1 CENTRIFUGAL LIQUID CHILLERS INSTALLATION INSTRUCTIONS Supersedes: N1 (715) Form N1 (1217) ODEL YK (STYLE G) R-134a or R-531A WITH OPTIVIEW CONTROL CENTER FOR ELECTRO-ECHANICAL STARTER, SOLID STATE STARTER AND VARIABLE SPEED DRIVE LD15222 Issue Date: December 29, 2017

2 IPORTANT! READ BEFORE PROCEEDING! GENERAL SAFETY GUIDELINES FOR N1 This equipment is a relatively complicated apparatus. During rigging, installation, operation, maintenance, or service, individuals may be exposed to certain components or conditions including, but not limited to: heavy objects, refrigerants, materials under pressure, rotating components, and both high and low voltage. Each of these items has the potential, if misused or handled improperly, to cause bodily injury or death. It is the obligation and responsibility of rigging, installation, and operating/service personnel to identify and recognize these inherent hazards, protect themselves, and proceed safely in completing their tasks. Failure to comply with any of these requirements could result in serious damage to the equipment and the property in which it is situated, as well as severe personal injury or death to themselves and people at the site. This document is intended for use by owner-authorized rigging, installation, and operating/service personnel. It is expected that these individuals possess independent training that will enable them to perform their assigned tasks properly and safely. It is essential that, prior to performing any task on this equipment, this individual shall have read and understood the on-product labels, this document and any referenced materials. This individual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in question. SAFETY SYBOLS The following symbols are used in this document to alert the reader to specific situations: Indicates a possible hazardous situation which will result in death or serious injury if proper care is not taken. Identifies a hazard which could lead to damage to the machine, damage to other equipment and/or environmental pollution if proper care is not taken or instructions and are not followed. Indicates a potentially hazardous situation which will result in possible injuries or damage to equipment if proper care is not taken. Highlights additional information useful to the technician in completing the work being performed properly. External wiring, unless specified as an optional connection in the manufacturer s product line, is not to be connected inside the OptiView cabinet. Devices such as relays, switches, transducers and controls and any external wiring must not be installed inside the micro panel. All wiring must be in accordance with Johnson Controls published specifications and must be performed only by a qualified electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper connections to the controls or application of improper control signals. Failure to follow this warning will void the manufacturer s warranty and cause serious damage to property or personal injury. 2 JOHNSON CONTROLS

3 CHANGEABILITY OF THIS DOCUENT In complying with Johnson Controls policy for continuous product improvement, the information contained in this document is subject to change without notice. Johnson Controls makes no commitment to update or provide current information automatically to the manual or product owner. Updated manuals, if applicable, can be obtained by contacting the nearest Johnson Controls Service office or accessing the Johnson Controls QuickLIT website at johnsoncontrols.com. It is the responsibility of rigging, lifting, and operating/ service personnel to verify the applicability of these documents to the equipment. If there is any question regarding the applicability of these documents, rigging, lifting, and operating/service personnel should verify whether the equipment has been modified and if current literature is available from the owner of the equipment prior to performing any work on the chiller. CHANGE BARS Revisions made to this document are indicated with a line along the left or right hand column in the area the revision was made. These revisions are to technical information and any other changes in spelling, grammar or formatting are not included. ASSOCIATED LITERATURE ANUAL DESCRIPTION Solid State Starter (od B ) Operation and aintenance Variable Speed Drive Operation Installation Unit Operation OptiView Control Panel Renewal Parts Unit Renewal Parts OptiView Control Center Wiring Diagram YK Chiller (Style G) Field Control odifications Wiring Diagram YK Chiller (Style G) OptiView Control Center with Remote Low or edium Voltage ES Wiring Diagram YK Chiller (Style G) OptiView Control Center with Unit ounted Low or edium Voltage SSS, Unit ounted Low Voltage VSD with odbus, or Remote edium Voltage VSD Wiring Diagram YK Chiller (Style G) OptiView Control Center with LTC I/O Board with Remote Low or edium Voltage ES Wiring Diagram YK Chiller (Style G) OptiView Control Center with LTC I/O Board with Unit ounted Low or edium Voltage SSS, Unit ounted Low Voltage VSD with odbus or Remote edium Voltage VSD aintenance Requirements Log Sheets Installation and ReAssembly - Unit Operation - Unit FOR NUBER O O N O RP RP PW PW PW PW PW R N O1 JOHNSON CONTROLS 3

4 NOENCLATURE YK KC K4 H9 CY G STYLE (Design Level) POWER SUPPLY for 60 Hz 5 for 50 Hz OTOR CODE COPRESSOR CODE* CODE* ODEL* EVAPORATOR CODE* * Refer to YK Engineering Guide (Form EG1) for Shell/otor/Compressor combinations. 4 JOHNSON CONTROLS

5 LIST OF FIGURES FIGURE 1 - odel YK Chiller...7 FIGURE 2 - Rigging...9 FIGURE 3 - Neoprene Isolators FIGURE 4 - Neoprene Isolators...12 FIGURE 5 - Spring Isolators...13 FIGURE 6 - Spring Isolators...14 FIGURE 7 - Schematic of a Typical Piping Arrangement...16 FIGURE 8 - Typical Refrigerant Vent Piping...18 FIGURE 9 - Control Panel Positioning (H9, K1-K7)...19 FIGURE 10 - Unit Insulation...20 FIGURE 11 - Dimensions P and Q Compressor Units (ft in)...23 FIGURE 12 - Dimensions P and Q Compressor Units (mm)...24 FIGURE 13 - Dimensions H Compressor Units (ft in)...25 FIGURE 14 - Dimensions H Compressor Units (mm)...26 FIGURE 15 - Dimensions K Compressor Units (ft in)...27 FIGURE 16 - Dimensions K Compressor Units (mm)...28 FIGURE 17 - Dimensions Evaporator Compact Waterboxes...29 FIGURE 18 - Dimensions Condenser Compact Waterboxes...30 FIGURE 19 - Dimensions Evaporator Compact Waterboxes A thru L Evaporators...31 FIGURE 20 - Dimensions Evaporator Compact Waterboxes thru Z Evaporators...32 FIGURE 21 - Dimensions Condenser Compact Waterboxes - Standard (mm)...33 FIGURE 22 - Dimensions Condenser Compact Waterboxes - Standard (mm)...34 FIGURE 23 - Dimensions Condenser Heat Recovery Compact Waterboxes - Standard (mm)...35 FIGURE 24 - Dimensions Evaporator Nozzle Arrangements - Standard (mm)...36 FIGURE 25 - Dimensions Condenser Nozzle Arrangements - Standard (mm)...37 FIGURE 26 - Dimensions Evaporator arine Waterboxes...38 FIGURE 27 - Dimensions Condenser arine Waterboxes...39 LIST OF TABLES TABLE 1 - Available Compressor/Shell/otor Combinations...21 TABLE 2 - Approximate Unit Weight Including otor for Flooded Evaporator Units - LBS (KGS)...42 TABLE 3 - Approximate Unit Weight Including otor for Hybrid Falling Film Evaporator Units - LBS (KGS) TABLE 4 - Evaporator arine Waterbox Weights - LBS (KGS)...43 TABLE 5 - Condenser arine Waterbox Weights - LBS (KGS)...44 TABLE 6 - SI etric Conversion...45 JOHNSON CONTROLS 5

6 THIS PAGE INTENTIONALLY LEFT BLANK. 6 JOHNSON CONTROLS

7 SECTION 1 - INTRODUCTION 1 GENERAL This manual describes the installation of a YORK YK od "G" Centrifugal Chiller. This unit can be shipped as a single factory assembled, piped, wired package, requiring a minimum of field labor to make chilled water connections, condenser water connections, refrigerant atmospheric relief connections, and electrical power connections. Refrigerant and oil charges are shipped separately unless optional condenser isolation valves are ordered. Chillers can also be shipped dismantled when required by rigging conditions, but generally it is more economical to enlarge access openings to accommodate the factory assembled unit. Chillers shipped dismantled UST be field assembled under the supervision of a Johnson Controls representative, but otherwise installation will be as described in this instruction. FIELD ASSEBLED UNITS ONLY Use Unit - Installation Instructions (Form N3) in conjunction with this installation instruction. This instruction will be furnished with all units that are to be field assembled. The services of a Johnson Controls representative will be furnished to check the installation, supervise the initial start-up and operation of all chillers installed within the Continental United States. The Johnson Controls Warranty may be voided if the following restrictions are not adhered to: 1. No valves or connections should be opened under any circumstances because such action will result in loss of the factory nitrogen charge. 2. Do not dismantle or open the chiller for any reason except under the supervision of a Johnson Controls representative. 3. When units are shipped dismantled, notify the nearest Johnson Controls office in ample time for a Johnson Controls representative to supervise rigging the unit to its operating position and the assembly of components. 4. Do not make final power supply connections to the compressor motor or control center. CONTROL CENTER COPRESSOR OTOR LD15222 EVAPORATOR Figure 1 - ODEL YK CHILLER JOHNSON CONTROLS 7

8 section 1 - INTRODUCTION 5. Do not charge the compressor with oil. 6. Do not charge the unit with refrigerant. 7. Do not attempt to start the system. 8. Do not run hot water (110 F / 43 C max) or steam through the evaporator or condenser at any time. SHIPENT The chiller may be ordered and shipped in any of the following forms: Form 1 Factory Assembled Unit, complete with motor, refrigerant and oil charges. The motor/compressor assembly mounted, with all necessary interconnecting piping assembled. OptiView Control Center is mounted on the unit. Complete unit factory leak tested, evacuated and charged with R- 134A. An optional Solid State Starter or Variable Speed Drive can be factory mounted and wired. iscellaneous material Four (4) vibration isolation pads (or optional spring isolators and brackets). K7 units will be shipped with 8 Vibration Isolation Pads. Form 2 Factory Assembled Unit, complete with motor (refrigerant and oil charges shipped separately). The motor/compressor assembly mounted, with all necessary interconnecting piping assembled. OptiView Control Center is mounted on the unit. Complete unit factory leak tested, evacuated and charged with holding charge of nitrogen. An optional Solid State Starter or Variable Speed Drive can be factory mounted and wired. iscellaneous material Four (4) vibration isolation pads (or optional spring isolators). K7 units will be shipped with 8 Vibration Isolation Pads. Form 3 Driveline Separate From Shells Shipped as two major assemblies. Unit first factory assembled, refrigerant piped, wired and leak tested; then dismantled for shipment. FOR N1 Compressor/motor assembly removed from shells and skidded. Evaporator/condenser is not skidded. All wiring integral with compressor is left on it, and all conduit is left on shell. All openings on compressor, oil separator, and shell are closed and charged with dry nitrogen (2 to 3 PSIG) (115/122 kpa). iscellaneous packaging of control center, tubing, water temperature controls, wiring, oil, isolators, solid state starter (option), etc.; refrigerant charge shipped separately. Units shipped dismantled UST be reassembled by, or under the supervision of, a Johnson Controls representative. Refer to Installation - Unit (Form N3) Form 7 Split Shells Shipped as three major assemblies. Unit first factory assembled, refrigerant piped, wired and leak tested; then dismantled for shipment. Compressor/motor assembly removed from shells and skidded. Evaporator and condenser shells are separated at tube sheets and are not skidded. Refrigerant lines between shells are flanged and capped, requiring no welding. All wiring integral with compressor is left on it. All wiring harnesses on shells are removed. All openings on compressor and shells are closed and charged with dry nitrogen (2 to 3 psig) (115/122 kpa). iscellaneous packaging of control center, tubing, water temperature controls, wiring, oil isolators, solid state starter (option), etc.; refrigerant charge shipped separately. Units shipped dismantled UST be reassembled by, or under the supervision of, a Johnson Controls representative. Refer to Installation - Unit (Form N3) When more than one chiller is involved, the major parts of each unit will be marked to prevent mixing of assemblies. (Piping and Wiring Drawings to be furnished by Johnson Controls) 8 JOHNSON CONTROLS

9 section 1 - INTRODUCTION FOR 9 Unit Separate from Variable Speed Drive Shipped as two major assemblies: Chiller Unit Variable Speed Drive The unit is first factory assembled, refrigerant piped, wired and leak tested; then dismantled for shipment. Evaporator/condenser is not skidded. All wiring integral with compressor is left on it, and all conduit is left on shell. All openings on compressor, and shell are closed and charged with dry nitrogen (2 to 3 PSIG). iscellaneous packaging of tubing, water temperature controls, wiring, isolators, etc. The unit is shipped with a nitrogen charge. Refrigerant charge shipped in appropriate cylinders. See Figure 2. FOR 10 Unit Separate from Variable Speed Drive Shipped as two major assemblies: Chiller Unit Variable Speed Drive The unit is first factory assembled, refrigerant piped, wired and leak tested; then dismantled for shipment. Evaporator/condenser is not skidded. All wiring integral with compressor is left on it, and all conduit is left on shell. iscellaneous packaging of tubing, water temperature controls, wiring, isolators, etc. The unit is shipped with refrigerant charge. See Figure 2. INSPECTION DAAGE SHORTAGE The unit shipment should be checked on arrival to see that all major pieces, boxes and crates are received. Each unit should be checked on the trailer or rail car when received, before unloading, for any visible signs of damage. Any damage or signs of possible damage must be reported to the transportation company immediately for their inspection. Johnson Controls will not be responsible for any damage in shipment, at job site, or loss of parts. (Refer to Shipping Damage Claims, Form N.) When received at the job site all containers should be opened and contents checked against the packing list. Any material shortage should be reported to Johnson Controls immediately. (Refer to Shipping Damage Claims, Form N.) CHILLER DATA PLATE A unit data plate is mounted on the control center assembly of each unit, giving unit model number; design working pressure; water passes; refrigerant charge; serial numbers; and motor power characteristics and connection diagrams. Additional information may be found on the motor data plate. This information should be included when contacting the factory on any problem relating to the motor in. Lifting Holes 65 in. Lifting Holes LD16730 Figure 2 - VARIABLE SPEED DRIVE RIGGING JOHNSON CONTROLS 9

10 section 1 - INTRODUCTION FOR N1 LD19197 Rigging and lifting should only be done by a professional rigger in accordance with a written rigging and lifting plan. The most appropriate rigging and lifting method will depend on job specific factors, such as the rigging equipment available and site needs. Therefore, a professional rigger must determine the rigging and lifting method to be used, and it is beyond the scope of this manual to specify rigging and lifting details. RIGGING The complete standard chiller is shipped without skids. (When optional skids are used it may be necessary to remove the skids so riggers skates can be used under the unit end sheets to reduce overall height.) Each unit has four (4) lifting holes (two in each end) in the end sheets which should be used to lift the unit. Care should be taken at all times during rigging and handling of the chiller to avoid damage to the unit and its external connections. Lift only using holes shown in Figure 3 on Page 11. Do not lift the unit with slings around motor/compressor assembly or by means of eyebolts in the tapped holes of the compressor motor assembly. Do not turn a unit on its side for rigging. Do not rig vertically. The rigging and operating weights and overall dimensions are given on pages 22 thru 40 as a guide in determining the clearances required for rigging. Add 6" (15 cm) to overall height for optional skidded unit. 10 JOHNSON CONTROLS

11 section 1 - INTRODUCTION 1 Figure 3 - RIGGING LD19569 LOCATION YORK Chillers are furnished with vibration isolator mounts for basement or ground level installations. Units may be located on upper floor levels providing the floor is capable of supporting the total unit operating weight and optional spring isolators are used. Sufficient clearance to facilitate normal service and maintenance work must be provided all around and above the unit and particularly space provided at either end to permit cleaning or replacement of evaporator and condenser tubes see Clearance. A doorway or other sufficiently large opening properly located may be used. The chiller should be located in an indoor location where temperatures range from 40 F to 110 F (4.4 C to 43.3 C). OTORS The YK open motor is air cooled. Check state, local and other codes for ventilation requirements. FOUNDATION A level floor, mounting pad or foundation must be provided by others, capable of supporting the operating weight of the unit. CLEARANCE Clearances should be adhered to as follows: Rear and above unit 2 ft (61 cm). Front of unit 3 ft (91 cm). Tube Removal 14 ft.* (4.3 m) (either end) * 16 ft (4.9 meters) on shell codes Q-Q, N-N, R-R, X-T and X-X. ** 18 ft (5.5 meters) on shell code S-S, S-V, Z-Z. *** 22 ft (6.7 meters) on shell code W-W. JOHNSON CONTROLS 11

12 section 1 - INTRODUCTION FOR N1 ALL DIENSIONS ARE IN INCHES () SHELL SHELL DIA. HOLE END SHEET DIA. HOLE END SHEET See Detail A See Detail A UNIT WEIGHT UP TO 16,365 Lbs (7,423 Kgs) LD12638a LD12639a UNIT WEIGHT 16,366-28,835 Lbs (7,424-13,080 Kgs) SHELL SHELL DIA. HOLE END SHEET DIA. HOLE END SHEET See Detail A See Detail A LD12640a UNIT WEIGHT 28,836-53,530 Lbs (13,081-24,281 Kgs) LD12641a UNIT WEIGHT 53, ,464 Lbs (24,283-45,559 Kgs) SHELL SHELL DIA. HOLE END SHEET DIA. HOLE END SHEET 5" (127) 9" (229) ounting Bracket 3/8 (10) See Detail A See Detail A Pad 3/4 (19) 9" (229) LD19571a LD12642a LD19578 UNIT WEIGHT 100, ,000 Lbs (45,570-58,967 Kgs) UNIT WEIGHT UP TO 200,928 Lbs (UP TO 91,332 Kgs) DETAIL A Figure 4 - NEOPRENE ISOLATORS 12 JOHNSON CONTROLS

13 section 1 - INTRODUCTION ALL DIENSIONS ARE IN INCHES () 1 SHELL SHELL 5 1/2 (140) 1 3/8 (35) END SHEET CAP SCREW 5 1/2 (140) 1 3/8 (35) END SHEET CAP SCREW ADJUSTING BOLT ADJUSTING BOLT 1 (25) 1 (25) 7 (178) 7 (178) 6 (152) 6 (152) 4-SPRING ISOLATORS 4-SPRING ISOLATORS UNIT WEIGHT 10,000 to 19,563 (4,536 to 8,873 Kgs) LD19572 UNIT WEIGHT 19,564 Lbs UP TO 35,009 Lbs (8,874 Kgs UP TO 15,880 Kgs) LD19573 END SHEET SHELL END SHEET SHELL 5 1/2" (140) 6-1/4" (159) CAP SCREW CAP SCREW ADJUSTING BOLT ADJUSTING BOLT 9 (229) 9 (229) 6-SPRING ISOLATORS 9-SPRING ISOLATORS UNIT WEIGHT 35,010 Lbs UP TO 58,349 Lbs (15,881 Kgs UP TO 26,467 Kgs) LD19579 UNIT WEIGHT 58,350 Lbs. UP TO 89,340 Lbs (26,468 Kgs UP TO 40,525 Kgs) LD19419 Figure 5 - SPRING ISOLATORS JOHNSON CONTROLS 13

14 section 1 - INTRODUCTION FOR N1 ALL DIENSIONS ARE IN INCHES () END SHEET SHELL END SHEET SHELL 16 1/4" (413) 5 1/4" (133) 6-1/4" (159) CAP SCREW ADJUSTING BOLT CAP SCREW ADJUSTING BOLT 12-SPRING ISOLATORS UNIT WEIGHT 89,341 Lbs UP TO 115,000 Lbs (40,526 Kgs UP TO 52,163 Kgs) LD SPRING ISOLATORS UNIT WEIGHT 115,000 Lbs. UP TO 190,000 Lbs (52,163 Kgs UP TO 86,183 Kgs) LD19581 Figure 6 - SPRING ISOLATORS 14 JOHNSON CONTROLS

15 SECTION 2 - INSTALLATION RIGGING UNIT TO FINAL LOCATION Rig the unit to its final location on the floor or mounting pad, lift the unit (or shell assembly) by means of an overhead lift and lower the unit to its mounting position. (If optional shipping skids are used, remove them before lowering the chiller to its mounting position.) At this point units shipped dismantled should be assembled under the supervision of a Johnson Controls representative. If evaporator is to be field insulated, the insulation should be applied to the evaporator before the unit is placed in position while the unit is in the lift position. Be sure unit is properly supported. (Refer to Figure 3 on Page 11) LOCATING AND INSTALLING ISOLATOR PADS The isolator pad mounts are to be located as shown in Figure 4 on Page 12 (rubber side down). After the isolator pads have been placed into position on the floor, lower the chiller onto the pads. When the unit is in place, remove the rigging equipment and check that the unit is level. The unit should be level within 1/4" (6 mm) from one end to the other end and from front to the rear. If the chiller is not level within the amount specified, lift it and place shims between the isolation pad and the chiller tube sheets. (Shims furnished by the installer.) Lower unit again and recheck to see that it is level. CHECKING THE ISOLATION PAD DEFLECTION All isolation pads should be checked for the proper deflection while checking to see if the unit is level. Each pad should be deflected approximately 0.10 inches (2.5 mm) to 0.20 inches (5 mm). If an isolation pad is under-deflected, shims should be placed between the unit tube sheet and the top of the pad to equally deflect all pads. LEVELING THE UNIT The longitudinal alignment of the unit should be checked by placing a level on the top center of the evaporator shell under the compressor/motor assembly. Transverse alignment should be checked by placing a level on top of the shell end sheets. INSTALLING OPTIONAL SPRING ISOLATORS When ordered, spring type isolator assemblies will be furnished with the unit. The 4 assemblies are identical and can be placed at any of the 4 corners of the unit. While the unit is still suspended by the rigging, the isolators should be bolted to the unit by inserting the cap screw(s) through the hole(s) in the mounting bracket into the tapped hole in the top of the isolator leveling bolt(s). Then the unit can be lowered onto the floor. The leveling bolts should now be rotated one (1) turn at a time, in sequence, until the unit end sheets are clear of the floor by the dimension shown in Figure 5 on Page 13 and Figure 6 on Page 14 and the unit is level. Check that the unit is level, both longitudinally and transversely (see Leveling the Unit). If the leveling bolts are not long enough to level unit due to an uneven or sloping floor or foundation, steel shims (grouted, if necessary) must be added beneath the isolator assemblies as necessary. After the unit is leveled, wedge and shim under each corner to solidly support the unit in this position while piping connections are being made, pipe hangers adjusted and connections checked for alignment. Then the unit is filled with water and checked for leaks. The leveling bolts should now be finally adjusted until the wedges and shims can be removed. The unit should now be in correct level position, clear of the floor or foundation and without any effect from the weight of the piping. PIPING CONNECTIONS After the unit is leveled (and wedged in place for optional spring isolators) the piping connections may be made; chilled water, condenser water and refrigerant relief. The piping should be arranged with offsets for flexibility, and adequately supported and braced independently of the unit to avoid strain on the unit and vibration transmission. Hangers must allow for alignment of pipe. Isolators (by others) in the piping and hangers are highly desirable, and may be required by specifications, in order to effectively utilize the vibration isolation characteristics of the vibration isolation mounts of the unit. Check for piping alignment Upon completion of piping, a connection in each line as close to the unit as possible should be opened, by removing the flange 2 JOHNSON CONTROLS 15

16 Section 2 - installation bolts or coupling and checked for piping alignment. If any of the bolts are bound in their holes, or if the connection springs are out of alignment, the misalignment must be corrected by properly supporting the piping or by applying heat to anneal the pipe. If the piping is annealed to relieve stress, the inside of the pipe must be cleaned of scale before it is finally bolted in place. EVAPORATOR AND WATER PIPING The evaporator and condenser liquid heads of chiller have nozzles which are grooved, suitable for welding 150 psig DWP flanges or the use of flexible couplings. Factory mounted flanges are optional. The nozzles and water pass arrangements are furnished in accordance with the job requirements (see Product Drawings) furnished with the job. Standard units are designed for 150 psig DWP on the water side. If job requirements are for greater than 150 psig DWP, check the unit data plate before applying pressure to evaporator or condenser to determine if the chiller has provisions for the required DWP. Inlet and outlet connections are identified by labels placed adjacent to each nozzle. The coolant temperature inside any JCI-supplied liquidcooled motor starter must be maintained above the dewpoint temperature in the equipment room to prevent condensing water vapor inside the starter cabinet. Therefore, an additional temperature-controlled throttle valve is needed in the COOLING TOWER FOR N1 flow path for the starter heat exchanger to regulate cooling above the equipment room dewpoint for applications using cooling sources other than evaporative air-exchange methods, such as wells, bodies of water, and chilled water. The temperature control valve should be the type to open on increasing drive coolant temperature, fail-closed, and set for a temperature above dewpoint. It can be requested as factorysupplied on a chiller order by special quotation. Chilled Water Foreign objects which could lodge in, or block flow through, the evaporator and condenser tubes must be kept out of the water circuit. All water piping must be cleaned or flushed before being connected to the chiller pumps, or other equipment. Permanent strainers (supplied by others) are required in both the evaporator and condenser water circuits to protect the chiller as well as the pumps, tower spray nozzles, chilled water coils and controls, etc. The strainer must be installed in the entering chilled water line, directly upstream of the chiller. Water piping circuits should be arranged so that the pumps discharge through the chiller, and should be controlled as necessary to maintain essentially constant chilled and condenser water flows through the unit at all load conditions. If pumps discharge through the chiller, the strainer may be located upstream from pumps to protect both pump and chiller. (Piping between strainer, pump and chiller must be very carefully cleaned before start-up.) If pumps are remotely installed from chiller, strainers should be located directly upstream of the chiller. STRAINER CONTROLLED COOLING TOWER BYPASS VALVE (IF NECESSARY) C = COPRESSOR = OTOR COOLING TOWER PUP COOLING UNIT CODEPAK EVAPORATOR Figure 7 - SCHEATIC OF A TYPICAL PIPING ARRANGEENT FLOW SWITCH CHILLED WATER PUP COOLING UNIT STRAINER LD JOHNSON CONTROLS

17 Section 2 - installation Condenser Water Circuit For proper operation of the unit, condenser refrigerant pressure must be maintained above evaporator pressure. If operating conditions will fulfill this requirement, no attempt should be made to control condenser water temperature by means of automatic valves, cycling of the cooling tower fan or other means, since chillers are designed to function satisfactorily and efficiently when condenser water is allowed to seek its own temperature level at reduced loads and off-peak seasons of the year. However, if entering condenser water temperature can go below the required minimum, Refer to Operation - Unit (Form O1) condenser water temperature must be maintained equal to or slightly higher than the required minimum. Refer to Figure 7 on Page 16 for typical water piping schematic. Stop Valves Stop valves may be provided (by others) in the evaporator and condenser water piping adjacent to the unit to facilitate maintenance. Thermometer wells and pressure taps should be provided (by others) in the piping as close to the unit as possible to facilitate operating check. Flow Switches Thermal type water flow switches are factory mounted in the chilled and condensed water nozzles and are factory wired to the OptiView control panel. These solid-state flow sensors have a small internal heating element and use the cooling effect of the flowing fluid to sense when an adequate flow rate has been established. Waterbox Drain and Vent Valves Drain and vent valves (by others) should be installed in the connections provided in the evaporator and condenser liquid heads. These connections may be piped to drain if desired. Checking Piping Circuits and Venting Air After the water piping is completed, but before any waterbox insulation is applied. Tighten and torque to maintain between 30 and 60 ft. lbs. (41 and 81 N m) the nuts on the liquid head flanges. Gasket shrinkage and handling during transit cause nuts to loosen. If water pressure is applied before tightening is done, the gaskets may be damaged and have to be replaced. Fill the chilled and condenser water circuits, operate the pumps manually and carefully check the evaporator and condenser water heads and piping for leaks. Repair leaks as necessary. Before initial operation of the unit both water circuits should be thoroughly vented of all air at the high points. UNIT PIPING Compressor lubricant piping and system external piping are factory installed on all units shipped assembled. On units shipped dismantled, the following piping should be completed under the supervision of the Johnson Controls representative: (1) the lubricant piping to oil sump and oil evaporator and system oil return connections using material furnished. Refer to Installation - Unit (Form N3). 2 JOHNSON CONTROLS 17

18 Section 2 - installation FOR N1 REFRIGERANT RELIEF PIPING Each unit is equipped with pressure relief valves located on the condenser and on the evaporator for the purpose of quickly relieving excess pressure of the refrigerant charge to the atmosphere as a safety precaution in case of an emergency, such as fire. Refrigerant relief vent piping (by others), from the relief valves to the outside of the building, is required by code in most areas and should be installed on all chillers. The vent line should be sized in accordance with the ANSI/ASHRAE-15, or local code. The vent line must include a dirt trap in the vertical leg to intercept and permit clean out and to trap any vent stack condensation. The piping UST be arranged to avoid strain on the relief valves, using a flexible connection, if necessary. When installing relief piping an ANSI flange or a piping union must be used to make a servicable piping connection. Horizontal is-aligned Vertical Compressed Offset When installing relief piping there must NOT be any piping strain. Relief piping must be properly aligned and supported to eliminate any possible piping strain. LD16677 VENT TO ATOSPHERE FLANGED JOINT TO PERIT PIPING DISASSEBLY SUPPORT VENT PIPING TO AVOID STRAIN ON RELIEF PIPING FLEXIBLE CONNECTOR CONDENSATION TRAP DUAL RELIEF VALVES EVAPORATOR SEE NOTE Figure 8 - TYPICAL REFRIGERANT VENT PIPING NOTE: SHELLS AY BE FURNISHED WITH ONE OR TWO RELIEF VALVES, DEPENDING ON SHELL SIZE. LD JOHNSON CONTROLS

19 Section 2 - installation CONTROL PANEL POSITIONING On large YK chillers equipped with H9 and K1-K7 compressors, the control panel height can be adjusted. Chillers equipped with P and Q compressors the control panel height is NOT adjustable. The OptiView Control Center is placed in a position above the evaporator for shipping. To move the control center into position for operation, proceed as follows: 1. While supporting the control center, remove the hardware between the support arms and the evaporator. 2. Swing the control center into a vertical position. 3. Slide the control center down the guide rails to the proper position. Tighten securely. 4. Discard unused hardware. SUPPORT ARS PANEL TRACK Figure 9 - CONTROL PANEL POSITIONING (H9, K1-K7) CONTROL WIRING LD03826 On units shipped disassembled, after installation of the control center, control wiring must be completed between unit components and control center, solid state starter, or variable speed drive, when used, using wiring harnesses furnished. Refer to Installation - Unit (Form N3). Field wiring connections for commonly encountered control modifications (by others) if required, are shown on Wiring Diagram Unit (Style G) Field Control odifications (Form PW4). POWER WIRING No deviations in unit wiring from that shown on drawings furnished shall be made without prior approval of the Johnson Controls representative. Chiller with Electro-echanical Starter A 115 volt single phase 60 or 50 Hertz power supply of 20 amperes must be furnished to the control center, from the control transformer (2 KVA required) included with the compressor motor starter. Do NOT make final power connections to control center until approved by YORK representative. OIL PUP 3 PHASE STARTER Separate wiring or a fused disconnect switch should be supplied by the installer. Remote Electro-echanical starters for the chiller must be furnished in accordance with YORK Starter Specifications Product Drawing Form PA1 to provide the features necessary for the starter to function properly with the YORK control system. Each chiller unit is furnished for a specific electrical power supply as stamped on the Unit Data Plate, which also details the motor connection diagrams. To insure proper motor rotation the starter power input and starter to motor connections must be checked with a phase sequence indicator in the presence of the Johnson Controls representative. DO NOT cut wires to final length or make final connections to motor terminals or starter power input terminals until approved by the Johnson Controls representative. YK otors (Electro-echanical Starter) otor leads are furnished with a crimp type connection having a clearance hole for a 3/8" bolt, motor terminal lugs are not furnished. Refer to Wiring Labels in motor terminal box for hook-up to suit motor voltage and amperage for power wiring connections. 2 JOHNSON CONTROLS 19

20 Section 2 - installation Chiller with Solid State Starter or Variable Speed Drive A chiller equipped with a factory mounted Solid State Starter or Variable Speed Drive does not require wiring to the compressor motor. The motor power wiring is factory connected to the Solid State Starter or Variable Speed Drive (or an optional factory installed disconnect switch). See Field Wiring Diagram. All wiring to the control panel and the oil pump starter is completed by the factory. A control transformer is furnished with the Solid State Starter or Variable Speed Drive. INSULATION DO NOT field insulate until the unit has been leak tested under the supervision of the Johnson Controls representative. Insulation of the type specified for the job, or minimum thickness to prevent sweating of 30 F (-1 C) surfaces should be furnished (by others) and applied to the evaporator shell, end sheets, liquid feed line to Tape Insulation to Filter Drier FOR N1 flow chamber, compressor suction connection, and evaporator liquid heads and connections. The liquid head flange insulation must be removable, to allow head removal for the tube maintenance. Details of areas to be insulated are given on the Product Drawing. Units are furnished factory anti-sweat insulated on order at additional cost. This includes all low temperature surfaces except the two (2) cooler liquid heads. INSTALLATION CHECK REQUEST FOR START-UP SERVICE The services of a Johnson Controls representative will be furnished to check the installation and supervise the initial start-up and operation on all chillers installed within the Continental United States. After the unit is installed, piped and wired as described in this Instruction, but before any attempt is made to start the unit, the Johnson Controls District Office should be advised so that the start-up service, included in the contract price, can be scheduled. Use the Installation Checklist and Request for startup, (Form CL1). Hot Gas Connection EVAPORATOR EVAPORATOR Refigerant from Oil Cooler to Cooler Hot Gas Connection 2 Liquid Level Indicator Tape Insulation around flanges to allow for removal Liquid Line Input Drain and Charging NOTE: Bold lines represent Insulation Figure 10 - UNIT INSULATION LD JOHNSON CONTROLS

21 Section 2 - installation Table 1 - AVAILABLE COPRESSOR/SHELL/OTOR COBINATIONS COPRESSOR CODES EVAPORATOR CODES YK OD G COBINATIONS CODES Q3 AP to AS AP to AS Q3, Q4 CP to CS DP to DS CP to CS DP to DS Q4 EP to ET EP to ET Q5 Q5, Q6, Q7 P7 CP to CS DP to DS EP to ET FQ to FT CP to CS DP to DS EP to ET FQ to FT OTOR CODES 60 HZ 50 HZ CF-CT EF-ET CH-CT EH-ET EP to ET EP to ET CU-CY FQ to FT FQ to FT EU-EY P8 GQ to GS EV to EX P8, P9 H9 HQ to HS JP to JS LQ to LS FV to FX JP to JS LQ to LS CH-CZ EH-EZ KP to KS, K2 to K4 KP to KS, K2 to K4 CN-CA Q to S, 2 to 4 P to S, 2 to 4 EN-EA K1 KT to KX, K5 to K7 KP to KS, K2 to K4 K1, K2 K3 K4 K7 Q to S, 2 to 4 NQ to NS, N2 to N4 PQ to PS, P2 to P4 QQ to QS, Q2 to Q4 NQ to NS, N2 to N4 QQ to QV, Q2 to Q4 RQ, RS, RN, R3, R5, R7 RP, RR, RT, R2, R4, R6 SQ, SS, SV, S3, S5, S7 XQ, XR, XS, X2, X3, X4 WP, WR, WT, W1, W2, W4, W6 ZQ, ZR, ZS, Z1, Z2, Z3, Z4 P to S, 2 to 4 NP to NS, N2 to N4 PQ to PS, P2 to P4 QQ to QS, Q2 to Q4 NP to NS, N2 to N4 QQ to QS, Q2 to Q4 RQ, RR, RS, R2, R3, R4 RQ, RR, RS, R2, R3, R4, R5 SQ, SR, SS, S2, S3, S4 VP, VQ, VR, VS, V2, V3, V4, V5 TP, TQ, TR, TS, T2, T3, T4, T5 XQ, XR, XS, X2, X3, X4 WQ, WR, WS, W1, W2, W3, W4 ZQ, ZR, ZS, Z1, Z2, Z3, Z4 CS-DC ES-FC DA-DJ FA-FD DA-DJ FA-FD DD-DL 5CC-5CO 5EC-5EO 5CE-5CO 5EE-5EO 5CP-5CU 5EP-5EU 5CE-5CU 5EE-5EU 5CK-5CW 5EK-5EW 5CN-5DC 5EN-5FB 5DA-5DH 5FA-5FB 5DA-5DJ 5FA-5FB 5DD-5DL 2 JOHNSON CONTROLS 21

22 Section 2 - installation FOR N1 TABLE 1 - ALLOWABLE COPRESSOR/EVAPORATOR//OTOR COBINATIONS (CONT'D) COPRESSOR CODES YK OD G HEAT RECOVERY COBINATIONS EVAPORATOR CODES CODES Q4 Q7 CP, CQ, CR, CS EP, EQ, ER, ES, ET BV, BW, BX IV, IW, IX CF-CT EF-ET H9 KP, KQ, KR, KS, K2, K3, K4 OW, OX, O7, O8, O9 CN-CA EN-EA K2 Q, R, S, 2, 3, 4 UW, UX, U7, U8, U9 CS-DC ES-FC OTOR CODES 60 HZ 50 HZ 5CC-5CO 5EC-5EO 5CK-5CW 5EK-5EW 5CN-5DC 5EN-5FB K7 ZQ, ZR, ZS, Z1, Z2, Z3, Z4 YW, YX, Y7, Y8, Y9 DD-DL 5DD-5DL COPRESSOR CODES Q3 Q4 Q5 Q5, Q6, Q7 P7 P8, P9 H9 YK OD G HYBRID FALLING FIL COBINATIONS HYBRID FALLING FIL EVAPORATOR CODES AC, AD, A3, A4 CC to CE, C3 to C5 CC to CE, C3 to C5 DC to DE, D3 to D5 CC to CE, C3 to C5 DC to DE, D3 to D5 EC to EE, E3 to E5 FC to FE, F3 to F5 CODES AP to AS CP to CS CP to CS DP to DS CP to CS DP to DS EP to ET FQ to FT OTOR CODES 60 HZ 50 HZ CF-CT EF-ET CH-CT EH-ET EC to EE, E3 to E5 EP to ET CU-CY FC to FE, F3 to F5 FQ to FT EU-EY GC to GE, G3 to G5 EV to EX, E3 to E4 CH-CZ HC to HE, H3 to H5 FV to FX, F3 to F4 EH-EZ KC, KD, K8, K9, K0 IB, IC, ID, IF, IH, I2, I4, I6, I8 B, D, F, 5, 7, 8 KP, KQ, KR, KS, K2, K3, K4 KP, KQ, KR, KS, K2, K3, K4, K5 P, Q, R, S, 2, 3, 4 K1 IB, IC, ID, IF, IH, I2, I4, I6, I8 KP, KQ, KR, KS, K2, K3, K4, K5 K1, K2 K3 B, D, F, 5, 7, 8, 9 NB, ND, NF, N5, N7, N8, N9 PB, PD, PF, P5, P7, P8 QB, QD, QF, Q5, Q7, Q8 P, Q, R, S, 2, 3, 4 NP, NQ, NR, NS, N2, N3, N4 PQ, PR, PS, P2, P3, P4 QQ, QR, QS, Q2, Q3, Q4 CN-CA EN-EA CS-DC ES-FC NB, ND, NF, N5, N7, N8, N9 NP, NQ, NR, NS, N2, N3, N4 DA-DJ QD, QF, QH, Q5, Q7, Q8, Q9 QQ, QR, QS, Q2, Q3, Q4 FA-FD 5CC-5CO 5EC-5EO 5CE-5CO 5EE-5EO 5CP-5CU 5EP-5EU 5CE-5CU 5EE-5EU 5CK-5CW 5EK-5EW 5CN-5DC 5EN-5FB 5DA-5DH 5FA-5FB 22 JOHNSON CONTROLS

23 Section 2 - installation P AND Q COPRESSOR UNITS (STANDARD) 2 LD07134 ADDITIONAL OPERATING HEIGHT CLEARANCE TO FLOOR Type Of Chiller ounting Neoprene Pad Isolators 1-3/4" Spring Isolators 1" Deflection 1" Direct ount 3/4" P7, Q7 COPRESSOR EVAPORATOR SHELL CODES E E E I F F A 6'-2" 7'-1 3/4" 6'-2" B 8'-0 5/8" 8'-8" 7'-6 1/2" C 1'-7 1/2" 1'-7 1/2" 1'-7 1/2" D 1'-5 1/2" 1'-11 3/8" 1'-5 1/2" E 12'-0" 12'-0" 16'-0" P8 COPRESSOR EVAPORATOR SHELL CODES G E H F J J L L A 6'-11" 6'-11" 7'-6 1/2" 7'-6 1/2" B 10'-6" 10'-6" 10'-11" 10'-11" C 2'-0" 2'-0" 2'-1 1/4" 2'-1 1/4" D 1'-5 1/2" 1'-5 1/2" 1'-8" 1'-8" E 12'-0" 16'-0" 12'-0" 16'-0" P9 COPRESSOR EVAPORATOR SHELL CODES H F J J L L A 6'-11" 7'-6 1/2" 7'-6 1/2" B 10'-3" 10'-8 1/2" 10'-8 1/2" C 2'-0" 2'-1 1/4" 2'-1 1/4" D 1'-5 1/2" 1'-8" 1'-8" E 16'-0" 12'-0" 16'-0" NOTES: 1. All dimensions are approximate. 2. For compact waterboxes (shown above), determine overall unit length by adding waterbox depth to tube sheet length. 3. Water nozzles can be located on either end of unit. Add 1/2" (13 mm) to nozzle length for flanges connections. 4. To determine overall height, add 7/8" (22 mm) for isolators. 5. Use of motors with motor hoods may increase overall unit dimensions. Figure 11 - DIENSIONS P AND Q COPRESSOR UNITS (FT IN) Q3 COPRESSOR EVAPORATOR SHELL CODES A A C C D D A 5'-1" 5'-6" 5'-6" B 7'-0" 7'-3 3/4" 7'-3 3/4" C 1'-3 1/2" 1'-5 1/2" 1'-5 1/2" D 1'-3" 1'-3 1/2" 1'-3 1/2" E 12'-0" 12'-0" 16'-0" Q4 COPRESSOR EVAPORATOR SHELL CODES C B C C D D E E A 6'-4 3/4" 5'-6" 5'-6" 7'-0" B 7'-11 3/8" 7'-2 1/2" 7'-2 1/2" 7'-8 1/2" C 1'-5 1/2" 1'-5 1/2" 1'-5 1/2" 1'-7 1/2" D 1'-8 7/8" 1'-3 1/2" 1'-3 1/2" 1'-5 1/2" E 12'-0" 12'-0" 16'-0" 12'-0" Q5 COPRESSOR EVAPORATOR SHELL CODES C C D D E E F F A 5'-6" 5'-6" 7'-0" 7'-0" B 7'-10 5/8" 7'-10 5/8" 8'-5 1/2" 8'-5 1/2" C 1'-5 1/2" 1'-5 1/2" 1'-7 1/2" 1'-7 1/2" D 1'-3 1/2" 1'-3 1/2" 1'-5 1/2" 1'-5 1/2" E 12'-0" 16'-0" 12'-0" 16'-0" Q6 COPRESSOR EVAPORATOR SHELL CODES E E F F A 7'-0" 7'-0" B 8'-3" 8'-3" C 1'-7 1/2" 1'-7 1/2" D 1'-5 1/2" 1'-5 1/2" E 12'-0" 16'-0" JOHNSON CONTROLS 23

24 Section 2 - installation FOR N1 P AND Q COPRESSOR UNITS (ETRIC) LD07134 ADDITIONAL OPERATING HEIGHT CLEARANCE Type of Chiller ounting Neoprene Pad Isolators 45 Spring Isolators 25mm Deflection 25 Direct ount 19 P7, Q7 COPRESSOR EVAPORATOR SHELL CODES E E E I F F A 1,880 2,178 1,880 B 2,299 2,642 2,299 C D E 3,658 3,658 4,877 P8 COPRESSOR EVAPORATOR SHELL CODES E E F F G G H H A 2,108 2,108 2,299 2,299 B 3,200 3,200 3,327 3,327 C D E 3,658 4,877 3,658 4,877 P9 COPRESSOR EVAPORATOR SHELL CODES H F J J L L A 2,108 2,299 2,299 B 3,124 3,264 3,264 C D E 4,877 3,658 4,877 NOTES: 1. All dimensions are approximate. 2. For compact waterboxes (shown above), determine overall unit length by adding waterbox depth to tube sheet length. 3. Water nozzles can be located on either end of unit. Add 13 mm (1/2 inch) to nozzle length for flanges connections. 4. To determine overall height, add 22 mm (7/8 inch) for isolators. 5. Use of motors with motor hoods may increase overall unit dimensions. Figure 12 - DIENSIONS P AND Q COPRESSOR UNITS () Q3 COPRESSOR EVAPORATOR SHELL CODES A A C C D D A 1,549 1,676 1,676 B 2,134 2,229 2,229 C D E 3,658 3,658 4,877 Q4 COPRESSOR EVAPORATOR SHELL CODE C C C B D D E E A 1,676 1,949 1,676 2,134 B 2,197 2,423 2,197 2,350 C D E 3,658 3,658 4,877 3,658 Q5 COPRESSOR EVAPORATOR SHELL CODES C C D D E E F F A 1,676 1,676 2,134 2,134 B 2,403 2,403 2,578 2,578 C D E 3,658 4,877 3,658 4,877 Q6 COPRESSOR EVAPORATOR SHELL CODES E E F F A 2,134 2,134 B 2,515 2,515 C D E 3,658 4, JOHNSON CONTROLS

25 Section 2 - installation H COPRESSOR UNITS (STANDARD) 2 LD07135 ADDITIONAL OPERATING HEIGHT CLEARANCE TO FLOOR Type of Chiller ounting Neoprene Pad Isolators 1 3/4" Spring Isolators 1" Deflection 1" Direct ount 3/4" H9 COPRESSORS EVAPORATOR SHELL CODES I-K & K K K O A 7'-6 1/2" 8'-9 1/4" 8'-7" B 10'-4" 10'-7 5/8" 10'-10 1/2" C 2'-1 1/4" 2'-1 1/4" 2'-4 1/2" D 1'-8" 2'-3 3/8" 1'-11" E 14'-0" 14'-0" 14'-0" NOTES: 1. All dimensions are approximate. 2. For compact waterboxes (shown above), determine overall unit length by adding waterbox depth to tube sheet length. 3. Water nozzles can be located on either end of unit. Add 1/2" (13 mm) to nozzle length for flanges connections. 4. To determine overall height, add 7/8" (22 mm) for isolators. 5. Use of motors with motor hoods may increase overall unit dimensions. Figure 13 - DIENSIONS H COPRESSOR UNITS (FT IN) JOHNSON CONTROLS 25

26 Section 2 - installation FOR N1 H COPRESSOR UNITS (ETRIC) 178 LD03886 ADDITIONAL OPERATING HEIGHT CLEARANCE Type of Chiller ounting Neoprene Pad Isolators 44 Spring Isolators 25mm Deflection 25 Direct ount 19 H9 COPRESSORS EVAPORATOR COND. SHELL CODES I-K & K K K O A 2,299 2,673 2,616 B 3,150 3,242 3,315 C D E 4,267 4,267 4,267 NOTES: 1. All dimensions are approximate. 2. For compact waterboxes (shown above), determine overall unit length by adding waterbox depth to tube sheet length. 3. Water nozzles can be located on either end of unit. Add 13 mm (1/2 inch) to nozzle length for flanges connections. 4. To determine overall height, add 22 mm (7/8 inch) for isolators. 5. Use of motors with motor hoods may increase overall unit dimensions. Figure 14 - DIENSIONS H COPRESSOR UNITS () 26 JOHNSON CONTROLS

27 Section 2 - installation K COPRESSOR UNITS (STANDARD) 2 LD07136 K1 COPRESSOR, EVAPORATOR SHELL CODES I-K & K K N N P P Q Q A 7'-6 1/2" 8'-7" 8'-7" 9'-1 1/2" 9'-1 1/2" B 9'-7" 11'-4" 11'-4" 11'-5 1/2" 11'-5 1/2" C 2'-1 1/4" 2'-4 1/2" 2'-4 1/2" 2'-5 1/2" 2'-5 1/2" D 1'-8" 1'-11" 1'-11" 2'-1 1/4" 2'-1 1/4" E 14'-0" 14'-0" 16'-0" 14'-0" 16'-0" K2 COPRESSOR, EVAPORATOR SHELL CODES U N N P P Q Q A 8'-7" 9'-6" 8'-7" 9'-1 1/2" 9'-1 1/2" B 11'-4" 11'-10" 11'-4" 11'-5" 11'-5" C 2'-4 1/2" 2'-4 1/2" 2'-4 1/2" 2'-5 1/2" 2'-5 1/2" D 1'-11" 2'-4 1/2" 1'-11" 2'-1 1/4" 2'-1 1/4" E 14'-0" 14'-0" 16'-0" 14'-0" 16'-0" K4 COPRESSOR, EVAPORATOR SHELL CODES R R S S S V X T X X A 9'-9" 9'-9" 10'-3" 10'-10" 11'-3" B 11'-11" 11'-11" 12'-4" 12'-4" 12'-4" C 2'-8" 2'-8" 2'-8" 2'-11 1/2" 2'-11 1/2" D 2'-3 1/2" 2'-3 1/2" 2'-5 1/2" 2'-5 1/2" 2'-8" E 16'-0" 18'-0" 18'-0" 16'-0" 16'-0" ADDITIONAL OPERATING HEIGHT CLEARANCE Type of Chiller ounting Neoprene Pad Isolators 1 3/4" Spring Isolators 1" Deflection 1" Direct ount 3/4" K3 COPRESSOR, EVAPORATOR SHELL CODES K7 COPRESSOR, EVAPORATOR SHELL CODES N N Q Q R R A 8'-7" 9'-1 1/2" 9'-9" B 10'-8" 11'-6" 11'-10" C 2'-4 1/2" 2'-5 1/2" 2'-8" D 1'-11" 2'-1 1/4" 2'-3 1/2" E 16'-0" 16'-0" 16'-0" W W Z Y Z Z A 10'-3" 12'-7" 11'-3" B 12'-2" 14'-1 5/8" 12'-10" C 2'-8" 2'-11 1/2" 2'-11 1/2" D 2'-5 1/2" 3'-4" 2'-8" E 22'-0" 18'-0" 18'-0" NOTES: 1. All dimensions are approximate. 2. For compact waterboxes (shown above), determine overall unit length by adding waterbox depth to tube sheet length. 3. Water nozzles can be located on either end of unit. Add 1/2" (13 mm) to nozzle length for flanges connections. 4. To determine overall height, add 7/8" (22 mm) for isolators. 5. Use of motors with motor hoods may increase overall unit dimensions. Figure 15 - DIENSIONS K COPRESSOR UNITS (FT IN) JOHNSON CONTROLS 27

28 Section 2 - installation FOR N1 K COPRESSOR UNITS (ETRIC) LD07139 K1 COPRESSOR, EVAPORATOR SHELL CODES I-K & K K N N P P Q Q A 2,299 2,616 2,616 2,781 2,781 B 2,921 3,454 3,454 3,493 3,493 C D E 4,267 4,267 4,877 4,267 4,877 K2 COPRESSOR, EVAPORATOR SHELL CODES U N N P P Q Q A 2,616 2,896 2,616 2,781 2,781 B 3,454 2,921 3,454 3,480 3,480 C D E 4,267 4,267 4,877 4,267 4,877 K4 COPRESSOR, EVAPORATOR SHELL CODES R R S S S V X T X X A 2,972 2,972 3,124 3,302 3,429 B 3,632 3,632 3,759 3,759 3,759 C D E 4,877 5,486 5,486 4,877 4,877 ADDITIONAL OPERATING HEIGHT CLEARANCE Type of Chiller ounting Neoprene Pad Isolators 44 Spring Isolators 1" Deflection 25 Direct ount 19 K3 COPRESSOR, EVAPORATOR SHELL CODES N N Q Q R R A 2,616 2,781 2,972 B 3,251 3,505 3,607 C D E 4,877 4,877 4,877 K7 COPRESSOR, EVAPORATOR SHELL CODES W W Z Y Z Z A 3,124 3,835 3,429 B 3,708 4,308 3,912 C D 749 1, E 6,706 5,486 5,486 NOTES: 1. All dimensions are approximate. 2. For compact waterboxes (shown above), determine overall unit length by adding waterbox depth to tube sheet length. 3. Water nozzles can be located on either end of unit. Add 13 mm (1/2 inch) to nozzle length for flanges connections. 4. To determine overall height, add 22 mm ( 7/8 inch) for isolators. 5. Use of motors with motor hoods may increase overall unit dimensions. Figure 16 - DIENSIONS K COPRESSOR UNITS () 28 JOHNSON CONTROLS

29 Section 2 - installation EVAPORATOR COPACT WATERBOXES - FT - IN () F F 2 ONE PASS EVAPORATORS, SHELL CODES DIENSIONS A C,D E,F G,H I,J,K,L,N P,Q R,S,W X,Z F 1'-2 1/4" (362) 1'-3" (381) 1'-3 1/2" (394) 1'-3 3/4" (400) 1'-5 1/2" (445) 1'-11 5/8" (600) 1'-11 5/8" (600) 2'-0 5/8" (625) 2'-1 3/4" (654) G F TWO PASS EVAPORATORS, SHELL CODES DIENSIONS A C,D E,F G,H I,J,K,L,N P,Q R,S,W X,Z F 1'-2 1/4" 1'-3" 1'-3 1/2" 1'-3 3/4" 1'-5 1/2" 1'-11 5/8" 1'-11 5/8" 2'-0 5/8" 2'-1 3/4" (362) (381) (394) (400) (445) (600) (600) (625) (654) G 0'-6 1/2" 0'-7" 0'-7 1/2" 0'-7 3/4" 0'-9 1/2" 1'-3 5/8" 1'-3 5/8" 1'-4 3/4" 1'-5 3/4" (165) (178) (191) (197) (241) (397) (397) (425) (451) F F THREE PASS EVAPORATORS, SHELL CODES DIENSIONS A C,D E,F G,H I,J,K,L,N P,Q R,S,W X,Z 1'-2 1/4" 1'-3" 1'-3 1/2" 1'-3 3/4" 1'-5 1/2" 1'-11 5/8" 1'-11 5/8" 2'-0 5/8" 2'-1 3/4" F (362) (381) (394) (400) (445) (600) (600) (625) (654) See Notes on page 14. LD07619 Figure 17 - DIENSIONS EVAPORATOR COPACT WATERBOXES JOHNSON CONTROLS 29

MODEL YK M3 M3 G4 THRU YK S6 S4 J2 (STYLE C) R-22 (COOLING ONLY) MODEL YK LB LB G4 THRU YK SE SC J4 (STYLE C) R-134a (COOLING ONLY)

MODEL YK M3 M3 G4 THRU YK S6 S4 J2 (STYLE C) R-22 (COOLING ONLY) MODEL YK LB LB G4 THRU YK SE SC J4 (STYLE C) R-134a (COOLING ONLY) MILLENNIUM TM CENTRIFUGAL LIQUID CHILLERS INSTALLATION INSTRUCTIONS Supersedes: Nothing 1296 FORM 160.49-N5 MODEL YK M3 M3 G4 THRU YK S6 S4 J2 (STYLE C) R-22 (COOLING ONLY) MODEL YK LB LB G4 THRU YK SE

More information

FIELD RE-ASSEMBLY FOR FORM 3 AND FORM 7 SHIPMENT MODEL YD CHILLERS - MOD A AND B WITH GRAPHIC CONTROL CENTER AND ELECTRO-MECHANICAL STARTER

FIELD RE-ASSEMBLY FOR FORM 3 AND FORM 7 SHIPMENT MODEL YD CHILLERS - MOD A AND B WITH GRAPHIC CONTROL CENTER AND ELECTRO-MECHANICAL STARTER CENTRIFUGAL LIQUID CHILLERS INSTALLATION INSTRUCTIONS Supersedes: 160.69-NM3 (912) Form 160.69-NM3 (715) FIELD RE-ASSEMBLY FOR FORM 3 AND FORM 7 SHIPMENT MODEL YD CHILLERS - MOD A AND B WITH GRAPHIC CONTROL

More information

CENTRIFUGAL LIQUID CHILLERS YMC 2 MODEL A WITH OPTIVIEW CONTROL CENTER. R-134a. INSTALLATION Supersedes: N1 (611) Form N1 (512) LD14000

CENTRIFUGAL LIQUID CHILLERS YMC 2 MODEL A WITH OPTIVIEW CONTROL CENTER. R-134a. INSTALLATION Supersedes: N1 (611) Form N1 (512) LD14000 CENTRIFUGAL LIQUID CHILLERS INSTALLATION Supersedes: 160.78-N1 (611) Form 160.78-N1 (512) YMC 2 MODEL A WITH OPTIVIEW CONTROL CENTER LD14000 R-134a Issue Date: May 30, 2012 IMPORTANT! READ BEFORE PROCEEDING!

More information

CENTRIFUGAL LIQUID CHILLERS MODEL YD (STYLE A) R-134A (COOLING ONLY) WITH OPTIVIEW CONTROL CENTER AND ELECTRO-MECHANICAL STARTER R-134A

CENTRIFUGAL LIQUID CHILLERS MODEL YD (STYLE A) R-134A (COOLING ONLY) WITH OPTIVIEW CONTROL CENTER AND ELECTRO-MECHANICAL STARTER R-134A CENTRIFUGAL LIQUID CHILLERS INSTALLATION INSTRUCTION Supersedes: 160.69-N1 (912) Form 160.69-N1 (715) MODEL YD (STYLE A) R-134A (COOLING ONLY) WITH OPTIVIEW CONTROL CENTER AND ELECTRO-MECHANICAL STARTER

More information

MODEL YST UNITS MANUFACTURED AFTER DECEMBER 2006

MODEL YST UNITS MANUFACTURED AFTER DECEMBER 2006 STEAM TURBINE CENTRIFUGAL LIQUID CHILLERS INSTALLATION INSTRUCTIONS Supersedes: 160.67-N2 (1109) Form 160.67-N2 (114) MODEL YST UNITS MANUFACTURED AFTER DECEMBER 2006 LD12189 Issue Date: January 10, 2014

More information

MODELS STEAM YIA-ST-1A1 THRU YIA-ST-14F3 HOT WATER YIA-HW-1A1 THRU YIA-HW-14F3

MODELS STEAM YIA-ST-1A1 THRU YIA-ST-14F3 HOT WATER YIA-HW-1A1 THRU YIA-HW-14F3 ABSORPTION CHILLERS WITH BUFFALO PUMPS INSTALLATION INSTRUCTIONS Supersedes: 155.16-N3 (904) Form 155.16-N3 (413) MODELS STEAM YIA-ST-1A1 THRU YIA-ST-14F3 HOT WATER YIA-HW-1A1 THRU YIA-HW-14F3 LD09451

More information

INSTALLATION, OPERATION, MAINTENANCE Supersedes: ICOM2 (1216) Form ICOM2 (318)

INSTALLATION, OPERATION, MAINTENANCE Supersedes: ICOM2 (1216) Form ICOM2 (318) MODEL YVWA DUAL COMPRESSOR 50 HZ AND 60 HZ 200-300 TONS 703-1055 KW WATER-COOLED SCREW LIQUID CHILLERS INSTALLATION, OPERATION, MAINTENANCE Supersedes: 201.30-ICOM2 (1216) Form 201.30-ICOM2 (318) 035 23322

More information

Water-Cooled Dual Compressor Screw Chiller

Water-Cooled Dual Compressor Screw Chiller Installation Manual IM 692-1 Group: Chiller Part Number: 629955 Effective: May 1997 Supersedes: IM663-1 IM683 IM692 Water-Cooled Dual Compressor Screw Chiller Installation Manual PFS 155C through PFS 210C,

More information

WATER-COOLED SCREW LIQUID CHILLERS. MODEL YVWA Dual Compressor 50 Hz and 60 Hz Tons kw. R-134a. Issue Date: April 30, 2015

WATER-COOLED SCREW LIQUID CHILLERS. MODEL YVWA Dual Compressor 50 Hz and 60 Hz Tons kw. R-134a. Issue Date: April 30, 2015 WATER-COOLED SCREW LIQUID CHILLERS INSTALLATION, OPERATION, AND MAINTENANCE Supersedes: 201.30-ICOM2 (113) Form 201.30-ICOM2 (415) MODEL YVWA Dual Compressor 50 Hz and 60 Hz 200-300 Tons 703-1055 kw 035

More information

Installation Manual IM

Installation Manual IM Installation Manual IM 1128-1 Group: Chiller Part Number: 331375601 REV: 01 Effective: April 2012 Supersedes: February 2012 WSC, WME and WMC-B Centrifugal Chillers Reassembly of Knockdown Shipments COMPRESSOR

More information

CENTRIFUGAL LIQUID CHILLERS YMC 2 MODEL A WITH OPTIVIEW CONTROL CENTER. R-134a in

CENTRIFUGAL LIQUID CHILLERS YMC 2 MODEL A WITH OPTIVIEW CONTROL CENTER. R-134a in CENTRIFUGAL LIQUID CHILLERS OPERATIONS AND MAINTENANCE Supersedes: 160.78-O1 (1112) Form 160.78-O1 (417) YMC 2 MODEL A WITH OPTIVIEW CONTROL CENTER 8.1415 in LD14000 R-134a Issue Date: April 28, 2017 IMPORTANT!

More information

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer 5/16 Rev. A 57-02509 2 Contents INTRODUCTION... 4 WARNING LABELS AND SAFETY INSTRUCTIONS... 5 PS SERIES PARALLEL

More information

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME: Supersedes: 201.28-CL2 (817) Form 201.28-CL2 (1017) MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: PHONE: JOB NAME: CUSTOMER ORDER NO: JCI CONTRACT NO: CHILLER MODEL

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS PART 0 A/E INSTRUCTIONS 0.01 Design Requirements A. Pumping system design 1. A primary-secondary pumping system is preferred. Redundant pipes are required for chillers and boilers. 2. Select pumps to operate

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions 38AH044-134 Air-Cooled Condensing Units 50/60 Hz Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

Guide Specifications

Guide Specifications Guide Specifications Hot Water fired Adsorption Liquid Chillers Bry-Air Adsorption Chiller Overview The chiller shall be a Bry-Air ADC series. The chiller shall consist of a robust, compact, packaged chiller

More information

Installation Instructions Part No , Part No Part No

Installation Instructions Part No , Part No Part No Torsion-Flex Motor mount for PSC motors and Rigid-Mount for ECM motors Replacement Kit Cancels: New Installation Instructions Part No. 327752-401, Part No. 327753-401 Part No. 327754-401 IIK-310A-45-11

More information

Installation Instructions

Installation Instructions Installation Instructions Centrifugal liquid chillers are designed to provide safe and reliable service when operated within design specifications. When operating this equipment, use good judgment and

More information

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO: Supersedes: (316) Form QTC4-CL2 (617) MODEL QTC4 EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: ADDRESS: PHONE: JOB NAME: LOCATION: CUSTOMER ORDER NO: TEL NO: ORDER NO: CONTRACT NO: CHILLER MODEL

More information

.2 Section Waste Management and Disposal.

.2 Section Waste Management and Disposal. Issued 2005/06/01 Section 15624 Packaged Rotary Screw Water Chillers Page 1 of 5 PART 1 General 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

INTRODUCTION. NOTE: Read the entire instruction manual before starting the installation. FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD

INTRODUCTION. NOTE: Read the entire instruction manual before starting the installation. FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD Installation Instructions NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance, or use can

More information

PBS did not observe any paint chips on soil at the school, and no areas of major concern were observed.

PBS did not observe any paint chips on soil at the school, and no areas of major concern were observed. January 6, 2017 Courtney Wilton Portland Public Schools 501 North Dixon Portland, OR 97227 Via email: Regarding: cwilton@pps.net Lead Paint Condition Assessment Cleveland High School 3400 SE 26th Avenue

More information

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13 R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions 38AH044-134 Air-Cooled Condensing Units 50/60 Hz Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS T CLASS TSA Series 6 to 20 Ton AIR CONDITIONERS 6 20 TONS 506147 01 06/11 Supersedes 3/11 Litho U.S.A. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE IMPORTANT The Clean Air Act

More information

KR Series Air Defrost Unit Coolers Operating and Installation Manual

KR Series Air Defrost Unit Coolers Operating and Installation Manual KR Series Air Defrost Unit Coolers Operating and Installation Manual KR Air Defrost Unit Coolers (PN E108317_L) TABLE OF CONTENTS 1 RECEIPT OF EQUIPMENT... 2 1.1 INSPECTION... 2 1.2 LOSS OF GAS HOLDING

More information

KR Electrical Defrost Unit Coolers (PN E108318_E)

KR Electrical Defrost Unit Coolers (PN E108318_E) KR Series Electric Defrost Unit Coolers Operating and Installation Manual KR Electrical Defrost Unit Coolers (PN E108318_E) TABLE OF CONTENTS 1 LOCATION RECOMMENDATIONS... 2 2 UNIT MOUNTING... 2 3 DRAIN

More information

Daikin Direct Expansion (DX) Cooling Coils

Daikin Direct Expansion (DX) Cooling Coils Installation and Maintenance Manual IM 902 Daikin Direct Expansion (DX) Cooling Coils Group: Applied Air Part Number: IM 902 Date: February 2008 Types EN, EF, ER, EJ, EK 2008 Daikin Applied Contents Introduction...

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance Series R Air-Cooled Helical Rotary Liquid Chiller RTAD 085-180 (50Hz) Standard, Free Cooling and Heat Recovery models RTAD-SVX01F-E4 General information Foreword These

More information

CS 2. Central Station Air Handlers Double Wall & Single Wall Installation, Operation & Maintenance Manual. Form No. 6120A

CS 2. Central Station Air Handlers Double Wall & Single Wall Installation, Operation & Maintenance Manual. Form No. 6120A CS 2 Central Station Air Handlers Double Wall & Single Wall Installation, Operation & Maintenance Manual Form No. 6120A TABLE OF CONTENTS Page Inspection... 2 Shipment of Units... 2 Handling... 2 Installation...

More information

IOM Installation, Operation, and Maintenance Manual. Magnitude Magnetic Bearing Centrifugal Chillers

IOM Installation, Operation, and Maintenance Manual. Magnitude Magnetic Bearing Centrifugal Chillers Installation, Operation, and Maintenance Magnitude Magnetic Bearing Centrifugal Chillers IOM 1033-5 Group: Chiller Part Number: IOM1033 Date: October 2016 Supercedes: November 2012 Model WME 400 to 700

More information

SECTION STEAM CONDENSATE PUMPS

SECTION STEAM CONDENSATE PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 22 23 STEAM CONDENSATE PUMPS SPEC WRITER NOTES: 1. Delete between // ---- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

YST PRE START-UP CHECKLIST

YST PRE START-UP CHECKLIST STEAM TURBINE CENTRIFUGAL LIQUID CHILLERS START-UP CHECKLIST Supersedes 160.67-CL1 (1108) Form 160.67-CL1 (114) YST PRE START-UP CHECKLIST OFFICE LOCATION TECHNICIAN S NAME UNIT MODEL NUMBER YORK CONTRACT

More information

Installation Instructions

Installation Instructions . AquaSnap 30MPA,MPW015-071 Liquid Chillers with Scroll Compressors and ComfortLink Controls 50/60 Hz Installation Instructions CONTENTS Page GENERAL........................................ 1 SAFETY CONSIDERATIONS.....................1,2

More information

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC!

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC! COIL Manufacturing Inc. When you want Quality, specify COLMAC! Installation, Operation, and Maintenance ENG00018621 Rev A Air Cooled Fluid Coolers Contents 1. SAFETY INSTRUCTIONS... 1 2. MODEL NOMECLATURE...

More information

THERMAPHASE INSTALLATION AND OPERATING INSTRUCTIONS

THERMAPHASE INSTALLATION AND OPERATING INSTRUCTIONS Page 1 of 10 THERMAPHASE INSTALLATION AND OPERATING INSTRUCTIONS Purpose of Manual The purpose of this manual is to provide operating, servicing and repair instructions for the Summit standard models ThermaPhase

More information

Water-Cooled Scroll Compressor Chillers

Water-Cooled Scroll Compressor Chillers Installation, and Maintenance Manual IMM WGZ-2 Group: Chiller Part Number: 331374401 Effective: October 2005 Supercedes: IOMM WGZ-1 Water-Cooled Scroll Compressor Chillers WGZ 030AW To WGZ 120AW, Packaged

More information

Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers

Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers Bulletin 1200/4 (Revised 5/12) Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers INNOVATORS IN HEAT TRANSFER I. INSTALLATION OF HEAT EXCHANGERS A. HEAT EXCHANGER SETTINGS 1)

More information

Central Station SIA Protocal

Central Station SIA Protocal Sensor name or Type AC Power Failure AT AT AT AT AT AT AT AC Power Restored AR AR AR AR AR AR AR Alarm Cancel OC OC OC Police Alarm Cancelled PH BH PH PH Auto Force Arm CF CF CF CF CF Automatic Phone Test

More information

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Page 236423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified by MSU Physical Plant

More information

Water-Cooled Scroll Compressor Chillers

Water-Cooled Scroll Compressor Chillers Installation, Operation and Maintenance Manual IOMM WGZ-1 Group: Chiller Part Number: 330389301 Effective: October 2004 Supercedes: IOMM WGZ Water-Cooled Scroll Compressor Chillers WGZ 030AW To WGZ 100AW,

More information

Model REAC / SEAC Self Contained Cooling / Electric Heating Units

Model REAC / SEAC Self Contained Cooling / Electric Heating Units Model REAC / SEAC Self Contained Cooling / Electric Heating Units Supersedes: 145.30-IOM1 (708) Form 145.30-IOM1 (908) UNIT MODELS REAC / SEAC - R22 ELECTRIC HEATING / ELECTRIC COOLING INSTALLATION, OPERATION

More information

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811 Description These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of Refrigerant R-410A for storage

More information

SECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

SECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower SECTION 15682 CENTRIFUGAL WATER CHILLERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15540 - Pumping Equipment (HVAC) 3. 15711 - Induced Draft Cooling Tower B. Removal

More information

YCIV Hz & Hz

YCIV Hz & Hz YCIV 0590-1500 50Hz & 0157-0397 60Hz Start-up Checklist SERVICE POLICY & PROCEDURES Supersedes: Nothing Form 201.23-CL1 (309) Commissioning PREPARATION Commissioning of this unit should only be carried

More information

WATER-COOLED REFRIGERANT RECOVERY AND RECYCLING UNITS

WATER-COOLED REFRIGERANT RECOVERY AND RECYCLING UNITS WATER-COOLED REFRIGERANT RECOVERY AND RECYCLING UNITS PORTABLE RECOVERY PAK EASYTANK RP 5400 RSR UNITS 1 www.res-ind.com IMPORTANT! READ BEFORE PROCEEDING! GENERAL SAFETY GUIDELINES This equipment is a

More information

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW INSTALLATION INSTRUCTIONS RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW 92-106595-01-00 TABLE OF CONTENTS Introduction.......................................

More information

Product Data. Features/Benefits. 19XB Positive Pressure Storage System

Product Data. Features/Benefits. 19XB Positive Pressure Storage System Product Data 19XB Positive Pressure Storage System 19XB028 Copyright 1992 Carrier Corporation 19XB052 Carrier s Positive Pressure Storage (PPS) System ensures the critical conservation of refrigerants

More information

Armstrong J Series Float, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual

Armstrong J Series Float, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual Armstrong J Series, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual This bulletin should be used by experienced personnel as a guide to the installation

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

Liebert CSU3000 Chiller

Liebert CSU3000 Chiller CSI 15620 - Packaged Water Chillers Liebert CSU3000 Chiller Guide Specifications for 7.5-37 Ton CS/CD/CT Models 1.0 GENERAL 1.1 CS/CD MODELS The main-frame coolant supply unit shall be a Liebert Model,

More information

Installation Instructions

Installation Instructions Installation Instructions Part No. 30RA-900---057 and 30RA-900---060 30RAP010-150 Remote Cooler Mounting Accessory SAFETY CONSIDERATIONS Installation of this accessory can be hazardous due to system pressures,

More information

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings.

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings. SECTION 15481 COMPRESSED AIR SYSTEM PART 1 - GENERAL 1.1 SECTION INCLUDES A. Pipe and pipe fittings, including valves, unions and couplings. B. Air compressor. C. After cooler. D. Refrigerated air dryer.

More information

BuildingName The Description of the Project P DOCUMENTS

BuildingName The Description of the Project P DOCUMENTS ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION

More information

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check for any interior and exterior damage, and

More information

APPLICATION DATA SHEET

APPLICATION DATA SHEET APPLICATION DATA SHEET General Piping Recommendations and Refrigerant Line Length for Split-System Air Conditioners and Heat Pumps GENERAL GUIDELINES This Split-System (Air Conditioning Condensing/Heat

More information

Remote Split System Units

Remote Split System Units Operation Maintenance Remote Split System Units Air Cooled Condensing Units and EVP Chillers Models V and Later Design Sequence RAUC-C20 RAUC-C40 RAUC-C25 RAUC-C50 RAUC-C30 RAUC-C60 October 2008 SS-SVX09A-EN

More information

Installation Instructions

Installation Instructions Installation Instructions Cased Horizontal Furnace Coil CK3B A96318 Fig. 1 Model CK3B Furnace Coil NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper

More information

IOM Installation, Operation, and Maintenance Manual. Magnitude Magnetic Bearing Centrifugal Chillers

IOM Installation, Operation, and Maintenance Manual. Magnitude Magnetic Bearing Centrifugal Chillers Installation, Operation, and Maintenance Manual Magnitude Magnetic Bearing Centrifugal Chillers IOM 1210-3 Group: Chiller Part Number: IOM1210-3 Date: June 2016 Model WMC, C Vintage 125 to 400 Tons (440

More information

Water-Cooled Modular Chillers. Product Data Catalog. Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X

Water-Cooled Modular Chillers. Product Data Catalog. Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X Product Data Catalog Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X Variable Speed Total Access Modules MS010W, MS020W, MS030W, MS050W MS010V, MS020V,

More information

Installation Owner Diagnostics

Installation Owner Diagnostics Installation Owner Diagnostics Split System Cooling Condensers Model CTA 7 1/2 to 15 Tons Models A and later Design Sequence CTA 090A***A 60 HZ 120A***A 60 HZ 120B***A 60 HZ 180B***A 60 HZ SS-SVN11A-EN

More information

MILLENNIUM TM CENTRIFUGAL LIQUID CHILLERS OPERATING & MAINTENANCE Supersedes: Nothing Form O2 (1296)

MILLENNIUM TM CENTRIFUGAL LIQUID CHILLERS OPERATING & MAINTENANCE Supersedes: Nothing Form O2 (1296) MILLENNIUM TM CENTRIFUGAL LIQUID CHILLERS OPERATING & MAINTENANCE Supersedes: Nothing Form 160.49-O2 (1296) MODEL YK M3 M3 G4 THRU YK S6 S4 J2 (STYLE C) R-22 (COOLING ONLY) MODEL YK LB LB G4 THRU YK SE

More information

65 MBH through 2890 MBH. LD16237a. June 18, 2015

65 MBH through 2890 MBH. LD16237a. June 18, 2015 AIR-COOLED CONDENSER AND FLUID COOLER INSTALLATION, OPERATION, MAINTENANCE Supersedes: 195.29-NM1 (413) Form 195.29-NM1 (615) 035 23478 100 MODEL VDC Condenser and MODEL VDCF Fluid Cooler VDC 66 Models

More information

SECTION CHILLERS

SECTION CHILLERS SECTION 15650 PART I - GENERAL 1.01 WORK INCLUDED A. Extent of work shall be as indicated on Drawings and provisions of this section, including schedules and equipment lists associated with either Drawings

More information

Installation Instructions

Installation Instructions Screw liquid chillers are designed to provide safe and reliable service when operated within design specifications. When operating this equipment, use good judgment and safety precautions to avoid damage

More information

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. Condensate Return Systems General Installation, Operation, & Service Instructions !

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. Condensate Return Systems General Installation, Operation, & Service Instructions ! Condensate Return Systems General Installation, Operation, & Service Instructions INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. SAFETY INSTRUCTIONS This safety alert symbol will be used in this

More information

Series 6, Vertical Floor-Mount Units

Series 6, Vertical Floor-Mount Units MISSION CRITICAL Air Conditioning Systems Series 6, Vertical Floor-Mount Units Installation Manual ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 Table of Contents

More information

MLCFC HMI NAVIGATION MANUAL

MLCFC HMI NAVIGATION MANUAL MLCFC HMI NAVIGATION MANUAL MOTIVAIR CORPORATION 85 WOODRIDGE DRIVE AMHERST, NY 14228 Phone# 716-691-9222 Fax# 716-691-9229 www.motivaircorp.com MAIN MENU 20:55 10/09/12 M0 Water inlet 12,0 C Water outlet

More information

Single Package Vertical R-410A A/C & H.P. UNIT MODELS VPC-B, VPP-B, & VPH-B INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

Single Package Vertical R-410A A/C & H.P. UNIT MODELS VPC-B, VPP-B, & VPH-B INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS Single Package Vertical R-410A A/C & H.P. Supersedes: 145.19-IOM1 (708) Form 145.19-IOM1 (908) UNIT MODELS VPC-B, VPP-B, & VPH-B INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS Unit Model VPC-B R-410A

More information

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program. 15682 CENTRIFUGAL WATER CHILLERS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 236416 An optional

More information

This label warns for risk of electrical shock when failing to observe.

This label warns for risk of electrical shock when failing to observe. MANUAL horizontal centrifugal pumps MB series ic drive SB series mechanical seal 1. Introduction 2. Safety precautions 3. Receipt 4. Installation / Operation and Maintenance 4.1 Installation 4.2 Operation

More information

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS 550.23-TG5Y (893) CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L2EU240 20 NOMINAL TONS DESCRIPTION This 20 ton evaporator blower is designed with two distinct modules to provide maximum application flexibility.

More information

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ)

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ) Technical Guide SUNLINE 2000 SPLIT-SYSTEM EVAPORATOR BLOWER K4EU180 15 NOMINAL TONS (WORLD 50 HZ) DESCRIPTION These completely assembled units include a well-insulated cabinet, a DX cooling coil with copper

More information

Air-Cooled Fluid Cooling Units (P/N E R2)

Air-Cooled Fluid Cooling Units (P/N E R2) Fluid Cooler Series Air-Cooled Fluid Cooling Units Operating and Installation Manual Air-Cooled Fluid Cooling Units (P/N E208134 R2) TABLE OF CONTENTS 1 RECEIPT OF EQUIPMENT 3 1.1 INSPECTION 3 1.2 LOSS

More information

Installation Instructions

Installation Instructions 8GXM / 0GXM Multi---Split High---Wall Duct Free Split System 8GXM --- Size 18k, k, and 0k 0GXM --- Size 9k, 1k, and 18k Installation Instructions NOTE: Read the entire instruction manual before starting

More information

User s Information and Installation Instructions

User s Information and Installation Instructions Outdoor Air Conditioner User s Information and Installation Instructions 10 SEER Standard Efficiency Split System These units have been designed and tested for capacity and efficiency in accordance with

More information

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS 036-21096-001 (0101) SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240 20 NOMINAL TONS DESCRIPTION This 20 ton evaporator blower is designed with two distinct modules to provide maximum application flexibility. The

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance Series R Air-Cooled Helical-Rotary Liquid Chiller Model RTAC 120-400 (50 Hz) 400-1500 kw Contents General Information 6 Unit Inspection 6 Loose Parts Inventory 6 General

More information

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check

More information

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) CS*/CD*/CP* Series Air Cooled Condensing Units Operating and Installation Manual CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) TABLE OF CONTENTS I. Receipt of Equipment 2 II. Piping...4 III. System

More information

Installation Instructions

Installation Instructions 30GTN015-035 Reciprocating Liquid Chillers with ComfortLink Controls 50/60 Hz Installation Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION.................................1-11

More information

Installation Instructions

Installation Instructions 38MPRA Outdoor Unit Single Zone Ductless System Sizes 09 to 12 Installation Instructions NOTES: Read the entire instruction manual before starting the installation. Images are for illustration purposes

More information

INFINITY FLUIDS CORPORATION

INFINITY FLUIDS CORPORATION INFINITY FLUIDS CORPORATION INFINITY FLUIDS CORPORATION 344 FRANKLIN STREET WORCESTER, MA 01522 888-565-8137 508-347-3674 CRES PRODUCT: WATER/LIQUID HEATER AIR/GAS HEATER INLINE/INSTANTANEOUS STEAM GENERATORS

More information

SECTION AIR COOLED WATER CHILLERS

SECTION AIR COOLED WATER CHILLERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Chiller package B. Charge of refrigerant and oil C. Controls and control connections D. Chilled water connections E. Starters F. Electrical power connections 1.2

More information

Installation, Operation and Maintenance Instructions for Thermax Semi-Storage Calorifier

Installation, Operation and Maintenance Instructions for Thermax Semi-Storage Calorifier OM001 Installation, Operation and Maintenance Instructions for Thermax Semi-Storage Calorifier These operating and maintenance instructions are for standard semi-storage calorifiers (vessels fitted with

More information

Installation, Operation, and Maintenance

Installation, Operation, and Maintenance Installation, Operation, and Maintenance Series E CVHH Water-Cooled CenTraVac Chillers With Tracer AdaptiView Control Model: CVHH X39641257003 SAFETY WARNING Only qualified personnel should install and

More information

SPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing N4C-0500

SPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing N4C-0500 SPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing 550.23-N4C-0500 MODEL L*BC240 035-16603 GENERAL This 20 ton evaporator blower is designed with two distinct modules

More information

Series 300 VTB. Installation Instructions

Series 300 VTB. Installation Instructions Series 300 VTB Installation Instructions Sizes 7 12 16 20 30 HP #2 Fuel Oil Gas (500 to 2500 BTU) Gas Light Oil Combination High Pressure Steam Sizes 7 thru 16 HP (125 PSI) Sizes 20 and 30 HP (150 PSI)

More information

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307 DESCRIPTION Technical Guide CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) This 20 ton evaporator blower is designed with two distinct modules to provide maximum application

More information

Installation Instructions

Installation Instructions 50ES---A, 50EZ---A, 50VL---A, 50VG---A, 50VR---A, 50VT---A, 604D--- ---A, 607C--- ---A, 607E,--- ---A, 704D--- ---A, 707C--- ---A, 707E--- ---A PA3G --- --- A, PH3G --- --- A SMALL PACKAGED PRODUCTS Electric

More information

Instruction Manual. Pharma-line ESE02198-EN Original manual

Instruction Manual. Pharma-line ESE02198-EN Original manual Instruction Manual Pharma-line ESE02198-EN 2012-05 Original manual Table of contents The information herein is correct at the time of issue but may be subject to change without prior notice 1. Description...

More information

Installation Instructions

Installation Instructions 50ES--A, 50EZ--A, 50VG--A, B, 50VL--A, B, 50VR--A, 50VT--A, B 604D-- --A, 607C-- --A, B, 607E-- --A, 704D-- --A, 707C-- --A, B, 707E-- --A PA3G -- -- A, PH3G -- -- A, PA4G, PH4G PAD3, PHD3, PAD4, PHD4,

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703 TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.

More information

Installation Instructions

Installation Instructions AQUAFORCE 30XW150-400 Water-Cooled Liquid Chillers Installation Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INTRODUCTION.................................1,2 System Design...................................

More information

TABLE OF CONTENTS ! DANGER. Dangers indicate a hazardous situation which will result in death or serious injury if not avoided. !

TABLE OF CONTENTS ! DANGER. Dangers indicate a hazardous situation which will result in death or serious injury if not avoided. ! Installation Manual IM 1137 Group: Chiller REV Part Number: IM1137 Effective: October 2011 Supersedes: New Templifier Heat Recovery Water Heaters TGZ040B to TGZ190B, Packaged Water Heater 0 to 3100 MBH

More information

568X, 587X, 588X Series

568X, 587X, 588X Series Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

4 route 147, C.P.33 Coaticook, Qc J1A 2S8

4 route 147, C.P.33 Coaticook, Qc J1A 2S8 4 route 147, C.P.33 Coaticook, Qc J1A 2S8 TABLE OF CONTENTS INSTALLATION Nozzles p.3 Clearance for dismantling p.4 Foundations p.4 Foundation bolts p.5 Leveling p.5 Bolted joints p.5 Recommended bolt tightening

More information

Direct Drive Fluid Coolers

Direct Drive Fluid Coolers H-IM-68 March 2000 Part No. 25001301 Replaces H-IM-44 Direct Drive Fluid Coolers Installation and Maintenance Data Table of Contents Inspection System Warranty Installation...2 Rigging Instructions...3

More information

MODEL YVWA VARIABLE-SPEED, WATER-COOLED SCREW COMPRESSOR CHILLERS

MODEL YVWA VARIABLE-SPEED, WATER-COOLED SCREW COMPRESSOR CHILLERS FORM 201.30-EG1 (617) MODEL YVWA VARIABLE-SPEED, WATER-COOLED SCREW COMPRESSOR CHILLERS 120-300 Tons 420-1055 kw 1 or 2 Compressors 50 and 60Hz HFC-134a FORM 201.30-EG1 (617) Nomenclature YVWA MB MB EVAP

More information