolers...24 Table 4 - VDC Charge Calculation...25 Table 5 - VDC Condenser 2.0 HP Rating And Physical Data...26 Table 6 - VDC Condenser 1.0 HP Rating And Physical Data...31 Table 7 - VDCF Fluid Cooler 2.0 HP Rating And Physical Data...36 Table 8 - VDCF Fluid Cooler 1.0 HP Rating And Physical Data...41 Table 9 - Lug Data...46 Table 10 - Minimum Ambient Temperatures For Fan Cycling Control...59 Table 11 - Temperature Settings For Fan Cycling...59 Table 12 - Resistance vs. Temperature...62 Table 13 - Replacement Temperature Sensor Product Code Numbers...63 Table 14 - Pressure vs. Voltage...64 Table 15 - VSD Inverter Connections JOHNSON CONTROLS

9 SECTION 1 - GENERAL INFORMATION 1 Mechanical Specifications Overview YORK Air-Cooled Condensers, Models VDC-113D10 through VDC-266C60, are available in 66 standard model sizes for air conditioning and refrigeration applications, and may be used with any type of compressor for halocarbon refrigerants. YORK Air-Cooled Fluid Coolers, Models VD- CF113B10 through VDCF268B60, are available in 22 standard model sizes for commercial and industrial fluid cooling and may be used with water or glycol. Contact Johnson Controls for special applications, for example, winter-weather chiller economizer duty or cooling industrial fluids. Air-cooled condensers and fluid coolers air-sides operate dry (requiring a minimum of maintenance) and do not require pump and water piping installation except for fluid-side fluid cooling. Vertical airflow units are standard design for low silhouette applications. Legs Made from heavy-gauge galvanized steel with foot pads and mounting holes on the bottom of each leg. Coil Seamless copper tubes are expanded into full-collar aluminum fins. Fins have a corrugated surface to enhance heat transfer. Fin edges are rippled to work harden and stiffen material for resistance to mechanical damage. Return bends and headers are brazed with highly ductile silver-bearing copper alloy. Coil casings and tubesheets are manufactured from galvanized steel. The tubesheets include aluminum inserts to prevent wear at the juncture of the tubes and tubesheets. Prior to shipment, coils are strength and leak tested at design pressure, dehydrated, evacuated, pressurized with dry air or nitrogen, and sealed for shipment. Condenser coils up to four fan lengths use 3/8 in. OD internally enhanced microfin tubes for optimum performance. Five- and six-fan length coils use 1/2 in. OD tubes. Fluid coolers use 5/8 in. OD tubes for low pressure drop. For R-22, R-134a, R-407C, R-404A, and R-507A condensing, the 3/8 in. and 1/2 in. OD tube coils have a 420 psig (29 barg) design pressure at 250 F (121 C) for up to a 140 F (60 C) condensing temperature. For R-410A, the 3/8 in. OD tube coils have a 650 psig (44.8 barg) design pressure at 250 F (121 C) for up to a 140 F (60 C) condensing temperature. For fluid coolers the 5/8 in. OD tube coils have a 250 psig (17.25 barg) design pressure for up to 145 F (62.8 C) entering fluid temperature. Headers Heavy-wall copper tube headers are designed for low pressure loss and proper refrigerant distribution. Double-wide units feature completely separate headers for each system circuit so there is no danger of refrigerant leakage between circuits. Inlet and outlet connections are provided. Integral subcooling is available for condensers. Housing The unit structure is comprised of heavy-gauge galvanized steel panels coated with baked-on champagnecolored powder paint, which, when subjected to ASTM B hour salt spray testing, yields a minimum ASTM 1654 rating of "6". These panels are assembled with high-tensile strength fasteners. Fan panels have long, smooth-radius outlet orifices to ensure high energy efficiency and low noise level. Each fan section is fully compartmentalized to prevent fan windmilling. Fan Guards Heavy-gauge OSHA-accepted fan guard design uses corrosion resistant, coated-steel wire. Fans High-efficiency, high-strength airfoil-profile blade fans are used for low noise and energy-efficient performance. Motors Totally enclosed air-over (TEAO) motors have builtin thermal overload (ATO) protection and are inverter duty ready. They feature ball bearings that are doublesealed and permanently lubricated. Standard motor is 2.0 hp, 3-phase, 60 Hz, 200, 230, 460, or 575 volts. Optional 1.0 hp, 3-phase, 60 Hz, 200, 230, 460, or 575 volts and 2.0 or 1.0 hp, 3-phase, 50 Hz, 380, 400, or 415 volts are also available. JOHNSON CONTROLS 9

10 SECTION 1 - GENERAL INFORMATION Motor Mounts Heavy-gauge galvanized steel channels are used to mount motors. Basic Factory Wiring (Standard) Motors are wired to contactors located in a UL-listed NEMA 4, weather-resistant enclosure, which includes a non-fused disconnect switch for single point power wiring, motor fuses, contactors, and an integral 115 volt control transformer. Enclosure is painted to match unit housing, and it ships mounted. FORM NM1 Basic Motor Control (Standard) Basic motor control does not support fan cycling. To include fan cycling, select an optional motor control. Shipping All units are shrink-wrapped with heavy sheet plastic wraps to protect the unit from road debris and temporary storage. Lifting Units must be crane lifted off shipping truck and to final location. FAN DECK CONTROL PANEL COIL HEADERS LOCKING HANDLE Note 1 : Fluid cooler inlet is horizontal UNIT COIL CONNECTIONS 1 UNIT LEG LD16237a Figure 1 - Unit Components 10 JOHNSON CONTROLS

11 SECTION 2 - PRODUCT DESCRIPTION Accessories and Options Special Coils While standard aluminum fins are compatible with most environments, when a unit is subjected to an especially corrosive atmosphere, such as coastal air with a high concentration of salt, special fin treatment may be required. The following options are available for these applications. Holly Gold Coat This gold-colored, corrosion-resistant, polyester-polymer-coated aluminum fin passes 1000 hours of ASTM B117 salt spray testing. Available only with 3/8 in. OD tube coils. ElectroFin Coat ElectroFin Coat is applied to the completed coil, protecting the tubes, fins, headers, and galvanized steel casing with a coating that passes 5000 hours of ASTM B117 salt spray testing. Does not include shipped loose manifold kit. Copper-Finned Coils Copper-finned coils are available for applications where the environment may cause galvanic corrosion of aluminum fins. Available only with 3/8 in. OD tube coils. Sealtite Conduit All fan motor wiring enclosed in sealed conduit. Manifold Kit Ties dual inlet and outlet connections together on double-wide units for a single field connection (shipped loose for field installation). Typically used on doublewide condensers for use with a single chiller circuits or double-wide fluid coolers. Not available from factory on units with 4 1/8 in. OD connections. Motor Wiring Options for Fan Control Motors are wired to contactors located in a UL-listed NEMA 4, weather-resistant enclosure, which includes a non-fused disconnect switch, motor fuses, contactors, and an integral 115 volt control transformer. See Table 10 on page 59 and Table 11 on page 59, for fan-cycling control settings or contact Application Engineering for support. Enclosure ships mounted. If there is a concern about noise due to fan cycling, it is recommended that Head Pressure Control (Variable Speed Drive (VSD) Ready) be used. Double-Wide Unit Fan Cycling Fan Cycling Options for Double-Wide Units are available with fans cycling in pairs or, for temperature-controlled and pressurecontrolled fan cycling, with individual fan-bank fan cycling so the VDC can serve individual chiller circuits. Fan Cycling Options Head Pressure Control by Temperature Motors are wired for temperature-controlled fan cycling. A temperature sensor, supplied with a clip for mounting in condenser s air stream or a bulb well for installation in fluid cooler s leaving fluid piping, must be field installed. Fans next to the header are always running when unit is activated by run signal. Receivers are not required. For fluid coolers, the lowest allowable leaving fluid temperature is -13 F (-25.0 C) which can be safely done with 50% Ethylene Glycol or 50% Propylene Glycol and a minimum ambient of -20 F (-28.9 C). When a glycol heat transfer fluid is used in the YORK VDCF fluid cooler ensure that the fluid maintains the correct design glycol concentration. It is imperative to maintain a high enough concentration to prevent the fluid cooler from experiencing a solution freeze that can permanently damage the coil. Johnson Controls recommends that the fluid be checked to verify that the correct concentration is maintained at the beginning of seasonal cold weather or any time the system is opened or a leak is discovered. It is also important that the unit is rated for the concentration of glycol that will be used. Higher concentrations than required will reduce the unit's heat transfer capacity and increase fluid pump horsepower. The concentration required for the given application will depend on the particular glycol-based heat transfer fluid used and the lowest expected temperature. Different fluids have different specific gravity, specific heat, viscosity and thermal conductivity at different percentages and temperatures. Typically the system should be protected to 15 degrees below the lowest anticipated temperature. The fluid manufacturer's recommenda- 2 JOHNSON CONTROLS 11

12 SECTION 2 - PRODUCT DESCRIPTION FORM NM1 tions should be closely followed for your particular application. The A350 controller and stage module are supplied with this option to control the fans. Head Pressure Control by Pressure Required when selecting a VDC for use as a remote condenser for a YCRL chiller. Motors are wired for pressure-controlled fan cycling. Included pressure transducer(s) must be field installed. Fans next to the header are always running when unit is activated by run signal. Receivers are not required. The P470 controller and stage module are supplied with this option to control the fans. Head Pressure Control (VSD Ready) Motors are wired for variable speed fan control. VSD bypass control circuit is included, but inverter drive (VSD) is not included. Temperature or pressure sensor(s) for control must be field provided and installed, if desired. Field-installed inverter drives (VSDs) shall be mounted on or in close proximity to the VDC unit. The inverter drive shall be equipped with load reactors for installations that require more than 25 feet of wire between the inverter and the VDC unit or whenever distortion is a concern to prevent voltage spikes that can damage the fan motors and void the VDC motor warranty. Motor damage caused by an improperly installed VSD is not warranted. The VSD s switching frequency shall not exceed 4 KHz. When this option is selected, the option Sealtite Conduit on page 11 shall also be selected to ensure that the motor wire is shielded from voltage spikes. Grounding of conduit and all wiring is of extreme importance. See Figure 18 on page 56 and VSD Inverter Wiring on page JOHNSON CONTROLS

13 SECTION 3 - HANDLING AND STORAGE Preface Your Johnson Controls Air-Cooled Condenser or Fluid Cooler incorporates the finest in engineering design, materials, and corrosion protection to provide a rugged long lasting unit. Proper installation, care and maintenance of your unit are essential to good performance and long life. Before rigging or beginning work on the unit, Johnson Controls recommends that experienced refrigeration contractors, operators, and maintenance technicians are formally trained on the Johnson Controls Air-Cooled Condenser features. Reading this manual is a minimum requirement. Before installing your unit, we suggest that you read the following instructions carefully and keep them handy for ready reference. After installation, the unit must be properly connected to appropriately designed and installed refrigeration systems. The engineering plans, piping layouts, etc., for the Johnson Controls Air-Cooled Condenser or Fluid Cooler and associated system components must be detailed in accordance with local/governing codes and the best industry standards and practices such as those outlined in current industry literature. Reference the DX Piping Guide, Form ES2 and the 2010 ASHRAE Refrigeration Handbook, Chapter 1, especially noting the Safety Requirements section for high pressure refrigerants on page Shipping Inspection Carefully examine the unit and notify the transportation agent of any missing parts or damage. It is advisable to inspect the unit as soon as received and to make a record of the serial number, and motor data. The unit shipment should be checked on arrival to ensure that all major pieces, boxes and crates are received. The unit should be checked on the trailer or rail car before unloading, for any visible signs of damage. Any damage or signs of possible damage should be reported to the transportation company immediately for their inspection. Contact the Johnson Controls Regional or District office in order for a Johnson Controls Representative to assist in filing damage claims. Johnson Controls will not be responsible for any damage in shipment or at job site, or loss of parts, if these shipping inspection instructions are not followed. (Refer to BOS Document Submitting and Processing Claims for materials lost or damaged in transit BEHQ) Once received at the job site, all containers should be opened and contents checked against the packing list. Any material shortage should be reported to Johnson Controls immediately. (Refer to Shipping Damage Claims, Form NM.) Coil Inspection The refrigerant coil has a low pressure charge from the factory. Check the coil to see that the holding charge is intact. To do this, remove the 1/4 inch cap and briefly depress the Schrader valve located on the liquid or suction header of each circuit to verify pressure. The charge must be maintained until refrigerant or fluid piping is connected to the unit. A coil that does not have a charge may have been damaged during transit. If the charge is not present when the unit is received, the coil must be pressure tested to 100 psig with dry nitrogen gas to confirm that it is leak free. Contact Johnson Controls before installing any air-cooled condenser or fluid cooler unit that has lost the factory charge. When communicating with the factory, refer to the model and serial numbers which are located on the unit nameplate. Safety Requirements Only experienced, qualified personnel should install, operate and maintain refrigeration equipment. Perform frequent visual inspections and continuously monitor a condenser to prevent the escape of refrigerant. Use electronic refrigerant detectors in the unit proximity for continuous monitoring and detection of the presence of refrigerant in the atmosphere. 3 JOHNSON CONTROLS 13

14 SECTION 3 - HANDLING AND STORAGE FORM NM1 This Page Intentionally Left Blank. 14 JOHNSON CONTROLS

15 SECTION 4 - INSTALLATION Mounting Once the unit is placed in the desired location, secure legs to floor or steel work with 3/4" diameter bolts to prevent movement. The top should be level and the unit should be supported along its entire length (i.e., every leg should be secured). Use of vibration pads or isolators is recommended. The supporting structure must be strong enough to support the weight of the unit. Crane Rigging Instructions All units are designed for removal from the truck by crane only. Use lifting brackets shown on Figure 2 on page 15. Be careful to lift units evenly and balanced to avoid undue stress on the equipment. Refer to customer submittal drawings for dimensional data and weight before installing units. 4 Figure 2 - Rigging And Leg Mounting Drawing LD14082 JOHNSON CONTROLS 15

16 SECTION 4 - INSTALLATION Location Johnson Controls remote Air-Cooled Condensers and Fluid Coolers are designed to meet practically any requirement for mounting either indoors or outdoors. Care should be taken not to mount the unit where it is continually exposed to loose dirt or foreign matter which might clog the coil surface. The unit must be mounted in a level position, both front-to-back and side-to-side. An important consideration when locating the condenser is providing for adequate airflow to and from the unit. A minimum distance of four feet is recommended on all sides of the unit, with eight feet minimum recommended between adjacent air-cooled condensers. The capability and performance of the unit is dependent upon the unimpeded flow of ambient air over the extended surface for removal of heat from the refrigerant discharge gas within the coil. Solar effect has negligible bearing on the performance of the air-cooled condenser. Indoor Applications When the condenser or fluid cooler is mounted indoors, the air leaving the unit must be discharged to the outdoors to prevent recirculation of heated air through the unit. Provision must also be made for sufficient fresh air intake into the area where the unit is located. When a discharge duct is used with a propeller fan, the duct's added static pressure leaves the unit subject to diminished heat transfer capacity because of a reduction in airflow. The unit's rated capacity can be preserved by designing the duct for negligible pressure loss, by the addition of an external fan to overcome the duct's static pressure, or by a combination of the two. All fan guards should be removed and access provided in the duct to allow for servicing the fan and drive assemblies. A flexible duct connection will minimize noise transmission. If louvers are to be installed on the duct outlet, the free open area should equal the duct cross sectional area. For ducts of greater or lesser cross sectional area, special fans and motors can be furnished by Johnson Controls. Consult the factory for specific recommendations and pricing. FORM NM1 If inlet ducts are not provided, unrestricted flow of fresh air to the unit must be ensured. Care must be taken to ensure that the fresh air supplied is at the ambient air temperature. If air is taken from an area where the heat exceeds the ambient air temperature, the unit s capacity will be reduced. The arrangement must ensure that heated condenser discharge air is not re-circulated to the air intake of the unit. Outdoor Applications Your Johnson Controls Air-Cooled Condenser or Fluid Cooler has the fan motor(s) located inside the casing and requires no special provisions for weather protection. Multiple units should be installed so that the discharge of one unit is not directed into the intake of another unit. A vertical airflow unit may be located without regard to prevailing wind. These units minimize fan noise and allow greater flexibility of location in relation to surrounding structures. When installing condensers and fluid coolers, a location should be chosen so that at least three sides of the unit have unrestricted airflow. The fan should have free flow unrestricted by any overhanging structures. The unit may be placed close to a building on one side with a minimum clearance of eight feet. In the case of multiple unit installations, units may be placed end-toend without penalty and side-by-side with a minimum of four feet apart for single-wide and eight feet apart for double-wide units. Where located on a roof, it is best to mount the unit with the longer side parallel to the roof edge to minimize the potential for drawing heated air from the roof surfaces. The rugged mounting legs of the Johnson Controls Air- Cooled Condensers and Fluid Coolers are designed to provide sufficient height for any operating condition. Mounting pads should be located for ground level installation. When the unit will be located where an excessive buildup of superheated air is expected, the unit should be mounted in a structural open frame. 16 JOHNSON CONTROLS

17 SECTION 4 - INSTALLATION Wiring A disconnect, as required by local codes, should be provided for each motor circuit. The motors have internal thermal overload protection; therefore, multiple motors may be started from each circuit. See SECTION 5 - TECHNICAL DATA for wiring diagrams. With factory wired motors, verify that the supply voltage is the same as the motor nameplate voltage. For field wiring, check the wiring terminals inside the motor to ensure that they are wired for proper power supply voltage. The wiring diagram is attached to the motor housing. Also, confirm fan rotation direction as indicated by the fan blades. Corrosive Environment These units must not be installed in environments that may be corrosive to the materials of construction. This could result in reduced performance, condenser fin deterioration and coil leaks not covered by warranty. Electric Power Supply Check the electrical characteristics on the unit nameplate to make sure the power supply is the same. Only qualified electricians should install the power supply. All work should be done in conformance with prevailing codes and regulations. Do not remove safety equipment or warning labels from equipment. Removal could result in serious injury or death. Disconnect the power supply to the unit before performing any service or maintenance. The disconnect should be locked in the OFF position following proper lockout tagging procedures. Refrigerant Piping - Condenser Special care must be taken to ensure adequate sizing of refrigerant piping for Johnson Controls Air-Cooled Condensers. Applicable standards should be consulted in this regard. The copper tubing should be de-oxidized and dehydrated Type L refrigeration tubing with wrought copper fittings employed. Keep all piping clean, and clean all pipe connections with a wire brush or the equivalent. Braze with 5% silver braze material with the recommended flux. Use a wet rag around the next solder joint when brazing. Piping systems with halocarbon refrigerants must be properly evacuated to remove noncondensables and moisture prior to the introduction of refrigerant. A vacuum of 750 microns is the minimum requirement to remove moisture. The liquid drain line should not be exposed to high temperatures, and therefore should be insulated if it passes through an environment where temperatures exceed 120 F. All refrigerant piping must be well supported and protected from vibration. The condenser piping connections should not be left open to the atmosphere for any longer than required for solder connections to be made. Install a shut-off valve at the receiver inlet (if used). Install a purge valve or fitting at the highest point in the discharge gas piping. In order to prevent condensed liquid refrigerant from causing damage to the compressor(s), install a trap in the vertical discharge piping at the compressor(s). The height of the trap should be 6 inches for every 10 feet of vertical discharge piping. If the height of the vertical piping makes this impractical, the trap may be replaced by a check valve. When installing refrigeration piping, make certain that it is well supported. Make sure the vibrations from the compressor, condenser and piping are not transmitted to the building. The use of a discharge muffler may be necessary to prevent noises due to refrigerant pulsations; particularly with high speed compressors. Refrigerant Line Sizing Refrigerant piping systems must be designed to provide practical line sizes without excessive pressure drops to prevent compressor oil from being "trapped" in the refrigerant piping, and to ensure proper flow of liquid refrigerant to the thermal expansion valve. Be sure to review DX Piping Guide, Form ES2. Considerations should be given to: 1. Discharge line pressure drop due to refrigerant flow. 2. Discharge line refrigerant velocity for oil return. 3. Liquid line pressure drop due to refrigerant flow. 4. Liquid line pressure drop (or gain) due to vertical rise of the liquid line. 5. Pressure rating of brazed Type L Copper tubing with high pressure refrigerants. 4 JOHNSON CONTROLS 17

18 SECTION 4 - INSTALLATION To ensure a solid column of liquid refrigerant to the expansion valve, the total liquid line pressure drop should never exceed 40 PSI (276 kpa). Refrigerant vapor in the liquid line will measurably reduce valve capacity and poor system performance can be expected. To allow adequate oil return to the compressor, discharge risers should be sized for a minimum of 1000 FPM (5.08 m/s) while the system is operating at minimum capacity to ensure oil return up the suction riser. Chiller Below Condenser On a system where the chiller is located below the condenser, the discharge line must be sized for both pressure drop and oil return. In some cases a double discharge riser must be installed to ensure reliable oil return at reduced loads. Condenser Below Chiller When the condenser is located below the chiller, the liquid line must be designed for both friction loss and static head loss due to the vertical rise. The value of static head loss of 5 PSI/ft. (3.4 kpa/30 cm) must be added to the friction loss pressure drop in addition to all pressure drops due to driers, valves, etc. Oil Traps All horizontal discharge lines should be pitched at least 1/4" per foot (2 cm/m) in the direction of the refrigerant flow to aid in the return of oil to the chiller. All discharge lines with a vertical rise exceeding 3 feet (.91 meters) should have a "P" trap at the bottom and top of the riser. Discharge lines with a vertical rise exceeding 25 feet (7.6 meters) should be trapped every 15 feet (4.6 meters). Refrigerant Piping Reference R-410A Copper Line Sizing When selecting pipe diameter and material for remote condenser piping R-410A systems, it is recommended that ASTM B280 material is used. For more details, refer to the 2014 ASHRAE Refrigeration Handbook, Chapter 1, and note that brazing reduces the strength of the heated pipe material to that of annealed material. Suggested Field Piping Arrangements This section shows four field piping arrangements for remote air-cooled condensers in field erected systems using receivers. Receivers are shown in Figures 3 through 6 for convenience. Many applications do not require receivers when the volume of the refrigerant charge does not exceed 80% of the condenser coil internal volume and can be stored entirely in the condenser coil. Loop Trap Discharge Line Condenser Compressor Liquid Line Receiver FORM NM1 Figure 3 - Condenser, Compressor And Receiver On Same Level LD16218 Figure 3 on page 18 covers a common application where the air- cooled condenser is located on the same elevation as the compressor and receiver. The discharge line in this case is not too critical. The main problem usually associated with this arrangement is insufficient vertical height to allow free draining of the liquid refrigerant from the condenser coil to the receiver. To prevent gas binding in the receiver and liquid buildup in the condenser coil, locate the receiver as far below the condenser outlet as possible. Liquid lines must be free of any loops or traps and horizontal runs must be pitched toward the receiver. YCRL Line Sizing Notes If the VDC is used in conjunction with a YCRL chiller with a design pressure of 650 psig, a mechanical high pressure cutout to shut the unit off at 585 psig, and (the unit) is rated at 650 psig, the maximum discharge pipe diameter that can be used is 1-5/8". 18 JOHNSON CONTROLS

19 SECTION 4 - INSTALLATION Loop Loop Discharge Line A Condenser Condenser Condenser Discharge Line B Trap Liquid Line Discharge Line Trap Liquid Line Compressor Receiver Figure 4 - Capacity Controlled Systems LD16219 Figure 4 on page 19 shows the recommended configuration for applications of capacity controlled systems. Discharge line A is sized for the maximum load conditions. Discharge line B is sized for the minimum loading conditions at sufficient velocity to carry the oil to the condenser at the reduced capacity. Discharge Line Condenser Compressor Receiver LD16221 Figure 6 - Two Or More Condensers Connected To One Compressor Figure 6 on page 19 illustrates another common application where two or more separate air-cooled condensers are interconnected to a single compressor. In this case, each condenser must have both equal capacity and equal pressure drop. The piping must also be arranged to ensure equal lengths to and from each condenser. If unlike piping and/or unequal condensers are used, the unequal pressure drop will cause liquid to build up in one of the condensers, reducing its effective capacity. 4 Trap Compressor Receiver Liquid Line Figure 5 - Condenser Higher Than Compressor And Receiver LD16220 Recommended Refrigeration Line Sizes The recommended refrigerant line sizes (discharge line-compressor to condenser and liquid line-condenser to receiver) can be determined from the DX Piping Guide, Form ES2, while exercising care with regards to internal working pressure of copper piping with brazed joints for use with high-pressure refrigerants. Figure 5 on page 19 illustrates a typical piping arrangement where the remote air-cooled condenser is located on a higher elevation than the compressor or receiver. In this arrangement, the design of the discharge line is very critical and should be modified to the arrangement in diagram Figure 4, unless a very constant and steady load is maintained. JOHNSON CONTROLS 19

20 SECTION 4 - INSTALLATION FORM NM LEGEND 1. YORK YCRL Chiller 2. YORK Solution Air Handler 3. Subcooler Liquid Plumbing 4. Chilled Liquid Pump 5. Discharge Line Muffler 6. Fused Disconnect Switch 7. Starter 8. Purge Valve 4 2 LD14090A Figure 7 - Typical Piping Arrangement - VDC 20 JOHNSON CONTROLS

21 SECTION 4 - INSTALLATION 4 Notes: LD Two Standard YORK single-wide condensers with single-circuit coils, one condenser used with each compressor. 2. One Standard YORK double-wide condenser with one dual-circuit coil, one circuit used with each compressor. Available with individual fan-bank fan cycling. 3. Two Standard YORK double-wide condensers with dual-circuit coils, one condenser used with each compressor, shown with optional manifolds (shipped loose). Figure 8 - Refrigerant Connections - VDC Receiver Location (if Required for Refrigerant Storage) It is preferable that the receiver be located in an ambient temperature above 65 F. When located in a lower ambient temperature, provision should be made to heat and insulate the receiver, especially if long off-cycles are encountered. Table 1 on page 21 shows suggested receiver and heater sizes. The receiver should be insulated with 1-inch thick Armaflex insulation or equivalent. Before applying the receiver insulation, the heater cable should be wrapped around the receiver throughout the length for even heat distribution. The heater must be field connected to the proper voltage and controlled so that it is energized on system shutdown. Table 1 - Receiver And Heater Data Receiver Heater Watts Receiver Heater Watts 8" x 4' " x 8' 420 8" x 6' " x 10' 420 8" x 8' " x 6' " x 6' " x 8' " x 8' " x 10' " x 10' " x 8' " x 6' " x 10' " x 8' " x 12' " x 10' " x 8' " x 6' " x 10' 700 JOHNSON CONTROLS 21

22 SECTION 4 - INSTALLATION Refrigerant Charge The chiller is charged and shipped with a dry nitrogen holding charge. The chiller and the remote piping condenser must be evacuated and the operating charge for the chiller, remote condenser and refrigerant piping must be weighed in after all refrigerant piping is installed, leak checked, and evacuated. A minimum of 70% of the calculated complete system charge must be installed before attempting to operate a system. Final adjustment of refrigerant charge should be verified by subcooling values. FORM NM1 Use of refrigerant other than that stamped on the nameplates may cause damage to the refrigeration coils. Coil must not be subject to higher pressure than design pressure stamped on the nameplate. The total system refrigerant charge is the sum of the operating charges of the evaporator, condenser and refrigerant piping. The Refrigerant charge for discharge lines and liquid lines may be found in Tables 15 and 16 respectively on pages 28 and 29 of the DX Piping Guide, Form ES2. The pump down capacity of the condenser should be equal to or greater than the total refrigerant charge required. Pumpdown capacity is normally the sum of the evaporator, condenser and refrigerant piping charges multiplied by LD16223 Notes: 1. Standard YORK fluid cooler with one single-circuit coil. 2. Standard YORK fluid cooler with two single-circuit coils, shown with optional manifolds (shipped loose), not available from factory on units with 4 1/8 in. OD connections. Figure 9 - Liquid Connections - VDCF 22 JOHNSON CONTROLS

23 SECTION 5 - TECHNICAL DATA Dimensions - Condenser L INLET 2 REQUIRED SHIPS ON SIDE LEGS SHIP LOOSE OUTLET 2 REQUIRED DOUBLE WIDE REMOVEABLE SHIPPING SKID HEADER END INLET 1 REQUIRED L OUTLET 1 REQUIRED Electrical Enclosure SINGLE WIDE 5 AIRFLOW AIRFLOW W 9.00 W 9.00 DOUBLE WIDE SINGLE WIDE H x 4 Mounting Pad A G Holes for 3 4" Bolts A 9.50 C E B D TYP LD17329 NOTE: Johnson Controls recommends the minimum distance between the condenser and walls be 8 ft. The minimum distance between adjacent condenser should be 4 ft for single-wide units and 8 ft for double-wide units. This will prevent condenser air recirculation and faulty operation. Table 2 - Unit Dimensions - Condensers Model Dimensions number L W H (1) A B C D E G VDC VDC VDC VDC VDC VDC VDC VDC VDC VDC VDC (1) Add 5.0 to the height on VDC-156, -166, -256, and Note: Dimensions are in inches and for reference only. JOHNSON CONTROLS 23

24 SECTION 5 - TECHNICAL DATA FORM NM1 Dimensions - Fluid Cooler L INLET 2 REQUIRED SHIPS ON SIDE LEGS SHIP LOOSE OUTLET 2 REQUIRED DOUBLE WIDE REMOVEABLE SHIPPING SKID HEADER END INLET 1 REQUIRED L OUTLET 1 REQUIRED SINGLE WIDE Electrical Enclosure AIRFLOW AIRFLOW W 9.00 W 9.00 DOUBLE WIDE SINGLE WIDE H x 4 Mounting Pad A G Holes for 3 4" Bolts A 9.50 C E B D TYP LD17330 NOTE: Johnson Controls recommends the minimum distance between the fluid cooler and walls be 8 ft. The minimum distance between adjacent fluid coolers should be 4 ft for single-wide units and 8 ft for double-wide units. This will prevent air recirculation and faulty operation. Table 3 - Unit Dimensions - Fluid Coolers Model Number Dimensions L W H (1) A B C D E G VDCF VDCF VDCF VDCF VDCF VDCF VDCF VDCF VDCF VDCF VDCF (1) Add 5.0 to the height on fluid cooling units with 6 and 8 row coils Note: Dimensions are in inches and for reference only and expressed in inches. 24 JOHNSON CONTROLS

25 SECTION 5 - TECHNICAL DATA VDC Charge Calculation The following is an example of how to determine the operating charge and pumpdown storage capacity for the VDC condensers. Table 4 - VDC Charge Calculation EXAMPLE BASIS Model VDC-244D60 Refrigerant circuits one Internal condenser tube volume shown below 4.9 cu ft OPERATING CHARGE Total operating charge = coil vol (cu ft) x rfr density (lb/cu ft) x 0.24 Total operating charge (R-22) = 4.9 x 70.3 x 0.24 = 83 Ibs Total operating charge (R-134a) = 4.9 x 71.4 x 0.24 = 84 Ibs Total operating charge (R-404A) = 4.9 x 60.0 x 0.24 = 71 Ibs Total operating charge (R-407C) = 4.9 x 66.5 x 0.24 = 78 Ibs Total operating charge (R-410A) = 4.9 x 60.7 x 0.24 = 71 Ibs Total operating charge (R-507 A) = 4.9 x 60.1 x 0.24 = 71 Ibs PUMPDOWN STORAGE CAPACITY Total pumpdown capacity = coil vol (cu ft) x rfr density (Ib/cu ft) x 0.8 Total pumpdown capacity (R-22) = 4.9 x 70.3 x 0.8 = 276 Ibs Total pumpdown capacity (R-134a) = 4.9 x 71.4 x 0.8 = 280 Ibs Total pumpdown capacity (R-404A) = 4.9 x 60.0 x 0.8 = 235 Ibs Total pumpdown capacity (R-407C) = 4.9 x 66.5 x 0.8 = 261 Ibs Total pumpdown capacity (R-410A) = 4.9 x 60.7 x 0.8 = 238 Ibs Total pumpdown capacity (R-507A) = 4.9 x 60.1 x 0.8 = 236 Ibs 5 Note: Refrigerant temperature for this example is 105 F. Use the density of the refrigerant at the most appropriate temperature for the application. JOHNSON CONTROLS 25

26 SECTION 5 - TECHNICAL DATA FORM NM1 Physical Data Table 5 - VDC Condenser 2.0 HP Rating And Physical Data Model COIL (1) INTernal VOLume (CU FT) APPROXimate UNIT WEIGHT (LBS) VDC-113D VDC-114D VDC-116D VDC-123D VDC-124D VDC-126D VDC-133D ,189 VDC-134D ,246 VDC-136D ,363 VDC-143D ,546 VDC-144D ,621 VDC-146D ,777 VDC-153C ,027 VDC-154C ,167 VDC-156C ,529 VDC-163C ,414 VDC-164C ,582 VDC-166C ,015 VDC-223D ,405 VDC-224D ,481 VDC-226D ,636 VDC-233D ,034 VDC-234D ,147 VDC-236D ,380 VDC-243D ,653 VDC-244D ,804 VDC-246D ,115 VDC-253C ,521 VDC-254C ,801 VDC-256C ,500 VDC-263C ,202 VDC-264C ,537 VDC-266C ,374 Quantity Fans Nominal HP 50 Hz Power Input (kw) 60 Hz Power Input (kw) NOTE: 1. Coil internal volume includes header internal volume. 26 JOHNSON CONTROLS

27 SECTION 5 - TECHNICAL DATA TABLE 5 - VDC Condenser 2.0 HP Rating And Physical Data (Cont'd) MOTOR CURRENT DRAW, 3 PH, 60 Hz AT STANDARD AIR (AMPS) (2) MODEL 200/3/60 230/3/60 460/3/60 575/3/60 FLA MCA MOP FLA MCA MOP FLA MCA MOP FLA MCA MOP VDC-113D60 VDC-114D60 VDC-116D60 VDC-123D VDC-124D60 VDC-126D60 VDC-133D VDC-134D60 VDC-136D60 VDC-143D VDC-144D60 VDC-146D60 VDC-153C VDC-154C60 VDC-156C60 VDC-163C VDC-164C60 VDC-166C60 VDC-223D VDC-224D60 VDC-226D60 VDC-233D VDC-234D60 VDC-236D60 VDC-243D VDC-244D60 VDC-246D60 VDC-253C VDC-254C60 VDC-256C60 VDC-263C VDC-264C60 VDC-266C NOTE: 2. For Temperature-Controlled Fan Cycling and Pressure-Controlled Fan Cycling. JOHNSON CONTROLS 27

28 SECTION 5 - TECHNICAL DATA FORM NM1 TABLE 5 - VDC Condenser 2.0 HP Rating And Physical Data (Cont'd) MODEL VDC-113D60 VDC-114D60 VDC-116D60 VDC-123D60 VDC-124D60 VDC-126D60 VDC-133D60 VDC-134D60 VDC-136D60 VDC-143D60 VDC-144D60 VDC-146D60 VDC-153C60 VDC-154C60 VDC-156C60 VDC-163C60 VDC-164C60 VDC-166C60 VDC-223D60 VDC-224D60 VDC-226D60 VDC-233D60 VDC-234D60 VDC-236D60 VDC-243D60 VDC-244D60 VDC-246D60 VDC-253C60 VDC-254C60 VDC-256C60 VDC-263C60 VDC-264C60 VDC-266C60 MOTOR CURRENT DRAW, 3 PH, 50 Hz AT STANDARD AIR (AMPS) (2) 380/3/50 400/3/50 415/3/50 FLA MCA MOP FLA MCA MOP FLA MCA MOP NOTE: 2. For Temperature-Controlled Fan Cycling and Pressure-Controlled Fan Cycling. 28 JOHNSON CONTROLS

29 SECTION 5 - TECHNICAL DATA TABLE 5 - VDC Condenser 2.0 HP Rating And Physical Data (Cont'd) MOTOR CURRENT DRAW, 3 PH, 60 Hz AT STANDARD AIR (AMPS) (3) MODEL 200/3/60 230/3/60 460/3/60 575/3/60 FLA MCA MOP FLA MCA MOP FLA MCA MOP FLA MCA MOP VDC-113D60 VDC-114D60 VDC-116D60 VDC-123D VDC-124D60 VDC-126D60 VDC-133D VDC-134D60 VDC-136D60 VDC-143D VDC-144D60 VDC-146D60 VDC-153C VDC-154C60 VDC-156C60 VDC-163C VDC-164C60 VDC-166C60 VDC-223D VDC-224D60 VDC-226D60 VDC-233D VDC-234D60 VDC-236D60 VDC-243D VDC-244D60 VDC-246D60 VDC-253C VDC-254C60 VDC-256C60 VDC-263C VDC-264C60 VDC-266C NOTE: 3. For VSD-ready for Variable Speed Fan Control and Standard Control without Fan Cycling. JOHNSON CONTROLS 29

30 SECTION 5 - TECHNICAL DATA FORM NM1 TABLE 5 - VDC Condenser 2.0 HP Rating And Physical Data (Cont'd) MODEL VDC-113D60 VDC-114D60 VDC-116D60 VDC-123D60 VDC-124D60 VDC-126D60 VDC-133D60 VDC-134D60 VDC-136D60 VDC-143D60 VDC-144D60 VDC-146D60 VDC-153C60 VDC-154C60 VDC-156C60 VDC-163C60 VDC-164C60 VDC-166C60 VDC-223D60 VDC-224D60 VDC-226D60 VDC-233D60 VDC-234D60 VDC-236D60 VDC-243D60 VDC-244D60 VDC-246D60 VDC-253C60 VDC-254C60 VDC-256C60 VDC-263C60 VDC-264C60 VDC-266C60 MOTOR CURRENT DRAW, 3 PH, 50 Hz AT STANDARD AIR (AMPS) (3) 380/3/50 400/3/50 415/3/50 FLA MCA MOP FLA MCA MOP FLA MCA MOP NOTE: 3. For VSD-ready for Variable Speed Fan Control and Standard Control without Fan Cycling. 30 JOHNSON CONTROLS

31 SECTION 5 - TECHNICAL DATA Table 6 - VDC Condenser 1.0 HP Rating And Physical Data Model COIL (1) INTernal VOLume (CU FT) APPROXimate UNIT WEIGHT (LBS) VDC-113D VDC-114D VDC-116D VDC-123D VDC-124D VDC-126D VDC-133D ,189 VDC-134D ,246 VDC-136D ,363 VDC-143D ,546 VDC-144D ,621 VDC-146D ,777 VDC-153C ,027 VDC-154C ,167 VDC-156C ,529 VDC-163C ,414 VDC-164C ,582 VDC-166C ,015 VDC-223D ,405 VDC-224D ,481 VDC-226D ,636 VDC-233D ,034 VDC-234D ,147 VDC-236D ,380 VDC-243D ,653 VDC-244D ,804 VDC-246D ,115 VDC-253C ,521 VDC-254C ,801 VDC-256C ,500 VDC-263C ,202 VDC-264C ,537 VDC-266C ,374 NOTE: 1. Coil internal volume includes header internal volume. Quantity Fans Nom HP 60 HZ Power Input (kw) 50 HZ Power Input (kw) JOHNSON CONTROLS 31

32 SECTION 5 - TECHNICAL DATA FORM NM1 TABLE 6 - VDC Condenser 1.0 Hp Rating And Physical Data (Cont'd) MODEL VDC-113D10 VDC-114D10 VDC-116D10 VDC-123D10 VDC-124D10 VDC-126D10 VDC-133D10 VDC-134D10 VDC-136D10 VDC-143D10 VDC-144D10 VDC-146D10 VDC-153C10 VDC-154C10 VDC-156C10 VDC-163C10 VDC-164C10 VDC-166C10 VDC-223D10 VDC-224D10 VDC-226D10 VDC-233D10 VDC-234D10 VDC-236D10 VDC-243D10 VDC-244D10 VDC-246D10 VDC-253C10 VDC-254C10 VDC-256C10 VDC-263C10 VDC-264C10 VDC-266C10 MOTOR CURRENT DRAW, 3 PH, 60 HZ AT STANDARD AIR (AMPS) (2) 200/3/60 230/3/60 460/3/60 575/3/60 FLA MCA MOP FLA MCA MOP FLA MCA MOP FLA MCA MOP NOTE: 2. For Temperature-Controlled Fan Cycling and Pressure-Controlled Fan Cycling. 32 JOHNSON CONTROLS

33 SECTION 5 - TECHNICAL DATA TABLE 6 - VDC Condenser 1.0 HP Rating And Physical Data (Cont'd) MODEL VDC-113D60 VDC-114D60 VDC-116D60 VDC-123D60 VDC-124D60 VDC-126D60 VDC-133D60 VDC-134D60 VDC-136D60 VDC-143D60 VDC-144D60 VDC-146D60 VDC-153C60 VDC-154C60 VDC-156C60 VDC-163C60 VDC-164C60 VDC-166C60 VDC-223D60 VDC-224D60 VDC-226D60 VDC-233D60 VDC-234D60 VDC-236D60 VDC-243D60 VDC-244D60 VDC-246D60 VDC-253C60 VDC-254C60 VDC-256C60 VDC-263C60 VDC-264C60 VDC-266C60 MOTOR CURRENT DRAW, 3 PH, 50 Hz AT STANDARD AIR (AMPS) (2) 380/3/50 400/3/50 415/3/50 FLA MCA MOP FLA MCA MOP FLA MCA MOP NOTE: 2. For Temperature-Controlled Fan Cycling and Pressure-Controlled Fan Cycling. JOHNSON CONTROLS 33

34 SECTION 5 - TECHNICAL DATA FORM NM1 TABLE 6 - VDC Condenser 1.0 Hp Rating And Physical Data (Cont'd) MODEL VDC-113D10 VDC-114D10 VDC-116D10 VDC-123D10 VDC-124D10 VDC-126D10 VDC-133D10 VDC-134D10 VDC-136D10 VDC-143D10 VDC-144D10 VDC-146D10 VDC-153C10 VDC-154C10 VDC-156C10 VDC-163C10 VDC-164C10 VDC-166C10 VDC-223D10 VDC-224D10 VDC-226D10 VDC-233D10 VDC-234D10 VDC-236D10 VDC-243D10 VDC-244D10 VDC-246D10 VDC-253C10 VDC-254C10 VDC-256C10 VDC-263C10 VDC-264C10 VDC-266C10 MOTOR CURRENT DRAW, 3 PH, 60 HZ AT STANDARD AIR (AMPS) (3) 200/3/60 230/3/60 460/3/60 575/3/60 FLA MCA MOP FLA MCA MOP FLA MCA MOP FLA MCA MOP NOTE: 3. For VSD-ready for Variable Speed Fan Control and Standard Control without Fan Cycling. 34 JOHNSON CONTROLS

35 SECTION 5 - TECHNICAL DATA TABLE 6 - VDC Condenser 1.0 HP Rating And Physical Data (Cont'd) MODEL VDC-113D60 VDC-114D60 VDC-116D60 VDC-123D60 VDC-124D60 VDC-126D60 VDC-133D60 VDC-134D60 VDC-136D60 VDC-143D60 VDC-144D60 VDC-146D60 VDC-153C60 VDC-154C60 VDC-156C60 VDC-163C60 VDC-164C60 VDC-166C60 VDC-223D60 VDC-224D60 VDC-226D60 VDC-233D60 VDC-234D60 VDC-236D60 VDC-243D60 VDC-244D60 VDC-246D60 VDC-253C60 VDC-254C60 VDC-256C60 VDC-263C60 VDC-264C60 VDC-266C60 MOTOR CURRENT DRAW, 3 PH, 50 Hz AT STANDARD AIR (AMPS) (2) 380/3/50 400/3/50 415/3/50 FLA MCA MOP FLA MCA MOP FLA MCA MOP NOTE: 3. For VSD-ready for Variable Speed Fan Control and Standard Control without Fan Cycling. JOHNSON CONTROLS 35

36 SECTION 5 - TECHNICAL DATA FORM NM1 Table 7 - VDCF Fluid Cooler 2.0 HP Rating And Physical Data Model Coil (1) Internal Volume (cu ft) APPROXimate Unit Weight (lbs) VDCF113B60XXB VDCF113B60XXC VDCF114B60XXB VDCF116B60XXB VDCF116B60XXC VDCF118B60XXB VDCF124B60XXB VDCF126B60XXB ,168 VDCF126B60XXC ,160 VDCF128B60XXB ,304 VDCF134B60XXB ,415 VDCF136B60XXB ,679 VDCF136B60XXC ,671 VDCF138B60XXB ,881 VDCF144B60XXB ,846 VDCF146B60XXB ,189 VDCF146B60XXC ,181 VDCF148B60XXB ,457 VDCF154B60XXB ,275 VDCF156B60XXB ,699 VDCF156B60XXC ,691 VDCF158B60XXB ,033 VDCF164B60XXB ,704 VDCF166B60XXB ,210 VDCF166B60XXC ,202 VDCF168B60XXB ,609 VDCF224B60XXB ,736 VDCF226B60XXB ,074 VDCF226B60XXC ,071 VDCF228B60XXB ,346 VDCF234B60XXB ,499 VDCF236B60XXB ,998 VDCF236B60XXC ,995 VDCF238B60XXB ,402 VDCF244B60XXB ,267 VDCF246B60XXB ,919 VDCF246B60XXC ,916 VDCF248B60XXB ,455 VDCF254B60XXB ,030 VDCF256B60XXB ,840 VDCF256B60XXC ,837 VDCF258B60XXB ,508 VDCF264B60XXB ,795 VDCF266B60XXB ,764 VDCF266B60XXC ,761 VDCF268B60XXB ,562 NOTE: 1. Coil internal volume includes header internal volume. Quantity Fans Nom HP 60 HZ Power Input (kw) 50 HZ Power Input (kw) JOHNSON CONTROLS

37 SECTION 5 - TECHNICAL DATA TABLE 7 - VDCF Fluid Cooler 2.0 HP Rating And Physical Data (Cont'd) MODEL VDCF113B60XXB VDCF113B60XXC VDCF114B60XXB VDCF116B60XXB VDCF116B60XXC VDCF118B60XXB VDCF124B60XXB VDCF126B60XXB VDCF126B60XXC VDCF128B60XXB VDCF134B60XXB VDCF136B60XXB VDCF136B60XXC VDCF138B60XXB VDCF144B60XXB VDCF146B60XXB VDCF146B60XXC VDCF148B60XXB VDCF154B60XXB VDCF156B60XXB VDCF156B60XXC VDCF158B60XXB VDCF164B60XXB VDCF166B60XXB VDCF166B60XXC VDCF168B60XXB VDCF224B60XXB VDCF226B60XXB VDCF226B60XXC VDCF228B60XXB VDCF234B60XXB VDCF236B60XXB VDCF236B60XXC VDCF238B60XXB VDCF244B60XXB VDCF246B60XXB VDCF246B60XXC VDCF248B60XXB VDCF254B60XXB VDCF256B60XXB VDCF256B60XXC VDCF258B60XXB VDCF264B60XXB VDCF266B60XXB VDCF266B60XXC VDCF268B60XXB MOTOR CURRENT DRAW, 3 PH, 60 HZ AT STANDARD AIR (AMPS) (2) 200 Volts 230 Volts 460 Volts 575 Volts FLA MCA MOP FLA MCA MOP FLA MCA MOP FLA MCA MOP NOTE: 2. For Temperature-Controlled Fan Cycling and Pressure-Controlled Fan Cycling. JOHNSON CONTROLS 37

38 SECTION 5 - TECHNICAL DATA FORM NM1 TABLE 7 - VDC Condenser 2.0 HP Rating And Physical Data (Cont'd) MOTOR CURRENT DRAW, 3 PH, 50 Hz AT STANDARD AIR (AMPS) (2) MODEL VDCF113B60XXB VDCF113B60XXC VDCF114B60XXB VDCF116B60XXB VDCF116B60XXC VDCF118B60XXB VDCF124B60XXB VDCF126B60XXB VDCF126B60XXC VDCF128B60XXB VDCF134B60XXB VDCF136B60XXB VDCF136B60XXC VDCF138B60XXB VDCF144B60XXB VDCF146B60XXB VDCF146B60XXC VDCF148B60XXB VDCF154B60XXB VDCF156B60XXB VDCF156B60XXC VDCF158B60XXB VDCF164B60XXB VDCF166B60XXB VDCF166B60XXC VDCF168B60XXB VDCF224B60XXB VDCF226B60XXB VDCF226B60XXC VDCF228B60XXB VDCF234B60XXB VDCF236B60XXB VDCF236B60XXC VDCF238B60XXB VDCF244B60XXB VDCF246B60XXB VDCF246B60XXC VDCF248B60XXB VDCF254B60XXB VDCF256B60XXB VDCF256B60XXC VDCF258B60XXB VDCF264B60XXB VDCF266B60XXB VDCF266B60XXC VDCF268B60XXB 380 Volts 400 Volts 415 Volts FLA MCA MOP FLA MCA MOP FLA MCA MOP NOTE: 2. For Temperature-Controlled Fan Cycling and Pressure-Controlled Fan Cycling. 38 JOHNSON CONTROLS

39 SECTION 5 - TECHNICAL DATA TABLE 7 - VDCF Fluid Cooler 2.0 HP Rating And Physical Data (Cont'd) MOTOR CURRENT DRAW, 3 PH, 60 HZ AT STANDARD AIR (AMPS) (3) MODEL VDCF113B60XXB VDCF113B60XXC VDCF114B60XXB VDCF116B60XXB VDCF116B60XXC VDCF118B60XXB VDCF124B60XXB VDCF126B60XXB VDCF126B60XXC VDCF128B60XXB VDCF134B60XXB VDCF136B60XXB VDCF136B60XXC VDCF138B60XXB VDCF144B60XXB VDCF146B60XXB VDCF146B60XXC VDCF148B60XXB VDCF154B60XXB VDCF156B60XXB VDCF156B60XXC VDCF158B60XXB VDCF164B60XXB VDCF166B60XXB VDCF166B60XXC VDCF168B60XXB VDCF224B60XXB VDCF226B60XXB VDCF226B60XXC VDCF228B60XXB VDCF234B60XXB VDCF236B60XXB VDCF236B60XXC VDCF238B60XXB VDCF244B60XXB VDCF246B60XXB VDCF246B60XXC VDCF248B60XXB VDCF254B60XXB VDCF256B60XXB VDCF256B60XXC VDCF258B60XXB VDCF264B60XXB VDCF266B60XXB VDCF266B60XXC VDCF268B60XXB 200/3/60 230/3/60 460/3/60 575/3/60 FLA MCA MOP FLA MCA MOP FLA MCA MOP FLA MCA MOP NOTE: 3. For VSD-ready for Variable Speed Fan Control and Standard Control without Fan Cycling. JOHNSON CONTROLS 39

40 SECTION 5 - TECHNICAL DATA FORM NM1 TABLE 7 - VDC Condenser 2.0 HP Rating And Physical Data (Cont'd) MOTOR CURRENT DRAW, 3 PH, 50 Hz AT STANDARD AIR (AMPS) (2) MODEL VDCF113B60XXB VDCF113B60XXC VDCF114B60XXB VDCF116B60XXB VDCF116B60XXC VDCF118B60XXB VDCF124B60XXB VDCF126B60XXB VDCF126B60XXC VDCF128B60XXB VDCF134B60XXB VDCF136B60XXB VDCF136B60XXC VDCF138B60XXB VDCF144B60XXB VDCF146B60XXB VDCF146B60XXC VDCF148B60XXB VDCF154B60XXB VDCF156B60XXB VDCF156B60XXC VDCF158B60XXB VDCF164B60XXB VDCF166B60XXB VDCF166B60XXC VDCF168B60XXB VDCF224B60XXB VDCF226B60XXB VDCF226B60XXC VDCF228B60XXB VDCF234B60XXB VDCF236B60XXB VDCF236B60XXC VDCF238B60XXB VDCF244B60XXB VDCF246B60XXB VDCF246B60XXC VDCF248B60XXB VDCF254B60XXB VDCF256B60XXB VDCF256B60XXC VDCF258B60XXB VDCF264B60XXB VDCF266B60XXB VDCF266B60XXC VDCF268B60XXB 380 Volts 400 Volts 415 Volts FLA MCA MOP FLA MCA MOP FLA MCA MOP NOTE: 3. For VSD-ready for Variable Speed Fan Control and Standard Control without Fan Cycling. 40 JOHNSON CONTROLS

41 SECTION 5 - TECHNICAL DATA Table 8 - VDCF Fluid Cooler 1.0 HP Rating And Physical Data MODEL COIL (1) INTernal VOLume (CU FT) APPROXIMATE UNIT WEIGHT (LBS) VDCF113B10XXB VDCF113B10XXC VDCF114B10XXB VDCF116B10XXB VDCF116B10XXC VDCF118B10XXB VDCF124B10XXB VDCF126B10XXB ,168 VDCF126B10XXC ,160 VDCF128B10XXB ,304 VDCF134B10XXB ,415 VDCF136B10XXB ,679 VDCF136B10XXC ,671 VDCF138B10XXB ,881 VDCF144B10XXB ,846 VDCF146B10XXB ,189 VDCF146B10XXC ,181 VDCF148B10XXB ,457 VDCF154B10XXB ,275 VDCF156B10XXB ,699 VDCF156B10XXC ,691 VDCF158B10XXB ,033 VDCF164B10XXB ,704 VDCF166B10XXB ,210 VDCF166B10XXC ,202 VDCF168B10XXB ,609 VDCF224B10XXB ,736 VDCF226B10XXB ,074 VDCF226B10XXC ,071 VDCF228B10XXB ,346 VDCF234B10XXB ,499 VDCF236B10XXB ,998 VDCF236B10XXC ,995 VDCF238B10XXB ,402 VDCF244B10XXB ,267 VDCF246B10XXB ,919 VDCF246B10XXC ,916 VDCF248B10XXB ,455 VDCF254B10XXB ,030 VDCF256B10XXB ,840 VDCF256B10XXC ,837 VDCF258B10XXB ,508 VDCF264B10XXB ,795 VDCF266B10XXB ,764 VDCF266B10XXC ,761 VDCF268B10XXB ,562 QUANTITY FANS NOM HP 60 HZ POWER INPUT (KW) 50 HZ Power Input (Kw) NOTES: 1. Coil internal volume includes header internal volume. JOHNSON CONTROLS 41

42 SECTION 5 - TECHNICAL DATA FORM NM1 TABLE 8 - VDCF Fluid Cooler 1.0 HP Rating And Physical Data MOTOR CURRENT, 30 Ph, 60 HZ DRAW AT STANDARD AIR (AMPS) (2) MODEL VDCF113B10XXB VDCF113B10XXC VDCF114B10XXB VDCF116B10XXB VDCF116B10XXC VDCF118B10XXB VDCF124B10XXB VDCF126B10XXB VDCF126B10XXC VDCF128B10XXB VDCF134B10XXB VDCF136B10XXB VDCF136B10XXC VDCF138B10XXB VDCF144B10XXB VDCF146B10XXB VDCF146B10XXC VDCF148B10XXB VDCF154B10XXB VDCF156B10XXB VDCF156B10XXC VDCF158B10XXB VDCF164B10XXB VDCF166B10XXB VDCF166B10XXC VDCF168B10XXB VDCF224B10XXB VDCF226B10XXB VDCF226B10XXC VDCF228B10XXB VDCF234B10XXB VDCF236B10XXB VDCF236B10XXC VDCF238B10XXB VDCF244B10XXB VDCF246B10XXB VDCF246B10XXC VDCF248B10XXB VDCF254B10XXB VDCF256B10XXB VDCF256B10XXC VDCF258B10XXB VDCF264B10XXB VDCF266B10XXB VDCF266B10XXC VDCF268B10XXB 200 Volts 230 Volts 460 Volts 575 Volts FLA MCA MOP FLA MCA MOP FLA MCA MOP FLA MCA MOP NOTES: 2. For Temperature-Controlled Fan Cycling and Pressure-Controlled Fan Cycling. 42 JOHNSON CONTROLS

43 SECTION 5 - TECHNICAL DATA TABLE 8 - VDC Condenser 1.0 HP Rating And Physical Data (Cont'd) MOTOR CURRENT DRAW, 3 PH, 50 Hz AT STANDARD AIR (AMPS) (2) MODEL VDCF113B10XXB VDCF113B10XXC VDCF114B10XXB VDCF116B10XXB VDCF116B10XXC VDCF118B10XXB VDCF124B10XXB VDCF126B10XXB VDCF126B10XXC VDCF128B10XXB VDCF134B10XXB VDCF136B10XXB VDCF136B10XXC VDCF138B10XXB VDCF144B10XXB VDCF146B10XXB VDCF146B10XXC VDCF148B10XXB VDCF154B10XXB VDCF156B10XXB VDCF156B10XXC VDCF158B10XXB VDCF164B10XXB VDCF166B10XXB VDCF166B10XXC VDCF168B10XXB VDCF224B10XXB VDCF226B10XXB VDCF226B10XXC VDCF228B10XXB VDCF234B10XXB VDCF236B10XXB VDCF236B10XXC VDCF238B10XXB VDCF244B10XXB VDCF246B10XXB VDCF246B10XXC VDCF248B10XXB VDCF254B10XXB VDCF256B10XXB VDCF256B10XXC VDCF258B10XXB VDCF264B10XXB VDCF266B10XXB VDCF266B10XXC VDCF268B10XXB 380 Volts 400 Volts 415 Volts FLA MCA MOP FLA MCA MOP FLA MCA MOP NOTES: 2. For Temperature-Controlled Fan Cycling and Pressure-Controlled Fan Cycling. JOHNSON CONTROLS 43

44 SECTION 5 - TECHNICAL DATA FORM NM1 TABLE 8 - VDCF Fluid Cooler 1.0 HP Rating And Physical Data MOTOR CURRENT DRAW, 30 PH, 50 HZ AT STANDARD AIR (AMPS) (3) MODEL VDCF113B10XXB VDCF113B10XXC VDCF114B10XXB VDCF116B10XXB VDCF116B10XXC VDCF118B10XXB VDCF124B10XXB VDCF126B10XXB VDCF126B10XXC VDCF128B10XXB VDCF134B10XXB VDCF136B10XXB VDCF136B10XXC VDCF138B10XXB VDCF144B10XXB VDCF146B10XXB VDCF146B10XXC VDCF148B10XXB VDCF154B10XXB VDCF156B10XXB VDCF156B10XXC VDCF158B10XXB VDCF164B10XXB VDCF166B10XXB VDCF166B10XXC VDCF168B10XXB VDCF224B10XXB VDCF226B10XXB VDCF226B10XXC VDCF228B10XXB VDCF234B10XXB VDCF236B10XXB VDCF236B10XXC VDCF238B10XXB VDCF244B10XXB VDCF246B10XXB VDCF246B10XXC VDCF248B10XXB VDCF254B10XXB VDCF256B10XXB VDCF256B10XXC VDCF258B10XXB VDCF264B10XXB VDCF266B10XXB VDCF266B10XXC VDCF268B10XXB 200 VOLTS 230 VOLTS 460 VOLTS 575 VOLTS FLA MCA MOP FLA MCA MOP FLA MCA MOP FLA MCA MOP NOTES: 3. For VSD-ready for Variable Speed Fan Control and Standard Control without Fan Cycling. 44 JOHNSON CONTROLS

45 SECTION 5 - TECHNICAL DATA TABLE 8 - VDC Condenser 1.0 HP Rating And Physical Data (Cont'd) MOTOR CURRENT DRAW, 3 PH, 50 Hz AT STANDARD AIR (AMPS) (2) MODEL VDCF113B10XXB VDCF113B10XXC VDCF114B10XXB VDCF116B10XXB VDCF116B10XXC VDCF118B10XXB VDCF124B10XXB VDCF126B10XXB VDCF126B10XXC VDCF128B10XXB VDCF134B10XXB VDCF136B10XXB VDCF136B10XXC VDCF138B10XXB VDCF144B10XXB VDCF146B10XXB VDCF146B10XXC VDCF148B10XXB VDCF154B10XXB VDCF156B10XXB VDCF156B10XXC VDCF158B10XXB VDCF164B10XXB VDCF166B10XXB VDCF166B10XXC VDCF168B10XXB VDCF224B10XXB VDCF226B10XXB VDCF226B10XXC VDCF228B10XXB VDCF234B10XXB VDCF236B10XXB VDCF236B10XXC VDCF238B10XXB VDCF244B10XXB VDCF246B10XXB VDCF246B10XXC VDCF248B10XXB VDCF254B10XXB VDCF256B10XXB VDCF256B10XXC VDCF258B10XXB VDCF264B10XXB VDCF266B10XXB VDCF266B10XXC VDCF268B10XXB 380 Volts 400 Volts 415 Volts FLA MCA MOP FLA MCA MOP FLA MCA MOP NOTES: 3. For VSD-ready for Variable Speed Fan Control and Standard Control without Fan Cycling. JOHNSON CONTROLS 45

46 SECTION 5 - TECHNICAL DATA FORM NM1 Table 9 - Lug Data VDC AND VDCF MODELS VDC-11 and VDCF11 VDC-12 and VDCF12 VDC-13 and VDCF13 VDC-14 and VDCF14 VDC-15 and VDCF15 VDC-16 and VDCF16 VDC-22 and VDCF22 VDC-23 and VDCF23 VDC AND VDCF VOLTAGE DISCONNECT WIRE RANGE 1 HP 2 HP /400/415 #14-10 AWG #14-10 AWG /400/415 #14-10 AWG #14-10 AWG #10-3 AWG 380/400/415 #14-10 AWG 460 #14-10 AWG #10-3 AWG 380/400/415 #14-10 AWG 460 #14-10 AWG #10-3 AWG #14-2/0 AWG 380/400/ #14-10 AWG #10-3 AWG 575 #14-10 AWG #10-3 AWG #14-2/0 AWG 380/400/ #14-10 AWG #10-3 AWG #10-3 AWG 380/400/415 #14-10 AWG 460 #14-10 AWG #10-3 AWG #14-2/0 AWG 380/400/ #14-10 AWG #10-3 AWG JOHNSON CONTROLS

47 SECTION 5 - TECHNICAL DATA Table 9 - Lug Data (Cont'd) VDC AND VDCF MODELS VDC-24 and VDCF24 VDC-25 and VDCF25 VDC-26 and VDCF26 VDC AND VDCF VOLTAGE DISCONNECT WIRE RANGE 1 HP 2 HP #14-2/0 AWG #14-2/0 AWG 380/400/415 #10-3 AWG 460 #10-3 AWG 575 #14-10 AWG #14-2/0 AWG #6-3/0 AWG 380/400/ #10-3 AWG #14-2/0 AWG 575 #10-3 AWG #14-2/0 AWG #6-3/0 AWG 380/400/ #10-3 AWG #14-2/0 AWG 575 #10-3 AWG 5 JOHNSON CONTROLS 47

48 SECTION 5 - TECHNICAL DATA FORM NM1 Legend Power Wiring Control Wiring All electrical wiring connections should be made by a licensed electrical contractor in conformance with the national electrical code and local regulations which may apply. Wiring Diagrams Components: SD - Non-fused safety disconnect (handle on door) MC - Motor contractors SS - Motor contractor surge suppressors FUM - Motor fuses TR - Control circuit transformer FUT - Transformer fuses FUC - Control circuit fuse TB - Terminal blocks NOTES: LD16230a 1. Power supply (by others) to be 3-phase, 60 Hz (200, 230, 460, or 575 volts) or 50 Hz (380, 400, or 475 votls). 2. Compressor Interlock (by other) is 115 volts with 200, 230, 380, 400, 415, 460, or 575 volt supply. It allows the VDC condensers to operate when the chiller compressor starts. 3. Standard motors are 2.0 hp, 1150 rpm, 3 phase, 60 Hz with built-in thermal overload protection. 4. Supply voltage must be specified on purchase order. 5. All field wiring must meet NEC and local codes. 6. Double-wide units with motors wired in pairs require the optional manifold kit or a customer-supplied manifold. Figure 10 - Basic Factory Wiring - Standard, 1-6 Fans Long - VDC and VDCF 48 JOHNSON CONTROLS

49 SECTION 5 - TECHNICAL DATA Components: SD - Non-fused safety disconnect (handle on door) SWA - System 350 control switch (temperature type) SWB - System 350 stage modules (temperature type) Y350R - Power module SL - Outside Air Sensor MC - Motor contractors SS - Motor contractor surge suppressors FUM - Motor fuses TR - Control circuit transformer FUT - Transformer fuses FUC - Control circuit fuse TB - Terminal blocks SMC - Surface mount clip (Ships loose) Legend Power Wiring Control Wiring 5 NOTES: 1. Power supply (by others) to be 3-phase, 60 Hz (200, 230, 460, or 575 volts) or 50 Hz (380, 400, or 415 volts). 2. Compressor Interlock (by other) is 115 volts with 200, 230, 380, 400, 415, 460, or 575 volt supply. It allows the VDC condensers to operate when the chiller compressor starts. 3. Standard motors are 2.0 hp, 1150 rpm, 3 phase, 60 Hz with built-in thermal overload protection. 4. Supply voltage must be specified on purchase order. 5. All field wiring must meet NEC and local codes. 6. Double-wide units with motors wired in pairs require the optional manifold kit or a customer-supplied manifold. Figure 11 - Temp-Controlled Fan Cycling, 2-6 Fans Long - VDC LD16231a JOHNSON CONTROLS 49

50 SECTION 5 - TECHNICAL DATA FORM NM1 Components: SD - Non-fused safety disconnect (handle on door) SWA - System 350 control switch (temperature type) SWB - System 350 stage modules (temperature type) Y350R - Power module SL - Outside air sensor MC - Motor contractors SS - Motor contractor surge suppressors FUM - Motor fuses TR - Control circuit transformer FUT - Transformer fuses FUC - Control circuit fuse TB - Terminal blocks SMC - Surface Mount clip (Ships loose) Legend Power Wiring Control Wiring LD16232a NOTES: 1. Power supply (by others) to be 3-phase, 60 Hz (200, 230, 460, or 575 volts) or 50 Hz (380, 400, or 415 volts). 2. Compressor Interlock (by other) is 115 volts with 200, 230, 380, 400, 415, 460, or 575 volt supply. It allows the VDC condensers to operate when the chiller compressor starts. 3. Standard motors are 2.0 hp, 1150 rpm, 3 phase, 60 Hz with built-in thermal overload protection. 4. Supply voltage must be specified on purchase order. 5. All field wiring must meet NEC and local codes. Figure 12 - Temp-Controlled Fan Cycling, 2-6 Fans Long, Double-Wide, Fans Wired Individually - VDC 50 JOHNSON CONTROLS

51 SECTION 5 - TECHNICAL DATA Components: SD - Non-fused safety disconnect (handle on door) SWA - System 350 control switch (temperature type) SWB - System 350 stage modules (temperature type) Y350R - Power module SL - Outside air sensor (sensing fluid leaving temperature) MC - Motor contractors SS - Motor contractor surge suppressors FUM - Motor fuses TR - Control circuit transformer FUT - Transformer fuses FUC - Control circuit fuse TB - Terminal blocks IM - Imersion well 11A-601R (ships loose) Legend Power Wiring Control Wiring 5 LD16238a NOTES: 1. Power supply (by others) to be 3-phase, 60 Hz (200, 230, 460, or 575 volts) or 50 Hz (380, 400, or 415 volts). 2. Compressor Interlock (by other) is 115 volts with 200, 230, 380, 400, 415, 460, or 575 volt supply. It allows the VDC condensers to operate when the chiller compressor starts. 3. Standard motors are 2.0 hp, 1150 rpm, 3 phase, 60 Hz with built-in thermal overload protection. 4. Supply voltage must be specified on purchase order. 5. All field wiring must meet NEC and local codes. 6. Double-wide units with motors wired in pairs require the optional manifold kit or a customer-supplied manifold. Figure 13 - Temp-Controlled Fan Cycling, 2-6 Fans Long - VDCF JOHNSON CONTROLS 51

52 SECTION 5 - TECHNICAL DATA FORM NM1 Components: SD - Non-fused safety disconnect (handle on door) SWA - System 350 control switch (temperature type) SWB - System 350 stage modules (temperature type) Y350R - Power module SL - Outside air sensor (sensing fluid leaving Temperature) MC - Motor contractors SS - Motor contractor surge suppressors FUM - Motor fuses TR - Control circuit transformer FUT - Transformer fuses FUC - Control circuit fuse TB - Terminal blocks IM - Imersion well 11A-601R (ships loose) Legend Power Wiring Control Wiring LD16239a NOTES: 1. Power supply (by others) to be 3-phase, 60 Hz (200, 230, 460, or 575 volts) or 50 Hz (380, 400, or 415 volts). 2. Compressor Interlock (by other) is 115 volts with 200, 230, 380, 400, 415, 460, or 575 volt supply. It allows the VDC condensers to operate when the chiller compressor starts. 3. Standard motors are 2.0 hp, 1150 rpm, 3 phase, 60 Hz with built-in thermal overload protection. 4. Supply voltage must be specified on purchase order. 5. All field wiring must meet NEC and local codes. Figure 14 - Temp-Controlled Fan Cycling, 2-6 Fans Long, Double-Wide, Fans Wired Individually - VDCF 52 JOHNSON CONTROLS

53 SECTION 5 - TECHNICAL DATA Components: SD - Non-fused safety disconnect (handle on door) P470 - JCI P470 control switch (pressure type) PT - Electronic pressure transducer MC - Motor contractors SS - Motor contractor surge suppressors FUM - Motor fuses TR - Control circuit transformer FUT - Transformer fuses FUC - Control circuit fuse TB - Terminal blocks NUT - 1/4" Flare x 1/4" OD solder (ships loose) Legend Power Wiring Control Wiring 5 LD16233a NOTES: 1. Power supply (by others) to be 3-phase, 60 Hz (200, 230, 460, or 575 volts) or 50 Hz (380, 400, or 415 volts). 2. Compressor Interlock (by other) is 115 volts with 200, 230, 380, 400, 415, 460, or 575 volt supply. It allows the VDC condensers to operate when the chiller compressor starts. 3. Standard motors are 2.0 hp, 1150 rpm, 3 phase, 60 Hz with built-in thermal overload protection. 4. Supply voltage must be specified on purchase order. 5. All field wiring must meet NEC and local codes. 6. Double-wide units with motors wired in pairs require the optional manifold kit or a customer-supplied manifold. Figure 15 - Pressure-Controlled Fan Cycling, 2-5 Fans Long - VDC JOHNSON CONTROLS 53

54 SECTION 5 - TECHNICAL DATA Components: SD - Non-fused safety disconnect (handle on door) P470 - JCI P470 control switch (pressure type) PT - Electronic pressure transducer MC - Motor contractors SS - Motor contractor surge suppressors FUM - Motor fuses TR - Control circuit transformer FUT - Transformer fuses FUC - Control circuit fuse TB - Terminal blocks NUT - 1/4" Flare x 1/4" OD solder (ships loose) FORM NM1 Legend Power Wiring Control Wiring NOTES: 1. Power supply (by others) to be 3-phase, 60 Hz (200, 230, 460, or 575 volts) or 50 Hz (380, 400, or 415 volts). 2. Compressor Interlock (by other) is 115 volts with 200, 230, 380, 400, 415, 460, or 575 volt supply. It allows the VDC condensers to operate when the chiller compressor starts. 3. Standard motors are 2.0 hp, 1150 rpm, 3 phase, 60 Hz with built-in thermal overload protection. 4. Supply voltage must be specified on purchase order. 5. All field wiring must meet NEC and local codes. 6. Double-wide units with motors wired in pairs require the optional manifold kit or a customer-supplied manifold. Figure 16 - Pressure-Controlled Fan Cycling, 6 Fans Long - VDC LD16234a 54 JOHNSON CONTROLS

55 SECTION 5 - TECHNICAL DATA Components: SD - Non-fused safety disconnect (handle on door) P470 - JCI P470 control switch (pressure type) PT - Electronic pressure transducer MC - Motor contractors SS - Motor contractor surge suppressors FUM - Motor fuses TR - Control circuit transformer FUT - Transformer fuses FUC - Control circuit fuse TB - Terminal blocks NUT - 1/4" Flare x 1/4" OD solder (ships loose) 5 LD16235a NOTES: 1. Power supply (by others) to be 3-phase, 60 Hz (200, 230, 460, or 575 volts) or 50 Hz (380, 400, or 415 volts). 2. Compressor Interlock (by other) is 115 volts with 200, 230, 380, 400, 415, 460, or 575 volt supply. It allows the VDC condensers to operate when the chiller compressor starts. 3. Standard motors are 2.0 hp, 1150 rpm, 3 phase, 60 Hz with built-in thermal overload protection. 4. Supply voltage must be specified on purchase order. 5. All field wiring must meet NEC and local codes. Figure 17 - Pressure-Controlled Fan Cycling, 2-6 Fans Long, Double-Wide, Fans Wired Indivdualy - VDC JOHNSON CONTROLS 55

56 SECTION 5 - TECHNICAL DATA FORM NM1 Components: SD - Non-fused safety disconnect (handle on door) MC - Motor contractors SS - Motor contractor surge suppressors FUM - Motor fuses TR - Control circuit transformer FUT - Transformer fuses FUC - Control circuit fuse TB - Terminal blocks IC - Inverted contractor BP - Bypass contractor SS1 - VSD Bypass switch on door RR - Run relay NOTES: 1. Power supply (by others) to be 3-phase, 60 Hz (200, 230, 460, or 575 volts) or 50 Hz (380, 400, or 415 volts). 2. Compressor Interlock (by other) is 115 volts with 200, 230, 380, 400, 415, 460, or 575 volt supply. It allows the VDC condensers to operate when the chiller compressor starts. 3. Standard inverter-duty motors are 2.0 hp, 1150 rpm, 3-phase, 60 Hz with built-in thermal overload protection. 4. VSD controller is not included and must be field provided. 5. Temperature or pressure sensors for controls must be field provided and installed, if desired. 6. Supply voltage must be specified on purchase order. 7. All field wiring must meet NEC and local codes. 8. Double-wide units with motors wired in pairs require the optional manifold kit or a customer-supplied manifold. 9. WARNING DO NOT connect Incoming AC power to output terminals. Severe damage to the drive will result. Figure 18 - VSD-Controlled Fans, 2-6 Fans Long, Double-Wide Fans Wired in Pairs - VDC and VDCF 56 JOHNSON CONTROLS

57 SECTION 6 - COMMISSIONING Unit Identification A nameplate permanently attached to the unit identifies air-cooled condenser unit information. Figures 19 through 22 on page 57 shows the information provided. We recommend that the nameplate data be entered on the ID Plate Information graphic, Figures 19 through 22 on page 57, for reference when ordering parts. Provide the MODEL and SERIAL NUM- BER from the nameplate and installation date when making inquiries about the unit or ordering replacement parts. If failure occurs provide the date of the failure. Start-Up Check that the fan(s) are rotating in the right direction for draw through operation. If it is necessary to reverse rotation of the three phase motors, interchange any two electrical leads at the condenser fan contactor or main disconnect switch. Be sure that all noncondensable gases are purged from each refrigerant circuit. 6 LD16226 LD16227 Figure 19 - ID Plate Information, VDC - Monterrey, Mexico Figure 21 - ID Plate Information, VDC - San Antonio, TX Figure 20 - ID Plate Information, VDCF - Monterrey, Mexico LD16228 Figure 22 - ID Plate Information, VDCF - San Antonio, TX LD16229 JOHNSON CONTROLS 57

58 SECTION 6 - COMMISSIONING FORM NM1 This Page Intentionally Left Blank. 58 JOHNSON CONTROLS

59 SECTION 7 - UNIT OPERATION Standard Fan Cycling Air-cooled condensers must operate at lower than design ambient dry bulb temperature. A minimum operating pressure must be maintained under all ambient operating conditions to ensure sufficient pressure and satisfactory system operation. Therefore, if air-cooled condenser operation below 40 F ambient temperature is required, refer to Fan Cycling Options on page 11 and Low Ambient Control Options on page 60. The capacity of an air-cooled condenser is directly proportional to the TD, which is the temperature difference between the condensing temperature and the air dry bulb entering the condenser. A condenser is normally selected to operate on a TD suitable for summer ambient temperature conditions. The capacity of this condenser, however, is substantially increased when operated with low ambient temperatures. The result of the increase in condenser capacity is to reduce the system head pressure. When the ambient temperature drops below a certain value, the head pressure falls below the point where the expansion valve cannot properly feed the evaporator and very poor or unsatisfactory system operation results. On multiple fan units, individual fan sections can be cycled to not exceed nominal condenser capacity at low ambient conditions. Table 10 on page 59 provides minimum ambient temperatures for this method of control. Table 11 on page 59 gives individual thermostat settings for all units referenced to various design temperature differences. In lieu of thermostats, fan cycling can be controlled by pressure switches connected to condenser inlet (hot gas) headers. This is recommended for process applications. Contact Johnson Controls for special pricing. Table 10 - Minimum Ambient Temperatures For Fan Cycling Control Type Of Condenser Single Wide No. Of Fans Double Wide No. Of Fans Minimum Outside Temperature For 100% Capacity Design Temperature Difference (Td F) , Table 11 - Temperature Settings For Fan Cycling Single-Wide Double-Wide Temp Design temperature Difference (TD F) Number of Number of Settings Fans Fans (Stage) Setpoint (l) Setpoint (2) Offset (1) Setpoint (3) Offset (2) Offset (1) Setpoint (4) Offset (3) Offset (2) Offset (1) Setpoint (5) Offset (4) Offset (3) Offset (2) Offset (I) JOHNSON CONTROLS 59

60 SECTION 7 - UNIT OPERATION VDC Pressure Setting Guidelines When a YORK VDC is used as a remote condenser with a YCRL chiller, the VDC must be ordered and installed with the Head Pressure Control by Pressure option, which provides Johnson Controls model P470 pressure controllers factory mounted in the VDC control panel. P470 controller operating manuals, included in the VDC control panel, provide guidance for field fan-staging setup. Johnson Controls recommends the following pressure set points for general use; if excessive fan cycling is noted the final stage of cycling should be adjusted (deadband increased). The deadband proposed in these guidelines is set to 125 psi, which is the standard setting for Johnson Controls air-cooled R-410A units (YLAA, YCAL and YCRL). Two-stage units (2-fan single-wide, 4-fan double-wide VDC) Stage 1, ON when any compressor is ON. Stage 2, ON at 380 psig, OFF at 255 psig. Three-stage units (3-fan single-wide, 6-fan double-wide VDC) Stage 1, ON when any compressor is ON. Stage 2, ON at 380 psig, OFF at 255 psig. Stage 3, ON at 405 psig, OFF at 280 psig. Four-stage units (4-fan single-wide, 8-fan double-wide VDC) Stage 1, ON when any compressor is ON. Stage 2, ON at 380 psig, OFF at 255 psig. Stage 3, ON at 405 psig, OFF at 280 psig. Stage 4, ON at 430 psig, OFF at 305 psig. Compressor will unload when the discharge pressure reaches 565 psig. Low Ambient Operation Since air-cooled condensers are often required to operate over a wide range of ambient air temperatures and variable loading conditions, provision must be made to maintain the overall system balance. Any air-cooled condenser tends to run at a low head pressure when operating in a low ambient air temperature. Low head pressures can result in poor expansion valve operation, which will in turn cause poor system operation. Within limits, air conditioning applications allow the operating head pressure to vary with the ambient air temperature without adversely affecting the system operation. The head pressure lower limit depends upon the required pressure drop across the thermostatic expansion valve. For normal air conditioning applications, the low pressure limit should correspond to a condensing temperature of 65 to 70 F. This corresponds to an ambient air temperature lower limit of approximately 55 to 60 F. Air conditioning may not be required at or below these ambient temperatures. However, to ensure sufficient receiver pressure during compressor start-up, it is recommended that a high-pressure cut-in switch be used to allow the head pressure to rise before the condenser fan starts. Many applications, such as commercial refrigeration, require operation below the above ranges (55 to 60 F). Johnson Controls offers fan cycling to maintain a desired condensing pressure. Low Ambient Control Options FORM NM1 Fan Cycling Control On multiple fan units, individual fan sections can be controlled to prevent exceeding nominal condenser capacity at low ambient conditions. Table 10 on page 59 provides minimum ambient temperatures for effective fan cycle control. Lower ambient temperatures than listed are not recommended for this method of control. Table 11 on page 59 gives temperature settings for all units referenced to various design temperature differences. Head Pressure Control by Temperature on page 11 for VDCs and VDCFs and Head Pressure Control by Pressure on page 12 for VDCs can be used to control individual fans in single-wide models and individual fans or pairs of fans in double-wide models. Head Pressure Control (VSD Ready) on page 12 for VDCs and VDCFs can be used to vary speeds of all fans in unison. 60 JOHNSON CONTROLS

61 SECTION 7 - UNIT OPERATION A99 Temperature Sensor Description and Mounting Description Accessories See Figure 24 on page 61 for A99B series accessories. All accessories are available through local Johnson Control/Penn representatives using part numbers shown. Figure 23 - A99B Temperature Sensors LD14536 Operation The A99B sensor incorporates a PTC silicon sensing element whose resistance increases with an increase in temperature. The sensor has a reference resistance of 1035 ohms at 77 F (25 C). Each element is calibrated according to a standard graph, as shown in Table 12 on page 62. The A99B Series Temperature Sensors are passive PTC (Positive Temperature Coefficient) sensors. The A99B sensors are splashproof and are designed to measure temperature in a variety of refrigeration applications. Several accessories allow easy tailoring of the temperature sensor to various mounting configurations. 1/4 (6) 2 (50) Figure 25 - A99B Sensor Dimensions in. (mm) LD14535 Applications include temperature sensing for freezers and coolers, as well as in defrost termination sensing, space and return air temperature sensing, and condenser fan cycling /8 (229) 4 5/16 (110) 1/2 (13) 1 3/4 (44) Sun Shield SHL10A-603R EMT Conduit Adapter ADP11A-600R 4 1/2 (113.5) 1 11/16 (42) PVC Enclosure BOX10A-600R 1 3/8 (35) 1/4 (6) 1 (25.4) 1 (25.4) Surface Mount Clip A99-CLP-1 4 3/4 (119) 3 (76) Dia. 3/8 (9.3) 7/8 (23) Immersion Well WEL 11A-601R LD14537 Figure 24 - A99B Sensor Accessories JOHNSON CONTROLS 61

62 SECTION 7 - UNIT OPERATION FORM NM1 Table 12 - Resistance vs. Temperature F ( C) Resistance in Ohms F ( C) Resistance in Ohms -40 (-40) (45) (-35) (50) (-30) (55) (-25) (60) (-20) (65) (-15) (70) (-10) (75) (-5) (80) (0) (85) (5) (90) (10) (95) (15) (100) (20) (105) (25) (110) (30) (115) (35) (120) (40) 1153 Temperature Sensor Mounting - VDC Air-cooled condenser ambient air temperature sensor mounting should use the surface mounting clip provided inside the control box and observe the following guidelines: Sensor can be mounted in any position. Locate in an area that represents a steady temperature and air mixing. Do not mount near excessive vibration or electrical noise. For outdoor applications avoid mounting in direct sunlight. Mounting on the north side of the unit is preferred, but if not possible use a sun shield. Temperature Sensor Mounting - VDCF Fluid coolers sensing liquid outlet temperature use the immersion well provided inside the control box and observe the following guidelines: Select a location in the outlet pipe line. A 1/2 in. opening is required to braze the immersion well. The pipe diameter must be greater than 3 in. Perform a leak test on the braze joint before putting system into operation. Use thermally conductive paste inside the immersion well. Loosen the set screw in the immersion well and thread the spring, then the bushing, onto the sensor lead. At least one-half of the bushing is inserted into the immersion well (bushing will compress spring) and tighten the set screw against the bushing. Mounting Using an Immersion Well - VDCF 1. Select the mounting location in the pipe line. A 1/2", 14 NPT, opening is required to properly install the immersion well (WEL11A-601R). The pipe s diameter must be greater than the length of the well probe. 2. Insert an appropriate amount of thermally conductive paste in the well. 3. Install the immersion well. Tighten hex nut securely using a wrench. 1/2 inch 14 NPT Opening Tighten with Wrench LD14539 Figure 26 - Installing The Immersion Well 4. Using a straight slot screwdriver, loosen the set screw at top of the immersion well. 5. Thread the spring, then the bushing, onto the sensor lead. Sensor Lead. Figure 27 - Insert Sensor, Spring And Bushing LD Insert sensor, spring, and bushing into well so that at least one-half of the bushing is inserted into the well, as shown in Figure 27 on page 62 (bushing will compress the spring). 7. Tighten the set screw against the bushing. 62 JOHNSON CONTROLS

63 SECTION 7 - UNIT OPERATION Temperature Sensor Replacement Parts See Table 13 on page 63 for temperature sensor product code numbers. Table 13 - Replacement Temperature Sensor Product Code Numbers Product Code Description Number A99BA-200C PTC Silicon Sensor with Shielded Cable; Cable length: 6-1/2 ft (2 m); Range: -40 to 212 F (-40 to 100 C). A99BB-25C PTC Silicon Sensor with PVC Cable; Cable length: 9-3/4 in. (0.25 m); Range: -40 to 212 F (-40 to 100 C). A99BB-200C PTC Silicon Sensor with PVC Cable; Cable length: 6-1/2 ft (2 m); Range: -40 to 212 F (-40 to 100 C). A99BB-200D PTC Silicon Sensor with PVC Cable Bulk Pack; contains 100 A99BB-200 sensors. Individual sensor cable length: 6-1/2 ft (2 m); Range: -40 to 212 F (-40 to 100 C). A99BB-300C PTC Silicon Sensor with PVC Cable; Cable length: 9-3/4 ft (3 m); Range: -40 to 212 F (-40 to 100 C). A99BB-500C PTC Silicon Sensor with PVC Cable; Cable length: 16-3/8 ft (5 m); Range: -40 to 212 F (-40 to 100 C). A99BB-600C PTC Silicon Sensor with PVC Cable; Cable length: 19-1/2 ft (6 m); Range: -40 to 212 F (-40 to 100 C). A99BC-25C PTC Silicon Sensor with High Temperature Silicon Cable; Cable length: 9-3/4 in. (0.25 m); Range: -40 to 248 F (-40 to 120 C). A99BC-300C PTC Silicon Sensor with High Temperature Silicon Cable; Cable length: 9-3/4 ft (3 m); Range: -40 to 248 F (-40 to 120 C). A99BC-1500C PTC Silicon Sensor with High Temperature Silicon Cable; Cable length: 49 ft (15 m); Range: -40 to 248 F (-40 to 120 C). Note: All sensors are available through local Johnson Controls / Penn representatives using part numbers shown. Pressure Transducers Mounting Condensers sensing inlet pressure use the 1/4" SAE flare nut provided inside the control box and observe the following guidelines: 7 LD14541 Select a location in the inlet pipe line and braze the 1/4" SAE flare nut. Hand thread the transducer to the pressure tap point. Tighten the connection using the wrench flats on the transducer to avoid damaging it. Perform a leak test on the braze joint before putting system into operation. Use only the shielded wire harness provided. Figure 28 - P499 Electronic Pressure Transducers 24V COM VDC SEN Red Wire = SUPPLY Black Wire = COMMON White Wire = OUTPUT CONTROLLER LD14540 Figure 29 - Pressure Transducer Wiring JOHNSON CONTROLS 63

64 SECTION 7 - UNIT OPERATION FORM NM1 Table 14 - Pressure vs. Voltage P499 RCP-105C (0-500PSIG) TRANSDUCER P499 RCP-107C (0-700PSIG) TRANSDUCER Voltage (VDC) Pressure (psig) Voltage (VDC) Pressure (psig) VSD Inverter Wiring Reference WIRING DIAGRAMS FIGURE 18: Threephase power supplied to the inverter, LINE TO VSD, shall be run in a conduit separate from the power output conduit, LOAD FROM VSD. Each conduit shall contain only the three-phase power wires and a ground wire with no additional wiring. The VSD ground wire in each conduit shall be grounded to its own ground lug located in the VDC motor control panel. Table 15 - VSD Inverter Connections VDC Control Panel Terminal Block Lugs Terminal Block, tb3 U1, V1, W1 U2, V2, W2 drive manufacturer input terminals output terminals ABB U1, V1, W1 U2, V2, W2 Eaton L1, L3, L3 U, V, W Danfoss L1, L3, L3 U, V, W Schneider L1, L3, L3 U, V, W Note: 1. Connect VSD inverter drive terminals to the appropriate control panel terminal block lug. VSD Inverter Installation Checklist Installation environment conforms to the drive s specifications for ambient conditions. The drive is mounted securely. The drive has adequate ventilation. The motor and driven equipment are ready to be run. The correct RFI filter screws for the power source are used. The drive and motor are properly grounded. The input voltage matches the drive s rating. The input power, motor and control wiring are through separate conduit runs. NO power factor compensation capacitors are in the motor cable. NO tools or foreign objects (such as drill shavings) are inside the drive. NO alternate power source for the motor is connected, and no voltage is applied to the output of the drive. All connections are tightened per specification, and all wiring is correct. 64 JOHNSON CONTROLS

65 SECTION 8 - MAINTENANCE General When our Johnson Controls remote Air-Cooled Condenser or Fluid Cooler has been properly installed, it will require little in the way of regular service or maintenance. A regular schedule of periodic maintenance should be established, which includes a complete annual checkup. Motors are equipped with sealed bearings; no motor grease is required. Cleaning When visual inspection so indicates, the condenser coil should be cleaned with a vacuum cleaner, compressed air or brush to clear dust and debris which will impede performance. A clean coil saves energy. Consult the material Safety Data Sheet to determine a cleaning solution that is compatible with all parts of the unit. If the unit's casing shows signs of rust, the rust spots should be cleaned and sprayed with a rust preventative. Recommended Spare Parts See Renewal Parts Guide, Form RP1 for replacement and recommended spare parts for earlier as well as current models. 8 JOHNSON CONTROLS 65

66 P.O. Box 1592, York, Pennsylvania USA Copyright by Johnson Controls 2015 Form NM1 (615) Issue Date: June 18, 2014 Supersedes: NM1 (413) Subject to change without notice. Printed in USA ALL RIGHTS RESERVED

FIELD RE-ASSEMBLY FOR FORM 3 AND FORM 7 SHIPMENT MODEL YD CHILLERS - MOD A AND B WITH GRAPHIC CONTROL CENTER AND ELECTRO-MECHANICAL STARTER

FIELD RE-ASSEMBLY FOR FORM 3 AND FORM 7 SHIPMENT MODEL YD CHILLERS - MOD A AND B WITH GRAPHIC CONTROL CENTER AND ELECTRO-MECHANICAL STARTER CENTRIFUGAL LIQUID CHILLERS INSTALLATION INSTRUCTIONS Supersedes: 160.69-NM3 (912) Form 160.69-NM3 (715) FIELD RE-ASSEMBLY FOR FORM 3 AND FORM 7 SHIPMENT MODEL YD CHILLERS - MOD A AND B WITH GRAPHIC CONTROL

More information

MACH N-407 Heat Pump Air-Cooled Chiller

MACH N-407 Heat Pump Air-Cooled Chiller MACH060-01-N-407 Heat Pump Air-Cooled Chiller Heat Pump Air-Cooled Chillers for Global Residential and Light Commercial Microclimates MACH NOMENCLATURE BREAKDOWN MACH-060-01 - N - 407 Refrigerant Type

More information

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811 Description These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of Refrigerant R-410A for storage

More information

MAC N-407 Air-Cooled Chiller

MAC N-407 Air-Cooled Chiller MAC036-01-N-407 Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial MicroClimates MAC036 NOMENCLATURE BREAKDOWN MAC036-01 - N - 407 Refrigerant Type Air-Cooled Chiller 036=

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703 TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.

More information

PACKAGE AIR CONDITIONER

PACKAGE AIR CONDITIONER PACKAGE AIR CONDITIONER FORM NO. ATZ-206 TZAA- HIGH EFFICIENCY SERIES NOMINAL SIZE 10 TON [35.2 kw] 10 TON MODEL [35.2 kw] This product is shipped with a nitrogen holding charge that must be vented prior

More information

Installation, Operation, and Maintenance Information

Installation, Operation, and Maintenance Information Installation, Operation, and Maintenance Information Air Cooled Condensers 8-2016 Rev 0 Table of Contents General Safety Information 2 Inspection 2 Installation 2 6 Rigging and Assembly 2 Unit Location

More information

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL The LA/LB line is a flexible performer. LA300, LB360 & 480 can be

More information

Model VDC Direct-Drive Remote Air-Cooled Condensers

Model VDC Direct-Drive Remote Air-Cooled Condensers Model VDC Direct-Drive Remote Air-Cooled Condensers 33 Models R-22, R-134a, R-404A, R-407C, R-410A, R-507A Nominal Heat Rejection Capacity 175 MBH through 2280 MBH Table of Contents... 1 Mechanical Specifications...

More information

CENTRIFUGAL LIQUID CHILLERS YMC 2 MODEL A WITH OPTIVIEW CONTROL CENTER. R-134a. INSTALLATION Supersedes: N1 (611) Form N1 (512) LD14000

CENTRIFUGAL LIQUID CHILLERS YMC 2 MODEL A WITH OPTIVIEW CONTROL CENTER. R-134a. INSTALLATION Supersedes: N1 (611) Form N1 (512) LD14000 CENTRIFUGAL LIQUID CHILLERS INSTALLATION Supersedes: 160.78-N1 (611) Form 160.78-N1 (512) YMC 2 MODEL A WITH OPTIVIEW CONTROL CENTER LD14000 R-134a Issue Date: May 30, 2012 IMPORTANT! READ BEFORE PROCEEDING!

More information

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer 5/16 Rev. A 57-02509 2 Contents INTRODUCTION... 4 WARNING LABELS AND SAFETY INSTRUCTIONS... 5 PS SERIES PARALLEL

More information

12 In Row. Installation Manual. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

12 In Row. Installation Manual. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc. MISSION CRITICAL Air Conditioning Systems 12 In Row Installation Manual ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 Table of Contents Table of Contents... 3 Site

More information

Microchannel REMOTE AIR COOLED CONDENSER. Technical Bulletin: MXCC_004_ Products that provide lasting solutions.

Microchannel REMOTE AIR COOLED CONDENSER. Technical Bulletin: MXCC_004_ Products that provide lasting solutions. Microchannel REMOTE AIR COOLED CONDENSER Technical Bulletin: MXCC_004_030817 Products that provide lasting solutions. Krack s new Microchannel Remote Air Cooled Condenser incorporates a new patented modular

More information

Air Cooled Condenser Installation and Operating Instructions

Air Cooled Condenser Installation and Operating Instructions Bulletin CAC_O&I 02 August 2016 Air Cooled Condenser Installation and Operating Instructions CAC Air Cooled Condensers Table of Contents Section 1. General Information... 2 Section 2. Refrigeration Piping...

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions 38AH044-134 Air-Cooled Condensing Units 50/60 Hz Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin ACU_O&I 02 August 2016 Condensing Unit Installation and Operating Instructions ACU Air Cooled Condensers Table of Contents Section 1. General Information... 2 Section 2. Refrigeration Piping...

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin WCU_O&I 01 June 2003 Condensing Unit Installation and Operating Instructions WCU Air Cooled Condensing Unit Table of Contents Section 1. Section 2. Section 3. Section 4. Section 5. Section 6.

More information

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) CS*/CD*/CP* Series Air Cooled Condensing Units Operating and Installation Manual CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) TABLE OF CONTENTS I. Receipt of Equipment 2 II. Piping...4 III. System

More information

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes). Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz) DESCRIPTION These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of refrigerant-22 for storage

More information

Air-Cooled Condensers

Air-Cooled Condensers Catalog Cat 622-2 Air-Cooled Condensers Model ACH 014-225 Model ACX 014-225 Model ACL 014-225 Capacities from 130 MBH to 2225 MBH R-134a, R-407c, R-410A Table of Contents Introduction...3 Model Description...4

More information

SECTION AIR COILS

SECTION AIR COILS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

Service Step by Step Trouble-Shooting Check-List

Service Step by Step Trouble-Shooting Check-List WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:

More information

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.1 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.1 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

Levitor II. AIR-COOLED CONDENSER WITH ELECTRONICALLY COMMUTATED AXITOP MOTORS (Available for Fluid Cooler Applications)

Levitor II. AIR-COOLED CONDENSER WITH ELECTRONICALLY COMMUTATED AXITOP MOTORS (Available for Fluid Cooler Applications) Levitor II AIR-COOLED CONDENSER WITH ELECTRONICALLY COMMUTATED AXITOP MOTORS (Available for Fluid Cooler Applications) Technical Bulletin: LEVE_002_103116 Products that provide lasting solutions. Table

More information

Liebert CSU3000 Chiller

Liebert CSU3000 Chiller CSI 15620 - Packaged Water Chillers Liebert CSU3000 Chiller Guide Specifications for 7.5-37 Ton CS/CD/CT Models 1.0 GENERAL 1.1 CS/CD MODELS The main-frame coolant supply unit shall be a Liebert Model,

More information

MAC-120HE-03 Air-Cooled Chiller

MAC-120HE-03 Air-Cooled Chiller MAC-120HE-03 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 380/415/460-3-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-03

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions 09AZ091-182 Remote Air-Cooled Condensers 90 to 200 Tons Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS.....................1,2 GENERAL........................................

More information

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.2 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

1.1 This section applies to air handling units for HVAC Systems.

1.1 This section applies to air handling units for HVAC Systems. AIR HANDLING UNITS GENERAL INFORMATION 1.1 This section applies to air handling units for HVAC Systems. DESIGN REQUIREMENTS 2.1 Design Criteria a. The decision to use modular central station air handling

More information

Series 6, Vertical Floor-Mount Units

Series 6, Vertical Floor-Mount Units MISSION CRITICAL Air Conditioning Systems Series 6, Vertical Floor-Mount Units Installation Manual ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 Table of Contents

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance Series R Air-Cooled Helical Rotary Liquid Chiller RTAD 085-180 (50Hz) Standard, Free Cooling and Heat Recovery models RTAD-SVX01F-E4 General information Foreword These

More information

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS CROWN Boiler Co Santa-Fe Series Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS These instructions must be affixed on or adjacent to the air handler Models: SAC049A20 SAC059A25

More information

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT: GENERAL SPECIFICATIONS OUTDOOR UNIT: TECHNICAL GUIDE COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM MODELS HB 180 & HB 240 MODELS LB 180 & LB 240 15 & 20 NOMINAL TONS 9.7 EER Two independent refrigerant

More information

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton G Series ENCASED/UNCASED AIR COILS Geothermal/Water Source Heat Pumps R-410A Refrigerant 2- Ton Dimensional Data G Series Air Coils Installation ti Manual Installation Information Maintenance IM1018AG1

More information

Installation Instructions

Installation Instructions PREFERREDT SERIES AIR CONDITIONER WITH PURONR REFRIGERANT 1-1/2 TO 5 NOMINAL TONS Installation Instructions Fig. 1 --- 538A NOTE: Read the entire instruction manual before starting the installation. TABLE

More information

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS SECTION 236200 - PACKAGED COMPRESSOR AND CONDENSER UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply

More information

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS 036-21096-001 (0101) SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240 20 NOMINAL TONS DESCRIPTION This 20 ton evaporator blower is designed with two distinct modules to provide maximum application flexibility. The

More information

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 PROVEN PERFORMANCE GENERAL FEATURING

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 PROVEN PERFORMANCE GENERAL FEATURING TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 PROVEN PERFORMANCE GENERAL The LA/LB line is a flexible performer. LA300, LB360 & 480 canbepositionedinupto12differentpositionsandsuspended

More information

Air-Cooled Condensers

Air-Cooled Condensers Catalog Cat 622-3 Air-Cooled Condensers Model ACH 014-225 Model ACX 014-225 Model ACL 014-225 Capacities from 130 MBH to 2225 MBH R-134a, R-407c, R-410A Table of Contents Introduction...3 Model Description...4

More information

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307 DESCRIPTION Technical Guide CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) This 20 ton evaporator blower is designed with two distinct modules to provide maximum application

More information

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC!

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC! COIL Manufacturing Inc. When you want Quality, specify COLMAC! Installation, Operation, and Maintenance ENG00018621 Rev A Air Cooled Fluid Coolers Contents 1. SAFETY INSTRUCTIONS... 1 2. MODEL NOMECLATURE...

More information

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13 R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions 38AH044-134 Air-Cooled Condensing Units 50/60 Hz Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................

More information

Daikin Direct Expansion (DX) Cooling Coils

Daikin Direct Expansion (DX) Cooling Coils Installation and Maintenance Manual IM 902 Daikin Direct Expansion (DX) Cooling Coils Group: Applied Air Part Number: IM 902 Date: February 2008 Types EN, EF, ER, EJ, EK 2008 Daikin Applied Contents Introduction...

More information

Installation Instructions

Installation Instructions 24AHA4 Performance Series Air Conditioner with Puron Refrigerant 1-1/2 to 5 Nominal Tons Installation Instructions Fig. 1-24AHA4 A07532 SAFETY CONSIDERATIONS Improper installation, adjustment, alteration,

More information

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS 550.23-TG5Y (893) CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L2EU240 20 NOMINAL TONS DESCRIPTION This 20 ton evaporator blower is designed with two distinct modules to provide maximum application flexibility.

More information

Air-Cooled Fluid Cooling Units (P/N E R2)

Air-Cooled Fluid Cooling Units (P/N E R2) Fluid Cooler Series Air-Cooled Fluid Cooling Units Operating and Installation Manual Air-Cooled Fluid Cooling Units (P/N E208134 R2) TABLE OF CONTENTS 1 RECEIPT OF EQUIPMENT 3 1.1 INSPECTION 3 1.2 LOSS

More information

Product Data. GEMINI SELECT 09DPS ,09DPM Air-Cooled Condensers with PURON Refrigerant (R-410A) 50/60 Hz

Product Data. GEMINI SELECT 09DPS ,09DPM Air-Cooled Condensers with PURON Refrigerant (R-410A) 50/60 Hz Product Data GEMINI SELECT 09DPS018-030,09DPM035-130 Air-Cooled Condensers with PURON Refrigerant (R-410A) 50/60 Hz 18 to 130 Nominal Tons (63 to 457 Nominal kw) a38-7096 09DPS030 UNIT WITH LOW SOUND OPTION

More information

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw) FALCON Rooftop Units ACPSE 50/60Hz Cooling : 36 to 1388 MBH (11 to 407 ) Heating : 40 to 1298 MBH (12 to 380 ) R Products that perform...by people who care NOMENCLATURE 6 AC P S E 435 P - HP G Q 6-60 Hz

More information

SECTION AIR HANDLING UNIT

SECTION AIR HANDLING UNIT SECTION 15800 - AIR HANDLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR

More information

APPLICATION DATA SHEET

APPLICATION DATA SHEET APPLICATION DATA SHEET General Piping Recommendations and Refrigerant Line Length for Split-System Air Conditioners and Heat Pumps GENERAL GUIDELINES This Split-System (Air Conditioning Condensing/Heat

More information

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION 100 TON AIR-COOLED SCROLL PACKAGED SPECIFICATIONS Call us today! (800)341-4297 Trane Portable Packaged Air Conditioner units contain the best compressor technology available, in order to achieve the highest

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

Microchannel REMOTE AIR COOLED CONDENSER WITH ELECTRONICALLY COMMUTATED AXITOP MOTORS. Technical Bulletin. Products that provide lasting solutions.

Microchannel REMOTE AIR COOLED CONDENSER WITH ELECTRONICALLY COMMUTATED AXITOP MOTORS. Technical Bulletin. Products that provide lasting solutions. Microchannel REMOTE AIR COOLED CONDENSER WITH ELECTRONICALLY COMMUTATED AXITOP MOTORS Technical Bulletin Products that provide lasting solutions. Krack Corporation has a long tradition of leadership and

More information

Installation Owner Diagnostics

Installation Owner Diagnostics Installation Owner Diagnostics Split System Cooling Condensers Model CTA 7 1/2 to 15 Tons Models A and later Design Sequence CTA 090A***A 60 HZ 120A***A 60 HZ 120B***A 60 HZ 180B***A 60 HZ SS-SVN11A-EN

More information

.2 Section Waste Management and Disposal.

.2 Section Waste Management and Disposal. Issued 2005/06/01 Section 15624 Packaged Rotary Screw Water Chillers Page 1 of 5 PART 1 General 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13 Tag Data - Split System Air Conditioning Units (Large) (Qty: 6) Item Tag(s) Qty Description Model Number A1 20 ton vfd 6 6-25 Ton Unitary Split Systems ( SSC2 TTA24004H00-TWE240E404A TTA Air Condensing

More information

Catalog Air Cooled Split System Condensing Units for Rooftop Systems and Air Handlers

Catalog Air Cooled Split System Condensing Units for Rooftop Systems and Air Handlers Air Cooled Split System Condensing Units for Rooftop Systems and Air Handlers Models RCS 025C through 135C 25 to 135 Tons R-22/R407C Refrigerant Catalog 221-1 Table of Contents Introduction.... 3 The Condensing

More information

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW INSTALLATION INSTRUCTIONS RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW 92-106595-01-00 TABLE OF CONTENTS Introduction.......................................

More information

MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH

MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH 318 MHNCCX NOMENCLATURE BREAKDOWN 4-Pipe Heat/Cool Ceiling Concealed Fan Coil MHNCCW- XX - XX Ceiling Concealed

More information

TECHNICAL GUIDE DESCRIPTION EA090/FA090 SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNIT INDOOR UNIT

TECHNICAL GUIDE DESCRIPTION EA090/FA090 SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNIT INDOOR UNIT TECHNICAL GUIDE SPLIT-SYSTEM HEAT PUMPS EA090/FA090 DESCRIPTION YORK has combined the latest concepts in modern technology with time-proven quality standards to design a split-system heat pump to meet

More information

Air-Cooled Split System Condensing Unit for Rooftop Systems and Air Handlers

Air-Cooled Split System Condensing Unit for Rooftop Systems and Air Handlers Catalog 221-1 Air-Cooled Split System Condensing Unit for Rooftop Systems and Air Handlers Model RCS 025C to 135C R-22/R-407C Refrigerant Contents Introduction............................... 3 The Condensing

More information

High Profile Evaporator

High Profile Evaporator PRODUCT DATA & INSTALLATION Bulletin K30-KHPA-PDI-5 Part # 1081585 PRODUCT SUPPORT web: k-rp.com/khp email: evaps@k-rp.com call: 1-844-893-3222 x520 scan: High Profile Evaporator High & Medium Temperature

More information

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check

More information

Series 6, Vertical Floor-Mount Units

Series 6, Vertical Floor-Mount Units MISSION CRITICAL Air Conditioning Systems Series 6, Vertical Floor-Mount Units Installation Manual ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 Table of Contents

More information

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS SUNLINE 2000ô MODELS: H5CE090, H3CE120 & H1CE150 7-1/2, 10, & 12-1/2 NOMINAL TONS 9.0-9.5 EER DESCRIPTION These Sunline 2000ô units are completely

More information

SECTION AIR COOLED WATER CHILLERS

SECTION AIR COOLED WATER CHILLERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Chiller package B. Charge of refrigerant and oil C. Controls and control connections D. Chilled water connections E. Starters F. Electrical power connections 1.2

More information

MODELS B1PA024, 030 AND 036

MODELS B1PA024, 030 AND 036 STELLAR 2000 SINGLE PACKAGE HEAT PUMPS INSTALLATION INSTRUCTION Supersedes: 511.26-N1Y (892) 511.26-N1Y (893) MODELS B1PA024, 030 AND 036 035-11622 GENERAL YORK Model B1PA units are factory assembled heat

More information

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS DLCLRA INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 Fig. 1 - Size 36 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 WIRING...

More information

Construction Standards Page

Construction Standards Page Construction Standards Page 236313-1 SECTION 236313 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS Concepcion Carrier Air conditioning Company Philippines INSTALLATION MANUAL, START-UP & SERVICE INSTRUCTIONS 38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS CONTENTS: Physical Data and Dimensions........

More information

Commercial High-Efficiency Condensing Units

Commercial High-Efficiency Condensing Units FORM NO. A22-194 REV. 2 Supersedes Form No. A22-194 Rev. 1 Commercial High-Efficiency Condensing Units RAWL High Efficiency 6.5 & 7.5 TON MODEL [22.86 & 26.38 kw] TABLE OF CONTENTS Model Number Designation...2

More information

30GT FLOTRONIC AIR-COOLED CHILLERS

30GT FLOTRONIC AIR-COOLED CHILLERS 30GT-41SB 30GT040-110 FLOTRONIC AIR-COOLED CHILLERS PERFORMANCE DATA FIELD WIRING DIAGRAM 1998 Carrier Corporation Syracuse, New York 13221 Form 30GT-41SB Supersedes 30GT-21SB, 30GT-22SB, 30GT-23SB, Printed

More information

SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ DESCRIPTION

SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ DESCRIPTION SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ E3FB090/E1FB120/F3EH090 & 120 7-1/2 & 10 NOMINAL TONS (60 HZ) 7 & 9 NOMINAL TONS (50 HZ) (9.0-9.2 EER) 208/230/460 VOLT ONLY 208/230 VOLT ONLY DESCRIPTION YORK has

More information

38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT

38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT Concepcion Carrier Air conditioning Company Philippines INSTALLATION, START-UP AND SERVICE INSTRUCTIONS 38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT CONTENTS Safety Considerations 1 Complete

More information

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check

More information

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ)

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ) Technical Guide SUNLINE 2000 SPLIT-SYSTEM EVAPORATOR BLOWER K4EU180 15 NOMINAL TONS (WORLD 50 HZ) DESCRIPTION These completely assembled units include a well-insulated cabinet, a DX cooling coil with copper

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM SECTION 23 81 06 - PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. This Section includes equipment types that contain all the components of the refrigeration process within

More information

30GN FLOTRONIC II AIR-COOLED CHILLERS

30GN FLOTRONIC II AIR-COOLED CHILLERS 30GN-19SB 30GN040-110 FLOTRONIC II AIR-COOLED CHILLERS PERFORMANCE DATA FIELD WIRING DIAGRAM 1998 Carrier Corporation Syracuse, New York 13221 Form 30GN-19SB Supersedes 30GN-6SB, 30GN-7SB, 30GN-8SB, Printed

More information

Modular Supply Make-Up Air Unit

Modular Supply Make-Up Air Unit Modular Supply Make-Up Air Unit Model MSX Flexible Design Factory Assembled Heating Options Hot Water Steam Electric Cooling Options Evaporative Direct Expansion Chilled Water November 2009 Product Features

More information

Product Chillers A P P L I C AT I O N S

Product Chillers A P P L I C AT I O N S Product Chillers A P P L I C AT I O N S Wineries Bottling Product Storage Product Ripening Meat Processing Florist Boxes Packaging Rooms Walk-in Coolers Beverage Boxes CENTURY PRODUCT CHILLERS Unit Configuration

More information

HEATCRAFT. Air-Cooled Condensers Tons. Installation and Maintenance Data. Refrigeration Products. Table of Contents

HEATCRAFT. Air-Cooled Condensers Tons. Installation and Maintenance Data. Refrigeration Products. Table of Contents HEATCRAFT Refrigeration Products Bulletin No. H-INI-65A August 1996 Part Number 90800701 Replaces H-IM-65, March 1994 Angle Leg Models Table of Contents Channel Legs Models Air-Cooled Condensers 21-212

More information

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER 2001927 Prepared by: 860 Douglas Way PO Box 530 Natural Bridge Station, VA 24579 1 1.0 SCOPE: This

More information

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES 60 TON AIR-COOLED CHILLER PA-ACCTR-60 Call us today! (800)341-4297 The 60-Ton portable chiller package features a Trane CGAM chiller unit. Trane leads the industry in providing some of the most reliable,

More information

Call us today! (800)

Call us today! (800) 500 TON AIR-COOLED CHILLER PA-ACCTR-500 Call us today! (800)341-4297 The 500-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

CHS. Product Specifications COMMERCIAL SPLIT SYSTEMS HEAT PUMP UNITS R 410A, 6 10 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

CHS. Product Specifications COMMERCIAL SPLIT SYSTEMS HEAT PUMP UNITS R 410A, 6 10 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE COMMERCIAL SPLIT SYSTEMS HT PUMP UNITS R 410A, 6 10 TONS BUILT TO LAST, SY TO INSTALL AND SERVICE Single stage cooling capacity control on all models All models utilize round copper tube, aluminum plate

More information

Brasch Hazardous Location Unit Heaters

Brasch Hazardous Location Unit Heaters Brasch Hazardous Location Unit Heaters BHUH Features Designed for rugged industrial applications in hazardous locations where the possibility of explosion or fire exists due to the presence of certain

More information

YCAL-SB Millennium AIR COOLED LIQUID CHILLER R407C REFRIGERANT. COOLING CAPACITIES 141 kw to 360 kw

YCAL-SB Millennium AIR COOLED LIQUID CHILLER R407C REFRIGERANT. COOLING CAPACITIES 141 kw to 360 kw YCAL-SB Millennium AIR COOLED LIQUID CHILLER R407C REFRIGERANT COOLING CAPACITIES 141 kw to 360 kw YORK YCAL-SB Millennium air cooled scroll liquid chillers provide chilled liquid for all air conditioning

More information

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical ENGINEERING GUIDE Water-Cooled Self-Contained Units C-Series, Vertical TABLE OF CONTENTS Introduction...2 Product Overview...3 Nomenclature...4 General Data...5 Cooling Performance Data....6 Evaporator

More information

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March GENERAL: 1. This section provides criteria for the design and installation of air handling units. DESIGN GUIDELINES: Design General 1. Location 1.1. For new construction, and existing buildings where possible,

More information

VERTICAL STACK INNKEEPER GUIDE SPECIFICATION CGC Hybrid Heat Pump System

VERTICAL STACK INNKEEPER GUIDE SPECIFICATION CGC Hybrid Heat Pump System VERTICAL STACK INNKEEPER GUIDE SPECIFICATION CGC Hybrid Heat Pump System PART 1 SYSTEM DESCRIPTION 1.1 The HVAC system is based on the CGC HYBRID Hydronic Heat Pump System. 1.2 The system will automatically

More information

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS 15 THROUGH 20 NOMINAL TON HB B-0804

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS 15 THROUGH 20 NOMINAL TON HB B-0804 INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS 15 THROUGH 20 NOMINAL TON CONTENTS GENERAL................................. 3 REFERENCE............................... 3 INSPECTION...............................

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

Air-Cooled Condensers

Air-Cooled Condensers Air-Cooled Condenser Installation & Operation Bulletin No. H-IM-90 February 2017 Part Number 25007301 Replaces H-IM-90, October 2015 Air-Cooled Condensers Installation and Operation Guide Applicable for

More information

PACKAGED AIR COOLED Product Data Catalog

PACKAGED AIR COOLED Product Data Catalog PACKAGED AIR COOLED Product Data Catalog MODELS ASP-10A ASP-15A ASP-20A ASP-00P ASP-00F ASP-00G A MEMBER OF MARDUK HOLDING COMPANY, LLC The Leader in Modular Chillers ETL and CSA Approved CHILLER MODULES

More information

Air-Cooled Split System Condensing Units for Remote DX Coils and Air Handlers. Models RCS 015D to 140D R-410A Refrigerant.

Air-Cooled Split System Condensing Units for Remote DX Coils and Air Handlers. Models RCS 015D to 140D R-410A Refrigerant. Air-Cooled Split System Condensing Units for Remote DX Coils and Air Handlers Models RCS 015D to 140D R-410A Refrigerant Catalog 222-5 Introduction.... 3 The Condensing Unit for Applied Rooftop and Air

More information

YCIV Hz & Hz

YCIV Hz & Hz YCIV 0590-1500 50Hz & 0157-0397 60Hz Start-up Checklist SERVICE POLICY & PROCEDURES Supersedes: Nothing Form 201.23-CL1 (309) Commissioning PREPARATION Commissioning of this unit should only be carried

More information

Call us today! (800)

Call us today! (800) 150 TON AIR-COOLED CHILLER PA-ACCTR-150 Call us today! (800)341-4297 The 150-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information