1 Searle Adiabatic (Spray) Cooling Systems INSTALLATION & MAINTENANCE

2 ADIABATIC SPRAY COOLING SYSTEM Content : Important Information 1. Adiabatic system profile 2. Health and Safety 3. Legionella 4. Warranty Procedure 5. Installation Clearance 6. Sequence controller 7. Maintenance 8. Spare parts Searle Adiabatic (Spray) Cooling Systems

3 1. ADIABATIC SYSTEMS PROFILE The Searle Adiabatic cooling system is designed to enhance the thermal performance of air-cooled condensers and dry air coolers by reducing the effective incoming air temperature. Temperature reduction is achieved by spraying water into the incoming air via a series of sparge pipes and nozzles located adjacent to the heat exchange coils. The energy used to evaporate the spray water results in a reduction in air temperature and an increase in humidity. Searle is offering the Behring technology ensuring a microbiologic control of water, in combining a destruction of biofilm (aggregate of solid particles potentially containing bacteria) by hydrodynamic cavitation, followed by a specific UV treatment suited to intermittent flows. Adiabatic Features - The following benefits and features may be achieved when fitting adiabatic systems: Fluid temperatures lower than the ambient dry bulb can be achieved when conditions are suitable. Reduction in physical size of plant. Increasing the capacity on existing systems. Standby - used as emergency capacity on critical applications or upgrades. A sequence of operation has been developed: To ensure no free standing water is left in the system when inactive for long periods. Water in the supply pipe flushes the system before high pressure nozzle spraying starts System Description Searle adiabatic cooling systems are made up of two principal assemblies. The adiabatic control box, which can be factory fitted to air-cooled condensers and dry air coolers. The sparge and nozzle assembly is factory fitted to V bank units and supplied loose (for shipment) on flat bed units. These items are also available as a retro fit kit for site upgrades. Three versions of the adiabatic control box are available: Option 1: Low pressure spraying - Without a pressurisation pump where the supply water pressure, at design low rate, is not less than 5 bar. Option 2: Average pressure spraying - A low flow rate pressurisation pump where the supply water pre sure, at design flow rate, is not less than 2 bar. Option 3: High pressure misting - A high pressurisation pump (>100bars) where the supply water pressure, at design flow rate, is not less than 2 bar. All adiabatic control boxes are fitted with water strainer, mains inlet solenoid valve, vent solenoid valve, pressure regulator and pressure gauges, pressure switch, ultraviolet lamp, hydrodynamic cavitator, scale inhibitor and a 230-volt control panel. The electronic controls are mounted in a polycarbonate box and contain a mains isolator, adiabatic sequence controller and transformer. Water is sprayed into the air stream via a sparge system made of stainless steel pipes fitted with atomising nozzles and connected together with push fittings. A drain solenoid is fitted to the lowest part of the system. 3

4 Note: pointing away from the coil face. Make the connection with the adiabatic box. Ensure that the drain solenoid is at the lowest point of the system. The drain solenoid is normally fitted onto the lowest point on the inlet of the sparge assembly (if the unit is raised on steels and the adiabatic box is remote then it may be necessary to reposition the solenoid to avoid water trapping in the pipe work). ADIABATIC SEQUENCE When water is passed through the ultra -violet lamp the dose of UV radiation received is lethal to pathogens - including Legionella - eliminating any health risks. Prior to this, all solid aggregates contained into the water (biofilm) have been destroyed by hydrodynamic cavitation, which will ensure an absolute effectiveness of the UV rays. Searle adiabatic cooling systems conform to the design requirements of ACOP L8 control of Legionella bacteria in water systems and NSF55 Class A. The adiabatic system is normally started from an external volt free signal provided by a capacity control system, BMS or emergency override. The ultraviolet lamp is switched on and the vent and drain solenoids are closed. After a set time delay the main solenoid is opened to flush the system before the pump is started. The pressure in the system and operation of the ultraviolet lamp as well as cavitation are monitored. If the water flow falls below the required limit, or the lamp fails the system will be closed down. The ultraviolet lamp and vent/drain solenoids are cycled off at the end of the day s operation, ensuring the lamp operates at full power and that flushing is not repeated unnecessarily, no free standing water is left in the system when inactive for extended periods. At the end of the sequence, the system (downstream of the main solenoid valve) has been fully drained and blown by compressed air. Searle Adiabatic (Spray) Cooling Systems

5 Control box and pipe schematic Sparge and nozzle assembly Adiabatic Control box main Inlet Strainer Mains solenoid normally closed Vent solenoid normally open Non return valve spray nozzles pointing away from the cooling coils Pump Restrictor 0-10 Bar guage 0-10 Bar gauge Bar pressure regulator UV Lamp spray nozzles pointing away from the cooling coils 1-10 Bar Pressure Switch Mechanical descaler Fitted in lowest free draining point of the system Drain solenoid normally open 5

6 TECHNICAL DATA Referring to the below tables choose the Dry Cooler/Condenser module designation and fan speed and then select the relevant letter (A, B or C) for the equivalent air velocity. Refer to the tables below for the selected letter and this will give you the adiabatic effective erature for the specified ambient conditions. Example 1 - Assume R/LFA with 080N6D fans = Table A. Assume ambient 32.0 / 50% RH / 23.6 = 27.0 o C WB effective adiabatic erature Example 2 - Assume M/DVA-L with 080N8D fans = Table C. Assume ambient 35.0 / 40% RH / 23.9 = 25.0 o C WB effective adiabatic erature Unit designation Fan designation models and speeds (Air speed codes) Module Ranges 091H6D 091H6S 091N6D 091N6S 080N6D 080N6S 080N8D 080N8S R/LF-A module A A A B A B B C R/LF-B module A A A B A B B C R/LF-C module A B A B B B B C R/LF-D module A B A B C C C C M/DVA - M A B A B A B B C M/DVB - M A B A B B B B C M/DVC - M B B B B B C C C M/DVA - L A B A B B B C C M/DVB - L B B B B B C C C M/DVC - L B C B C C C C C Table A - High air velocity Ambient o C Dry Bulb 30% RH Effective 40% RH Effective 50% RH Effective 60% RH Effective Searle Adiabatic (Spray) Cooling Systems

7 Table B - Medium air velocity Ambient 30% RH Effective o C Dry Bulb 40% RH Effective 50% RH Effective 60% RH Effective Table C - Low air velocity Ambient 30% RH Effective o C Dry Bulb 40% RH Effective 50% RH Effective 60% RH Effective

8 2. HEALTH AND SAFETY INSTRUCTION AND SIGNS This concerns the following hazards, which may be encountered when installing and maintaining this equipment: CAUTION All work on the unit s must be carried out by qualif ied personnel. Installation and maintenance manual must be kept with unit at all times. Ensure that instruction manual is understood before installation Ensure working environment is suitable. Use suitable PPE (Personal Protection Equipment) as per site regulations and as appropriate for the task. It is the responsibility of the person performing the task and their employer to ensure that all suitable PPE is provided and worn at all times. Detailed below is some of the suggested PPE during installation and commissioning of the unit. Head protection Foot protection Hand protection High visibility clothing Eye protection Before installation ELECTRICAL VOLTAGE Ensure that 1. The power supply is isolated before any installation or maintenance work is carried out. 2. The voltage, working fluid and the maximum working pressure stated on the product nameplate is suitable for the working environment. PROTECTIVE CLOTHING Sharp edges on the casework of the units and coil fins are a possible cause of cuts to fingers and hands. Appropriate protective clothing /gloves should always be worn. Ensure that: The proposed method of mounting is adequate to support the total operational weight of the unit. Dry Weights are given on the nameplate and the product sheet. Nameplate Data: When further pressure tests are carried out, the pressure applied shall not exceed 1.3 times the maximum operating pressure ( PS) given on the nameplate. When ancillary pressure equipment, such as a receiver, is supplied on a frame with a unit, but not a pipe to it, the parts must be treated as separate components and data taken from individual nameplates. Rotating blades dangling items of clothing, jewellery or any items that could be pulled into the fan set are a hazard. Keep safe working distance from the fan plate Searle Adiabatic (Spray) Cooling Systems

9 The fan guard should not be removed nor should the fanset be removed from the unit. During installation and maintenance, ensure that: The unit is installed and maintained by qualified personnel only. When pressure testing is carried out, the pressure applied shall not exceed 1.3 times the maximum operating pressure given on the nameplate of the unit. The temperature of coils with vinyl-coated fins does not exceed 150 C (e.g. during brazing), as toxic fumes would be produced. Be aware of burn hazard: Burn hazards 1. Burn hazards from pipes and pipeline components when the heat exchanger temperature exceeds 60 C. 2. Burn caused by refrigerant coming into contact with the skin or eyes. 3. LEGIONELLA An ultraviolet disinfection lamp is fitted as standard to the unit and will kill any Legionella in the supply water. (It is mandatory that the UV lamp is changed once a year. Under no circumstance should this system be run without a fully functioning disinfection lamp.) The system is designed to drain daily, so as to not harbour bacteria. Note, if the supply water temperature is lower than 20 C then multiplication of Legionella is inhibited. For this reason it is recommended that the unit is supplied directly from a cold mains whenever possible. To reduce the possibility of supply water exceeding 20 C and Legionella being in the supply water it is necessary to loop the supply, rather than create a dead leg in which water can stagnate. 9

10 4. WARRANTY PROCEDURE This warranty applies to all units detailed in this price list and, unless otherwise stated in product literature or specific contracts, provides for a manufacturer s guarantee of twenty four months from date of dispatch against faults in workmanship or materials. When submitting a warranty claim the following information is required: Customer s original reference number job / order number. Searle s job number / advice note number. Type of unit and serial number. Date of installation. Details of defect. When providing details of the defect, please give as much information as possible, Was the unit satisfactory on delivery? Frequency of fault (continuous / intermittent) Is the unit leaking? (+ location of leak) Items manufactured by Searle : No work should be undertaken to resolve the problem either by the customer or a 3rd party until approved by Searle failure to do so could invalidate the warranty. The item may be replaced or rectified if the guarantee claim is valid. For items that have been installed, Searle have the right to decide if rectification on site is suitable and who should undertake the work or whether to return / replace the unit(s). For items where Searle decides to replace, the original faulty item must be returned. All items which are returned will be inspected. If the guarantee claim is not valid the customer will be advised and further instructions requested, either to return the item or to issue an official order to replace or rectify the item. If you require a replacement product the buyer will be asked to supply a purchase order, when the unit has been returned and evaluated, the buyer will be notified by Searle if the claim is valid. Items NOT manufactured by Searle: The item will be replaced and the customer will be invoiced The item will be returned to the supplier for evaluation. If the claim is valid the credit received from the supplier will be passed on to the customer. Searle Adiabatic (Spray) Cooling Systems

11 5. INSTALLATION CLEARANCES Searle adiabatic spray system has three models in the range, two pumped and one non-pumped. The pumped systems are available with two sizes of single phase pump. All units are fitted with an ultraviolet disinfection lamp. The adiabatic system is housed in a steel IP55 enclosure and is available as a factory fitted option to all of Searle s condenser and dry cooler models. It can also be supplied as a retrofit kit for existing installations and can be remote mounted. Factory fitted units are supplied with the adiabatic box fitted to the opposite end to the inlet/outlet headers. V-bank units are supplied with the sparge pipes fully assembled; flat bed units are supplied with the sparge assemblies loose for fitting on site. This is because they would interfere with lifting the unit. Installation clearances for particular condenser/dry cooler model should be adhered to. In addition to these clearances, provision for opening the adiabatic door should be made (min 1025mm from door face). A clearance below the coil face on flat bed units is also required (min 250mm). Flat Bed Units Locate the sparge support beams under the coil at the specified pitches (refer to unit drawing) and secure to the side plates using clamps provided (note locate the channels in descending hole positions to enable a sufficient drop for draining). Fit the pipe clamps into the channels and locate the sparge pipes into the clamps, join using fittings supplied. The spray nozzles should be V Bank Units Rivet the sparge support brackets to the support beams on the coil face using the holes provided. Fit pipe clamp arrangement to appropriate fixing positions on sparge support brackets. Follow diagram for relevant positions to provide a drop that allows good drainage. The spray nozzles should be pointing across the coil face with all 3 rows pointing up at an angle of approximately 30 to the vertical. Make the connection with the adiabatic box ensuring that the lime scale inhibitor is fitted in line (if supplied loose). Ensure that the drain solenoid is at the lowest point of the system and non-return assembly at the highest. The drain solenoid is normally fitted onto the lowest point on the inlet of the sparge assembly. (If the unit is raised on steels and the adiabatic box is remote then it may be necessary to reposition the solenoid to avoid water trapping in the pipe work). All components must be handled with care during assembly. D 2 x D Fig 1 Avoid obstructions within 2 x diameter of the fan outlet 11

12 0.5L 0.15L 0.25L 0.3L Solid wall 0.5L 0.5L 0.4L 0.7L Solid obstructions along Solid obstructions along any two walls 3 side of unit(s) 0.5L Note: L = Unit Length W= Width Fig 2: Recommended dimensions for location of units to avoid inlet or outlet restrictions objects such as walls. Extended legs offer a cost effective way to reduce warm air recirculation, reducing inlet flow velocities and increasing the average distance between warm and cool air. Fig 3: Avoid wind creating additional pressure for fans to work against, particularly at low speed - < 400 rpm. Not applicable to V bank units W < 0.75 H >2m >=1m w w H Fig 4: Avoid inlet air being drawn from above the height of the outlet. Fig 5: Avoid outlet air pulled down between adjacent units Searle Adiabatic (Spray) Cooling Systems 0.3L

13 Water Supply and Drainage Ensure that the method of supply complies with local water regulations. The supply water must be clean and free from particles. Although the unit is fitted with an inline filter and some nozzle types have separate filters it is the responsibility of the end user to ensure a clean supply; no liability will be accepted for blockage of nozzles. The minimum supply pressure required is 2 bar. Ensure that the supply pipe work does not transmit any load or vibration to the unit pipe work. Supply pressure at the control valve must be positive before and during operation. A significant proportion of the delivered water is lost by evaporation, but there will be some over-spray and provision should be made for drainage. Under no circumstances should over spray water be recycled back to the spray nozzles. Units Fitted With Pumps The maximum pump flows at 3 bar are 23l/m for 2HM4T and 46l/m for 2HM5T. For exact flow rates for individual units refer to Searle quoting the operating conditions required. PUMPS ARE NOT SELF PRIMING AND REQUIRE A MINIMUM OF 2 BAR AT THE INLET. Pump ratings 2HM4 (1 phase) Input Power 0.66Kw Input Current V 2.92A 2HM5 (1 phase) Input Power 0.85Kw Input Current V 3.72A Frost Protection The pump and spray system are self-draining so frost protection is not necessary. However, frost protection is required for the supply pipes up to the mains solenoid. 13

14 6. SEQUENCE CONTROLLER Both pumped and non-pumped units are fitted with a Dedicated Function Controller, the controller is factory set using a laptop and these settings cannot be altered by the customer without a laptop and relevant Software. Two programs are available to download to the controller and have the following strategies Standard Settings Pumped: When the Enable signal is closed, the UV lamp is energised, after a warm up delay the mains solenoid is energised allowing water to fill the system for 1 minute. The pump is then started and the system allowed to pressurise, if the pressure switch (set to 3 bar) closes within 1 minute The system displays Healthy and the System will run until the enable signal is removed. If the UV switch contacts fail to close within 3 minutes or open during operation the system will lock out and Display UV Fail. The pressure switch will shut down the adiabatic system in the event of water supply failure. To reset press the ESC button. Standard Settings Non-Pumped: On enable, the UV lamp is energised, after a 1 minute delay the mains solenoid is energised allowing water directly to the nozzles. A pressure switch is incorporated with a 1 minute delay after the mains solenoid is opened, this should be set at 3 bar. The pressure switch will shut down the adiabatic system in the event of water supply failure. To reset interrupt the enable signal. Both adiabatic systems will shut down under fault conditions due to the following: If the UV lamp fails If the pump delivery pressure falls below 3 bar The controller will display its start and run functions as below, If the unit suffers a low pressure fault, then the controller will store the event even when the power is turned off. When the fault has been rectified press the ESC button to reset the controller. To employ the Back Light function press and hold any other button. 5 Commissioning Instructions Adiabatic flow 5 Bar Model 1 Fan 2 Fan 3 Fan 4 Fan 5 Fan l/m l/m l/m l/m l/m V- bank n/a Flat bed Model 2x2 FAN 2x3 FAN 2x4 FAN 2x5 FAN 2x6 FAN l/m l/m l/m l/m l/m V- bank Flat bed The adiabatic control system can be linked a number of different control systems; refer to the unit controller instructions to check the settings and to initiate the system. Before running the unit for the first time, check that all pipe joints are secure. Supply pressure at the control valve must be positive before and during operation and is recommended to be no less than 2 bar. The unit will not run unless an adequate supply is present. With condenser fans running, initiate the adiabatic system. Set the system pressure / flow rate using the flow regulator and pump bypass (pump models only). The discharge pressure should be set between 3.7 and 5 bar depending on the unit water flow requirements. Check the spray coverage is even and if necessary adjust the spray direction by rotating the sparge pipes. A pressure switch is incorporated with up to 8 minute monitoring timer (dependant on unit type) and this is factory set to close at 3 bar, this will shut down the adiabatic system in the event of water supply failure. Searle Adiabatic (Spray) Cooling Systems

15 The adiabatic system will shut down under fault conditions due to the following: 1. If the UV lamp fails 2. If the water pressure falls below 3 bar. 3. There is a monitoring timer that overrides the pressure switch for up to 8 minutes from the time the unit is enabled (factory set at 1 minute). This allows the water flow to stabilize. If the UV lamp or water supply has failed, after the set delay the timer will lock out all functions. To reset interrupt the enable signal. UNDER NO CIRCUMSTANCES SHOULD ANY OF THE ABOVE SAFETY FEATURES BE OVERRIDDEN Searle Adiabatic System Operating Sequence from Enable Signal Closing Yes UV Warm up Time Dry Contacts Close < 3 minutes and closed during normal running No Yes System pressure switch closes within 1 minute and remains closed during operation No 15

16 7. MAINTENANCE The following routine maintenance is required: When the system is in standby over the winter months it is important to initiate the system and allow the pump to run for a period of 5 minutes every 2 months to the prevent bearings drying up. Every 3 Months of use: 1. Remove and wipe clean the quartz sleeve of the UV lamp. 2. Remove and clean the strainer. 3. Check the drain tubes are clear. 4. Check for blocked nozzles and replace filters if necessary Additionally, every 12 months, in the spring: 1. Dismantle and clean nozzles, replace nozzle filters where applicable. 2. Check the coil for limescale deposition. If this is significant it is necessary to further soften the water supply. 3. It mandatory to remove and replace the UV lamp element and clean the quartz sleeve every 12 months. A lamp change record sheet is fitted inside the adiabatic box, this must be updated and the next due date recorded every time the lamp is changed. 4. Check that the pump rotates freely. 5. Run the spray system, check it functions correctly and also check the pipelines for damage / leaks and that the spray nozzles are not blocked. 6. Ensure that the system drains completely when UV lamp deactivates. Additionally, every 3 years, in the spring: 1. Upon removing UV lamp sleeve/element, both the UV lamp element and the quartz sleeve should be replaced. Lamp and sleeve can only be removed from the reactor chamber as 1 piece ensuring the user is aware of any build up of minerals on quartz sleeve. The lamp can be easily removed and replaced for maintenance. Instructions for UV Lamp replacement Shut Down 1. Shut off mains solenoid and allow system to drain. 2. Unplug the power supply and let the lamp cool for 5 minutes. 3. Squeeze the sides of the safety cap in the area opposite the tabs (do not squeeze tabs), and remove the cap. 4. Pull the lamp plug off the lamp end. Do not pull on the cord when removing the plug. Lamp Removal 1. Unscrew the lamp/sleeve assembly and carefully remove it from the reactor. Handle assembly by ends only. If required, a wrench can be placed on the two flat sides of the sleeve bolt. Do not apply the wrench to the lamp end, which sits within the sleeve bolt and protrudes 1/4. 2. To remove the lamp from its sleeve, use a glove or cloth to support and hold on to the sleeve. Holding the sleeve bolt tight, unscrew the lamp end, the top of which protrudes 1/4 above the sleeve bolt. Be careful not to drop the sleeve. If required, place an adjustable wrench on the two flat sides of the lamp end. Cleaning 1. Remove first O-ring, sleeve bolt and second O-ring from lamp sleeve. 2. Clean lamp sleeve and sleeve bolt using a soft, lint-free cotton cloth and a chemical scale-remover such as Lime-a-WayTM or CLRTM (follow manufacturer s directions). Alternatively, use spirit vinegar or hydrofluoric acid followed by mild detergent. Remove all traces of cleaning solution by thoroughly rinsing. Searle Adiabatic (Spray) Cooling Systems

17 Lamp Installation 1. Each lamp and sleeve comes with two new O-rings. Place the new O-rings and the original sleeve bolt on the lamp sleeve. Caution: Do not lubricate any of the O-rings. 1. Put the lamp completely into the sleeve. Maintain it in that position and screw the sleeve bolt into the lamp end until solidly hand-tight. 2. Carefully place the lamp/sleeve assembly into the reactor, making sure it is centred. Apply pressure to the assembly and screw it into the reactor until solidly hand-tight. Caution: Over tightening will break the quartz lamp sleeve. 1. Push the plug onto the end of the lamp while ensuring that the male tab on the lamp end meets with the female tab on the plug. 2. Push the safety cap on while ensuring that the grounding wires are under the cap and not in the way of the tabs. Restarting 1. Press and hold the push-button on UV controller. 2. Connect the power supply to the outlet while continuing to press the push-button. The indicator light will flash green. 3. Continue to hold the push-button until the indicator light flashes red, then release immediately. 4. If timer does not reset, unplug power supply, wait 15 seconds and then repeat steps 1-3 of Restarting. 5. Enable adiabatic system (force adiabatic system on). After system has filled, check for leaks Searle accepts no liability according to Searle s terms and conditions of sale, or for loss or damage arising as a result of: 1. Failure to ins tall, set up or put to work any par t of equipment in the manner specif ied in the I&M instructions, 2. Failure to maintain the equipment in the manner specified in the I&M instructions, or 3. Replacement parts, additional parts or accessories manufactured by persons other than Searle having been incorporated into, or attached to the equipment, or (iv) The equipment having been adapted for use, operated or used in such a way as does not conform to Searle s recommendations. 8. SPARE PARTS Description Part number Description Part number 2HM4 Pump 1 Phase HM5 Pump 1 Phase Inline scale inhibitor (blue)- pre spring 2005 Inline magnetic scale inhibitorpost spring Strainer c/w Ball Valve bar Pressure Regulator Spray Tip 301AF Rapid Pipe Clamp (7/8 ) Spray Tip Filter 301AF Restrictor Solenoid Valve 1/4 N/O ½ Non Return Valve Solenoid Valve 1/2 N/C Pressure Switch Solenoid Coil Millenium Controller Trojan UV Max D C/W Volt Free Contacts Pushfit 22mm Cu Straight Conn Replacement UV Bulb Trojan UV Max D Pushfit 22mm Cu Equal Tee Replacement Quartz Sleeve Trojan UV Max D Pushfit 22mm Cu Elbow Pressure Gauge 0-10 bar Pushfit Release Tool

18 Copyright Searle Adiabatic (Spray) Cooling Systems Number Issue Oct

INSTALLATION & MAINTENANCE

INSTALLATION & MAINTENANCE INSTALLATION & MAINTENANCE MODELS: UVG SLT 2 (GT7-2UVG) UVG SLT 30 (GT7-4UVG) UVG SLT 40 (GT7-8UVG) UVG SLT 75 (GT7-13UVG) UVG SLT80 UVG SLT125 (GT7-15UVG) and UVG SLT 172 Stainless Steel Water Disinfection

More information

Owner s Manual. DO NOT REMOVE FROM UNIT See back cover for vital records

Owner s Manual. DO NOT REMOVE FROM UNIT See back cover for vital records Owner s Manual DO NOT REMOVE FROM UNIT See back cover for vital records ELECTRICAL SAFETY GROUNDING This product must be grounded. If it should malfunction or breakdown, grounding provides a path of least

More information

VMS-3. Part Number: Ultraviolet Systems VMS-3. Installation, Operation & Maintenance

VMS-3. Part Number: Ultraviolet Systems VMS-3. Installation, Operation & Maintenance VMS-3 Part Number: 95-0031 Ultraviolet Systems VMS-3 Installation, Operation & Maintenance The following are the types of flags used in this technical manual. They designate safety related items and important

More information

SLT-Series Installation and maintenance instructions

SLT-Series Installation and maintenance instructions Installation and maintenance instructions MODELS UVG SLT1, UVG SLT2, UVG SLT30, UVG SLT40, UVG SLT75, UVG SLT80, UVG SLT125, UVG SLT172 ATTENTION: Please read this manual carefully and follow the instructions.

More information

1020 Industrial Drive, Orlinda, TN fax

1020 Industrial Drive, Orlinda, TN fax Operation Manual Ultraviolet Disinfection System 615-654-4441 sales@specialtyh2o.com 615-654-4449 fax TABLE OF CONTENTS Section 1 GENERAL 1.1 Warnings and Cautions... 1 1.2 Theory of Operation... 2 1.3

More information

A measured step forward

A measured step forward A measured step forward Operations & Maintenance Manual TM JESCO UV 405-412-440-450-480-550-80 2 LCD LCD PLUS Contents 1. Introduction...3 2. General Principles and Safety Instructions...4 3. Instructions

More information

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT Carrier International Sdn. Bhd. Malaysia INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT 40LM 120-200 50Hz CONTENTS: Physical Data & Dimension 1-3 Safety Considerations 4 Rigging

More information

Installation and Testing of Inverted Bucket Steam Traps Manual

Installation and Testing of Inverted Bucket Steam Traps Manual Installation and Testing of Inverted Bucket Steam Traps Manual 307-EN Please read and save these instructions Armstrong IB Traps Installation Before Installing Run pipe to trap. Before installing the trap,

More information

Operation and Maintenance Manual GLACIER TALL BASE CS5-16-VD-TB CS5-18-VD-TB2 120V/60HZ

Operation and Maintenance Manual GLACIER TALL BASE CS5-16-VD-TB CS5-18-VD-TB2 120V/60HZ Operation and Maintenance Manual GLACIER TALL BASE CS5-16-VD-TB CS5-18-VD-TB2 120V/60HZ Operation & Maintenance Manual Table of Contents: 1.0 Introduction 1 2.0 Unpacking your COOL- SPACE 1 3.0 Set-up

More information

CRU-S Series Stainless Steel Condensate Recovery Unit

CRU-S Series Stainless Steel Condensate Recovery Unit IM-UK-CRU-S UK Issue 1 CRU-S Series Stainless Steel Condensate Recovery Unit 1. Safety information 2. General product information 3. Installation 4. Commissioning 5. Storage, shutdown and equipment protection

More information

Installation, Operation, and Maintenance Information

Installation, Operation, and Maintenance Information Installation, Operation, and Maintenance Information Low Velocity Unit Coolers Bulletin No. IOM 110.3 Table of Contents Inspection... 2 Installation... 2 4 General... 2 Location... 2 Drain Line... 3 Refrigerant

More information

Operation and Maintenance Manual 120V/60HZ

Operation and Maintenance Manual 120V/60HZ Operation and Maintenance Manual 120V/60HZ GLACIER CS5-16-VD CS5-16-VD-TB CS5-18-VD CS5-18-VD-TB AVALANCHE CS6-36-1D CS6-36-VD BLIZZARD CS6-50-VD Operation & Maintenance Manual 60HZ Models Table of Contents:

More information

CHILLER. Operator s & Installation Manual

CHILLER. Operator s & Installation Manual CHILLER MODELS: CH1001-A Operator s & Installation Manual Release Date: August 9, 2002 Publication Number: 620914301 Revision Date: May 6, 2010 Revision: E Visit the IMI Cornelius web site at www.cornelius.com

More information

SEALED THERMAL STORE

SEALED THERMAL STORE ISSUE 3 0717 INSTALLATION AND USER GUIDE ENERGYMANAGER SEALED THERMAL STORE ADVANCE APPLIANCES LTD PLEASE RETAIN AND ENSURE SERVICE RECORDS ARE KEPT UP TO DATE. SCHEMATIC DIAGRAM OF ENERYMANAGER THERMAL

More information

S-Series Installation and maintenance instructions

S-Series Installation and maintenance instructions Installation and maintenance instructions MODELS UVG S30, UVG S40-62, UVG S40-76, UVG S55, UVG S75, UVG S80, UVG S80-100, UVG S125, UVG S125-100, UVG S172, UVG S172-100, UVG S160, UVG S160-100, UVG S245,

More information

Friwa Compact. Operating instructions EN

Friwa Compact. Operating instructions EN Operating instructions EN Version 1.1 / Edition 09/2013 Contents 1 Key background information... 3 1.1 Limitation of liability... 3 1.2 Responsibilities of the operator... 3 1.3 Documentation... 3 1.3.1

More information

HOT WASHER MODEL NO: KING150

HOT WASHER MODEL NO: KING150 WARNING: Do not use the hot washer without reading this manual HOT WASHER MODEL NO: KING150 PART NO: 7320175 OPERATION & MAINTENANCE INSTRUCTIONS LS1215 INTRODUCTION Thank you for purchasing this CLARKE

More information

MDX. Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain Drain Trap. Operation & Maintenance Manual MDX MODELS 18 THRU 250

MDX. Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain Drain Trap. Operation & Maintenance Manual MDX MODELS 18 THRU 250 MDX Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain Drain Trap Operation & Maintenance Manual MDX MODELS 18 THRU 250 TABLE OF CONTENTS HOW TO USE THIS MANUAL 2 SYMBOLS 2 WARRANTY

More information

rev3 INSTALLATION & OPERATION MANUAL OIL CIRCULATING HEATING SYSTEM MODEL OSM

rev3 INSTALLATION & OPERATION MANUAL OIL CIRCULATING HEATING SYSTEM MODEL OSM 216279-000 rev3 INSTALLATION & OPERATION MANUAL OIL CIRCULATING HEATING SYSTEM MODEL OSM IDENTIFYING YOUR SYSTEM IOM216279-000 The HOTSTART heating system is designed to heat fluids for use in marine

More information

Freightliner Refrigerator Troubleshooting Guide For (TJ18F) (TJ22F) (TJ18FP3)

Freightliner Refrigerator Troubleshooting Guide For (TJ18F) (TJ22F) (TJ18FP3) www.dometic.com Freightliner Refrigerator Troubleshooting Guide For Before initiating troubleshooting, the following equipment is recommended: Multimeter, 20 gauge (min) wires to use as jumpers, and 12Vdc

More information

S-Series. Protect your water from pathogens and disease with the UV-Guard S-Series. Protect:

S-Series. Protect your water from pathogens and disease with the UV-Guard S-Series. Protect: UVG S440 MW UVG S160, S245 UVG S75, S40-76 S-Series Protect your water from pathogens and disease with the UV-Guard S-Series. The S-Series is a robust and dependable UV disinfection system able to provide

More information

THERMAL SYSTEMS, INC. Installation and Operation Manual

THERMAL SYSTEMS, INC. Installation and Operation Manual THERMAL SYSTEMS, INC. Installation and Operation Manual Revised September 2016 1. GENERAL SAFETY INFORMATION 1.1 Specification Never exceed the maximum allowable temperature or pressure ratings. Never

More information

NEWGATE TECHNOLOGIES, INC.

NEWGATE TECHNOLOGIES, INC. www W.newgatetechnologies.com NEWGATE TECHNOLOGIES, INC. Installation & Operations Manual SYNERGY Series High Inlet Temperature Refrigerated Air Dryers Models SYNERGY 025 ~ SYNERGY 125 Includes Safety

More information

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model BWXP OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER Electric Heater Company Base Model "BWXP" HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203)

More information

POWERFLOW Series. Unvented Electric Storage Water Heaters. Installation & Operating Instructions Manual

POWERFLOW Series. Unvented Electric Storage Water Heaters. Installation & Operating Instructions Manual POWERFLOW Series Unvented Electric Storage Water Heaters Installation & Operating Instructions Manual These Instructions must be left with the user after installation. Version 3.0 June 2009 Hyco POWERFLOW

More information

Service Step by Step Trouble-Shooting Check-List

Service Step by Step Trouble-Shooting Check-List WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:

More information

EBAC MODEL K100 DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL K100 DEHUMIDIFIER OWNER S MANUAL EBAC MODEL K100 DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 700 Thimble Shoals Boulevard Newport News VA 23606-2575 Telephone (757) 873-6800 Fax (757) 873-3632 Website: www.ebacusa.com INTRODUCTION

More information

T-Series Air Conditioner T15 Model

T-Series Air Conditioner T15 Model INSTRUCTION MANUAL T-Series Air Conditioner T15 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200

More information

The Danger signal indicates an immediately hazardous situation which, if not avoided, will result in death or serious injury.

The Danger signal indicates an immediately hazardous situation which, if not avoided, will result in death or serious injury. The Danger signal indicates an immediately hazardous situation which, if not avoided, will result in death or serious injury. The Warning signal alerts you to potential hazards or unsafe practices which,

More information

Installation, Operation, and Maintenance Information

Installation, Operation, and Maintenance Information Installation, Operation, and Maintenance Information Air Cooled Condensers 8-2016 Rev 0 Table of Contents General Safety Information 2 Inspection 2 Installation 2 6 Rigging and Assembly 2 Unit Location

More information

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC!

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC! COIL Manufacturing Inc. When you want Quality, specify COLMAC! Installation, Operation, and Maintenance ENG00018621 Rev A Air Cooled Fluid Coolers Contents 1. SAFETY INSTRUCTIONS... 1 2. MODEL NOMECLATURE...

More information

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check

More information

Ultraviolet Water Sterilizer Installation and Maintenance Manual

Ultraviolet Water Sterilizer Installation and Maintenance Manual Ultraviolet Water Sterilizer Installation and Maintenance Manual (Models:GP-UV6W, GP-UV12W, GP-UV55W) INSTALLERS: PLEASE READ ALL INSTRUCTIONS BEFORE INSTALLING AND USING THIS SYSTEM. PERFORMANCE IS GUARANTEED

More information

INSTALLATION AND OPERATION MANUAL STEAM COIL BASE CONVECTION STEAMER MODEL SCX-16

INSTALLATION AND OPERATION MANUAL STEAM COIL BASE CONVECTION STEAMER MODEL SCX-16 INSTALLATION AND OPERATION MANUAL STEAM COIL BASE CONVECTION STEAMER MODEL SCX-16 CROWN FOOD SERVICE EQUIPMENT LTD. 70 OAKDALE ROAD, DOWNSVIEW, (TORONTO), ONTARIO, CANADA, M3N 1V9 TELEPHONE: (416) 746-2358,

More information

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N PROAIR Air Conditioner CR23 Model INSTRUCTION MANUAL Rev. D P/N 89112522 TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N T-SERIES Air Conditioner T43 Model INSTRUCTION MANUAL Rev. I P/N 10-1008-145 TABLE OF CONTENTS Warranty and Return Policy...2 IMPORTANT NOTICE...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING

More information

Operation and Maintenance Manual BLIZZARD50 CS6-50-VD 120V/60HZ

Operation and Maintenance Manual BLIZZARD50 CS6-50-VD 120V/60HZ Operation and Maintenance Manual BLIZZARD50 CS6-50-VD 120V/60HZ CS6-50-VD Operation & Maintenance Manual Table of Contents: 1.0 Introduction 1 2.0 Unpacking your COOL- SPACE 1 3.0 Set-up of COOL-SPACE

More information

"S" SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S12 S16

S SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S12 S16 Webster Pumps "S" SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S12 S16 PLEASE READ THE FOLLOWING INFORMATION PRIOR TO INSTALLING AND USING Webster PUMPS or HAYWARD VALVES,

More information

SUPER NOVA SERIES UV STERILIZER HIGH INTENSITY ULTRAVIOLET STERILIZATION

SUPER NOVA SERIES UV STERILIZER HIGH INTENSITY ULTRAVIOLET STERILIZATION SUPER NOVA SERIES UV STERILIZER HIGH INTENSITY ULTRAVIOLET STERILIZATION Thank you for selecting an Aqua Logic, Inc. Ultraviolet (UV) Sterilizer. Each model has been designed and built to provide years

More information

Installation and Use Manual

Installation and Use Manual Installation and Use Manual EMABFWS-RF and LMABFWS-RF Retrofit Bottle Filling Stations IMPORTANT THIS IS AN INDOOR APPLICATION ONLY. ALL SERVICE TO BE PERFORMED BY AN AUTHORIZED SERVICE PERSON. TOOLS REQUIRED

More information

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD425 (1018110) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 704 Middle Ground Boulevard Newport News, VA 23606 Tel: 757 873 6800 Fax: 757 873 3632 Website: www.ebacusa.com

More information

HTD. High Temperature Non-Cycling Refrigerated Compressed Air Dryers. Operation & Maintenance Manual. MODELS HTD 21 thru HTD 100

HTD. High Temperature Non-Cycling Refrigerated Compressed Air Dryers. Operation & Maintenance Manual. MODELS HTD 21 thru HTD 100 HTD High Temperature Non-Cycling Refrigerated Compressed Air Dryers Operation & Maintenance Manual MODELS HTD 21 thru HTD 100 - TABLE OF CONTENTS - 1.0 GENERAL 2 1.1 How to use this manual 1.2 Symbols

More information

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD425 (1018110) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products, Inc. 700 Thimble Shoals Blvd, Suite 109 Newport News, VA. 23606-2575 Tel: (757) 873 6800 Fax: (757) 873 3632

More information

GENESIS Air Conditioners. All Models INSTRUCTION MANUAL nvent Rev. K P/N

GENESIS Air Conditioners. All Models INSTRUCTION MANUAL nvent Rev. K P/N GENESIS Air Conditioners All Models INSTRUCTION MANUAL Rev. K P/N 89104462 TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products, Inc. 700 Thimble Shoals Blvd, Suite 109 Newport News, VA. 23606-2575 Tel: (757) 873 6800 Fax: (757) 873 3632 Website www.ebacusa.com

More information

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N SPECTRACOOL Air Conditioner N21 Model INSTRUCTION MANUAL Rev. G P/N 89115088 TABLE OF CONTENTS WARRANTY AND RETURN POLICY...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL WM150 OWNERS MANUAL Page 1 of 9 INTRODUCTION Designed for a wide range of applications, the WM150 is a rugged, industrial unit, which utilizes an

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance Series R Air-Cooled Helical Rotary Liquid Chiller RTAD 085-180 (50Hz) Standard, Free Cooling and Heat Recovery models RTAD-SVX01F-E4 General information Foreword These

More information

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett

More information

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 704 Middle Ground Boulevard Newport News, VA 23606 Tel: 757 873 6800 Fax: 757 873 3632 Website: www.ebacusa.com UNPACKING

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin WCU_O&I 01 June 2003 Condensing Unit Installation and Operating Instructions WCU Air Cooled Condensing Unit Table of Contents Section 1. Section 2. Section 3. Section 4. Section 5. Section 6.

More information

EcoCooler Legionella Risk Assessment Information Pack

EcoCooler Legionella Risk Assessment Information Pack EcoCooler Legionella Risk Assessment Information Pack Purpose of Document This information in this document is intended to provide a basis for the understanding of the risk of Legionnaires disease in EcoCooling

More information

AEM EASY DRUM M A N U A L

AEM EASY DRUM M A N U A L AEM EASY DRUM M A N U A L 1 D A A2 A1 B 2 E H K1 I F K2 J G 2 3 L Z Q N O P M 4 M S R V E X Y (2x) W (5x) U H K1 I F K2 J G 3 TERMS OF USE 1. Build in height: Water level equal to bottom drain channel

More information

Air-Cooled Fluid Cooling Units (P/N E R2)

Air-Cooled Fluid Cooling Units (P/N E R2) Fluid Cooler Series Air-Cooled Fluid Cooling Units Operating and Installation Manual Air-Cooled Fluid Cooling Units (P/N E208134 R2) TABLE OF CONTENTS 1 RECEIPT OF EQUIPMENT 3 1.1 INSPECTION 3 1.2 LOSS

More information

BLG-HGP Model Bottom Mounted Full-Length Swing Glass Door Freezer Merchandisers

BLG-HGP Model Bottom Mounted Full-Length Swing Glass Door Freezer Merchandisers Installation & Operations Manual for BLG-HGP Model Bottom Mounted Full-Length Swing Glass Door Freezer Merchandisers 2 TABLE OF CONTENTS INTRODUCTION..... 4 STORE CONDITIONS........ 4 WARNING LABELS AND

More information

Instantaneous Electric Over-Sink Hand Wash Automatic no-touch model. Installation and User Instructions

Instantaneous Electric Over-Sink Hand Wash Automatic no-touch model. Installation and User Instructions 3 Sense Instantaneous Electric Over-Sink Hand Wash Automatic no-touch model Installation and User Instructions IMPORTANT This Step-by-Step guide should be given to the customer after installation and demonstration.

More information

UNIT MODEL/ POWER SUPPLY VOLTAGE VARIATION AMBIENT AIR ON CONDENSER

UNIT MODEL/ POWER SUPPLY VOLTAGE VARIATION AMBIENT AIR ON CONDENSER Room Air Conditioner Installation and Operation Manual UNIT MODEL/ POWER SUPPLY VOLTAGE VARIATION AMBIENT AIR ON CONDENSER (VOLTS) MIN. MAX. MIN. F ( C) MAX. F ( C) WAC060K7A 127-1-60 114.3 139.7 70(20.1)

More information

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N T-SERIES Air Conditioner T29 Model INSTRUCTION MANUAL Rev. I P/N 89104464 TABLE OF CONTENTS Warranty and Return Policy...2 IMPORTANT NOTICE...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE

More information

Evaporative Cooling Equipment Installer / Contractor Pre Start-Up Checklist

Evaporative Cooling Equipment Installer / Contractor Pre Start-Up Checklist Evaporative Cooling Equipment Installer / Contractor Pre Start-Up Checklist CONTENTS 2 Safety and equipment precautions 4 Site information 4 pre Start-up Checklist The installer/contractor shall completely

More information

MDX. Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain. Operation & Maintenance Manual MODELS MDX

MDX. Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain. Operation & Maintenance Manual MODELS MDX MDX Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain Operation & Maintenance Manual MODELS MDX 800 1000 1200 TABLE OF CONTENTS HOW TO USE THIS MANUAL 2 SYMBOLS 2 WARRANTY 2 1.0

More information

MODULAR AUTOMATIC GRANULAR ICE FLAKER

MODULAR AUTOMATIC GRANULAR ICE FLAKER MODULAR AUTOMATIC GRANULAR ICE FLAKER INSTRUCTIONS AND WARNINGS 24479 rev. 03 It is strictly forbidden to reproduce this instruction manual or any part thereof. Dear Customer, Congratulations on having

More information

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL nvent Rev. I P/N

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL nvent Rev. I P/N PROAIR Air Conditioner CR29 Model INSTRUCTION MANUAL Rev. I P/N 89104461 TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

Installation & operating manual. Swimming pool water. UV disinfection device UV10+

Installation & operating manual. Swimming pool water. UV disinfection device UV10+ Installation & operating manual Swimming pool water UV10+ WARNING: UV-C radiation damages eyes and skin. Avoid direct radiation 2013 V2.5 www.vanremmen.nl Page 2 of 2 Contents 1. GENERAL... 4 2. WHAT IS

More information

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check

More information

AUTOMATIC ICE-CUBE MAKER - INSTRUCTIONS AND WARNINGS

AUTOMATIC ICE-CUBE MAKER - INSTRUCTIONS AND WARNINGS AUTOMATIC ICE-CUBE MAKER - INSTRUCTIONS AND WARNINGS Dear Customer, Congratulations on having chosen a quality product which will certainly fully meet your expectations. Thank you for having purchased

More information

Caresaver Universal Refrigerant Recovery Unit

Caresaver Universal Refrigerant Recovery Unit Operation Manual Caresaver Universal Refrigerant Recovery Unit 2 CONTENTS CHAPTER 1 INTRODUCTION AND OVERVIEW Specifications 3 Health and Safety 4-5 Component Location and Identification 6-9 CHAPTER 2

More information

Table of Contents. Specifications... page 2. Installation... page 3. Customizing... page 4. Reversing door swing... page 5

Table of Contents. Specifications... page 2. Installation... page 3. Customizing... page 4. Reversing door swing... page 5 Introduction The Scotsman Compact Refrigerator is a unique product, capable of being built into a cabinet because of its front vented, forced-air cooling system. It s also designed to be a companion to

More information

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check for any interior and exterior damage, and

More information

UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions

UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions INSPECTION When the equipment is received, all items should be carefully checked against the bill

More information

OWNER S MANUAL. High-Wall Fan Coil Unit CONTENTS

OWNER S MANUAL. High-Wall Fan Coil Unit CONTENTS OWNER S MANUAL High-Wall Fan Coil Unit Page GENERAL 2,3 OPERATING MODES 2 REMOTE CONTROL 2 OPERATION 3-9 REMOTE CONTROL OPERATION 3 INDOOR UNIT DISPLAY 5 EMERGENCY OPERATION 5 PRESSING THE ON/OFF BUTTON

More information

EBAC MODEL KOMPACT INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL KOMPACT INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL KOMPACT INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL KOMPACT OWNERS MANUAL Page 1 of 9 INTRODUCTION Designed for a wide range of applications, the Kompact is a rugged, industrial unit, which utilizes

More information

USER INSTRUCTION MANUAL. Autofill Water Boiler

USER INSTRUCTION MANUAL. Autofill Water Boiler USER INSTRUCTION MANUAL Autofill Water Boiler GH187 GC719 (FILTERED PRODUCT) Buffalo Warranty 1 Year Parts 1 Year Labour 083347300-03/06/14 Introduction Thank you for purchasing this Buffalo appliance.

More information

Glass and Dishwashers AMX / AUX Series

Glass and Dishwashers AMX / AUX Series Glass and Dishwashers AMX / AUX Series INSTALLATION OPERATION VERSION 24.02.04 Important Notes Use in Accordance with Regulations This machine is exclusively to be used to wash ware such as plates, cups,

More information

WINDOW YORK TECHNICAL GUIDE. Single package Cooling only and Heat pump. Models YO-YM R407C YO V6 G YO V7 G

WINDOW YORK TECHNICAL GUIDE. Single package Cooling only and Heat pump. Models YO-YM R407C YO V6 G YO V7 G WINDOW TECHNICAL GUIDE Single package Cooling only and Heat pump Models YO-YM 09-24 R407C YM 09 V6 G YM 09 V7 G YO 12-19-24 V6 G YO 12-19-24 V7 G YORK List of Contents Page 1 - Safety...2 2 - Unit packaging...2

More information

INSTALLATION & OPERATION MANUAL

INSTALLATION & OPERATION MANUAL 216300-000 rev2 INSTALLATION & OPERATION MANUAL OIL CIRCULATING HEATING SYSTEM FOR HAZARDOUS LOCATIONS MODEL OSE OSX (this page intentionally left blank) IDENTIFYING YOUR SYSTEM IOM216300-000 The HOTSTART

More information

Installation, Operating and Servicing Instructions

Installation, Operating and Servicing Instructions Installation, Operating and Servicing Instructions Wall Mounted Water Boiler WMB3F/B,WMB3F/W Please make a note of your product details for future use: Date Purchased: Model Number: Serial Number: Dealer:

More information

e Bath Fan with Light User s Guide

e Bath Fan with Light User s Guide e Bath Fan with Light User s Guide abfl100rnl, BFL125RNL Item Stock Number(s): BFL100RNL, BFL125RNL IMPORTANT INSTRUCTIONS - OPERATING MANUAL READ AND SAVE THESE INSTRUCTIONS READ CAREFULLY BEFORE ATTEMPTING

More information

V150 SG2E / V190 SG2E. Instructions for use

V150 SG2E / V190 SG2E. Instructions for use V150 SG2E / V190 SG2E Instructions for use Warning. In case this appliance contains hydrocarbon refrigerant please refer to guidelines listed below. As the appliance contains a flammable refrigerant, it

More information

PROAIR Air Conditioner. CR43 Model INSTRUCTION MANUAL nvent Rev. H P/N

PROAIR Air Conditioner. CR43 Model INSTRUCTION MANUAL nvent Rev. H P/N PROAIR Air Conditioner CR43 Model INSTRUCTION MANUAL Rev. H P/N 10-1008-130 TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

Manual / Handbuch Spare parts list / Ersatzteilliste

Manual / Handbuch Spare parts list / Ersatzteilliste Manual / Handbuch Spare parts list / Ersatzteilliste Equipment Imp.-Exp. GmbH Zitterpappelweg 9 D - 22391 Hamburg Tel.: + 49 40 60009468-0 Fax: + 49 40 536 75 01 E - M a i l : i n f o @ w e s c o - n a

More information

Installation and Use Manual

Installation and Use Manual Installation and Use Manual HTHB-HAC Retrofit Hydroboost Bottle Filling Station IMPORTANT THIS IS AN INDOOR APPLICATION ONLY. ALL SERVICE TO BE PERFORMED BY AN AUTHORIZED SERVICE PERSON. TOOLS REQUIRED

More information

e Bath Fan with Light User s Guide

e Bath Fan with Light User s Guide e Bath Fan with Light User s Guide abfl50uq, BFL60UQ, BFL70, BFL85 Item Stock Number(s): BFL50UQ, BFL60UQ, BFL70, BFL85 IMPORTANT INSTRUCTIONS - OPERATING MANUAL READ AND SAVE THESE INSTRUCTIONS READ CAREFULLY

More information

HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP

HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP WWPPCHLFT260 Instructions WWPPCHLFT260_Horizontal Multistage Centrifugal Pump_IB.indd 1 READ THIS MANUAL CAREFULL BEFORE INSTALL, START THE PUMP 1. Suction 2. Plug

More information

USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES

USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES Bucket Fan 420 Bucket Fan 1055 Bucket Fan 1460 420 1055 1460 2 Bucket Fan CONTENT INTRODUCTION 3 USE 3 WHAT S INCLUDED IN THE BOX 3 DESIGNATION

More information

DBF 4XL Dryer Booster Fans

DBF 4XL Dryer Booster Fans Installation and Operation Manual Item #: 401315 Rev Date: 050814 DBF 4XL Dryer Booster Fans DBF4XL Kit Includes: Dryer Booster Fan, 1 pc Fan Mounting Bracket and Hardware, 1 pc Wall Label (Mount on wasll

More information

Owner s Manual. Healthy, clean and safe. Installation, Operation and Maintenance

Owner s Manual. Healthy, clean and safe.   Installation, Operation and Maintenance Printed in Canada. Copyright 2000 Trojan Technologies Inc. London, Ontario, Canada. No part of this manual may be reproduced, stored in a retrieval system, or transmitted in any form or by any means without

More information

Operation and Maintenance Manual 120V/60HZ

Operation and Maintenance Manual 120V/60HZ Operation and Maintenance Manual 120V/60HZ GLACIER CS5-18-VD CS5-18-VD-TB AVALANCHE CS6-36-1D CS6-36-VD BLIZZARD CS6-50-VD Contents 1.0 INTRODUCTION... 1 2.0 UNPACKING YOUR COOL-SPACE UNIT... 1 3.0 SET-UP

More information

Instantaneous Electric Over-Sink Hand Wash Installation and User Instructions

Instantaneous Electric Over-Sink Hand Wash Installation and User Instructions 3 Flow Instantaneous Electric Over-Sink Hand Wash Installation and User Instructions IMPORTANT This Step-by-Step guide should be given to the customer after installation and demonstration. CONTENTS 1.

More information

DIGITAL Warm & Cool Mist Humidifier

DIGITAL Warm & Cool Mist Humidifier DIGITAL Warm & Cool Mist Humidifier FOR MODEL: EE-6902 If you have any questions about the operation of your humidifier, please contact Crane Customer Care. Toll Free: 888-599-0992 Email: customer-service@crane-usa.com

More information

AIC Brazed Plate Heat Exchanger Operating and Instruction Manual

AIC Brazed Plate Heat Exchanger Operating and Instruction Manual AIC Brazed Plate Heat Exchanger Operating and Instruction Manual Advanced Industrial Components Page 1 of 8 Customer Service Call: 1-888-738-1350 1.0 Installation 1.1 Mounting/support unit: a) On a shelf

More information

INSTALLATION AND OPERATING INSTRUCTIONS FOR RW519 RAIN WATER FILTRATION SYSTEM

INSTALLATION AND OPERATING INSTRUCTIONS FOR RW519 RAIN WATER FILTRATION SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS FOR RW519 RAIN WATER FILTRATION SYSTEM INSTALLATION CAUTIONS Installation must conform to all local and state plumbing codes and regulations. Please read carefully

More information

PERSONAL Ultrasonic Cool Mist Humidifier

PERSONAL Ultrasonic Cool Mist Humidifier PERSONAL Ultrasonic Cool Mist Humidifier FOR MODEL: EE-5951 If you have any questions about the operation of your humidifier, please contact Crane Customer Care. Toll Free: 888-599-0992 Email: customer-service@crane-usa.com

More information

SERVICE REQUIREMENTS

SERVICE REQUIREMENTS SERVICE REQUIREMENTS WARNING! Read and understand the contents of this manual before attempting to service WL350 Water Treatment System. Failure to follow the instructions in this manual could result in

More information

ENERSTORE. Vented Hot Water Storage System INSTRUCTIONS PLEASE LEAVE WITH HOUSEHOLDER

ENERSTORE. Vented Hot Water Storage System INSTRUCTIONS PLEASE LEAVE WITH HOUSEHOLDER ENERSTORE Vented Hot Water Storage System INSTRUCTIONS PLEASE LEAVE WITH HOUSEHOLDER Newark Copper Cylinder Co Ltd Brunel Drive Newark Notts. NG24 2EG Tel: 01636 678437 Fax: 01636 678964 Internet: www.newarkcoppercylinder.co.uk

More information

The Classeq under counter range

The Classeq under counter range Installation & Operators Manual The under counter range Part number 902.0011 Revision C Effective date January 2010 Language English Glasswashers Eco 1 Eco 2 Eco 3 Duo 2 Duo 3 Dishwasher Hydro 500 Hydro

More information

12 In Row. Installation Manual. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

12 In Row. Installation Manual. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc. MISSION CRITICAL Air Conditioning Systems 12 In Row Installation Manual ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 Table of Contents Table of Contents... 3 Site

More information

Glass and Dishwashers AMX / AUX Series

Glass and Dishwashers AMX / AUX Series Glass and Dishwashers AMX / AUX Series INSTALLATION OPERATION REV. 8.xx 04.07.2005 Installation and Operation Instructions for Models of AMX / AUX Series Content Page 1 Installation... 3 2 Connections...

More information

EASYCLEAR 3000 YEAR GUARANTEE

EASYCLEAR 3000 YEAR GUARANTEE 2823 3003 EASYCLEAR 3000? Hozelock Ltd. Midpoint Park, Birmingham B76 1AB. England Tel: +44 (0) 121 313 1122 info@hozelock.com www.hozelock.com 33854-005 3 YEAR GUARANTEE 1 G D B C F A E I 2 J 3 K H 4A

More information

PART 1 - GENERAL 1.1 WORK INCLUDED

PART 1 - GENERAL 1.1 WORK INCLUDED PART 1 - GENERAL 1.1 WORK INCLUDED A. Nortec ML Series high pressure adiabatic in-space system[s] as indicated on drawing[s] and as indicated on schedule[s]. B. Complete and operable humidification system

More information

Installation, operating and servicing instructions

Installation, operating and servicing instructions English 57-115 - 144-1 - 259 Installation, operating and servicing instructions ITALIA EN 1 ITALIA English INDEX WARnINGS 3 Who should read these instructions 3 Symbols 3 Recommendations 3 Importants notes

More information