SUP 14: Floor laying. Unified procedures for use within NHS Scotland
|
|
- Jodie Cole
- 5 years ago
- Views:
Transcription
1 Unified procedures for use within NHS Scotland May 2015
2 Contents page Acknowledgements Introduction Control of Contractors Procedure Checklists Records... 5 Appendix... 6 Disclaimer The contents of this document are provided by way of general guidance only at the time of its publication. Any party making any use thereof or placing any reliance thereon shall do so only upon exercise of that party s own judgement as to the adequacy of the contents in the particular circumstances of its use and application. No warranty is given as to the accuracy, relevance or completeness of the contents of this document and Health Facilities Scotland, a Division of NHS National Services Scotland, shall have no responsibility for any errors in or omissions therefrom, or any use made of, or reliance placed upon, any of the contents of this document. Draft Version 0.05: May 2015 Page 2 of 6
3 Acknowledgements This unified procedures guidance has been produced for NHS Boards to adopt or adapt and incorporates information made available by NHS Lothian which is gratefully acknowledged. Draft Version 0.05: May 2015 Page 3 of 6
4 1. Introduction 1.1 It is the responsibility of the owners and occupiers of properties, NHS Board Chief Executive Officers and Managers to ensure that their premises comply with all statutory requirements. 1.2 Employers have a duty under the Health & Safety at Work etc Act 1974, so far as is reasonably practicable, to ensure the health and safety of employees, residents and visitors to their premises. It is incumbent upon both owners and occupiers of premises to ensure that there is a management regime in place for the proper operational and risk management of buildings, plant, equipment and systems. 1.3 All personnel should be made fully aware of their safety responsibilities, as required by statute and they should be given the necessary information and training properly to understand and carry them out. This also applies to organisations and individuals to whom work has been contracted. 1.4 The task of floor laying using vinyls, linoleum and marmoleum usually requires the use of a heat source to seal the joints between lengths of these materials. 1.5 Comprehensive information on Estates Operating Procedures relating to hot working can be found in the Unified Procedures guidance document Issuing hot work permits. However, the procedure for floor laying and heat sealing joints is seen to produce very low risks. Control of Contractors 1.6 The NHS Board s Control of Contractors procedures requirements must be applied to all persons engaged in maintenance and remedial work associated with laying of floor coverings. (Refer to Unified Procedures document SUP 01 Control of Contractors ) Draft Version 0.05: May 2015 Page 4 of 6
5 2. Procedure Checklists 2.1 Notwithstanding the low risks associated with heat sealing of the joints in the floor covering materials, the Checklist contained in the Appendix of this Unified Procedure must be completed to record that NHS Board managers have taken into account potential risks. 2.2 The completed checklist must be signed and dated with the area noted. (This record must be retained at management level, Team Leaders can be assumed to be in management team). 2.3 This process must be followed instead of the need to issue a Permit for this activity. Records 2.4 Risk Assessment must be issued to Contractor every time. 2.5 There is still a requirement to keep a record of the work in the Permit-to-Work issued logbook and in the remarks column note the unified procedure and risk assessment followed. (The risk assessment reference should be appended). Note: If during the assessment of area of work, it is determined that the control measures outlined in the unified procedures checklist set out in the Appendix will not be sufficient to reduce the risk, then the Permit-to-Work system must be used and a suitable risk assessment put in place. Draft Version 0.05: May 2015 Page 5 of 6
6 Appendix a. The area has been cordoned off (if required). b. The location has been inspected for combustible materials. c. There are no combustible liquids, vapours, gases or dusts present. Check Yes/No Comments d. If combustible materials are present, they are suitably protected. e. A suitable fire extinguisher is available. f. Fire detectors are isolated in the vicinity of the work. g. Operatives have been instructed in the NHS Board s fire procedures. h. It is now safe for this activity/task to commence. i. The completed work area has been inspected and 30 minutes has elapsed before fire detectors were re-instated. Area of work..... Authorising Manager Date Contractor... Draft Version 0.05: May 2015 Page 6 of 6
NHSScotland Firecode. A Model Management Structure for Fire Safety Version 4. This document forms part of NHSScotland Firecode Edition No
NHSScotland Firecode A Model Management Structure for Fire Safety Version 4 This document forms part of NHSScotland Firecode Edition No NHSScotland, P&EFEx, April 2004 Contents 1. About this document page
More informationFacilities and Estates. Hot Works: Standard Operating Procedure. Document Control Summary
Facilities and Estates Hot Works: Standard Operating Procedure Document Control Summary Status: Version: Author/Title: Owner/Title: Approved by: Ratified: Related Trust Strategy and/or Strategic Aims Implementation
More informationFIRE SAFETY POLICY. Approval Approved by: University Court Date: March 28 th 2017
Date: March 2017 Page 1 of 12 FIRE SAFETY POLICY Approval Approved by: University Court Date: March 28 th 2017 Page 1 of 12 Date: March 2017 Page 2 of 12 UNIVERSITY OF ABERDEEN FIRE SAFETY POLICY Contents
More informationNHS Tayside. Fire Safety Policy
NHS Tayside Fire Safety Policy Policy Manager Mark Anderson, Head of Property Policy Group Fire Safety Policy Review Group Policy Established Last Updated April 2014 Policy Review Period/Expiry April 2017
More informationFIRE SAFETY POLICY LEEDS METHODIST MISSION. Oxford Place Centre
FIRE SAFETY POLICY LEEDS METHODIST MISSION Oxford Place Centre P a g e 2 8 Version Draft 1 Name of responsible (ratifying) committee Leeds Methodist Mission Council Date ratified Document Manager (job
More informationFire Safety Management
Fire Safety Management Procedure () FIRE SAFETY MANAGEMENT PROCEDURE Contents Section 1: Management of Fire Safety Procedure in Operation Section 2 Organisational responsibilities Section 3: Emergency
More informationJoint Responsibility for Health and Safety Internal Guidance for Members and other occupiers of the Scottish Parliament Campus.
To: Leadership Group From: Jake Fenton Extension: 86917 Date: 17/5/12 Dear Colleague, S. Joint Responsibility for Health and Safety Internal Guidance for Members and other occupiers of the Scottish Parliament
More informationFire Safety Policy. Document Author: Director of Estates, Fleet & Facilities Management
Fire Safety Policy Document Author: Director of Estates, Fleet & Facilities Management Date Approved: January 2018 Document Reference Fire Safety Policy January 2020 Version V: 2.1 Responsible Committee
More informationFire Safety Policy 29/09/2017. Holme Grange School Whole School Policy Including EYFS. Fire Safety Policy
Holme Grange School Whole School Policy Including EYFS Fire Safety Policy This document details the school s policy on fire safety in operation at Holme Grange School. The document is split into a number
More informationNOTTINGHAM CITY HOMES
APPENDIX 1 NOTTINGHAM CITY HOMES FIRE SAFETY POLICY 2013/14 Draft for Board Uncontrolled when printed Page 1 of 14 DOCUMENT CONTROL Identification and Approval Status Document Title: Nottingham City Homes
More informationUNCONTROLLED IF PRINTED. Issued with the authority of the Chief Commissioner and General Manager of Scouts Australia NSW
PROCEDURE Emergency preparedness Issued with the authority of the Chief Commissioner and General Manager of Chief Commissioner signature Chief Executive Officer signature Sponsor Head of Risk Document
More informationJune 2017 (Updated 18 January 2018) Fire Safety Policy. Peter Webb, Project Manager Compliance First Choice Homes Oldham Limited
June 2017 (Updated 18 January 2018) Fire Safety Policy Peter Webb, Project Manager Compliance First Choice Homes Oldham Limited Trusted provider of quality homes, excellent landlord and support services,
More informationFire Safety Policy. Contents. This policy was approved by the Trustees on 6 September 2018 and will be reviewed not later than every 5 years.
Fire Safety Policy This policy was approved by the Trustees on 6 September 2018 and will be reviewed not later than every 5 years. Contents 1. Policy principles 2 2. Statutory and Regulatory Framework
More informationHealth and Safety Policy. Version Author Revisions Made Date 1 Colin Campbell First Draft March 2014
Fire Safety Policy Originator name: Section / Dept: Implementation date: Clive Parkinson Health & Safety March 2014 Date of next review: March 2017 Related policies: Health and Safety Policy Policy history:
More informationTo seek Cabinet approval of the Council s Fire Safety Policy. It is proposed that Cabinet approves the Fire Safety Policy.
NORTH AYRSHIRE COUNCIL Cabinet 1 May 2018 Title: Purpose: Recommendation: Fire Safety Policy To seek Cabinet approval of the Council s Fire Safety Policy. It is proposed that Cabinet approves the Fire
More informationH&S Forum. Fire Safety Policy Glascote Academy
Fierte Multi Academy Trust Health and Safety Policy Handbook Reference Number HR 103 Issue 6 Approved By H&S Forum Date September 2016 To be reviewed September2017 Policy Title Fire Safety Policy Glascote
More informationFire risk management plan. MH/05/Revised/06/17
Fire risk management plan MH/05/Revised/06/17 1 1. Scope This policy applies to fire safety arrangements in all workplaces, common areas of residential premises and any other premises managed and/or owned
More informationBush House buildings. Contractor Site induction
Bush House buildings Contractor Site induction October 2017 Welcome Bush House is the newest complex to the Strand Campus There are four buildings in the Bush House complex, shown on the map. We are currently
More informationPOLICY FOR THE SAFE WORKING WITH ELECTRICITY
AGENDA ITEM 2.3 7 October 2010 POLICY FOR THE SAFE WORKING WITH ELECTRICITY Report of Executive Director of Planning Paper prepared by Purpose of Paper Action/Decision required Link to Health Care Standards:
More informationNOT PROTECTIVELY MARKED. Fire Legislation
Fire Legislation Contents Policy Statement... 2 Legislation... 2 Fire Extinguisher Usage... 2 Fire Evacuation Procedure... 3... 4 Line Managers/Supervisors... 4 Business Support Officer... 5 Driver/Handy
More informationFire safety policy. Contents. This policy was approved by the Trustees on 3 September 2015 and will be reviewed not later than every 3 years.
Fire safety policy This policy was approved by the Trustees on 3 September 2015 and will be reviewed not later than every 3 years. Contents 1. Policy principles 2 2. Statutory and Regulatory Framework
More informationHIGH VOLTAGE ELECTRICAL SUPPLY CONNECTIONS Overview of High Voltage Customer Obligations
Overview of High Voltage Customer Obligations HIGH VOLTAGE (HV) CUSTOMERS CONNECTED TO THE SUPPLY AUTHORITY S NETWORK HAVE CERTAIN OBLIGATIONS TO ENSURE THE INSTALLATION IS OPERATED IN A SAFE MANNER. TO
More informationFire Safety Policy SH HS 06. Version: 4. Summary:
SH HS 06 Fire Safety Policy Summary: Keywords: Target Audience: The Fire Safety Policy sets out the Trusts approach to a proactive fire safety culture to protect its staff, patients, service users, all
More informationHealth & Safety Policy HSP 03 Fire Safety Version Status Date Title of Reviewer Purpose/Outcome
Health & Safety Policy HSP 03 Fire Safety Version Status Date Title of Reviewer Purpose/Outcome 1.0 Draft 07.03.2016 David Maine 1 st Draft for consultation/review 1.1 Approved 22.12.2016 David Maine 1
More informationISLE OF WIGHT FIRE & RESCUE SERVICE
ISLE OF WIGHT FIRE & RESCUE SERVICE Record of Fire Safety Equipment Testing Fire Drills & Training CONTENTS 1. MEANS OF ESCAPE 2. FIRE WARNING AND AUTOMATIC FIRE DETECTION 3. FIRE EXTINGUISHERS AND HOSEREELS
More informationREGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN
REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the Plan is to ensure the
More informationNZS 4517:2010. New Zealand Standard. Fire sprinkler systems for houses. Superseding NZS 4517:2002 NZS 4517:2010
New Zealand Standard Fire sprinkler systems for houses Superseding NZS 4517:2002 NZS 4517:2010 NZS 4517:2010 COMMITTEE REPRESENTATION This Standard was prepared under the supervision of the P 4517 Committee,
More informationPeninsula Dental Social Enterprise (PDSE)
Peninsula Dental Social Enterprise (PDSE) Fire Safety Policy and Procedure Version 2.0 Date approved: September 2016 Approved by: The Board Review due: September 2017 Policy will be updated as required
More informationCONTRACTOR WHS HAZARD STANDARD LASER SAFETY EXTERNAL USE ONLY
CONTRACTOR WHS HAZARD STANDARD LASER SAFETY EXTERNAL USE ONLY Principles in the Optus Contractor WHS management process CONTRACTOR MANAGEMENT STAGES PRINCIPLES THIS STANDARD REQUISITION Requisition WHS
More informationSTATEMENT OF THE HEALTH AND SAFETY STRATEGY FOR THE SYDNEY RUSSELL SCHOOL
Health & Safety Contents Health & Safety... 1 Contents... 2 HEALTH AND SAFETY STRATEGY... 3 GOVERNORS STATEMENT... 3 STATEMENT OF THE HEALTH AND SAFETY STRATEGY FOR THE SYDNEY RUSSELL SCHOOL... 3 HEALTH
More informationNHSScotland Firecode Scottish Fire Practice Note 3 Version 3
NHSScotland Firecode Scottish Fire Practice Note 3 Version 3 Escape bed lifts October 2010 Contents page About this publication...4 1. Introduction...5 2. Definitions...6 3. Considerations that will influence
More informationFIRE SAFETY POLICY. Executive Management Team. Health, Safety and Fire Steering Group.
FIRE SAFETY POLICY Approver Executive Management Team Policy Fire Safety Policy Monitored By Health, Safety and Fire Steering Group. Date last revised April 2017 Revised by James Warne Next Revision Date
More informationFIRE SAFETY POLICY Revised March 2013
FIRE SAFETY POLICY Revised March 2013 CONTENTS Page No 1.0 Statement of Intent 1 2.0 Fire Safety Accountability Structure 2 3.0 Roles and Responsibilities 3 4.0 Fire Safety Management 7 5.0 Fire Risk Assessment
More informationPOLICY FOR FIRE SAFETY MANAGEMENT
Directorate of Facilities and Information POLICY FOR FIRE SAFETY MANAGEMENT Reference: FMP021 Version: 1.1 This version issued: 21/12/11 Result of last review: Minor changes Date approved by owner (if
More informationPolicy for safe working on Fire Alarm Systems at Loughborough University and Loughborough University in London
Policy for safe working on Fire Alarm Systems at Loughborough University and Loughborough University in London Scope of document General This document sets out the procedure for the management and control
More informationDan Gray, Property Director. Date: November 2017 Review Due Date: November 2020
Policy title: Scope: Policy owner & job title: Approver: Fire Safety Policy Group-wide Dan Gray, Property Director Aspire Housing Board Date: November 2017 Review Due Date: November 2020 POLICY SUMMARY
More informationMillfield Schools Fire Risk Prevention Policy
Millfield Schools Fire Risk Prevention Policy This policy refers to the Senior School, Preparatory School, Pre-Preparatory School and EYFS 1. Introduction This policy sets out the approach that the school
More informationManagement Standard: Fire Safety
OHSS: H&S Management 201 Fire Safety Management : Fire Safety 1. Legal framework This standard is produced to comply with the following legislation in respect to fire safety: 1.1. Regulatory Reform (Fire
More informationFire Safety Protocol
CORPORATE HEALTH AND SAFETY POLICY: Part 3 Arrangements Fire Safety Protocol Document Status: [ ] Guidance for Managers [] Protocol [ ] Procedures Version 0.1/ August 2013 DRAFT EALING NCIL Table of Contents
More informationPART 3-O REQUIREMENTS FOR SPRINKLER SYSTEMS MAINTENANCE AND SUPERVISION. 3-O Introduction O.1 Scope of Maintenance and Supervision...
CONTENTS Schedule of amendments for this part of the scheme document Page 1 of 14 3-O Introduction...3 3-O.1 Scope of Maintenance and Supervision...3 3-O.2 Certification conditions...5 3-O.3 LPS 1233 Service
More informationReplacing a consumer unit in domestic premises where lighting circuits have no protective conductor
Replacing a in domestic premises where lighting circuits have no protective conductor This is one of a series of Best Practice Guides produced by the Electrical Safety Council* in association with leading
More informationARCHIVE. Scottish Health Technical Memorandum 2011 (Part 1 of 4) Emergency electrical services
Scottish Health Technical Memorandum 2011 (Part 1 of 4) Overview and management responsibilities Emergency electrical services Disclaimer The contents of this document are provided by way of guidance only.
More informationFire Safety. A TUC guide for trade union activists
Fire Safety A TUC guide for trade union activists Contents Section one Introduction 3 Section two The law 4 Section three Fire risk assesment 5 Section four Policies and procedures 6 Section five Enforcement
More informationFire Safety Management Audit Specification August 2017
Fire Safety Management Audit Specification August 2017 Membership Training Qualifications Audit and Consultancy Policy and Opinion Awards Contents Page 1 Introduction to the Fire Safety Management Audit
More informationYour specialist partner for total electrical compliance. Electrical Testing
Your specialist partner for total electrical compliance Electrical Testing "To achieve compliance with the legal requirements of the Electricity at Work Regulations 1989 requires proof that an electrical
More informationProtocol between Local Housing Authorities and Fire and Rescue Authorities to improve fire safety
Protocol between Local Housing Authorities and Fire and Rescue Authorities to improve fire safety Foreword by Communities and Local Government Ministers It is always a priority to ensure safety from the
More informationFire safety management issues identified by fire risk assessments
Health and Safety Safety Team The University of Manchester Waterloo Place, 180 Oxford Road, Manchester Health and M13 Safety 9GP www.manchester.ac.uk To From Vice-Presidents/Deans, Heads of Schools and
More informationFire Risk Assessment Safety Checklist
Fire Risk Assessment Safety Checklist This checklist has been prepared to help you comply with The Regulatory Reform Fire Safety Order 2005 What is the Regulatory Reform (Fire Safety) Order 2005? The Regulatory
More informationThe Association for Specialist Fire Protection. Guidance in Passive Fire Protection
The Association for Specialist Fire Protection Guidance in Passive Fire Protection Wilf Butcher CEO Association for Specialist Fire Protection The ASFP - A brief background history When Originally known
More informationScottish Health Technical Memorandum 08-05: Specialist services Building management systems Part A Overview and management responsibilities
Scottish Health Technical Memorandum 08-05: Specialist services Building management systems Part A Overview and management responsibilities April 2012 Contents page Acknowledgements...4 Preface...5 About
More informationKings Fire Safety Policy
Kings Fire Safety Policy All Kings policies will be ratified by the Board of Directors and signed by the Chairperson. Each policy will be co-signed by the principal of each school. Review dates will be
More informationFire Safety Policy Date: 0
Fire Safety Policy Date: 0 Policy Preparation & Introduction This document format has been produced by Firesafe Solutions (UK) Ltd to aid managers, tenants and others responsible for fire safety in their
More informationCYNGOR SIR POWYS COUNTY COUNCIL
Appendix A CYNGOR SIR POWYS COUNTY COUNCIL Housing Services Fire Safety in Council Housing Policy Version For Portfolio Holder decision (10-01-2017) Reference POL LL Fire Safety Housing Services Fire Safety
More informationA GUIDE TO THE REGULATORY REFORM ORDER (FIRE SAFETY) 2005 (RRO)
4 PEEL HOUSE,TAUNTON STREET,SHIPLEY,BN18 3NA TEL: 01274 595015 FAX: 01274 580804 EMAIL:sales@rosse-systems.co.uk A GUIDE TO THE REGULATORY REFORM ORDER (FIRE SAFETY) 2005 (RRO) THE PURPOSE OF THIS DOCUMENT
More informationFIRE SAFETY LOGBOOK ADDRESS OF PREMISES NOMINATED RESPONSIBLE PERSON
FIRE SAFETY LOGBOOK ADDRESS OF PREMISES NOMINATED RESPONSIBLE PERSON SURESITE LTD. All rights reserved. Not to be reproduced without prior permission 23 AN INTRODUCTION TO YOUR LOG BOOK This fire safety
More informationFIRE SAFETY LOG BOOK. (Record of Fire Safety Equipment Testing)
FIRE SAFETY LOG BOOK (Record of Fire Safety Equipment Testing) Fire safety log book MARCH 2013 CONTENTS 1.0 PREMISES SPECIFIC INFORMATION 2.0 FIRE SAFETY EQUIPMENT TESTING 2.1 Escape Routes 2.2 Fire Warning
More informationFIRE SAFETY POLICY AND STRATEGY
FIRE SAFETY POLICY AND STRATEGY 1 1 Policy : Fire Safety Policy and Strategy Executive Summary: The purpose of this policy is to provide an unambiguous statement on fire safety, outlining the responsibilities
More informationRRC SAMPLE MATERIAL MANAGING FIRE SAFETY LEARNING OUTCOMES
MANAGING FIRE SAFETY LEARNING OUTCOMES On completion of this element, you should be able to demonstrate understanding of the content by applying what you have learnt to familiar and unfamiliar situations.
More informationVisitors to Police Premises Standard Operating Procedure
Visitors to Police Premises Standard Operating Procedure Notice: This document has been made available through the Police Service of Scotland Freedom of Information Publication Scheme. It should not be
More informationDUQUESNE UNIVERSITY. Fire Protection System Impairment Program (Red etag Permit)
DUQUESNE UNIVERSITY Fire Protection System Impairment Program (Red etag Permit) Prepared by: Environmental Health and Safety Department TABLE OF CONTENTS Page Purpose 1 Scope 1 Exceptions 2 Definitions
More informationFIRE ALARMS EMERGENCY LIGHTS NURSE CALL ACCESS CONTROL GK FIRE & SECURITY LTD, UNIT 1 GREBE RD, PRIORSWOOD IND EST, TAUNTON, TA2 8PZ
BS5839-1 : 2013 FIRE ALARMS EMERGENCY LIGHTS NURSE CALL ACCESS CONTROL Forward It is recommended that this logbook be maintained by a relevant member of the premises management, to ensure that every entry
More informationLocal Rules: Fire Safety
1. Potential Effects of a Fire A small fire is most likely to cause damage to equipment and furniture, with the potential to cause additional smoke damage to the room of origin. A large and protracted
More informationHEALTH AND SAFETY FIRE SAFETY POLICY Putnoe Primary School
HEALTH AND SAFETY FIRE SAFETY POLICY Putnoe Primary School OBJECTIVE This Fire Safety Policy is designed to help Putnoe Primary School comply with their duties under the Regulatory Reform (Fire Safety
More informationFire Safety Policy. Mark Garthwaite, Fire Team Manager, Serco ASP. Sharon Fox, Associate Director of Corporate Affairs
Fire Safety Policy Lead Author Developed by Mark Garthwaite, Fire Team Manager, Serco ASP Sharon Fox, Associate Director of Corporate Affairs Approved by Clinical Executive Committee 31 October 2017 Ratified
More informationSCALES NW EMERGENCY ACTION PLAN
Purpose Each SCALES NW, INC location shall have a written Emergency Action Plan, appropriate to the hazards of the workplace, in order to respond to an emergency that may require rescue or evacuation.
More informationNHSScotland Firecode. Scottish Health Technical Memorandum 84 Version 3
NHSScotland Firecode Scottish Health Technical Memorandum 84 Version 3 Fire risk assessment in residential care premises This document forms part of NHSScotland Firecode Edition No 3 NHSScotland, P&EFEx,
More informationFIRE SAFETY POLICY June 2014
FIRE SAFETY POLICY June 2014 Policy Title Fire Safety Policy Reference Number Corpo11/002 Implementation Date June 2014 1 st Review Review Date June 2017 Responsible Officer Director of Performance and
More informationISO 6183 INTERNATIONAL STANDARD. Fire protection equipment Carbon dioxide extinguishing systems for use on premises Design and installation
INTERNATIONAL STANDARD ISO 6183 Second edition 2009-06-15 Fire protection equipment Carbon dioxide extinguishing systems for use on premises Design and installation Équipement de protection contre l'incendie
More informationHealth and Safety Documentation Updated Health & Safety Brief. Educational Parties & Youth Groups visiting the Peacock Theatre
Health & Safety Brief Educational Parties & Youth Groups visiting the Peacock Theatre 1 Contents Health, Safety and Welfare Policy Statement Health and Safety Management Sadler s Wells responsibilities
More informationFire Risk Assessment 2017
Fire Risk Assessment 2017 Westmorland House Windermere School Author Paul Brownless Date 11 April 2017 Revised Revised by 04/12/2017 Richard Hennah Reference FRA_WSWH_11042017 1 AUTHOR CLIENT Paul Brownless
More informationStatutory Compliance Checklist
Date of Issue: April 2017 Statutory Compliance Checklist This document is for clergy and churchwardens to help them in the maintenance of their Churches. Refer to supplementary notes for further guidance.
More informationEMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be
EMLC Academy Trust Fire Safety Policy 2017/19 Every child deserves to be the best they can be 1 Scope: EMLC Academy Trust & Academies within the Trust Version: 2 Filename: EMLC Academy Trust Fire Safety
More informationATM DEVICE THEFT & ATM GAS ATTACKS:
ATM DEVICE THEFT & ATM GAS ATTACKS: INFORMATION & ADVICE FOR BUSINESSES Safer Communities, Specialist Crime Division December 2018 Introduction This guidance is intended to assist the banking and retail
More informationFire Safety Policy. Billy Hanafin H & S and Operations Officer. Fife Cultural Trust. Version 1.0 October 2013 Page 1
Billy Hanafin H & S and Operations Officer Version 1.0 October 2013 Page 1 1. General The Trust is a responsible employer that takes its Fire Safety duties seriously. For that reason, this policy has been
More informationFire Safety Management
POLICY Fire Safety Management Policy Owners Policy Holder Author DCC Norfolk / DCC Suffolk Health & Safety Health & Safety Manager Estates Manager Policy No. 66 Approved by Legal Services 25.09.15. Policy
More informationHot Work Permit. Can this job be avoided? Is there a safer alternative? Permit No.:
Hot Work Permit Can this job be avoided? Is there a safer alternative? Permit No.: A Hot Work Permit is required for any non-production or maintenance operation involving cutting, welding, grinding, open
More informationFIRE SAFETY GUIDELINES for SCOUTING IRELAND Scout Dens and Meeting Places
FIRE SAFETY GUIDELINES for SCOUTING IRELAND Scout Dens and Meeting Places Prepared by Eamon O Boyle and Associates Client Scouting Ireland Date October 2018 Job Ref. No. 17103 Report Ref. No. 17103-FSG-R01
More information1.2 To ensure the safety of all persons working in or occupying a building where a hot work operation is performed.
REQUIREMENT 2. HOT WORK OPERATIONS 1.0 PURPOSE 1.1 To establish a requirement with responsibilities for any hot work operations during all phases of construction, renovation and routine maintenance work
More informationTable of Contents. EMERGENCY PROCEDURES Policy 190
Table of Contents EMERGENCY PROCEDURES Policy 190 1. TRAINING ON EMERGENCY PROCEDURES... 2 2. EVACUATION PLAN... 2 2.1 Purpose... 2 2.2 Initiation Of Evacuation Alarm... 2 2.3 Evacuation Procedures...
More informationDispute over the requirement for fire door signage to hotel suites at 124 Devon Street West, New Plymouth
Determination 2016/058 Dispute over the requirement for fire door signage to hotel suites at 124 Devon Street West, New Plymouth Summary This determination considers whether signage is required between
More informationFire Safety Strategy
SH HS 02 Summary: Keywords (minimum of 5): (To assist policy search engine) Target Audience: The aim of this strategy is the provision and maintenance of a safe environment for all staff, visitors and
More informationCCTV POLICY AND CODE OF PRACTICE
1 INTRODUCTION This policy applies to the Senior School, Prep School and Pre-Prep School CCTV POLICY AND CODE OF PRACTICE 1.1. Yarm School (the School ) has installed a comprehensive closed circuit television
More informationRenovation Program. Renovation Program GENERAL
Renovation Program GENERAL This program provides guidance and protocols for renovation projects in occupied, operational acute hospitals. Team building is essential to quality control and HFD Services
More informationFire Safety Policy. August 2014 review. Version number: 6. Director of Clinical Services. Lawson Bisset Head of Estates. Review Date: August 2017
Fire Safety Policy Date: August 2014 review Version number: 6 Author: Reviewer: Director of Clinical Services Lawson Bisset Head of Estates Review Date: August 2017 If you would like this document in an
More informationPASCOE S PTY LTD EMERGENCY RESPONSE MANUAL. (Public Version) SOP 517. July 2015
PASCOE S PTY LTD EMERGENCY RESPONSE MANUAL (Incorporating) Pollution Incident Response Management Plan (Public Version) SOP 517 July 2015 40-46 FAIRFIELD STREET FAIRFIELD EAST, NSW 2165 TELEPHONE: 02 8774
More informationSt Edward s Oxford FIRE SAFETY POLICY
FIRE SAFETY POLICY 1 CONTENTS Section Page No.(s) 1. Policy Statement 3-5 2. Organisation and Responsibilities 6 3. Responsibilities of Responsible Person 7-8 4. Responsibilities of Senior Management 9
More informationFIRE SAFETY POLICY. This policy document replaces any previously published documents and comes into effect September 2018.
FIRE SAFETY POLICY This policy document replaces any previously published documents and comes into effect September 2018. 1.0 Fire Safety: The priority of Shrewsbury School is to minimise the risk to life
More informationFIRE SAFETY RISK ASSESSMENT AUDIT - CENTRE. Identification of hazards
FIRE SAFETY RISK ASSESSMENT AUDIT - CENTRE Name and address of premises: The Beamsley Project Harrogate Road Hazelwood Skipton BD23 6JA Date of assessment: 27 th September 2006 Person carrying out assessment:
More informationFire Safety Procedures and Associated Training
Fire Safety Procedures and Associated Training Revised March 2016 NOTE: HEADS OF SCHOOL/RI/DEPARTMENT MUST ENSURE THAT ALL MEMBERS OF STAFF, STUDENTS AND VISITORS FOR WHOM THEY HAVE RESPONSIBILITY ARE
More informationLYHA Fire Safety Policy
LYHA Fire Safety Policy Introduction This Fire Safety Policy shows our approach to Fire Safety in the work place and in our homes. It identifies our approach to Fire Safety in: The workplace Flats with
More informationWest Yorkshire Fire & Rescue Authority. Fire Protection Policy
West Yorkshire Fire & Rescue Authority Fire Protection Policy Risk Based Inspection Program 2017-2020 West Yorkshire Fire & Rescue Service Oakroyd Hall Birkenshaw Bradford BD11 2DY Date Issued: 28/03/2018
More informationEnvironmental Planning and Assessment Amendment (Smoke Alarms) Regulation 2006
New South Wales Environmental Planning and Assessment Amendment (Smoke Alarms) under the Environmental Planning and Assessment Act 1979 Her Excellency the Governor, with the advice of the Executive Council,
More informationFIRE SAFETY POLICY & EMERGENCY EVACUATION POLICY
FIRE SAFETY POLICY & EMERGENCY EVACUATION POLICY Under the terms of the Regulatory Reform (Fire Safety) Order 2005, and subsequent regulations, Seaford College must ensure the safety from fire of all staff,
More informationFire Risk Management Policy. UK September 2017
UK September 2017 5 & 7 Diamond Court, Opal Drive, Eastlake Park, Fox Milne, Milton Keynes MK15 0DU, T: 01908 396250, F: 01908 396251, www.cognitaschools.co.uk Registered in England Cognita Limited No
More informationNHS Isle of Wight Clinical Commissioning Group: Governing Body
NHS Isle of Wight Clinical Commissioning Group: Governing Body Date of Meeting: 21 March 2013 Agenda Item: 6.2 Paper number: GB13/022 FIRE SAFETY Sponsor: Summary of issue: Action required/ recommendation:
More informationFire Protection. A Health and Safety Guideline for Your Workplace. Introduction. Fire Prevention and Control. Workplace Assessment
A Health and Safety Guideline for Your Workplace Fire Protection Introduction Fire Protection is an organized approach designed to prevent fires. In the event of a fire, a fire protection program will
More informationEMERGENCY LIGHTING COMPLETION CERTIFICATE For small installations and verification of existing installations
A DETAILS OF THE CLIENT Client/ B DETAILS OF THE EMERGENCY LIGHTING INSTALLATION Extent of the installation covered by this certificate The Owner 19 Walker Grove, Hatfield, Hertfordshire 19 Walker Grove,
More informationRecord of fire safety risk assessment
Record of fire safety risk assessment Healthy Working Lives Company organisation: Address: Name of person(s) with fire safety duties: Building use: Name and contact details of Assessor: Signed: (Assessor)
More informationNATIONAL COMPETENCY STANDARD
NATIONAL COMPETENCY STANDARD WSQ Framework : WSH Professionals Competency Category : Implement operational control of WSH Competency Code : WP-IC-302C-1 Competency Unit : Coordinate implementation of emergency
More informationChesterfield Borough Council
Reviews December 2013 Prepared For: Town Hall Rose Hill Chesterfield S40 1LP Prepared By: Savills UK Limited 33 Margaret Street London W1G 0JD CHESTERFIELD BOROUGH COUNCIL FIRE RISK ASSESSMENT Report by:
More information