Isolux Arsenic Removal Systems Central Treatment Systems Operation and Maintenance Manual

Size: px
Start display at page:

Download "Isolux Arsenic Removal Systems Central Treatment Systems Operation and Maintenance Manual"

Transcription

1 500 Point Breeze Rd. Flemington, NJ (908) Phone (908) FAX Isolux Arsenic Removal Systems Central Treatment Systems Operation and Maintenance Manual - 1

2 Contents 1. System Description 3 2. Safety Considerations 6 3. System Installation System Start-Up System Operation and Maintenance Arsenic Monitoring 9 System Operation and Maintenance... 9 Pre-Filter and Isolux Cartridge Replacement 9 Pre-Filter Service. 9 Isolux Housing Service. 10 Storage and Handling Of Isolux Cartridges 11-2

3 1. System Description Existing Chlorination Point Well Supply Header Existing Sample Existing Sample Valve No. 1 Valve No. 2 Valve No. 1 Electrical Supply (460 v/3 phase/60 Hz) By-Pass Valve Flow Totalizer Isolux Module Sample Valve No. 3 To Existing Distribution System Return Header Check Valve Valve No. 3 Sample Valve No. 4 Figure I. Typical Treatment Flow Diagram The system consists of the following components: Module No. 1 Complete 80 gpm Treatment System Comprising: A. Two 48 X 20 Coated Steel Tanks 100 psi pressure rated B. 1-1µ Stainless Steel Particulate Pre-Filter Housing C. 1-1µ Bag-Type Particulate Pre-Filter D. 1-3 hp Booster Pump, 480 v, 3-Phase E Isolux Arsenic Removal Cartridges - 3

4 The system has two coated steel tanks, or housings. The two housings combined contain 18 (eighteen) Isolux cartridges. The combined system is rated for maximum operation at 80 gpm with the two housings in parallel. The pressure drop across the system has been tested to be approximately 30 psi at 80 gpm. The following details the system specifications: Contaminant Removal Max. Flow Rate ISOLUX CTS Specifications Arsenic III & V 80 gpm # of Vessels 2 # of Cartridges 18 replaceable Isolux MC (9 per vessel) Media Bed Residence Time 27 seconds Typical Media Life* Up to 1,000,000 gal ph Range Booster Pump Flow Regulator Pre-Filter Cartridge Disposal ph Included Included 1-micron Bag Type Included Landfill or return to MEL ISOLUX CTS Technical Specifications System Footprint: 48 W x 48 L x 60 H Vessel Size: 20 OD x 48 H Number of Vessels 2 Vessel Description 200 psi (customizable) rated carbon steel with NSF grade epoxy coating Cartridge Size 4.5 OD x 42 L Cartridge Dry Weight Shipping Weight (dry) Operating Weight External Piping Outlet Connection Inlet Connection 22 lbs 1500 lbs 3200 lbs 2 Sch. 80 PVC, glued 2 PVS Slip 1 ¼ NPT Electrical Requirements 3 hp, 230/460 v, 3ph - 4

5 The system utilizes a manual flow control valve to tune the booster pump to the requirements of the site. The flow diagram shows the interconnecting piping between the well, the Isolux system, and the storage tank. The system uses a 3 hp booster pump which requires /460 v 3-phase power. The booster pump must be tied-in to the well pump so that it comes on and off with the pump. Use of a time delay relay is recommended so that there is a 10 second time delay between start-up of the well pump and start-up of the booster pumps. No time delay on shutdown is necessary. A Material Safety Data Sheet for Isolux media is included as an attachment. Further information on the pre-filter is included as an attachment. Further information on the booster pump is included as an attachment. - 5

6 2. Safety and Handling Considerations Isolux media is NSF Std. 61 certified and is non-hazardous. A Material Safety Data Sheet is included with this manual as Attachment I. Install this system on cold water only. Do not use on water lines exceeding 100 F. Maximum water pressure for this system is 100 psi. Protect the system from direct sunlight and from temperatures below 35 F. Use only NSF approved pipe dope or similar compounds on plastic pipe. Glue all joints or use Teflon tape to seal pipe thread joints. Keep exterior surfaces of the system clean with soap and water. Do not use spray cleaners or insecticides near this system. Always wear safety glasses during installation. Spent Isolux cartridges are non-hazardous and should always be disposed of properly. Isolux media and cartridges should not be exposed to air for a prolonged period before installation. Prolonged exposure to air will have a negative effect on the media or cartridge s capacity to adsorb arsenic. Isolux cartridges should remain sealed in their air-tight wrappers until just prior to installation. No work should be done on any element of the system without first shutting that element down and releasing any pressure. Lockout/Tagout procedures consistent with OSHA requirements must be employed. The pre-filter and cartridge housings are designed for a rated pressure. Operating pressure in excess of the pressure rating creates a serious safety hazard. The pre-filter and cartridge vessels are provided with pressure gages. These pressure gages must be operational at all times when the system is functioning. The pre-filter and cartridge housings are equipped with vents so that residual pressure can be vented when they are taken out of service. Never attempt to open the pre-filter or cartridge housing without first opening the vent to relieve residual pressure. - 6

7 3. System Installation Upon arrival, carefully unpack all equipment and check for damage. Remove any enclosed Operations & Maintenance Manual, data sheets, or MSDS s. Pressure gauges to be installed on the lid of each cartridge vessel have been wrapped in plastic and placed on the equipment skid. Two top tubesheets and two pre-filter bags have been packaged with the cartridge skid. Take care not to switch inlet and outlet connections during installation. Inlet and outlet connections are identified on the drawing. All interconnecting piping is Sch. 80 glued PVC, either 2 or 3 as shown in the flow diagram. Any new valves used in the installation should be one-quarter turn ball valves. As shown on the flow diagram, installation with a by-pass line around the arsenic removal system is recommended as it simplifies system startup. All valves and piping supplied on individual modules are 2-inch Sch. 80 PVC. All materials in contact with water are NSF certified or FDA compliant. Electrical supply to the booster pump must be tied into the well pump so that when the well pump starts or stops the booster pump also automatically starts or stops. Use of a time delay relay is recommended so that there is a 10 second time delay between start-up of the well pump and start-up of the booster pump. No time delay on shutdown is necessary. - 7

8 4. System Startup Initial start-up instructions assume that the well is in operation supplying the storage tank via a by-pass line, that all manual valves are closed, and that the booster pump is electrically connected but with the disconnect in the off position. Prior to initial start-up, open all housings and install the pre-filter bag and all Isolux cartridges. Do not remove the Isolux cartridges from their protective, clear plastic bags until you are ready to install them in the cartridge housings. For detailed instructions on cartridge replacement see Section 5(C). For initial start-up with a new set of cartridges: 1. Make sure the pre-filter housing and the cartridge housings are securely closed. Open the vent on the top of each of the three housings. Open the flow control valve to its maximum setting. Connect a hose to the Sample Valve No. 3 so it can drain outside of the well house. Make sure the manual inlet and outlet valves to each cartridge housing are open. 2. Slowly crack open Valve No. 1 and allow the pre-filter and cartridge housings to fill until water emerges from the vent at the top of each. Once water emerges, close the vent. 3. Open Valve No. 1 completely. Slowly open Sample Valve No. 3 and allow water to flush to the drain. Exercise caution because the initial water from the sample valve may be hot. Water temperature should return to ambient within one minute. This is a normal result of the initial activation of the media. 4. Flush approximately 405 gallons to the drain. This is equivalent to 10 bed volumes. After flushing, close Sample Valve No. 3 and open the product water shutoff valve No Slowly close the valve in the by-pass line in order to force the output of the well pump through both modules. When the by-pass line is fully closed, turn on the booster pump. 6. Adjust the flow control valve with the booster pump in operation so that the flowrate through the system matches the well pump output. 7. The system is now on-line. - 8

9 5. System Operation and Maintenance A. Arsenic Monitoring 1. Product water arsenic level should be checked within several hours of system start-up at the Sample Valve. Use a field test kit or sample bottle supplied by the laboratory that will do the analysis. Follow the laboratory or field test kit instructions. The arsenic level measured either way should be non-detectable. If any measurable arsenic result is obtained, contact Isolux immediately. 2. When taking samples for arsenic measurement, always run the sample port for several seconds before taking the sample. 3. Arsenic measurement in the product water should be performed at some frequency to be determined by regulatory requirements. Follow the field test kit or laboratory instructions. When the product arsenic level equals 80% of the applicable MCL, it is time to replace Isolux cartridges. B. System Operation During normal operation, the Isolux Arsenic Removal System requires no operator actions other than periodic measurement of the product water arsenic content. C. Pre-Filter and Isolux Cartridge Replacement Exercise caution when opening the pre-filter housing or any Isolux housing as they may be under pressure. Be sure to close both the inlet and outlet valves prior to opening any housing. If the housing is equipped with an air bleed valve at the top, open it to vent any pressure before opening the housing. Pre-filters should be changed each time Isolux cartridges are replaced. When sufficient operating experience has been accumulated, the Purchaser may decide to change prefilters on a different schedule. When servicing the Isolux system, first shutdown the booster pump and the well pump, and close the inlet and outlet shutoff valves. - 9

10 D. Pre-Filter Service: Make sure valves No. 1 and No. 3 are closed. Make sure both the well pump and the booster pump are not in operation. Remove the bolts or other devices that secure the top of the pre-filter housing and remove the top, setting it to one side. Remove any internal pieces so that the top of the bag is exposed. Remove the used bag and properly dispose of it. Install a new bag and any internal pieces holding it in place. Re-install the top and tighten the bolts or other devices that secure it in place. More detailed instructions can be found in the information from the filter manufacturer. E. Isolux Housing Service: For a two-housing system, cartridges in both housings will typically be changed at the same time. Therefore a total of 18 cartridges will be removed and replaced. Start with one housing and service it completely before starting to service the other housing. When servicing, make sure valves No. 1 and No. 3 are closed. 1. Connect a hose to the Sample Valve No. 3. Open the sample valve and the vents on the top of each housing and allow the water in the housing to drain out. 2. Remove the bolts or other devices that secure the top of the two housings and lift the top. The top is spring loaded so that it lifts easily and will remain in a vertical position while servicing is underway. Lift out the top tubesheet so that the tops of the individual cartridges are exposed. 3. Lift the spent cartridges out of the first housing. Allow any free water from the cartridges to drain back into the housing as they are removed. Remove all spent cartridges before installing any new ones. Allow the spent cartridges to stand off to one side while new cartridges are installed. This gives time for most of the free water to drain. Spent cartridges should be placed in plastic bags and disposed of properly. 4. Insert new cartridges taking care that they properly seat at the bottom of the housing. One end of each cartridge has an opening in the center. This end goes in the bottom of the housing. Lubricate this opening with any NSF certified lubricant prior to installation. The opening in each cartridge mates with a pipe nipple in the bottom tubesheet equipped with dual o-rings. The dual o-rings seat inside the cartridge opening, and the cartridge itself sits on the bottom tubesheet. - 10

11 5. Install nine cartridges in the first housing. The end of each cartridge that is now at the top of the housing has a plastic nub that projects from the center of the cartridge end. Each of these plastic nubs mates with a hole in the top tubesheet. Re-install the top tubesheet so that each of the nine cartridges is held in position by the tubesheet. 6. Close the housing lid carefully and re-secure it. Four flexible balls attached to the top tubesheet make contact with the underside of the lid and this holds the housing internals in place. 7. Repeat this procedure for the second housing. When work on both housing has been completed, see Section 4 for startup procedures. F. Storage and Handling of Isolux Cartridges Isolux cartridges contain Isolux s patented zirconium hydroxide media for adsorption of arsenic. The media is a relatively fine powder with a structure that can be affected by handling and vibration. Improper handling or excessive vibration can reduce the service lifetime of the cartridges. Follow these guidelines when handling cartridges. Isolux cartridges should always be transported and stored in an upright position. The cartridge shipping container is designed for storage. Cartridges should not be removed from the shipping container until they are ready to be installed. Keep cartridges in a cool, dry location. Protect cartridges from rain and from freezing weather. Avoid excessive vibration. Cartridges should not be stored in a truck or other vehicle in over-the-road service. - 11

Installation Instructions AS-WH Whole House Water Filter

Installation Instructions AS-WH Whole House Water Filter Installation Instructions AS-WH Whole House Water Filter Contents The AS-WH Whole House System is tested to NSF standards to reduce 97% of chlorine. It can also reduce sediment, synthetic chemicals and

More information

Whole House Descaler Installation Instructions

Whole House Descaler Installation Instructions Whole House Descaler Installation Instructions MODEL HF-SOFT Safe, effective scale prevention without the use of chemicals or salt. HF-SOFT DIRECTION OF FLOW 26" Shut-Off Valve 48" 5-Micron Pre-Filter

More information

Parts & Material Included

Parts & Material Included O² Hydro Well System Installation, Use & Care Guide Parts & Material Included 1. Funnel 11. Drain Line 21. Air Head 2. Media Tank Distributer Tube 12. Air Release 22. Drain Fitting 3. Air Tank Distributer

More information

IMPORTANT SAFETY INFORMATION READ ALL...

IMPORTANT SAFETY INFORMATION READ ALL... INSTALLATION and SERVICE MANUAL HOUSEPURE MODELS HP03 and HP04 736-0137 Table of Contents IMPORTANT SAFETY INFORMATION READ ALL... 3 P/N 41482 Rev A 06/04 INSTRUCTIONS BEFORE USING... 3 FEEDWATER... 4

More information

Installation Instructions EQ-AST-WH & EQ-AST-WH-C. Whole House Water Filter

Installation Instructions EQ-AST-WH & EQ-AST-WH-C. Whole House Water Filter Installation Instructions EQ-AST-WH & EQ-AST-WH-C Whole House Water Filter Welcome to the Aquasana experience. You are about to enjoy clean, clear water and the peace of mind that comes from knowing award

More information

Kinetico 2060f OD Sulfur Guard Installation Instructions

Kinetico 2060f OD Sulfur Guard Installation Instructions SAFETY GUIDELINES Read all steps, guides, and rules carefully before installing and using the Kinetico 2060f OD Sulfur Guard. Check your local building and sanitation codes for installation compliance.

More information

Tier1 Water Home Filtration System

Tier1 Water Home Filtration System Tier1 Water Home Filtration System Carbon+KDF Series OWNERS MANUAL BEFORE YOU BEGIN INSTALLATION, READ THIS ENTIRE MANUAL. FOLLOW THE INSTALLATION INSTRUCTIONS CAREFULLY. 1. Avoid pinched o-rings during

More information

EXTREME 4 Reverse Osmosis System

EXTREME 4 Reverse Osmosis System EXTREME 4 Reverse Osmosis System Leader Evaporator Co., Inc. 49 Jonergin Drive Swanton, VT 05488 Tel: 802-868-5444 www.leaderevaporator.com TABLE OF CONTENTS INTRODUCTION... 4 THEORY OF OPERATION... 4

More information

GROWMAX WATER Perfect Water for Plants and Gardens

GROWMAX WATER Perfect Water for Plants and Gardens GROWMAX WATER Perfect Water for Plants and Gardens WATER SYSTEMS FOR HYDROPONICS AND GARDENING GROWMAX 3000 Ultra-Pure Reverse Osmosis Water System Up to 3000 L/D of Pure Water Don't forget to register

More information

7500-S Sediment Backwash Filter Guide

7500-S Sediment Backwash Filter Guide Clean Water Made Easy. www.cleanwaterstore.com 7500-S Sediment Backwash Filter Guide Thank you for purchasing a Clean Water System! With proper installation and a little routine maintenance your system

More information

EXTREME HC-2 Reverse Osmosis System

EXTREME HC-2 Reverse Osmosis System EXTREME HC-2 Reverse Osmosis System Leader Evaporator Co., Inc. 49 Jonergin Drive Swanton, VT 05488 Tel: 802-868-5444 www.leaderevaporator.com Contents INTRODUCTION... 3 THEORY OF OPERATION... 4 Terms...

More information

Clean Water Made Easy

Clean Water Made Easy Clean Water Made Easy http://www.cleanwaterstore.com Pro-OX 1650 Iron Filter Installation & Start-Up Guide Thank you for purchasing a Clean Water System! With proper installation and a little routine maintenance

More information

Tier1 Water Home Filtration System

Tier1 Water Home Filtration System Tier1 Water Home Filtration System Salt-Free Softener OWNERS MANUAL BEFORE YOU BEGIN INSTALLATION, READ THIS ENTIRE MANUAL. FOLLOW THE INSTALLATION INSTRUCTIONS CAREFULLY. 1. Avoid pinched o-rings during

More information

HYDROGEN SULFIDE REMOVAL SYSTEMS

HYDROGEN SULFIDE REMOVAL SYSTEMS OX120U5, OX120U10 OX120B5, OX120B10 OX120U10R & OX120U5R INSTALLATION, OPERATION & SERVICE INSTRUCTIONS HYDROGEN SULFIDE REMOVAL SYSTEMS NO MEDIA NO CHEMICALS NO WASTE PRESSURE BOOSTING SYSTEM MODELS:

More information

INSTALLATION INSTRUCTIONS (please become familiar with these instructions before installing).

INSTALLATION INSTRUCTIONS (please become familiar with these instructions before installing). Customer Support: Tel: 1-347-492-4014 Email: info@pureeffectfilters.com www.pureeffectfilters.com Thank you, and Congratulations on your purchase of The PureEffect TM ULTRA-WHC Whole-House Water Filtration

More information

EXTREME 1 Reverse Osmosis System

EXTREME 1 Reverse Osmosis System EXTREME 1 Reverse Osmosis System Leader Evaporator Co., Inc. 49 Jonergin Drive Swanton, VT 05488 Tel: 802-868-5444 www.leaderevaporator.com TABLE OF CONTENTS INTRODUCTION... 4 THEORY OF OPERATION... 4

More information

WM-450-PT WM-900-PT Commercial Wall Mounted Reverse Osmosis

WM-450-PT WM-900-PT Commercial Wall Mounted Reverse Osmosis WM-450-PT WM-900-PT Commercial Wall Mounted Reverse Osmosis Installation And Service Manual Watts Pure Water 1725 W. Williams Dr. C-20., Phoenix, Arizona 85027 Phone: 888-774-7405 Fax: 602-588-0356 www.wattspurewater.com

More information

EXTREME HC-8 Reverse Osmosis System

EXTREME HC-8 Reverse Osmosis System EXTREME HC-8 Reverse Osmosis System Leader Evaporator Co., Inc. 49 Jonergin Drive Swanton, VT 05488 Tel: 802-868-5444 www.leaderevaporator.com TABLE OF CONTENTS INTRODUCTION... 4 THEORY OF OPERATION...

More information

EXTREME HP-1 Reverse Osmosis System

EXTREME HP-1 Reverse Osmosis System EXTREME HP-1 Reverse Osmosis System Leader Evaporator Co., Inc. 49 Jonergin Drive Swanton, VT 05488 Tel: 802-868-5444 www.leaderevaporator.com TABLE OF CONTENTS INTRODUCTION... 4 THEORY OF OPERATION...

More information

Technical Specifications & Pricing

Technical Specifications & Pricing Nu/Clean Model 510 Recirculating Water Deionizer Inline Aqueous Cleaning System for Closed Loop, Zero Discharge Operations Technical Specifications & Pricing The base machine in its standard configuration

More information

This material is intended only for Glass Water Systems customers. Reproduction or distribution of this material is strictly prohibited and protected.

This material is intended only for Glass Water Systems customers. Reproduction or distribution of this material is strictly prohibited and protected. This material is intended only for Glass Water Systems customers. Reproduction or distribution of this material is strictly prohibited and protected. For further questions contact Glass Water Systems or

More information

ispring Whole House Water Filter Systems USER S MANUAL

ispring Whole House Water Filter Systems USER S MANUAL ispring Whole House Water Filter Systems USER S MANUAL Version 2014-5 Introduction Congratulations on your purchase of the ispring Whole House Water Filter system. Featuring a three-stage filtration process,

More information

TITAN SYSTEM ENGINEERING DATA SHEET TITAN HXS

TITAN SYSTEM ENGINEERING DATA SHEET TITAN HXS This document and specifications are the property of REsys and shall not be reproduced or disseminated other than for recipients use for internal evaluation of REsys prices and product specifications.

More information

SYSTEMS for CATALYTIC FILTERS

SYSTEMS for CATALYTIC FILTERS OP40U5F, OP40B5F, OP80U10F, OP80B10F, OP120U15F & OP120B15F INSTALLATION, OPERATION & SERVICE INSTRUCTIONS Hydrogen Sulfide Removal SYSTEMS for CATALYTIC FILTERS NO DIAPHRAGMS OR AIR CELLS COMPLETELY CORROSION

More information

EXTREME 2 Reverse Osmosis System

EXTREME 2 Reverse Osmosis System EXTREME 2 Reverse Osmosis System Leader Evaporator Co., Inc. 49 Jonergin Drive Swanton, VT 05488 Tel: 802-868-5444 www.leaderevaporator.com TABLE OF CONTENTS INTRODUCTION... 4 THEORY OF OPERATION... 4

More information

AIR SENTRY DESICCANT BREATHERS

AIR SENTRY DESICCANT BREATHERS AIR SENTRY DESICCANT BREATHERS Extending fluid life saves money and downtime GUARDIAN BREATHERS There is no such thing as too much reliability 1 Silica Gel, Carbon 25 cfm/187 gpm Optional Yes GUARDIAN

More information

Installation, Operation and Maintenance Instructions for ThermaFlex Gasketed Plate Heat Exchangers

Installation, Operation and Maintenance Instructions for ThermaFlex Gasketed Plate Heat Exchangers OM010 Installation, Operation and Maintenance Instructions for ThermaFlex Gasketed Plate Heat Exchangers The operating and maintenance instructions contained within this package are for ThermaFlex gasketed

More information

INSTRUCTIONS FOR USE PORTABLE VACUUM SYSTEM LEI Part # s / , , , IMPORTANT INFORMATION

INSTRUCTIONS FOR USE PORTABLE VACUUM SYSTEM LEI Part # s / , , , IMPORTANT INFORMATION INSTRUCTIONS FOR USE PORTABLE VACUUM SYSTEM LEI Part # s / 27-009, 27-010, 27-015, 27-020 IMPORTANT INFORMATION UNATHORIZED CHANGES OR ALTERATIONS TO ANY LINCOLN PORTABLE VACUUM SYSTEM WILL AUTOMATICALLY

More information

Series 47 and 247 Mechanical Water Feeders. Series 47-2 and Combination Mechanical Water Feeder/Low Water Cut-Off ! WARNING

Series 47 and 247 Mechanical Water Feeders. Series 47-2 and Combination Mechanical Water Feeder/Low Water Cut-Off ! WARNING Series 47 and 247 Mechanical Water Feeders McDonnell & Miller Installation & Maintenance Instructions MM-316(C) Series 47-2 and 247-2 Combination Mechanical Water Feeder/Low Water Cut-Off Series 47 Water

More information

CWS Plus Sediment Filter Installation & Start Up Guide

CWS Plus Sediment Filter Installation & Start Up Guide Clean Water Made Easy www.cleanwaterstore.com CWS Plus Sediment Filter Installation & Start Up Guide Thank you for purchasing a Clean Water System! With proper installation and a little routine maintenance

More information

Clean Water Made Easy

Clean Water Made Easy Clean Water Made Easy http://www.cleanwaterstore.com Pro-OX 2510 Iron Filter Installation & Start- Up Guide Thank you for purchasing a Clean Water System! With proper installation and a little routine

More information

PRF-RO Pentair Reverse Osmosis System Installation and Maintenance Manual SAFETY GUIDES THE BASIC REVERSE OSMOSIS SYSTEM. Tools and Materials Required

PRF-RO Pentair Reverse Osmosis System Installation and Maintenance Manual SAFETY GUIDES THE BASIC REVERSE OSMOSIS SYSTEM. Tools and Materials Required PRF-RO Pentair Reverse Osmosis System Installation and Maintenance Manual SAFETY GUIDES Read and follow all steps and guides carefully before installing and using your reverse osmosis system. Do not use

More information

Clean Water Made Easy

Clean Water Made Easy Clean Water Made Easy http://www.cleanwaterstore.com Pro-OX 5700-E Iron Filter Installation & Start-Up Guide Thank you for purchasing a Clean Water System! With proper installation and a little routine

More information

Fleck 2510 SXT Catalox Installation & Start Up Guide

Fleck 2510 SXT Catalox Installation & Start Up Guide Fleck 2510 SXT Catalox Installation & Start Up Guide For Catalox Filters with PotPerm Bleach Solution Tank Thank you for purchasing a Clean Water System! With proper installation and a little routine maintenance

More information

1 ESMA, Inc. P. O. BOX 734 * SOUTH HOLLAND, IL * (800) * FAX (708)

1 ESMA, Inc. P. O. BOX 734 * SOUTH HOLLAND, IL * (800) * FAX (708) 1 2 Instructions for Ultrasonic Washer E789 (U.L. Approved) 1. INTRODUCTION The E789 Automatic Ultrasonic Washer automatically performs a cleaning cycle, the major steps of which are: Ultrasonic cleaning

More information

Fleck 5600 Carbon Filter Installation & Start Up Guide

Fleck 5600 Carbon Filter Installation & Start Up Guide Clean Water Made Easy www.cleanwaterstore.com Fleck 5600 Carbon Filter Installation & Start Up Guide Thank you for purchasing a Clean Water System! With proper installation and a little routine maintenance

More information

Filabot EX6 Extruder. Operation Manual. CAUTION! Read Carefully. Filabot Vermont, USA, Earth

Filabot EX6 Extruder. Operation Manual. CAUTION! Read Carefully. Filabot Vermont, USA, Earth Filabot Vermont, USA, Earth 1-802-505-6772 CAUTION! Read Carefully HOT MATERIALS & SURFACES Use gloves and eye protection while operating the EX6 Extruder. The barrel and nozzle are HOT and melted plastic

More information

EXTREME HC-4 Reverse Osmosis System Leader Evaporator Co., Inc. 49 Jonergin Drive Swanton, VT Tel:

EXTREME HC-4 Reverse Osmosis System Leader Evaporator Co., Inc. 49 Jonergin Drive Swanton, VT Tel: [Type a quote from the document or the summary of an interesting point. You can position the text box anywhere in the document. Use the Drawing Tools tab to change the formatting of the pull quote text

More information

Installation, Operation, and Maintenance Manual

Installation, Operation, and Maintenance Manual Installation, Operation, and Maintenance Manual Product Preservers Anti-Scale System Chemical-Free, Salt-Free Scale Prevention Introduction The Product Preservers Anti-Scale System will condition the tap

More information

User Manual / Care Instructions

User Manual / Care Instructions Product Code: MYWEO140 User Manual / Care Instructions PRODUCT #: MYWEO140 ITEM: Classic Wall Mount from Myson BRAND: Myson SOURCE FOR PURCHASE: SpaEquip, Inc. 211 Wappo Ave., Calistoga, CA 94515 p: 707.737.1100

More information

Installation Instructions PP-AS20 Anti-Scale System

Installation Instructions PP-AS20 Anti-Scale System Installation Instructions PP-AS20 Anti-Scale System THIS UNIT MUST BE INSTALLED BY A LICENSED PLUMBER TO VALIDATE THE WARRANTY. COMPONENTS PP-AS20 Filter Housing PP-AS20R Filter Cartridge Installation

More information

INSTALLATION MANUAL. Series 322 Ice Cube Machine SPECIFICATIONS UNPACKING. Series 322 Ice Cube Machine Installation Instructions

INSTALLATION MANUAL. Series 322 Ice Cube Machine SPECIFICATIONS UNPACKING. Series 322 Ice Cube Machine Installation Instructions INSTALLATION MANUAL Series 322 Ice Cube Machine SPECIFICATIONS 7.00 15.00 C A 6 ft electrical cord 1.00 2.00 22.00 5.00 Front 16.38 11.25 5.00 F E Air In D 2.75 2.25 14.75.75 B 23.50 21.00 Opening 23.50

More information

General System Layout Sketch

General System Layout Sketch General System Layout Sketch EZ-37 Solar Panels PV panel Glycol Fill Valve Expansion Tank ` 1 Introduction This document describes how to install a Heliatos GH type solar water heating system. These systems

More information

INSTALLATION INSTRUCTIONS WARRANTY

INSTALLATION INSTRUCTIONS WARRANTY QT FLOW CENTER INSTALLATION INSTRUCTIONS Fig. 1. Low Head Pump Center Flow Chart Fig. 2. High Head Pump Center Flow Chart NOTE: Read the entire instruction manual before starting the installation. WARRANTY

More information

VMS-3. Part Number: Ultraviolet Systems VMS-3. Installation, Operation & Maintenance

VMS-3. Part Number: Ultraviolet Systems VMS-3. Installation, Operation & Maintenance VMS-3 Part Number: 95-0031 Ultraviolet Systems VMS-3 Installation, Operation & Maintenance The following are the types of flags used in this technical manual. They designate safety related items and important

More information

Ultraviolet Systems UV-C 50 INSTALLATION INSTRUCTIONS & PRODUCT MANUAL

Ultraviolet Systems UV-C 50 INSTALLATION INSTRUCTIONS & PRODUCT MANUAL Ultraviolet Systems Inc. UV-C 50 INSTALLATION INSTRUCTIONS & PRODUCT MANUAL TABLE OF CONTENTS SECTION 1 General Information 1A. Description...1 1B. Specifications...1 SECTION 2 Installation 2A. Pool Preparation...

More information

DRY AIR SYSTEMS, INC Metro Boulevard Maryland Heights, Missouri (314) fax (314)

DRY AIR SYSTEMS, INC Metro Boulevard Maryland Heights, Missouri (314) fax (314) DRY AIR SYSTEMS, INC. 2655 Metro Boulevard Maryland Heights, Missouri 63043 (314) 344-1114 fax (314) 344-0677 HD SERIES DRIERS TABLE OF CONTENTS WHY AN AIR DRYER 3 WHAT IS A DESICCANT AIR DRYER 3 Desiccant

More information

ANSUL. Twin-Agent Fire Fighting/Securing Systems Specifications. Models 450/50-B, 450/100-B, 900/100-B INDEX SPECIFICATIONS

ANSUL. Twin-Agent Fire Fighting/Securing Systems Specifications. Models 450/50-B, 450/100-B, 900/100-B INDEX SPECIFICATIONS ANSUL Twin-Agent Fire Fighting/Securing Systems Specifications Models 450/50-B, 450/100-B, 900/100-B INDEX 1.0 GENERAL 1.1 References 1.2 Submittals 1.3 System Capabilities 1.4 Quality Control 1.5 Warranty,

More information

One Less Thing to Forget...

One Less Thing to Forget... Installation Guide One Less Thing to Forget... Sign up now for cartridge auto-renew and save 10%! Stop stressing about when to purchase your next nuvoh2o replacement cartridge. Sign up for our auto-renew

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS MODEL RLV-700 REFRIGERANT RECOVERY / RECYCLING UNIT (PATENTED) NATIONAL REFRIGERATION PRODUCTS 985 Wheeler Way Langhorne, PA 19047 (215) 638-8909 FAX (215) 638-9270 REVISED 03-21-2018

More information

COBRA -300H EXTRACTOR

COBRA -300H EXTRACTOR COBRA -300H EXTRACTOR 120V INFORMATION & OPERATING INSTRUCTIONS DO NOT OPERATE MACHINE UNTIL YOU HAVE READ ALL SECTIONS OF THIS INSTRUCTIONS IMPROPER USE OF THE MACHINE WILL VOID THE WARRANTY 1. Always

More information

Twin-Agent Fire Fighting/Securing Systems Specifications

Twin-Agent Fire Fighting/Securing Systems Specifications Twin-Agent Fire Fighting/Securing Systems Specifications Models 450/50, 450/100, 900/100 & 1350/200 INDEX 1.0 GENERAL 1.1 References 1.2 Submittals 1.3 System Capabilities 1.4 Quality Control 1.5 Warranty,

More information

120V CAUTION: DO NOT OPERATE MACHINE UNTIL YOU HAVE READ ALL SECTIONS OF THIS INSTRUCTION MANUAL IMPROPER USE OF THE MACHINE WILL VOID THE WARRANTY

120V CAUTION: DO NOT OPERATE MACHINE UNTIL YOU HAVE READ ALL SECTIONS OF THIS INSTRUCTION MANUAL IMPROPER USE OF THE MACHINE WILL VOID THE WARRANTY KING COBRA 1200 120V INFORMATION & OPERATING INSTRUCTIONS CAUTION: DO NOT OPERATE MACHINE UNTIL YOU HAVE READ ALL SECTIONS OF THIS INSTRUCTION MANUAL IMPROPER USE OF THE MACHINE WILL VOID THE WARRANTY

More information

Advanced Two-Stage Drinking Water Filter

Advanced Two-Stage Drinking Water Filter OWNER'S MANUAL E L I T E Advanced Two-Stage Drinking Water Filter MODEL NO. 625.385010 Caution: Read and follow all safety rules and operating instructions before first use of this product. Questions?

More information

TOWEL WARMERS ARE HEAVY! WE RECOMMEND THAT TWO PEOPLE INSTALL THE TOWEL WARMER!

TOWEL WARMERS ARE HEAVY! WE RECOMMEND THAT TWO PEOPLE INSTALL THE TOWEL WARMER! 1. Please follow instructions carefully to ensure that the towel warmer is properly attached to the wall or floor. FAILURE TO FOLLOW THESE STEPS COULD RESULT IN PROBLEMS. 2. Do not use an abrasive or chlorine-based

More information

Installation & Operation Manual Models:

Installation & Operation Manual Models: SJS-I-O Rev C Installation & Operation Manual Models: 60-119 : If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss

More information

The Inlet and Outlet should be as per below illustration. This will ensure that water will flow through the filter in an upflow configuration

The Inlet and Outlet should be as per below illustration. This will ensure that water will flow through the filter in an upflow configuration Owners Manual The Inlet and Outlet should be as per below illustration. This will ensure that water will flow through the filter in an upflow configuration INLET OUTLET NRV Filter FOLLOWTHE INSTALLATION

More information

OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN.

OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN. INSTALLATION, OPERATION & SERVICE MANUAL FOR COOLER TYPES OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN. 1. Introduction This manual is a guide for the installation, maintenance

More information

STOP. SAFETY INFORMATION Please read and understand this entire manual before attempting to assemble, operate or install the product.

STOP. SAFETY INFORMATION Please read and understand this entire manual before attempting to assemble, operate or install the product. STOP Power supply required Questions, problems, missing parts? Before returning to your retailer, call our customer service department at 1-800-742-5044, 7:30 a.m. - 5 p.m., EST, Monday - Friday. 115 volts

More information

A Green Solutions Company

A Green Solutions Company A Green Solutions Company INSTALLATION AND OPERATING GUIDE HIGH CAPACITY SYSTEMS MODELS: EZ010-HC, EZ017-HC, EZ025-HC (EZ010-HC PICTURED) For an overview of the EZ-FLO System Installation & operation:

More information

INFINITY FLUIDS CORPORATION

INFINITY FLUIDS CORPORATION INFINITY FLUIDS CORPORATION INFINITY FLUIDS CORPORATION 344 FRANKLIN STREET WORCESTER, MA 01522 888-565-8137 508-347-3674 CRES PRODUCT: WATER/LIQUID HEATER AIR/GAS HEATER INLINE/INSTANTANEOUS STEAM GENERATORS

More information

Professional Series. Chemical Feed System Model # US Patent No. 6,752,930 B2

Professional Series. Chemical Feed System Model # US Patent No. 6,752,930 B2 Professional Series Chemical Feed System Model # 22152-02 US Patent No. 6,752,930 B2 Product Manual SureWater Technologies, Inc. The Solution X-2 Model # 22152-02 Table of Contents 1. Installation Instruction

More information

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings.

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings. SECTION 15481 COMPRESSED AIR SYSTEM PART 1 - GENERAL 1.1 SECTION INCLUDES A. Pipe and pipe fittings, including valves, unions and couplings. B. Air compressor. C. After cooler. D. Refrigerated air dryer.

More information

451 Black Forest Road Hull, IA Ph: (712) Fax: (712) TS g/hr Turnkey Ozone Generation System

451 Black Forest Road Hull, IA Ph: (712) Fax: (712) TS g/hr Turnkey Ozone Generation System 451 Black Forest Road Hull, IA 51239 Ph: (712) 439-6880 Fax: (712) 439-6733 TS-40 40 g/hr Turnkey Ozone Generation System Installation and Operation Manual TS-40 Manual Cautions, Warnings and Hazards

More information

Aer-Max Installation Instructions

Aer-Max Installation Instructions Aer-Max Installation Instructions Congratulations on selecting this quality Aer-Max system. Important: Please read all instructions before assembling and installing the Aer-Max system. Consult local plumbing

More information

SuperKlean Washdown Products

SuperKlean Washdown Products February 2012 DURAMIX 8000 INSTALLATION AND MAINTENANCE INSTRUCTIONS **DO NOT THROW AWAY AFTER INSTALLATION** **SAVE AND DISPLAY PROMINENTLY WHERE THIS EQUIPMENT IS USED** WARNING HIGH PRESSURE AND HOT

More information

SECTION DOMESTIC WATER PIPING SPECIALTIES

SECTION DOMESTIC WATER PIPING SPECIALTIES SECTION 22 11 19 DOMESTIC WATER PIPING SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Clean Water Made Easy. CWS Time Clock Softener Installation & Start Up Guide. Questions?

Clean Water Made Easy. CWS Time Clock Softener Installation & Start Up Guide. Questions? Clean Water Made Easy www.cleanwaterstore.com CWS Time Clock Softener Installation & Start Up Guide Thank you for purchasing a Clean Water System! With proper installation and a little routine maintenance

More information

General System Layout Sketch

General System Layout Sketch General System Layout Sketch EZ-37 Solar Panels PV panel Can use Standard Copper, CPVC or PEX Pipes Pump Existing Water Heater Bottom Feed Connector 1 Introduction This document describes how to install

More information

FILTRATION SYSTEM MODEL: FILTER - 5 MULTI-SHIFTER, INC. P.O. BOX CHARLOTTE, N.C TEL#: FAX#:

FILTRATION SYSTEM MODEL: FILTER - 5 MULTI-SHIFTER, INC. P.O. BOX CHARLOTTE, N.C TEL#: FAX#: FILTRATION SYSTEM MODEL: FILTER - 5 MULTI-SHIFTER, INC. P.O. BOX 411047 CHARLOTTE, N.C. 28241-1047 TEL#: 1-704-588-9611 FAX#: 1-704-588-4730 CONTENTS 1. System Overview 2. Air and Electrical Requirements

More information

ARV -3 & ARV -10 Active Reservoir Vent Installation and Operation Manual

ARV -3 & ARV -10 Active Reservoir Vent Installation and Operation Manual ARV -3 & ARV -10 Active Reservoir Vent Installation and Operation Manual Manual P568800 Rev 1, Mar 30, 2010 1 As the installer or operator, you should make yourself familiar with this Installation and

More information

5700-E Sediment Filter Installation & Start-Up Guide

5700-E Sediment Filter Installation & Start-Up Guide Clean Water Made Easy www.cleanwaterstore.com 5700-E Sediment Filter Installation & Start-Up Guide Thank you for purchasing a Clean Water System! With proper installation and a little routine maintenance

More information

4-1 1 / 2 " Tees / 2 " hole saw w/ 1/4" drill bit / 2 " Male slip plugs

4-1 1 / 2  Tees / 2  hole saw w/ 1/4 drill bit / 2  Male slip plugs Section 1: Parts List 1-50 Flex PVC pipe 2-1 1 / 2 " Ball Valves 4-1/2" 90 degree elbows 4 - Lengths of 1/2" PVC 4 - Jet bodies 4 - Jet nozzles 4 - Female slip/female slip unions 2 - Female slip/fpt union

More information

LABORATORY ULTRA ZERO AIR GENERATOR. ZAC-ULT Series USER MANUAL

LABORATORY ULTRA ZERO AIR GENERATOR. ZAC-ULT Series USER MANUAL LABORATORY ULTRA ZERO AIR GENERATOR ZAC-ULT Series USER MANUAL 166 Keystone Drive Montgomeryville, PA 18936 Telephone: 215-641-2700 Fax: 215-641-2714 Email: mtgmmville@matheson-trigas.com INT-0261-XX rev

More information

Installation & Service Guide

Installation & Service Guide Reverse Osmosis Ontario Soft Water.ca Kitchener, Canada 519-579-0500 Installation & Service Guide Pentair 75 gpd Encapsulated Membrane System Standard System 75gpd Membrane Your New Reverse Osmosis System

More information

INFORMATION & OPERATING INSTRUCTIONS

INFORMATION & OPERATING INSTRUCTIONS KING COBRA 310 120V INFORMATION & OPERATING INSTRUCTIONS DO NOT OPERATE MACHINE UNTIL YOU HAVE READ ALL SECTIONS OF THE INSTRUCTIONS IMPROPER USE OF THE MACHINE WILL VOID THE WARRANTY 1. Always use a defoamer

More information

WILKERSON MODELS DE3, DE4 AND DE5 COMPACT HEATLESS AIR DRYERS

WILKERSON MODELS DE3, DE4 AND DE5 COMPACT HEATLESS AIR DRYERS INSTRUCTION MANUAL FOR WILKERSON MODELS DE3, DE4 AND DE5 COMPACT HEATLESS AIR DRYERS DE3 - DE5 OPERATIONS GENERAL This instruction manual covers the installation, operation, maintenance and troubleshooting

More information

215 Gallon Waste Oil Tank With Bypass Regulator Installation Instructions

215 Gallon Waste Oil Tank With Bypass Regulator Installation Instructions 215 Gallon Waste Oil Tank With Bypass Regulator Installation Instructions Lanair Products LLC 4109 Capital Circle Janesville, Wisconsin 53546 1-888-370-6531 www.lanair.com BEFORE YOU BEGIN INSTALLATION...

More information

Installation, Operation and Maintenance Instructions ThermaFlex Gasketed Plate Heat Exchanger OM010

Installation, Operation and Maintenance Instructions ThermaFlex Gasketed Plate Heat Exchanger OM010 Installation, Operation and Maintenance Instructions ThermaFlex Gasketed Plate Heat Exchanger OM010 Calorifiers Heat Exchangers Pressurisation Units Sales Tel: 01457 835700 Sales Fax: 01457 832700 E-mail:

More information

OWNERS GUIDE TO INSTALLATION AND OPERATION

OWNERS GUIDE TO INSTALLATION AND OPERATION OWNERS GUIDE TO INSTALLATION AND OPERATION SPM SERIES HIGH POWER CENTRIFUGALS READ THESE INSTRUCTIONS CAREFULLY Read these installation instructions in detail before installing your pump. Be sure to check

More information

the condensate management specialist PURO-CT Sustainable Condensate Management CONDENSATE SEPARATORS

the condensate management specialist PURO-CT Sustainable Condensate Management CONDENSATE SEPARATORS the condensate management specialist PURO-CT CONDENSATE SEPARATORS Sustainable Condensate Management A typical compressed air system will produce thousands of gallons of oily, contaminated condensate every

More information

Installation and Operation Manual. ACF-18 Automatic Chlorinating Feeder

Installation and Operation Manual. ACF-18 Automatic Chlorinating Feeder Installation and Operation Manual ACF-18 Automatic Chlorinating Feeder Operating Specifications Inlet Flow: 1.0-1.5 gpm Outlet Flow: = Inlet Flow Inlet Pressure: 10-45 psi Maximum Output: 26 lbs. of Available

More information

TECHNICAL DATA. Wet 26a. February 22, 2009

TECHNICAL DATA. Wet 26a. February 22, 2009 February 22, 2009 Wet 26a 1. DESCRIPTION The Viking Alarm Check Valve serves as a check valve by trapping pressurized water above the clapper and preventing reverse flow from sprinkler piping. The valve

More information

ECONO FLO 2.7HP VARIABLE SPEED PUMP OWNER S MANUAL

ECONO FLO 2.7HP VARIABLE SPEED PUMP OWNER S MANUAL ECONO FLO 2.7HP VARIABLE SPEED PUMP OWNER S MANUAL IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS WARNING: Before installing this product, read and follow all warning

More information

SMF PUMP OWNER S MANUAL

SMF PUMP OWNER S MANUAL SMF PUMP OWNER S MANUAL IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS WARNING: Before installing this product, read and follow all warning notices and instructions

More information

Rev B, 9/2/2009. Kodiak Chiller Overview

Rev B, 9/2/2009. Kodiak Chiller Overview 930-0001 Rev B, 9/2/2009 Kodiak Chiller Overview Presentation Outline Phone: 781-933-7300 Lytron Technical Support Contact Information 3 Introduction 4 Part I: Unpacking 5 Part II: Installation 7 Part

More information

OWNER S MANUAL AND INSTALLATION GUIDE PLEASE READ THIS MANUAL CAREFULLY BEFORE ATTEMPTING INSTALLATION

OWNER S MANUAL AND INSTALLATION GUIDE PLEASE READ THIS MANUAL CAREFULLY BEFORE ATTEMPTING INSTALLATION ClearChoice Economy Under Sink Drinking Water System OWNER S MANUAL AND INSTALLATION GUIDE PLEASE READ THIS MANUAL CAREFULLY BEFORE ATTEMPTING INSTALLATION Congratulations on the purchase of your ClearChoice

More information

WATER FILTRATION SYSTEM (USF3) OWNER S MANUAL

WATER FILTRATION SYSTEM (USF3) OWNER S MANUAL WATER FILTRATION SYSTEM (USF3) OWNER S MANUAL 1 INTRODUCTION Congratulations on choosing Permatech to improve the quality of your water. You will immediately begin to notice the numerous benefits of having

More information

OptiSoft Softeners Simple Install Steps 1-17

OptiSoft Softeners Simple Install Steps 1-17 OptiSoft Softeners Simple Install Steps 1-17 (models OS-10, OS-13, OS-20 & OS-29) Refer to Installation, Operation & Maintenance Manual for More Details v Installation Requirements Installation must conform

More information

Standard Installation Manual

Standard Installation Manual Standard Installation Manual READ THIS MANUAL BEFORE INSTALLATION Caution If you plan to install your solar heater system on a roof be sure you are experienced in working on roofs and have the proper safety

More information

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC!

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC! COIL Manufacturing Inc. When you want Quality, specify COLMAC! Installation, Operation, and Maintenance ENG00018621 Rev A Air Cooled Fluid Coolers Contents 1. SAFETY INSTRUCTIONS... 1 2. MODEL NOMECLATURE...

More information

SAFE DRINKING WATER AND TOXIC ENFORCEMENT ACT

SAFE DRINKING WATER AND TOXIC ENFORCEMENT ACT Installation instructions for your new Spacemaker Laundry WSM2780 Gas Before you begin Read these instructions completely and carefully. IMPORTANT OBSERVE ALL GOVERNING CODES AND ORDINANCES. Note to Installer

More information

I-VICFLEX.AB4. Victaulic VicFlex Style AB4 Sprinkler Fitting for Hat Furring Channel Ceiling Systems WARNING INSTALLATION INSTRUCTIONS

I-VICFLEX.AB4. Victaulic VicFlex Style AB4 Sprinkler Fitting for Hat Furring Channel Ceiling Systems WARNING INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS I-VICFLEX.AB Victaulic VicFlex Style AB Sprinkler Fitting for Hat Furring Channel Ceiling Systems Read and understand all instructions before attempting to install any Victaulic

More information

Instructions for Model E782 Betman Cleaning System (Cleaner/Rinser/Rinser/Dryer)

Instructions for Model E782 Betman Cleaning System (Cleaner/Rinser/Rinser/Dryer) 1 2 Esma Inc. PO Box 734 450 W. Taft Drive South Holland, IL 60473 708-331-1855 800-276-2466 FAX 708-331-8919 Introduction Instructions for Model E782 Betman Cleaning System (Cleaner/Rinser/Rinser/Dryer)

More information

NBSeries Installation Operation & Maintenance

NBSeries Installation Operation & Maintenance Revised - March, 208 NBSeries Installation Operation & Maintenance Models: NB-6-P Acidic Condensate ph Treatment Tank/Pump Coleman Ave. Westfield, MA 0085-527-89 690 Island Way Unit 206, Clearwater, FL

More information

Installation Instructions

Installation Instructions Installation Instructions 6 KW and 11.5KW Basic Circulation Water Heater and Pump Application: The Basic Circulation Water Heater has been in use for nearly 50 years, and it is the most prevalent model

More information

STORAGE TANK INSTALLATION and OPERATION MANUAL

STORAGE TANK INSTALLATION and OPERATION MANUAL LST-I-O 100161529_2000014416 Rev F STORAGE TANK INSTALLATION and OPERATION MANUAL LOW LEAD CONTENT The information contained in this manual is intended for use by qualified professional installers, or

More information

7800 Neutralizer Installation & Start-Up Guide

7800 Neutralizer Installation & Start-Up Guide Clean Water Made Easy www.cleanwaterstore.com 7800 Neutralizer Installation & Start-Up Guide Thank you for purchasing a Clean Water System! With proper installation and a little routine maintenance your

More information

Installation Manual PS-225 & PS-275

Installation Manual PS-225 & PS-275 Installation Manual PS-225 & PS-275 Table of Contents Pre-Uncrating Checklist... 1 Verifying System Requirements... 2 Verifying System Direction... 2 Verifying the Electrical Requirements... 2 Removal

More information

FOR THE RECORD. You should record the model and serial numbers, which can be found on the back of the unit, for future reference.

FOR THE RECORD. You should record the model and serial numbers, which can be found on the back of the unit, for future reference. FOR THE RECORD You should record the model and serial numbers, which can be found on the back of the unit, for future reference. Warranty: 18 mo. on unit and 1 year on check valve assembly Model: The Ozone

More information