All of the lift stations visited appeared to be clean and well maintained with working alarms and lights.
|
|
- Toby Beverly Fletcher
- 5 years ago
- Views:
Transcription
1 June 15, 2011 Ms. Melba Verke, Mayor City of Alicia P.O. Box 132 Alicia, AR RE: Sanitary Sewer Overflow Inspection AFIN: NPDES Permit No.: AR Dear Ms. Verke: On May 18, 2011, I performed an inspection of the waste water collection system in accordance with the provisions of the Federal Clean Water Act, the Arkansas Water and Air Pollution Control Act, and the regulations promulgated thereunder. This inspection revealed that your facility appeared to be following the terms of the permit: All of the lift stations visited appeared to be clean and well maintained with working alarms and lights. If I can be of any assistance, please contact me at Sincerely, Mike Kennedy District 11 Field Inspector Water Division cc: Water Division Enforcement Branch Water Division Permits Branch
2 Form Approved OMB No UNITED STATES ENVIRONMENTAL PROTECTION AGENCY Washington, D.C NPDES Compliance Inspection Report Section A: National Data System Coding Transaction Code NPDES Yr/Mo/Day Inspec. Type Inspector Fac. Type 1 N A R V 19 S 20 1 A F I N Inspection Work Days Remarks Facility Evaluation Rating BI QA Reserved N 71 N 72 N Section B: Facility Data Name and Location of Facility Inspected (For industrial users discharging to POTW, also include POTW name and NPDES permit number) Alicia Wastewater Treatment Plant East of city center off Highway #230 Alicia, AR (Lawrence County) Entry Time/Date 1215 / Exit Time/Date 1400 / Permit Effective Date April 1, 2007 Permit Expiration Date May 31, 2012 Name(s) of On-Site Representative(s)/Title(s)/Phone and Fax Number(s) Bob Lee / Plant Operator / Cell: Name, Address of Responsible Official/Title/Phone and Fax Number Melba Verke / Mayor /Office: P.O. Box 132 Alicia, AR Yes Contacted No Other Facility Data N35º53'27.134" W-91º Section C: Areas Evaluated During Inspection (S = Satisfactory, M = Marginal, U = Unsatisfactory, N = Not Evaluated) N Permit N Flow Measurement N Operations & Maintenance N Sampling N Records/Reports N Self-Monitoring Program N Sludge Handling/Disposal N Pollution Prevention N Facility Site Review N Compliance Schedules N Pretreatment N Multimedia N Effluent/Receiving Waters N Laboratory N Storm Water N Other: Section D: Summary of Findings/Comments (Attach additional sheets if necessary) No violations were noted during the inspection. Refer to attached letter and inspection report for a listing and explanation of findings. Name(s) and Signature(s) of Inspector(s) Mike Kennedy Agency/Office/Telephone/Fax AR Dept. of Environmental Quality-Batesville office / Fax Date May 26, 2011 Signature of Reviewer Agency/Office/Phone and Fax Numbers Date NPDES Report Page 2
3 COLLECTION SYSTEM INSPECTION AND OVERALL RATING PROVIDE A BRIEF DESCRIPTION OF THE COLLECTION SYSTEM: Alicia WWTP has a gravity collection system with 4 lift stations and force mains pumping to gravity lines finally to Sand Bed Filter System POPULATION SERVED/NUMBER OF RESIDENTIAL AND COMMERCIAL CONNECTIONS: Approx. 175 people Approx. 100 Residential connections FEET OF SEWER SYSTEM: Approx. 4,500 feet of gravity sewer and Approx. 4,000 feet of force mains through 4-6 inch pipes AGE OF SYSTEM: From Approx. 28 years old to newer DOES THE SYSTEM EXPERIENCE PROBLEMS DURING DRY OR WET WEATHER (EXPLAIN): Inflow and Infiltration IS THERE A SYSTEM IN PLACE FOR REPORTING SSOS TO ADEQ (DESCRIBE): All staff report SSOs to supervisor who reports SSOs to ADEQ within 24 hours or each occurrence. ARE ALL SSOs REPORTED REGARDLESS OF SIZE: HAVE SSOs REACHED WATERS OF THE STATE (LIST DATE AND LOCATION OF EACH): Not in the previous 18 months PUMP STATIONS NUMBER OF PUMP STATIONS IN SYSTEM: 4 NUMBER WITH BACKUP POWER: All Lift stations have hookups for Auxiliary Pumps HOW OFTEN ARE PUMP STATIONS INSPECTED/MONITORED: All pump stations are inspected daily ARE MAINTENANCE RECORDS AND/OR OPERATOR LOGS KEPT: Yes ADEQUATE INVENTORY OF SPARE PARTS: Yes TYPE OF REMOTE ELECTRONIC MONITORING USED (I.E. SCADA OR AUTO DIALERS): None BRIEF SUMMARY OF EMERGENCY PROCEDURES: Inventory of spare parts kept in case of breakdowns. Alicia WWTP has hookups for Auxiliary Pumps for all lift stations. NUMBER OF PUMP STATIONS VISITED DURING INSPECTION (SEE ATTACHED CHECKLISTS FOR EACH): 4 SATELLITE SYSTEMS DOES THE COLLECTION SYSTEM RECEIVE FLOW FROM SATELLITE SYSTEMS: No BRIEFLY DESCRIBE THE SATELLITE SYSTEM: ANY KNOWN PROBLEMS WITH SATELLITE SYSTEM NAME, ADDRESS AND PHONE NUMBER OF PERSON RESPONSIBLE FOR SATELLITE SYSTEM: NPDES Report Page 3
4 PUMP STATION VISIT (COMPLETE A SEPARATE CHECKLIST FOR EACH PUMP STATION VISITED) GENERAL INFORMATION AND OVERALL EVALUATION NAME AND/OR LOCATION OF PUMP STATION: Lift Station #1 on West 1 st Street in Alicia NUMBER OF PUMPS: 2 NUMBER AND SIZE OF PUMPS APPEARS ADEQUATE: EVIDENCE OF RECENT OVERFLOWS OR HIGH LEVELS: NUMBER OPERATIONAL: 2 (Submersible) GENERAL OPERATION AND MAINTENANCE CLEAN AND WELL MAINTAINED WITH MINIMAL STORAGE OF UNRELATED EQUIPMENT: GATES/DOORS/HATCHES/LIDS/ETC. LOCKED TO PREVENT UNAUTHORIZED ACCESS AND/OR TAMPERING: WET WELLS, SUMPS AND PITS ADEQUATELY COVERED, GRATED OR OTHERWISE PROTECTED: ELECTRICAL CONTROLS COVERS CONDUIT AND EQUIPMENT PROPERLY INSTALLED AND MAINTAINED: GUARDS AND SHIELDS IN PLACE AROUND MOVING EQUIPMENT (BELTS, PULLEYS, DRIVESHAFTS, ETC.) : (Submersible pumps) ADEQUATE VENTILATION TO PREVENT EXCESSIVE CONDENSATION AND/OR GASES AND FUMES: ADEQUATE LIGHTING FOR ROUTINE INSPECTION/MAINTENANCE (No building) SEALS, VALVES AND PACKING ADEQUATELY MAINTAINED TO PREVENT LEAKS (Submersible pumps) MINIMAL ACCUMULATION OF GREASE AND SOLIDS IN WET WELLS: BACKUP POWER AND ALARMS PROVISIONS FOR GENERATOR AND/OR EMERGENCY TRANSFER PUMP: Yes (Has hookups for Auxiliary Pumps) AUDIBLE/VISUAL ALARM WITH EMERGENCY CONTACT INFORMATION POSTED: (Lights and Alarms) SCADA SYSTEM (LIST PARAMETERS MONITORED): NPDES Report Page 4
5 PUMP STATION VISIT (COMPLETE A SEPARATE CHECKLIST FOR EACH PUMP STATION VISITED) GENERAL INFORMATION AND OVERALL EVALUATION NAME AND/OR LOCATION OF PUMP STATION: Lift Station #2 On Highway #230 in Alicia NUMBER OF PUMPS: 2 NUMBER AND SIZE OF PUMPS APPEARS ADEQUATE: EVIDENCE OF RECENT OVERFLOWS OR HIGH LEVELS: NUMBER OPERATIONAL: 2 (Submersible) GENERAL OPERATION AND MAINTENANCE CLEAN AND WELL MAINTAINED WITH MINIMAL STORAGE OF UNRELATED EQUIPMENT: GATES/DOORS/HATCHES/LIDS/ETC. LOCKED TO PREVENT UNAUTHORIZED ACCESS AND/OR TAMPERING: WET WELLS, SUMPS AND PITS ADEQUATELY COVERED, GRATED OR OTHERWISE PROTECTED: ELECTRICAL CONTROLS COVERS CONDUIT AND EQUIPMENT PROPERLY INSTALLED AND MAINTAINED: GUARDS AND SHIELDS IN PLACE AROUND MOVING EQUIPMENT (BELTS, PULLEYS, DRIVESHAFTS, ETC.) : (Submersible pumps) ADEQUATE VENTILATION TO PREVENT EXCESSIVE CONDENSATION AND/OR GASES AND FUMES: ADEQUATE LIGHTING FOR ROUTINE INSPECTION/MAINTENANCE: (No building) SEALS, VALVES AND PACKING ADEQUATELY MAINTAINED TO PREVENT LEAKS: (Submersible pumps) MINIMAL ACCUMULATION OF GREASE AND SOLIDS IN WET WELLS: BACKUP POWER AND ALARMS PROVISIONS FOR GENERATOR AND/OR EMERGENCY TRANSFER PUMP: Yes (Has hookups for Auxiliary Pumps) AUDIBLE/VISUAL ALARM WITH EMERGENCY CONTACT INFORMATION POSTED: (Lights and Alarms) SCADA SYSTEM (LIST PARAMETERS MONITORED): NPDES Report Page 5
6 PUMP STATION VISIT (COMPLETE A SEPARATE CHECKLIST FOR EACH PUMP STATION VISITED) GENERAL INFORMATION AND OVERALL EVALUATION NAME AND/OR LOCATION OF PUMP STATION: Lift Station #3 On 1 st Street in Alicia NUMBER OF PUMPS: 2 NUMBER AND SIZE OF PUMPS APPEARS ADEQUATE: EVIDENCE OF RECENT OVERFLOWS OR HIGH LEVELS: NUMBER OPERATIONAL: 2 (Submersible) GENERAL OPERATION AND MAINTENANCE CLEAN AND WELL MAINTAINED WITH MINIMAL STORAGE OF UNRELATED EQUIPMENT: GATES/DOORS/HATCHES/LIDS/ETC. LOCKED TO PREVENT UNAUTHORIZED ACCESS AND/OR TAMPERING: WET WELLS, SUMPS AND PITS ADEQUATELY COVERED, GRATED OR OTHERWISE PROTECTED: ELECTRICAL CONTROLS COVERS CONDUIT AND EQUIPMENT PROPERLY INSTALLED AND MAINTAINED: GUARDS AND SHIELDS IN PLACE AROUND MOVING EQUIPMENT (BELTS, PULLEYS, DRIVESHAFTS, ETC.) : (Submersible pumps) ADEQUATE VENTILATION TO PREVENT EXCESSIVE CONDENSATION AND/OR GASES AND FUMES: ADEQUATE LIGHTING FOR ROUTINE INSPECTION/MAINTENANCE: (No building) SEALS, VALVES AND PACKING ADEQUATELY MAINTAINED TO PREVENT LEAKS: (Submersible pumps) MINIMAL ACCUMULATION OF GREASE AND SOLIDS IN WET WELLS: BACKUP POWER AND ALARMS PROVISIONS FOR GENERATOR AND/OR EMERGENCY TRANSFER PUMP: Yes (Has hookups for Auxiliary Pumps) AUDIBLE/VISUAL ALARM WITH EMERGENCY CONTACT INFORMATION POSTED: (Lights and Alarms) SCADA SYSTEM (LIST PARAMETERS MONITORED): NPDES Report Page 6
7 PUMP STATION VISIT (COMPLETE A SEPARATE CHECKLIST FOR EACH PUMP STATION VISITED) GENERAL INFORMATION AND OVERALL EVALUATION NAME AND/OR LOCATION OF PUMP STATION: Lift Station #4 On County Road #556 at Alicia NUMBER OF PUMPS: 2 NUMBER AND SIZE OF PUMPS APPEARS ADEQUATE: EVIDENCE OF RECENT OVERFLOWS OR HIGH LEVELS: NUMBER OPERATIONAL: 2 (Submersible) GENERAL OPERATION AND MAINTENANCE CLEAN AND WELL MAINTAINED WITH MINIMAL STORAGE OF UNRELATED EQUIPMENT: GATES/DOORS/HATCHES/LIDS/ETC. LOCKED TO PREVENT UNAUTHORIZED ACCESS AND/OR TAMPERING: WET WELLS, SUMPS AND PITS ADEQUATELY COVERED, GRATED OR OTHERWISE PROTECTED: ELECTRICAL CONTROLS COVERS CONDUIT AND EQUIPMENT PROPERLY INSTALLED AND MAINTAINED: GUARDS AND SHIELDS IN PLACE AROUND MOVING EQUIPMENT (BELTS, PULLEYS, DRIVESHAFTS, ETC.) : (Submersible pumps) ADEQUATE VENTILATION TO PREVENT EXCESSIVE CONDENSATION AND/OR GASES AND FUMES: ADEQUATE LIGHTING FOR ROUTINE INSPECTION/MAINTENANCE: (No building) SEALS, VALVES AND PACKING ADEQUATELY MAINTAINED TO PREVENT LEAKS: (Submersible pumps) MINIMAL ACCUMULATION OF GREASE AND SOLIDS IN WET WELLS: BACKUP POWER AND ALARMS PROVISIONS FOR GENERATOR AND/OR EMERGENCY TRANSFER PUMP: Yes (Has hookups for Auxiliary Pumps) AUDIBLE/VISUAL ALARM WITH EMERGENCY CONTACT INFORMATION POSTED: (Lights and Alarms) SCADA SYSTEM (LIST PARAMETERS MONITORED): NPDES Report Page 7
8 Water Division NPDES Photographic Evidence Sheet Location: Lift Station #1 on West 1 st Street in Alicia (Lawrence County) Photographer: Mike Kennedy Witness: Bobby Lee & Heath Vaughan Photo # 1 Of 4 Date: Time: 1217 Description: A view of the lift station. It had working lights, alarms and was locked. Photographer: Mike Kennedy Witness: Bobby Lee & Heath Vaughan Photo # 2 Of 4 Date: Time: 1202 Description: A view of Lift Station #2 on Highway #230. It had working alarms, lights and was locked. NPDES Report Page 8
9 Water Division NPDES Photographic Evidence Sheet Location: Lift Station #3 on 1 st Street in Alicia (Lawrence County) Photographer: Mike Kennedy Witness: Bobby Lee & Heath Vaughan Photo # 3 Of 4 Date: Time: 1217 Description: A view of the lift station. It had working lights, alarms and was locked. Photographer: Mike Kennedy Witness: Bobby Lee & Heath Vaughan Photo # 4 Of 4 Date: Time: 1202 Description: A view of Lift Station #4 on Co. Rd. #556. It had working alarms, lights and was locked. NPDES Report Page 9
For additional information you may contact the Enforcement Branch by telephone at or by fax at
March 16, 2012 Terry McGinister, General Manager 702 Cherry Street Helena, Arkansas 72342 RE: Sanitary Sewer Collection System AFIN: 54-00083 NPDES Permit No.: AR0043389 Dear Mr. McGinister: On March 13,
More informationWATER DIVISION INSPECTION REPORT
Inspection Report: City of Camden, Water Utility, AFIN: 52-00073, Permit #: AR0022365 WATER DIVISION INSPECTION REPORT AFIN: 52-00073 PERMIT #: AR0022365 COUNTY: 52 Ouachita PDS #: 077614 MEDIA: WN GPS
More informationWATER DIVISION INSPECTION REPORT
FACILITY INFORMATION NAME: Heber Springs Wastewater Treatment Plant LOCATION: 1174 Bypass Rd CITY: Heber Springs, AR RESPONSIBLE OFFICIAL NAME: / TITLE Kent Latch / General Manager COMPANY: Heber Springs
More informationInspection Report: Berryville Collection System, AFIN: , Permit #: AR FACILITY TYPE: 1 - Municipal
FACILITY INFORMATION NAME: Berryville Collection System LOCATION: CITY: Berryville RESPONSIBLE OFFICIAL NAME: / TITLE Honorable Tim McKinney / Mayor COMPANY: City of Berryville MAILING ADDRESS: P.O. Box
More informationWATER DIVISION INSPECTION REPORT
FACILITY INFORMATION NAME: Rogers Pollution Cont. Fac. LOCATION: 4300 Rainbow Road CITY: Rogers RESPONSIBLE OFFICIAL NAME: / TITLE Earl Rausch / Utility Superintendent COMPANY: City of Rogers MAILING ADDRESS:
More informationInspection Report: Cave City WWTP - Cypress Ln Lift Station, AFIN: , Permit #: AR FACILITY TYPE: 1 - Municipal
FACILITY INFORMATION NAME: Cave City WWTP - Cypress Ln Lift Station LOCATION: Cypress Lane CITY: Cave City, AR RESPONSIBLE OFFICIAL NAME: / TITLE Jim Smith / Public Works Director COMPANY: City of Cave
More informationRE: Quarterly Inspection conducted on September 6, 2017 AFIN Permit Number 0180-SG-WTX
Document ID 099278 September 25, 2017 Ms. Robyn Reed Boston Mountain RSWMD 11398 Bond Road Prairie Grove, AR 72753 RE: Quarterly Inspection conducted on September 6, 2017 AFIN 72-00778 Permit Number 0180-SG-WTX
More informationINFLOW & INFILTRATION REPORT
INFLOW & INFILTRATION REPORT The City of Cameron owns a 1.6 MGD, oxidation ditch treatment facility, located in DeKalb County, Missouri. The treatment facility operates under Permit # MO-0104299. Daily
More informationVillage of Sloan Smoke Testing September 2017
Village of Sloan Smoke Testing September 2017 What is Smoke Testing? Smoke testing is used to detect any water other than wastewater entering the sanitary sewer system. This water could be coming from
More informationStormwater Program Robert Patterson (919) 807-6369 E-mail: robert.patterson@ncdenr.gov Division of Energy, Mining, and land Resources Stormwater Permitting Unit 1612 Mail Service Center Raleigh NC 27699-1612
More informationFats, Oils and Grease Program (FOG)
Fats, Oils and Grease Program (FOG) SECTION A GENERAL INFORMATION 1. Facility Name: 2. Facility Street Address: City: State: Zip: Phone Number: Fax Number: 3. Business Mailing Address: (if different from
More informationEMERGENCY INFORMATION
EMERGENCY INFORMATION It is important for the water system users to have accurate information regarding the water system. They also need the manager s contact information, including address and phone number.
More informationKeeping. Fats, Oils, and. Grease. Out of the Sewer
Keeping Fats, Oils, and Grease Out of the Sewer Questions and Answers for Food Service Establishments regarding Fats, Oil, and Grease and Grease Removal Devices City of Paso Robles, Wastewater Division,
More information168 Spotnap Road Charlottesville, VA Tel (434) Fax (434)
Re: Fats, Oils and Grease (FOG) Abatement Program Dear Restaurant/Food Service Facility Manager: The Albemarle County Service Authority (ACSA) prides itself on maintaining the general public health of
More informationSmall Business Assistance Program Metal Finishers Compliance Checklist
Small Business Assistance Program Metal Finishers Compliance Checklist 1 Company Information Business Representative Present for Assessment: Date: Company Name: Physical Address: City: Mailing Address:
More information1. Researchers are familiar with the location and contents of: The lab s Chemical Hygiene Plan YES NO
Safety Self-Inspection Checklist for Laboratories One Inspection form per Laboratory Room DATE: BUILDING: ROOM: INSPECTOR: Professor Inspector s Signature Professor s Signature: Answer each question by
More informationJoseph Florio, Commissioner of Pub. Works Tel
Bob Calderone, Supervisor Matt Calderone, Asst. Supervisor Two Systems The Township of Union has two separate sewage systems. One is for storm water and one is for sanitary waste. The sanitary system which
More informationGuidelines for the Sanitary Sewer Evaluation Survey (SSES) Report PLAN A
Guidelines for the Sanitary Sewer Evaluation Survey (SSES) Report PLAN A 2 nd Cycle Report Due November 12, 2012 Revision 11/05/2015 wps-pa Report Cover Letter Requirements - Sample SSES PLAN A 2nd CYCLE
More informationFats, Oils & Grease (FOG)
Fats, Oils & Grease (FOG) FOOD SERVICE ESTABLISHMENT (FSE) Compliance Assistance Program Proper disposal of fats, oils and grease protects your business, public health and the environment. Compliance Assistance
More informationLIMITED ENVIRONMENTAL REVIEW
LIMITED ENVIRONMENTAL REVIEW A. Project Identification Project Name: Montpelier CSO Phase V WPCLF# CS390624-0006 Address: Kevin Brooks, Village Administrator 211 North Jonesville St. P.O. Box 148 Montpelier,
More informationSecure Residence Initiative ARLINGTON POLICE DEPARTMENT CRIME PREVENTION UNIT
Secure Residence Initiative ARLINGTON POLICE DEPARTMENT CRIME PREVENTION UNIT Does your homeowner s insurance company offer a discount when you invest in security improvements for your residence? Chapter
More informationAccess Controls for High Radiation Areas NISP-RP-05
NUCLEAR INDUSTRY STANDARD PROCESS Radiological Protection NISP-RP-05 Effective Date: 06/12/2017 This is an industry document for standardizing radiation protection processes used by supplemental radiation
More informationDesign Assessment Checklists for Ponds/ Wetlands
Objectives This checklist can be used by the organisation approving the drainage scheme (drainage approving body) to help assess submissions for drainage approval. This checklist is aimed at providing
More informationOHIO UNIVERSITY RADIATION SAFETY REVIEW
Appendix 29 OHIO UNIVERSITY RADIATION SAFETY REVIEW (Refer to Annual Radiation Safety Report Summary for comments on circled items.) I. LICENSE CONDITIONS 1. Expiration date of license: 2. Were license
More informationSouth Davis Metro Fire Agency
Agency Proudly Serving the Communities of Bountiful - Centerville - Davis County - North Salt Lake - West Bountiful - Woods Cross Fire Prevention Division Dear Business Owner: We are committed to the safety
More informationFLORIDA INSTITUTE OF TECHNOLOGY DEPARTMENT OF CHEMISTRY SAFETY MANUAL
FLORIDA INSTITUTE OF TECHNOLOGY DEPARTMENT OF CHEMISTRY SAFETY MANUAL INTRODUCTION Safety is important to all members of the Florida Institute of Technology community. The Florida Tech Department of Chemistry
More informationLIFT STATION INSPECTION & ASSESSMENT
David E. Koberlein, PE, GISP Burgess & Niple, Inc. LIFT STATION INSPECTION & ASSESSMENT Presentation Outline Why Perform Lift Station Assessments System Components and What to Look For What to do with
More informationProgram Introduction and Policy 1. Frequently Asked Questions 2. Device Maintenance..3. Best Management Practices...4
Carmel Utilities, in accordance with the National Pretreatment Program set forth by E.P.A. regulations (40 CFR 403), has hereby enacted a program for the controlling of Fats, Oils, and Grease discharges
More informationTesting the System. Battery Test. Dialer Test. Fire Drill Test (Code + [#] + 69) One-Man Fire Walk-Test (Code + [#] + 68)
F A 1 7 0 0 c Testing the System Battery Test When AC power is present, the FA1700C runs a brief battery test every 60 seconds to determine if there is a battery connected, and runs an extended battery
More informationI. Best Management Practices (BMPs) to Prevent Blockages in the Sanitary Sewer System
BMP Train kitchen staff and other employees about how they can help ensure BMPs are implemented. Post "No Grease" signs above sinks and on the front of dishwashers. I. Best Management Practices (BMPs)
More informationCITY OF HOLLY SPRINGS STORMWATER UTILITY FREQUENTLY ASKED QUESTIONS
CITY OF HOLLY SPRINGS STORMWATER UTILITY FREQUENTLY ASKED QUESTIONS GENERAL What is a Stormwater Utility and why is it needed in Holly Springs? A Stormwater Utility is an entity responsible for the daily
More informationWEST VIRGINIA STATE BOARD OF LANDSCAPE ARCHITECTS
Mailing address: West Virginia State Board of Landscape Architects P.O. Box 1355 Phone: (304) 727-5501 FAX: (304) 727-5580 Affix a photograph of yourself taken within 30 days of submitting this application.
More informationFATS, OIL AND GREASE (FOG) PROGRAM
FATS, OIL AND GREASE (FOG) PROGRAM LONDON GROVE TOWNSHIP MUNICIPAL AUTHORITY (LGTMA) October 17, 2014 Introductions Karen Crossan, LGTMA Manager Jeff Simpson, LGTMA WWTP Operator Ross Unruh, UTB&F Jerry
More informationResource, Support, Development, Inc. FIRE EVACUATION DRILL REPORT
FIRE EVACUATION DRILL REPORT LOCATION OF EVACUATION: Name Address City State DATE OF EVACUATION: Month Day Year PLACE INDIVIDUALS WERE EVACUATED TO: Time IF INDIVIDUALS WERE NOT EVACUATED TO A SAFE AREA
More informationFats, Oils, & Grease (FOG)
Workshop for Area 7 Fats, Oils, & Grease (FOG) PROPOSED Program and Ordinance Orange County Sanitation District August 3, 2004 What is FOG? Fats from cooking meats Lard, shortening, cooking oils Fryer
More informationDeveloping Dam Operations & Maintenance Manuals
Developing Dam Operations & Maintenance Manuals WEBINAR AGENDA Introduction General Information Operations Inspections Question & Answer Break Instrumentation & Monitoring Typical Maintenance Issues Question
More informationBrigitte A. Berger, Director of Engineering
Brigitte A. Berger, Director of Engineering Wilmette s Sewer System Overview of Wilmette s Sewer System Green vs. Gray? Stormwater Action Plan Regulatory Compliance Why Homes Flood What can
More informationRaingardens in Clay and Shallow Bedrock. by Rusty Schmidt Washington Conservation District
Raingardens in Clay and Shallow Bedrock by Rusty Schmidt Washington Conservation District Training Programs MetroBlooms (Homeowners) Train the Trainers Programs in KC Stormwater U! in Twin Cities Metro
More informationDepartment Of Public Works: Internal Operations
Department Of Public Works: Internal Operations A Checklist There are over 800 municipalities in the Michigan Municipal League s Pool and Fund Programs. Most perform public works functions of one type
More informationUniversity of California, Davis Laboratory Self-Inspection Checklist
University of California, Davis Laboratory Self-Inspection Checklist Principal Investigator/Laboratory Supervisor: Laboratories Reviewed: Date: Reviewer: Revised 11/2014 I. SAFETY PROGRAM ADMINISTRATON
More informationRESOLUTION Adopted this day of, President of June Lake Public Utility District and its Board of Directors
RESOLUTION 2017-04 RESOLUTION OF THE BOARD OF DIRECTORS OF JUNE LAKE PUBLIC UTILITY DISTRICT ESTABLISHING BEST MANAGEMENT PRACTICES FOR THE DISPOSAL OF FATS OILS AND GREASE Whereas, the June Lake Public
More informationTHE CITY OF DELAWARE, OHIO ILLICIT DISCHARGE DETECTION AND ELIMINATION PLAN
THE CITY OF DELAWARE, OHIO ILLICIT DISCHARGE DETECTION AND ELIMINATION PLAN OCTOBER 2014 Table of Contents Section 1.0 Overview/Background... 1 Section 2.0 - General Permit Information... 2 Section 3.0
More informationAction Plan to Address Erosional Outfalls
Action Plan to Address Erosional Outfalls Hawaii State Department of Transportation Highways Division, Oahu District Storm Water Management Program NPDES Permit No. HI S000001 Action Plan to Address Erosional
More informationThe checklist can be used for a single filter strip or groups of filter strips with the same characteristics.
Objectives This checklist can be used by the organisation approving the drainage scheme (drainage approving body) to help assess submissions for drainage approval. This checklist is aimed at providing
More informationdss PHILADELPHIA POLICE DEPARTMENT DIRECTIVE 4.11
dss PHILADELPHIA POLICE DEPARTMENT DIRECTIVE 4.11 Issued Date: 01-24-94 Effective Date: 01-24-94 Updated Date: 11-09-16 SUBJECT: POLICE RESPONSE TO ALARM SYSTEMS 1. POLICY A. It will be the responsibility
More informationFOR THE PERIOD JANUARY 1, TO DECEMBER 31, GENERAL INFORMATION
3850-PM-BCW0083h Rev. 11/2016 COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF CLEAN WATER PAG-03 NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES) GENERAL PERMIT FOR
More informationSEWER SYSTEM MANAGEMENT PLAN
SEWER SYSTEM MANAGEMENT PLAN Prepared for San Bernardino Community College District June 26 Prepared by: ITF & Associates Inc. 278 Los Alamitos Blvd., #354 Los Alamitos, CA 972 (8) 797-9483 SEWER SYSTEM
More informationPUBLIC NOTIFICATION PLAN
VILLAGE OF LA GRANGE, ILLINOIS NPDES PERMIT NO. ILM580009 COMBINED SEWER OVERFLOW PUBLIC NOTIFICATION PLAN NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM PROGRAM ILLINOIS ENVIRONMENTAL PROTECTION AGENCY
More informationWORKPLACE INSPECTION CHECKLIST FOR LABORATORY ENVIRONMENTS
WORKPLACE INSPECTION CHECKLIST FOR LABORATORY ENVIRONMENTS Standard OHS Workplace Inspection Checklist Review Date: Next Review: Inspection Site: Inspection Team: Contacts: Written Laboratory Safety Policies/Procedures/Records
More information-SAMPLE- Safety Inspection Checklist: Manufacturing
-SAMPLE- Safety Inspection Checklist: Manufacturing Prepared by: Midwest Builders Casualty The following procedures are not intended to be an exhaustive treatment of the subject, and should not be interpreted
More informationNorth Liberty Fire Department Permit Application Temporary Storage & Use of LPG
Application Fee: $50.00 Application Date: Permit Information Have you previously applied for this type of permit? Date of previous application: Owner/Applicant Information Applicant s Last Name: Applicant
More informationFRUCHTMAN & ASSOCIATES
FRUCHTMAN & ASSOCIATES CONSULTING MECHANICAL ENGINEERS September 27, 2018 Ocean Towers Housing Corporation 201 Ocean Avenue Santa Monica, CA 90402 Attn: Mr. Gerry Suenram General Manager Re: Ocean Towers
More informationExplain in writing if the address of the building is different than the address on this form:
ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO
More information1. Accident Prevention
Office of Environmental Health & Safety Facility Inspection Program 333 S. Beaudry Avenue, 20 th Floor Los Angeles, Ca 90017 Phone: (213) 241-3199 Fax: (213) 241-6816 SCHOOL SAFETY COMPLIANCE CHECKLIST
More informationLONDON GROVE TOWNSHIP MUNICIPAL AUTHORITY FOG PROGRAM BEST MANAGEMENT PRACTICES
2014 LONDON GROVE TOWNSHIP MUNICIPAL AUTHORITY FOG PROGRAM BEST MANAGEMENT PRACTICES 8/19/2014 TABLE OF CONTENTS WHAT IS FOG 3 WHO MUST COMPLY 4 LEGAL 4 BEST MANAGEMENT PRACTICES 5-11 MAINTENANCE LOG 12
More informationCommercial Business Licensing Requirements
SPRINGVILLE CITY BUSINESS LICENSING 110 SOUTH MAIN STREET SPRINGVILLE, UT 84663 OFFICE 801.491.7811 Commercial Business Licensing Requirements In our effort to make this application a One-Stop process
More informationImagine the result. Dear Ms. Vanderlaan:
Mary Vanderlaan Supervisor, Lansing District Michigan Department of Environmental Quality Water Resources Division 525 W. Allegan (Constitution Hall, 4N) P. O. Box 30242 Lansing, MI 48909-7742 ARCADIS
More informationColorado Division of Fire Prevention & Control, Fire & Life Safety Section
Colorado Division of Fire Prevention & Control, Fire & Life Safety Section Partnering with Colorado s Fire Professionals to Protect Our Citizens from Fire November 24, 2015 Colorado Backflow Preventer
More informationWATERFRONT FACILITY COMPLIANCE BOOKLET
U. S. COAST GUARD WATERFRONT FACILITY COMPLIANCE BOOKLET NAME: FIN: MOBILE UNIT # COTP: DATE: CG TEAM LEADER: DEPARTMENT OF TRANSPORTATION, U.S. COAST GUARD, CG-5562A (Rev 6-04) INSTRUCTIONS 1. Initial
More informationTHE CITY OF MOBILE, ALABAMA
THE CITY OF MOBILE, ALABAMA LETTER OF DECISION Ark of Safety, Inc. Mobile, AL 36617 Re: (Northwest corner of Main Street and First Avenue, extending to the Southwest corner of Esau Avenue and Main Street.)
More informationORDINANCE NO WHEREAS, the Council has received the following record of recent actions taken by the HSW Board which:
SPONSOR: 2 nd District Councilman Jack Uylaki 1 st District Councilman Mark Kalwinski Councilwoman at Large Janet Venecz ORDINANCE NO. 9262 WHEREAS, the Council has been informed of the determination by
More informationWELDING, CUTTING, AND BRAZING SAFETY PROGRAM
WELDING, CUTTING, AND BRAZING SAFETY PROGRAM HOT WORK TABLE OF CONTENTS 1.0 Introduction 1.1 Purpose 1.2 Scope 2.0 Responsibilities 2.1 Building Office 2.2 Building Personnel 2.3 Individuals Performing
More informationMS4 Permit and Storm Water Management Program Overview
MS4 Permit and Storm Water Management Program Overview What is an MS4? A conveyance or system of conveyances owned by a Public Entity that discharges to the Waters of the U.S. and is: Used for collecting
More informationLABORATORY INSPECTION CHECKLIST
LABORATORY INSPECTION CHECKLIST Date of Inspection: Conducted by: Department: Building/Room #: Principal Investigator: PI Present? Yes No Type of Inspection: Semi-Annual (scheduled) Complaint Follow Up
More informationA Visual Guide to Assessing, Inspection and Maintaining LID Practices
A Visual Guide to Assessing, Inspection and Maintaining LID Practices Welcome to the Webcast To Ask a Question Submit your question in the chat box located to the left of the slides. We will answer as
More information2. Location of Event: 3. Dates/times of Operation: Begin Date: Begin time: End date: End Time: 4. Organization/business name: 5.
TEMPORARY FOOD SERVICES PERMIT APPLICATION YADKIN COUNTY HUMAN SERVICES PO BOX 457 YADKINVILLE, NC 27055 TELEPHONE 336-679-4244 A Temporary Food Service Permit Application- Must use this application if
More informationPhase 2 Security Response
Tivoli Village Security Procedures The following procedures are to be used for all contractor check in, permits for Roof Access, Hot Work, Electrical/Phone Room Access, Placing Fire Alarm System Notification
More informationCITY OF DANIA BEACH Local Business Tax Receipt Division 100 W Dania Beach Blvd. Dania Beach, FL Phone: ext 3644 / Fax
REV 11/09 CITY OF DANIA BEACH Phone: 954-924-6805 ext 3644 / Fax 954 924-6812 BUSINESS LICENSE APPLICATION INFORMATION & REQUIREMENTS PLEASE SUBMIT THE FOLLOWING DOCUMENTS (AS APPLICABLE): 1. BEFORE submitting
More informationThe Participant will select one of the two Approval Categories (below) and submit the appropriate documentation.
ACCL Participant: Date of Inspection: Test Stand Inspection Report Number: Approval Results: FORM ACCL-PC4 ACCL FACILITY APPROVAL PROCEDURE AND CHECKLIST AHRI CERTIFICATION PROGRAM FOR AIR-COOLED (ACCL)
More informationCHAPTER VI BUILDING PLUMBING
CHAPTER VI BUILDING PLUMBING 6.1. INTRODUCTION The chapter covers questions related to water demand, distribution and drainage. The basic principles for planning and installing common plumbing systems
More informationSite Plan Review Residential Accessory Building
COMMUNITY DEVELOPMENT DEPARTMENT Planning Division P.O. Box 490 333 Broadalbin Street SW Albany, OR 97321 Phone (541) 917-7550 Fax (541) 917-7598 www.cityofalbany.net Site Plan Review Residential Accessory
More information1 LIST OF POTENTIAL PCB SOURCES
Ms. Mary Vanderlaan Supervisor, Lansing District Michigan Department of Environmental Quality Water Resources Division P. O. Box 30242 Lansing, MI 48909 Subject: NPDES Permit No. MI0001597 2017 Annual
More informationMANUAL OF ENVIRONMENTAL HEALTH PROCEDURES
West Virginia Department of Health and Human Resources MANUAL OF ENVIRONMENTAL HEALTH PROCEDURES Section Drinking Water Date April 16, 2012 Procedure # DW-36 Subject Operator Exception Requests for Automated
More informationBest Management Practices (BMPs)
Best Management Practices (BMPs) Prevent Blockages in the Sanitary Sewer System Properly Maintain Grease Traps and Interceptors to Prevent Introduction into the Sanitary Sewer System Prevent Fats, Oil,
More informationBALTIMORE CITY RENTAL LICENSE INSPECTION FORM RENTAL LICENSING INSPECTOR GUIDANCE
BALTIMORE CITY RENTAL LICENSE INSPECTION FORM RENTAL LICENSING INSPECTOR GUIDANCE Checklist items A - L may receive a result of Pass or Fail A. Railing is present for interior and exterior steps with more
More informationEvent Monitoring Device (EMD)
Event Monitoring Device (EMD) DRK-S701 INSTALLATION AND OPERATION MANUAL VERSION 2.2 - NOVEMBER 2015 PART NUMBER DRAM-BOOK DO NOT DISCARD! Contents Description Page Introduction/Features 2 Controls and
More informationOPERATION & MAINTENANCE
Curb Inlet Filter OPERATION & MAINTENANCE Bio Clean Environmental Services, Inc. 398 Via El Centro Oceanside, CA 92058 www.biocleanenvironmental.com p: 760.433.7640 f: 760.433.3176 OPERATION & MAINTENANCE
More informationTrinity River Authority of Texas
Trinity River Authority of Texas Central Regional Wastewater System 3110.005.100 November 19, 2015 Attention: Contractors / Suppliers / Delivery Personnel Subject: Central Regional Wastewater System Risk
More informationEl Segundo Fire Department. Unified Program (UP) Form CONSOLIDATED CONTINGENCY PLAN I. FACILITY IDENTIFICATION
I. FACILITY IDENTIFICATION BUSINESS NAME 3 FACILITY ID # 1 9 0 1 3 3 0 SITE ADDRESS 103 CITY 104 ZIP CODE 105 The Consolidated Contingency Plan provides businesses a format to comply with the emergency
More informationCategory V. NOTE: Fire Investigations are covered in Criterion 5D.
Category V Criterion 5B: Fire Prevention/Life Safety Program The agency operates an adequate, effective, and efficient program directed toward fire prevention, life safety, hazard risk reduction, the detection,
More informationCity of Joshua 101 S. Main Joshua, Texas
City of Joshua 101 S. Main Joshua, Texas 76058 817-558-7447 APPLICATION FOR ON-SITE SEWAGE FACITLITY FOR NEW CONSTRUCTION 1. Property Owner's Name: 2. Current Mailing Address: 3. Daytime Telephone No.:
More informationBoston Water and Sewer Commission
Boston Water and Sewer Commission 980 Harrison Avenue Boston, MA 02119-2540 617-989-7000 March 27, 2017 Michael Rooney Boston Planning & Development One City Hall Square Boston, MA 02201 Re: 159-20 1 Washington
More informationCONSOLIDATED EDISON CO. OF NEW YORK INC. 4 IRVING PLACE NEW YORK, N.Y DISTRIBUTION ENGINEERING CABLE SYSTEMS
CONSOLIDATED EDISON CO. OF NEW YORK INC. 4 IRVING PLACE NEW YORK, N.Y. 10003 DISTRIBUTION ENGINEERING CABLE SYSTEMS SPECIFICATION EO-4082 REVISION 2 May, 1998 OPERATION AND MAINTENANCE OF CONDUIT SYSTEM,
More informationSeptember 17, Linda Tucker City of Isle of Palms PO Drawer 508 Isle of Palms SC 29451
September 17, 2012 Linda Tucker City of Isle of Palms PO Drawer 508 Isle of Palms SC 29451 RE: Pre-Project Lighting Survey Isle of Palms Shoal Management Project [CSE 2384] Dear Ms Tucker, As a special
More informationJuly 17, Dear Mr. Fields:
July 17, 2015 Whitney Fields Director, Safety & Risk Management Human Resources and Employee Relations SAN BERNARDINO COMMUNITY COLLEGE DISTRICT 114 South Del Rosa Drive San Bernardino, California 92408
More informationBiosolids Processing Report City of Buffalo, Minnesota
April 2017 Biosolids Processing Report City of Buffalo, Minnesota W13.112989 Submitted by: Bolton & Menk, Inc. 2040 Highway 12 East Willmar, MN 56201 P: 320-231-3956 F: 320-231-9710 Certification Biosolids
More informationCity of Fayetteville, Arkansas Page 1 of 1
City of Fayetteville, Arkansas 113 West Mountain Street Fayetteville, AR 72701 479-575-8323 Legislation Text File #: 2014-0577, Version: 1 AN ORDINANCE WAIVING THE REQUIREMENTS OF FORMAL COMPETITIVE BIDDING
More informationNew State Storm Water Rules: WHAT MUNICIPALITIES NEED TO KNOW &
New State Storm Water Rules: WHAT MUNICIPALITIES NEED TO KNOW & Detecting Eliminating Illicit Discharges Storm water runoff in urban areas is a major and visible source of pollutants in our streams and
More information19 Washington State Patrol Detective Sergeant with over thirty years of criminal investigative
E-FILED IN COUNTY CLERK'S OFFICE PIERCE COUNTY, WASHINGTON September 14 2016 10:01 AM 1 KEVIN STOCK COUNTY CLERK NO: 16-1-03648-3 2 3 4 5 6 7 STATE OF WASHINGTON PIERCE COUNTY SUPERIOR COURT 8 9 THE STATE
More information2012 Saginaw Bay Watershed Conference
2012 Saginaw Bay Watershed Conference March 16, 2012 Russ Beaubien, P.E., CFM Low Impact Development Fundamentals Summary LID overview Education on LID Fundamentals of LID Examples of LID practices Other
More informationROGUE VALLEY SEWER SERVICES STORMWATER MANAGEMENT PROGRAM (SWMP)
ROGUE VALLEY SEWER SERVICES STORMWATER MANAGEMENT PROGRAM (SWMP) 1.0 INTRODUCTION This Stormwater Management Program (SWMP) for Rogue Valley Sewer Services (RVS) has been developed to meet the Municipal
More informationExplain in writing if the address of the building is different than the address on this form:
ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO
More informationExplain in writing if the address of the building is different than the address on this form:
ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO
More informationPutting a LID on Stormwater Pollution. Michele Loudenback, RPES Stormwater Enforcement Water Quality Division
Putting a LID on Stormwater Pollution Michele Loudenback, RPES Stormwater Enforcement Water Quality Division Outline Brief Regulatory History Conventional vs. Green Practices LID/GI Controls in Use Clean
More informationBUILDING AND CODES DEPARTMENT 350 Pageant Lane Suite 309 Clarksville, TN 37040
Phone 931-648-5718 BUILDING AND CODES DEPARTMENT 350 Pageant Lane Suite 309 Clarksville, TN 37040 Fax 931-553-5121 Food Service Establishment Fats, Oil and Grease Best Management Practices 1. Introduction
More informationSewage Sludge Disposal in Ohio for 2007
Sewage Sludge Disposal in Ohio for 2007 Publicly owned treatment works and semi-public treatment works (hereinafter collectively referred to as POTWs) in Ohio are required to have an effective National
More informationSewage Sludge Disposal in Ohio for 2003
Sewage Sludge Disposal in Ohio for 2003 Publicly owned treatment works and semi-public treatment works (hereinafter collectively referred to as POTWs) in Ohio are required to have an effective National
More informationSummary of Conversion Steps. 1. Obtain the abandonment/conversion permit from the Department of Health.
One of the benefits of connecting to the Central Wastewater System is the opportunity it provides to convert your septic tank into a cistern. For slightly more than the cost of septic tank abandonment
More informationTemporary LPG Heat for Construction Sites Work At Risk and Inspection Information Packet
Temporary LPG Heat for Construction Sites Work At Risk and Inspection Information Packet Colorado Springs Fire Department Division of the Fire Marshal December 2013 W:\Packets\Haz Mat\IFC2009_Work_At_Risk_Temp_LPG_Heat
More informationAIRVAC sewer systems are reliable, dependable, and will save you money.
AIRVAC sewer systems are reliable, dependable, and will save you money. Reliable and Economical Thirty years ago, vacuum sewers were regarded as new and only to be used as a system of last resort. Improvements
More information