CENTRIFUGAL LIQUID CHILLERS MODEL YD (STYLE A) R-134A (COOLING ONLY) WITH OPTIVIEW CONTROL CENTER AND ELECTRO-MECHANICAL STARTER R-134A

Size: px
Start display at page:

Download "CENTRIFUGAL LIQUID CHILLERS MODEL YD (STYLE A) R-134A (COOLING ONLY) WITH OPTIVIEW CONTROL CENTER AND ELECTRO-MECHANICAL STARTER R-134A"

Transcription

1 CENTRIFUGAL LIQUID CHILLERS INSTALLATION INSTRUCTION Supersedes: N1 (912) Form N1 (715) MODEL YD (STYLE A) R-134A (COOLING ONLY) WITH OPTIVIEW CONTROL CENTER AND ELECTRO-MECHANICAL STARTER LD08634 R-134A Issue Date: July 31, 2015

2 IMPORTANT! READ BEFORE PROCEEDING! GENERAL SAFETY GUIDELINES FORM N1 This equipment is a relatively complicated apparatus. During rigging, installation, operation, maintenance, or service, individuals may be exposed to certain components or conditions including, but not limited to: heavy objects, refrigerants, materials under pressure, rotating components, and both high and low voltage. Each of these items has the potential, if misused or handled improperly, to cause bodily injury or death. It is the obligation and responsibility of rigging, installation, and operating/service personnel to identify and recognize these inherent hazards, protect themselves, and proceed safely in completing their tasks. Failure to comply with any of these requirements could result in serious damage to the equipment and the property in which it is situated, as well as severe personal injury or death to themselves and people at the site. This document is intended for use by owner-authorized rigging, installation, and operating/service personnel. It is expected that these individuals possess independent training that will enable them to perform their assigned tasks properly and safely. It is essential that, prior to performing any task on this equipment, this individual shall have read and understood the on-product labels, this document and any referenced materials. This individual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in question. SAFETY SYMBOLS The following symbols are used in this document to alert the reader to specific situations: Indicates a possible hazardous situation which will result in death or serious injury if proper care is not taken. Identifies a hazard which could lead to damage to the machine, damage to other equipment and/or environmental pollution if proper care is not taken or instructions and are not followed. Indicates a potentially hazardous situation which will result in possible injuries or damage to equipment if proper care is not taken. Highlights additional information useful to the technician in completing the work being performed properly. External wiring, unless specified as an optional connection in the manufacturer s product line, is not to be connected inside the control cabinet. Devices such as relays, switches, transducers and controls and any external wiring must not be installed inside the micro panel. All wiring must be in accordance with Johnson Controls published specifications and must be performed only by a qualified electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper connections to the controls or application of improper control signals. Failure to follow this warning will void the manufacturer s warranty and cause serious damage to property or personal injury. 2 JOHNSON CONTROLS

3 CHANGEABILITY OF THIS DOCUMENT In complying with Johnson Controls policy for continuous product improvement, the information contained in this document is subject to change without notice. Johnson Controls makes no commitment to update or provide current information automatically to the manual or product owner. Updated manuals, if applicable, can be obtained by contacting the nearest Johnson Controls Service office or accessing the Johnson Controls QuickLIT website at johnsoncontrols.com. It is the responsibility of rigging, lifting, and operating/ service personnel to verify the applicability of these documents to the equipment. If there is any question regarding the applicability of these documents, rigging, lifting, and operating/service personnel should verify whether the equipment has been modified and if current literature is available from the owner of the equipment prior to performing any work on the chiller. CHANGE BARS Revisions made to this document are indicated with a line along the left or right hand column in the area the revision was made. These revisions are to technical information and any other changes in spelling, grammar or formatting are not included. ASSOCIATED LITERATURE MANUAL DESCRIPTION YD Unit Field Reassembly Instructions YD with OptiView Control Center and EMS (Cooling Only) Operating Manual Wiring Diagram YD Unit Installation Checklist and Request for Startup Engineer Service Policy FORM NUMBER NM O PW CL NM1 JOHNSON CONTROLS 3

4 NOMENCLATURE YD XF XA J2 CA A DESIGN LEVEL MODEL EVAPORATOR CODE XF, XH YF, YG, YH, ZF, ZG, ZH AF, AG, AH COMPRESSOR CODE J1, J2, J3, J4, J5 CONDENSER CODE XA, XB, XC, XD, YA, YB, YC, YD, ZA, ZB, ZC, ZD, AA, AB, AC, AD POWER SUPPLY - for 60 Hz 5 for 50 Hz MOTOR CODE 60 Hz 50 Hz CW 5CS CX 5CT CY 5CU CZ 5CV CA 5CW CB 5CX DA 5DA DB 5DB DC 5DC DD 5DD DE 5DE DF 5DF 5DG DH 5DH DJ 5DJ 4 JOHNSON CONTROLS

5 TABLE OF CONTENTS SECTION 1 - INTRODUCTION...7 General...7 Field Assembled Units Only...7 Shipment...7 Inspection Damage Shortage...8 Chiller Data Plate...9 Rigging...9 Location...9 Motors...9 Foundation...9 Clearance...9 Neoprene Isolators Spring Isolators...13 Unit Dimensions...15 Unit Weights...16 Motor Weights and Voltage...16 SECTION 2 - INSTALLATION...17 Rigging Unit To Final Location...17 Locating And Installing Isolator Pads...17 Checking The Isolation Pad Deflection...17 Leveling The Unit...17 Installing Optional Spring Isolators...17 Piping Connections...17 Evaporator And Condenser Water Piping...18 Chilled Water...18 Condenser Water Circuit...18 Stop Valves...20 Flow Switches...20 Drain and Vent Valves...20 Checking Piping Circuits and Venting Air...20 Refrigerant Relief Piping...20 Unit Piping...20 Control Panel Positioning...20 Control Wiring...21 Power Wiring...21 Oil Pump 3 Phase Starter...21 YD Motors (Electro-Mechanical Starter)...21 Insulation...21 Installation Check Request For Start-Up Service...22 Compressor Motor Field Connection Diagram...22 JOHNSON CONTROLS 5

6 LIST OF FIGURES FIGURE 1 - Rigging...10 FIGURE 2 - Neoprene Isolators...11 FIGURE 3 - Neoprene Isolators...12 FIGURE 4 - Spring Isolators...13 FIGURE 5 - Model YD Chiller...14 FIGURE 6 - Dimensions J Compressor Units...15 FIGURE 7 - Schematic of a Typical Piping Arrangement...19 FIGURE 8 - Typical Refrigerant Vent Piping...19 FIGURE 9 - Control Panel Positioning...20 FIGURE 10 - Motor Connections (Electro Mechanical Starter Application)...22 LIST OF TABLES TABLE 1 - Evaporator - Condenser Shell Codes...15 TABLE 2 - Approximate Unit Weight Including Motor...16 TABLE 3 - Approximate Unit Motor Weights...16 TABLE 4 - Motor Connections JOHNSON CONTROLS

7 SECTION 1 - INTRODUCTION 1 GENERAL This instruction describes the installation of a MOD- EL YD Liquid Chilling Unit. This unit is shipped as a single factory assembled, piped, wired package, requiring a minimum of field labor to make chilled water connections, condenser water connections, refrigerant atmospheric relief connections, and electrical power connections. (Refrigerant and oil charges shipped separately unless optional condenser isolation valves are ordered.) Chillers can also be shipped dismantled when required by rigging conditions, but generally it is more economical to enlarge access openings to accommodate the factory assembled unit. Chillers shipped dismantled MUST be field assembled under the supervision of a Johnson Controls representative, but otherwise installation will be as described in this instruction. FIELD ASSEMBLED UNITS ONLY Use Form NM3 in conjunction with this installation instruction. This instruction will be furnished with all units that are to be field assembled. Extra copies may be ordered from the Johnson Controls Publication Distribution Center. The services of a Johnson Controls representative will be furnished to check the installation, supervise the initial start-up and operation of all chillers installed within Continental United States. The Johnson Controls Warranty may be voided if the following restrictions are not adhered to: 1. No valves or connections should be opened under any circumstances because such action will result in loss of the factory nitrogen charge. 2. Do not dismantle or open the chiller for any reason except under the supervision of a Johnson Controls representative. 3. When units are shipped dismantled, notify the nearest Johnson Controls office in ample time for a Johnson Controls representative to supervise rigging the unit to its operating position and the assembly of components. 4. Do not make final power supply connections to the compressor motors or control center. 5. Do not charge the compressors with oil. 6. Do not charge the unit with refrigerant. 7. Do not attempt to start the system. 8. Do not run hot water (110 F / 43 C max) or steam through the evaporator or condenser at any time. SHIPMENT The chiller may be ordered and shipped in any of the following forms: Form 1 Factory Assembled Unit, complete with motor, refrigerant and oil charges. 1. The motor/compressor assembly mounted, with all necessary interconnecting piping assembled. OptiView Control Center is mounted on the unit. Complete unit factory leak tested, evacuated and charged with R-134A. 2. Miscellaneous material Four (4) vibration isolation pads (or optional spring isolators and brackets). Form 2 Factory Assembled Unit, complete with motors (refrigerant and oil charges shipped separately). 1. The motor/compressor assemblies mounted, with all necessary interconnecting piping assembled. OptiView Control Center is mounted on the unit. Complete unit factory leak tested, evacuated and charged with holding charge of nitrogen. 2. Miscellaneous material Four (4) vibration isolation pads (or optional spring isolators and brackets). Form 3 Drivelines Separate From Shells Shipped as three major assemblies. Unit first factory assembled, refrigerant piped, wired and leak tested; then dismantled for shipment. Compressor/motor assemblies removed from shells and skidded. Evaporator/condenser is not skidded. All wiring integral with compressors are left on them, and all conduit is left on shell. All openings on compressors, oil separator, and shells are closed and charged with dry nitrogen (2 to 3 PSIG) (14-21 kpa). Miscellaneous packaging of control center, tubing, water temperature controls, wiring, oil, isolators, solid state starters (option), etc.; refrigerant charge shipped separately. JOHNSON CONTROLS 7

8 SECTION 1 - INTRODUCTION Units shipped dismantled MUST be reassembled by, or under the supervision of, a Johnson Controls representative. (See Form NM3) FORM N1 Units shipped dismantled MUST be reassembled by, or under the supervision of, a Johnson Controls representative. (See Form NM3) Form 7 Split Shells Shipped as four major assemblies. Unit first factory assembled, refrigerant piped, wired and leak tested; then dismantled for shipment. Compressor/motor assemblies removed from shells and skidded. Evaporator and condenser shells are separated at tube sheets and are not skidded. Refrigerant lines between shells are flanged and capped, requiring no welding. All wiring integral with compressors are left on them. All wiring harnesses on shells are removed. All openings on compressors and shells are closed and charged with dry nitrogen (2 to 3 psig) (14-21 kpa). Miscellaneous packaging of control center, tubing, water temperature controls, wiring, oil isolators, solid state starter (option), etc.; refrigerant charge shipped separately. When more than one chiller is involved, the major parts of each unit will be marked to prevent mixing of assemblies. (Piping and Wiring Drawings to be furnished by YORK.) INSPECTION DAMAGE SHORTAGE The unit shipment should be checked on arrival to see that all major pieces, boxes and crates are received. Each unit should be checked on the trailer or rail car when received, before unloading, for any visible signs of damage. Any damage or signs of possible damage must be reported to the transportation company immediately for their inspection. Johnson Controls will not be responsible for any damage in shipment or at job site or loss of parts. (Refer to Shipping Damage Claims, Form NM) Rigging and lifting should only be done by a professional rigger in accordance with a written rigging and lifting plan. The most appropriate rigging and lifting method will depend on job specific factors, such as the rigging equipment available and site needs. Therefore, a professional rigger must determine the rigging and lifting method to be used, and it is beyond the scope of this manual to specify rigging and lifting details. 8 JOHNSON CONTROLS

9 SECTION 1 - INTRODUCTION When received at the job site all containers should be opened and contents checked against the packing list. Any material shortage should be reported to Johnson Controls immediately. (Refer to Shipping Damage Claims, Form NM) CHILLER DATA PLATE A unit data plate is mounted on the control center assembly of each unit, giving unit model number; design working pressure; water passes; refrigerant charge; serial numbers; and motor power characteristics and connection diagrams. Additional information may be found on the motor data plates. This information should be included when contacting the factory on any problem relating to the motor. RIGGING The complete standard chiller is shipped without skids. (When optional skids are used it may be necessary to remove the skids so riggers skates can be used under the unit end sheets to reduce overall height.) Each unit has four (4) lifting holes (two in each end) in the end sheets which should be used to lift the unit. Care should be taken at all times during rigging and handling of the chiller to avoid damage to the unit and its external connections. Lift only using holes shown in Figure 1 on page 10. Do not lift the unit with slings around motor/compressor assemblies or by means of eyebolts in the trapped holes of the compressor motor assemblies. Do not turn a unit on its side for rigging. Do not rig vertically. The rigging and operating weights and overall dimensions are given on pages 6 thru 8 as a guide in determining the clearances required for rigging. Add 6" (15 cm) to overall height for optional skidded unit. The lengthwise rigging bar should be longer than the chiller tube length, and must have counter or clevis adjustments to allow for center of gravity adjustments. Chain spreaders should be used to avoid contact with drive motors or other chiller parts. LOCATION YORK Chillers are furnished with vibration isolator mounts for basement or ground level installations. Units may be located on upper floor levels providing the floor is capable of supporting the total unit operating weight and optional spring isolators are used. MOTORS Sufficient clearance to facilitate normal service and maintenance work must be provided all around and above the unit and particularly space provided at either end to permit cleaning or replacement of evaporator and condenser tubes see CLEARANCE. A doorway or other sufficiently large opening properly located may be used. The chiller should be located in an indoor location where temperatures range from 40 F to 110 F (4.4 C to 43.3 C). The YK open motor is air cooled. Check state, local and other codes for ventilation requirements. FOUNDATION A level floor, mounting pad or foundation must be provided by others, capable of supporting the operating weight of the unit. CLEARANCE Clearances should be adhered to as follows: Rear and above unit 2 ft (61 cm). Front of unit 3 ft (91 cm). Tube Removal 18 ft. (5.5 m) (either end) 1 JOHNSON CONTROLS 9

10 SECTION 1 - INTRODUCTION FORM N1 LD09014a Figure 1 - RIGGING 10 JOHNSON CONTROLS

11 SECTION 1 - INTRODUCTION NEOPRENE ISOLATORS 1 SHELL SHELL DIA. HOLE END SHEET DIA. HOLE END SHEET 5" (127) 10" (254) 5" (127) 10" (254) 8" (203) 8" (203) See Detail A See Detail A 9" (229) Y/Y - Y/Y - Up to 225,000 lbs. (102,060 Kgs) X/X - X/X - Up to 130,000 lbs (58,967 Kgs) Z/Z - Z/Z - Up to 280,000 lbs (127,005 Kgs) A/A - A/A - Up to 280,000 lbs (127,005 Kgs) LD19590 LD19589 Mounting Bracket 3/8 (10) Pad 3/4 (19) LD19571a DETAIL A Figure 2 - NEOPRENE ISOLATORS JOHNSON CONTROLS 11

12 SECTION 1 - INTRODUCTION FORM N1 NEOPRENE ISOLATORS * * B * Typical both ends. LD12643a SHELL CODE UNIT WEIGHT DIM "A" DIM "B" DIM "C" DIM "D" QUANTITY Y - Y Z - Z A - A Up to 190,000 lbs (86,184 Kgs) Up to 240,000 lbs (108,862 Kgs) Up to 240,000 lbs (108,862 Kgs) 12' 9" (3887) Approx weight including motor and 150# compact water boxes. 9" (229) 10" (254) 8 8 x 1" 13' 8" (4166) 11" (279) 10" (254) 8 from edge. 14' 8" (4471) 11" (279) 10" (254) 8 Figure 3 - NEOPRENE ISOLATORS 12 JOHNSON CONTROLS

13 SECTION 1 - INTRODUCTION SPRING ISOLATORS 1 END SHEET SHELL END SHEET SHELL 16 1/4" (413) 3" (76) 6-1/4" (159) CAP SCREW ADJUSTING BOLT CAP SCREW ADJUSTING BOLT 12-SPRING ISOLATORS LD SPRING ISOLATORS LD19591 UNIT WEIGHT x/x - x/x - Up to 115,000 lbs (52,163 Kgs) UNIT WEIGHT Y/Y - Y/Y - Up to 190,000 lbs (86,184 Kgs) Z/Z - Z/Z - Up to 240,000 lbs (108,862 Kgs) A/A - A/A - Up to 240,000 lbs (108,862 Kgs) Figure 4 - SPRING ISOLATORS JOHNSON CONTROLS 13

14 SECTION 1 - INTRODUCTION FORM N1 MOTOR #1 MOTOR #2 COMPRESSOR #2 COMPRESSOR #1 OPTIVIEW CONTROL CENTER EVAPORATOR CONDENSER LD08634 Figure 5 - MODEL YD CHILLER 14 JOHNSON CONTROLS

15 SECTION 1 - INTRODUCTION UNIT DIMENSIONS CONDENSER 1 EVAPORATOR B COMPRESSORS MOTORS M D L C A SHIPPING WIDTH FLOOR LINE J LD mm H F E G Figure 6 - DIMENSIONS J COMPRESSOR UNITS LD09012 Table 1 - EVAPORATOR - CONDENSER SHELL CODES SHELL CODE FT. IN. X-X Y-Y Z-Z A-A A 10'-7-1/2" (3,240) 11'-5" (3,480) 13'-6" (4,115) 14'-6-1/4" (4,426) 15'-5-1/4" (4,705) B 12'-0" (3,658) 12'-0" (3,658) 13'-0" (3,962) 13'-8" (4,166) 14'-2" (4,318) C 2'-8" (813) 2'-8" (813) 3'-5" (1,041) 3'-9" (1,143) 4'-0" (1,219) D 2'-5 1/2" (749) 2'-5 1/2" (749) 2'-11-1/2" (902) 3'-1-1/2" (955) 3'-4" (1,016) E 18'-0" (5,486) 18'-0" (5,486) 18'-0" (5,486) 18'-0" (5,486) 18'-0" (5,486) F 2'-0-3/4" (629) 2'-0-3/4" (629) 2'-1" (635) 2'-3" (686) 2'-3-9/16" (700) G 1'-4-3/4" (425) 1'-4-3/4" (419) 1'-4-1/4" (413) 1'-6-1/4" (464) 1'-6-7/8" (479) H 0'-11-11/16" (297) 0'-11-11/16" (297) 1'-2-5/8" (371) 1'-3-5/8" (397) 1'-4-1/4" (413) J 1'-7-5/8" (498) 1'-7-5/8" (498) 2'-1-1/2" (648) 2'-2" (660) 2'-1" (635) L 5'-1-1/2" (1562) 5'-1-1/2" (1,562) 6'-4 1/2" (1,943) 6'-10-1/2" (2,096) 7'-4" (2,235) NOTES: 1. All dimensions are approximate. Certified dimensions are available on request. 2. For compact water boxes (shown above), determine overall unit length by adding water box depth to tube sheet length. 3. Water nozzles can be located on either end of unit. Add 1/2" to nozzle length for flanges connections. 4. To determine overall height, add dimension "M" for the appropriate isolator type. 5. Use of motors with motor hoods may increase overall unit dimensions. ADDITIONAL OPERATING HEIGHT CLEARANCE TO FLOOR TYPE OF CHILLER MOUNTING FT.-IN. MM Neoprene Pad Isolators 1-3/4" 44 Spring Isolators 1" Deflection 1" 25 Direct Mount 3/4" 19 JOHNSON CONTROLS 15

16 SECTION 1 - INTRODUCTION FORM N1 UNIT WEIGHTS Table 2 - APPROXIMATE UNIT WEIGHT INCLUDING MOTOR SHELLS COMPRESSOR SHIPPING WEIGHT (LBS.) SHIPPING WEIGHT (KGS.) OPERATING WEIGHT (LBS.) OPERATING WEIGHT (KGS.) EST. REFRIGERANT CHARGE (LBS.) EST. REFRIGERANT CHARGE (KGS.) X-X J1, J2 75,000 34,300 94,400 42,800 6,000 2,722 Y-Y J3 116,000 52, ,000 66,364 7,925 3,602 Z-Z J4 136,000 61, ,000 78,182 9,725 4,420 A-A J5 155,000 70, ,000 89,545 10,875 4,943 Refer to product drawings for detailed weight information. MOTOR WEIGHTS AND VOLTAGE Table 3 - APPROXIMATE UNIT MOTOR WEIGHTS MEDIUM VOLTAGE MOTOR CODE WEIGHT WEIGHT MOTOR CODE 60 HZ HP (LBS.) (KGS.) 50 HZ HP WEIGHT (LBS.) WEIGHT (KGS.) CW 655 4,415 2,007 5CS 658 4,640 2,109 CX 690 4,445 2,020 5CT 704 5,800 2,636 CY 740 4,540 2,064 5CU 750 5,800 2,636 CZ 790 4,640 2,109 5CV 800 5,800 2,636 CA 845 5,800 2,636 5CW 850 6,800 3,091 CB 900 5,800 2,636 5CX 900 6,800 3,091 DA ,800 3,091 5DA ,050 3,205 DB ,800 3,091 5DB ,300 3,318 DC ,050 3,205 5DC ,300 3,318 DD ,300 3,318 5DD ,300 3,318 DE ,300 3,318 5DE ,500 3,409 DF ,500 3,409 5DF ,500 3,409 5DG ,900 3,591 DH ,500 3,409 5DH ,250 5,114 DJ ,500 3,864 5DJ ,750 5, JOHNSON CONTROLS

17 SECTION 2 - INSTALLATION RIGGING UNIT TO FINAL LOCATION Rig the unit to its final location on the floor or mounting pad, lift the unit (or shell assembly) by means of an overhead lift and lower the unit to its mounting position. (If optional shipping skids are used, remove them before lowering the chiller to its mounting position.) At this point units shipped dismantled should be assembled under the supervision of a Johnson Controls representative. If evaporator is to be field insulated, the insulation should be applied to the evaporator before the unit is placed in position while the unit is in the lift position. Be sure unit is properly supported. (See Insulation on page 21) LOCATING AND INSTALLING ISOLATOR PADS (Refer to Figure 2 on page 11 and Figure 3 on page 12) The isolator pad mounts are to be located as shown in Figure 2 on page 11 and Figure 3 on page 12. After the isolator pads have been placed into position on the floor, lower the chiller onto the pads. When the unit is in place, remove the rigging equipment and check that the unit is level. The unit should be level within 1/4" (6 mm) from one end to the other end and from front to the rear. If the chiller is not level within the amount specified, lift it and place shims between the isolation pad and the chiller tube sheets. (Shims furnished by the installer.) Lower unit again and recheck to see that it is level. CHECKING THE ISOLATION PAD DEFLECTION All isolation pads should be checked for the proper deflection while checking to see if the unit is level. Each pad should be deflected approximately 0.10 inchs (2.5 mm) to 0.20 inchs (5 mm). If an isolation pad is underdeflected, shims should be placed between the unit tube sheet and the top of the pad to equally deflect all pads. LEVELING THE UNIT The longitudinal alignment of the unit should be checked by placing a level on the top center of the evaporator shell. Transverse alignment should be checked by placing a level on top of the shell end sheets. INSTALLING OPTIONAL SPRING ISOLATORS (Refer to Figure 4 on page 13) When ordered, spring type isolator assemblies will be furnished with the unit. The 4 assemblies are identical and can be placed at any of the 4 corners of the unit. While the unit is still suspended by the rigging, the isolators should be bolted to the unit by inserting the cap screws through the holes in the mounting bracket into the tapped hole in the top of the isolator leveling bolts. Then the unit can be lowered onto the floor. The leveling bolts should now be rotated one (1) turn at a time, in sequence, until the unit end sheets are clear of the floor by the dimension shown in Figure 4 on page 13 and the unit is level. Check that the unit is level, both longitudinally and transversely (see Leveling the Unit). If the leveling bolts are not long enough to level unit due to an uneven or sloping floor or foundation, steel shims (grouted, if necessary) must be added beneath the isolator assemblies as necessary. After the unit is leveled, wedge and shim under each corner to solidly support the unit in this position while piping connections are being made, pipe hangers adjusted and connections checked for alignment. Then the unit is filled with water and checked for leaks. The leveling bolts should now be finally adjusted until the wedges and shims can be removed. The unit should now be in correct level position, clear of the floor or foundation and without any effect from the weight of the piping. PIPING CONNECTIONS After the unit is leveled (and wedged in place for optional spring isolators) the piping connections may be made; chilled water, condenser water and refrigerant relief. The piping should be arranged with offsets for flexibility, and adequately supported and braced independently of the unit to avoid strain on the unit and vibration transmission. Hangers must allow for alignment of pipe. Isolators (by others) in the piping and hangers are highly desirable, and may be required by 2 JOHNSON CONTROLS 17

18 SECTION 2 - INSTALLATION specifications, in order to effectively utilize the vibration isolation characteristics of the vibration isolation mounts of the unit. Check for piping alignment Upon completion of piping, a connection in each line as close to the unit as possible should be opened, by removing the flange bolts or coupling and checked for piping alignment. If any of the bolts are bound in their holes, or if the connection springs are out of alignment, the misalignment must be corrected by properly supporting the piping or by applying heat to anneal the pipe. If the piping is annealed to relieve stress the inside of the pipe must be cleaned of scale before it is finally bolted in place. EVAPORATOR AND CONDENSER WATER PIPING The evaporator and condenser liquid heads of chiller have nozzles which are grooved, suitable for welding 150 psig DWP flanges or the use of Victaulic couplings. Factory mounted flanges are optional. The nozzles and water pass arrangements are furnished in accordance with the job requirements (see Product Drawings) furnished with the job. Standard units are designed for 150 psig DWP on the water side. If job requirements are for greater than 150 psig DWP, check the unit data plate before applying pressure to evaporator or condenser to determine if the chiller has provisions for the required DWP. Inlet and outlet connections are identified by labels placed adjacent to each nozzle. Chilled Water FORM N1 Foreign objects which could lodge in, or block flow through, the evaporator and condenser tubes must be kept out of the water circuit. All water piping must be cleaned or flushed before being connected to the chiller pumps, or other equipment. Permanent strainers (supplied by others) are required in both the evaporator and condenser water circuits to protect the chiller as well as the pumps, tower spray nozzles, chilled water coils and controls, etc. The strainer must be installed in the entering chilled water line, directly upstream of the chiller. Water piping circuits should be arranged so that the pumps discharge through the chiller, and should be controlled as necessary to maintain essentially constant chilled and condenser water flows through the unit at all load conditions. If pumps discharge through the chiller, the strainer may be located upstream from pumps to protect both pump and chiller. (Piping between strainer, pump and chiller must be very carefully cleaned before start-up.) If pumps are remotely installed from chiller, strainers should be located directly upstream of the chiller. Condenser Water Circuit For proper operation of the unit, condenser refrigerant pressure must be maintained above evaporator pressure. If operating conditions will fulfill this requirement, no attempt should be made to control condenser water temperature by means of automatic valves, cycling of the cooling tower fan or other means, since chillers are designed to function satisfactorily and efficiently when condenser water is allowed to seek its own temperature level at reduced loads and off-peak seasons of the year. However, if entering condenser water temperature can go below the required minimum, (refer to O2) condenser water temperature must be maintained equal to or slightly higher than the required minimum. Refer to Figure 7 on page 19 for typical water piping schematic. 18 JOHNSON CONTROLS

19 SECTION 2 - INSTALLATION 2 EVAPORATOR Figure 7 - SCHEMATIC OF A TYPICAL PIPING ARRANGEMENT LD08529 OIL PUMP HOUSING Figure 8 - TYPICAL REFRIGERANT VENT PIPING LD09021 JOHNSON CONTROLS 19

20 SECTION 2 - INSTALLATION FORM N1 Stop Valves Stop valves may be provided (by others) in the evaporator and condenser water piping adjacent to the unit to facilitate maintenance. Thermometer wells and pressure taps should be provided (by others) in the piping as close to the unit as possible to facilitate operating check. Flow Switches Thermal type water flow switches are factory mounted in the chilled and condensed water nozzles and are factory wired to the OptiView control panel. These solidstate flow sensors have a small internal heating element and use the cooling effect of the flowing fluid to sense when an adequate flow rate has been established. Drain and Vent Valves Drain and vent valves (by others) should be installed in the connections provided in the evaporator and condenser liquid heads. These connections may be piped to drain if desired. Checking Piping Circuits and Venting Air After the water piping is completed, but before any water box insulation is applied. Tighten and torque to maintain between 30 and 60 ft. lbs. (41 and 81 N m) the nuts on the liquid head flanges. Gasket shrinkage and handling during transit cause nuts to loosen. If water pressure is applied before tightening is done, the gaskets may be damaged and have to be replaced. Fill the chilled and condenser water circuits, operate the pumps manually and carefully check the evaporator and condenser water heads and piping for leaks. Repair leaks as necessary. Before initial operation of the unit both water circuits should be thoroughly vented of all air at the high points. REFRIGERANT RELIEF PIPING Each unit is equipped with pressure relief valves located on the condenser, on the evaporator, and on the oil pump housing for the purpose of quickly relieving excess pressure of the refrigerant charge to the atmosphere as a safety precaution in case of an emergency, such as fire. line must include a dirt trap in the vertical leg to intercept and permit clean out and to trap any vent stack condensation. The piping MUST be arranged to avoid strain on the relief valves, using a flexible connection, if necessary. UNIT PIPING Compressor lubricant piping and system external piping are factory installed on all units shipped assembled. On units shipped dismantled, the following piping should be completed under the supervision of the Johnson Controls representative: (1) the lubricant piping to oil sump and oil evaporator and system oil return connections using material furnished. See Form NM3. CONTROL PANEL POSITIONING (See Figure 9 on page 20) The OptiView Control Center is placed in a position above the evaporator for shipping. To move the control center into position for operation, proceed as follows: 1. While supporting the control center, remove the hardware between the support arms and the evaporator. 2. Swing the control center into a vertical position. 3. Slide the control center down the guide rails to the proper position. Tighten securely. 4. Discard unused hardware. Control Wiring SUPPORT ARMS PANEL TRACK Refrigerant relief vent piping (by others), from the relief valves to the outside of the building, is required by code in most areas and should be installed on all chillers. The vent line should be sized in accordance with the ANSI/ASHRAE-15, or local code. The vent Figure 9 - CONTROL PANEL POSITIONING LD JOHNSON CONTROLS

21 SECTION 2 - INSTALLATION CONTROL WIRING On units shipped disassembled, after installation of the control center, control wiring must be completed between unit components and control center, solid state starter, or variable speed drive, when used, using wiring harness furnished. Refer to Form N3. Field wiring connections for commonly encountered control modifications (by others) if required, are shown on Form PW1. POWER WIRING No deviations in unit wiring from that shown on drawings furnished shall be made without prior approval of the Johnson Controls representative. Oil Pump 3 Phase Starter Separate wiring or a fused disconnect switch should be supplied by the installer and connected to the variable speed oil pump panel. DO NOT make final power connections to the chiller until approved by a Johnson Controls representative. Remote Electro-Mechanical starters for the chiller must be furnished in accordance with Johnson Controls Standard (Product Drawing Form PA5.1) to provide the features necessary for the starter to function properly with the YORK control system. Each chiller unit is furnished for a specific electrical power supply as stamped on the Unit Data Plate, which also details the motor connection diagrams. To insure proper motor rotation the starter power input and starter to motor connections must be check with a phase sequence indicator in the presence of the Johnson Controls representative. YD Motors (Electro-Mechanical Starter) Figure 10 on page 22 shows the power wiring hookup for Motor Connections. (Refer to Wiring Labels in Motor Terminal Box for hook-up to suit motor voltage and amperage.) Motor leads are furnished with a crimp type connection having a clearance hole for a 3/8" bolt, motor terminal lugs are not furnished. The YD Chiller has two motors which must be connected to the proper starter. When viewed from the chiller control panel, motor #1 is on the left and motor #2 is on the right. INSULATION (See Product Drawings Form PA1) DO NOT field insulate until the unit has been leak tested under the supervision of a Johnson Controls representative. Insulation of the type specified for the job, or minimum thickness to prevent sweating of 30 F (-1 C) surfaces should be furnished (by others) and applied to the evaporator shell, end sheets, liquid feed line to flow chamber, compressor suction connection, and evaporator liquid heads and connections. The liquid head flange insulation must be removable, to allow head removal for the tube maintenance. Details of areas to be insulated are given on the Product Drawing. Units are furnished factory anti-sweat insulated on order at additional cost. This includes all low temperature surfaces except the two (2) cooler liquid heads. DO NOT cut wires to final length or make final connections to motor terminals or starter power input terminals until approved by the Johnson Controls representative. JOHNSON CONTROLS 21

22 INSTALLATION CHECK REQUEST FOR START-UP SERVICE The services of a Johnson Controls representative will be furnished to check the installation and supervise the initial start-up and operation on all chillers installed within the Continental United States. After the unit is installed, piped and wired as described in this Instruction, but before any attempt is made to start the unit, the Johnson Controls District Office should be advised so that the start-up service, included in the contract price, can be scheduled. Notification to the Johnson Controls office should be by means of Installation Check List and Request, Form CL1, in triplicate. Table 4 - MOTOR CONNECTIONS 3 PHASE MOTOR VOLTAGE 50 / 60 HZ MOTOR RATED LOAD AMPS CT RADIO 200:1 350:1 700:1 1400: A A A A NOTES: C A A B A 1. Requires passing motor lead thru current transformer (CT) once before connecting to power supply. 2. Requires passing motor lead thru CT twice before connecting to power supply. 3. Requires passing motor lead thru CT three times before connecting to power supply COMPRESSOR MOTOR FIELD CONNECTION DIAGRAM LD00710 Figure 10 - MOTOR CONNECTIONS (ELECTRO MECHANICAL STARTER APPLICATION) 22 JOHNSON CONTROLS

23 NOTES JOHNSON CONTROLS 23

24 P.O. Box 1592, York, Pennsylvania USA Subject to change without notice. Printed in USA Copyright by Johnson Controls ALL RIGHTS RESERVED Form N1 (715) Issue Date: July 31, 2015 Supersedes: N1 (912)

FIELD RE-ASSEMBLY FOR FORM 3 AND FORM 7 SHIPMENT MODEL YD CHILLERS - MOD A AND B WITH GRAPHIC CONTROL CENTER AND ELECTRO-MECHANICAL STARTER

FIELD RE-ASSEMBLY FOR FORM 3 AND FORM 7 SHIPMENT MODEL YD CHILLERS - MOD A AND B WITH GRAPHIC CONTROL CENTER AND ELECTRO-MECHANICAL STARTER CENTRIFUGAL LIQUID CHILLERS INSTALLATION INSTRUCTIONS Supersedes: 160.69-NM3 (912) Form 160.69-NM3 (715) FIELD RE-ASSEMBLY FOR FORM 3 AND FORM 7 SHIPMENT MODEL YD CHILLERS - MOD A AND B WITH GRAPHIC CONTROL

More information

MODEL YK M3 M3 G4 THRU YK S6 S4 J2 (STYLE C) R-22 (COOLING ONLY) MODEL YK LB LB G4 THRU YK SE SC J4 (STYLE C) R-134a (COOLING ONLY)

MODEL YK M3 M3 G4 THRU YK S6 S4 J2 (STYLE C) R-22 (COOLING ONLY) MODEL YK LB LB G4 THRU YK SE SC J4 (STYLE C) R-134a (COOLING ONLY) MILLENNIUM TM CENTRIFUGAL LIQUID CHILLERS INSTALLATION INSTRUCTIONS Supersedes: Nothing 1296 FORM 160.49-N5 MODEL YK M3 M3 G4 THRU YK S6 S4 J2 (STYLE C) R-22 (COOLING ONLY) MODEL YK LB LB G4 THRU YK SE

More information

CENTRIFUGAL LIQUID CHILLERS YMC 2 MODEL A WITH OPTIVIEW CONTROL CENTER. R-134a. INSTALLATION Supersedes: N1 (611) Form N1 (512) LD14000

CENTRIFUGAL LIQUID CHILLERS YMC 2 MODEL A WITH OPTIVIEW CONTROL CENTER. R-134a. INSTALLATION Supersedes: N1 (611) Form N1 (512) LD14000 CENTRIFUGAL LIQUID CHILLERS INSTALLATION Supersedes: 160.78-N1 (611) Form 160.78-N1 (512) YMC 2 MODEL A WITH OPTIVIEW CONTROL CENTER LD14000 R-134a Issue Date: May 30, 2012 IMPORTANT! READ BEFORE PROCEEDING!

More information

MODELS STEAM YIA-ST-1A1 THRU YIA-ST-14F3 HOT WATER YIA-HW-1A1 THRU YIA-HW-14F3

MODELS STEAM YIA-ST-1A1 THRU YIA-ST-14F3 HOT WATER YIA-HW-1A1 THRU YIA-HW-14F3 ABSORPTION CHILLERS WITH BUFFALO PUMPS INSTALLATION INSTRUCTIONS Supersedes: 155.16-N3 (904) Form 155.16-N3 (413) MODELS STEAM YIA-ST-1A1 THRU YIA-ST-14F3 HOT WATER YIA-HW-1A1 THRU YIA-HW-14F3 LD09451

More information

MODEL YST UNITS MANUFACTURED AFTER DECEMBER 2006

MODEL YST UNITS MANUFACTURED AFTER DECEMBER 2006 STEAM TURBINE CENTRIFUGAL LIQUID CHILLERS INSTALLATION INSTRUCTIONS Supersedes: 160.67-N2 (1109) Form 160.67-N2 (114) MODEL YST UNITS MANUFACTURED AFTER DECEMBER 2006 LD12189 Issue Date: January 10, 2014

More information

MODEL YK (STYLE G) R-134a or R-531A WITH OPTIVIEW CONTROL CENTER FOR ELECTRO-MECHANICAL STARTER, SOLID STATE STARTER AND VARIABLE SPEED DRIVE

MODEL YK (STYLE G) R-134a or R-531A WITH OPTIVIEW CONTROL CENTER FOR ELECTRO-MECHANICAL STARTER, SOLID STATE STARTER AND VARIABLE SPEED DRIVE CENTRIFUGAL LIQUID CHILLERS INSTALLATION INSTRUCTIONS Supersedes: 160.75-N1 (715) Form 160.75-N1 (1217) ODEL YK (STYLE G) R-134a or R-531A WITH OPTIVIEW CONTROL CENTER FOR ELECTRO-ECHANICAL STARTER, SOLID

More information

Water-Cooled Dual Compressor Screw Chiller

Water-Cooled Dual Compressor Screw Chiller Installation Manual IM 692-1 Group: Chiller Part Number: 629955 Effective: May 1997 Supersedes: IM663-1 IM683 IM692 Water-Cooled Dual Compressor Screw Chiller Installation Manual PFS 155C through PFS 210C,

More information

INSTALLATION, OPERATION, MAINTENANCE Supersedes: ICOM2 (1216) Form ICOM2 (318)

INSTALLATION, OPERATION, MAINTENANCE Supersedes: ICOM2 (1216) Form ICOM2 (318) MODEL YVWA DUAL COMPRESSOR 50 HZ AND 60 HZ 200-300 TONS 703-1055 KW WATER-COOLED SCREW LIQUID CHILLERS INSTALLATION, OPERATION, MAINTENANCE Supersedes: 201.30-ICOM2 (1216) Form 201.30-ICOM2 (318) 035 23322

More information

WATER-COOLED SCREW LIQUID CHILLERS. MODEL YVWA Dual Compressor 50 Hz and 60 Hz Tons kw. R-134a. Issue Date: April 30, 2015

WATER-COOLED SCREW LIQUID CHILLERS. MODEL YVWA Dual Compressor 50 Hz and 60 Hz Tons kw. R-134a. Issue Date: April 30, 2015 WATER-COOLED SCREW LIQUID CHILLERS INSTALLATION, OPERATION, AND MAINTENANCE Supersedes: 201.30-ICOM2 (113) Form 201.30-ICOM2 (415) MODEL YVWA Dual Compressor 50 Hz and 60 Hz 200-300 Tons 703-1055 kw 035

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions 38AH044-134 Air-Cooled Condensing Units 50/60 Hz Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................

More information

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer 5/16 Rev. A 57-02509 2 Contents INTRODUCTION... 4 WARNING LABELS AND SAFETY INSTRUCTIONS... 5 PS SERIES PARALLEL

More information

Installation Manual IM

Installation Manual IM Installation Manual IM 1128-1 Group: Chiller Part Number: 331375601 REV: 01 Effective: April 2012 Supersedes: February 2012 WSC, WME and WMC-B Centrifugal Chillers Reassembly of Knockdown Shipments COMPRESSOR

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS PART 0 A/E INSTRUCTIONS 0.01 Design Requirements A. Pumping system design 1. A primary-secondary pumping system is preferred. Redundant pipes are required for chillers and boilers. 2. Select pumps to operate

More information

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME: Supersedes: 201.28-CL2 (817) Form 201.28-CL2 (1017) MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: PHONE: JOB NAME: CUSTOMER ORDER NO: JCI CONTRACT NO: CHILLER MODEL

More information

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13 R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.

More information

Installation Instructions Part No , Part No Part No

Installation Instructions Part No , Part No Part No Torsion-Flex Motor mount for PSC motors and Rigid-Mount for ECM motors Replacement Kit Cancels: New Installation Instructions Part No. 327752-401, Part No. 327753-401 Part No. 327754-401 IIK-310A-45-11

More information

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC!

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC! COIL Manufacturing Inc. When you want Quality, specify COLMAC! Installation, Operation, and Maintenance ENG00018621 Rev A Air Cooled Fluid Coolers Contents 1. SAFETY INSTRUCTIONS... 1 2. MODEL NOMECLATURE...

More information

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811 Description These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of Refrigerant R-410A for storage

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions 38AH044-134 Air-Cooled Condensing Units 50/60 Hz Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................

More information

THERMAPHASE INSTALLATION AND OPERATING INSTRUCTIONS

THERMAPHASE INSTALLATION AND OPERATING INSTRUCTIONS Page 1 of 10 THERMAPHASE INSTALLATION AND OPERATING INSTRUCTIONS Purpose of Manual The purpose of this manual is to provide operating, servicing and repair instructions for the Summit standard models ThermaPhase

More information

SECTION STEAM CONDENSATE PUMPS

SECTION STEAM CONDENSATE PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 22 23 STEAM CONDENSATE PUMPS SPEC WRITER NOTES: 1. Delete between // ---- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

Installation, Operation, and Maintenance

Installation, Operation, and Maintenance Installation, Operation, and Maintenance Series E CVHH Water-Cooled CenTraVac Chillers With Tracer AdaptiView Control Model: CVHH X39641257003 SAFETY WARNING Only qualified personnel should install and

More information

Model REAC / SEAC Self Contained Cooling / Electric Heating Units

Model REAC / SEAC Self Contained Cooling / Electric Heating Units Model REAC / SEAC Self Contained Cooling / Electric Heating Units Supersedes: 145.30-IOM1 (708) Form 145.30-IOM1 (908) UNIT MODELS REAC / SEAC - R22 ELECTRIC HEATING / ELECTRIC COOLING INSTALLATION, OPERATION

More information

CENTRIFUGAL LIQUID CHILLERS YMC 2 MODEL A WITH OPTIVIEW CONTROL CENTER. R-134a in

CENTRIFUGAL LIQUID CHILLERS YMC 2 MODEL A WITH OPTIVIEW CONTROL CENTER. R-134a in CENTRIFUGAL LIQUID CHILLERS OPERATIONS AND MAINTENANCE Supersedes: 160.78-O1 (1112) Form 160.78-O1 (417) YMC 2 MODEL A WITH OPTIVIEW CONTROL CENTER 8.1415 in LD14000 R-134a Issue Date: April 28, 2017 IMPORTANT!

More information

IOM Installation, Operation, and Maintenance Manual. Magnitude Magnetic Bearing Centrifugal Chillers

IOM Installation, Operation, and Maintenance Manual. Magnitude Magnetic Bearing Centrifugal Chillers Installation, Operation, and Maintenance Magnitude Magnetic Bearing Centrifugal Chillers IOM 1033-5 Group: Chiller Part Number: IOM1033 Date: October 2016 Supercedes: November 2012 Model WME 400 to 700

More information

Guide Specifications

Guide Specifications Guide Specifications Hot Water fired Adsorption Liquid Chillers Bry-Air Adsorption Chiller Overview The chiller shall be a Bry-Air ADC series. The chiller shall consist of a robust, compact, packaged chiller

More information

SECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

SECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower SECTION 15682 CENTRIFUGAL WATER CHILLERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15540 - Pumping Equipment (HVAC) 3. 15711 - Induced Draft Cooling Tower B. Removal

More information

Installation, Operation, and Maintenance

Installation, Operation, and Maintenance Installation, Operation, and Maintenance Series E CDHH Water-Cooled CenTraVac Chillers With Tracer AdaptiView Control Model: CDHH X39641258004 SAFETY WARNING Only qualified personnel should install and

More information

ISOLATED DIRECT DRIVE PLENUM FAN (IDDP)

ISOLATED DIRECT DRIVE PLENUM FAN (IDDP) Our Expertise, Your Air-Moving Solution ISOLATED DIRECT DRIVE PLENUM FAN (IDDP) PART# 0601710001_rev_A INSTALLATION, OPERATION & MAINTENANCE MANUAL Please read and save these instructions for future reference.

More information

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL The LA/LB line is a flexible performer. LA300, LB360 & 480 can be

More information

INTRODUCTION. NOTE: Read the entire instruction manual before starting the installation. FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD

INTRODUCTION. NOTE: Read the entire instruction manual before starting the installation. FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD Installation Instructions NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance, or use can

More information

.2 Section Waste Management and Disposal.

.2 Section Waste Management and Disposal. Issued 2005/06/01 Section 15624 Packaged Rotary Screw Water Chillers Page 1 of 5 PART 1 General 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

CS 2. Central Station Air Handlers Double Wall & Single Wall Installation, Operation & Maintenance Manual. Form No. 6120A

CS 2. Central Station Air Handlers Double Wall & Single Wall Installation, Operation & Maintenance Manual. Form No. 6120A CS 2 Central Station Air Handlers Double Wall & Single Wall Installation, Operation & Maintenance Manual Form No. 6120A TABLE OF CONTENTS Page Inspection... 2 Shipment of Units... 2 Handling... 2 Installation...

More information

Installation Instructions

Installation Instructions 40MBFQ Floor Console Ductless System Sizes 09 to 12 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 DIMENSIONS... 5 CLEARANCES... 5

More information

Installation Instructions

Installation Instructions AQUAFORCE 30XW150-400 Water-Cooled Liquid Chillers Installation Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INTRODUCTION.................................1,2 System Design...................................

More information

Water-Cooled Scroll Compressor Chillers

Water-Cooled Scroll Compressor Chillers Installation, and Maintenance Manual IMM WGZ-2 Group: Chiller Part Number: 331374401 Effective: October 2005 Supercedes: IOMM WGZ-1 Water-Cooled Scroll Compressor Chillers WGZ 030AW To WGZ 120AW, Packaged

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

Single Package Vertical R-410A A/C & H.P. UNIT MODELS VPC-B, VPP-B, & VPH-B INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

Single Package Vertical R-410A A/C & H.P. UNIT MODELS VPC-B, VPP-B, & VPH-B INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS Single Package Vertical R-410A A/C & H.P. Supersedes: 145.19-IOM1 (708) Form 145.19-IOM1 (908) UNIT MODELS VPC-B, VPP-B, & VPH-B INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS Unit Model VPC-B R-410A

More information

KR Series Air Defrost Unit Coolers Operating and Installation Manual

KR Series Air Defrost Unit Coolers Operating and Installation Manual KR Series Air Defrost Unit Coolers Operating and Installation Manual KR Air Defrost Unit Coolers (PN E108317_L) TABLE OF CONTENTS 1 RECEIPT OF EQUIPMENT... 2 1.1 INSPECTION... 2 1.2 LOSS OF GAS HOLDING

More information

SPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing N4C-0500

SPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing N4C-0500 SPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing 550.23-N4C-0500 MODEL L*BC240 035-16603 GENERAL This 20 ton evaporator blower is designed with two distinct modules

More information

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check for any interior and exterior damage, and

More information

Water-Cooled Scroll Compressor Chillers

Water-Cooled Scroll Compressor Chillers Installation, Operation and Maintenance Manual IOMM WGZ-1 Group: Chiller Part Number: 330389301 Effective: October 2004 Supercedes: IOMM WGZ Water-Cooled Scroll Compressor Chillers WGZ 030AW To WGZ 100AW,

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance Series R Air-Cooled Helical Rotary Liquid Chiller RTAD 085-180 (50Hz) Standard, Free Cooling and Heat Recovery models RTAD-SVX01F-E4 General information Foreword These

More information

IOM Installation, Operation, and Maintenance Manual. Magnitude Magnetic Bearing Centrifugal Chillers

IOM Installation, Operation, and Maintenance Manual. Magnitude Magnetic Bearing Centrifugal Chillers Installation, Operation, and Maintenance Manual Magnitude Magnetic Bearing Centrifugal Chillers IOM 1210-3 Group: Chiller Part Number: IOM1210-3 Date: June 2016 Model WMC, C Vintage 125 to 400 Tons (440

More information

"S" SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S12 S16

S SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S12 S16 Webster Pumps "S" SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S12 S16 PLEASE READ THE FOLLOWING INFORMATION PRIOR TO INSTALLING AND USING Webster PUMPS or HAYWARD VALVES,

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

Installation Owner Diagnostics

Installation Owner Diagnostics Installation Owner Diagnostics Split System Cooling Condensers Model CTA 7 1/2 to 15 Tons Models A and later Design Sequence CTA 090A***A 60 HZ 120A***A 60 HZ 120B***A 60 HZ 180B***A 60 HZ SS-SVN11A-EN

More information

Armstrong J Series Float, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual

Armstrong J Series Float, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual Armstrong J Series, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual This bulletin should be used by experienced personnel as a guide to the installation

More information

40 RM/RMS Packaged Air-Handling Units

40 RM/RMS Packaged Air-Handling Units ConcepcionCarrier Air conditioning Company Philippines 40 RM/RMS 008034 Packaged AirHandling Units INSTALLATION MANUAL, STARTUP & SERVICE INSTRUCTIONS Contents Page Page Safety Considerations 1 40RM Physical

More information

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO: Supersedes: (316) Form QTC4-CL2 (617) MODEL QTC4 EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: ADDRESS: PHONE: JOB NAME: LOCATION: CUSTOMER ORDER NO: TEL NO: ORDER NO: CONTRACT NO: CHILLER MODEL

More information

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check

More information

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW INSTALLATION INSTRUCTIONS RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW 92-106595-01-00 TABLE OF CONTENTS Introduction.......................................

More information

Operation & Maintenance Manual

Operation & Maintenance Manual (Vertical Model) Semi-Instantaneous Water Heater Steam to Water Design Manual # 9636-0550 Rev. C Operation & Maintenance Manual 340 West 8 th Street Peru, IN 46970 PH: 765-472-3351 FX: 765-472-3968 www.thrushco.com

More information

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check

More information

Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers

Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers Bulletin 1200/4 (Revised 5/12) Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers INNOVATORS IN HEAT TRANSFER I. INSTALLATION OF HEAT EXCHANGERS A. HEAT EXCHANGER SETTINGS 1)

More information

MODELS B1PA024, 030 AND 036

MODELS B1PA024, 030 AND 036 STELLAR 2000 SINGLE PACKAGE HEAT PUMPS INSTALLATION INSTRUCTION Supersedes: 511.26-N1Y (892) 511.26-N1Y (893) MODELS B1PA024, 030 AND 036 035-11622 GENERAL YORK Model B1PA units are factory assembled heat

More information

RCF Closed Circuit Cooling Towers RCC Evaporative Condensers

RCF Closed Circuit Cooling Towers RCC Evaporative Condensers RCF RCC RCT RCF Closed Circuit Cooling Towers RCC Evaporative Condensers ASSEMBLY & RIGGING INSTRUCTIONS RCF Closed Circuit Cooling Towers and RCC Evaporative Condensers should be rigged and assembled

More information

Installation Instructions

Installation Instructions . AquaSnap 30MPA,MPW015-071 Liquid Chillers with Scroll Compressors and ComfortLink Controls 50/60 Hz Installation Instructions CONTENTS Page GENERAL........................................ 1 SAFETY CONSIDERATIONS.....................1,2

More information

Installation Instructions

Installation Instructions Installation Instructions Disassembly and Reassembly Units CVHH and CDHH Water-Cooled CenTraVac Chillers Models: CVHH, CDHH X39641259002 SAFETY Only qualified personnel should install and service the equipment.

More information

Model CPH Horizontal Water-Cooled Air Conditioning Unit

Model CPH Horizontal Water-Cooled Air Conditioning Unit Model CPH Horizontal Water-Cooled Air Conditioning Unit Supersedes: 145.14-IOM1 (708) Form 145.14-IOM1 (908) MODEL CPH 060, 096, 120 HORIZONTAL WATER-COOLED AIR CONDITIONING UNITS INSTALLATION & OPERATION

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS CPA INSTALLATION INSTRUCTIONS General: Please read the following instructions before attempting to rig or install EVAPCO CPA critical process air units. The CPA Series of units can be a complicated piece

More information

SECTION ROTARY SCREW WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

SECTION ROTARY SCREW WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower SECTION 15684 ROTARY SCREW WATER CHILLERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15540 - Pumping Equipment (HVAC) 3. 15711 - Induced Draft Cooling Tower B.

More information

Air-Cooled Fluid Cooling Units (P/N E R2)

Air-Cooled Fluid Cooling Units (P/N E R2) Fluid Cooler Series Air-Cooled Fluid Cooling Units Operating and Installation Manual Air-Cooled Fluid Cooling Units (P/N E208134 R2) TABLE OF CONTENTS 1 RECEIPT OF EQUIPMENT 3 1.1 INSPECTION 3 1.2 LOSS

More information

Daikin Direct Expansion (DX) Cooling Coils

Daikin Direct Expansion (DX) Cooling Coils Installation and Maintenance Manual IM 902 Daikin Direct Expansion (DX) Cooling Coils Group: Applied Air Part Number: IM 902 Date: February 2008 Types EN, EF, ER, EJ, EK 2008 Daikin Applied Contents Introduction...

More information

568X, 587X, 588X Series

568X, 587X, 588X Series Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

Water-Cooled Modular Chillers. Product Data Catalog. Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X

Water-Cooled Modular Chillers. Product Data Catalog. Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X Product Data Catalog Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X Variable Speed Total Access Modules MS010W, MS020W, MS030W, MS050W MS010V, MS020V,

More information

Installation Instructions

Installation Instructions 40MAQ High Wall Ductless Split System Sizes 09 to 36 Installation Instructions NOTE: Read the entire instruction manual before starting the installation TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS

More information

Installation Instructions

Installation Instructions Installation Instructions Centrifugal liquid chillers are designed to provide safe and reliable service when operated within design specifications. When operating this equipment, use good judgment and

More information

BuildingName The Description of the Project P DOCUMENTS

BuildingName The Description of the Project P DOCUMENTS ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION

More information

YCIV Hz & Hz

YCIV Hz & Hz YCIV 0590-1500 50Hz & 0157-0397 60Hz Start-up Checklist SERVICE POLICY & PROCEDURES Supersedes: Nothing Form 201.23-CL1 (309) Commissioning PREPARATION Commissioning of this unit should only be carried

More information

Product Data. Features/Benefits. 19XB Positive Pressure Storage System

Product Data. Features/Benefits. 19XB Positive Pressure Storage System Product Data 19XB Positive Pressure Storage System 19XB028 Copyright 1992 Carrier Corporation 19XB052 Carrier s Positive Pressure Storage (PPS) System ensures the critical conservation of refrigerants

More information

Single Package Vertical R-22 A/C & HP UNIT MODELS VPC, VPP, & VPH INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

Single Package Vertical R-22 A/C & HP UNIT MODELS VPC, VPP, & VPH INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS Single Package Vertical R-22 A/C & HP Supersedes: 145.20-IOM1 (708) Form 145.20-IOM1 (908) UNIT MODELS VPC, VPP, & VPH INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS Unit Model VPC R-22 Single Packaged

More information

Installation Instructions

Installation Instructions 40MBFQ Floor Console Ductless System Sizes 09 to 58 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 WIRING... 4 DIMENSIONS... 5 CLEARANCES...

More information

Installation, Operation, and Maintenance Information

Installation, Operation, and Maintenance Information Installation, Operation, and Maintenance Information Air Cooled Condensers 8-2016 Rev 0 Table of Contents General Safety Information 2 Inspection 2 Installation 2 6 Rigging and Assembly 2 Unit Location

More information

MODELS W1LC220, 260 AND 320 STYLE B

MODELS W1LC220, 260 AND 320 STYLE B LIQUID CHILLER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: 570.05-NY (494) 570.05-N3Y (495) MODELS WLC0, 60 AND 30 STYLE B 035-3053 Only -5 and -46 voltage codes GENERAL YORK s WLC Packaged Air-Cooled

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703 TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.

More information

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program. 15682 CENTRIFUGAL WATER CHILLERS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 236416 An optional

More information

Always keep this manual in a safe readily accessible location. MODEL SERIAL SERVICE COMPANY TELEPHONE NUMBER

Always keep this manual in a safe readily accessible location. MODEL SERIAL SERVICE COMPANY TELEPHONE NUMBER Always keep this manual in a safe readily accessible location. MODEL SERIAL SERVICE COMPANY TELEPHONE NUMBER For Operating Instructions or Technical Support Call 1-507-886-6666 Last Revision: 1/31/12 Starting

More information

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS 550.23-TG5Y (893) CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L2EU240 20 NOMINAL TONS DESCRIPTION This 20 ton evaporator blower is designed with two distinct modules to provide maximum application flexibility.

More information

TECHNICAL INSTRUCTIONS

TECHNICAL INSTRUCTIONS TID-0004_0A TECHNICAL INSTRUCTIONS Hardware Procedure: Coil and Riser Replacement Procedures for All Styles of A, B, C, and D Indirect-Fired Water Heaters Applies to: Indirect-Fire Water Heaters. Description

More information

Installation Instructions

Installation Instructions 38MHR Outdoor Unit Single Zone Ductless System Sizes 09 to 24 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. NOTE: Images are for illustration purposes

More information

Installation Instructions

Installation Instructions Installation Instructions Cased Horizontal Furnace Coil CK3B A96318 Fig. 1 Model CK3B Furnace Coil NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper

More information

Installation Instructions

Installation Instructions 30GTN015-035 Reciprocating Liquid Chillers with ComfortLink Controls 50/60 Hz Installation Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION.................................1-11

More information

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. Condensate Return Systems General Installation, Operation, & Service Instructions !

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. Condensate Return Systems General Installation, Operation, & Service Instructions ! Condensate Return Systems General Installation, Operation, & Service Instructions INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. SAFETY INSTRUCTIONS This safety alert symbol will be used in this

More information

APPLICATION DATA SHEET

APPLICATION DATA SHEET APPLICATION DATA SHEET General Piping Recommendations and Refrigerant Line Length for Split-System Air Conditioners and Heat Pumps GENERAL GUIDELINES This Split-System (Air Conditioning Condensing/Heat

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS T CLASS TSA Series 6 to 20 Ton AIR CONDITIONERS 6 20 TONS 506147 01 06/11 Supersedes 3/11 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE IMPORTANT The Clean Air Act

More information

Model SWAC Self Contained Cooling/ Hot Water Heating Units UNIT MODEL SWAC - R22 INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

Model SWAC Self Contained Cooling/ Hot Water Heating Units UNIT MODEL SWAC - R22 INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS Model SWAC Self Contained Cooling/ Hot Water Heating Units Supersedes: 145.26-IOM1 (708) Form 145.26-IOM1 (908) UNIT MODEL SWAC - R22 Hot Water Heating / Electric Cooling INSTALLATION, OPERATION & MAINTENANCE

More information

Daikin Water Cooling, Heating, and High Capacity Booster Coils

Daikin Water Cooling, Heating, and High Capacity Booster Coils Installation and Maintenance Manual IM 900 Daikin Water Cooling, Heating, and High Capacity Booster Coils Group: Applied Air Part Number: IM 900 Date: February 2008 Types HI-F5, E-F5 2008 Daikin International

More information

This label warns for risk of electrical shock when failing to observe.

This label warns for risk of electrical shock when failing to observe. MANUAL horizontal centrifugal pumps MB series ic drive SB series mechanical seal 1. Introduction 2. Safety precautions 3. Receipt 4. Installation / Operation and Maintenance 4.1 Installation 4.2 Operation

More information

CONTENTS. B. System Design and Performance Requirements

CONTENTS. B. System Design and Performance Requirements 15625 Water Chillers This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes

More information

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 PROVEN PERFORMANCE GENERAL FEATURING

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 PROVEN PERFORMANCE GENERAL FEATURING TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 PROVEN PERFORMANCE GENERAL The LA/LB line is a flexible performer. LA300, LB360 & 480 canbepositionedinupto12differentpositionsandsuspended

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS C7BA & C7BH Series Split System Indoor Cased Coils INSTALLATION INSTRUCTIONS IMPORTANT It is your responsibility to know this product better than your customer. This includes being able to install the

More information

Drop-In Refrigeration System

Drop-In Refrigeration System Drop-In Refrigeration System Original Instructions Installation, Operation and Maintenance Manual This manual is updated as new information and models are released. Visit our website for the latest manual.

More information

Installation, Operation, and Maintenance

Installation, Operation, and Maintenance Installation, Operation, and Maintenance Series S Water-Cooled CenTraVac Chillers With Tracer AdaptiView Control Model: CVHS X39641230010 SAFETY WARNING Only qualified personnel should install and service

More information

INFINITY FLUIDS CORPORATION

INFINITY FLUIDS CORPORATION INFINITY FLUIDS CORPORATION INFINITY FLUIDS CORPORATION 344 FRANKLIN STREET WORCESTER, MA 01522 888-565-8137 508-347-3674 CRES PRODUCT: WATER/LIQUID HEATER AIR/GAS HEATER INLINE/INSTANTANEOUS STEAM GENERATORS

More information

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS DLCLRA INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 Fig. 1 - Size 36 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 WIRING...

More information

InterSeptor Centrifugal Separators Operating & Maintenance Manual

InterSeptor Centrifugal Separators Operating & Maintenance Manual General Information: This manual was prepared to assist in the installation, operation, and maintenance of PEP ICS centrifugal separator systems. For immediate response to questions not covered in this

More information

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program. 15684 ROTARY SCREW WATER CHILLERS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 236423 An optional

More information

Installation & Operation Manual

Installation & Operation Manual Installation & Operation Manual Flat Top Bottle Cooler BC Series BC72 shown C US Form No. Z2295 Rev. 04.05.2018 JOB AREA ITEM NO. MODEL NO. BC24 SERIES BC36 SERIES BC48 SERIES BC24 shown BC72 shown BC48LT

More information

65 MBH through 2890 MBH. LD16237a. June 18, 2015

65 MBH through 2890 MBH. LD16237a. June 18, 2015 AIR-COOLED CONDENSER AND FLUID COOLER INSTALLATION, OPERATION, MAINTENANCE Supersedes: 195.29-NM1 (413) Form 195.29-NM1 (615) 035 23478 100 MODEL VDC Condenser and MODEL VDCF Fluid Cooler VDC 66 Models

More information