A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. i Protection & Control. b^n Telecontrol.
|
|
- Claud Spencer
- 5 years ago
- Views:
Transcription
1 A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical ^ Q ^pfi;sslo4rq Mechanical Civil R LE GD SiG ira rte, E pv/a-07 ^^ O i Protection & Control ^ Gi + 0'''' Transmission & Distribution NfWE b^n Telecontrol System Planning REPLACE UNIT 3 RELAY PANELS Holyrood Thermal Generating Station April 2010 newfoundland labrador h d ro a nalcor energy company
2 Table of Contents 1 INTRODUCTION 1 2 PROJECT DESCRIPTION 3 3 EXISTING SYSTEM Age of Equipment or System Major Work and/or Upgrades Anticipated Useful life Maintenance History Outage Statistics Industry Experience Maintenance or Support Arrangements Vendor Recommendations Availability of Replacement Parts Safety Performance Environmental Performance Operating Regime 13 4 JUSTIFICATION Net Present Value Levelized Cost of Energy Cost Benefit Analysis Legislative or Regulatory Requirements Historical Information Forecast Customer Growth Energy Efficiency Benefits Losses during Construction Status Quo Alternatives 18 5 CONCLUSION Budget Estimate Project Schedule 23 Newfoundland and Labrador Hydro
3 1 INTRODUCTION The Holyrood Thermal Generating Station (Holyrood) is an essential part of the Island Interconnected System, with three units providing a total capacity of 490 MW. The generating station was constructed in two stages. In 1971, Stage I was completed bringing on line two generating units, Units 1 and 2, each capable of producing 150 MW. In 1979 Stage II was completed bringing on line one additional generating unit, Unit 3, capable of producing 150 MW. In 1988 and 1989, Units I and 2 were up-rated to 170 MW. Holyrood (illustrated in Figure 1) represents approximately one third of Hydro's Island Interconnected system total generating capacity. Figure 1: Holyrood Thermal Generating Station The electrical interlock controls for Unit 3 are composed of 167 electromechanical relays that are installed in one large three compartment enclosure commonly referred to as the Unit 3 Relay Panels. The hardwired controls contained within these panels allow either the Newfoundland and Labrador Hydro Page 1
4 manual or automatic operation of all motors, drives and valves installed on Unit 3. As a result of several modifications that were made to these circuits since they were installed in 1978, the panels that contain these relays have become overcrowded to the point where the panel doors can no longer be closed. The condition of these panels is considered by the plant as being a significant safety hazard and a potential point of failure that could result in an outage on Unit 3. Newfoundland and Labrador Hydro Page 2
5 2 PROJECT DESCRIPTION The project is required to replace the existing hardwired relay logic infrastructure contained in the three relay panels on Unit 3 with a distributed control system (DCS) that will allow more dependability and better operator control functionality. The installation will be completed by removing the existing field wiring that terminates inside the existing relay panels. A new junction box will be installed to house the cabling required for the existing DCS control to remain functional. A new electrical enclosure containing all the required DCS hardware will be installed at the existing location and the field wiring will be re-terminated inside the new DCS control panels. The existing hardwired relay logic will be converted to a software based operating logic that will allow the system to function as it currently does. This new DCS hardware will be an expansion to the existing Foxboro DCS control system and will offer all the benefits of having a single reliable control system operating the entire plant. This will result in an ergonomically acceptable enclosure layout that will be more reliable and safer to maintain. Newfoundland and Labrador Hydro Page 3
6 3 EXISTING SYSTEM The existing Unit 3 Relay Panels consist of a three section panel or electrical enclosure that is located inside the Stage Two Relay Room in Holyrood (see Figure 2). This panel makes up the control logic section of the plant interlock system and controls the operation of most motors, valves and drives associated with generating Unit 3. The purpose of this panel is to house the relays, pneumatic timers, current transducers and terminal blocks that interface the Holyrood Central Control Room controls to the field mounted equipment that monitors and controls the generating unit. It also houses various relays that provide the existing automated systems with remote feedback indication. It serves as an interface panel for equipment that was incorporated into the Foxboro DCS in The Unit 3 Relay Panels have become a major safety and operational concern as these panels are overloaded and crowded. The problem of overcrowding has escalated to the point where the enclosure equipment doors can no longer be closed. Figures 3, 4 and 5 are pictures showing the amount of wiring contained in each of the three sections of this panel. Figure 6 shows how each of the enclosure doors are prevented from closing by the excess wiring contained inside each enclosure. A custom made plexiglass cover was installed in 2005 to prevent personnel working in the area from accidentally contacting energized electrical sources (see Figure 7). This plexiglass cover also prevents anyone from trying to close the doors on this cabinet which could possibly result in a wire being pulled out of a terminal block resulting in a unit outage. The physical condition of the terminal blocks inside these panels have deteriorated and are no longer acceptable. These compression type terminal blocks have become brittle and Newfoundland and Labrador Hydro Page 4
7 have the tendency to crack whenever maintenance crews tighten them. In some cases, the bases of several of these blocks have cracked leaving these terminal blocks no longer connected to the mounting rail that is used to support them inside the cabinet (see Figure 8). As a result, several terminal blocks that contain energized conductors are often left hanging inside the panel risking exposure to anyone working on the control system. Figure 2: Unit 3 Relay Panels Newfoundland and Labrador Hydro Page 5
8 Figure 3: Unit 3 Relay Panels - Compartment 1 of 3 Figure 4: Unit 3 Relay Panels - Compartment 2 of 3 Newfoundland and Labrador Hydro Page 6
9 Figure 5: Unit 3 Relay Panels - Compartment 3 of 3 Figure 6: Unit 3 Relay Panels - showing doors prevented from closing Newfoundland and Labrador Hydra Page 7
10 Figure 7: Unit 3 Relay Panels - showing temporary plexiglass cover Figure 8: Unit 3 Relay Panels - showing poor condition of terminal blocks Newfoundland and Labrador Hydro Page 8
11 3.1 Age of Equipment or System The Unit 3 Relay Panels were installed in 1978 and commissioned in the spring of 1979 when Stage Two came on line. 3.2 Major Work and/or Upgrades There have been no major upgrades to the existing Unit 3 Relay Panels since they were installed in There have been, however, additions to this panel over the years that have caused overcrowding to the point that the enclosure doors will no longer close. These additions include the installation of several motor current transducers in 1993 when the original Unit 3 control system was converted to a Westinghouse DCS. There have also been other minor operating logic changes and alarm installations since In addition, in 2004, the plant changed the Westinghouse DCS into a Foxboro DCS platform. At that time, several relays were removed from this panel and placed in the DCS logic. As a result of this upgrade, new cables had to be installed and terminated in these cabinets making the cabinets overcrowded and untidy. 3.3 Anticipated Useful life The Unit 3 Relay Panels is composed mainly of terminal blocks, electromechanical relays and timers that have an estimated life span of 25 years. 3.4 Maintenance History Hydro does not separately track maintenance costs for the relay panels. Maintenance costs for the Unit 3 Relay Panels are included in the costs of other electrical systems. Newfoundland and Labrador Hydro Page 9
12 Ho/yrood - Replace Unit 3 Relay Panels 3.5 Outage Statistics There have been no outages directly related to the Unit 3 Relay Panels. However, as this panel serves as one of the main interface panels to the existing DCS and the plant equipment, due to the current condition of the panel and the overcrowding of wires, the panel is considered by Hydro to be a major risk that could lead to an outage on Unit Industry Experience The industry standard is that every electrical enclosure should be designed and sized to allow for safe access and easy troubleshooting of individual electrical components to enable performance, reliability, and maintainability of any electrical system. Utilities are upgrading the older relay based electrical control systems to programmable or distributed logic control systems. These newer systems offer fault tolerant designs that can remain operational despite a single point fault failure. In addition, they have a smaller footprint design, provide easier maintenance and allows for future logic changes without having to make wiring changes. 3.7 Maintenance or Support Arrangements The Unit 3 Relay Panels are maintained by Hydro. In the event of a failure, there are currently no maintenance or support arrangements in place to provide assistance on the existing control system. However, after this upgrade, the existing service agreement with Invensys Systems (Foxboro) will cover the new control system for continued operational support. Hydro personnel will have unlimited access to the Foxboro system support program, remote system support, and ten hours of on site support per year as well as Newfoundland and Labrador Hydro Page 10
13 reduced training cost benefits. 3.8 Vendor Recommendations Invensys Systems, the manufacturer of the existing plant wide DCS control system, recommends replacing the Unit 3 Relay Panels by moving the hardwired logic into the existing plant DCS platform. 3.9 Availability of Replacement Parts Replacement parts are readily available for the existing Unit 3 Relay Panels Safety Performance The Unit 3 Relay Panels are considered by Hydro as being a significant safety hazard. The sub standard condition of these panels resulted in the submittal of a safe workplace observation program (SWOP) condition. The results of the investigation into this condition revealed that the panels contain sub-standard or poor wiring that present shock hazards to personnel working inside these panels. It also revealed that the amount of wiring located inside these panels will impede or delay future maintenance. Rule number of the Canadian Electrical Code states that "Electrical equipment shall be installed as to ensure that after installation there is ready access to nameplates and access to parts requiring maintenance". Rule number (2)(a)(ii) of the Canadian Electrical Code states that enclosures identified shall be only permitted to be used as junction boxes "where wiring is being added to an enclosure forming part of an existing Newfoundland and Labrador Hydro Page 11
14 installation and the conductors, splices and taps do not fill the wiring space at any cross section to more than 75 percent of the cross sectional area of the space". Rule of the National Fire Protection Association (NFPA) 79 Electrical Standard for Industrial Machinery states that "Ail items of control equipment shall be placed and oriented so that they can be identified without moving them or the wiring. " Rule of this same code states that terminal blocks shall be mounted to provide unobstructed access to the terminals and their conductors. As a result of these deficiencies, it is evident that the condition of the Unit 3 Relay Panels does not meet Canadian Electrical Code or other electrical standards and is thus a potential safety hazard to anyone working inside these enclosures. In addition to the code deficiencies outlined above, the physical condition of the terminal blocks located inside the panels have deteriorated and are no longer acceptable. These compression type terminal blocks have become brittle and have the tendency to crack whenever maintenance crews tighten them. In some cases the bases of several of these blocks have cracked leaving these terminal blocks no longer connected to the mounting rail that is used to support them inside the cabinet. As a result, terminal blocks that contain energized conductors are often found floating inside the panel risking exposure to workers. The plant standard for Electrical Equipment Enclosures (standard MSTD-059) states that enclosures shall be National Electrical Manufacturers Association (NEMA) 12 rated or greater when installed in any area of the plant not exposed to damp or corrosive environments. NEMA 12 is a standard from the National Electrical Manufacturers Association, which defines enclosures with protection against dirt, dust, splashes by noncorrosive liquids, and salt spray. The panels do not meet this requirement, since the doors of the enclosures will no longer close. As a result, air borne dust, fibers or splashing water is free to enter these enclosures. In addition, since the doors of these enclosures no longer Newfoundland and Labrador Hydro Page 12
15 close, if an electrical fire was to occur inside these panels, it would spread to the surrounding areas with the possibility of causing significant equipment damage and personnel injury or death. Although the plexiglass barrier does provide some additional protection, it is a temporary installation that does not meet Hydro standards Environmental Performance There are no environmental issues associated with the existing relay panels Operating Regime Unit 3 has the capability to operate in generation or synchronous condense modes. This unit operates predominately in the generation mode in the winter and in synchronous condense mode for summer months to provide voltage support to the Island Interconnected System. The controls in the Unit 3 Relay Panels are vital to the operation of the generating unit whether it is in generation or synchronous condense mode. In addition, there are relays and wiring contained in this panel that monitor and control auxiliary functions of the turbine that are required even when the generating unit is not in service. The relay panels are essential to the daily operation of the plant whether or not Unit 3 is operating. Newfoundland and Labrador Hydro Page 13
16 4 JUSTIFICATION This project is justified on the need to replace sub-standard equipment and eliminate safety hazards. Unit 3 Relay Panels are overcrowded with wiring which prevents the doors from being able to close. There is a risk of an electrical fire occurring inside the panels that could spread to the surrounding areas of the plant leading to significant equipment damage and potential personnel injury or death. There are several direct violations of the Canadian Electrical Code and other applicable standards pertaining to the condition of these panels. In addition, the plant maintenance personnel have identified the panels as an area of significant safety concern and expressed direct concerns about working inside these panels. As a result of the age of these panels and the amount of wiring contained inside them, the terminal blocks that are used to terminate energized conductors inside the panel have become very brittle. This has lead to them cracking in the areas that hold the conductors and on the bases that hold the block to the mounting rail inside the panel. As a result, energized terminal blocks are hanging inside the panel. In addition, maintenance crews have also found non terminated energized conductors inside this enclosure. Also, by integrating the relay controls into the existing DCS system, the future availability of Unit 3 will be improved. The Foxboro DCS control system offers a fault tolerant design and a redundant communication network that will continue to operate despite a single point failure. The proposed upgrade will also allow easier system troubleshooting after a failure and offers the advantage of being able to make future changes in software as opposed to Newfoundland and Labrador Hydro Page 14
17 having to make physical wiring changes. 4.1 Net Present Value A net present value analysis was not performed considering two alternatives. Please see section 4.3 `Cost Benefit Analysis' for details. 4.2 Levelized Cost of Energy A levelized cost of energy analysis is not applicable since no new generation sources are being evaluated. 4.3 Cost Benefit Analysis The following two viable alternatives were evaluated in a cost benefit analysis: Alternative 1: Replacement with DCS System. Replace the existing relay panels and relay logic with a new panel equipped with a DCS controlled system (total proposed capital cost of $830,700); Alternative 2: Replacement with Electromechanical Relays. Replace the existing relay panels and relay logic with a new relay panel equipped with electromechanical relays (total proposed capital cost of $676,500). These two alternatives were evaluated using a cost benefit analysis. The analysis included the following assumptions: The study period for the cost benefit analysis is 25 years, (2012 to 2037). Electromechanical relays have an anticipated useful life of 25 years. The DCS option has an anticipated useful life of 15 years and carries an additional cost of $75,000 in year 2027 to replace any obsolete hardware after the 15 years. Newfoundland and Labrador Hydro Page 15
18 To assure that both alternatives are compared equally, it is assumed that 1/3 of the value remaining in the DCS system hardware to be installed in 2027 can be recovered at the end of 25 years (2037) since it has an anticipated lifespan of 15 years and has only been in service for ten years. $3,500 per annum is allowed for engineering to investigate electrical faults in the electromechanical relay alternative since there would be no single common plant wide control system equipped with Sequence of Events monitoring. + $4,100 per annum after year ten is allowed for maintenance work in the electromechanical relay alternative. An extra $50,000 every ten years is allowed for completing wiring changes inside the electromechanical relay panels for major upgrades that require significant rewiring as opposed to simple logic changes required if the DCS alternative was installed. + Electromechanical relays do not offer internal diagnostics that quickly indicate the source of a failure. In the event of an outage of unit 3 prior to 2020, as a result of an electromechanical relay failure, requiring the gas turbines to be dispatched for 15 hours would cause the cost benefit analysis to be in a virtual break even position. Using the average required gas turbine energy values for this period (637 MWh) it was determined that the incremental cost of fuel for gas turbine operation over the No. 6 Heavy oil which is burned in Holyrood, will result in an additional cost of $93,668 in the electromechanical relay option. Using these assumptions, the results of the cost benefit analysis showed that the Electromechanical Relay Alternative is slightly more expensive over the 25 year anticipated useful life of the project. Figure 9 shows the results. Newfoundland and Labrador Hydro Page 16
19 HRD relay panels Alternative Comparison Cumulative Net Present Value To The Year 2037 Alternatives Cumulative Net Present Value [CPW[ CPW Difference between Alternative and the Least Cost Alternative DCS Alternative Electromechanical Relay Alternative 776, , Figure 9: Cost Benefit Analysis 1 Summary Table 4.4 Legislative or Regulatory Requirements As stated in rule 478(1) of the Newfoundland and Labrador Occupational Health and Safety Regulations 2009 "an electrical installation, equipment, apparatus and appliance shall conform to the requirements of the Canadian Electrical Code as adopted in the Electrical Regulations under the Public Safety Act". As a result of the existing Canadian Electrical Code deficiencies outlined in the safety performance section of this report, Hydro has decided that this installation should be brought up to standard. 4.5 Historical Information There is no historical information associated with this proposal as there have been no similar replacements of the existing control systems. Newfoundland and Labrador Hydro Page 17
20 4.6 Forecast Customer Growth Forecast customer growth has no impact on this project. 4.7 Energy Efficiency Benefits There are no energy efficiency benefits associated with upgrading the existing relay control panels. 4.8 Losses during Construction There will be no anticipated energy losses while upgrading the existing control systems. The electrical controls in the panels will be integrated into the Foxboro DCS during the planned annual outage. 4.9 Status Quo The status quo relay based control system is not an acceptable alternative. Due to safety concerns with the existing system, the age and condition of the equipment, the relay panels need to be replaced Alternatives When evaluating this project, Hydro has considered the following two alternatives: + Replacement of the existing relay panels and relay logic with a new panel equipped with a DCS controlled system (total proposed capital cost of $830.7K); Newfoundland and Labrador Hydro Page 18
21 Replacement of the existing relay panels and relay logic with a new panel equipped with electromechanical relays (total proposed capital cost of $676,500). Despite the fact that the upfront capital cost of the DCS alternative is more than the electromechanical relay alternative, in the event of a single electromechanical relay failure that results in Unit 3 becoming unavailable, the DCS alternative becomes the more cost effective option. As a result of this fact and the following benefits gained with going with the DCS alternative, Hydro has decided to proceed with the DC5 alternative: Overall safer system since maintenance and troubleshooting can be completed from the safety of the control room - The DCS system allows maintenance crews to observe the status of input and outputs from an engineering workstation located inside the control room. However, in the electromechanical relay alternative, maintenance crews would have to work inside energized electrical panels when trying to perform maintenance and troubleshoot problems. More dependable system as solid state relays contain no moving parts - DCS outputs operate using an electronic switch or transistor which contains no moving parts. As a result, fewer faults will occur on the DCS system which will result in more dependable operation of the Unit 3 generator; Easier troubleshooting capabilities since there is less wiring and electrical components to fail - In the event that an electromechanical relay was to fail, several hours or possibly days would be spent trying to determine the source of the problem. This will lead to extended system unavailability or possibly a Unit 3 outage. The DCS alternative offers built in internal diagnostics, that will alert operators of a problem immediately; Built in fault tolerance that can accept some single point control system failures - Since the DCS option contains redundant processors and communications, the Newfoundland and Labrador Hydro Page 19
22 system will continue to operate despite a failure on any of these critical components; Smaller equipment footprint that frees up valuable plant real estate - When replacing the existing system with electromechanical relays, a much larger panel would be required to house all the relays and wiring than what would be required if the DCS alternative was used. Currently, there is very little extra room inside the Stage 2 relay room for a larger enclosure; Easier future upgrade capabilities that will not involve wiring changes for simple logic changes - The DCS alternative will allow technicians to make simple logic changes by re-configuring software as opposed to spending hours or days rewiring relays. In addition, it will allow more complicated logic processes to be installed in the event that any future plant upgrades take place. The electromechanical relay option only supports discrete relay logic and does not offer any advanced control capabilities such as analog inputs, analog outputs, closed loop control, accurate timing functions and counting functions; Reduced commissioning time required to fix errors as small logic changes are made much easier in software than in hardwired systems - If during commissioning, any logic changes are required, the DCS alternative will allow these changes to be made without having to change any of the wiring or equipment inside the panel. However, if changes are required when using the electromechanical relay alternative, this could result in hours or days of re-wiring and if the change is significant enough, there may not be any extra space inside the panel to add extra relays; Better automation capabilities and much faster control processing speeds available in DCS controlled system - The DCS alternative will allow engineering to program alarms and other automation logic into the system that will inform Newfoundland and Labrador Hydro Page 20
23 operators when something has gone wrong in the process. It will also operate at much faster speeds than relay logic allowing the process to respond to changes much faster than they currently do; + Common plant wide control system that allows operators to analyze faults and historically trend and display any information required -The existing DCS is equipped with sequence of events recording capabilities and historical trending of all inputs and outputs. These features will allow operators and engineering to quickly analyze faults and disturbances by knowing exactly what events occurred at the time of a fault. DCS system allows for remote monitoring and control of systems via HMI computers or operator workstations -The DCS alternative will allow the operators inside the control room to see the entire process on one Human Machine Interface (HMI) computer screen. This system will allow automatic alarming capabilities and will reduce the amounts of lights, switches and pushbuttons currently installed inside the control room. It will therefore streamline the operation of the process and will reduce the chances of operator error. In addition, it will allow future control room modernization to take place without having to replace any of these systems. Newfoundland and Labrador Hydro Page 21
24 5 CONCLUSION The Unit 3 Relay Panels must be upgraded to ensure the safety of Hydro's maintenance crews and the overall operational reliability of the Holyrood plant. The existing hardwired control panels are over 30 years old and are overcrowded with wiring to the point that the doors of this panel will no longer close. These panels are in direct violation of several Canadian Electrical Code rules and pose significant safety hazards to anyone working inside these panels. Hydro is proposing that the existing panels be replaced and the hardwired controls be integrated into the existing plant wide Foxboro DCS control system. 5.1 Budget Estimate The budget estimate for this project is shown in Table 1. Table 1: Budget Estimate Project Cost:($ x1,000) Beyond Total Material Supply Labour Consultant Contract Work Other Direct Costs O/H, AFUDC & Escln Contingency TOTAL Newfoundland and Labrador Hydro Page 22
25 5.2 Project Schedule The anticipated project schedule is shown in Table 2. Table 2: Project Schedule Activity Milestone Project Initiation January 2011 Review existing drawings and develop I/O list March 2011 Develop contract for Foxboro and issue Purchase Order June 2011 Finalize Engineering Drawings and Design September 2011 Develop DCS Programming November 2011 Develop Electrical Installation Contract February 2012 Complete Factory Acceptance Testing April 2012 Complete Installation and Commissioning July 2012 In Service September 2012 Project Completion and Close Out December 2012 Newfoundland and Labrador Hydro Page 23
26
SEL Arc-Flash Solutions
SEL Arc-Flash Solutions Arc-Flash Protection at the Speed of Light Protect personnel and equipment Detect arc-flash events and send a trip signal in as little as 2 ms to enhance safety and minimize equipment
More informationFunctional Safety: the Next Edition of IEC 61511
HazAus2015/1507 Functional Safety: the Next Edition of IEC 61511 Mirek Generowicz Engineering Manager I&E Systems Pty Ltd Level 2, 445 Hay Street Perth WA 6000 Abstract The functional safety standard IEC
More informationA REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution
A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES cpwlpy SIGNA Z2L LAND Electrical Mechanical Civil Protection & Control Transmission & Distribution Telecontro I System Planning REPLACE FUEL OIL
More informationMoving to the Cloud: The Potential of Hosted Central Station Services
Moving to the Cloud: The Potential of Hosted Central Station Services Moving to the Cloud: The Potential of Hosted Central Station Services The global market for alarm monitoring services is expected to
More informationSEL Arc-Flash Solutions
SEL Arc-Flash Solutions Arc-Flash Protection at the Speed of Light Protect personnel and equipment. Detect arc-flash events and send a trip signal in as little as 2 ms to enhance safety and minimize equipment
More informationSession Four Functional safety: the next edition of IEC Mirek Generowicz Engineering Manager, I&E Systems Pty Ltd
Abstract Session Four Functional safety: the next edition of IEC 61511 Mirek Generowicz Engineering Manager, I&E Systems Pty Ltd The functional safety standard IEC 61511 provides a framework for managing
More informationVACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES
Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete
More information4. Applicability: 4.1. Functional Entities: 4.2. Facilities: 5. Effective Date: See Implementation Plan
Standard PRC-005-2 Protection System Maintenance A. Introduction 1. Title: Protection System Maintenance 2. Number: PRC-005-2 3. Purpose: To document and implement programs for the maintenance of all Protection
More informationSECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More information4. Applicability: 4.1. Functional Entities: 4.2. Facilities: 5. Effective Date: See Implementation Plan
Standard PRC-005-2 Protection System Maintenance A. Introduction 1. Title: Protection System Maintenance 2. Number: PRC-005-2 3. Purpose: To document and implement programs for the maintenance of all Protection
More informationCONTENTS AUTOMATIC TRANSFER SWITCHES
CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training
More informationSECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL
SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply
More informationDENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL
PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Minimum lighting control (base scope of work) shall include all corridors. The lighting in all the corridors shall be turned on (if not already on) if
More informationStandard PRC Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance
A. Introduction 1. Title: Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance 2. Number: PRC-005-6 3. Purpose: To document and implement programs for the maintenance of all
More informationStandard Development Roadmap
Standard PRC-005-2 Protection System Standard Development Roadmap This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective.
More informationStandard PRC Protection System and Automatic Reclosing Maintenance. Standard Development Roadmap
Standard Development Roadmap This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed:
More informationDelta T Alert: Wireless Temperature Monitoring of Electrical Enclosures
Delta T Alert: Wireless Temperature Monitoring of Electrical Enclosures Fred Baier, Level III Certified Infrared Thermographer Delta T Engineering, LLC 136 Main Street Metuchen, NJ 08840 Ph: 877-321-0576
More information100 & 120 Series Pressure and Temperature Switches Safety Manual
100 & 120 Series Pressure and Temperature Switches Safety Manual MECH-SM-01 1 INTRODUCTION This Safety Manual provides information necessary to design, install, verify and maintain a Safety Instrumented
More informationElectrical Safety Compliance: NFPA 70E
Electrical Safety Compliance: NFPA 70E From Graybar and Schneider Electric Risks associated with shock and electrocution from inadvertent contact with energized parts have long been recognized as a threat
More informationInsert Photo Here Bos Howard Johns Manville
What can TWO GUYS AND A TRUCK" do with PlantPAx? Insert Photo Here Bos Howard Johns Manville Rockwell Automation Process Solutions User Group (PSUG) November 14-15, 2011 Chicago, IL McCormick Place West
More informationIs your current safety system compliant to today's safety standard?
Is your current safety system compliant to today's safety standard? Abstract It is estimated that about 66% of the Programmable Electronic Systems (PES) running in the process industry were installed before
More informationSLATE. Integrated Combustion Equipment Management Success Stories
SLATE Integrated Combustion Equipment Management Success Stories Full Steam Ahead SLATE TM Integrated Combustion Management System Improves Production Efficiency for Candy Factory. See how Honeywell s
More informationSECTION AUTOMATIC TRANSFER SWITCHES
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC
More informationSECTION SOLAR PHOTOVOLTAIC (PV) POWER GENERATION SYSTEM
SECTION 48 14 14 SOLAR PHOTOVOLTAIC (PV) POWER GENERATION SYSTEM PART 1 GENERAL 1.1 SECTION INCLUDES The work of this section consists of furnishing a complete Solar Photovoltaic (PV) Power Generation
More informationStandard PRC-005-3(i) Protection System and Automatic Reclosing Maintenance
A. Introduction 1. Title: Protection System and Automatic Reclosing 2. Number: PRC-005-3(i) 3. Purpose: To document and implement programs for the maintenance of all Protection Systems and Automatic Reclosing
More informationIntegrated Automation Instrumentation & Terminal Devices
Sections Included In This Standard: 1.1 Building Systems Control 1.2 Building Aumotation Systems (BAS) 1.1 BUILDING SYSTEMS CONTROL A. HVAC CONTROLS: 1. General: Temperature control zones shall not combine
More informationGuide To Troubleshooting INEFFICIENT COOLING FANS
Guide To Troubleshooting INEFFICIENT COOLING FANS TABLE OF CONTENTS Introduction Enclosure Cooling Basics Key Attributes of Enclosure Cooling Symptoms of Poor Enclosure Cooling Typical Cooling Fan Problems
More informationVIDEO VISITATION APPLICATION: FUNCTIONS AVAILABLE:
VIDEO VISITATION S E C U R I T Y E L E C T R O N I C S APPLICATION: SecurVu Video Visitation provides a robust IP-based solution custom designed for the harsh correctional environment. Facilities of any
More informationPractical Distributed Control Systems (DCS) for Engineers & Technicians. Contents
Practical Distributed Control Systems (DCS) for Engineers & Technicians Contents Chapter 1 Introduction to Computer Based Control Systems 1 1.1 Introduction to computer based measurement and control systems
More informationSubstation Monitoring System
Substation Monitoring System SF6 Gas Density Monitoring System Description Introduction As a result of recent European legislation on the control of greenhouse gasses, utilities and manufacturers alike
More informationFailure Modes, Effects and Diagnostic Analysis
Failure Modes, Effects and Diagnostic Analysis Project: Detcon FP-700 Combustible Gas Sensor Customer: Detcon The Woodlands, TX USA Contract No.: DC 06/08-04 Report No.: DC 06/08-04 R001 Version V1, Revision
More informationDistributed Generation (greater than 10kW) Connecting to Vector s electricity network
Distributed Generation (greater than 10kW) Connecting to Vector s electricity network Important information about installing distributed generation with capacity greater than 10 kilowatts Purpose of this
More informationUSER APPROVAL OF SAFETY INSTRUMENTED SYSTEM DEVICES
USER APPROVAL OF SAFETY INSTRUMENTED SYSTEM DEVICES Angela E. Summers, Ph.D., P.E, President Susan Wiley, Senior Consultant SIS-TECH Solutions, LP Process Plant Safety Symposium, 2006 Spring National Meeting,
More informationUnited Electric Controls One Series Safety Transmitter Safety Manual
United Electric Controls One Series Safety Transmitter Safety Manual OneST-SM-02 1 INTRODUCTION This Safety Manual provides information necessary to design, install, verify and maintain a Safety Instrumented
More informationA. Introduction 1. Title: Transmission and Generation Protection System Maintenance and Testing
A. Introduction 1. Title: Transmission and Generation Protection System Maintenance and 2. Number: PRC-005-1.1b 3. Purpose: To ensure all transmission and generation Protection Systems affecting the reliability
More informationPWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R
Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,
More informationOracle Real Application Clusters (RAC) 12c Release 2 What s Next?
Oracle Real Application Clusters (RAC) 12c Release 2 What s Next? Markus Michalewicz Oracle Redwood Shores, CA, USA Keywords: RAC, Cloud, Private Cloud, Storage, Network, Development, Market Trends, Future
More informationHow to reduce exposure to arc flash hazards
GE Electrical Distribution How to reduce exposure to arc flash hazards Multiple solutions for new and existing facilities imagination at work Multiple Issues Today s power system engineer must not only
More informationVeriSafe Absence of Voltage Tester The safe way to verify the absence of voltage
VeriSafe Absence of Voltage Tester The safe way to verify the absence of voltage www.panduit.com/verisafe What is an Absence of Voltage Tester? Absence of Voltage Testers (AVTs) are permanently-mounted
More informationOPTIMIZING YOUR TECHNOLOGY INVESTMENT WITH SERVICE AND SUPPORT
I Connected IndustriaI OPTIMIZING YOUR TECHNOLOGY INVESTMENT WITH SERVICE AND SUPPORT Total Care Field Services Maximize the Return on Your Technology Count on Honeywell Total Care Field Services to help
More informationEnhanced FOUNDATION Fieldbus Physical Layer Diagnostics with the DeltaV System
November 2006 Page 1 Enhanced FOUNDATION Fieldbus Physical Layer Diagnostics This document provides possible solutions that allow enhanced Ff (FOUNDATION fieldbus) physical layer diagnostics using the
More informationSafety Instrumented Systems The Smart Approach
Safety Instrumented Systems The Smart Approach The Emerson Approach to Safety More than ever, running your plant productively and safely requires the right technologies and experience. With increasingly
More informationIE Code IE Competency Title Credit OAC Ref.
Compulsory Workplace Competency Standards Level Four IE Code IE Competency Title Credit OAC Ref. IE119-4WC Design and draw electrical and electronic drawings including schematics, 4 F5 maintain documentation
More informationProperty risk solutions
Property risk solutions Inside this issue Welcome to this edition of the Property risk solutions newsletter. This quarterly publication focuses on fixed fire protection and human element safety solutions
More informationEffective Alarm Management for Dynamic and Vessel Control Systems
DYNAMIC POSITIONING CONFERENCE October 12-13, 2010 OPERATIONS SESSION Effective Alarm Management for Dynamic and Vessel Control Systems By Steve Savoy Ensco Offshore Company 1. Introduction Marine control
More informationSPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL
SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in
More informationSECTION AUTOMATIC TRANSFER SWITCHES
SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationDISTRIBUTION OPERATIONS AND MAINTENANCE
EB-00-0 Tab Schedule Page of 0 DISTRIBUTION OPERATIONS AND MAINTENANCE PREDICTIVE MAINTENANCE Predictive maintenance expenditures fund work that is required to test and audit distribution system assets.
More informationStandard PRC-005-3(X) Protection System and Automatic Reclosing Maintenance
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed
More informationInfrastructure Projects Signalling - Shared Learning. 18/02: March 2018 December Dec-18 / 1
Infrastructure Projects Signalling - Shared Learning 18/02: March 2018 December 2018 20-Dec-18 / 1 Introduction This Shared Learning document details key issues and incidents that have occurred on Signalling
More informationDigital EPIC 2 Safety manual
Safety manual Before installation these instructions must be fully read and understood Table of contents Safety manual... 1 1. Introduction... 1 1.1 Terms and abbreviations... 2 1.2 Acronyms... 2 1.3 Product
More informationSECTION 7 AIR CONDITIONING (COOLING) UNIT 39 CONTROLS
SECTION 7 AIR CONDITIONING (COOLING) UNIT 39 CONTROLS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the control sequence for an air-conditioning system. Explain the function
More informationSECTION 7 AIR CONDITIONING (COOLING) UNIT 39 CONTROLS UNIT OBJECTIVES UNIT OBJECTIVES. After studying this unit, the reader should be able to
SECTION 7 AIR CONDITIONING (COOLING) UNIT 39 CONTROLS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the control sequence for an air-conditioning system. Explain the function
More informationBrazil. Current status in NPP I&C and Discussion Topics. 24th Meeting of the IAEA TWG-NPPIC
Brazil Current status in NPP I&C and Discussion Topics 24th Meeting of the IAEA TWG-NPPIC Marcos Candeias Silva Fuad Kassab Junior Ricardo Paulino Marques (Eletronuclear) (University of São Paulo) (University
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018
SECTION 26 2913 - ENCLOSED CONTROLLERS GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationUpdate all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.
11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.
More informationSafety lnstrumentation Simplified
A United Electric Controls White Paper Safety lnstrumentation Simplified by: Wil Chin, Vice President of Marketing and Business Development at United Electric Controls Rick Frauton, Senior Product Marketing
More informationOptions for Developing a Compliant PLC-based BMS
Options for Developing a Compliant PLC-based BMS Jack Boone aesolutions Greenville, South Carolina, United States of America ABSTRACT Facilities are focusing on improving the reliability of their burner
More informationReducing Arc Flash Risks with Electrical Maintenance Safety Devices - Part 2
Reducing Arc Flash Risks with Electrical Maintenance Safety Devices - Part 2 By: Martin Robinson, CEO of IRISS Group and Level III Thermographer Abstract Every year thousands electrical workers are injured
More informationALTERNATIVE PROPOSAL TO SATISFY REQUIREMENTS OF FRA RS&I -- RULE GROUNDS AUTHORS
ALTERNATIVE PROPOSAL TO SATISFY REQUIREMENTS OF FRA RS&I -- RULE 236.2 GROUNDS AUTHORS TIMOTHY C. HEYWOOD SENIOR DESIGN ENGINEER WAYSIDE PRODUCTS ALSTOM SIGNALING, INC. JAMES B. BALLIET VICE PRESIDENT
More informationSECTION (16460) - LOW-VOLTAGE TRANSFORMERS
PART 1 GENERAL 1.01 SUMMARY SECTION 26 22 00 (16460) - LOW-VOLTAGE TRANSFORMERS A. Section Includes: 1. Dry-Type Distribution And Specialty Transformers Rated 1000 V And Less. a. General-Purpose Distribution
More informationEPSS Monitoring for Total Compliance
EPSS Monitoring for Total Compliance A Lawyer s Playground PRESENTED BY Dan Chisholm, Sr. Chairman of NFPA 110 Technical Committee Dan.Chisholm@mgi-epss.com Learning Objectives What CMS surveyors are looking
More informationThe safe way to verify the absence of voltage.
VeriSafe Absence of Voltage Tester The safe way to verify the absence of voltage www.panduit.com/verisafe What is an Absence of Voltage Tester? Absence of Voltage Testers (AVTs) are permanently-mounted
More informationRelay Performance Index for a Sustainable Relay Replacement Program
Relay Performance Index for a Sustainable Relay Replacement Program Aaron Feathers, Abesh Mubaraki, Nai Paz, Anna Nungo Pacific Gas & Electric Company San Francisco, CA Western Protective Relay Conference
More informationDynamic Solutions. Endless Possibilities. Steve Padasack, Finch Paper LLC Rick Van Fleet, Honeywell
Honeywell Users Group 2010 Dynamic Solutions. Endless Possibilities. Steve Padasack, Finch Paper LLC Rick Van Fleet, Honeywell A(bout) with Obsolescence Moore Micro DCS Transition to Experion Background
More informationBulletin 1608N MiniDySC Dynamic Sag Corrector
User Manual Bulletin 1608N MiniDySC Dynamic Sag Corrector Single Phase Voltage Sag Correction 2...6 Amps (250...750 VA) Important User Information Solid-state equipment has operational characteristics
More informationOverfill Prevention Control Unit with Ground Verification & Vehicle Identification Options. TÜVRheinland
Scully Intellitrol Safety Manual Overfill Prevention Control Unit with Ground Verification & Vehicle Identification Options TÜVRheinland Functional Safety Type Approved FS IEC 61508 Certified SIL 2 / SIL
More informationTOP R4 Unknown Operating State
TOP-004-2 R4 Unknown Operating State September 30, 2014 Greg Sorenson, PE Senior Compliance Engineer gsorenson.re@spp.org 501.688.1713 Outline Requirement Language Study Outcomes and Limitations Self-Check
More informationSpectron LSN (Life Safety Network) Suggested Specifications
1. General 1.1 Scope A Dual-Lite Spectron LSN (Life Safety Network) Series Inverter System shall be furnished to provide a reliable source of power, and shall operate during a utility line deficiency without
More informationRelease of Updated Training Standard Log Book
Release of Updated Training Standard Log Book Trade Name & Code Implementation Date of New Standard Implementation Plan Impact on Curriculum Standards or Related Trades Training Standard Access Skill(s)
More informationSAFETY MANAGER SC Ensure safety, simplify operations and reduce lifecycle costs
SAFETY MANAGER SC Ensure safety, simplify operations and reduce lifecycle costs Meet Today s Cost and Complexity Challenges Industrial process plants are trying to reduce their process control and safety
More informationfrom In this issue teamwork... OBSOLESCENCE ALERTS Product Enhancements Akrion Systems News SPECIAL OFFERS!
from February 5, 2009 ISSUE 1-3 teamwork... that's what it took for the Pittsburgh Steelers to win the NFL Super Bowl. A group of people working together can accomplish great things. We here in Pennsylvania
More informationNational Grid / DG Installation Process Guide per NY SIR / July 2011 ver. 1.0
Distributed Generation Installation Process Guide for Connections to National Grid Distribution Facilities per the New York Standardized Interconnection Requirements Introduction National Grid ( The Company
More informationStandard Development Timeline
Standard Development Timeline The drafting team maintained this section while developing the standard. It will be removed when the standard becomes effective. Description of Current Draft This draft is
More informationGE Security Vigilant Fire & Life Safety. Easy. V-Series Intelligent Life Safety Systems
GE Security Vigilant Fire & Life Safety Easy. V-Series Intelligent Life Safety Systems Stylishly Simple Quick setup, easy maintenance, and striking good looks makes V-Series the life safety system of choice
More informationRutgers Environmental Health and Safety (REHS)
Rutgers Environmental Health and Safety (REHS) Program Name: Laboratory Laser Safety Program Responsible Executive: Executive Director of REHS Adopted: February 20, 2001 Reviewed/Revised: July 10, 2018
More informationSECTION AUTOMATIC TRANSFER SWITCHES
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph
More informationFunctional Safety of Machinery Presented by Greg Richards Manufacturing in America 02/22-23/2017
Functional Safety of Machinery Presented by Greg Richards Manufacturing in America 02/22-23/2017 AGENDA Definition of Safety? Machinery Safety Standards Comparison of ISO 13849-1 and IEC 62061 Safety-related
More informationStandard PRC Transmission Relay Loadability
A. Introduction 1. Title: Transmission Relay Loadability 2. Number: PRC-023-2 3. Purpose: Protective relay settings shall not limit transmission loadability; not interfere with system operators ability
More informationAPPLICATION STORY. Nuclear scientists choose PSS programmable safety system
19 December 2006 APPLICATION STORY Nuclear scientists choose PSS programmable safety system A new Australian Nuclear Science and Technology Organisation (ANSTO) experimental facility uses five Pilz PSS
More informationPilz Safety Lockout System (PSLS)
Pilz Safety Lockout System (PSLS) An alternative isolation method for LOTO By Doug Sten, Safety Consultant, Pilz Automation Safety Objectives Challenges with manual, mechanical isolation disconnects Challenges
More informationNeed for a Bipole III rating of 2300 Mw to transmit Keeyask power.
Need for a Bipole III rating of 2300 Mw to transmit Keeyask power. Introduction Further to the Technical Assessment of the Need for the Bipole III Line, dated 21 November 2014- Dennis Woodford P. Eng.
More informationInstruction Manual December 2001 ENACOCU02
SENACOCU02 Instruction Manual December 2001 ENACOCU02 Safety Guidelines Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected
More informationSIL Safety Guide Series MS Single-Acting Spring-Return Hydraulic Linear Actuators
SIL Safety Guide Series MS Single-Acting Spring-Return Hydraulic Linear Actuators Rev 0, November 17 2015 Page 1 of 9 Table of Contents 1 INTRODUCTION 3 1.1 Terms and abbreviations 3 1.2 Acronyms 4 1.3
More informationREMOTE MONITORING AND ALARM SYSTEM
FUNCTIONALITY A. The water and wastewater facilities remote monitoring, reporting and alarm notification system shall be comprised of a hosted, Web-based user-interface which communicates to remotely monitored
More informationENERGY CONTROL LOCKOUT/TAGOUT PROGRAM PLAN
ENERGY CONTROL LOCKOUT/TAGOUT PROGRAM PLAN Published by Environmental Health and Safety Last updated: 1/25/2017 Page 1 of 16 1. INTRODUCTION John Jay College Environmental Health and Safety (EHS) office
More informationYour Global Automation Partner. Minimizing Arc Flash Exposure in Industrial Applications. White Paper - W1000
Your Global Automation Partner Minimizing Arc Flash Exposure in Industrial Applications White Paper - W1000 Industrial environments present multiple safety challenges, including fire hazards that require
More informationSECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD
PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard
More informationDTW Master Specification Section EMCS: Start Up, Verification and Commissioning
Page 1 of 6 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Related Sections..1 The contractor is to ensure that all related work is co ordinated among all specification sections, as well as between Division 11,
More informationElectrical Safety Requirements
Electrical Safety Requirements Purpose This document defines the minimum required control measures to reduce the risk of injury or illness related to electricity. Scope Applicable to all Coca-Cola system
More informationON THE BUTTON A reference guide to environmental ratings used for push button enclosures
ON THE BUTTON A reference guide to environmental ratings used for push button enclosures A REFERENCE GUIDE TO KEY TOPICS IN PUSH BUTTON SELECTION AND SAFETY CONTENTS I. INTRODUCTION...............................
More informationSECTION GENERATOR PARALLELING CONTROLS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 23 13 GENERATOR PARALLELING CONTROLS SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also delete any other item or paragraph not applicable
More informationCommunity Development and Recreation Committee
STAFF REPORT ACTION REQUIRED Results of the Fire Insurance Grades Study Date: November 20, 2013 To: From: Wards: Reference Number: Community Development and Recreation Committee Fire Chief and General
More informationWhite Paper. NFPA 70E 2018 Edition Changes and Implications for. Personnel Performing Condition Based Maintenance. Abstract: iriss.
NFPA 70E 2018 Edition Changes and Implications for Personnel Performing Condition Based Maintenance By Rudy Wodrich, P.Eng., MBA, CRL, L1 Thermographer, VP Engineering Services, IRISS Inc. Abstract: The
More informationFailure Modes, Effects and Diagnostic Analysis
Failure Modes, Effects and Diagnostic Analysis Project: Fireye Flame Sensor Module CE Flameswitch, model MBCE-110/230FR Company: Fireye Derry, NH USA Contract Number: Q09/10-26 Report No.: FIR 09/10-26
More informationPlease make yourselves familiar with the changes and start implementing them immediately so you can be better prepared for June 30 th, 2018.
Included below are the top fifteen changes within the 2018 Canadian Electrical Code (CEC). Here in Newfoundland and Labrador, the 2018 Code was adopted as of January 1 st, 2018 and will be enforced as
More informationSECTION ENCLOSED CONTROLLERS
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes ac,
More informationMICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR INTERSECTION WARNING SYSTEM (IWS) SUP:DG 1 of 12 ITS:APPR:CLC:DBP:
MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR INTERSECTION WARNING SYSTEM (IWS) SUP:DG 1 of 12 ITS:APPR:CLC:DBP:12-15-09 a. Description. This section describes wireless vehicle detection
More informationAPC BC300 Series 40kW 208/450/480V User Guide
APC BC300 Series 40kW 208/450/480V User Guide Copyright 2002 APC Denmark ApS This manual is subject to change without notice and does not represent a commitment on the part of the vendor Thank You Thank
More informationModule Features are-configurable, no module jumpers to set
December 2011 PACSystems* RX3i Isolated Thermocouple Input Module, 6 Channels, IC695ALG306 Isolated Thermocouple Input Module, 12 Channels, IC695ALG312 Isolated Thermocouple Input module IC695ALG306 provides
More information