Pre-Engineered Fire Suppression

Size: px
Start display at page:

Download "Pre-Engineered Fire Suppression"

Transcription

1 Marine Fire Pre-Engineered Fire Suppression 727 Series Installation & Maintenance Manual Catef srl - Marine Fire Via Grecale Viareggio (LU) Italy Tel: Fax: Date: 2011 / M Series Manual - Rev. 00 Rev 00

2 FOR ASSISTANCE: INTRODUCTION: MARINE FIRE 727 series pre-engineered fire suppression systems are designed for installation in Engine Rooms and other not normally occupied areas on board Pleasure Craft (ISO 9094/1 and ISO 9094/2 standard for Recreational Craft) up to 24mt waterline length. These systems have undergone rigorous testing in a recognised laboratory and are certified by R.I.N.A. to protect against A and B class fires in machinery spaces up to 20m3 Net volume and not exceeding 70m3 gross compartment volume. MARINE FIRE 727 series systems are easy to install (no pipework required) and simple to maintain. 727 series systems contain Clean Agent FM-200 (HFC-227) and are designed to extinguish fire in less than 10 seconds from discharge. FM-200 is non-toxic leaves no residue thereby reducing clean up costs and downtime after a fire has occurred. This manual is intended to give you basic information and instructions regarding the installation, use and maintenance of your 727 series systems. More detailed information can be requested by contacting or Tel Series Fire Extinguishing systems use Clean Agent HFe-227 extinguishing agent, more commonly know as FM-200. FM-200 is a colourless, odourless, liquified compressed gas. It is stored as a liquid but discharges in the form of a gaseous vapour. FM-200 extinguishes fire by cooling the environment very rapidly. At the design concentration, FM-200 gas is non-toxic. Marine Fire 727 series systems are designed and approved for use in not normally occupied areas by RINA (e.g. engine rooms), for net volumes up to 700 cubic feet or 19,80 m3, under the ISO 9094 / 1 and ISO 9094 /2 standards. ATTENTION: MARINE FIRE 727 SERIES Fire Suppression Systems can be AUTOMATICALLY ACTIVATED via a heat sensitive bulb in the cylinder head. The system will activate at 68 C. Marine Fire 727 Fire Suppression systems are suitable for installation in: Machinery spaces Engine Compartments Electrical and electronic hazard areas Storage Rooms / lockers (flammable liquids and gases) - Page 2 -

3 Catef srl - Marine Fire INSTALLATION: WHICH MODEL? Choose the model of 727 series systems according to the NET volume of the compartment to be protected. It is important to get this calculation correct to ensure the correct operation of your 727 Series fire suppression system. MODEL PROTECTS VOLUME CUBIC FEET PROTECTS VOLUME CUBIC METRES IMPORTANT: if you require assistance in calculating the compartment volume, please contact the sales office. WHAT COMES IN THE BOX? Before you start installation, check that all the items are present : series cylinder, including valve, pressure gauge and nameplate. 2. The name plate is a white label on the side of the cylinder which provides information that is specific to each container : a. Serial Number b. Weight information c. Installation, Operation & safety information. 3. A support bracket. - Page 3 -

4 FOR ASSISTANCE: How to install the system MARINE FIRE 727 series systems must be installed INSIDE the protected compartment, and must be mounted in a secure location such as a structural column, bulkhead or deck. If moisture is present on the deck, elevate the system container a minimum of 2 (5 cm) off the deck. Never install a fire suppression system on the under side of a hatch cover or access door which are susceptible to damage or being thrown clear if an explosion occurs. The extinguisher would not work if the hatch or access door is left open. 727 Series systems are designed to activate manual, automatically at 68 C or both activation systems. For automatic or automatic/manual activations DO NOT mount the system where the thermal valve will be in the viciinity of the engine exhaust system or turbocharger, where radiated heat may cause the system to discharge. Mounting distances from heat producing appliances should be a minimum of 18 (50cm). NO pipework is required. To enhance response time and increase the distribution capabilty, mount the cylinder with the valve ABOVE THE CENTRELINE of the compartment. Mount the cylinder as high as possible with the centre of the discharge orifice facing the opposite bulkhead. The area immediately surrounding the discharge head should be free of obstacles to ensure that the gas can exit unimpeded. - Page 4 -

5 Catef srl - Marine Fire Maintenance Programme A regular maintenance programme must be established to ensure the continuous safe operation of the Marine Fire 727 Series system. The manufacturer recommends that a maintenance log be maintained for ready reference with the following information: Inspection Interval Inspection Prodedure Performed Maintenance Performed as a result of an Inspection Name of Inspector performing the task. Inspection intervals can vary according to class or flag rules, but a visual inspection is recommended on a weekly basis to include: 1. Check that the fire suppression system is secure in its bracket 2. Check support brackets, secure loose fittings, replace any corroded or damaged parts. 3. Check all components for physical damage, deterioration or corrosion. If significant damage or corrosion is present, remove the system from service and contact your nearest MARINE FIRE authorised distributor. 4. Check the pressure gauge on each cylinder. The nominal pressure should be 240PSI at 70 F 21 C). However t he pressure will vary with temperature. In the range of 50 F to 80 F (10 C - 27 C) the difference is approximately 2 psig (15 kpa) per degree. If the pressure loss indicated exceeds 10 per cent of the nominal pressure, check the container for leaks and repair as necessary. 5. If in doubt, contact the manufacturer TEL , or an authorised distributor. - Page 5 -

6 FOR ASSISTANCE: EVERY SIX MONTHS: 1. Check all system components are free from physical damage, deterioration or corrosion.. If significant damage or corrosion is present, remove the system from service and contact your nearest MARINE FIRE authorised distributor. 2. Inspect all labels. All fire suppression labels must be readable. If labels are missing or damaged, the system from service and contact your nearest MARINE FIRE authorised distributor. 3. Verify the weight of the agent in each container marche the agent weight on the label. Remove the system from the bracket using estreme caution. With a certified scale, weigh the container. If the measured weight indicates a shortage exceeding 5 per cent of the require agent weight, the container must be removed from service for repair and/or recharge. 4. Check the pressure gauge on each cylinder. The nominal pressure should be 240PSI at 70 F 21 C). However t he pressure will vary with temperature. In the range of 50 F to 80 F (10 C 27 C) the difference is approximately 2 psig (15 kpa) per degree. If the pressure loss indicated exceeds 10 per cent of the nominal pressure, check the container for leaks and repair as necessary. 5. Marine Fire 727 Series containers should not be recharged without a retest if more than five years have elapsed sinced the last test. The retest consists of a complete external and internal visual inspection. Cylinders continuously in service without discharging shall receive a complete external (visual) test every five years. The cylinder does not need to be emptied for this inspection. AFTER SYSTEM DISCHARGE: 1. Before accessing the area after a fire, ventilate the compartment thoroughly to ensure smoke and fumes have cleared before re-entry. 2. The 727 Series Marine Fire system should be removed and sent to the factory, or to an authorised service centre for refurbishing, and refilling. - Page 6 -

7 Catef srl - Marine Fire INSPECTION REPORT : - Page 7 -

8 RINA Type Approval Catef srl - Marine Fire Via Grecale Viareggio (LU) Italy Tel: Fax: All information is correct at the time of printing. Subject to variation or revision without further notice.

Reflex fire detection and extinguishing system filled with ABC dry powder. Installation, operation and maintenance instructions

Reflex fire detection and extinguishing system filled with ABC dry powder. Installation, operation and maintenance instructions Reflex fire detection and extinguishing system filled with ABC dry powder Installation, operation and maintenance instructions document number: 0221.321 revision: A:01.09.2018 table of contents 1. Your

More information

ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS SECTION 1 GENERAL SPECIFICATIONS I. SCOPE This specification outlines the requirements for a pre-engineered

More information

Reflex fire detection and extinguishing system charged with Novec 1230 extinguishing agent. Installation, operation and maintenance instructions

Reflex fire detection and extinguishing system charged with Novec 1230 extinguishing agent. Installation, operation and maintenance instructions Reflex fire detection and extinguishing system charged with Novec 1230 extinguishing agent Installation, operation and maintenance instructions document number: 0224.321 revision: 0:01-06-2018 table of

More information

MAINTENANCE AND INPSECTION OF FIRE PROTECTION SYSTEMS AND APPLIANCES

MAINTENANCE AND INPSECTION OF FIRE PROTECTION SYSTEMS AND APPLIANCES SHIPPING NOTICE Maritime Authority of the Cayman Islands Head Office 3 rd Floor, Government Administration Building, 133 Elgin Avenue PO Box 2256, Grand Cayman, KY1-1107, Cayman Islands Tel: +1 345 949

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply

More information

PURPLE K POWDER EXTINGUISHERS INSTALLATION, OPERATION, MAINTENANCE AND RECHARGE MANUAL

PURPLE K POWDER EXTINGUISHERS INSTALLATION, OPERATION, MAINTENANCE AND RECHARGE MANUAL PURPLE K POWDER EXTINGUISHERS INSTALLATION, OPERATION, MAINTENANCE AND RECHARGE MANUAL NO. 05602 FOR AMEREX STORED PRESSURE, HAND PORTABLE DRY CHEMICAL FIRE EXTINGUISHERS. ABC (Ammonium Phosphate Base)

More information

BMA INFORMATION BULLETIN No. 97 FIRE FIGHTING EQUIPMENT

BMA INFORMATION BULLETIN No. 97 FIRE FIGHTING EQUIPMENT BMA INFORMATION BULLETIN No. 97 FIRE FIGHTING EQUIPMENT Guidance and Instructions for Ship-owners, Managers, Masters, Bahamas Recognised Organisations and Bahamas Approved Nautical Inspectors Note: This

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply with this chapter and the International

More information

GASEOUS HYDROGEN SYSTEMS

GASEOUS HYDROGEN SYSTEMS CHAPTER 7 GASEOUS HYDROGEN SYSTEMS SECTION 701 GENERAL 701.1 Scope. The installation of gaseous hydrogen systems shall comply with this chapter and Chapters 30 and 35 of the Fire Compressed gases shall

More information

Government of Bermuda Bermuda Shipping and Maritime Authority BERMUDA SHIPPING NOTICE

Government of Bermuda Bermuda Shipping and Maritime Authority BERMUDA SHIPPING NOTICE Government of Bermuda Bermuda Shipping and Maritime Authority 2017 021 BERMUDA SHIPPING NOTICE Maintenance and Inspection of Fire Protection Systems, Appliances and Certain Emergency Equipment Ref: SOLAS

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply

More information

SPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM

SPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM 1. GENERAL SPECIFICATION 1.1 An Engineered Carbon Dioxide Fire Suppression System shall be installed to meet a minimum design concentration of %, by volume in all designated spaces/areas to be protected.

More information

COMPONENT MAINTENANCE MANUAL WITH ILLUSTRATED PARTS LIST

COMPONENT MAINTENANCE MANUAL WITH ILLUSTRATED PARTS LIST 98 Columbus Street, Pointe Claire, QC, Canada H9R 4K4 info@caspaerospace.com www.caspaerospace.com T: 514-630-7777 F: 514-630-9999 HAND PORTABLE AIRCRAFT FIRE EXTINGUISHERS 3.0 lb. Halon 1211 Part No.

More information

COMPONENT MAINTENANCE MANUAL

COMPONENT MAINTENANCE MANUAL MAINTENANCE INSTRUCTIONS WITH ILLUSTRATED PARTS LIST HALON 1/ 1.2/ 2.5 AIR TOTAL List of Portable Fire Extinguishers Part No. Type: 74-00 HAL 1.0 74-20 HAL 1.2 74-21 HAL 1.2 (LH) 74-22 HAL 1.2 (AF) 76-00

More information

F-CLASS MODEL M6L WET CHEMICAL FIRE EXTINGUISHER Installation, Operation, Recharge and Maintenance Manual

F-CLASS MODEL M6L WET CHEMICAL FIRE EXTINGUISHER Installation, Operation, Recharge and Maintenance Manual F-CLASS MODEL M6L WET CHEMICAL FIRE EXTINGUISHER Installation, Operation, Recharge and Maintenance Manual 008094 All fire extinguishers should be installed, inspected and maintained in accordance with

More information

Planned Preventative Maintenance Schedule. Fire Suppression PPM Schedule

Planned Preventative Maintenance Schedule. Fire Suppression PPM Schedule Planned Preventative Maintenance Schedule Fire Suppression PPM Schedule Support Planned and contracted maintenance services To ensure that data centre or building services are always operating to their

More information

Attachment 1. to ClassNK Technical Information No.TEC-0764 Malta Maritime Authority Date Revised 28 August 2008 Page 1 of 10 This Administration Requi

Attachment 1. to ClassNK Technical Information No.TEC-0764 Malta Maritime Authority Date Revised 28 August 2008 Page 1 of 10 This Administration Requi Subject Periodical Maintenance, Inspection and Testing for Fire Protection Systems, and Appliances and Compressed Gas Cylinders onboard Maltese Flagged Vessels (Partly Amended) To whom it may concern Technical

More information

CERTIFICATE OF FIRE APPROVAL

CERTIFICATE OF FIRE APPROVAL CERTIFICATE OF FIRE APPROVAL This is to certify that The product detailed below will be accepted for compliance with the applicable Lloyd s Register Rules and Regulations and with the International Convention

More information

ClassNK Technical Information No. TEC-0970 For any questions about the above, please contact: NIPPON KAIJI KYOKAI (ClassNK) Survey Department, Adminis

ClassNK Technical Information No. TEC-0970 For any questions about the above, please contact: NIPPON KAIJI KYOKAI (ClassNK) Survey Department, Adminis Subject Maintenance, inspection and test of Fire-Protection Systems and Appliances on board the Panama-registered ships To whom it may concern Technical Information No. TEC-0970 Date 31 October 2013 The

More information

IMO INTERPRETATIONS OF FIRE PROTECTION-RELATED PROVISIONS OF THE HSC CODE

IMO INTERPRETATIONS OF FIRE PROTECTION-RELATED PROVISIONS OF THE HSC CODE INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: 0171-735 7611 Fax: 0171-587 3210 Telex: 23588 IMOLDN G Ref. T4/4.01 IMO E MSC/Circ.911 4 June 1999 INTERPRETATIONS OF FIRE

More information

TOTALPAC2 Integrated Fire Protection System

TOTALPAC2 Integrated Fire Protection System TOTALPAC2 Integrated Fire Protection System Page 1 of 8 General 1. Applicable Standards The TOTALPAC2 Surefire complies with the following standards: - NFPA-13 Sprinkler Systems; - NFPA-15 Water Spray

More information

THÔNG BÁO KỸ THUẬT TÀU BIỂN TECHNICAL INFORMATION ON SEA-GOING SHIPS

THÔNG BÁO KỸ THUẬT TÀU BIỂN TECHNICAL INFORMATION ON SEA-GOING SHIPS VRTB.TI CỤC ĐĂNG KIỂM VIỆT NAM VIETNAM REGISTER ĐỊA CHỈ: 18 PHẠM HÙNG, HÀ NỘI ADDRESS: 18 PHAM HUNG ROAD, HA NOI ĐIỆN THOẠI/ TEL: +84 4 3 7684701 FAX: +84 4 3 7684779 EMAIL: vr-id@vr.org.vn WEB SITE: www.vr.org.vn

More information

automatic FiReFighTing SYSTeMS in PainT booths

automatic FiReFighTing SYSTeMS in PainT booths SPECIAL HAZARDS PROTECTION automatic FiReFighTing SYSTeMS in PainT booths hazard type The risks considered, according to existing regulations, are Class A risk: solids fire. Class B risk: fire of flammable

More information

COMPONENT MAINTENANCE MANUAL

COMPONENT MAINTENANCE MANUAL WITH ILLUSTRATED PARTS LIST HALON 1/ 1,2/ 2,5 AIR TOTAL List of Portable Fire Extinguishers Part No. Type: 74-00 HAL 1,0 74-20 HAL 1,2 74-21 HAL 1,2 (LH) 76-00 HAL 2,5 COMPONENT MAINTENANCE MANUAL TOTAL

More information

ENVIROPRESS CAN CRUSHER Model : EP005 / EP005HD

ENVIROPRESS CAN CRUSHER Model : EP005 / EP005HD ENVIROPRESS CAN CRUSHER Model : EP005 / EP005HD WARNING READ AND FOLLOW ALL INSTRUCTIONS AND SAFETY PRECAUTIONS BEFORE INSTALLING OR OPERATING THIS EQUIPMENT. KEEP THIS MANUAL READILY AVAILABLE FOR FUTURE

More information

AUTOMATIC FIREFIGHTING SYSTEMS IN PAINT BOOTHS

AUTOMATIC FIREFIGHTING SYSTEMS IN PAINT BOOTHS SPECIAL HAZARDS PROTECTION AUTOMATIC FIREFIGHTING SYSTEMS IN PAINT BOOTHS Hazard type The risks considered, according to existing regulations, are Class A risk: solids fire. Class B risk: fire of flammable

More information

FIre Extinguishers. K-GUARD Wet Chemical Fire Extinguishers Manual INSTALLATION 2014-DEC-29 REV. 03 PAGE 1 EXTINGUISHERS

FIre Extinguishers. K-GUARD Wet Chemical Fire Extinguishers Manual INSTALLATION 2014-DEC-29 REV. 03 PAGE 1 EXTINGUISHERS K-GUARD Wet Chemical K-GUARD K-Guard WET CHEMICAL Wet Chemical EXTINGUISHERS FIre Extinguishers INSTALLATION 2014-DEC-29 REV. 03 PAGE 1 Installation, OPERATION, Recharge, and Maintenance Manual 004327

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION FC 1801 GENERAL 1801.1 Scope. This chapter shall govern the design, installation, operation and maintenance of semiconductor fabrication facilities

More information

CertifiedSafetyPassion. CertifiedSafetyPassion. Distributors and UL AML

CertifiedSafetyPassion. CertifiedSafetyPassion. Distributors and UL AML CertifiedSafetyPassion SAFETY HI - TECH. Founded in 1990, Safety Hi-Tech is a customer-focused provider of innovative fire suppression solutions, focusing on Clean Agent Extinguishing Systems. Safety Hi-Tech

More information

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND 1. GENERAL SPECIFICATION 1.1 A pre-engineered, fixed pipe, automatic dry chemical fire suppression system shall be provided and installed for the hazard including work area, plenums and all exhaust ventilation

More information

WHEELED STORED PRESSURE

WHEELED STORED PRESSURE OWNERS SERVICE MANUAL NO. 19795 INSTALLATION, OPERATING & SERVICING INSTRUCTIONS All fire extinguishers should be installed, inspected and maintained in accordance with the National Fire Protection Association

More information

Service Requirements SEMI- ANNUAL ANNUALLY OTHER REF. REQUIREMENT

Service Requirements SEMI- ANNUAL ANNUALLY OTHER REF. REQUIREMENT 58 Fire protection equipment requires care and maintenance at scheduled intervals to assure it will operate properly and safely when needed. Only personnel who are trained and qualified to maintain the

More information

SPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM

SPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM 1. GENERAL SPECIFICATION 1.1. A total flooding, FM-200 fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in all designated

More information

Laboratories and Hazardous Materials. Company Overview

Laboratories and Hazardous Materials. Company Overview Laboratories and Hazardous Materials Don E. Contois, P.E. Sam Sinapi Company Overview R.W. Sullivan Engineering (RWS) was established in 1945 and currently has 95 employees. RWS is a full service engineering

More information

MARINE CIRCULAR MC-7/2011/1

MARINE CIRCULAR MC-7/2011/1 Singapore Operations Office: 10 Anson Road #25-16, International Plaza, Singapore 079903 Tel: (65) 6224 2345 Fax: (65) 6227 2345 Email: info@tvship.com Website: www.tvship.com 6/2018 MARINE CIRCULAR MC-7/2011/1

More information

Circular. Maintenance and Inspection of Fire-Protection Systems and Appliances

Circular. Maintenance and Inspection of Fire-Protection Systems and Appliances CCS Circular China Classification Society (2011)Circ. No.54 Total No.118(Rev.1) August 07, 2012 (Total pages: 12+10+5) To: Surveyors,auditors and relevant shipping companies Maintenance and Inspection

More information

ANSUL. Twin-Agent Fire Fighting/Securing Systems Specifications. Models 450/50-B, 450/100-B, 900/100-B INDEX SPECIFICATIONS

ANSUL. Twin-Agent Fire Fighting/Securing Systems Specifications. Models 450/50-B, 450/100-B, 900/100-B INDEX SPECIFICATIONS ANSUL Twin-Agent Fire Fighting/Securing Systems Specifications Models 450/50-B, 450/100-B, 900/100-B INDEX 1.0 GENERAL 1.1 References 1.2 Submittals 1.3 System Capabilities 1.4 Quality Control 1.5 Warranty,

More information

Safe, Effective, Environment-friendly

Safe, Effective, Environment-friendly IG-55 (Argon/Nitrogen) Safe, Effective, Environment-friendly Introduction With the phase out of the most commonly used but environmentally damaging Halon 1301 and CO 2 fire suppressant, inert gases are

More information

CORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS

CORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS CORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS FIRE EXTINGUISHER REQUIREMENTS 1. All commercial cooking operations require at least one 2A10BC rated (5 or 6 pound size) fire extinguisher.

More information

5.07 Air Replenishment Systems

5.07 Air Replenishment Systems 5.07 Air Replenishment Systems Reference: 2010 SFFC, Section 511.2 Definitions: CERTIFIED COMPRESSOR. A compressor used by a contractor for maintenance and testing of air replenishment systems that is

More information

STAR-MAX PROPANE GAS GRIDDLE

STAR-MAX PROPANE GAS GRIDDLE Star Manufacturing International Inc. 10 Sunnen Drive St. Louis, MO 63143 Phone: (314) 781-2777 Fax: (314) 781-3636 Installation and Operating Instructions 2M-Z3793 Rev. B 3/28/03 STAR-MAX PROPANE GAS

More information

Fire Protection for Cable Tunnels

Fire Protection for Cable Tunnels Fire Protection for Cable Tunnels Targeted protection November 2009 Details on fires in cable tunnels and how to suppress them using FIRETRACE automatic suppression 1 systems Background Information A fire

More information

A. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition.

A. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition. 1. GENERAL SPECIFICATION 1.1 A total flooding, FM-200 fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in all designated

More information

Seaward Products OWNER S MANUAL WATER HEATERS. Serial Number:

Seaward Products OWNER S MANUAL WATER HEATERS. Serial Number: Seaward Products WATER HEATERS OWNER S MANUAL Serial Number: IMPORTANT SAFETY INSTRUCTIONS WARNING When using electrical appliances, basic safety precautions to reduce the risk of fire, electrical shock,

More information

Fire, extreme heat, smoke, toxic fumes, noise, falling objects, uneven terrain, debris,

Fire, extreme heat, smoke, toxic fumes, noise, falling objects, uneven terrain, debris, Policy Sponsor: Assistant Vice President Facilities Management Approval Date: February 2010 Facilities Management Fire Extinguishers and Fighting Fires Safe Work Instructions Responsible Unit: Facilities

More information

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS 12 December 1996 Ref. T4/4.01 GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS 1 The Maritime Safety

More information

Contractor Worksheet Underground Fires Major Hazard Standard

Contractor Worksheet Underground Fires Major Hazard Standard WMC Environment, Health & Safety Management System Worksheet Major Hazard Standard MHS-02 DocsOpen Ref: 57267, 17/10/2001 Uncontrolled copy check web for latest revision Revision Reviewed Description of

More information

Twin-Agent Fire Fighting/Securing Systems Specifications

Twin-Agent Fire Fighting/Securing Systems Specifications Twin-Agent Fire Fighting/Securing Systems Specifications Models 450/50, 450/100, 900/100 & 1350/200 INDEX 1.0 GENERAL 1.1 References 1.2 Submittals 1.3 System Capabilities 1.4 Quality Control 1.5 Warranty,

More information

S a n F r a n c i s c o F i r e D e p a r t m e n t B u r e a u o f F i r e P r e v e n t i o n & I n v e s t i g a t i o n 1 of 8 P a g e

S a n F r a n c i s c o F i r e D e p a r t m e n t B u r e a u o f F i r e P r e v e n t i o n & I n v e s t i g a t i o n 1 of 8 P a g e 5.07 Air Replenishment Systems (2016) Reference: SFFC, Section 511.2. Purpose: The purpose of this bulletin is to describe the requirements for air replenishment systems intended to be used to fill firefighters'

More information

Only the Danish version is authentic Notice D II-2 N(2) 1 October 2002 CHAPTER II-2 N(2)

Only the Danish version is authentic Notice D II-2 N(2) 1 October 2002 CHAPTER II-2 N(2) Only the Danish version is authentic Notice D II-2 N(2) 1 October 2002 Technical regulation on the construction and equipment, etc. of passenger ships on domestic voyages CHAPTER II-2 N(2) Construction,

More information

SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection

SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection 1. GENERAL SPECIFICATION 1.1 A total flooding, Novec 1230 fluid, fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in

More information

OWNER'S SERVICE MANUAL NO INSPECTION, MAINTENANCE AND RECHARGE

OWNER'S SERVICE MANUAL NO INSPECTION, MAINTENANCE AND RECHARGE FOAM FIRE EXTINGUISHERS MODEL 254-6 LITER AFFF FOAM WITH SPRAY NOZZLE Model 250 2 ½ GAL.LON AFFF FOAM WITH ASPIRATED NOZZLE MODEL 252 2 ½ GAL.LON FFFP (ALCOHOL RESISTANT) FOAM WITH ASPIRATED NOZZLE OWNER'S

More information

OWNER'S OPERATION AND MAINTENANCE MANUAL

OWNER'S OPERATION AND MAINTENANCE MANUAL OWNER'S OPERATION AND MAINTENANCE MANUAL P/N 15064 Amerex Industrial Dry Chemical Fire Suppression System MODELS IS18ABC (18 lb. ABC) / IS35ABC (35 lb. ABC) / IS45ABC (45 lb. ABC) / Manufactured by: AMEREX

More information

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE GENERAL INDUSTRY SAFETY STANDARDS PART 8. PORTABLE FIRE EXTINGUISHERS

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE GENERAL INDUSTRY SAFETY STANDARDS PART 8. PORTABLE FIRE EXTINGUISHERS DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE GENERAL INDUSTRY SAFETY STANDARDS (By authority conferred on the director of the department of licensing and regulatory affairs by sections

More information

Basic Vehicle Fire Protection Manual

Basic Vehicle Fire Protection Manual Basic Vehicle Fire Protection Manual Basic Vehicle Fire Protection Manual TABLE OF CONTENTS Introduction... 3 System Operation...... 5 Component Overview.... 7 Operator Controls Control Panel.........

More information

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL Annex 2, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL Section 1 Application 1 The following new sentence is added to the end of paragraph 1.2:

More information

Specified Systems List

Specified Systems List Specified Systems List Index: SS 1 Automatic systems for fire suppression SS 2 Automatic or manual emergency warning systems for fire or other dangers SS 3 Electromagnetic or automatic doors or windows

More information

CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15

CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15 CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15 COMPACT PLUS 10 and 15 Litre Unvented Under and Over Sink Water Heater INSTALLATION AND USER GUIDE 1 DIMENSIONS 10L - 250mm 15L - 310mm 100mm 80mm 410mm

More information

ELECTRIC ASH CAN Model: CVACASH500 Part No:

ELECTRIC ASH CAN Model: CVACASH500 Part No: ELECTRIC ASH CAN Model: CVACASH500 Part No: 6471132 OPERATING & MAINTENANCE INSTRUCTIONS GC0614 INTRODUCTION Thank you for purchasing this electrically powered Ash Can which is designed for fast, easy

More information

Ariazone 601HD Refrigerant Recovery&Recycling unit

Ariazone 601HD Refrigerant Recovery&Recycling unit Automotive Air-Conditioning Service Equipment Ariazone 601HD Refrigerant Recovery&Recycling unit OPERATOR MANUAL 1 1. SAFETY FIRST! Important safety information's - Read this user manual carefully before

More information

installation & operating instructions

installation & operating instructions installation & operating instructions RGE 410 RA/RM-2D 822706106 MO-M 0740 INTRODUCTION We are pleased that you have chosen this refrigerator and hope you will derive much satisfaction from using it.

More information

MGN 453 (M) Maritime and Coastguard Agency Logo MARINE GUIDANCE NOTE

MGN 453 (M) Maritime and Coastguard Agency Logo MARINE GUIDANCE NOTE Maritime and Coastguard Agency Logo MARINE GUIDANCE NOTE MGN 453 (M) FIRE PROTECTION Fire Retardant Treatment for Floor Coverings, Suspended Textile Materials, Upholstery Materials and Bedding Components

More information

Moduflex. Desiccant Air Dryer P3TJA13A1AN - P3TJA13A7AN. USER GUIDE (Original Language) Dry Air System NL DE FR FI SV NO DA EL ES PT IT PL SK CS ET HU

Moduflex. Desiccant Air Dryer P3TJA13A1AN - P3TJA13A7AN. USER GUIDE (Original Language) Dry Air System NL DE FR FI SV NO DA EL ES PT IT PL SK CS ET HU Moduflex Dry Air System Desiccant Air P3TJA13A1AN - P3TJA13A7AN EN USER GUIDE (Original Language) NL DE FR FI SV NO DA EL ES PT IT PL SK CS ET HU LV LT RU SL TR MT CONTENTS 1 Safety Information...2 1.1

More information

Pizza Oven with Stand

Pizza Oven with Stand Pizza Oven with Stand Cooks up to 3 pizzas at a time Use to cook a variety of food Easy clean vitreous enamel interior Model No. P0104 Powerful 22MJ/h stainless steel burner Viewing window and temperature

More information

Getz Equipment Innovators 450 lb Dual Portable Dry Chemical Fill System

Getz Equipment Innovators 450 lb Dual Portable Dry Chemical Fill System Getz Equipment Innovators 450 lb Dual Portable Dry Chemical Fill System 1 Revised 11/18/10 2320 Lakecrest Drive, Pekin IL 61554 PH. (888) 747-4389 Fax (309) 495-0625 Website: www.getzequipment.com LIMITED

More information

KD Innovative extinguishing with Novec TM 1230 by 3M TM

KD Innovative extinguishing with Novec TM 1230 by 3M TM KD-1230 Innovative extinguishing with Novec TM 1230 by 3M TM KD-1230 fire extinguishing system The next generation in fixed fire protection is the fire extinguishing system KD-1230 engineered for use with

More information

WSU-TFREC Fire Safety Training

WSU-TFREC Fire Safety Training WSU-TFREC Fire Safety Training WSU-TFREC Locate the nearest exits, alarms and fire extinguishers to your work area Floor plans are available online: Overley Building http://www.tfrec.wsu.edu/pages/safety/overley_building_floor_plan

More information

ELECTRIC ASHCAN MODEL NO: ASHVAC1200 OPERATING & MAINTENANCE INSTRUCTIONS PART NO: ORIGINAL INSTRUCTIONS

ELECTRIC ASHCAN MODEL NO: ASHVAC1200 OPERATING & MAINTENANCE INSTRUCTIONS PART NO: ORIGINAL INSTRUCTIONS ELECTRIC ASHCAN MODEL NO: ASHVAC1200 PART NO: 6471133 OPERATING & MAINTENANCE INSTRUCTIONS ORIGINAL INSTRUCTIONS GC1216 INTRODUCTION Thank you for purchasing this CLARKE product which is designed for fast,

More information

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA TXV Coils for Manufactured Housing EMA NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance,

More information

OWNER S MANUAL. Models: Herkules Equipment Corporation 2760 Ridgeway Court Walled Lake, MI USA Fax

OWNER S MANUAL. Models: Herkules Equipment Corporation 2760 Ridgeway Court Walled Lake, MI USA Fax Part# 1000692 7/12/99 tn INSTRUCTIONS This manual contains important information concerning the installation and operation of the gun washers listed at the right. Read manual thoroughly and keep for future

More information

Space Saver. Installation and user manual SS3 SS5 SS7 SS9. Issue 001 September 2017 ENGLISH UK IRL SmithsEP.co.uk

Space Saver. Installation and user manual SS3 SS5 SS7 SS9. Issue 001 September 2017 ENGLISH UK IRL SmithsEP.co.uk Space Saver Installation and user manual SS3 SS5 SS7 SS9 Issue 001 September 2017 ENGLISH UK IRL SmithsEP.co.uk Contents Introduction 2 Declaration of conformity 3 Symbols used in this guide 3 Important

More information

26 June 2001 *** I:\CIRC\MSC\1007.DOC INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR

26 June 2001 *** I:\CIRC\MSC\1007.DOC INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: 020 7735 7611 Fax: 020 7587 3210 Telex: 23588 IMOLDN G IMO E Ref. T4/4.01 MSC/Circ.1007 26 June 2001 GUIDELINES FOR THE

More information

ariazone 601HD Refrigerant Recovery & Recycling Unit User's manual

ariazone 601HD Refrigerant Recovery & Recycling Unit User's manual ariazone 601HD Refrigerant Recovery & Recycling Unit User's manual Model: Ariazone 601 HD Serial No: 1 1. SAFETY FIRST! Important safety information's - Read this user manual carefully before operating

More information

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting life and

More information

DRY CHEMICAL AND CLEAN AGENT HAND PORTABLE FIRE EXTINGUISHERS

DRY CHEMICAL AND CLEAN AGENT HAND PORTABLE FIRE EXTINGUISHERS DRY CHEMICAL AND CLEAN AGENT HAND PORTABLE FIRE EXTINGUISHERS OPERATION, RECHARGE, INSPECTION, AND MAINTENANCE MANUAL 000769 One Stanton Street / Marinette, WI 54143-2542, USA / +1-715-735-7411 Copyright

More information

MODEL V-BB SPECIFIC APPLICATION TECHNICAL DATA

MODEL V-BB SPECIFIC APPLICATION TECHNICAL DATA Page 1 of 15 1. DESCRIPTION The Model V-BB (Back to Back) is a Specific Application Attic Sprinkler designed to provide superior fire protection in combustible and non-combustible sloped attic spaces when

More information

Evacuation Fire Safety Program

Evacuation Fire Safety Program Evacuation Fire Safety Program Emergency Procedures Provisions must be made for prompt medical attention in case of serious injury. The location and phone number of emergency service providers will be

More information

Safety Policy and Procedure

Safety Policy and Procedure Safety Policy and Procedure Policy Number: 007 Authorized By: The Cianbro Companies Alan Burton Title: Watch for Fire, Smoke and Sparks Effective Date: 02/01/93 Page 1 of 5 1 Status 1.1 Update of existing

More information

freedom residential Upright sprinkler vk467 (k4.9)

freedom residential Upright sprinkler vk467 (k4.9) Page 1 of 6 1. DESCRIPTION Viking Freedom Residential Upright Sprinkler VK467 is a small, thermosensitive, glassbulb residential sprinkler available in several different finishes and temperature ratings

More information

WORKPLACE INSPECTION CHECKLIST FOR LABORATORY ENVIRONMENTS

WORKPLACE INSPECTION CHECKLIST FOR LABORATORY ENVIRONMENTS WORKPLACE INSPECTION CHECKLIST FOR LABORATORY ENVIRONMENTS Standard OHS Workplace Inspection Checklist Review Date: Next Review: Inspection Site: Inspection Team: Contacts: Written Laboratory Safety Policies/Procedures/Records

More information

Australian Standard. Gaseous fire extinguishing systems AS (Incorporating Amendment No. 1) AS

Australian Standard. Gaseous fire extinguishing systems AS (Incorporating Amendment No. 1) AS AS 4214 2002 (Incorporating Amendment No. 1) AS 4214 2002 Australian Standard Gaseous fire extinguishing systems This Australian Standard was prepared by Committee FP-011, Gaseous Fire Protection. It was

More information

Notice on the implementation of the amendments to the FSS Code in resolution MSC.339(91)

Notice on the implementation of the amendments to the FSS Code in resolution MSC.339(91) C C S 通函 Circular China Classification Society (2013) Circ.111 /Total No.397 25/07/2013 (total pages:18) To relevant departments of CCS Headquarters, Shanghai Rules and Research Institute, plan approval

More information

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required* 1.0 Description of Services Required: Revised March 2015 Fire Alarm Systems Verification Schedule I(A) Services *Manditory Site visit required* Perform the annual fire alarm system and sprinkler system

More information

SPECIFICATION: ARGONITE Engineered Fire Suppression System

SPECIFICATION: ARGONITE Engineered Fire Suppression System 1. GENERAL SPECIFICATION 1.1 A total flooding, clean agent, fire suppression system, filled with Argonite agent shall be installed to meet a minimum design concentration of %, by volume in all designated

More information

WET & DRY VACUUM CLEANERS

WET & DRY VACUUM CLEANERS WET & DRY VACUUM CLEANERS MODEL NO: CCVAC20SS, CVAC25SS & CVAC30SSR PART NO: 6471105, 6471110 & 6471120 OPERATING & MAINTENANCE INSTRUCTIONS GC0114 INTRODUCTION Thank you for selecting this VAC KING Vacuum

More information

ODS & SGG Alternatives for the Fire Protection Industry 2018

ODS & SGG Alternatives for the Fire Protection Industry 2018 Fire Protection Industry (ODS & SGG) Board www.fpib.com.au Fact Sheet ODS & SGG Alternatives for the Fire Protection Industry 2018 The Australian Government is committed to reducing emissions of ozone

More information

FIRE SUPPRESSION SYSTEM

FIRE SUPPRESSION SYSTEM FIRE SUPPRESSION SYSTEM An effective fire suppression systems work fundamentally in three ways; The corner stone has to be an efficient means of early warning/detection. Followed by either an Oxygen reduction

More information

SERVICE MANUAL (v1) UL / ULC. WET CHEMICAL HAND PORTABLE RESTAURANT KITCHEN FIRE EXTINGUISHERS Model: SF-6LK / WBDL-6LK

SERVICE MANUAL (v1) UL / ULC. WET CHEMICAL HAND PORTABLE RESTAURANT KITCHEN FIRE EXTINGUISHERS Model: SF-6LK / WBDL-6LK STRIKE FIRST CORPORATION AKC SERVICE MANUAL (v1) UL / ULC WET CHEMICAL HAND PORTABLE RESTAURANT KITCHEN FIRE EXTINGUISHERS Model: SF-6LK / WBDL-6LK All fire extinguishers should be installed, inspected

More information

Fundamental Principles of Air Conditioners for Information Technology

Fundamental Principles of Air Conditioners for Information Technology Fundamental Principles of Air Conditioners for Information Technology By Tony Evans White Paper #57 Revision 2 Executive Summary Every Information Technology professional who is responsible for the operation

More information

Attachment 1. to ClassNK Technical Information No. TEC-1077 Isle of Man Ship Registry Manx Shipping Notice SOLAS II-2 The Maintenance and inspection o

Attachment 1. to ClassNK Technical Information No. TEC-1077 Isle of Man Ship Registry Manx Shipping Notice SOLAS II-2 The Maintenance and inspection o Subject Periodical inspection, maintenance and tests of fire extinguishing system etc. on board for the Isle of Man flagged ships To whom it may concern Technical Information No. TEC-1077 Date 20 July

More information

PRODUCT MANUAL FIRE EXTINGUISHER

PRODUCT MANUAL FIRE EXTINGUISHER PRODUCT MANUAL FIRE EXTINGUISHER Clean Agent (FE-36) 2, 4 & 6 Kg Capacity Kanadia Fyr Fyter Pvt Ltd Laxminagar, Ghatkopar (E), Mumbai -400 075 Page 1 of 5 INTRODUCTION [KANEX FIRE EXTINGUISHER] Store Pressure

More information

The Next Generation of Foam Fire Suppression. Automatic CAF Fire hose reel system FEATURES

The Next Generation of Foam Fire Suppression. Automatic CAF Fire hose reel system FEATURES Fire hose reel system The first automatic CAF, fire hose reel system FEATURES The Automatic CAF Fire Hose Systems are ideal for firefighting needs in locations that require foam as a fire fighting agent.

More information

***DRAFT - NOT FOR FILING***

***DRAFT - NOT FOR FILING*** ACTION: Original ***DRAFT - NOT FOR FILING*** DATE: 09/29/2017 1:14 PM 1301:7-7-27 Semiconductor fabrication facilities. (A) Section 2701 General (1) 2701.1 Scope. Semiconductor fabrication facilities

More information

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

Some of these procedures need to be performed to conform to requirements of the Clean Air Act. Leak Detection, Recovery, Evacuation and Charging Four basic service procedures used to repair and maintain a mechanical refrigeration system are leak detection, evacuation, recovery, and refrigerant charging.

More information

FM-200 In-Cabinet Series

FM-200 In-Cabinet Series 1. GENERAL SPECIFICATION 1.1 A total flooding, In-Cabinet fire suppression system, employing FM-200 superpressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by

More information

Business License Pre-inspection Checklist

Business License Pre-inspection Checklist Business License Pre-inspection Checklist August, 2016 Alberta Fire Code business license pre-inspection and annual checklist This checklist provides business owners with Alberta Fire Code requirements

More information

HIGH PERFORMANCE HEAVY DUTY INDUSTRIAL STORED PRESSURE

HIGH PERFORMANCE HEAVY DUTY INDUSTRIAL STORED PRESSURE HIGH PERFORMANCE HEAVY DUTY INDUSTRIAL STORED PRESSURE ABC (AMMONIUM PHOSPHATE BASE),Regular (SODIUM BICARBONATE BASE), PURPKE K (POTASSIUM BICARBONATE BASE) OWNERS SERVICE MANUAL NO. 0566 INSTALLATION,

More information

Committee on NFPA 51A

Committee on NFPA 51A Committee on M E M O R A N D U M TO: FROM: NFPA Technical Committee on Industrial and Medical Gases Patti Mucci, Administrative Assistant DATE: May 6, 2010 SUBJECT: ROC Letter Ballot The ROC letter ballot

More information

DC200 Digital Dispenser Operating Manual

DC200 Digital Dispenser Operating Manual DC200 Digital Dispenser Operating Manual 2015 Fisnar Phone: (973) 646-5044 E-mail: info@fisnar.com Table of Contents Product Safety Statements 4 Specifications 6 Accessories 6 External Controls 7 Machine

More information

South African Maritime Safety Authority

South African Maritime Safety Authority South African Maritime Safety Authority Ref: SM6/5/2/1 Date: 20 July 2016 Marine tice. 29 of 2016 South African Maritime Code of Practice for Marine Fire Service Stations the SAMFAS Code TO MARINE FIRE

More information