Commercial Piping Systems Engineer Reference Guide

Size: px
Start display at page:

Download "Commercial Piping Systems Engineer Reference Guide"

Transcription

1 COMMERCIAL PIPING SYSTEMS CANADA REFERENCE GUIDE Uponor PEX-a Pipe Support Commercial Piping Systems Engineer Reference Guide Uponor crosslinked polyethylene (PEX-a) pipe and ProPEX expansion fittings offer value, durability and performance to your commercial plumbing and hydronic distribution piping projects. With more than 40 years of service in installations around the world, Uponor products and systems are the proven solution that professionals require to meet the demands of the commercial building industry. This reference guide is designed for architects, building officials, engineers and mechanical contractors interested in Uponor Commercial Piping Systems. It describes general installation recommendations that use Uponor PEX-a pipe and ProPEX fitting products. Uponor is not liable for installation practices that deviate from this guide or are not acceptable practices within the mechanical trades, codes or standards of practice. Always refer to local codes for additional requirements. For further assistance, refer to the Uponor Plumbing Design Assistance Manual (PDAM), Uponor Complete Design Assistance Manual (CDAM) or contact Uponor Technical Services at or Uponor Crosslinked Polyethylene (PEX-a) Pipe The Core of Uponor Piping Systems Hydrostatic Temperature and Pressure Ratings Uponor maintains standard-grade ratings for Uponor PEX-a pipe as tested in accordance with PPI TR-. Uponor PEX-a products have the following temperature and pressure ratings: 9. C (200 F) at 550 kpa (80 psi) 82.2 C (80 F) at 690 kpa (00 psi) 2 C (7.4 F) at,05 kpa (60 psi) Excessive Short-term Temperature - Pressure Capacity: 99 C (20 F) at,04 kpa (50 psi) tested up to 720 hours In accordance with Section 6.6 of ASTM F876 (the standard for PEX which is referenced in CSA B24), the minimum hydrostatic burst pressure for 2" pipe is,09 kpa (480 psi) at 2 C (7.4 F). For 4" pipe and larger, the minimum burst pressure is,275 kpa (475 psi) at 2 C (7.4 F). Uponor s quality lab performs daily burst pressure testing on all pipe sizes above and beyond the ASTM F876 standard. All samples are tested at 2 C (7.4 F) and burst at an elevated pressure of 5,55 kpa/800 psi (+/- 20 psi) nearly twice the pressure requirement of ASTM F876.

2 Uponor PEX-a vs. Copper, CPVC, Black Iron Pipe (BIP) and Polypropylene Random (PP-R) Pipe Comparisons PEX-a Copper CPVC BIP PP-R Flexible, fewer required connections, reduces potential leak liability Yes No No No No Expands up to X its diameter to help resist freeze damage Yes No No No No Manufactured fitting connection, cannot be dry fit Yes No No No Yes One simple tool for connections Yes No No No No Resists corrosion, pitting and scaling Yes No Yes No Yes Dampens rushing water noise, eliminates water hammer Yes No Yes No Yes Retains more heat in hot water lines Yes No Yes No Yes Less susceptible to condensation on cold-water lines Yes No Yes No Yes Stable material costs; eliminates jobsite theft concerns Yes No Yes Yes Yes Pipe and fittings warranty Yes No Yes No Yes Uponor PEX-a Copper CPVC Black Iron Pipe (BIP) Polypropylene Random (PP-R) Not All PEX is Created Equal Uponor PEX-a PEX-b PEX-c Most tested and third-party listed of all PEX Highest degree of crosslinking (>80%) Hot crosslinking above the crystal melting temperature Most flexible of all PEX and allows kink reparability Shape memory ideal for cold-expansion ProPEX fittings Increased resistance to corrosion Lowest degree of crosslinking (65-70%) Crosslinking performed in a secondary, post-extrusion process Stiffer product No kink reparability Not ideal for cold-expansion fittings Standard insert fittings have less flow Lesser degree of crosslinking (70-75%) Cold crosslinking below the crystal melting temperature Less uniform, less consistent Stiffer product No kink reparability Not ideal for cold-expansion fittings Standard insert fittings have less flow 2

3 ProPEX Fittings vs. Standard Insert Fittings A Wall thickness Uponor ProPEX Cold Expansion Fitting Standard Insert Fitting ASTM F960 Brass ASTM F960 EP ASTM F807 Brass ASTM F259 Plastic 2" 0.057" 0.057" 0.028" 0.056" 4" 0.057" 0.057" 0.07" 0.082" B Flow path 2" C Internal diameter " 0.072" 0.072" 0.04" 0.00" 4" " 0.2 sq. inches m/s (8 ft/s) 4.2 m/s (2 ft/s) sq. inches m/s (8 ft/s) 0.4 m/s (2 ft/s) sq. inches m/s (8 ft/s) 8.6 m/s (2 ft/s) 0.6 sq. inches m/s (8 ft/s) 4.4 m/s (2 ft/s) 0.27 sq. inches m/s (8 ft/s) 0.2 m/s (2 ft/s) sq. inches m/s (8 ft/s) 8.2 m/s (2 ft/s) sq. inches m/s (8 ft/s).6 m/s (2 ft/s) 0.22 sq. inches m/s (8 ft/s) 8. m/s (2 ft/s) 0.96 sq. inches m/s (8 ft/s) 4.8 m/s (2 ft/s) 2" 0.78" 0.85" 0.50" 0.5" 4" 0.595" 0.590" 0.50" 0.460" " 0.795" 0.788" 0.70" 0.60" sq. inches m/s (8 ft/s) 2.9 m/s (2 ft/s) 0.66 sq. inches m/s (8 ft/s) 6.2 m/s (2 ft/s) sq. inches m/s (8 ft/s) 0.9 m/s (2 ft/s) C A - Wall thickness B - Flow path C Double and 70% the wall thickness greater flow 2 ProPEX F960 Expansion Fitting C - Internal diameter F807/F259 Insert Fitting When comparing 2" F960 with F807 brass fittings 2 When comparing " F960 engineered polymer (EP) with F259 plastic fittings ProPEX EP Tee Commercial EP Multiport Tee ProPEX EP Elbow Minimum Distance Between ProPEX Fittings Fitting Size Cut Length of Pipe 2" 6.5mm (2 2") 4" 88.9mm ( 2") ProPEX Transition Fittings " 4.mm (4 2") 4" 9.7mm (5 2") 2" 65.mm (6 2") 2" 90.5mm (7 2")

4 Uponor PEX-a Codes and Standards (Includes both Canada and U.S.) Codes: ICC, IPC, IRC, IMC, UPC, UMC, NSPC, HUD, UFGS, NPC of Canada, NBC of Canada Listings: cnsfus-fs (up to 2"), cnsfus-pw, cqaius, UL, CSA, WH, ETL, PPI TR-4, ICC-ES, IAPMO, BMEC, CCMC Standards Compliance: AWWA C904, CSA B7.5, CSA B24, ASTM F876, ASTM F877, ASTM F202, ASTM E84/ULC S02.2, ASTM E9/UL 26/ULC S0, ASTM E84/ULC S5, UL 82/ULC ORD C99P, NSF/ANSI-4, NSF/ANSI-6 Plenum Listings All Uponor PEX-a pipe, Uponor ProPEX Rings, Uponor engineered polymer (EP) fittings, and ProPEX connections and valves were tested and certified for installation in return-air plenums. This applies to piping runs with or without Uponor EP fittings as described below. ½" Uponor PEX-a (Un-insulated) There is no limitation on spacing for adjacent runs of un-insulated ½" Uponor PEX-a pipe in a return-air plenum. Classified as to Surface Burning Characteristics ULC S02.2 Flame Spread Smoke Developed Nominal ½" size 25 or less 50 or less ¾" to " Uponor PEX-a (Un-insulated) Adjacent runs of un-insulated ¾" to " Uponor PEX-a pipe in a return-air plenum must be separated by 8". Classified as to Surface Burning Characteristics ULC S02.2 Flame Spread Smoke Developed Nominal ¾" to " size 25 or less 50 or less Up to " Uponor PEX-a (Insulated) Adjacent runs of up to " Uponor PEX-a pipe encased in ½" fiberglass insulation in a return-air plenum shall have no limitation on spacing. Classified as to Surface Burning Characteristics ULC S02.2 Flame Spread Smoke Developed Up to " Uponor PEX-a with ½" insulation 25 or less 50 or less Up to 2" Uponor PEX-a (Water-filled test) Adjacent runs of up to 2" Uponor PEX-a pipe with water-filled in a return-air plenum shall have no limitation on spacing. Classified as to Surface Burning Characteristics ULC S02.2 Flame Spread Smoke Developed Up to 2" Uponor PEX-a with water filled 25 or less 50 or less Per certification agencies fire-resistance classifications and follow-up service inspections, ongoing verification of product compliance is achieved through quarterly inspection audits at manufacturing location(s) during which a review of the product s process, suppliers and in-house quality control procedure is conducted. This audit ensures the product has not changed since the ULC S02.2 testing was conducted and will still meet the requisite standards. Uponor PEX-a Pipe Support 4

5 Concrete Floor/Ceiling Assembly (ULC ITS Design No. UW/FCA 20-0/02) Steel-stud Wall Assembly (ULC ITS Design No. UW/WA 60-0) Non-rated wall or non-load bearing wall assembly with Uponor AquaPEX pipe installed per CAN/ULC S0 (refer to ULC Design No. UW/WA 60-0) For CAN/ULC S0 steel-stud rated walls maximum Uponor AquaPEX pipe of. lbs./ft. and not to exceed total weight per stud cavity of 8.0 lbs. Uponor AquaPEX pipe riser Steel stud Copper manifold or Uponor EP multi-port tee with a weight not exceeding.0 lbs. per cavity (typical) Uponor PEX one or five-loop stand-up bracket or metal/2x4 wood pre-drilled mounting bracket on top side of slab 6½" minimum restrained or un-restrained Structural rebar (two layers) Fire-resistant Construction Ratings Construction Type Non-combustible Concrete/Steel Construction Wood Frame Construction CAN/ULC S0 Assembly ITS Design No. Type UW/FCA 20-0/02 Floor/Ceiling G524 Walls UW/WA 60-0 Floor/Ceiling UW/FCA 60-0 Walls UW/WA Recommended mid-story guide (see riser details on pages 6-7) Riser clamp (see riser details on pages 6-7) Firestop listed to CAN/ULC S0 (must be Uponor AquaPEX pipe compatible) CAN/ULC S0 slab listed with Uponor AquaPEX pipe only (refer to ULC ITS Design No. UW/FCA 20-0/02) Maximum tubing density is cubic inches with or without sleeve per one cubic foot of concrete (equivalent of " average spacing through slab between ½" Uponor AquaPEX pipe); polyethylene sleeve ¾" to " nominal tubing or PVC conduit " to ¼" nominal and ½" to 2" Uponor AquaPEX pipe Risers Risers typically feature Uponor PEX-a pipe in sizes from ¼" to 2" with CTS riser clamps at the base of each floor. The installation should also include a riser clamp at the top of every-other story for plumbing and every story for hydronic distribution to limit the expansion and contraction of the pipe. This translates to an expansion of about 8.mm (½") in 0.46m (25 ft.) at a. C (60 F) Delta T [installed at 5.6 C (60 F) with an operating temp. of 48.9 C (20 F)]. In this application, the piping will snake slightly in areas where it is not constrained, requiring the use of mid-story guides. Use discarded framing as a backer plate for the guide. Ensure the guide has no sharp edges or is fire-rated for risers in walls requiring fire-resistant construction. Through Penetrant Firestop The following firestop manufacturers offer PEX solutions as tested in accordance with ULC S5. M TM Hilti HoldRite HydroFlame TM Metacaulk Passive Fire Protection Partners ProSet Systems Tremco See firestop manufacturer s website for selection of appropriate fire assembly and product. 2" Uponor PEX-a Expansion Joint Expansion and Contraction Because PEX pipe expands at a rate of 27.94mm per 0.4m per 5.56 C (." per 00' per 0 F) temperature rise, an expansion joint, offset or change in direction is necessary to accommodate the expansion and contraction of the pipe. Uponor offers a preformed 2" Uponor AquaPEX Expansion Joint (F852000) and 2" Wirsbo hepex Expansion Joint (A992000) to make expansion joint installations more efficient. 5

6 Plumbing Riser Detail Uponor AquaPEX pipe risers Appropriate firestop material (must be Uponor AquaPEX compatible) Use appropriate floor assembly per code Overhead plumbing distribution ProPEX EP tee Branch piping isolation valve Plastic grommet required if pentrating steel stud EP multiport tee Mid-story guide recommended between each floor Use appropriate wall assembly per code Fixture termination rough-in assembly Riser clamp required at the base of each floor Wall-framing member Pre-sleeved Uponor AquaPEX In-slab plumbing distribution Refer to appropriate fire assembly listing for penetration requirements Riser clamp required at the top of every-other floor to limit expansion and contraction to 7.62m (25 ft.) 6

7 Hydronic Distribution Piping Riser Detail Wirsbo hepex TM hot and chilled water supply and return risers Appropriate firestop material (must be Wirsbo hepex compatible) Riser clamp required at the top of each floor ProPEX EP tee Fan Coil Unit (FCU) Plastic bend support Mid-story guide recommended between each floor ProPEX transition fitting for valve assembly Wall-framing member Use appropriate wall assembly per code Riser clamp required at the base of each floor Riser clamp required at the top of each floor ProPEX EP tee Fan Coil Unit (FCU) Fan Coil Unit (FCU) Plastic bend support Note: Other terminal units, such as heat pumps, radiators, VAV boxes and chilled beams can be supplied through similar means. Mid-story guide recommended between each floor Refer to appropriate fire assembly listing for penetration requirements Riser clamp required at the base of each floor Riser clamp required at the top of each floor 7

8 Typical Suspended Piping Installation Detail Steel Joist Strapping Uponor PEX-a Pipe Support Note: The above diagram is constructed based on U.S. requirements. Uponor AquaPEX Pipe Uponor ProPEX Expansion Ring Uponor ProPEX EP Fitting Pipe Support Trapeze Strapping For suspended runs of piping, Uponor PEX-a can be supported by the same conventional means as metallic pipe using copper tube size (CTS) pipe hangers or supports. Uponor recommends using hangers and supports designed for use with plastic pipe. Use PEX-a pipe support or pipe support channel that continuously supports the pipe to achieve nearly the same support spacing as copper pipe. Maximum Distance Between PEX-a Pipe Supports Pipe Size Maximum Distance ½" to 2" 0.8m (2") Strapping Guidelines for Clamps and Hanger Applications For more information regarding support solutions, contact Uponor Technical Services at or Application Clamps Hangers Maximum Distance Greater than.2m (48") = tie mid-span Less than.2m (48") = 2 ties equally spaced Greater than.2m (48") = ties [ mid-span and on each end placed 50.8mm (2") from end of support] 8

9 Surge Pressure and Sound Intensity The main sources of sound in a water piping system are cavitation, surface roughness and water hammer caused by surge pressure. Cavitation is generally a design issue, so the question is which material will absorb more of the sound if it occurs? Typical polymers will absorb sound in the range of 0 db/cm, whereas metals are on the order of 0. to.0 db/cm. For a given change in velocity, the intensity of sound from a copper pipe will be at least 8 times higher than that of PEX-a pipe and peak pressures caused by a quickacting valve could be reduced by 8% to 40% by utilizing PEX-a in lieu of copper pipe. PEX-a offers up to Surge Pressure Generated in Response to a Quick-acting Valve (PPI Report #285) Pipe Material 40% Maximum Measured Pressure, psi Flow Rate, gpm " Uponor PEX-a " PEX-b " CPVC " Type L Copper Pressure response measurements include 44 kpa (60 psi) static pressure. Closing speed of quick-acting valve estimated at 25 milliseconds. Test performed at 2.2 C (54 F) cold water temperature. reduction in surge pressure Commercial Flush Bank Detail Water hammer arrestor where required by code (exact locations vary by manufacturer) Bend support (½" - ¾" typical) Uponor AquaPEX pipe supply (size varies) Isolation ball valve (typical) Stud wall assembly Uponor AquaPEX pipe header (size varies) Uponor ProPEX EP tee Support Vent pipe Waste pipe Copper stub Urinal carrier behind Copper carrier bracket Water closet carrier 9

10 Uponor Logic Plumbing Uponor Logic is the smart way to plumb, using flexible PEX-a pipe and multiport tees to minimize connections and maximize system performance. With an Uponor Logic layout, plumbing systems typically require fewer fittings than a trunk-and-branch design and less tubing than a home-run layout. Uponor Logic Number of Fittings 9 Number of Connections Pipe Size Length 2" 79.6m (26 ft.) 4".6m (8 ft.) ".5m (5 ft.) Total 92.7m (04 ft.) Home Run Number of Fittings 7 Number of Connections 27 Pipe Size Length 2" 44.8m (475 ft.) 4" 9.m (0 ft.) ".5m (5 ft.) Total 55.4m (50 ft.) Critical Path = HWS - W.H. to Tub CWS = 5.6 C (60 F) HWS = 48.9 C (20 F) Mixed = 4. C (0 F) NPC Tub = 4 wsfu = 4 gpm Hot-water Multiplier = 0.8 NPC Tub x Hot-water Multiplier =.2 gpm I.D. (in.) Distance (ft.) Volume (gal.) Velocity Pressure Loss (psi) HW Time-to-fixture System (ft./sec.) Type 2" 4" 2" 4" 2" 4" Total 2" 4" 2" 4" Total Critical Path - Tub Only Copper T & B sec. Home Run sec. Uponor Logic sec. 0

11 Copper Trunk and Branch Number of Fittings 9 Number of Connections 9 Pipe Size Length 2" 7.m (24 ft.) 4" 22.2m (7 ft.) Copper T&B Homerun Uponor Logic ".5m (5 ft.) Total 95.m (2 ft.) 0 Fittings Connections Copper T&B Homerun Uponor Logic Feet of Pipe Copper T&B Homerun Uponor Logic Uponor Logic Delivers Hot water to fixtures 45% faster than copper trunk and branch Hot water to fixtures with % less pressure loss compared to home run Over 65% fewer fittings and connections than trunk and branch 40% less tubing than home run

12 Plumbing Systems Pipe Sizing an Uponor AquaPEX System Uponor recommends using the uniform friction loss method of pipe sizing. After determining the system s friction loss [psi/0.48m (00 ft.)] by performing a building supply water calculation, develop a water size chart for each system s water temperature and pipe size. To do this, reference the Uponor AquaPEX flow charts on Uponorpro.com and convert the gallons per minute (gpm) to fixture units for each nominal pipe size or use Uponor s Pipe Sizing Calculator at Per manufacturer s recommendations, Uponor allows the dedicated fixture supply pipe to be of the same nominal size as the fixture being supplied, provided the dedicated pipe is no longer than 6.m (20 ft.) from a uniform-friction-loss-sized pipe. Maximum Velocity NPC 200 section indicates the potable-water system shall be designed, fabricated and installed in accordance with good engineering practice, such as described in the ASHRAE Handbooks and ASPE Data Books. ASPE Data Book Vol. 2 (20/202) Chapter 5 Cold Water Systems, indicates that the velocity is determined as the meters per second (m/s) of the piping used specified by the manufacturer at each location. Uponor recommends a velocity of.0 m/s (0 ft/s), which is the same as shown in NPC 200 Table A (2)A. Maximum velocity through Uponor AquaPEX systems shall be.7 m/s (2 ft/s). This maximum velocity may be used as a basis for the design of a plumbing system if there is sufficient available pressure. Please consult with Uponor Design Services at or technical.services@uponor.com to ensure the proposed plumbing system can accommodate the maximum velocity of.7 m/s (2 ft/s). Pressure Loss (psi) per 00 Feet of Uponor AquaPEX Pipe at 5.6 C (60 F) Velocity 2 ft./second Velocity ft./second Velocity 0 ft./second Velocity 9 ft./second Velocity 8 ft./second Velocity 7 ft./second Velocity 6 ft./second Velocity 4 ft./second Velocity 5 ft./second Velocity ft./second Velocity 2 ft./second " PEX Tubing 2" PEX Tubing / 2" PEX Tubing / 4 " PEX Tubing " PEX Tubing / 4 " PEX Tubing 20.0 Flow Rate (gpm) 2.0 / 2" PEX Tubing / 8 " PEX Tubing 0..0 Pressure Loss (psi)

13 Pre-insulated Uponor AquaPEX is available in: 2"-2" pipe sizes with 2" PEX-foam insulation 4"-" pipe sizes with " PEX-foam insulation (special order) Thermal Conductivity PEX-a pipe has a very low coefficient of thermal conductivity, Btu in/(hr ft² F), whereas copper has a coefficient of thermal conductivity between 2,080 and 2,77 Btu in/(hr ft² F) depending on wall thickness (Type K, L or M). Therefore, PEX-a pipe does not sweat like copper does. PEX-a has superior insulative qualities when compared to copper in the same application. Even though the difference in R-Value is relatively small, the higher R-Value with a PEX-a pipe will always result in less heat loss when compared to the same nominal size copper pipe. Uponor recommends insulating all return piping as well as any hydronic distribution piping (heating/chilled) to conserve energy and maintain desired fluid temperature. Uponor also recommends insulating any piping installed in an unconditioned space or poorly ventilated areas with excessive moisture content. Pre-insulated AquaPEX R-value/Heat Loss Pipe Size R-value Heat Loss at 70 F ΔT 2". 8.9 Btu/(hr ft² F) 4".. Btu/(hr ft² F) ".0. Btu/(hr ft² F) 4" Btu/(hr ft² F) 2" Btu/(hr ft² F) 2" Btu/(hr ft² F) Pre-insulated Uponor AquaPEX consists of PEX-a pipe and closed cell, crosslinked polyethylene insulation with a thermal conductivity of 0.25 Btu in/(hr ft 2 F). Uninsulated PEX-a pipe offers 2% less heat loss compared to uninsulated copper pipe PEX-a vs. Copper Heat Loss Comparison Btu in/(h ft² F) Delta T ( F) Nominal Pipe Sizes Insulation Thickness 0" 2" " (K=0.24) 2" 0" 2" " 2" 0" 2" " 2" 0" 2" " 2" 0" 2" " 2" Uponor PEX-a " Type L Copper " " 4" 2" 2" " Uponor PEX-a Type L Copper Uponor PEX-a Type L Copper Uponor PEX-a Type L Copper Uponor PEX-a Type L Copper Uponor PEX-a Type L Copper Uponor PEX-a Type L Copper All calculations based on cylindrical thermal resistance methodology (ASPE/ASHRAE) Based on fluid velocity of 2.4 m/s (8 ft/s) at 7. C (60 F) (maximizing heat transfer from 00% water) Pipe convection set to be.76 Btu/hr ft² F (based on standard value for free convection of air) This heat loss comparison uses 0.24 Btu in/(hr ft 2 F) as the insulation thermal conductivity. This is a standard value for fiberglass pipe insulation at a 00 F mean temperature.

14 Hydronic Distribution Systems Pipe Sizing a Wirsbo hepex System Wirsbo hepex tubing is sized using the Darcy Wiesbach friction factor methodology. Sizing with this method allows for accurate calculation of head loss based on the internal roughness of Uponor s PEX-a pipe. The hydronic distribution pipe sizing tables on this page yield typical flow and BTU ranges based on specified pipe size, minimum velocity, maximum velocity, fluid type, fluid temperature, temperature differential (supply vs. return) and maximum head loss per 0.48m (00 ft.) of piping. Uponor s online hydronic sizing calculator is capable of generating flow tables for four-pipe hydronic distribution systems based on user specified inputs similar to the inputs used to create the tables on this page. This calculator allows the engineer/user to create easy-to-use tables that will accurately assist in system design. Note: Uponor recommends a minimum velocity of 0.46m (.5 ft/s) and a maximum velocity of 2.4m (8 ft/s) for hydronic distribution systems. The heating table is based on a. C (20 F) temperature differential and the chilled water table is based on a 5.56 C (0 F) temperature differential between supply and return. Wirsbo hepex Hydronic Sizing Table Heating at. C (20 F) ΔT 00% Water at 7 C (60 F).2m (4 ft.) of Head Loss/0.48m (00 ft.) Min. Velocity = 0.46m (.5 ft/s) Max. Velocity =.7m (5.5 ft/s) Pipe Size BTU Range GPM Range Velocity (ft./sec.) Feet of Head per 00 ft. of Pipe 2" 8,00, " 2,00 8, " 5,500 27, " 27,00 54, " 40,800 92, " 56,800 47, " 97, , " 48, , " 2, , " 284,600,04, " 68,800,52, Wirsbo hepex Hydronic Sizing Table Cooling at 5.56 C (0 F) ΔT 0% Propylene Glycol at 7.2 C (45 F).2m (4 ft.) of Head Loss/0.48m (00 ft.) Min. Velocity = 0.46m (.5 ft/s) Max. Velocity =.7m (5.5 ft/s) Pipe Size BTU Range GPM Range Velocity (ft./sec.) Feet of Head per 00 ft. of Pipe 2" N/A N/A N/A N/A 5 8" N/A N/A N/A N/A 4" 8,250 9, ",650 8, " 20,400 2, " 28,400 5, " 48,750 07, " 74,250 88, " 05,600 02, " 42,00 455, " 84,400 65,

15 Ecoflex Pre-insulated Piping for Hydronic Distribution Uponor Ecoflex pre-insulated pipe features single or twin PEX-a service pipes surrounded by multilayer, PEX-foam insulation and covered by a corrugated, high-density polyethylene (HDPE) jacket. There are currently more than 0 different Ecoflex assembly configurations available. B A F A Heating Source C B Manifold C Remote Manifold D E D Radiant Loops E Snow Melting Loops F Ecoflex Supply and Return Piping Layout (Ecoflex vs. Suspended Piping) Ecoflex Suspended Piping Traditional Suspended Hydronic Perimeter Loop Distribution System Overlaid with an Underground Ecoflex Pre-insulated Distribution System 5

16 Uponorengineering.com The Engineer s Resource Portal The Uponor Engineering Resource Center is your single destination for designing and creating a desirable, costeffective and energy-efficient structure. This portal is custom-made especially for you, the engineer, to help you meet all your goals. Whether it s meeting specific LEED or other green-building certification standards or incorporating value engineering into a project, Uponor can provide all the tools and resources, including specifications, submittals, CAD details, instructional manuals, design guidelines and even industry resource links to get you moving and on your way to a successful build. Building Information Modeling (BIM) AutoDesk Seek Search Uponor Building-DATA.net/TSI Uponor parts included in Building Data s content library for use with TSI MEP modeling software. Specifications SpecAgent Import specification selections directly into your specification text. CommPipingEngineer_RefGuide_CM00_06CA, Copyright 20 Uponor. Printed in the United States Uponor Design Services Uponor s full-service design department is staffed with professional designers and project managers with the experience, expertise and knowledge to lead your project from start to finish. Our team Uponor Ltd Argentia Rd., Plaza, Ste. 200 Mississauga, ON L5N W CANADA holds the necessary credentials and qualifications to ensure your project meets all code requirements and incorporates the most efficient use of time and materials to maximize system performance. Tel: Fax: design.services@uponor.com

Tube Clamp Submittal Information Revision A: July 25, 2013

Tube Clamp Submittal Information Revision A: July 25, 2013 Tube Clamp Revision A: July 25, 2013 Polypropylene (PP) Tube Clamps secure ½" and ¾" Uponor crosslinked polyethylene (PEX-a) tubing products. Suspension Standard Description Part Number A B C Weight Tube

More information

Chapter 3 Uponor Tubing Products

Chapter 3 Uponor Tubing Products Chapter 3 Uponor Tubing Products PEX is an acronym for crosslinked polyethylene. The PE refers to the raw material used to make polyethylene, and the X refers to the crosslinking of the polyethylene across

More information

EVALUATION SUBJECT: DIVISION: HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION: HYDRONIC PIPING.

EVALUATION SUBJECT: DIVISION: HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION: HYDRONIC PIPING. ICC-ES Report Reissued 08/2016 This report is subject to renewal 08/2017 EVALUATION SUBJECT: UNIPIPE PEX-AL-PEX DIVISION: 23 00 00 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION: 23 21 13 HYDRONIC

More information

Viega PEX Water Systems Installation Manual

Viega PEX Water Systems Installation Manual Viega PEX Water Systems Installation Manual The global leader in plumbing, heating and pipe joining systems Welcome Viega, heritage of quality, vision for the future Viega s heritage of superiority demands

More information

Potable Piping System

Potable Piping System Page, May 2006 Potable Piping System BOW SUPERPEX is designed with three distinct layers for ultimate protection. The middle layer provides chlorine resistance as well as UV light exposure resistance plus

More information

POTABLE PIPING SYSTEM

POTABLE PIPING SYSTEM POTABLE PIPING SYSTEM Designed Especially for Contractors PRODUCT INSTALLATION GUIDE BOW SUPERPEX JUne 2017 PRODUCT INSTALLATION GUIDE IMPORTANT NOTICE The information in this manual was gathered from

More information

Heating Installation Guide published by

Heating Installation Guide published by Heating Installation Guide published by MrPEX Systems 2613 87th Court W. Northfield, MN 55057 800-716-3406 mrpexsystems.com mrpex@mrpexsystems.com 2014 MrPEX Systems All rights reserved Printed September

More information

REHAU RADIANT HEATING SYSTEMS

REHAU RADIANT HEATING SYSTEMS REHAU RADIANT HEATING SYSTEMS DESIGN GUIDE www.rehau.com Construction Automotive Industry TABLE OF CONTENTS 1...... Scope...3 2...... Design Considerations.........................4 3...... System Overview.............................5

More information

What You Need to Know about Residential Sprinkler Design

What You Need to Know about Residential Sprinkler Design What You Need to Know about Residential Sprinkler Design Melisa Rodriguez, P.E., NICET IV Design Services Supervisor, Fire Safety melisa.rodriguez@uponor.com www.uponor-usa.com The Residential Sprinkler

More information

Uponor AquaSAFE system installation guide

Uponor AquaSAFE system installation guide Uponor AquaSAFE system installation guide Uponor AquaSAFE system installation guide Published by Uponor 5925 148th Street West Apple Valley, MN 55124 USA Tel: 800.321.4739 Fax: 952.891.1409 uponorpro.

More information

What Builders Need to Know about Residential Sprinkler Design

What Builders Need to Know about Residential Sprinkler Design What Builders Need to Know about Residential Sprinkler Design Melisa Rodriguez, P.E., NICET IV Design Services Supervisor, Fire Safety melisa.rodriguez@uponor.com www.uponor-usa.com Agenda Brief history

More information

Pipe: ASTM B88, hard drawn copper, Type K. Fittings: ASTM B16.22 Wrought copper and copper alloy.

Pipe: ASTM B88, hard drawn copper, Type K. Fittings: ASTM B16.22 Wrought copper and copper alloy. Design Standard Hydronic Piping in Buildings Detailed specifications follow. PART 1 - GENERAL 1.01 Above ground hydronic piping 2 inches and less in diameter shall be as follows: Copper PEX-A Pipe: ASTM

More information

A. ASHRAE Handbook HVAC Applications, Snow Melting and Freeze Protection

A. ASHRAE Handbook HVAC Applications, Snow Melting and Freeze Protection PAGE 238318-1 SECTION 238318 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification sections,

More information

Radiant Heating Installation Notes

Radiant Heating Installation Notes Radiant Heating Installation Notes GENERAL INFORMATION 1. It is the installer's responsibility to assure the system functions properly, safely, and meets all local, state and regional codes. 2. Installer

More information

UPONOR Ltd. Specification for UPONOR Q&E PEX Shrinkfit Plumbing Systems

UPONOR Ltd. Specification for UPONOR Q&E PEX Shrinkfit Plumbing Systems UPONOR Ltd Specification for UPONOR Q&E PEX Shrinkfit Plumbing Systems Reference Page(s) UPONOR Q&E PEX 2 Operating Conditions 2 Pipe Properties 2 Fittings Range 3 Radiator Heating Systems 3 H&C Water

More information

Residential Fire Safety Systems. Installation Guide. A Looped, Non-stagnant, Multipurpose Plumbing and Residential Fire Safety System

Residential Fire Safety Systems. Installation Guide. A Looped, Non-stagnant, Multipurpose Plumbing and Residential Fire Safety System Residential Fire Safety Systems Aquasafe TM Looped system Installation Guide A Looped, Non-stagnant, Multipurpose Plumbing and Residential Fire Safety System Uponor AquaSAFE TM Looped System Installation

More information

CONNECTION SYSTEM AUGUST Reliance Worldwide USA

CONNECTION SYSTEM AUGUST Reliance Worldwide USA CONNECTION SYSTEM Reliance Worldwide USA AUGUST 2010 1-877-700-4242 www.sharkbitepro.com the sharkbite Connection system includes push-fit and barb products and pex tubing. Contents Introduction and Applications...........................................

More information

CONNECTION SYSTEM JULY

CONNECTION SYSTEM JULY CONNECTION SYSTEM JULY 2009 IT ALL STARTED WITH A DEEP NEED FOR THE MOST RELIABLE VALVES EVER BUILT. The year was 1893 when the young engineer A.W. Cash was given the toughest challenge of his career:

More information

Radiant Heating & Cooling for Commercial Buildings

Radiant Heating & Cooling for Commercial Buildings Radiant Heating & Cooling for Commercial Buildings Kaveesh Padiachy, PEng, PMP, LEED AP Business Development Manager Central Canada kaveesh.padiachy@uponor.com www.uponorpro.com/engineering Radiant Heating

More information

Installation Guide P L U M B I N G

Installation Guide P L U M B I N G Installation Guide P L U M B I N G Plumbing Installation Guide published by MrPEX Systems 2613 87th Court W. Northfield, MN 55057 800-716-3406 mrpexsystems.com info@mrpexsystems.com 2015 MrPEX Systems

More information

APPENDIX A. A 3.2 Determine the elevation of the highest. A 3.3 Subtract the sum of loss in static pressure

APPENDIX A. A 3.2 Determine the elevation of the highest. A 3.3 Subtract the sum of loss in static pressure APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM Because of the variable conditions encountered, it is impractical to lay down definite detailed rules of procedure for determining the sizes

More information

Construction Automotive Industry

Construction Automotive Industry FOR IMMEDIATE RELEASE CONTACT: REHAU Communications Department Susanne Martin sue.martin@rehau.com Corrie Neukirchner cordula.neukirchner@rehau.com (703) 777-5255 REHAU Radiant Heating and Cooling, Plumbing

More information

A Pipe as Versatile and Flexible as Your Business

A Pipe as Versatile and Flexible as Your Business A Pipe as Versatile and Flexible as Your Business Multi-Flex Five Layer Composite Pipe: Multi-Flex consist of five layers. All layers are permanently bonded with each other during the production process.

More information

Making Crimp Connections

Making Crimp Connections Making Crimp Connections Cut tube off square (90 ) with a tube cutter. Tube Cutter Slide the PEX crimp ring over the end end of the tube. BE SURE the crimp ring is centered over the PEX barb. Slide the

More information

Meeting the One-Cup Challenge

Meeting the One-Cup Challenge 42 TECHNICAL SERIES HIGH PERFORMANCE HOT WATER SYSTEMS JANUARY/FEBRUARY 2010 OFFICIAL Meeting the One-Cup Challenge A SERIES ON HIGH PERFORMANCE HOT WATER SYSTEMS PART THREE: CENTRAL CORE PLUMBING About

More information

REHAU RADIANT HEATING SYSTEMS

REHAU RADIANT HEATING SYSTEMS REHAU RADIANT HEATING SYSTEMS DESIGN GUIDE www.rehau.com Construction Automotive Industry TABLE OF CONTENTS 1...... Scope...3 2...... Design Considerations...4 3...... System Overview...5 3.1.... Applications...5

More information

PRODUCT SPECIFICATION DRAWING Hydroflame Pro Series Sleeves

PRODUCT SPECIFICATION DRAWING Hydroflame Pro Series Sleeves Cap & Locator Whiskers PRODUCT SPECIFICATION DRAWING Hydroflame Pro Series Sleeves CD Plate (optional) See Dim *"C" (Telescoping) Safety Cap & Locator Whiskers Included (Shown with optional CD Plate) (OSHA

More information

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes.

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes. Introduction to Hydronics A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes. Hydronic heating systems use hot water or steam to deliver the

More information

MAXI-VENT Air Admittance Valve

MAXI-VENT Air Admittance Valve MAXI-VENT Air Admittance Valve Manufacturer: Studor, Inc. Connec on Size: 3 or 4 Model #: MAXI VENT Item #: 20302 An air admittance valve shall be acceptable as a vent termination for any individual vent,

More information

SECTION RADIANT HEATING UNITS

SECTION RADIANT HEATING UNITS PART 1 GENERAL 1.01 SECTION INCLUDES A. Hydronic radiant panel heaters. B. Electric radiant ceiling panel heaters. C. Radiant heating hydronic piping. SECTION 23 8300 RADIANT HEATING UNITS D. Outdoor electric

More information

propanel Series Installation Manual

propanel Series Installation Manual propanel Series Installation Manual propanel Series Installation Manual is published by Uponor Wirsbo 5925 148th Street West Apple Valley, MN 55124 (952) 891-2000 2003 Uponor Wirsbo All rights reserved

More information

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint. (816) 373-4878 U1208-01/FAI29-029 (573) 751-2624 SECTION 2 105 17 - SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the

More information

WATER HAMMER ARRESTORS & MISC. SPECIALTIES

WATER HAMMER ARRESTORS & MISC. SPECIALTIES TABLE OF CONTENTS Pictorial Index Water Hammer Arrestors Certification Sizing & Placement Backwater Valves Typical Installations Trap Seal Primers Compliance Pressure & Flow Characteristics Typical Installations

More information

VSL II QUICK START GUIDE

VSL II QUICK START GUIDE This Quick Start Guide must be left with owner and should be hung on or adjacent to the boiler for reference. VSL II QUICK START GUIDE DIRECT-VENT SEALED COMBUSTION CONDENSING BOILER ~ GAS-FIRED BOILER

More information

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM SECTION 21 10 00 PART 1 - GENERAL 1.1 CODES A. Work shall conform to NFPA 13 Sprinkler Systems, 2002 Edition and NFPA 24 Outside Protection, 2002 Edition. NFPA 14 Standpipe Systems, 2000 Edition and International

More information

C O D E S & A M M E N D M E N T S

C O D E S & A M M E N D M E N T S SEVIER COUNTY UTILITY DISTRICT SEPTEMBER 2, 2014 Sevier County Utility District has adopted the 2009 International Fuel Gas Code for gas inspections. The following pages contain frequently used codes and

More information

Hydronic Product & Application Catalog

Hydronic Product & Application Catalog Hydronic Product & Application Catalog Brazed Plate Heat Exchangers MJanuary 2005 for: Radiant Floor Heating Domestic Water Heating Snow Melt Swimming Pools Steam Close Approach High Pressure Systems Multi-Purpose

More information

CONNECTION SYSTEM Reliance Worldwide USA

CONNECTION SYSTEM Reliance Worldwide USA CONNECTION SYSTEM Reliance Worldwide USA AUGUST 2010 The SharkBite Connection System Includes Push-Fit and Barb Products and PEX tubing. CONTENTS Introduction and Applications...........................................

More information

Sprinkler Permit Applications

Sprinkler Permit Applications REQUIREMENTS FOR NFPA 13 SYSTEM Building Inspections Sprinkler Permit Applications A complete application for a Sprinkler Permit will comply with the requirements of Chapter 8 of NFPA 13. Hydraulic calculations

More information

Zurn PEX New Product. Zurn PEX New Product. Zurn PEX Large Diameter Compact Tool

Zurn PEX New Product. Zurn PEX New Product. Zurn PEX Large Diameter Compact Tool March 2011 Zurn PEX New Product Zurn PEX Large Diameter Compact Tool Tool is capable of making 1 ¼, 1 ½ and 2 crimps with the assistance of an impact wrench. YouTube Video of Tool in Use (Go to www.youtube.com,

More information

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM SECTION 213100 WET PIPE FIRE PROTECTION SPRINKLER SYSTEM PART 1 - GENERAL 1.01 GENERAL REQUIREMENTS A. The requirements of the General Conditions and Supplementary Conditions apply to all work herein.

More information

CodeNotes. Solar Water Heating Systems Based on the 2018 International Solar Energy Provisions (ISEP ) Introduction OFFICIAL

CodeNotes. Solar Water Heating Systems Based on the 2018 International Solar Energy Provisions (ISEP ) Introduction OFFICIAL CodeNotes is provided courtesy of the ICC PMG Official Membership Council OFFICIAL CodeNotes Solar Water Heating Systems Based on the 2018 International Solar Energy Provisions (ISEP ) Introduction Solar

More information

TANKLESS PRODUCT GUIDE CANADA TANKLESS PRODUCT GUIDE. A. O. Smith

TANKLESS PRODUCT GUIDE CANADA TANKLESS PRODUCT GUIDE. A. O. Smith TANKLESS PRODUCT GUIDE CANADA TANKLESS PRODUCT GUIDE A. O. Smith www.hotwater.com A. O. Smith Tankless Advantage ENDLESS HOT WATER * Heating water only as it s being used means you will never run out of

More information

Fundamentals of Hydronic Design

Fundamentals of Hydronic Design Radiant Based HVAC Systems Differential Pressure Fundamentals of Hydronic Design This educational material is copy written by Robert Bean, R.E.T., All Rights Reserved. If you wish to use this presentation

More information

DUCT SYSTEMS CHAPTER 6

DUCT SYSTEMS CHAPTER 6 SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter except as otherwise

More information

CALIFORNIA PLUMBING CODE MATRIX ADOPTION TABLE APPENDIX A - RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM 1 2 1/AC AC SS SS/CC

CALIFORNIA PLUMBING CODE MATRIX ADOPTION TABLE APPENDIX A - RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM 1 2 1/AC AC SS SS/CC CALIFORNIA PLUMBING CODE MATRIX ADOPTION TABLE APPENDIX A - RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM Adopting Agency BSC SFM HCD DSA OSHPD CSA DPH AGR DWR CA 1 2 1/AC AC SS SS/CC 1 2 3 4 Adopt

More information

Hydronic Air Handler Powered by Tankless Technology

Hydronic Air Handler Powered by Tankless Technology Integrated Solutions Hydronic Air Handler Powered by Tankless Technology RW1P/RW1T- Series Nominal Heating Capacities: 40-100 kbtu [11.7-29.3 kw] Tankless Water Heater Models: RTG-64DVL indoor direct vent

More information

DIVISION 21 - FIRE SUPPRESSION

DIVISION 21 - FIRE SUPPRESSION DIVISION 21 - FIRE SUPPRESSION DESIGN CRITERIA It is the policy of UC Davis to install fire sprinkler systems in all new construction/facilities. If the building is classified as a pole barn, shed, carport,

More information

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions: SECTION 21 13 13 WET-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

iq1001, Gen II Submittal Data

iq1001, Gen II Submittal Data , Gen II Submittal Data Date: Project Name: Bid Date: Fuel Type: Natural Gas Propane Project #: City State Zip: Engineer: Contractor: Factory Option: intouchbms KEY FEATURES Multiple Stainless (316L) Heat

More information

BASE-RAY CAST IRON BASEBOARD RADIATION

BASE-RAY CAST IRON BASEBOARD RADIATION INSTALLATION MANUAL FOR BASE-RAY CAST IRON BASEBOARD RADIATION TABLE OF CONTENTS PAGE 2 RATINGS 4 ASSEMBLY CHART 5 SYSTEM TYPES 6 SERIES LOOP SYSTEMS 7 SERIES LOOP DESIGN 8 INSTALLATION DETAILS 9 INSTALLATION

More information

SECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS

SECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS SECTION 15501 WET AUTOMATIC FIRE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Wet automatic fire sprinkler systems including fire pump, fire pump controller, alarms, safety devices,

More information

INFINITI K APPLICATIONS MANUAL. Indoor Residential and Tankless Water Heaters. Warning: Follow each appliance's instructions precisely.

INFINITI K APPLICATIONS MANUAL. Indoor Residential and Tankless Water Heaters. Warning: Follow each appliance's instructions precisely. Warning: Follow each appliance's instructions precisely. Installation and service must be performed by a trained and certified installer, service agency or the gas supplier. Application drawings in this

More information

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers. SECTION 22 10 00 PLUMBING PIPING AND PUMPS PART 1 - GENERAL 1.1 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design.

More information

AFUE up to 85.2% Heating Input 105,000 to 245,000 Btuh

AFUE up to 85.2% Heating Input 105,000 to 245,000 Btuh WATER HEATERS / BOILERS COWB3 Oil-Fired Hot Water Boiler PRODUCT SPECIFICATIONS Bulletin No. 0654 March 08 Supersedes September 05 AFUE up to 85.% Heating Input 05,000 to 45,000 Btuh MODEL NUMBER IDENTIFICATION

More information

CodeNotes. Solar Water Heating Systems Based on the 2015 International Solar Energy Provisions. Introduction. Solar Water Heating System Designs

CodeNotes. Solar Water Heating Systems Based on the 2015 International Solar Energy Provisions. Introduction. Solar Water Heating System Designs CodeNotes is provided courtesy of the ICC PMG Official Membership Council CodeNotes Solar Water Heating Systems Based on the 2015 International Solar Energy Provisions Introduction Solar water heating

More information

iq751/iq1001/iq1501 Specifications (Floor-standing units)

iq751/iq1001/iq1501 Specifications (Floor-standing units) iq751/iq1001/iq1501 Specifications (Floor-standing units) Type Fuel PARAMETERS MODELS iq751 iq1001 iq1501 Indoor/Outdoor, Floor Mounted, Condensing, Fully Modulating, On-demand Water Heater Preset for

More information

SHARKBITE CONNECTING SYSTEM

SHARKBITE CONNECTING SYSTEM INDEX CASH ACME valves with sharkbite connectors ball valves... 14-8 check valves... 14-8 connectors bullnose... 14-3 reducing... 14-3 straight... 14-3 couplings reducing... 14-2 straight... 14-2 elbows

More information

union swing check valve spring loaded check valve purging valve pressure relief valve relief valve metered balancing valve

union swing check valve spring loaded check valve purging valve pressure relief valve relief valve metered balancing valve VENT APPENDIX A: PIPING SYMBOL LEGEND GENERIC COMPONENTS CALEFFI COMPONENTS circulator circulator w/ ThermoBloc union circulator w/ swing check spring loaded balancing balancing w/ gate check globe s purging

More information

VSL II QUICK START GUIDE

VSL II QUICK START GUIDE This Quick Start Guide must be left with owner and should be hung on or adjacent to the boiler for reference. VSL II QUICK START GUIDE DIRECT-VENT SEALED COMBUSTION CONDENSING BOILER ~ GAS-FIRED BOILER

More information

The intelligent alternative for flue gas venting systems

The intelligent alternative for flue gas venting systems The intelligent alternative for flue gas venting systems FIRST LISTED InnoFlue is the first polymeric vent system tested and listed to ULC-S636 and UL-1738 in North America Intelligent for a good reason

More information

SECTION HYDRONIC PIPING AND SPECIALTIES

SECTION HYDRONIC PIPING AND SPECIALTIES SECTION 15511 HYDRONIC PIPING AND SPECIALTIES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Pipe Materials. 2. Fittings. 3. Specialty Items. 4. Glycol Antifreeze Protection. 5. Process Cooling B.

More information

Guidelines for Specifying Structured Plumbing Systems January, 2007

Guidelines for Specifying Structured Plumbing Systems January, 2007 Guidelines for Specifying Structured Plumbing Systems January, 2007 PART I - GENERAL A. Description This section includes requirements for materials for the installation Structured Plumbing systems for

More information

FULL PORT BALL SWEAT X PEX W/WASTE /2" PEX X 1/2" SWEAT BALL VALVE W/WASTE & LEVER HANDLE

FULL PORT BALL SWEAT X PEX W/WASTE /2 PEX X 1/2 SWEAT BALL VALVE W/WASTE & LEVER HANDLE PRODUCT GROUP # 5 PEX-READY VALVES, TOOLS & ACCESSORIES - valves FULL PORT BALL VALVES w/waste (BC) 4490 /2" FULL PORT BALL VALVE W/ WASTE PEX X PEX 440075 3/4" FULL PORT BALL VALVE W/ WASTE PEX X PEX

More information

EXTROL EXPANSION TANKS

EXTROL EXPANSION TANKS EXTROL EXPANSION TANKS For Closed Hydronic Heating & Chilled Water Systems MADE IN USA SINCE 954 AMTROL Quality Expansion Tanks Table of Contents AMTROL Quality Expansion Tanks... 2 How It Works... 2 The

More information

SUH-8 UNIT HEATERS. High Efficiency Heating Equipment

SUH-8 UNIT HEATERS. High Efficiency Heating Equipment SUH-8 UNIT HEATERS High Efficiency Heating Equipment Efficient Heating Solutions for all Applications Sterling unit heaters provide efficient heating solutions for all residential and commercial applications.

More information

PureFlow. PureFlow. Fittings system This section doesn t meet California AB1953, Vermont ACT 193 and NSF 61 Annex G Standards.

PureFlow. PureFlow. Fittings system This section doesn t meet California AB1953, Vermont ACT 193 and NSF 61 Annex G Standards. Fittings system This section doesn t meet California AB1953, Vermont ACT 193 and NSF 1 Annex G Standards. 11 PEX Manifold Plumbing Systems # of Outlets: Dimension (hot,cold) MANABLOC -BRONZE PEX PRESS

More information

Chilled Water DOAS Fan Powered Terminal Units

Chilled Water DOAS Fan Powered Terminal Units Chilled Water DOAS Fan Powered Terminal Units CHILLED WATER DOAS FAN POWERED TERMINAL UNITS DOAS TERMINAL UNITS FEATURES AND BENEFITS MINIMUM VENTILATION CONTROL The DOAS unit provides the Designer, Owner

More information

iq251, Gen II Submittal Data

iq251, Gen II Submittal Data iq25, Gen II Submittal Data Date: Project Name: Bid Date: Fuel Type: Natural Gas Propane Project #: City State Zip: Engineer: Contractor: Factory Option: intouch-bms KEY FEATURES Stainless (36L) Heat Exchanger

More information

BlazeMaster Fire Sprinkler Systems

BlazeMaster Fire Sprinkler Systems Engineered Polymers FACT SHEET The Lubrizol Corporation is the world leader in chlorinated polyvinyl chloride (CPVC) resins and compounds, which are trusted in various applications, including plumbing,

More information

DIVISION 21 - FIRE SUPPRESSION

DIVISION 21 - FIRE SUPPRESSION DIVISION 21 - FIRE SUPPRESSION DESIGN CRITERIA It is the policy of UC Davis to install fire sprinkler systems in all new construction/facilities. If the building is classified as a pole barn, shed, carport,

More information

endless advances for your customers WATER HEATING SOLUTIONS FOR BUILDERS

endless advances for your customers WATER HEATING SOLUTIONS FOR BUILDERS endless advances for your customers WATER HEATING SOLUTIONS FOR BUILDERS endless advantages Less space for heating, more space for living Only the size of a small suitcase, our wall-mounted models can

More information

PRE-ASSEMBLED RADIANT CONTROL PANEL INSTALLATION MANUAL

PRE-ASSEMBLED RADIANT CONTROL PANEL INSTALLATION MANUAL FloorHeat PRE-ASSEMBLED RADIANT CONTROL PANEL INSTALLATION MANUAL Thank you for purchasing this radiant control panel assembly. Following are some important notes that will make the installation successful.

More information

Dual Function SMART VENT. Superior Flood Protection and Natural Air Ventilation SMART VENT - Model:

Dual Function SMART VENT. Superior Flood Protection and Natural Air Ventilation SMART VENT - Model: SMART VENT - Model: 1540-510 Dual Function SMART VENT Superior Flood Protection and Natural Air Ventilation ICC-ES Evaluated and FEMA Accepted Foundation Flood Vents n Potential savings on homeowner s

More information

FIRE SPRINKLER SYSTEMS POLICY

FIRE SPRINKLER SYSTEMS POLICY FIRE SPRINKLER SYSTEMS POLICY Revised 1/1/17 DESIGN AND SUBMITTAL REQUIREMENTS All new and existing fire sprinkler systems within the jurisdiction of the City Fire Department shall meet all of the applicable

More information

MEP Syllabus CAREER DEVELOPMENT CENTRE SHRISTI MEP. Trichy-26

MEP Syllabus CAREER DEVELOPMENT CENTRE SHRISTI MEP. Trichy-26 SHRISTI MEP CAREER DEVELOPMENT CENTRE Trichy-26 MEP Syllabus Contact : dhinesh.shristimep@gmail.com / sangeetha.shristimep@gmail.com +91-80984 49847, 97158 67493 ELECTRICAL DESIGNING AND DRAUGHTING FUNDAMENTALS

More information

... Green Building Details

... Green Building Details Combining Solar HW with Radiant Floor using a Demand Water Heater back-up and a Tempering Tank with a line voltage three-way valve to prevent heating the solar storage with the gas DHW... A short list

More information

APPENDIX H (DESIGN SUBMISSION CRITERIA)

APPENDIX H (DESIGN SUBMISSION CRITERIA) APPENDIX H (DESIGN SUBMISSION CRITERIA) FIRE ALARM SYSTEM As per ACCORD standard Part 5, section 5.7 Fire Alarm System Design to be verified by ACCORD Chief Safety Inspector. Testing of the installation

More information

B. HI Compliance: Design, manufacture, and install pumps in accordance with HI "Hydraulic Institute Standards."

B. HI Compliance: Design, manufacture, and install pumps in accordance with HI Hydraulic Institute Standards. PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

DESIGN GUIDE Residential PEX Water Supply Plumbing Systems

DESIGN GUIDE Residential PEX Water Supply Plumbing Systems DESIGN GUIDE Residential PEX Water Supply Plumbing Systems Prepared for Plastics Pipe Institute, Inc (PPI) 105 Decker Court Suite 825 Irving, TX 75062 www.plasticpipe.org and Plastic Pipe and Fittings

More information

PLUMBING DESIGN GUIDELINES SECTION DESIGN GUIDELINES DUVAL COUNTY PUBLIC SCHOOLS

PLUMBING DESIGN GUIDELINES SECTION DESIGN GUIDELINES DUVAL COUNTY PUBLIC SCHOOLS The Design Guidelines, which follow, are intended to supplement the Educational Specifications and State Requirements for Educational Facilities (SREF). Note: All fittings shall be installed by no less

More information

PLUMBING PEX PIPE PDF

PLUMBING PEX PIPE PDF PLUMBING PEX PIPE PDF ==> Download: PLUMBING PEX PIPE PDF PLUMBING PEX PIPE PDF - Are you searching for Plumbing Pex Pipe Books? Now, you will be happy that at this time Plumbing Pex Pipe PDF is available

More information

VSA SEWAGE PUMP. Capacities to 1600 gpm, Heads to 120, Horsepower range 3/4 thru 40, 3 thru 6 discharge, 1750 and 1150 operation.

VSA SEWAGE PUMP. Capacities to 1600 gpm, Heads to 120, Horsepower range 3/4 thru 40, 3 thru 6 discharge, 1750 and 1150 operation. Brochure# 228E 122011 TYPE VSA SEWAGE PUMP Capacities to 100 gpm, Heads to 120, Horsepower range 3/ thru 0, 3 thru discharge, 1750 and 1150 operation. HIGHLIGHTS Wet-Pit Installations Pumps Suspend From

More information

CANADIAN FLEXIBLE GAS PIPING DESIGN GUIDE & INSTALLATION INSTRUCTIONS

CANADIAN FLEXIBLE GAS PIPING DESIGN GUIDE & INSTALLATION INSTRUCTIONS CANADIAN FLEXIBLE GAS PIPING DESIGN GUIDE & INSTALLATION INSTRUCTIONS November 2011 RESIDENTIAL COMMERCIAL INDUSTRIAL FGP-001CAN 11/11 Omega Flex, Inc. TABLE OF CONTENTS Chapter 1 Introduction 1.0 User

More information

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD INSTALLATION OF COMMERCIAL FIRE SPRINKLER SYSTEMS STANDARD #C-001 EFFECTIVE 03-25-2009 PURPOSE: To ensure that sprinkler plans submitted for review contain

More information

Hydronic Air Handler Powered by Tankless Technology

Hydronic Air Handler Powered by Tankless Technology Integrated Solutions Hydronic Air Handler Powered by Tankless Technology RHWB- Series Nominal Heating Capacities: 32-90 kbtu [9.38-26.39 kw] A.F.U.E. (Annual Fuel Utilization Efficiency) calculated in

More information

Hydronic Air Handler Powered by Tankless Technology

Hydronic Air Handler Powered by Tankless Technology Integrated Solutions Hydronic Air Handler Powered by Tankless Technology RHWB- Series Nominal Heating Capacities: 32-90 kbtu [9.38-26.39 kw] A.F.U.E. (Annual Fuel Utilization Efficiency) calculated in

More information

Air-Fuel Ratio (AFR) Sensor Exhaust & Water Temperature Safety Control Overheat Cut-Off Fuse

Air-Fuel Ratio (AFR) Sensor Exhaust & Water Temperature Safety Control Overheat Cut-Off Fuse TANKLESS HIGH EFFICIENCY CONDENSING WATER HEATERS COMMERCIAL-GRADE RESIDENTIAL / COMMERCIAL Ultra-Low NOx gas tankless water heaters with condensing technology featuring up to.95 Uniform Energy Factor

More information

CALEFFI. Thermostatic mixing valves, low-lead, high-flow series 01256/18 NA. Replaces 01256/15 NA

CALEFFI. Thermostatic mixing valves, low-lead, high-flow series 01256/18 NA. Replaces 01256/15 NA Thermostatic mixing valves, low-lead, high-flow 5 series CCREDITED ISO 9 FM 5 ISO 9 No. CLEFFI 5/ N Replaces 5/5 N Function The thermostatic mixing valve is used in systems producing domestic hot water

More information

Installation Guidelines

Installation Guidelines See our WaterPEX System Catalog for parts and supplies for the professional plumber. 3/8" 1" WaterPEX tubing (red, blue, white) Flow-through, Swedged, and CustomCut manifolds, sweat, and compression 1/4-turn

More information

endless quality and support

endless quality and support endless quality and support 100 years of smart comfort The highest standards of quality For nearly a century, Rinnai has been fiercely committed to delivering a smarter kind of comfort. With headquarters

More information

IPC Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer.

IPC Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer. IPC Plumbing Exam Name: Date: Score: Carefully read each question and then circle the letter of the best answer. 1. A vent stack handling 25 dfu s with a developed length of 35 feet shall be inches minimum

More information

NAVIEN AMERICA INC FITCH AVENUE IRVINE, CALIFORNIA, USA

NAVIEN AMERICA INC FITCH AVENUE IRVINE, CALIFORNIA, USA Navien America Inc. Specification Details for the Navien models: CR-210 CR-210A For Indoor Installation Only For Potable Water Heating and Space Heating NAVIEN AMERICA INC. 17855 FITCH AVENUE IRVINE, CALIFORNIA,

More information

Internal Use Only INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR

Internal Use Only INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR ELECTRICAL OR HIGH-DENSITY MAGNETIC ANTI-SCALE OR WATER CONDITIONING APPLIANCE IGC 91-2009 1. PURPOSE 1.1 The purpose

More information

Tankless Condensing High Efficiency Water Heaters

Tankless Condensing High Efficiency Water Heaters Tankless Residential Water Heater Series Tankless Condensing High Efficiency Water Heaters Ultra-Low NOx gas tankless water heaters with condensing technology featuring up to an unprecedented.95 Uniform

More information

RESCOM 2100 HOT WATER BASEBOARD RADIANT HEATING Unique, slim-design baseboard radiators

RESCOM 2100 HOT WATER BASEBOARD RADIANT HEATING Unique, slim-design baseboard radiators RESCOM 2100 HOT WATER BASEBOARD RADIANT HEATING www.b Unique, slim-design baseboard radiators The RESCOM 2100 system is unlike traditional baseboard heating systems. Smooth flat panels are easily secured

More information

Mascot. Gas-Fired Residential and Commercial Wall-Mounted Boiler. Easy Installation, 96% Efficiency, Fully Condensing

Mascot. Gas-Fired Residential and Commercial Wall-Mounted Boiler. Easy Installation, 96% Efficiency, Fully Condensing Mascot Gas-Fired Residential and Commercial Wall-Mounted Boiler Easy Installation, 96% Efficiency, Fully Condensing Mascot is a high-efficiency, wall-mounted boiler available in three BTU sizes 126, 167,

More information

MULTI-LINK UP TO 20 UNITS COMMON VENT UP TO 8 UNITS COMPLIES WITH LEAD FREE STANDARDS SAFETY FEATURES:

MULTI-LINK UP TO 20 UNITS COMMON VENT UP TO 8 UNITS COMPLIES WITH LEAD FREE STANDARDS SAFETY FEATURES: TANKLESS CONDENSING HIGH EFFICIENCY COMMERCIAL GAS Ultra-Low NOx gas tankless water heaters with condensing technology featuring up to 0.95 Uniform Energy Factor (UEF) which lowers operating costs and

More information

PROMAX XL MODELS CIRCULATING LOOP HEAT EXCHANGER MANUAL. Installation. Operation. Maintenance. Fill in the Rating Pate Information Here:

PROMAX XL MODELS CIRCULATING LOOP HEAT EXCHANGER MANUAL. Installation. Operation. Maintenance. Fill in the Rating Pate Information Here: CIRCULATING LOOP HEAT EXCHANGER MANUAL PROMAX XL MODELS Installation Operation Maintenance Fill in the Rating Pate Information Here: MODEL NO. SERIAL NO. INSTALLATION DATE Month Day Year CAUTION PLEASE

More information

Hydronic Radiant and Snowmelt. Product Catalog. Living full of energy

Hydronic Radiant and Snowmelt. Product Catalog. Living full of energy Hydronic Radiant and Snowmelt Product Catalog Tubing Panel Systems Manifold and Mixing Stations Fittings and Tools Valves and Controls Living full of energy Hydronic and Radiant Heating Product Catalog

More information