1 Operation & Maintenance Manual OMM Group: Chiller Part Number: Effective: November 2012 Supersedes: July 2012 Magnitude Magnetic Bearing Centrifugal Chillers Model WME Software Version:

2 Table of Contents Introduction...3 Features of the Control Panel...8 General Description...9 Component Description...10 Operator Interface Touch Screen...10 Unit Controller...10 Motor/Compressor Controller VFD Controller VFD Description: Key VFD Control Signals...12 Inputs and Outputs...12 Optional Harmonic Filters...15 Field Wiring Data...16 Operator Interface Touch Screen (OITS)19 Navigation...19 SET Screens...25 Service Screens...40 Downloading Data...41 Chiller Alarms...42 Trend Screens...46 Operating the Chiller Interface Panel On/Off Start/Stop Unit Changing Setpoints Sequence of Operation Troubleshooting Operation with Failed OITS Maintenance External Sensors and Valve Locations Routine Maintenance Annual Shutdown Annual Startup Repair of System Maintenance Schedule Service Programs Operator Training Warranty Statement Recognize Safety Symbols, Words, and Labels The following symbols and labels indicate immediate or potential hazards. Read and comply with all safety information and instructions accompanying these symbols. Failure to heed safety information increases the risk of property and/or product damage, serious injury or death. Improper installation, operation and maintenance can void the warranty. CAUTION Cautions indicate potentially hazardous situations, which can result in personal injury or equipment damage if not avoided. WARNING Warnings indicate potentially hazardous situations, which can result in property damage, personal injury, or death if not avoided. DANGER Dangers indicate a hazardous situation which will result in death or serious injury if not avoided Daikin Applied. Illustrations and data cover the McQuay product at the time of publication and we reserve the right to make changes in design and construction at anytime without notice. The following are trademarks or registered trademarks of their respective companies: BACnet from ASHRAE; LONMARK, LonTalk, LONWORKS, and the LONMARK logo are managed, granted and used by LONMARK International under a license granted by Echelon Corporation; Modbus from Schneider Electric; Victaulic from Victaulic Company; Magnitude, Energy Analyze, MicroTech E, Open Choices from McQuay International. 2 OMM

3 Introduction This manual provides operating, maintenance and troubleshooting information for the McQuay Magnitude frictionless centrifugal chiller with magnetic bearing compressor, Model WME, with MicroTech E control.! WARNING Electric shock hazard. Can cause personal injury or equipment damage. This equipment must be properly grounded. Connections to and service of the MicroTech control panel must be performed only by personnel that are knowledgeable in the operation of the equipment being controlled.! CAUTION Static sensitive components. A static discharge while handling electronic circuit boards can damage components. Discharge any static electrical charge by touching the bare metal inside the control panel before performing any service work. Never unplug any cables, circuit board terminal blocks, or power plugs while power is applied to the panel.! CAUTION Do not install any software not authorized by McQuay International or alter operating systems in any unit microprocessor, including the interface panel. Doing so can cause malfunction of the control system and possible equipment damage. NOTICE This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause interference to radio communications. Operation of this equipment in a residential area is likely to cause interference in which case the user will be required to correct the interference at their expense. McQuay International disclaims any liability resulting from any interference or for the correction thereof. Equipment Location WME chillers are intended only for installation in an indoor or weather protected area consistent with the NEMA 1 rating on the chiller, controls, and electrical panels. Equipment room temperature for operating and standby conditions is 40 F to 104 F (4.4 C to 40 C). OMM

4 Optimum Water Temperatures and Flow A key to improving energy efficiency for any chiller is minimizing the compressor pressure lift. Reducing the lift reduces the compressor work and its energy consumption per unit of output. The chiller typically consumes more energy than any other component in the chiller system. Therefore, the optimum plant design must take into account all of the interactions between chiller, pumps, and tower. Higher Leaving Chilled Water Temperatures Warmer leaving chilled water temperatures will raise the compressor's suction pressure and decrease the lift, improving efficiency. Using 45 F (7 C) leaving water instead of 42 F (5.5 C) will significantly reduce chiller energy consumption. Evaporator Temperature Drop The industry standard has been a 10 F (5.5 C) temperature drop in the evaporator. Increasing the drop to 12 F or 14 F (6.6 C or 7.7 C) can improve chiller efficiency. Chilled water pump energy will also be reduced. Reduced Evaporator Fluid Flow Several popular chiller plant control practices including Variable Primary Flow systems advocate reducing the evaporator fluid flow rate as the chiller capacity is reduced. This practice can significantly reduce the evaporator pumping power while having little effect on chiller energy consumption. The Magnitude chiller can operate effectively in variable evaporator flow systems as long as the minimum and maximum tube velocities are taken into consideration when selecting the chiller. See section on Variable Fluid Flow Rates on page 7. Condenser Entering Water Temperature As a general rule, a 1 F (0.5 C) drop in condenser entering water temperature will reduce chiller energy consumption by two percent. Cooler water lowers the condensing pressure and reduces compressor work. One or two degrees can make a noticeable difference. The incremental cost of a larger tower can be small and provide a good return on investment. Condenser Water Temperature Rise The industry standard of 3 gpm/ton or about a 9.5 F (5.3 C) delta-t works well for most applications. Reduced Condenser Fluid Flow Several popular chiller plant control practices also advocate reducing the condenser fluid flow rate as the chiller load is reduced. This practice can significantly reduce the condenser pumping power, but it may also have the unintended consequence of significantly increasing compressor power since the leaving condenser water temperature is directly related to compressor lift and power. The higher compressor power will typically be larger than the condenser pumping power reduction and will result in a net increase in chiller plant energy consumption. Therefore, before this strategy is applied for energy saving purposes it should be extensively modeled or used in an adaptive chiller plant control system which will take into account all of the interdependent variables affecting chiller plant energy. If it is decided to use variable condenser fluid flow, the Magnitude chiller can operate effectively as long as the minimum and maximum tube velocities are taken into consideration when selecting the chiller. Free-Cooling Pressure Inversion Pressure inversion can happen in the chiller when the building system uses free cooling. The chiller had been in the OFF state with no water flowing so the pressure inside was relatively high and corresponds to the water temperatures inside the heat exchangers. When the condenser pumps starts with cold water from the free-cooling system, the sudden drop in condenser temperature creates an inverted pressure situation. The refrigerant inside the heat exchangers flows to equalize the pressure. During this process, there can be enough pressure difference to cause refrigerant flow and impeller rotation for a short time. As long as power to the chiller is on, the WME software recognizes this condition and will levitate the bearings until the pressure equalizes. Once the pressure equalizes, the chiller will operate as normal. 4 OMM

5 Chilled Water Temperature The maximum temperature of water entering the chiller on standby must not exceed 105 F (46.1 C). Maximum temperature entering on start-up must not exceed 90 F (32 C). Minimum chilled water leaving temperature without antifreeze is approximately 38 F (3.3 C). Piping Piping must be adequately supported to remove weight and strain on the chiller's fittings and connections. Be sure piping is adequately insulated for job conditions. Install a cleanable 20-mesh water strainer upstream of the evaporator and condenser. Install enough shutoff valves to permit draining water from the evaporator or condenser without draining the complete system. Condenser Water Temperature When the ambient wet bulb temperature is lower than design, the entering condenser water temperature of Magnitude model WME chillers can be lowered to improve chiller performance. Chillers can start with entering condenser water temperatures as low as 40 F (4.4 C). For short periods of time during startup, the entering condenser water temperature can even be lower than the leaving chilled water temperature. Magnitude model WME chillers are equipped with electronic expansion valves (EXV) and will run with entering condenser water temperatures as low as shown in Figure 1 or as calculated from the following equation on which the curves are based: Min. ECWT = 5.25+(LWT)-0.75*DT FL *(PLD/100)+14 *(PLD/100) 2 Where: ECWT = Entering condenser water temperature LWT = Leaving chilled water temperature DTFL = Chilled Water Delta-T at full load PLD = The percent chiller load point to be checked Figure 1: Model WME Minimum Entering Condenser Water Temperature (EXV) (10 F Range at Full Load) 65 ECWT ( F) F LChWT 44 F LChWT 42 F LChWT Percent Load For example; at 44 F LWT, 10 F Delta-T at full load, and 50% full load operation, the entering condenser water temperature could be as low as 49 F. This provides excellent operation with water-side economizer systems. OMM

6 Depending on local climatic conditions, using the lowest possible entering condenser water temperature may be more costly in total system power consumed than the expected savings in chiller power would suggest, due to the excessive fan power required. In this scenario, cooling tower fans would continue to operate at 100% capacity at low wet bulb temperatures. The trade-off between better chiller efficiency and fan power should be analyzed for best overall system efficiency. The Daikin Energy Analyzer program can optimize the chiller/tower operation for specific buildings in specific locales. Even with tower fan control, some form of water flow control, such as tower bypass, is recommended. Figure 2 and Figure 3 illustrate two temperature-actuated tower bypass arrangements. The Cold Weather scheme, Figure 3, provides better startup under cold ambient air temperature conditions. The bypass valve and piping are indoors and thus warmer, allowing for warmer water to be immediately available to the condenser. The check valve may be required to prevent air at the pump inlet. Figure 2: Tower Bypass: Mild Weather Operation Figure 3: Tower Bypass: Cold Weather Operation (Bypass Indoors) Condenser water temperature control The standard MicroTech controller is capable of three stages of tower fan control plus an analog control of either a three-way tower-bypass valve or variable speed tower-fan motor. Stages are controlled from condenser-water temperature. The three-way valve can be controlled to a different water temperature or track the current tower stage. This allows optimum chilled water plant performance based upon specific job requirements. Pumps The condenser water pump(s) must be cycled off when the last chiller of the system cycles off. This will keep cold condenser water from migrating refrigerant to the condenser. Cold liquid refrigerant in the condenser can make start up difficult. In addition, turning off the condenser water pump(s) when the chillers are not operating will conserve energy. 6 OMM

7 Include thermometers and pressure gauges at the chiller inlet and outlet connections and install air vents at the high points of piping. Where noise and vibration are critical and the unit is mounted on spring isolators, flexible piping and conduit connections are necessary. Variable Fluid Flow Rates and Tube Velocities Many chiller system control and energy optimization strategies require significant changes in evaporator and condenser water flow rates. The Magnitude chiller line is particularly well suited to take full advantage of these energy saving opportunities provided that the maximum and minimum fluid flow rates are taken into consideration for a specific application. The sales engineer has the flexibility to use different combinations of shell size, number of tubes, and pass arrangements to select the optimum chiller for each specific application. Both excessively high or excessively low fluid flow rates should be avoided. Excessively high fluid flow rates and correspondingly high tube velocities will result in high fluid pressure drops, high pumping power, and potentially tube corrosion and/or tube erosion damage. Excessively low fluid flow rates and correspondingly low velocities should also be avoided as they will result in poor heat transfer, high compressor power, sedimentation and tube fouling. Excessively high and low tube velocities can be particularly problematic and damaging in open loop systems. Rates of Fluid Flow Change If it is decided to vary the evaporator water flow rate the rate of change should not exceed 50% per minute and should not exceed the minimum or maximum velocity limits as determined by the McQuay chiller software program. Vibration Mounting The Magnitude chillers are almost vibration-free. Consequently, floor mounted spring isolators are not usually required. Rubber mounting pads are shipped with each unit. It is wise to continue to use piping flexible connectors to reduce sound transmitted into the pipe and to allow for expansion and contraction. System Water Volume All chilled water systems need adequate time to recognize a load change, respond to that load change and stabilize, without undesirable short cycling of the compressors or loss of control. In air conditioning systems, the potential for short cycling usually exists when the building load falls below the minimum chiller plant capacity or on close-coupled systems with very small water volumes. Some of the things the designer should consider when looking at water volume are the minimum cooling load, the minimum chiller plant capacity during the low load period and the desired cycle time for the compressors. Assuming that there are no sudden load changes and that the chiller plant has reasonable turndown, a rule of thumb of gallons of water volume equal to two to three times the chilled water gpm flow rate is often used. A properly designed storage tank should be added if the system components do not provide sufficient water volume. Multi-chiller Up to eight WME chillers are capable of being interconnected and operating in a multi chiller mode using their internal control network. Please contact McQuay International service for installation of the correct software for multi-chiller operation. System Analysis Although we recommend analyzing the entire system, it is generally effective to place the chiller in the most efficient mode because it is a large energy consumer. The McQuay Energy Analyzer program is an excellent tool to investigate the entire system efficiency, quickly and accurately. It is especially good at comparing different system types and operating parameters. Contact your local McQuay International sales office for assistance on your particular application. OMM

8 Features of the Control Panel Control of leaving chilled water within a ±0.5 F (±0.3 C) tolerance. Systems with a large water volume and relatively slow load changes can achieve higher stability. Readout of the following temperature and pressure readings: Entering and leaving chilled water temperature Entering and leaving condenser water temperature Saturated evaporator refrigerant temperature and pressure Saturated condenser temperature and pressure Suction line, liquid line and discharge line temperatures - calculated superheat for discharge and suction lines calculated sub-cooling for liquid line Automatic control of primary and standby evaporator and condenser pumps. Control up to 3 stages of cooling tower fans plus modulating bypass valve and/or tower fan VFD. The controller will store and display key historic operating data for recall in a graphic format on the screen. Data can also be exported for archival purposes via a USB port. Security password protection against unauthorized changing of setpoints and other control parameters. Warning and fault diagnostics to inform operators of warning and fault conditions in plain language. Al1 warnings, problems and faults are time and date stamped so there is no guessing of when the fault condition occurred. Eight latest faults are displayed on the touch screen. Data can be exported for archival purposes via a USB Drive. Soft loading feature reduces electrical consumption and peak demand charges during the cooling loop pull-down. Adjustable load pull-down rate reduces over-shoot during initial loop pull-down. Remote input signals for chilled water reset, demand limiting, unit enable. Manual (Service) control mode allows the service technician to command the unit to different operating states. Useful for system checkout. Optional Building Automation System communication capability via LONMARK, Modbus or BACnet standard protocols for BAS manufacturers. Pressure transducers for direct reading of system pressures. Preemptive control of high motor amps, high motor temperature, low evaporator pressure conditions and high discharge temperature takes corrective action prior to a fault trip. 8 OMM

9 General Description General Description The centrifugal MicroTech-E control system consists of microprocessor-based controllers that provide all monitoring and control functions required for the controlled, efficient operation of the chiller. The system consists of the following components: Operator Interface Touch Screen (OITS), one per chiller, provides unit information and is the primary user interface for all system data and setpoint information. Unit Controller, one per chiller, controls unit functions and communicates with all other controllers. It is located in a panel adjacent to the OITS. Compressor Controller located in the compressor controls compressor functions such as loading and unloading and collects I/O points near the compressor,. The operator can monitor all operating conditions by using the unit-mounted OITS. In addition to providing all normal operating controls, the MicroTech-E control system monitors equipment protection devices on the unit and will take corrective action if the chiller is operating outside of its normal design conditions. If a fault condition develops, the controller will shut the compressor or entire unit down and activate an alarm output. Important operating conditions at the time an alarm condition occurs are retained in the controller s history log to aid in troubleshooting and fault analysis. The system is protected by a password scheme that only allows access by authorized personnel. The operator must enter the password into the touch screen before any setpoints can be altered. Control Architecture Figure 4, Major Control Components Chiller #1 BAS (BACnet, Modbus, LONTALK) Ethernet/RS232/RS485/LON Color [Type a quote from the VGA RS232 12VDC BAS Card Chiller Controller Variable Frequency Drive Compressor Controller Local User Interface Ethernet Firewall Ethernet (Local Network) Ethernet (Local Network) Chiller #2 OMM

10 Component Description Operator Interface Touch Screen The operator interface touch screen (OITS) is the primary device by which commands and entries into the control system are made (a laptop computer can also be used). It also displays all controller data and information on a series of graphic screens. The control panel contains a USB port that can be used for loading information to and from the control system including download of trend log data and uploading software upgrades. The OITS panel is mounted on a moveable arm to allow placement in a convenient position for the operator. There is a screen-saver programmed into the system. The screen is reactivated by touching it anywhere on the front surface. Unit Controller There is one unit controller mounted on the chiller which is the primary interface to the user and for field I/O connections. Unit and compressor on/off switches are mounted in the unit controller panel located adjacent to the OITS panel. They are designated 1 for on and O for off. The compressor on/off switch should only be used when an immediate stop is required since the normal shut down sequence is bypassed. There is a unit enable switch located on the left outside of the panel that causes a controlled shutdown of the compressor. The unit controller's primary function is processing data relating to the entire chiller unit operation, as compared to data relating to the compressor operation. The unit controller processes information and sends data to other controllers and devices and relays information to the OITS for graphic display. The following functions operate in the unit controller: User interface BAS interface Field I/O; pumps, alarm contact, remote start/stop, tower control Chiller I/O; water temperatures, EXV control, condenser pressure Data trending Chiller alarm handling Alarm display Figure 5, Unit Control Panel Unit Switch Normal Shutdown External Control Wiring Entry Knockouts (4) Comp. Switch Immediate Stop (1) USB Port on Top of Bracket Ethernet Port CPU Bracket External Normal Shutdown Switch (2) USB Ports Under Bracket 10 OMM

11 Motor/Compressor Controller The following functions operate in the compressor controller: Bearing Control Suction/Discharge Temperature and Pressure IGV control Speed Control RPM sensing Load Control Compressor Alarm Handling Motor Temperature control Compressor staging and load balancing on multi-chiller installations VFD Controller The following functions operate in the VFD controller: Controls motor according to speed setpoint VFD heat sink temp control (solenoids) High Pressure switch monitoring Ground fault protection (optional) Over-current protection VFD alarm handling Control power distribution Regenerative power in case of power loss Short circuit protection VFD Description: The VFD has several main components or sections: 1) Input power section: Circuit breaker ( standard) Ground fault detection ( optional) Power meter ( optional) 2) Control power section: 120VAC 24VDC, 12VDC, 15VDC 300VDC (intermediate power supply) 3) Power conditioning Main power autotransformer used for low harmonics version or where buck/boost is required. - ( 460V low harmonics option, 575V, 380V ) EMI filters (optional), use where low-level EM emission from the VFD panel are undesirable. Line Reactors - standard 4) Heat sink assemblies: ( main power control assembly) M2 version 1 heat sink assembly M3, M4 version 2 heat sink assemblies The main purpose of the M3 version with the transformer is to provide lower harmonics than the standard M2 system. OMM

12 Key VFD Control Signals VFD enable from Compressor to VFD (relay contact) Speed reference (command speed) from compressor to VFD (4-20 ma analog) Compressor RPM sensor output to VFD (digital pulse) VFD amps to Compressor (Ethernet) The remaining chiller data, setpoints, and control signals travel between the chiller, compressor, and VFD using an Ethernet network. Inputs and Outputs Unit Controller Table 1, Unit Controller, Analog Inputs # Description Wiring Source Signal Range NTC Entering Evaporator Water 1 Chiller Thermistor 10k@25 C -40 to 125 C Temperature (Note 1) Leaving Evaporator Water Temperature Entering Condenser Water Temperature Leaving Condenser Water Temperature Entering Heat Recovery Water Temperature Leaving Heat Recovery Water Temperature Chiller Chiller Chiller Chiller Chiller 7 Liquid Line Refrigerant Temperature Chiller 8 Condenser Refrigerant Pressure Chiller 9 Evaporator Water Flow Rate Field 10 Condenser Water Flow Rate Field 11 Reset of Leaving Water Temperature Field NTC Thermistor (Note 1) NTC Thermistor (Note 1) NTC Thermistor (Note 1) NTC Thermistor (Note 1) NTC Thermistor (Note 1) NTC Thermistor (Note 1) Sealed Gage Transducer Water Flow Sensor Water Flow Sensor BAS 12 Demand Limit Field BAS 10k@25 C -40 to 125 C 10k@25 C -40 to 125 C 10k@25 C -40 to 125 C 10k@25 C -40 to 125 C 10k@25 C -40 to 125 C 10k@25 C -40 to 125 C 0.3 to 4.5 VDC 4 to 20 ma Current 4 to 20 ma Current 4-20 ma Current 4-20 ma Current Note 1: Thermistor curves according to standard McQuay thermistor probe specification to 410 psi 0 to 10,000 gpm 0 to 10,000 gpm 0 to100% %RLA 12 OMM

13 Table 2, Unit Controller, Digital Inputs # Description Wiring Signal Source States OPEN/CLOSED 1 Front Panel Stop/Auto Switch Chiller Isolated Switch Contacts Stop / Auto 2 Remote Start/Stop Field Isolated Switch or Relay Contacts Stop / Auto 3 Mode Switch Field Isolated Switch or Relay Normal / Contacts Alternate Mode 4 Evaporator Water Flow Switch Chiller & Field Isolated Flow Switch (in series) Contacts No Flow / Flow 5 Condenser Water Flow Switch Chiller & Field Isolated Flow Switch (in series) Contacts No Flow / Flow 6 Compressor Manual OFF Switch Chiller Isolated Switch Contact Stop/Auto Table 3, Unit Controller, Digital Outputs # Description Load Rating 1 Alarm Indicator Light 240 VAC 2 Evaporator Water Pump #1 Pump Contactor 240 VAC 3 Evaporator Water Pump #2 Pump Contactor 240 VAC 4 Condenser Water Pump #1 Pump Contactor 240 VAC 5 Condenser Water Pump #2 Pump Contactor 240 VAC 6 Cooling Tower Fan #1 Fan Contactor 240 VAC 7 Cooling Tower Fan #2 Fan Contactor 240 VAC 8 Cooling Tower Fan #3 Fan Contactor 240 VAC Table 4, Unit Controller, Analog Outputs # Description Output Signal Range 1 Cooling Tower Bypass Valve Position 0 to 10 VDC 0 to 100% Open 2 Cooling Tower VFD Speed 0 to 10 VDC 0 to 100% Table 5, Stepper Motor Outputs The following output is provided for stepper motor driven actuators. # Description Motor 1 Electronic Expansion Valve 12VDC, 10VA max 2 Range Extension Valve 12VDC, 10VA max OMM

14 Compressor Controller Table 6, Compressor Controller, Analog Inputs # Description Source Signal Range 1 Compressor Suction Temperature NTC Thermistor 10k@25 C -40 to 125 C 2 Compressor Discharge Temperature NTC Thermistor 10k@25 C -40 to 125 C 3 Suction Refrigerant Pressure Sealed Gage Transducer 0.3 to 4.5 VDC -6.6 to 132 psi 4 Discharge Refrigerant Pressure Sealed Gage Transducer 0.3 to 4.5 VDC to 410 psi 5 Rotor Pump Temperature NTC Thermistor 10k@25 C -40 to 125 C 6 Inlet Guide Vane Position Rotary Transducer 0.5 to 4.5 VDC Closed to Open 7 Motor Winding Temperature 1 NTC Thermistor 10k@25 C -40 to 150 C 8 Motor Winding Temperature 2 NTC Thermistor 10k@25 C -40 to 150 C 9 Motor Winding Temperature 3 NTC Thermistor 10k@25 C -40 to 150 C 10 Motor Case Temperature 11 Motor Gap Temperature NTC Thermistor 10k@25 C -40 to 125 C Table 7, Compressor Controller, Digital Inputs None Table 8, Compressor Controller, Analog Outputs None Table 9, Compressor Controller, Digital Outputs # Description Load Output OFF Output ON 1 VFD Enable VFD Compressor OFF Compressor ON 2 Liquid Injection Solenoid (24 VDC, 20 VA max) No Injection Injection 3 Stator Cooling Solenoid (24 VDC, 20 VA max) Cooling OFF Cooling ON Table 10, Stepper Motor Outputs The following output is provided for stepper motor driven actuators. # Description Motor 1 Inlet Guide Vane Position 4.2VDC, 30VA max 2 Rotor Cooling 12VDC, 10VA max 14 OMM

15 Optional Harmonic Filters The optional harmonic filter is a device that reduces harmonics. It may be factory-mounted in the chiller power panel or remotely mounted in the field. Operation The harmonic filter is a passive device and there is no operator action required for normal operation. Cleaning Excessive accumulations of dirt on the reactor windings or insulators and capacitor terminals should be removed to permit free circulation of air and to guard against the possibility of insulation breakdown. Particular attention should be given to cleaning the top and bottom ends of the winding assemblies and to cleaning out ventilating ducts. Windings should be lightly cleaned by the use of a vacuum cleaner. If necessary a blower or compressed air may be used but pressure should not exceed 25 psi. Lead supports, tap changers and terminal boards, bushings, and other major insulating surfaces should be brushed or wiped with a dry cloth. The use of liquid cleaners is not recommended due to deteriorating effects on most insulating materials. Periodic Inspection and Maintenance The filter has no moving or active parts and therefore requires only minimal periodic maintenance when installed in a clean and well ventilated environment. Annual maintenance is recommended. This should include: 1. Visual inspection for evidence of loose connections, dirt, moisture, rusting, corrosion, and deterioration of the insulation, varnish or paint. Observations should be made for signs of overheating and overvoltage creeping. Corrective measures should be taken as necessary. 2. For early detection of any developing hotspots, an infrared scan can be performed while the unit is operating under its heaviest load condition. 3. The unit capacitors are equipped with an internal Tear-Off fuse pressure interrupter to prevent explosive failure. At the end of its service life, pressure within a capacitor will build due to the release of gases as its dielectrics breakdown. The covers on the cans are designed to expand or bulge and Tear-Off the internal fuse as this pressure builds. Capacitors should be inspected regularly and replaced when found to have an expanded cover. CAUTION Ensure that power to the unit is turned off and safely isolated before replacing failed capacitors or blown fuses. 4. Most units are also equipped with capacitor fuses. Capacitor fuses are intended to provide additional protection against overloading of the capacitors. A blown fuse can be detected by checking for illumination of the blown fuse indicator when this option has been purchased or by measuring the voltage across the fuse terminals while energized. If voltage is not near zero or the blown fuse indicator is on, the fuse should be replaced. 5. Measuring the current in each of the three phases of the capacitor circuit can be a quick and easy method of determining the condition of the capacitors. The capacitors can be assumed to be in good operating condition when all three phases carry approximately the same amount of load current. Measurements should be taken at the input to the capacitor distribution block and can be done at any loading condition. Phase currents that are imbalanced by more than 10%, indicate a capacitor failure or blown fuse. When the filter capacitor bank has been connected in a wye configuration (ie. Two jumpers create a common point on each set of three capacitors), locating the problem capacitor(s) can be achieved by measuring the voltage between the common neutral point of each set to ground. If the voltage difference is greater than 10 volts, at least one of the capacitors in that set has failed or has a blown fuse. Testing should be conducted annually or whenever the unit seems to be operating in an abnormal manner. The unit is capable of continued operation with some failed capacitors or blown capacitor fuses. Harmonic mitigation performance will be sacrificed however, so it is recommended that all failed capacitors or blown capacitor fuses be replaced as soon as is practically possible after detection. CAUTION Service work on this device must be only be performed by technicians trained and experienced on them. OMM

16 Field Wiring Data Electrical Notes Input power options: 3ph 380V 50/60Hz 3ph 400V 50/60Hz 3ph 415V 50/60Hz 3ph 460V 50/60Hz 3ph 480V 50/60Hz 3ph 575V 60Hz Wiring, fuse and wire size must be in accordance with the National Electric Code (NEC). Important: Voltage unbalance not to exceed 2%. Power Wiring Use only copper supply wires with ampacity based on 75 C conductor rating. Connections to terminals must be made with copper lugs and copper wire. Lug size range is: (3) 3/0 AWG kc mil. Short Circuit Current Ratings WME chillers are available with an optional High Short Circuit Rating HSCCR) or Ultra High Short Circuit Motor 3-Ph 6-Ph Voltage Standard Panel Optional High SCCR Optional Ultra High SCCR 380V- 480V 35 ka 65 ka 100 ka 575V 25 ka 50 ka N/A 380V- 480V 35 ka 65 ka 100 ka 575V N/A N/A N/A Current Rating (UHSCCR) in lieu of the standard rating (SCCR) as shown in the above table. 3-Phase vs. 6-phase Motors WME 500 motors are designated as M2 or M3. "M2 motors are standard 3-phase and the VFD performs similar to a 6-pulse drive. "M3 motors are 6-phase (connected to a 3-phase power supply) and the VFD performs similar to a 12-pulse drive. They provide increased protection against harmonic distortion, but are not required on most applications. WME 700 motors are 6-phase and designated as M4. The VFD performs similar to a 12-pulse drive. Notes for field wiring diagram ( page 17) 1 Optional Flow Switches; If field supplied pressure differential flow switches are used, they must be installed across the vessel and not the pump. They must provide isolated dry contacts at J27. Removing the factory jumpers will correctly put the field switches in series with the factory-mounted switches. 2 CW Reset & Demand Limit; External 4-20mA signals can be wired to J23 for leaving (chilled) water reset and to J26 for demand limit. 3 Tower Bypass Valve & Tower Fan VFD; 0-10VDC analog outputs to these devices. 4 Chiller Remote On/Off Control of unit can be accomplished by connecting a set of isolated dry contacts at J25. 5 Mode Switch; Switch used for ice mode currently not available on WME chillers. 6 Condenser & Evaporator GPM; Connections for 4-20 ma flow signal from field-supplied devices. 7 Alarm Relay; A customer furnished 24 to 240 Vac power for controller alarm relay may be connected at J18. Maximum rating of the alarm relay coil is 25 VA. 8 Evap Water Pump #1 & #2; A digital output for a optional customer supplied 25 VA maximum coil rated, chilled water pump relay. One or two may be wired as shown. This option will cycle the chilled water pump in response to chiller demand. 9 Cond Water Pump #1 & #2; The condenser water pump must cycle with the unit. A customer supplied 25 VA maximum coil rated, condenser water pump relay (one or two) must be wired as shown. Units used in a freecooling application must have condenser water above 50 F before starting. 10 Tower Fan Staging #1, #2 & #3; Digital outputs for optional customer supplied 25 VA maximum coil rated cooling tower fan relays may be wired as shown. This option will cycle the cooling tower fans as prescribed by the tower control set points. 16 OMM

17 Figure 6, Field Wiring Diagram (see notes on page 16) NOTE: The J terminals blocks are on the top of the back panel under the four knockouts for field wiring. OMM

18 OM Centrif Micro ΙΙ-2

19 Operator Interface Touch Screen (OITS) Navigation The home screen shown in VIEW screen is usually left on (there is a screen-saver built in that is reactivated by touching the screen anywhere on the front surface). This VIEW screen contains the STOP and AUTO buttons used to start and stop the unit when in user control. Other groups of screens can be accessed from the Home screen by pressing one of the buttons on the bottom of the screen; TREND, VIEW, SET, ALARM. TREND will graph the recent data for several system variables: evaporator water temperatures, condenser water temperatures, evaporator pressure, condenser pressure, % RLA, % RPM, % Vanes. VIEW will go to the next View screen and other sub-view screens used to look in detail at settings and the operation of the chiller. Pressing View from any other screen will return to the previously selected View screen. View screens are used for looking at unit status and conditions. SET will go to a series of screens used to set or view setpoints. ALARM will display recent and active alarms. NOTE: The data shown on screens in this section do not necessarily reflect actual operating conditions. Figure 7, Home View Screen Home View Screen The Home View Screen shows the basic condition of the chiller. Information State of compressor and pumps; a green light indicates on. black indicates off. Active chilled water (LWT) setpoint Entering and leaving chilled and condenser water temperatures Percent motor amps (approximates percent load) UNIT STATUS consists of unit MODE, followed by STATE, followed by the SOURCE that is the device or signal that created the STATE. The possible messages are in the following table: OMM

20 Table 11, UNIT STATUS Combinations MODE STATE SOURCE COOL OFF Manual Switch SHUTDOWN ( See Note) Remote Switch AUTO User BAS Network Note: Shutdown is the chiller state when in the process of shutting down. The Home View Screen-Detail gives additional information on the refrigerant pressures and temperatures, compressor speed and other system data. When first booted up, this screen will only show the left side. As soon as one of the details, such as STATE is selected, and from then on, the screen will show information appearing on the right side. Figure 8, Home View Screen-Detail Pressing the STATE button will bring up a display of the compressor state superimposed on the View Home Screen- Detail as shown in Figure 8. Pressing the I/O button will bring up a display of the compressor inputs and output status (I/O) superimposed on the View Home Screen-Detail as shown in Figure 9. These I/Os are to and from the compressor controller. Range extension position is the percent opening of the range extension valve. The value locks to zero if the feature is not configured. 20 OMM

21 Figure 9, Compressor I/O Screen Digital Outputs: a green light to the left of a condition indicates it is active. Liquid injection is a user option controlled by a setpoint Analog Inputs: data from sensors connected to the compressor Analog Output: compressor speed output Stepper Outputs: compressor stepper outputs for inlet guide position, rotor cooling, and range extension Range Extension Position: range extension position is the percent opening of the range extension valve. The value locks to zero if the feature is not configured OMM

22 Pressing the UNIT I/O button, located in the lower-left corner of the screen, displays the current unit inputs and outputs superimposed on the View Home Screen-Detail as shown in Figure 10. These I/Os are to and from the unit controller. Figure 10, Unit Input/Output (I/O) Digital Inputs: inputs to the unit controller that determine if the compressor can start. Digital Outputs: outputs to start the evaporator and condenser pumps and tower fans or indicate an alarm condition such as no flow. Analog Outputs: analog outputs to set the tower bypass valve and/or the tower fan VFD to the correct position or speed. Analog Inputs: inputs usually from a BAS to control LWT reset and demand limiting for the compressor power input. Range Extension Position: range extension position is the percent opening of the range extension valve. The value locks to zero if the feature is not configured. Pressing the EVAP or COND button, located on the vessels, will give detailed information on the evaporator or condenser pressures and temperatures as shown on the following page. 22 OMM

23 Figure 11, Evaporator Screen Figure 12, Condenser Screen OMM

24 Pressing the Power button, located on the left side of the screen, will access the screen giving power data. Individual line current and voltage values, power factor and kw Hours are only available with the optional Input Power Meter. Figure 13, Power Screen 24 OMM

25 SET Screens The set screens on the Interface Panel are used to input the many setpoints associated with equipment of this type. MicroTech-E provides an extremely simple method for accomplishing this. Appropriate setpoints are factory set and checked by McQuay International service or a Factory Authorized Service Company during commissioning. However, adjustments and changes are often required to meet job conditions. Certain settings involving pumps and tower operation are always field set. Pressing the SET button from any other screen accesses the SET screen. Pressing the SET button while on a SET screen will access the SERVICE screen. The various setpoint groups are in a column on the right side of the screen. Each button contains a number of setpoints grouped together by similar content. For example, The WATER contains various setpoints relating to water temperatures. NOTE: Some setpoints that do not apply to a particular application may still be listed on the screen. They will be inactive and can be ignored. The numbered buttons in the second from right column are pressed to select a particular setpoint. The selected setpoint will appear in green on the screen and a description of it (with the range of available settings) will appear in the upper left-hand box. Figure 14, Typical Setpoint Screen Current Unit & Compressor Status Current Setpoint Values Setpoint Access Numbers Setpoint Groups Setpoint Description and Range of Values Keypad Buttons to Access Other Menus OMM

26 Procedure for Changing a Setpoint A list of setpoints, their default value, their available setting range, and password authority are shown on the page relating to the particular setpoint screen beginning on page 27. Press the applicable Setpoint Group Button. A complete explanation of setpoint content of each group follows this section. 1) Select the desired setpoint by pressing the numbered button. 2) Press the CHANGE button indicating that you wish to change a setpoint value. A keypad dialog box will be turned on automatically for entering the password. 3) O= Operator password : default = 100 4) T = Technician level password is reserved for authorized technicians 5) Press the appropriate numbers in the keypad box to enter the password. There is a small delay between pressing the keypad and recording the entry. Be sure that an asterisk appears in the window before pressing the next number. Press ENTER to return to the SETPOINT screen. The password will remain open for 15 minute after initiation and does not need to be re-entered during this period. 6) Press CHANGE again 7) The numeric keypad and action buttons in the lower left-hand corner of the screen will be activated. Setpoints with numeric values can be changed in two ways: Select the desired value by pressing the numbered buttons. Press ENTER to enter the value or CANCEL to cancel the transaction. Press the UP or DOWN button to increase or decrease the value displayed. Press ENTER to enter the value or CANCEL to cancel the transaction. Some setpoints are text rather than numeric values. For example, LWT Reset Type can be "None" or "4-20 ma". The selection can be made by toggling between choices using the UP or Down button. If dashed lines appear in the setpoint window, it indicates that you have toggled too far and need to reverse direction. Press ENTER to enter the choice or CANCEL to cancel the transaction. Setpoints requiring text entry open an alphanumeric keyboard. Once CHANGE is selected, the CANCEL or ENTER buttons must be pressed before another setpoint can be selected. Additional setpoints can be changed by selecting another setpoint on the screen or by selecting an entirely new group of setpoints. Range Extension The range extension function is only accessible with the technician password. Consult McQuay International service. Explanation of Setpoints Each of the setpoint groups of screens are detailed in the following section. The groups are: WATER, UNIT, STAGING, POWER, TOWER, VALVE, ALARMS, BAS In some cases, pressing the button again may display a second page of setpoints in the same group. Pressing SET from any SET screen accesses the SERVICE screen. In other words, it is the second "SET" screen. While containing information and activity buttons for the service technician, it also has valuable information for the operator. The software version numbers shown in the lower left corner are the controllers' software identification. These numbers may be required by McQuay International to answer questions about unit operation or to assist in possible future upgrades of software. 26 OMM

27 Setpoint Screens Figure 15, BAS Setpoint Screen #1 Figure 16, BAS Setpoint Screen #2 Screen details on the following page. OMM

28 Table 12, BAS Screen #1 Setpoints Description BACnet IP - Foreign Device Time BACnet IP - BBMP IP Address BACnet IP - Default Gateway BACnet IP UDP Port BAC net IP Subnet Mask BACnet IP - Network Addr BACnet (all) - UTC Offset BACnet (all) - Daylight Savings Time BACnet (all) - APDU Retries BACnet (all) - APDU Tiimeout BACnet (all) - Description BACnet (all) - Object Name BACnet (all) - Device Instance BACnet (all) - English / Metric BAS Network Protocol No. Default Range Password Comments 15 0 (0) to Seconds O = "None 13 None decimal (BAC0 hexadeci mal) (XXX.XXX.XXX.XXX) where each XXX can be 0 to 255 (XXX.XXX.XXX.XXX) where each XXX can be 0 to 255 O O 0 to decimal O (XXX.XXX.XXX.XXX) where each XXX can bo 0 to 255 (XXX.XXX.XXX.XXX) where each XXX can bo 0 to to +780 minutes O 8 None NO: Do not use Daylight Savings Time. YES: Use Daylight Savings Time to 10 O milliseconds O O 0 to 60,000 milliseconds O 5 None 31characters maximum. O The Time-to-Live, in seconds, within which the Chiller (a Foreign Device) must re-register with the BBMD. The Internet Protocol (IP) address for the BACnet Broadcast Management Device (BBMD) to which the chiller is registered. The Internet Protocol (IP) address of the BACnet IP router. The User Datagram Protocol (UDP) port number to use on the IP network. Subnet Mask for the communication module. The four-octet (32-bit) Internet Protocol (IP) address for the communications module. Sets the local time zone by Specifying the zone's offset from Universal Time Coordinated (UTC) in minutes.example: US Central Standard Time (CST) is -360.) O --- The maximum number of times an Application Protocol Data Unit (APDU) transmission shall be sent when there is no acknowledgment. The retry timeout interval (msec) for Application Protocol Data Unit (APDU) transmissions that require acknowledgment. The desired BACnet description of this particular chiller 4 31 characters maximum. O The unique BACnet Object Name to O 2 English 1 None ENGLISH: Use English units. (Deg F, PSI, GPM) METRIC: Use Metric units. (Deg C, kpa, liter/sec) BAS Network Protocol NONE: No BAS network MODBUS: RTU - RS485 LON: LONtalk - FTT-10A BACnet IP: IP - Ethernet BACnet Ethernet: Ethernet BACnet MS/TP: RS485 The unique BACnet Device Instance number. O --- O OMM

29 Table 13, BAS Screen #2 Setpoints Description No. Default Range Password Comments MODBUS - Baud Rate MODBUS - Network Address MODBUS Eng/Metric BACnet MS/TP - Baud Rate BACnet MS/TP Max Info Frames BACnet MS/TP - Max Masters BACnet MS/TP - MAC Address BACnet Ethernet - MAC Address , 2400, 4800, 9600, to 247 O 6 English English or Metric O , 19200, 38400, to(5 O to 127 O to 127 O 1 XX-XX-XX-XX-XX-XX Each XX can be 00 through FF hexadecimal O O O Sets the communications baud rate to use on the RS485 network. Sets the address to use on the RS485 network. ENGLISH: Use English units. (Deg F, PSI, GPM) METRIC: Use Metric units. (Deg C, kpa, liter/sec) Sets the communications baudrate to use on the RS485 network. Maximum number of Information Frames that can be sent before the communication module must pass the token. Maximum number of master controllers currently on the network. Unique MAC Address of the communication module. Unique MAC Address of the communication module. Figure 17, Alarms Screen OMM

30 Table 14, ALARM Setpoints Description No. Default Range Condenser Freeze Protect Evaporator Freeze Protect Password F -9.0 to 45.0 F O F -9.0 to 45.0 F O Motor Current Threshold 9 5% 3% to 99% T Surge Slope Limit deg F/min. T Surge Temperature Limit deg F T High Discharge Temp- Stop High Discharge Temp- Load F 120 to 240 F T F 120 to 240 F T High Condenser Pressure psi 120 to 240 psi T Low Evap Pressure, Stop 3 26 psi 10 to 45 psi O Low Evap Pressure- Unload Low Evap Pressure- Inhibit 2 31 psi 20 to 45 psi O 1 35 psi 20 to 45 psi O Comments Sets the value of condenser saturated temperature below which the condenser pump is forced ON. Sets the value of evaporator saturated temperature below which the evaporator pump is forced ON. When %RLA is below this SP, motor is considered OFF. When above, motor is considered ON. Sets the Surge Temp (ST) slope value above which alarm occurs. Active only if ST > SP7 at start. Deactivated when ST drops below SP7. At start,surge Temp(ST) is compared to this SP.(ST=Sctn Temp-Evap LWT) if Less:Alarm occurs when ST>2X this SP. if Greater:Slope alarm is active until ST<this SP. Then alarm at 2X this SP. Sets the discharge temperature above which the compressor is shut down. Sets the discharge temperature above which a forced capacity increase occurs. Sets the condenser pressure above which the compressor is shut down. Sets the evaporator pressure value below which the compressor is shut down. Sets the evaporator pressure value below which a forced capacity decrease occurs. Sets the evaporator pressure value below which any capacity increase is inhibited. 30 OMM

31 Figure 18, Tower Bypass VALVE Setpoint Screen Table 15, Tower Bypass VALVE Setpoints (See page 33 for complete explanation.) Description No. Default Range Password Comments Valve Control Slope Gain to 99 O Control gain for temperature (or lift) slope Valve Control Error Gain to 99 O Control gain for temperature (or lift) error Valve Control Range(Max) 13 90% 0 to 100% O Maximum valve position, overrides all other settings Valve Control Range (Min) 12 10% 0 to 100% O Minimum valve position, overrides all other settings Temp Max. Start Position F 0 to 100 F O Condenser EWT at which initial valve position is set to setpoint #10 Maximum Start Position % 0 to 100% O Initial valve position when condenser EWT is at or above Setpoint # 11 Temp Min. Start Condenser EWT at which initial valve position is set to Setpoint # 9 60 F 0 to 100 F O Position 8 Minimum Start Position 8 0% 0 to 100% O Minimum position of valve when condenser EWT is at or below Setpoint # 9 Stage 7 20% 0 to 100% O Valve position below which the fans can stage down (Tower Setpoint #2 = Valve Stage VFD speed below which the fans can stage down (Tower Setpoint # 2 = /VFD stage or valve SP/VFD stage Stage 6 80% 0 to 100% O Valve position above which the fans can stage up (Tower Setpoint #2 = Valve Stage VFD speed above which the fans can stage up (Tower Setpoint # 2 = VFD or valve SP/VFD stage Valve Deadband (Lift) psi 1.0 to 20.0 psi O Sets control deadband, Tower Setpoint #1=Lift Valve Deadband (Temp) F 1.0 to 10.0 F O Sets control deadband, Tower Setpoint #1=Temp Valve Target (Lift) 3 30 psi 10 to 130 psi O Target for lift pressure (Tower Setpoint #1= Lift), Works with Setpoint # 5 Valve Target (Temp) 2 65 F 40 to 120 F O Target for condenser EWT (Tower Setpoint #1= Temp), Works with Setpoint # 4 Tower Valve Type 1 NC (To Tower) NC, NO O Normally closed or normally open to tower OMM

32 Figure 19, Cooling Tower Setpoint Screen (See page 33 for complete explanation.) Table 16, Tower Fan Settings Description No. Default Range Password Comments Stage #3 On (Lift) psi 10 to 130 psi O Lift pressure for fan stage #3 on Stage #2 On (Lift) psi 10 to 130 psi O Lift pressure for fan stage #2 on Stage #1 On (Lift) psi 10 to 130 psi O Lift pressure for fan stage #1 on Stage #3 On (Temp) F 40 to 120 F O Temperature for fan stage #3 on Stage #2 On (Temp) 9 75 F 40 to 120 F O Temperature for fan stage #2 on Stage #1 On (Temp) 8 70 F 40 to 120 F O Temperature for fan stage #1 on Stage Differential (Lift) psi 1.0 to 20.0 psi O Fan staging deadband with Setpoint # 1=Lift Stage Differential (Temp) F 1.0 to 10.0 F O Fan staging deadband with Setpoint #1=Temp Fan Stage Down Time 5 5 min 1 to 60 min O Time delay between stage up/down event and next stage down Fan Stage Up Time 4 2 min 1 to 60 min O Time delay between stage up/down event and next stage up Cooling Tower Stages to 3 O Number of fan stages used Twr Valve/Fan VFD Control 2 None Tower Control 1 None None, Valve Setpoint, Valve Stage, VFD Stage, Valve SP/VFD Stage None, Temperature, Lift O O None: No tower valve or VFD Valve Setpoint: Valve controls to VALVE SP3(4) & 5(6) Valve Stage: Valve controls between fan stages VFD Stage: 1 st fan is VFD controlled, no valve Valve Setpoint/VFD Stage: Both valve and VFD None: No tower fan control Temperature: Fan and valve controlled by condenser EWT Lift: Fan and valve controlled by lift pressure 32 OMM

33 Explanation of Tower Control Settings The MicroTech control can control cooling tower fan stages, a tower bypass valve, and/or a tower fan VFD if the chiller has a dedicated cooling tower. The Tower Bypass Valve position will always control the Tower Fan Staging if Valve Setpoint, Stage Setpoint is selected. Fan staging is determined by Min & Max Tower Valve Position. There are five possible tower control strategies as noted below and explained in detail later in this section. They are selected from SETPOINT TOWER SP2. 1. NONE, Tower fan staging only. In this mode the tower fan staging (up to 3 stages) is controlled by either the condenser Entering Water Temperature (EWT) or LIFT pressure (difference between the condenser and evaporator pressures). Tower bypass or fan speed are not controlled. 2. VALVE SP, Tower staging with low-limit controlled bypass valve. In this mode the tower fans are controlled as in #1 plus a tower bypass valve is controlled to provide a minimum condenser EWT. There is no interconnection between the fan control and the valve control. 3. VALVE STAGE, Tower staging with stage controlled bypass valve. In this mode the bypass valve controls between fan stages to smooth the control and reduce fan cycling 4. VFD STAGE. In this mode a VFD controls the first fan. Up to 2 more fans are staged on and off and there is no bypass valve. 5. VALVE/VFD, Tower fan control with VFD plus bypass valve control. Tower Fan Staging Only (NONE) The following settings are used for the Tower Fan Staging Only mode, (SP= setpoint) 1) TOWER SETPOINT Screen 2) See Figure 6, Field Wiring Diagram on page 17 for fan staging field wiring connection points. a) SP1. Select TEMP if control is based on condenser EWT or LIFT if based on compressor lift expressed as a pressure difference. b) SP2. Select NONE for no bypass valve or fan VFD control. c) SP3. Select one to three fan outputs depending on the number of fan stages to be used. More than one fan can be used per stage through the use of relays. d) SP4. Select STAGE UP TIME from 1 to 60 minutes. The default value is probably a good starting point. The value may need to be adjusted later depending on actual system operation. e) SP5. Select STAGE DOWN TIME from 1 to 60 minutes. The default value is probably a good starting point. The value may need to be adjusted later depending on actual system operation. 3) If TEMP is selected in SP1, use a) SP6. Select STAGE DIFFERENTIAL in degrees F (degrees C), start with default of 3 degrees F. b) SP8-11. Set the STAGE ON temperatures consistent with the temperature range over which the condenser EWT is desired to operate. The default values of 70 F, 75 F and 80 F are a good place to start in climates with moderate wet bulb temperatures. The number of STAGE ON setpoints used must be the same as SP3. 4) If LIFT is selected in SP1, use a) SP7. Select STAGE DIFFERENTIAL in PSI (kpa). Start with default of 6 PSI. b) SP Start with default setpoints. The number of STAGE ON setpoints used must be the same as SP3. OMM

34 Tower Fan Staging With Bypass Valve Controlling Minimum EWT (VALVE SP) 1) TOWER SETPOINT Screen a) SP1. Select TEMP if control is based on condenser EWT or LIFT if based on compressor lift expressed as a pressure difference. b) SP2. Select Valve SP for control of bypass valve based on temperature or lift. c) SP3. Select one to three fan outputs depending on the number of fan stages to be used. More than one fan can be used per stage through the use of relays. d) SP4. Select STAGE UP TIME from 1 to 60 minutes. The default value of 2 minutes is probably a good starting point. The value may need to be adjusted later depending on actual system operation. e) SP5. Select STAGE DOWN TIME from 1 to 60 minutes. The default value of 5 minutes is probably a good starting point. The value may need to be adjusted later depending on actual system operation. f) If TEMP is selected in SP1, use: i) SP6. Select STAGE DIFFERENTIAL in degrees F (C), start with default of 3 degrees F. ii) SP8-11. Set the STAGE ON temperatures consistent with the temperature range over which the condenser EWT is desired to operate. The default values of 70 F, 75 F, and 80 F are a good place to start in climates with moderate wet bulb temperatures. The number of STAGE ON setpoints used must be the same as SP3. g) If LIFT is selected in SP1, use i) SP7. Select STAGE DIFFERENTIAL in PSI (kpa). Start with default of 6 PSI. ii) SP Start with default setpoints. The number of STAGE ON setpoints used must be the same as SP3. 2) VALVE SETPOINT Screen a) SP1, Select NC or NO depending if valve is closed to tower with no control power or open to tower with no control power. b) If TEMP was selected for fan control above, use: i) SP2, Set the VALVE TARGET (setpoint), usually 5 degrees F below the minimum fan stage setpoint established in TOWER SP8. This keeps full flow through the tower until the last fan is staged off. ii) SP4, Set VALVE DEADBAND, the default of 2 degrees F is a good place to start. iii) SP8, Set MINIMUM START POSITION when EWT is at or below SP9. Default is 0%. iv) SP9, Set the EWT at which the valve position will be at (SP8). Default is 60 F. v) SP10, Set the initial valve position when EWT is at or above SP11. Default is 100%. vi) SP11, Set the EWT at which initial valve position is set to SP8. Default is 90 F. vii) SP12, Set the minimum position to which the valve can go. Default is 10%. viii) SP13, Set the maximum position to which the valve can go. Default is 90%. ix) SP14, Set the control gain for error. Default is 25. x) SP15, Set the control gain for slope. Default is 25. NOTE: Setpoints 14 and 15 are site specific dealing with system fluid mass, component size and other factors affecting the reaction of the system to control inputs. These setpoints should be set by personnel experienced with setting up this type of control. 3) If LIFT was selected for fan control, use a) SP3, Set the VALVE TARGET (setpoint), usually 30 psi below the minimum fan stage setpoint established in TOWER SP11. This keeps full flow through the tower until the last fan is staged off. b) SP5, Set VALVE DEADBAND, the default of 6 psi is a good place to start. c) SP8, Set MINIMUM START POSITION when EWT is at or below SP9. Default is 0%. d) SP9, Set the EWT at which the valve position will be at (SP8). Default is 60 F. e) SP10, Set the initial valve position when EWT is at or above SP11. Default 100%. 34 OMM

35 f) SP11, Set the EWT at which initial valve position is set to SP8. Default is 90 F. g) SP12, Set the minimum position to which the valve can go. Default is 10%. h) SP13, Set the maximum position to which the valve can go. Default is 100%. i) SP14, Set the control gain for error. Default is 25. j) SP15, Set the control gain for slope. Default is 25. NOTE: Setpoints 14 and 15 are site-specific dealing with system fluid mass, component size and other factors affecting the reaction of the system to control inputs. These setpoints should be set by personnel experienced with setting up this type of control. Temp-Max Start Setpoint (90 F) Initial Valve Position Temp-Min Start Setpoint (60 F) Min Start Position Set Point (10%) Max Start Position Set Point (90%) See Figure 6 on page 17 for fan staging and bypass valve field wiring connection points. Tower Staging with Bypass Valve Controlled by Fan Stage (VALVE STAGE) This mode is similar to #2 above except that the bypass valve setpoint changes to be set at the same point of whatever fan stage is active rather than just maintaining a single minimum condenser EWT. In this mode the valve controls between fan stages and tries to maintain the fan stage setting in effect. When it is max open or max closed (staging up or down) and the temperature (or lift) moves to the next fan stage, the valve will go the opposite extreme setting. This mode reduces fan cycling. This mode is programmed the same as Mode #2 above except that in SETPOINT, TOWER, SP2, VALVE STAGE is selected instead of VALVE SP. Fan VFD, No Bypass Valve (VFD STAGE) The fan VFD mode assumes the tower is driven by one large fan. Set-up is as above except in SETPOINT, TOWER, SP2, VALVE/VFD is selected. OMM

36 Figure 20, Power Setpoint Screen Table 17, Power Setpoints Description No. Default Range Password Over Voltage Limit to 633 Volts Sets the over voltage limit Nameplate RLA Amps 100 to 600 Amps T Overload Factor to T Comments Sets the Rated Load Amps (RLA) per compressor phase as given on the McQuay nameplate - Load Side Phase Data. VFD over-current trip occurs at Nameplate RLA times Overload Factor. VFD Min Speed offset % to +5 Correction to minimum speed calculation VFD Minimum Speed 7 70% 70 to 100 % T Sets the minimum speed at which the VFD can operate. Has priority over SPs 8 & 9. Soft Load Ramp Time to 60 Minutes O Sets the time period over which the %RLA limit is increased from the SP 5 value to 100%. Used with SPs 5 & 6. Initial Soft Load Limit 5 40% 10 to 100 % O Sets the initial %RLA limit for the soft load ramp. Used with SPs 5 & 7. Soft Load Enable 4 OFF ON, OFF O ON: Soft loading is ON using SPs 5 & 6. OFF: Soft Loading is disabled. Maximum Amps 3 100% 10 to 100 % T Inhibits capacity increase above the %RLA Unloading is forced at 5% above this value. Minimum Amps 2 5% 5 to 80 % T Sets the %RLA below which unloading is inhibited. Demand Limit Enable 1 Off ON, OFF O ON: Limits %RLA to a value set by the Demand Limit analog input, where: 4mA = 0 %RLA 20mA = 100 %RLA OFF: The Demand Limit input is ignored. 36 OMM

37 Figure 21, Staging Setpoint Screen Table 18, Staging Setpoints Description No. Default Range Compr #1 Stage Sequence # 3 1 Compr #1 Staging Mode 2 Normal Maximum Compressors ON 1 to No of Comp. In System NORMAL HI-EFF PUMP STANDBY Password O O 1 1 to 64 O Comments Sets a sequence (order) for compressors staging ON/OFF. Compressors with the same sequence # will auto balance starts/hours. Sequence # takes priority over staging mode. NORMAL: Uses only sequence number and/or balance starts/hours HI EFF: Starts 1 compressor on each dual first. PUMP: Starts all compressors on one chiller first. STANDBY: Use this compr only if another fails. For a standby system, normally set to: (total # of compressors) minus (# of standby compressors). OMM

38 Figure 22, Unit Setpoint Screen Table 19, Unit Setpoints Description No. Default Range Password Comments Liquid Injection 14 Off Off, Auto T EXV Total Offset to 100% O The EXV position is offset by this constant amount. EXV Balance Offset EXV Balance Gain to 10 Deg F O to 5 O Unload Timer sec 10 to 240 Seconds O Stop To Start Timer 9 1 Min 0 to 20 Minutes O Start To Start Timer 8 1 Min 0 to 60 Minutes O Evap Recirculate min 0.2 to 5.0 Minutes O Timer Nominal Capacity 6 500/ O Continued next page. Adds to difference between Condenser Approach and Suction Superheat. A more positive value raises the evaporator liquid level. Gain factor applied to: (Condenser Approach - Suction Superheat + EXV Balance Offset). An increase makes the balance function more sensitive Sets the maximum amount of time a compressor will unload before it turns OFF (goes to postlube). Sets the amount of time that must occur after a compressor stops until it can restart. Sets the amount of time that must occur after a compressor starts until it can start again. Sets the amount of time the evaporator pump must run before a compressor can start. Sets the nominal capacity of an individual compressor. Used to decide when to turn OFF a compressor (stage down) 38 OMM

39 Description No. Default Range Condenser Pump 5 #1 Only Evaporator Pump Control Source 4 #1 Only #1 ONLY, #2 ONLY AUTO #1 PRiMARY, #2 PRIMARY #1 ONLY, #2 ONLY AUTO #1 PRiMARY, #2 PRIMARY Password 3 USER USER, SWITCH, BAS O O O Comments #1 ONLY: Use only pump #1 #2 ONLY: Use only pump #2 AUTO: Balance hours between #1 and #2. #1 PRIMARY: Use #1. If it fails, then use #2. #2 PRIMARY: Use #2. If it fails, then use #1 #1 ONLY: Use only pump #1 #2 ONLY: Use only pump #2 AUTO: Balance hours between #1 and #2. #1 PRIMARY: Use #1. If it fails, then use #2. #2 PRIMARY: Use #2. If it fails, then use #1. Sets control source for Unit Enable, Mode, & LWT SPs. USER: Control is from touchscreen or remote user SWITCH: As USER except Mode is controlled by the Mode digital input. BAS: Control is from the BAS network. Unit Mode 2 COOL Cool, ICE, HEAT O COOL: Maintains evaporator LWT at WATER-SP1. Unit Enable 1 OFF OFF AUTO O OFF: Compressors, pumps, & fans are OFF. AUTO: Evap pump is ON, Compressors, condenser pump, & fans will operate as needed to maintain water temperature. Figure 23, Water Setpoint Screen Detail table on following page. OMM

40 Table 20, Water Setpoints Description No. Default Range Password Comments Condenser Flow Full Scale Evaporator Flow Full Scale Maximum Reset Delta-T Start Reset Delta-T LWT Reset Type 7 None Maximum LWT Rate Minimum LWT Rate to 10,000 GPM O Sets the full scale (20mA) value for the condenser flow rate analog input to 10,000 GPM O Sets the full scale (20mA) value for the evaporator flow rate analog input to 20.0 Deg F O Reset Type (SP9) = Return: Sets the maximum LWT reset that can occur. Reset Type (SP9) = 4-20mA: Sets amoumt of reset at 20mA input to 20.0 Deg F O Sets evaporator delta-t above which Return reset begins Return 4-20mA 0.1 to 5.0 Deg F/min 0.1 to 5.0 Deg F/min Stage Delta-T to 5.0 Deg F O Startup Delta-T 3 3 Deg F 0.0 to 10.0 Deg F O Shutdown Delta-T 2 3 Deg F 0.0 to 3.0 Deg F O Leaving Water Temp - COOL 1 44 F 35 to 80 Deg F O O O O Reset raises LWT setpoint Return (uses SPs 10 & 11) 4-20mA (4mA=None,20mA=Max asset by SP 11) If the LWT rate is above this value, capacity increase is inhibited. Sets the value below which an additional compressor can stage on. Sets amount leaving water must go above set point for next compressor to start. Sets amount leaving water must go above for first compressor to start. Sets amount leaving water must drop below setpoint for last compressor to stop. Sets control target for evaporator leaving water temperature in COOL mode. Service Screens Figure 24, Service Screen Screen explanation on following page. 40 OMM

41 A matrix in the middle of the screen shows the chillers and compressors attached to the network. A green box indicates that a given controller is present and communicating. This is an effective means for verifying communication between units and compressors on the same network. SELECT LANGUAGE allows toggling between the available languages. The language can be set separately for display or history, which is used for alarm and trend files. Currently only English is available. The UNAUTHORIZE/AUTHORIZE button is used to access a keypad dialog box to enter a password. O= Operator password : default = 100 T = Technician level password is reserved for authorized technicians Date/Time in the upper-right corner is pressed to set the correct date and time. Downloading Data Trend data can be downloaded for review and storage as a personal computer file or printed as a hard copy for future reference. This is valuable for troubleshooting potential problems or reviewing the chiller s general performance. The last 30 days of history data can be downloaded from the controller, one day at a time. To download history data from the chiller: 1) Install a USB memory stick into an open USB slot on the chiller controller. These slots are located on the top and bottom of the metal bracket holding the main chiller controller (see page 10 for panel layout). (NOTE: one of these slots will have a USB cable going to J13. DO NOT UNPLUG THIS CABLE). Do not remove the main memory stick located behind the metal bracket. Thirty MB per day should be available on the USB memory stick for data accumulation. There is no warning of insufficient space. 2) Navigate to the OITS ALARM screen. 3) Highlight a day on the calendar. 4) Press download button. The controller will display a notification of "download complete" at the end. To analyze downloaded data: 1. The chiller data is in binary format and must be compiled into spreadsheet format with a separate program. Download trend"wme Trend Tool" from on the Download tab, under Application Software. Troubleshooting: 1) "Error mounting the USB drive". Action: Remove and reinstall USB memory stick and repeat. If problem persists, try a different USB memory stick. Name brand memory sticks are recommended. 2) No data appears on the disk after download. Cause: no data available for that day. OMM

42 Chiller Alarms Figure 25: Active Alarm Screen The Active Alarm screen is accessible when an active alarm exists on the unit by pressing the red alarm signal on any screen. Pressing any ALARM on the screen will open another screen that will show the condition of the chiller at the time of alarm. The last eight alarms are arranged in order of occurrence, with the most recent on top. Once the abnormal condition is corrected, pressing the "CLEAR" key will clear the alarm. Both current active alarms and cleared alarms (there may be more than one of each) are displayed. Alarms with a red bar to the left are current, uncleared alarms. Cleared alarms have a black bar. Alarms shown in red are for equipment protection control and cause a compressor shutdown, Alarms shown in yellow or blue will inhibit loading, or load or unload the compressor to correct a potential problem or indicate a condition requiring attention but not serious enough to cause a shutdown. The date/time and cause of the alarm are displayed. Pressing any alarm will open a snapshot screen showing the unit operating parameters at the time of failure. Touching the gray area of this screen will close it. After eliminating the cause of the alarm, clear the alarm by pressing the CLEAR button. This will clear the alarm from the register and allow the unit to restart after going through the start sequence. The alarm button will return to its normal color. However, if the cause of the alarm is not remedied, the alarm is still active and the alarm message will remain active. The unit will not begin its starting sequence. Always remedy the cause of an alarm before attempting to clear it. See Table 21 for alarm details. 42 OMM

43 Table 21, Alarm Details and Troubleshooting Guide Severity Clear Screen Text Occurs When Troubleshooting Shutdown Manual Discharge Temperature High Shutdown Manual Mechanical High Pressure Temp > High Discharge Temperature SP Digital Input on VFD= High Pressure (this switch connects directly to the VFD) (from MBR 201/15) Causes: Low or No Condenser Water Flow Causes: Loss of condenser water flow HPS failure Condenser water flow low. Rotor and/or stator cooling circuit fault Shutdown Manual Motor Stator Temperature High Analog Motor Temp (any sensor) > Motor Temp SP Causes: Motor stator cooling solenoid not open, rotor cooling stepper motor not functioning correctly, Motor rotor superheat or gain setpoints incorrect ( contact factory) Shutdown Shutdown Manual Manual Motor Gap Temperature High Rotor Pump Superheat Low Shutdown Manual Surge Temperature Shutdown Manual Motor Start Failure Shutdown Manual No Compressor Stop Shutdown Manual VFD Fault Shutdown Manual VFD Reference Fault Motor Gap Temperature > 130 F Rotor Pump Superheat (Rotor Pump Temp Saturated Suction Temp) < 5 F for 5 minutes with compressor running FOR Surge Temp (ST) = Sctn Temp Evap LWT: IF (ST < Surge Temp Limit SP at compressor start) THEN (alarm if ST > 2 X Surge Temp Limit SP) ELSE (alarm if ST slope > Surge Slope Limit SP until ST < Surge Temp Limit SP, then alarm if ST > 2 X Surge Temp Limit SP). (Motor speed not = speed command AND Compressor ON) for > 15 seconds %RLA > Motor Current Threshold SP with Compressor OFF for 30 sec VFD Fault AND Compressor State = FLOAT, START, RUN, or UNLOAD Failure to calculate speed pulse reference position at 900 rpm Shutdown Manual VFD Loss of Motor Sync Loss of VFD phase lock loop synchronization Shutdown Manual VFD Motor Stall Shutdown Manual Continued next page. VFD Speed Command Fault No speed pulse detected when motor should be running Commanded speed fault Rotor and/or stator cooling circuit fault. Causes: Motor stator cooling solenoid not open Motor rotor cooling stepper motor not opening, Motor rotor superheat or gain setpoints incorrect ( contact factory) Rotor cooling circuit fault. Causes: rotor cooling valve stuck open, Motor rotor superheat or gain setpoints incorrect ( contact factory) Compressor Surge detected. Causes: Compressor Surge/Stall line not set properly. See setpoint section. Loss of condenser or evaporator GPM Low Evaporator or condenser GPM Condenser fouling Motor did not start. Causes: VFD control failure, Check VFD enable signal wiring, Check VFD breaker Motor running while it should be off. Causes: VFD enable relay failure VFD CTs failure VFD loss of communications. General VFD fault. Normally accompanied by another fault. Speed pulse feedback not present: Causes: Speed sensor fault, Speed sensor wiring fault, VFD controller fault Speed pulse loss while running Causes: Speed sensor fault, Speed sensor wiring fault, VFD controller fault Speed pulse feedback not present: Causes: Speed sensor fault Speed sensor wiring fault VFD controller fault Motor speed outside of expected range. Causes: Speed sensor fault, Speed sensor wiring fault, VFD controller fault OMM

44 Severity Clear Screen Text Occurs When Troubleshooting Shutdown Manual VFD Cooling Fan Fault Failure of fan monitor circuit Fan is stopped. Causes: Check fan CT wiring, check CT for open circuit, fan failure Shutdown Manual VFD Processor Fault VFD processor hardware or software trap fault Causes: Processor fault or overheating. Check fan operation for proper airflow. If persistent, replace controller. Shutdown Manual VFD Maintenance Mode Maintenance mode switch activated (B17 MBR 201/14) Jumper missing. See VFD schematic. Jumper required for normal chiller operation Shutdown Manual Suction Pressure Sensor Fault Sensor shorted or open (Input voltage < 0.2 OR > 4.6 volts) Causes: Sensor wiring fault, sensor fault Shutdown Manual Discharge Pressure Sensor Fault Sensor shorted or open (Input voltage < 0.2 OR > 4.6 volts) Causes: Sensor wiring fault, sensor fault Shutdown Manual Condenser Rfr Ckt #1 Pressure Sensor Fault Sensor shorted or open (Input voltage < 0.2 OR > 4.6 volts) Causes: Sensor wiring fault, sensor fault Shutdown Manual Condenser Rfr Ckt #2 Pressure Sensor Fault Sensor shorted or open (Input voltage < 0.2 OR > 4.6 volts) Causes: Sensor wiring fault, sensor fault Shutdown Manual Suction Temperature Sensor Fault Sensor shorted or open (Input voltage < 0.2 OR > 4.6 volts) Causes: Sensor wiring fault, sensor fault Shutdown Manual Discharge Temperature Sensor Fault Sensor shorted or open (Input voltage < 0.2 OR > 4.6 volts) Causes: Sensor wiring fault, sensor fault Shutdown Manual Motor Gap Temperature Sensor Fault Sensor shorted or open (Input voltage < 0.2 OR > 4.6 volts) Causes: Sensor wiring fault, sensor fault Shutdown Manual Rotor Pump Temperature Sensor Fault Sensor shorted or open (Input voltage < 0.2 OR > 4.6 volts) Causes: Sensor wiring fault, sensor fault Shutdown Manual Compressor Surge/ Bearing Orbit Shutdown Manual Communications Fault Mag bearings exceed allowable orbit or sensor fault Loss of communications between compressor and chiller controller Causes: Compressor dynamic load change. Compressor surge. Improperly set stall/surge line setpoints Bearing controller fault or bearing amplifier fault. Contact factory if persistent. Check wiring and verify correct software versions Shutdown Manual Evaporator Leaving Water Temperature Sensor Fault Sensor shorted or open (Input voltage < 0.2 OR > 4.6 volts) AND Unit Mode = COOL or ICE Causes: Sensor wiring fault, sensor fault Shutdown Manual Condenser Leaving Water Temperature Sensor Fault Sensor shorted or open (Input voltage < 0.2 OR > 4.6 volts) AND Unit Mode = Heat Causes: Sensor wiring fault, sensor fault Shutdown Manual Software Fault Controller internal check failure Causes: Compressor controller fault. If persistent, contact factory. Shutdown Manual Evaporator Water Flow Loss Evaporator Flow DI = No Flow for > 12 sec with compressor running Causes: Loss of evaporator flow, evaporator pump off, evap head gasket leaking or missing, sensor wiring fault, evaporator flow sensor failure Shutdown Manual Condenser Water Flow Loss Condenser Flow DI = No Flow for > 20 sec with compressor running OR no flow in START state at a point (Pre-Start Timer SP + 30 sec) after Pressure Ratio is OK Causes: Loss of condenser flow, condenser pump off, condenser head gasket leaking or missing, sensor wiring fault, condenser flow sensor failure Limit Auto Low Evaporator Pressure Inhibit Loading Suction Pressure < (Low Evap Press SP)+3psi Causes: Low evaporator water flow rate, low refrigerant in chiller, setpoints incorrect for operating conditions Continued next page. 44 OMM

45 Severity Clear Screen Text Occurs When Troubleshooting Limit Auto Evaporator Pressure Low (Freeze) Saturated Suction Temp < Evaporator Freeze SP Causes: Low evaporator water flow rate, low refrigerant in chiller, setpoints incorrect for operating conditions Limit Auto Condenser pressure Low (Freeze) Saturated Cond Temp < Condenser Freeze SP Causes: Low evaporator water flow rate, low refrigerant in chiller, setpoints incorrect for operating conditions Limit Auto Discharge Temperature High Temperature > High Discharge Temperature- Load SP AND Suction superheat < 15 F Causes: Low or No Condenser Water Flow Notice None Software Problem (Compressor) Controller internal check failure Causes: Compressor control fault. Contact factory if persistent. Limit Manual Evaporator Pump #1 Fault No flow indicated for (5 sec) with Evaporator Pump #1 ON AND [the other pump is available (per the Evap Pump SP) AND has not faulted] Evaporator flow not detected. Causes: improper pump wiring Limit Manual Evaporator Pump #2 Fault No flow indicated for (5 sec) with Evaporator Pump #2 ON AND [the other pump is available (per the Evap Pump SP) AND has not faulted] Evaporator flow not detected. Causes: improper pump wiring Limit Manual Condenser Pump #1 Fault No flow indicated for (5 sec) with Condenser Pump #1 ON AND [the other pump is available (per the Evap Pump SP) AND has not faulted] Condenser flow not detected. Causes: improper pump wiring Limit Manual Condenser Pump #2 Fault No flow indicated for (5 sec) with Condenser Pump #2 ON AND [the other pump is available (per the Evap Pump SP) AND has not faulted] Condenser flow not detected. Causes: improper pump wiring Limit Notice Notice Notice Notice Manual Auto Auto Auto Auto Evaporator Entering Water Temperature Sensor Fault Evaporator Entering Temperature Sensor Fault Condenser Entering Temperature Sensor Fault Condenser Leaving Temperature Sensor Fault Liquid Line #1 Refrigerant Temperature Sensor Fault Sensor fault (Input voltage < 0.2 OR > 4.6 volts) AND the LWT Reset Type SP is set to RETURN Sensor is open or shorted (Input voltage < 0.2 OR > 4.6 volts) Sensor is open or shorted (Input voltage < 0.2 OR > 4.6 volts) Sensor is open or shorted (Input voltage < 0.2 OR > 4.6 volts) Sensor is open or shorted (Input voltage < 0.2 OR > 4.6 volts) Notice None System Fault Controller internal fault Causes: Sensor wiring fault, sensor fault Causes: Sensor wiring fault, sensor fault Causes: Sensor wiring fault, sensor fault Causes: Sensor wiring fault, sensor fault Causes: Sensor wiring fault, sensor fault Causes: controller fault. If persistent contact factory. OMM

46 Trend Screens Figure 26, Trend History Screen This screen plots the parameters shown over various time frames; 8 = eight hours, 2 = two hours, 1/3 = 20 min., < and > move the screen to the right or left. NOW displays current status. 46 OMM

47 Operating the Chiller Interface Panel On/Off The Operator Interface Panel is turned on and off with a push-push switch located on the right side of the OITS. The screen is equipped with a screen saver that blackens the screen. Touching the screen anywhere reactivates it. If the screen is black, touch it first to be sure it is on before using the ON/OFF switch. Start/Stop Unit There are four ways to start/stop the chiller. Three are selected in SETPOINT\MODE\SP3, the fourth way is through panel-mounted switches: 1. Operator Interface Panel (LOCAL): View screens have AUTO and STOP buttons that are only active when the unit is in "LOCAL CONTROL". This prevents the unit from being accidentally started or stopped when it is under control from a remote switch or BAS. When these buttons are pressed, the unit will cycle through its normal starting or stopping sequence. 2. Remote Switch: Selecting SWITCH in Unit/ Control Source (SP3) will put the unit under the control of a remote switch that must be wired into the control panel (see Figure 6 on page 17). 3. BAS: BAS input is field-wired into a card that is factory installed (can also be field installed)on the unit controller. 4. Control Panel Switches: The unit control panel, located adjacent to the Interface Panel has switches inside the panel for stopping the unit and compressor. When the UNIT switch is placed in the OFF position the chiller will shut down through the normal shutdown sequence. The COMPRESSOR switch will immediately shut down the compressor without going through the shutdown sequence when placed in the OFF position. A third switch is mounted on the left outside of the unit controller. It performs the same function as the UNIT switch inside the panel and causes a normal shutdown. Changing Setpoints Set points are easily changed on the Operator Interface Touch Screen (OITS). A complete description of the procedure begins on page 26. Sequence of Operation Start-up of Magnitude Compressors: Next On Status If none of the OFF conditions are true, then all the MicroTech compressor controls in a network of units will pole the status of each to determine the one having Next On status, which is usually the compressor with the least starts. This takes about one minute. Evap (Evaporator) Pump Start Once this is determined, the unit controller of the chiller with the Next On compressor (when there are multiple chillers) will start the evaporator pump and determine if there is load based on the water temperature. This is determined if the leaving evaporator water is above the LWT Setpoint plus Startup Delta T. If there is no load, based on the temperature, the unit is in the state of Awaiting Load. Bearing Levitation If there is load, the unit waits for the Evaporator Recirculation Timer period (default value of 30 seconds) and then executes bearing levitation. OMM

48 Cond (Condenser) Pump Start After levitation is confirmed, the controller starts the Condenser Pump and checks for condenser flow before starting the first compressor. Compressor Start The compressor starts when the following conditions are met: 1) Condenser flow present for 5-seconds (condenser state is RUN) 2) Vanes are at the start position 3) Pre-start timer expired Starting the compressor is accomplished by closing the VFD enable relay in the compressor controller. The VFD ramps to 900 rpm for WME 500 and 700 rpm for WME 700, waits at this speed until motor synchronization occurs, then ramps up to the VFD minimum speed value. Compressor Run The compressor that is running will signal all other compressors (including compressor on other chillers when multiple chillers are networked together) when it reaches full load. 1) Percent RLA exceeds the Maximum Amps setpoint (typically 100%) or the Active-Amp-Limit from an externallimiting source. 2) Evaporator (suction) Saturation pressure drops below the Low Evap Pressure Inhibit setpoint. 3) Actual compressor RPM is at its maximum speed capability and the vanes are within 5% of the Maximum Vane Position setpoint. The maximum speed capability is when it exceeds 99% of Max RPM limit for the compressor or the VFD has reached an internal limit preventing further increase in speed. Capacity Control: During the compressor run state, the chiller will modulate to maintain the evaporator leaving water temperature at the set point. The status window will indicate the operating mode: Speed control, Inlet Guide Vane (IGV) control, or Range Extension System control. The chiller will pick the optimum capacity control mode for best efficiency. Speed Control: IGV is 100%, Range Extension is 0% and capacity is adjusted using compressor speed. IGV Control: Speed has been reduced to the minimum speed for the operating conditions and capacity is adjusted using inlet guide vanes. Range Extension Valve is set for 0%. Range Extension Control: Speed and IGV at their minimum for the operating conditions and the capacity is adjusted using the range extension valve. This mode provides greater unloading capability at high lift conditions. Note: the options for capacity control mode are in High Lift Mode setpoint in the SERVICE group on the setpoint screen (technician password required). As lift and load conditions vary, the minimum speed and minimum IGV position will vary. In general, the higher the lift, the higher the minimum speed and minimum IGV position. Staging Compressors Off: The setpoint of Nominal Capacity is used for defining the point to stage off a compressor on a multi-chiller system. With each compressor having its Nominal Capacity defined, then the network, which is load balanced, continues to unload when below setpoint. Each compressor keeps computing the spare capacity of the network. When the designated Next Off sees enough spare capacity, it will turn off. Then similarly, in about 40 seconds, a new compressor will be designated as the Next Off and the spare capacity will continue to be calculated between the remaining compressors. Compressors continue to unload and stage off until there is only one compressor running. It will shut off when the water temperature reaches the LWT Setpoint minus the Shutdown Delta T. Staging Compressors On The Stage Delta-T setpoint is used to define when another compressor must stage on. The compressor with Next On will start when the leaving water temperature exceeds the value of the active LWT plus the Stage Delta-T. 48 OMM

49 Troubleshooting The primary troubleshooting method is to use the interface panel (OITS) to determine the alarm status, I/O status, unit state, and trend data. If this method is not successful, the next step is to determine if all controllers are present, powered up, fully booted up, and are communicating normally. All controllers have tell-tale LEDs that should be lit to determine powered-up state. Control power starts from the Intermediate Power Supply (IPS) in the VFD panel with a few exceptions. The IPS powers a variety of smaller power supplies for control power, the bearings, and most auxiliary systems. The control power for the cabinet fans, ground fault and VFD cooling solenoids comes from a control power transformer. PROBLEM Controls won't boot up LEDs are not lit POSSIBLE CAUSES/CONDITION If no power Troubleshooting Chart POSSIBLE CORRECTIVE STEPS Check state of LEDs on chiller controller, compressor controller, and VFD controller. LEDs should be lit. Check DC voltage distribution board LEDs. Check IPS. Check fuses into IPS. Check small fuse on IPS PCB ( 110V). Check control power transformer. One LED is not lit VFD will not start Chiller will not start Check fuses/breakers into power supplies. If persistent, identify corresponding power supply and repair/replace. Check OITS alarms. Check control harness to VFD, enable signal, 24VDC power, rpm signal. Check VFD communication cable, Ethernet. Check VFD voltage breakout board that all LED's are lit. Check that all VFD control cables are plugged in and fully seated. Check sequence of operation. Check chiller OITS State screen to determine what state the unit is in. Check alarms. VFD starts but shuts off on alarm Inlet Guide Vane (IGV) alarm Check Alarm codes. Follow VFD troubleshooting chart. IGV feedback doesn't match setpoint on I/O OITS screen. Bearing alarm During operation, Out of orbit alarm due to surge/ stall. If data is from compressor data Verify Compressor communication present. Look for lit up green boxes in chiller controller on "SET" screen #2. If not, check Ethernet cable and that compressor controller board LEDs are lit. If yes, reboot chiller. OITS data missing OITS data missing Controller unhealthy alarm If data is from VFD If data from power meter If data is from chiller controller Check communication cable. Cycle power to reset VFD controller. Verify LEDs lit on VFD controller. Check power supply. Verify power meter communication cable wiring. Verify power meter configuration. Check that sensors are wired properly. Check that LEDs are lit on chiller controller. Check power supply. Verify communications cable is properly connected. Reboot chiller OMM

50 Operation with Failed OITS The touchscreen does not have any control function; it is only a window into the unit s controller and operation. Chiller operation is not affected by a failed touchscreen. The touchscreen (OITS) is the primary user interface to the chiller. If this screen is not operating as expected, use the following troubleshooting procedure: Indication; Screen is blank, power indicator is green. Procedure: Screen is in screen saver mode. Touch screen and image will appear. Indication; Screen is blank, power indicator is unlit. Problem: Screen has been powered off. Procedure: Press power button on lower outside edge of screen. Indication; Screen is blank, power indicator is unlit. Problem: Screen is not receiving power, Procedure: Ensure power cable is plugged into screen and controller. Indication; Screen is blank, power indicator is unlit. Problem: Unit controller is not powered. Procedure: Check to see if LEDs are lit/blinking within chiller controller box. If not, contact chiller service. Indication; Screen is blank, power indicator is unlit Problem: Touchscreen failure Procedure: Replace touchscreen. Indication; Screen is working but touch function isn't working. Problem: Disconnected serial cable. Procedure: Ensure cable is connected, reboot chiller. Indication; Screen is working but touch function isn't working. Problem: Touchscreen failure Procedure: Replace touchscreen. As temporary measure, install USB mouse on chiller controller to replace the touch function. Plug USB mouse into spare USB port on chiller controller. As a temporary replacement for a completely failed touchscreen, 1) Install a VGA monitor using cable from chiller controller box. (Blue plug) 2) Plug USB mouse into spare USB port on chiller controller. 50 OMM

51 Maintenance External Sensors and Valve Locations Discharge Pressure Sensor Discharge Temp Sensor High Pressure Switch Suction Pressure Suction Temperature IGV Stepper Mtr Control & IGV Position Sensor 300VDC Power Compressor Sensor Harness VFD Control Cable Ethernet Connection OMM

52 Flow Switch Water Temperature Sensor Liquid Line Temperature Sensor Electronic Expansion Valve 52 OMM

53 Compressor Liquid Injection VFD Cooling In Rotor Injection Cooling Stator Cooling In Liquid Line Shut Off Valve Compressor Controller. Cover Removed Rotor Cooling Inlet Rotor Injection Cooling Rotor Cooling Outlet Compressor Bottom) OMM

Magnitude Frictionless Centrifugal Chillers

Magnitude Frictionless Centrifugal Chillers Operation & Maintenance Manual OMM 1034-1 Group: Chiller Part Number: 331499501 Effective: July 2011 Supersedes: June 2011 Magnitude Frictionless Centrifugal Chillers Model WME 0500-700 Software Version:

More information

GeneSys Air-Cooled Screw Compressor Chiller

GeneSys Air-Cooled Screw Compressor Chiller Operation Manual OM AGSB-5 Group: Chiller Part Number: 331373201 Date: June 2005 Supersedes: OM AGSB-4 GeneSys Air-Cooled Screw Compressor Chiller AGS 230A/B through AGS 475A/B, 60 Hertz AGS 206A/B through

More information

Open Protocol Data Communications

Open Protocol Data Communications MicroTech Series-100 Centrifugal Chiller Open Protocol Data Communications Information Packet Version 3.2 April, 1996 - C O N F I D E N T I A L - This Document may not be copied or reproduced in any way

More information

Sales and Engineering Data Sheet ED

Sales and Engineering Data Sheet ED Sales and Engineering Data Sheet ED 15121-7 Group: Controls Part Number: ED 15121 Date: July 2017 MicroTech III Chiller Unit Controller Protocol Information Modbus Networks ANSI/ASHRAE 135-2004, BACnet

More information

IOM Installation, Operation, and Maintenance Manual. Magnitude Magnetic Bearing Centrifugal Chillers

IOM Installation, Operation, and Maintenance Manual. Magnitude Magnetic Bearing Centrifugal Chillers Installation, Operation, and Maintenance Manual Magnitude Magnetic Bearing Centrifugal Chillers IOM 1210-1 Group: Chiller Part Number: IOM1210-1 Date: August 2014 Model WMC, C Vintage 125 to 400 Tons (440

More information

IOM Installation, Operation, and Maintenance Manual. Magnitude Magnetic Bearing Centrifugal Chillers

IOM Installation, Operation, and Maintenance Manual. Magnitude Magnetic Bearing Centrifugal Chillers Installation, Operation, and Maintenance Manual Magnitude Magnetic Bearing Centrifugal Chillers IOM 1210-1 Group: Chiller Part Number: IOM1210-1 Date: August 2014 Model WMC, C Vintage 125 to 400 Tons (440

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

Chiller Manufacturer should have been manufacturing chillers utilizing magnetic bearing, oil free technology for more than 10 years.

Chiller Manufacturer should have been manufacturing chillers utilizing magnetic bearing, oil free technology for more than 10 years. TURBOCOR COMPRESOR CHILLERS General Description Microprocessor controlled, water chiller using HFC 134a refrigerant, two stage centrifugal oil free variable speed compressor's and electronic expansion

More information

CONTROL PANEL OPERATING MANUAL AIR-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMAC00A10-12EN

CONTROL PANEL OPERATING MANUAL AIR-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMAC00A10-12EN CONTROL PANEL OPERATING MANUAL AIR-COOLED SCREW CHILLER MICROTECH III CONTROLLER Table of Contents - 2 - INTRODUCTION... 3 OPERATING LIMITS:... 4 CONTROLLER FEATURES... 4 GENERAL DESCRIPTION... 5 CONTROL

More information

Cutting Edge Compressor Technology

Cutting Edge Compressor Technology CHILLER MODULES Cutting Edge Compressor Technology MagLev ; magnetic levitation Oil Free design Quieter than typical background noise Soft start; pulls only 2 amps at 460V Superior part load efficiency

More information

MicroTech Series 200 Centrifugal Chiller

MicroTech Series 200 Centrifugal Chiller Protocol Data Information Packet Version 2.2 Group: Controls Date: March 1999 MicroTech Series 200 Centrifugal Chiller Data Communications Packet for Protocol 2002 McQuay International Revision History

More information

Pathfinder Air-Cooled Chillers

Pathfinder Air-Cooled Chillers Operating & Maintenance Manual OMM 1123 Group: Chiller Part Number: OMM 1123 Date: January 2012 Supercedes: December 2011 Rev 00 Pathfinder Air-Cooled Chillers AWS 170A/B through AWS 550A/B (Includes Models

More information

Air-Cooled Screw Compressor Chillers

Air-Cooled Screw Compressor Chillers Catalog Cat AGSD-1 Air-Cooled Screw Compressor Chillers Models AGS 225D to AGS 450D 210 to 450 Tons, 740 to 1580 kw Packaged or with Remote Evaporator or Chilled Water Pump Package R-134a, Hz Engineered

More information

Pathfinder Air-Cooled Chillers

Pathfinder Air-Cooled Chillers Operating & Maintenance Manual OMM 1168 Group: Chiller Part Number: OMM 1168 Date: September 2012 Rev 00 Supercedes: OMM 1123, July 2012 Pathfinder Air-Cooled Chillers AWS 170A/B through AWS 550A/B (Includes

More information

Magnitude Magnetic Bearing Centrifugal Chiller

Magnitude Magnetic Bearing Centrifugal Chiller Installation Manual IM 10-2 Group: Chiller Part Number: 1499601 Effective: October 2011 Supersedes: August 2011 Magnitude Magnetic Bearing Centrifugal Chiller Model WME 0500, WME 0700 400 to 700 tons (1400

More information

Call us today! (800)

Call us today! (800) 500 TON AIR-COOLED CHILLER PA-ACCTR-500 Call us today! (800)341-4297 The 500-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes). Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage

More information

Magnitude Frictionless Centrifugal Chiller

Magnitude Frictionless Centrifugal Chiller Installation Manual IM 1033-1 Group: Chiller Part Number: 331499601 Effective: February 2010 Supersedes: November 2009 Magnitude Frictionless Centrifugal Chiller Model WME 400 to 550 tons (1400 to 1900

More information

CONTROL PANEL OPERATING MANUAL WATER-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMWC00A04-14EN

CONTROL PANEL OPERATING MANUAL WATER-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMWC00A04-14EN CONTROL PANEL OPERATING MANUAL WATER-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMWC00A04-14EN Table of Contents INTRODUCTION... 2 CONTROLLER OPERATING LIMITS:... 3 CONTROLLER FEATURES... 3 GENERAL

More information

Call us today! (800)

Call us today! (800) 150 TON AIR-COOLED CHILLER PA-ACCTR-150 Call us today! (800)341-4297 The 150-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

Water-Cooled Dual Compressor Screw Chiller

Water-Cooled Dual Compressor Screw Chiller Installation Manual IM 692-1 Group: Chiller Part Number: 629955 Effective: May 1997 Supersedes: IM663-1 IM683 IM692 Water-Cooled Dual Compressor Screw Chiller Installation Manual PFS 155C through PFS 210C,

More information

Call us today! (800)

Call us today! (800) PA-ACCTR-200 Call us today! (800)341-4297 The 200-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable, efficient and quiet chiller

More information

CONTROL PANEL OPERATING MANUAL WATER-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMWC00A07-16EN

CONTROL PANEL OPERATING MANUAL WATER-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMWC00A07-16EN CONTROL PANEL OPERATING MANUAL WATER-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMWC00A07-16EN - 2 - Table of Contents INTRODUCTION... 2 CONTROLLER OPERATING LIMITS:... 3 CONTROLLER FEATURES... 3

More information

MicroTech Series-200 Flooded Screw Chiller

MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Infomation Packet Version 1.0 Group: Controls Date: February 1997 MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Communications 2002 McQuay International - C O N F I D

More information

NQ Series Portable Chillers

NQ Series Portable Chillers NQ Series Portable Chillers Electrical Components Mounted and Wired All electrical components and sensors are mounted, wired, and fully tested at the factory to reduce installation time and ensure the

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas User s Manual TIGER S EYE E-Series Mark V Jockey TIGERFLOW Systems, Inc. 4034 Mint Way Dallas, Texas 75237 214-337-8780 www.tigerflow.com TABLE OF CONTENTS Introduction... 4 Sequence of Operation... 5

More information

Water-Cooled Modular Chillers. Product Data Catalog. Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X

Water-Cooled Modular Chillers. Product Data Catalog. Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X Product Data Catalog Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X Variable Speed Total Access Modules MS010W, MS020W, MS030W, MS050W MS010V, MS020V,

More information

Date: August 21, Proposal Number: G Engineer: Payment Terms: Net 30 Days

Date: August 21, Proposal Number: G Engineer: Payment Terms: Net 30 Days Proposal Trane A Division of American Standard Inc. Prepared For: John Weston Desmet Ballestra Job Name: LAUER1 Biodiesel Chiller Pennsylvania Date: August 21, 2006 Proposal Number: G1-95502-1 Engineer:

More information

PACKAGED AIR COOLED Product Data Catalog

PACKAGED AIR COOLED Product Data Catalog PACKAGED AIR COOLED Product Data Catalog MODELS ASP-10A ASP-15A ASP-20A ASP-00P ASP-00F ASP-00G A MEMBER OF MARDUK HOLDING COMPANY, LLC The Leader in Modular Chillers ETL and CSA Approved CHILLER MODULES

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

opti-visor ultra-efficient chiller plant automation Typical specification

opti-visor ultra-efficient chiller plant automation Typical specification opti-visor ultra-efficient chiller plant automation Typical File No: 90.893 Date: february 9, 2015 Supersedes: 90.893 Date: april 20, 2012 contents 1.0 Chilled water plant 4 1.1 General system requirements

More information

Tri-Stack Smart System

Tri-Stack Smart System Tri-Stack Smart System TM Notes & Warnings - The protection provided by this equipment may be impaired if it is not used in the manner specified herein. - Ensure all wiring meets applicable national and

More information

FieldServer Driver - Serial FS McQuay Microtech Open Protocol

FieldServer Driver - Serial FS McQuay Microtech Open Protocol Description FieldServer Driver - Serial FS-8700-80 McQuay Microtech Open Protocol This is an active client protocol. The driver is capable of acting as a master or slave. As a master, the Fieldserver polls

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

Magnitude Magnetic Bearing Centrifugal Chillers. Model WME 400 to 1500 Tons (1400 to 5300 kw) HFC-134a Refrigerant. Catalog 604-8

Magnitude Magnetic Bearing Centrifugal Chillers. Model WME 400 to 1500 Tons (1400 to 5300 kw) HFC-134a Refrigerant. Catalog 604-8 Magnitude Magnetic Bearing Centrifugal Chillers Model WME 400 to 1500 Tons (1400 to 5300 kw) HFC-134a Refrigerant Catalog 604-8 Table of Contents Table of Contents Introduction.... 3 Technology That Just

More information

APC BC300 Series 40kW 208/450/480V User Guide

APC BC300 Series 40kW 208/450/480V User Guide APC BC300 Series 40kW 208/450/480V User Guide Copyright 2002 APC Denmark ApS This manual is subject to change without notice and does not represent a commitment on the part of the vendor Thank You Thank

More information

Water-Cooled Screw Compressor Chillers

Water-Cooled Screw Compressor Chillers Catalog Cat WGS Water-Cooled Screw Compressor Chillers WGS 130AW To WGS 190AW, Packaged Water-Cooled Chiller WGS 130AA To WGS 190AA, Chiller with Remote Condenser 120 to 200 Tons, 420 to 700 kw R-134A,

More information

GeneSys. Air-Cooled Screw Compressor Chillers. Catalog

GeneSys. Air-Cooled Screw Compressor Chillers. Catalog Catalog Cat AGS-2 GeneSys Air-Cooled Screw Compressor Chillers Models AGS 120C to AGS 210C 110 to 210 Tons, 420 to 740 kw Packaged and with Remote Evaporator R-134a, 60 Hz Engineered for flexibility and

More information

Water-cooled chillers with High Speed Centrifugal Compressors

Water-cooled chillers with High Speed Centrifugal Compressors Water-cooled chillers with High Speed Centrifugal Compressors Refrigerant R134a 190-760 (395 to 2660 kw) Refrigerant R1234ze 135 G - 505 G (310 to 1820 kw) Table of Contents Introduction...3 Features and

More information

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification February 11, 2019 Master Panel Product Description The Master Panel shall provide lead/lag control and time based, automatic rotation of up to eight (8) boilers, when used in conjunction with LMV3 or LMV5

More information

IOM Installation, Operation, and Maintenance Manual. Magnitude Magnetic Bearing Centrifugal Chillers

IOM Installation, Operation, and Maintenance Manual. Magnitude Magnetic Bearing Centrifugal Chillers Installation, Operation, and Maintenance Magnitude Magnetic Bearing Centrifugal Chillers IOM 1033-5 Group: Chiller Part Number: IOM1033 Date: October 2016 Supercedes: November 2012 Model WME 400 to 700

More information

SECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

SECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower SECTION 15682 CENTRIFUGAL WATER CHILLERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15540 - Pumping Equipment (HVAC) 3. 15711 - Induced Draft Cooling Tower B. Removal

More information

MACH N-407 Heat Pump Air-Cooled Chiller

MACH N-407 Heat Pump Air-Cooled Chiller MACH060-01-N-407 Heat Pump Air-Cooled Chiller Heat Pump Air-Cooled Chillers for Global Residential and Light Commercial Microclimates MACH NOMENCLATURE BREAKDOWN MACH-060-01 - N - 407 Refrigerant Type

More information

I/O ZONE 560/583 USERS GUIDE

I/O ZONE 560/583 USERS GUIDE I/O ZONE 560/583 USERS GUIDE 641-224 641-242 641-237 1 Table of Contents Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:... 16 SPECIFICATIONS...5 CONTROLLER COMPONENTS...6

More information

.2 Section Waste Management and Disposal.

.2 Section Waste Management and Disposal. Issued 2005/06/01 Section 15624 Packaged Rotary Screw Water Chillers Page 1 of 5 PART 1 General 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

The McQuay DISTINCTION SERIES. Single/Dual Compressor Centrifugal Chillers. Installation and Maintenance Manual

The McQuay DISTINCTION SERIES. Single/Dual Compressor Centrifugal Chillers. Installation and Maintenance Manual Installation and Maintenance Manual IMM WSCWDC-5 Group: Chiller Part Number: 331374801 Effective: August 2007 Supersedes: July 2006 The McQuay DISTINCTION SERIES Single/Dual Compressor Centrifugal Chillers

More information

60Hz. R134a HXWC SERIES. 205 to 560 Tons. Products That Perform...By People Who Care WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS

60Hz. R134a HXWC SERIES. 205 to 560 Tons. Products That Perform...By People Who Care WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS R Products That Perform...By People Who Care FORM NO: MS0455A WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS R134a HXWC SERIES 205 to 560 Tons 60Hz INTRODUCTION Dunham-Bush's HXWC water cooled

More information

Air-Cooled Scroll Compressor Chiller

Air-Cooled Scroll Compressor Chiller Air-Cooled Scroll Compressor Chiller Operation Manual OM AGZC-1 Group: Chiller Part Number: 331376301 Effective: February 2010 Supercedes: April 2009 AGZ 030CH through 190CH, Packaged AGZ 030CB through

More information

Water-Cooled Scroll Compressor Chillers

Water-Cooled Scroll Compressor Chillers Operating Manual OM WGZC-2 Group: Chiller Part Number: 331975301 Effective: August 2011 Supercedes: November 2010 Water-Cooled Scroll Compressor Chillers WGZ 030CW To WGZ 200CW, Packaged Water-Cooled Chiller

More information

Water-Cooled Scroll Compressor Chillers

Water-Cooled Scroll Compressor Chillers Operating and Maintenance Manual OMM 1130 Group: Chiller Part Number: OMM 1130 Effective: March 2012 Supercedes: November 2011 Water-Cooled Scroll Compressor Chillers WGZ030DW to WGZ200DW, Packaged Water-Cooled

More information

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program. 15682 CENTRIFUGAL WATER CHILLERS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 236416 An optional

More information

Centrifugal Compressor Water Chillers

Centrifugal Compressor Water Chillers Centrifugal Compressor Water Chillers Models WSC, WDC, WCC, HSC Includes Higher Voltage (10/11kV) WDC/WCC models People and ideas you can trust. Catalog 605-3 Contents Contents..................................

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00 PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00 1 Contents INTRODUCTION... 3 WARNING LABELS AND SAFETY INSTRUCTIONS... 4 PARALLEL RACK NOMENCLATURE... 5 GENERAL RACK DESCRIPTION...

More information

Magnitude Magnetic Bearing Centrifugal Chillers. Model WME, B-vintage 400 to 1500 Tons (1400 to 5300 kw) HFC-134a Refrigerant.

Magnitude Magnetic Bearing Centrifugal Chillers. Model WME, B-vintage 400 to 1500 Tons (1400 to 5300 kw) HFC-134a Refrigerant. Magnitude Magnetic Bearing Centrifugal Chillers Model WME, B-vintage 400 to 1500 Tons (1400 to 5300 kw) HFC-134a Refrigerant Catalog 629 Table of Contents Table of Contents Introduction.... 3 Technology

More information

CVGF. Water Cooled Centrifugal Chillers

CVGF. Water Cooled Centrifugal Chillers CVGF Water Cooled Centrifugal Chillers January 2010 CVGF Key Features 2 stage centrifugal compressor Semi-hermetic compressor R134a refrigerant Falling film evaporator Economizer cycle NEW Tracer Adaptiview

More information

Sales and Engineering Data Sheet ED

Sales and Engineering Data Sheet ED Sales and Engineering Data Sheet ED 15121-6 Group: Controls Part Number: ED 15121 Date: March 2017 MicroTech III Chiller Unit Controller Protocol Information Modbus Networks ANSI/ASHAE 135-2004, BACnet

More information

Centrifugal, Magnetic Bearing, Compressor Water Chiller Model WMC-035T, 110 to 175 Tons

Centrifugal, Magnetic Bearing, Compressor Water Chiller Model WMC-035T, 110 to 175 Tons Catalog Cat WMC-1 Centrifugal, Magnetic Bearing, Compressor Water Chiller Model WMC-035T, 110 to 175 Tons 3/60/460, 3/50/400 R-134a HFC 134a, The Global Refrigerant of Choice Engineered for flexibility

More information

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION 100 TON AIR-COOLED SCROLL PACKAGED SPECIFICATIONS Call us today! (800)341-4297 Trane Portable Packaged Air Conditioner units contain the best compressor technology available, in order to achieve the highest

More information

Water-Cooled Scroll Compressor Chillers

Water-Cooled Scroll Compressor Chillers Operating Manual OM WGZ-2 Group: Chiller Part Number: 331374501 Effective: March 2005 Supercedes: OM WGZ-1 Water-Cooled Scroll Compressor Chillers WGZ 030AW To WGZ 120AW, Packaged Water-Cooled Chiller

More information

Magnitude Frictionless Centrifugal Chiller Catalog 604-1

Magnitude Frictionless Centrifugal Chiller Catalog 604-1 Magnitude Frictionless Centrifugal Chiller Catalog 604-1 Model WME 400 to 550 tons (1400 to 1900 kw) 3/60/460 HFC-134a Engineered for flexibility and performance Note: The unit shown is for the default

More information

Water-Cooled Screw Compressor Chillers

Water-Cooled Screw Compressor Chillers Water-Cooled Screw Compressor Chillers Catalog 617 WGS 130AW To WGS 190AW, Packaged Water-Cooled Chiller WGS 130AA To WGS 190AA, Chiller with Remote Condenser 120 to 200 Tons, 420 to 700 kw R-134A, 60

More information

Water-Cooled Scroll Compressor Chillers

Water-Cooled Scroll Compressor Chillers Operating Manual OM WGZC Group: Chiller Part Number: 331374501 Effective: January 2008 Supercedes: New Water-Cooled Scroll Compressor Chillers WGZ 030CW to WGZ 200CW, Packaged Water-Cooled Chiller WGZ

More information

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program. 15684 ROTARY SCREW WATER CHILLERS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 236423 An optional

More information

GP SERIES Packaged Chillers

GP SERIES Packaged Chillers Material Handling Process Cooling Temperature Control Size Reduction Temperature Control Process Cooling Material Handling Size Reduction GP SERIES Packaged Chillers Precision Comprehensive Engineered

More information

Dunham Bush Air Cooled Screw Chiller AFVX B 6SR Series

Dunham Bush Air Cooled Screw Chiller AFVX B 6SR Series Dunham Bush Air Cooled Screw Chiller AFVX B 6SR Series Type of Compressors Compressor Rotary Scroll Reciprocating Screw Centrifugal Air Cooled Chiller 77 ~ 329TR (270 ~ 1156 kw) ACDX Series 100 ~ 520TR

More information

AC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT

AC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT AC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT Central Chiller Plant (with Cooling Tower and Chilled Water distribution) The other AC configuration is called a Chilled Water or Larger Cooler system. It

More information

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA 99336 www.jmcvr.com 1-509-586-9893 Table of Contents TABLE OF FIGURES...1 OVERVIEW OF THE HRC CAPABILITIES...2 INSTALLATION AND

More information

Water-Cooled Screw Compressor Chillers

Water-Cooled Screw Compressor Chillers Water-Cooled Screw Compressor Chillers Catalog 617-4 WGS 130AW To WGS 190AW, Packaged Water-Cooled Chiller WGS 130AA To WGS 190AA, Chiller with Remote Condenser 120 to 200 Tons, 420 to 700 kw R-134A, 60

More information

Rev B, 9/2/2009. Kodiak Chiller Overview

Rev B, 9/2/2009. Kodiak Chiller Overview 930-0001 Rev B, 9/2/2009 Kodiak Chiller Overview Presentation Outline Phone: 781-933-7300 Lytron Technical Support Contact Information 3 Introduction 4 Part I: Unpacking 5 Part II: Installation 7 Part

More information

TWLC - Tempered Water Logic Controller. The Intelligent Control

TWLC - Tempered Water Logic Controller. The Intelligent Control TWLC - Tempered Water Logic Controller The Intelligent Control Chiller Controls Features: Up to six (6) stages: individual board for each stage maximizes redundancy. Menu driven access and programming.

More information

Engineered for flexibility and performance

Engineered for flexibility and performance Centrifugal Chillers 200 to 2700 tons Engineered for flexibility and performance Daikin McQuay Single Compressor Centrifugal Chillers A Life Cycle Return on Your Investment Centrifugal chillers are a significant

More information

Magnitude Magnetic Bearing Centrifugal Chillers. Model WME, C-vintage 800 to 1500 Tons (2800 to 5300 kw) HFC-134a Refrigerant.

Magnitude Magnetic Bearing Centrifugal Chillers. Model WME, C-vintage 800 to 1500 Tons (2800 to 5300 kw) HFC-134a Refrigerant. Magnitude Magnetic Bearing Centrifugal Chillers Model WME, C-vintage 800 to 1500 Tons (2800 to 5300 kw) HFC-134a Refrigerant Catalog 632 Table of Contents Table of Contents Introduction.... 3 Technology

More information

As a standard, heat exchangers are provided with flange water connections (BS Standard Table E). All evaporator are supplied fully insulated.

As a standard, heat exchangers are provided with flange water connections (BS Standard Table E). All evaporator are supplied fully insulated. NOMENCLATURE INTRODUCTION The HTT HWDX water-cooled chillers range is the latest addition to HTT s growing family of commercial products, featuring the most current technologies advances. The HWDX main

More information

Introduction. What is the W2W Open controller?

Introduction. What is the W2W Open controller? W2W Open CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-538-01 2/8/2017 Verify that you have the most current version of this document

More information

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC. WYETH-AYERST CANADA INC. 1025, BOUL. MARCEL-LAURIN S T - L A U R E N T, Q U É B E C INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER MODEL P448800LT--55WC--22C66S Prepared par Claude Gadoury, P.

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone: 620-421-0480,

More information

Modular Standard HP Chiller 1/4 screw compressor with Carel driver

Modular Standard HP Chiller 1/4 screw compressor with Carel driver Program for pco¹ pco 2 and pcoc Modular Standard HP Chiller 1/4 screw compressor with Carel driver Manual version 1.0 25 September 2003 Program code: FLSTDmMSDE Do we want you to save you time and money?

More information

AIRSYS-P-SC-CHILLROW-E1503V01.1 CHILLROW. Row Cooling Precision Air Conditioner. Cooling Capacity: 26.2kW~68.6kW

AIRSYS-P-SC-CHILLROW-E1503V01.1 CHILLROW. Row Cooling Precision Air Conditioner. Cooling Capacity: 26.2kW~68.6kW AIRSYS-P-SC-CHILLROW-E1503V01.1 CHILLROW Row Cooling Precision Air Conditioner Cooling Capacity: 26.2kW~68.6kW CHILLROW is installed closely with the server cabinets and refrigerating independently. The

More information

Installation and Maintenance Manual IM Single Duct VAV Terminals. Group: Controls Part Number: IM 1093 Date: February 2015

Installation and Maintenance Manual IM Single Duct VAV Terminals. Group: Controls Part Number: IM 1093 Date: February 2015 Installation and Maintenance Manual IM 1093-1 Single Duct VAV Terminals Group: Controls Part Number: IM 1093 Date: February 2015 Table of Contents Introduction.... 3 Revision History...3 Reference Documents...3

More information

Air-Cooled Global Chiller

Air-Cooled Global Chiller Product Manual PM 970 Group: Chiller Effective: June 1997 Supersedes: None Air-Cooled Global Chiller Type AGR 055AS through 100AS Reciprocating Compressor with R-22 60 hertz 1997 McQuay International Table

More information

MAC N-407 Air-Cooled Chiller

MAC N-407 Air-Cooled Chiller MAC036-01-N-407 Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial MicroClimates MAC036 NOMENCLATURE BREAKDOWN MAC036-01 - N - 407 Refrigerant Type Air-Cooled Chiller 036=

More information

Tempered Water Logic Control OPERATION l TROUBLE SHOOTING

Tempered Water Logic Control OPERATION l TROUBLE SHOOTING Tempered Water Logic Control OPERATION l TROUBLE SHOOTING English For MPE Multiple Chiller Units Control Panel TEMPERED WATER SYSTEMS L-2199 Rev. 20080223 Revision: L-2199 20101104 *** IMPORTANT NOTICE

More information

PowerLogic ION Setup Meter Configuration Software Configuration Guide

PowerLogic ION Setup Meter Configuration Software Configuration Guide PowerLogic ION Setup Meter Configuration Software Configuration Guide 70002-0293-03 12/2010 Conventions Used in this Manual This section describes the symbols and terminology used in this guide. Symbols

More information

Water-Cooled Screw Compressor Chillers

Water-Cooled Screw Compressor Chillers Operating Manual OM WGS-5 Water-Cooled Screw Compressor Chillers WGS 130AW to WGS 190AW, Packaged Water-Cooled Chiller WGS 130AA to WGS 190AA, Chiller with Remote Condenser 120 to 200 Tons, 420 to 700

More information

RPM1600 Series Room Pressure Monitors

RPM1600 Series Room Pressure Monitors RPM1600 Series Room Pressure Monitors Technical Bulletin LB-RPM1611-0, LB--0 Code No. LIT-12012228 Issued October 2017 Refer to the QuickLIT website for the most up-to-date version of this document. How

More information

Service Step by Step Trouble-Shooting Check-List

Service Step by Step Trouble-Shooting Check-List WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:

More information

MicroTech Water-Cooled Screw Chiller Controller

MicroTech Water-Cooled Screw Chiller Controller BACnet Data Information Packet BD 02-8 Group: Controls Date: January 2003 MicroTech Water-Cooled Screw Chiller Controller Point mapping data for the MicroTech BACdrop Gateway with PMF version 1.10 software

More information

User s Information and Installation Instructions

User s Information and Installation Instructions Outdoor Air Conditioner User s Information and Installation Instructions 13 SEER R-410A High Efficiency Split System These units have been designed and tested for capacity & efficiency in accordance with

More information

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw SPECIFICATION GUIDE NEOSYS Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw Air-to-water Heat Pump for outdoor installation (NAH) Nominal cooling capacity:

More information

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Page 236423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified by MSU Physical Plant

More information

LC Series Chillers. Engineering Catalog. Air-Cooled Condenser

LC Series Chillers. Engineering Catalog. Air-Cooled Condenser LC Series Chillers Engineering Catalog Air-Cooled Condenser Table of Contents Features and Benefits... 5 Application Information... 7 Unit Selection... 11 Evaporator Pressure Drops... 14 LC Base Model

More information

SECTION ROTARY SCREW WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

SECTION ROTARY SCREW WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower SECTION 15684 ROTARY SCREW WATER CHILLERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15540 - Pumping Equipment (HVAC) 3. 15711 - Induced Draft Cooling Tower B.

More information

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Table of Contents Refrigeration Cycle Service Procedures Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Solving Problems Identifying Low System Charge (9-11) Identifying High

More information

Spectron LSN (Life Safety Network) Suggested Specifications

Spectron LSN (Life Safety Network) Suggested Specifications 1. General 1.1 Scope A Dual-Lite Spectron LSN (Life Safety Network) Series Inverter System shall be furnished to provide a reliable source of power, and shall operate during a utility line deficiency without

More information

Refrigerant Recovery Unit, Model RRU134

Refrigerant Recovery Unit, Model RRU134 Installation, Operation & Maintenance Manual IOMM RRU134 Group: Refrigerant Effective: December 2000 Supersedes: New Refrigerant Recovery Unit, Model RRU134 1999 McQuay International Table of Contents

More information

WaterFurnace FX10 Application Guide Reversible Chiller

WaterFurnace FX10 Application Guide Reversible Chiller 2011 WaterFurnace FX10 Application Guide Reversible Chiller Introduction This manual provides information about the FX10 Water Source Heat Pump (WSHP) controller as it relates to dual compressor water

More information

Air-Cooled Scroll Compressor Chiller

Air-Cooled Scroll Compressor Chiller Operating and Maintenance Manual OMM 1087-1 Air-Cooled Scroll Compressor Chiller Group: Chiller Part Number: OMM 1087 Effective: May 2012 Supersedes: April 2012 AGZ-D 25 to 190 Tons 50-60-Hertz, -410A

More information