1 Edinburgh Research Explorer Effects of a travelling fire on a concrete columns - Tisova Fire Test Citation for published version: Rush, D, Lange, D, Maclean, J & Rackauskaite, E 2015, 'Effects of a travelling fire on a concrete columns - Tisova Fire Test' Paper presented at Applications of Structural Fire Engineering, Dubrovnik, Croatia, 15/10/15-16/10/15,. Link: Link to publication record in Edinburgh Research Explorer General rights Copyright for the publications made accessible via the Edinburgh Research Explorer is retained by the author(s) and / or other copyright owners and it is a condition of accessing these publications that users recognise and abide by the legal requirements associated with these rights. Take down policy The University of Edinburgh has made every reasonable effort to ensure that Edinburgh Research Explorer content complies with UK legislation. If you believe that the public display of this file breaches copyright please contact openaccess@ed.ac.uk providing details, and we will remove access to the work immediately and investigate your claim. Download date: 08. Apr. 2019

2 Applications of Structural Fire Engineering, October 2015, Dubrovnik, Croatia EFFECTS OF A TRAVELLING FIRE ON A CONCRETE COLUMN TISOVA FIRE TEST David Rush a, David Lange b, Jamie Maclean a, and Egle Rackauskaite c a BRE Centre for fire safety engineering, The University of Edinburgh, Edinburgh, UK b SP Technical Research Institute of Sweden, Boras, Sweden c Imperial College, London, UK Abstract The Tisova Fire Test was a large fire test conducted in the Czech Republic in January 2015 inside of a 4-storey concrete frame building, with concrete and composite deck floors. The test compartment was on the ground floor and the fire compartment had a total area of ca. 230m 2 with a height of 4.4m. The fire compartment included four columns from the original 1958 concrete construction, one of which was instrumented for temperatures, chosen due to its higher likelihood of observable structural response both during and after the fire. This paper presents selected results of the test, concentrating on the thermal environment around the column showing the variability of temperatures through the compartment height. The paper also present the columns thermal response, as well as a post-fire assessments of the columns visual condition. Keywords: concrete column, travelling fire, large scale structural fire test, Tisova Fire Test 1 INTRODUCTION Current fire engineering design guidance (e.g. CEN, 2010), in general, assesses structures and their response to fire on a pass/fail assessment usually consisting of prescribed fire resistance criteria and times. This assessment is usually based on a standard fire (e.g. ISO-834 (CEN, 2009)) that represents only one fire out of a range of possible fires which may occur, and may not represent the most onerous (or more realistic) fire insult that a structure might experience (Gales, Maluk and Bisby, 2012). Also standard fire testing, from which the deign guidance is generally based, are, in general, limited to single elements rather than full structures and cannot capture the full complexities of the structural interactions of a building subject to a real fire. Current fire engineering design is also based almost entirely on life safety performance goals and, in general, has no means of quantifying property protection goals (i.e. damage level, reinstatement costs, business continuity, etc ), which are however becoming more popular with building owners and insurers alike, and are now becoming frequently considered as a design driver. Property protection is rarely explicitly considered in fire engineering design due to a lack of credible data from which to assess/model full structures in fire - this is particularly true for concrete structures (Bisby, Mostafaei and Pimienta, 2014). Modelling of concrete elements and structures to nonstandard fires has shown that long durations of some travelling fires (Law et al., 2011) or parametric fires (Rush et al., 2014) can have significant effects on the fire and post-fire damage and response of concrete structures. However the validity of these models remains in question due to the lack of experimental data, with very few tests conducted in large compartments with travelling fires (e.g. (Horová, Wald and Bouchair, 2013). The Tisova Fire Test aimed to generate experimental data on some of the modelling uncertainties namely; travelling fires; the thermal and structural response of composite slabs, concrete slabs, and concrete columns to real fires as an input to round robin studies; and a post-fire assessment of a structure after a quantified fire event. This paper considers one aspect of the Tisova Fire Test the thermal response of columns to a travelling fire. 2 FIRE TEST The Tisova Fire Test was carried out in January of 2015 by a team from SP, the University of Edinburgh, Imperial College London, Luleå Technical University, and Technical University Ostrava, Majaczech, CSTB and CERIB. The fire test was conducted inside of a real building, Figure 1, which

3 was scheduled for demolition. The building was constructed in 1958 as a powdered coal boiler and comprised of a reinforced concrete frame and slab construction. In 1980 the buildings use was changed to a combination of workshops and offices and additional floors and slabs were added using composite slab construction tied in to the original frame. The aim of the test was to achieve a structurally challenging travelling fire. Figure 1: Left Southwest corner of test building, and Right fire compartment The test compartment shown in Figure 2 was on the ground floor and the fire compartment had a total area of approximately 230m 2 and was 4.4 m high from floor to slab soffit. The layout was generally open, with a series of large rooms enclosing one side as well as one corner. There was also a central lift shaft. Four columns were fully within the fire compartment. The smallest 30 x 30 cm column (C1) indicated in Figure 2 was chosen to be examined due to its slenderness and was therefore most likely to experience higher core temperatures and damage during the fire test. N FI C1 Figure 2: Fire compartment showing fire ignition point (FI) and path of travel (arrows), and column C1 and associated TC tree locations The size and layout of the compartment meant that it was ideal for testing the travelling fires methodology developed by Stern-Gottfried & Rein (2012). The fuel was laid out as a uniform single fuel bed across the whole floor, apart from a m path around the perimeter of the floor area. Fuel covered approximately 170 m 2 of the floor area as shown in Figure 2. The arrangement of the fuel bed was 5.5 layers/m 2 of 8 x 1m x 0.06m x 0.04m sticks per layer of spruce timber conditioned to a targeted 11% moisture content. The 44 sticks per layer which gives a fuel load of approximately 40kg/m 2 within the fuel bed, or approximately 680MJ/m 2. The fire was well ventilated to ensure that fire was fuel load controlled and not controlled by ventilation, and the fire was ignited at location FI in Figure 2 using organic fuel soaked in lighter fuel within the crib.

4 Fire temperatures within the compartment were recorded using 56 thermocouple (TC) trees incorporating Type-K Inconel sheathed thermocouples hung from the ceiling at approximately 2.5m spacing s. Figure 2 shows the four thermocouple trees within a 2.5m radius of the column C1, named,,, and TC trees, respectively. Each thermocouple tree had 6 thermocouples at heights below the soffit of the slab of: 5cm, 65cm, 140cm, 205cm, 260cm, and 370cm, respectively. The top of the fuel bed was approximately 40cm off the floor. The and TC trees are shown in Figure 3: Section A-A. Figure 3: Section A-A: TC tree thermocouple layout, and column TC and PT height, and Section B-B: Column cross-section showing TC and PT placement Column C1 was instrumented with 6 thermocouples at two heights, 1.5m above the floor and 3m above the floor, unfortunately the thermocouples 1.5m above the floor suffered from a failure early on in the test and all data was corrupted and will not be discussed any further in this paper. Figure 3 b) shows the locations of the thermocouples at the 3m height of the column. Figure 3 shows four TCs which were placed 6 cm from each of the four faces, and two TCs which were placed 10 cm from the North and West faces. Holes were drilled at an angle of 45 from above to mid-depth of the columns and TCs were then temporarily held in position and re-cast into the column using quick setting mortar. A plate thermometer (PT) was placed 10 cm from each of the North (N), East (E), South (S), and West (W) column faces with their centres at the same height from the floor as the thermocouple ends as an indication of the fire exposure to the column at the 3m height. 3 RESULTS The fire was successfully ignited as planned however it soon became evident that fire spread rate was very slow with the flame length along the path (shown in Figure 2) of approximately 1 m with a flame height between m. The resulting temperatures in the compartment, especially near the ceiling, were not high enough for a structurally challenging fire, i.e. well below 100 o C. To encourage fire growth during the test the ventilation was reduced and a 10 litre mixture of gasoline and diesel at a ratio of 1:1 was poured over the fuel bed along the southern perimeter 2.5 hrs into the test. This resulted in a more severe fire covering cribs in the west and south ends of the building. However, as the fire started to move north (Figure 2), the intensity of the fire reduced and the fire spread further

5 400 Height from underside of slab (cm) into the compartment slowed significantly. The reason for the poor severity of the fire was mainly due to the moisture content of the wood, which when controlled specimens were tested after the fire, showed a moisture content between 18-22% rather than 11%. Higher moisture contents results in more energy being absorbed in the evaporation of water rather than into the fire environment, and reduces the rate of flame spread (Fons, Clements and George, 1963) 5cm a) 0:00-2:30 3:00 3:30 b) 65cm 4:00 140cm 205cm 6:00 5:00 4:30 5: Temperature ( C) 260cm 370cm 0:00 1:00 2:00 3:00 4:00 5:00 6:00 0:00 1:00 2:00 3:00 4:00 5:00 6:00 Figure 4: a) Time-temperature curves at each of the 6 TC heights below the soffit of 5cm, 65cm, 140cm, 205cm, 260cm, and 370cm; and b) variation in temperature over the height of the compartment at 30 minute intervals 3.1 Gas phase temperatures in region of column Figure 4 a) shows the recorded temperatures during the fire test with respect to the height below the soffit, and shows the clear jump in temperatures after 2:30 hrs due to the addition of gasoline to the fire compartment to encourage the growth of the fire. It can also be seen from Figure 4 a) that the temperatures nearer the ceiling (5cm, 65cm, and 140cm) are fairly consistent across all four TC trees (,,, and ). Maximum average temperatures experienced in the top 140cm of the fire compartment were in the region of o C. In contrast the temperatures further away from the ceiling were more varied but in general hotter than those near the ceiling, with average temperatures

6 peaking at 500 o C, 635 o C, and 510 o C, at 205cm, 260cm, and 370cm from the ceiling, respectively. This is clearly shown in Figure 4 b) which shows the variation in temperature over the height of the compartment at 30 minute intervals, with the maximum temperatures, after the gasoline was added at 2:30 hrs, consistently observed within the lower half of the compartment for over two hours. 3.2 Plate thermocouple data Figure 4 shows that there is a great deal of variation within the fire environment through the height of the compartment. However the temperature measurements were at a not insignificant distance from the column C1 which is being investigated. To understand the thermal boundary for the column at 3m above the floor, four plate thermometers (PT) were installed around the perimeter of the column (Figure 3: Section B-B). Figure 5 shows the recorded PT temperatures for the individual PTs and compares the average temperatures from the PTs to the average TC-140cm temperature data, showing a very good correlation between the two averages. Any future modelling of the heat transfer to the column can be confident of the thermal boundary present in the tests. PT-N PT-E PT-S PT-W PTs TC 140cm 0:00 1:00 2:00 3:00 4:00 5:00 6:00 Figure 5: Comparison of PT and TC tree recorded temperatures at 140cm below ceiling soffit Figure 6: Recorded temperatures within concrete column C1 3.3 Column temperature data TC1 TC2 TC3 TC4 TC5 TC6 0 0:00 1:00 2:00 3:00 4:00 5:00 6:00 7:00 As previously stated, unfortunately temperatures at 1.5m above the floor failed to be recorded, so comparisons of the heat transfer to the column from the more severe temperatures recorded within the lower half of the compartment to the cooler upper half cannot be made. However, Figure 6 shows the data recorded at 3m above the floor (1.4m below the ceiling), and shows an increase in structural temperatures at around 2:40 which increase relatively linearly until 4:30 at approximately 1 o C/min.

7 The very slow heating rate causes very similar temperatures to be observed within the cross-section. As the maximum observed temperatures are well below those that would be considered structurally significant, little to no damage would have been experienced by the concrete material and a visual inspection of the column showed no signs of damage apart from aesthetic smoke damage. 4 CONCLUSIONS This paper has presented selected results from the large scale Tisova Fire Test conducted in the Czech Republic in January 2015, from which we can conclude: The moisture content of wood severely retarded the fire severity and flame spread rate, and even after a gasoline/diesel mix was introduced to promote fire growth, temperatures struggled to get above 500 o C for any prolonged amount of time within the compartment. Temperatures within compartment were found to be hotter in the lower half of the compartment (i.e. nearer the flames) rather than near the ceiling. If this were true for all large compartment travelling fires, this could have implications for the design of columns within such compartments. With temperatures being on average less than 500 o C in the lower half of the compartment and less than 400 o C in the upper half for approximately 2 hrs, recorded concrete temperatures within the column instrumented did not rise above 140 o C, and as such the column experienced very little if any damage. More analytical and experimental research into the structural consequences of realistic and travelling fires is required so that performance based designs, where property protection is an additional driver to life safety, can be rationally and defensible conducted. ACKNOWLEDGMENTS The authors would like to express their most sincere thanks to all of the firefighters of the fire and rescue service in Carlsbad for their enthusiastic support. The work reported has been carried out within projects supported financially by grants from the Swedish Fire Research Board (Brandforsk), and from the Engineering and Physical Sciences Research Council in the UK (EPSRC). REFERENCES Bisby, L. A., Mostafaei, H. and Pimienta, P. (2014) State-of-the-art on Fire Resistance of Concrete Structures: Structure-Fire Model Validation. CEN (2009) BS EN :2002 Eurocode 1- Actions on structures; Part 1-2: General Actions - Actions on structures exposed to fire. Brussels, Belgium. CEN (2010) BS EN : Eurocode 2 : Design of concrete structures Structural fire design. Brussels, Belgium. Fons, W. L., Clements, H. B. and George, P. M. (1963) Scale effects on propagation rate of laboratory crib fires, Symposium (International) on Combustion, 9(1), pp doi: /S (63) Gales, J., Maluk, C. and Bisby, L. (2012) Large- scale structural fire testing- How did we get here, Where are we, and where are we going?, in 15th ICEM Porto, Portugal, pp Horová, K., Wald, F. and Bouchair, A. (2013) Travelling Fire in Full-Scale Experimental Building, in Design, Fabrication and Economy of Metal Structures. Berlin, Heidelberg: Springer Berlin Heidelberg, pp doi: / _56. Law, A., Stern-Gottfried, J., Gillie, M. and Rein, G. (2011) The influence of travelling fires on a concrete frame, Engineering Structures. Elsevier Ltd. doi: /j.engstruct Rush, D., Bisby, L., Ioannou, I. and Rossetto, T. (2014) Towards fragility analysis for concrete buildings in fire: residual capacity of concrete columns, in 8th International Conference on Structures in Fire. Shanghai, pp Stern-Gottfried, J. and Rein, G. (2012) Travelling fires for structural design-part II: Design methodology, in Fire Safety Journal, pp doi: /j.firesaf

EFFECTS OF A TRAVELLING FIRE ON A CONCRETE COLUMN TISOVA FIRE TEST

EFFECTS OF A TRAVELLING FIRE ON A CONCRETE COLUMN TISOVA FIRE TEST Applications of Structural Fire Engineering, 15-16 October 215, Dubrovnik, Croatia EFFECTS OF A TRAVELLING FIRE ON A CONCRETE COLUMN TISOVA FIRE TEST David Rush a,david Lange b, Jamie Maclean a, Egle Rackauskaite

More information

Fire Severity for Structural Design

Fire Severity for Structural Design Fire Severity for Structural Design A UK Perspective Susan Deeny, PhD 2 Broadgate Phase 8 3 5 Shaping a better world Experience of working in Abu Dhabi 6 UAE 7 Fire Severity for Structural Analysis Building

More information

FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability

FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability Proceedings of the International Conference in Dubrovnik, 15-16 October 2015 FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability Johan Anderson a, Lars Boström a, Robert Jansson

More information

Experimental Room Fire Studies with Perforated Suspended Ceiling

Experimental Room Fire Studies with Perforated Suspended Ceiling Experimental Room Fire Studies with Perforated Suspended Ceiling FIONA S.C. TSUI 1, W.K. CHOW 1, N.K. FONG 1, Y. GAO 2, H. DONG 2, and G.W. ZOU 2 1 Research Centre for Fire Engineering Department of Building

More information

EPSRC Research Project: Real Fires for the Safe Design of Tall Buildings

EPSRC Research Project: Real Fires for the Safe Design of Tall Buildings EPSRC Research Project: Real Fires for the Safe Design of Tall Buildings Prof Luke Bisby, Acting Director BRE Centre for Fire Safety Engineering Arup Chair of Fire and Structures BRE Centre for Fire Safety

More information

1.1. Design fires for structural engineering

1.1. Design fires for structural engineering 1.1. Design fires for structural engineering M. Gillie School of Engineering, University of Edinburgh, Edinburgh, UK F. Wald & K. Horová Czech Technical University in Prague, Czech Republic 1.1.1 THE NATURE

More information

Advantages and Disadvantages of Fire Modelling

Advantages and Disadvantages of Fire Modelling Advantages and Disadvantages of Fire Modelling Dr Guillermo Rein School of Engineering University of Edinburgh & Imperial College London Dr Guillermo Rein 9 May 2012 Chief Fire Officers Association Annual

More information

Sponsors: CERIB. Dr. Guillermo Rein. Department of Mechanical Engineering

Sponsors: CERIB. Dr. Guillermo Rein. Department of Mechanical Engineering Travelling Fires for Structural Design Sponsors: CERIB Dr. Guillermo Rein Department of Mechanical Engineering Across Disciplines Fire & Structures Fire Structures The interface between fire and structures

More information

Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation

Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation Downloaded from orbit.dtu.dk on: Mar 02, 2018 Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation Wu, Xiaozhou; Fang, Lei; Olesen, Bjarne

More information

Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls

Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls Journal of Mechanics Engineering and Automation 5 (2015) 465-471 doi: 10.17265/2159-5275/2015.08.007 D DAVID PUBLISHING Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls

More information

Fire propagation over combustible exterior facades exposed to intensified flame in Japan

Fire propagation over combustible exterior facades exposed to intensified flame in Japan MATEC Web of Conferences 46, 02002 (2016) DOI: 10.1051/matecconf/20164602002 C Owned by the authors, published by EDP Sciences, 2016 Fire propagation over combustible exterior facades exposed to intensified

More information

ASSESSING THE FIRE PERFORMANCE OF ELECTRIC CABLES (FIPEC)

ASSESSING THE FIRE PERFORMANCE OF ELECTRIC CABLES (FIPEC) ASSESSING THE FIRE PERFORMANCE OF ELECTRIC CABLES (FIPEC) P. Van Hees and J. Axelsson, SP Sweden, S. J. Grayson and A. M. Green, Interscience Communications UK, H Breulet, ISSeP Belgium and U Vercellotti,

More information

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs 1 ABSTRACT Noureddine Benichou and Ahmed H. Kashef * Institute for Research in Construction National Research Council of Canada

More information

CITE: Gales, J. (2013) Travelling fires and the St. Lawrence Burns Project, Fire Technology. 9 pp.

CITE: Gales, J. (2013) Travelling fires and the St. Lawrence Burns Project, Fire Technology. 9 pp. Travelling Fires and the St. Lawrence Burns Project John Gales Department of Civil and Environmental Engineering, Carleton University, Ottawa, ON, Canada Abstract This paper represents a timely communication

More information

Residential Building Walls and Environment in Amman, Jordan

Residential Building Walls and Environment in Amman, Jordan Int. J. of Thermal & Environmental Engineering Volume 3, No. 2 (211) 1-7 Residential Building Walls and Environment in Amman, Jordan S. J. Sulaiman*, N. Beithou Department of Mechanical Engineering, Applied

More information

CHANCES AND LIMITS OF THE TIME-EQUIVALENCE-METHOD IN STRUCTURAL FIRE DESIGN

CHANCES AND LIMITS OF THE TIME-EQUIVALENCE-METHOD IN STRUCTURAL FIRE DESIGN CHANCES AND LIMITS OF THE TIME-EQUIVALENCE-METHOD IN STRUCTURAL FIRE DESIGN ABSTRACT P. Schaumann and S. Hothan University of Hannover, Institute for Steel Construction Appelstraße 9a, D-3167 Hannover,

More information

Fire Resistance - Implications for regulations and standards of the September 11th terrorist attacks on the world trade centre Tom Lennon, FRS, BRE

Fire Resistance - Implications for regulations and standards of the September 11th terrorist attacks on the world trade centre Tom Lennon, FRS, BRE Fire Resistance - Implications for regulations and standards of the September 11th terrorist attacks on the world trade centre Tom Lennon, FRS, BRE Malaysia May 2003 Questions What is fire resistance?

More information

FAÇADE FIRE TESTS Towards a new European standard method

FAÇADE FIRE TESTS Towards a new European standard method FAÇADE FIRE TESTS Towards a new European standard method Lars Boström November 22, 2017 RISE Research Institutes of Sweden Safety Content Current state in Europe regarding façade fire tests History on

More information

Development of a European approach to assess the fire performance of facades

Development of a European approach to assess the fire performance of facades Development of a European approach to assess the fire performance of facades This presentation was made in Brussels on December 8, 2017, for EC, AGF and stakeholders Lars Boström, Roman Chiva, Anja Hofmann-Böllinghaus,

More information

First Revision No. 6-NFPA [ Section No. 2.2 ]

First Revision No. 6-NFPA [ Section No. 2.2 ] Page 1 of 18 First Revision No. 6-NFPA 555-2014 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 12, Standard on Carbon

More information

A Priori Modelling of Fire Test One

A Priori Modelling of Fire Test One A Priori Modelling of Fire Test One Authorship: Brave Users Guillermo Rein, José L. Torero, Wolfram Jahn, Jamie Stern-Gottfried, Noah L. Ryder, Sylvain Desanghere, Mariano Lázaro, Frederick Mowrer, Andrew

More information

WARRES No Page 1 of 27. Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier

WARRES No Page 1 of 27. Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier Page 1 of 27 Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier Test Sponsor Saveguard (UK) Limited Warrington Fire Research Centre Ltd.,

More information

Can painted glass felt or glass fibre cloth be used as vapour barrier?

Can painted glass felt or glass fibre cloth be used as vapour barrier? Downloaded from orbit.dtu.dk on: Oct 22, 2018 Can painted glass felt or glass fibre cloth be used as vapour barrier? El-Khattam, Amira; Andersen, Mie Them; Hansen, Kurt Kielsgaard; Møller, Eva B. Published

More information

Are we using the wrong design fires for tall building fire strategies, in light of recent full height fires?

Are we using the wrong design fires for tall building fire strategies, in light of recent full height fires? Are we using the wrong design fires for tall building fire strategies, in light of recent full height fires? Tall Building Fire Safety Network meeting & seminar FIREX, London, 22 nd June 2016 Eoin O Loughlin

More information

This document is a preview generated by EVS

This document is a preview generated by EVS TECHNICAL REPORT ISO/TR 15657 First edition 2013-06-15 Fire resistance tests Guidelines for computational structural fire design Essais de résistance au feu Lignes directrices sur la conception statistique

More information

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS FIRE EXTINGUISHING INSTALLATIONS SECTION POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS Version 1 29-09-04 0 Eurofeu position paper on water mist for fire fighting applications 1 Scope The

More information

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER , Volume 9, Number 1, p.38-58, 2007 ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER C.W. Leung and W.K. Chow Department of Building Services Engineering, The Hong Kong

More information

PERFORMANCE OF CLT ASSEMBLIES IN FIRE

PERFORMANCE OF CLT ASSEMBLIES IN FIRE PERFORMANCE OF CLT ASSEMBLIES IN FIRE Noureddine Benichou, Ph.D., National Research Council Canada Christian Dagenais, Eng., M.Sc., FPInnovations May 28, 2015 Background Mass timber, such as CLT, are generally

More information

Certain Uncertainty - Demonstrating safety in fire engineering design and the need for safety targets.

Certain Uncertainty - Demonstrating safety in fire engineering design and the need for safety targets. Certain Uncertainty - Demonstrating safety in fire engineering design and the need for safety targets. Danny Hopkin 1, Ruben Van Coile 2 & David Lange 3 Introduction In his 2008 IAFSS plenary, Andy Buchannan

More information

NUMERICAL SIMULATION OF THE NEW SOUTH WALES FIRE BRIGADE COMPARTMENT FIRE BEHAVIOUR TRAINING TEST CELL

NUMERICAL SIMULATION OF THE NEW SOUTH WALES FIRE BRIGADE COMPARTMENT FIRE BEHAVIOUR TRAINING TEST CELL , Volume 9, Number 4, p.154-162, 7 NUMERICAL SIMULATION OF THE NEW SOUTH WALES FIRE BRIGADE COMPARTMENT FIRE BEHAVIOUR TRAINING TEST CELL D. Mackay and T. Barber School of Mechanical and Manufacturing

More information

120 YEARS OF STRUCTURAL FIRE TESTING: MOVING AWAY FROM THE STATUS QUO

120 YEARS OF STRUCTURAL FIRE TESTING: MOVING AWAY FROM THE STATUS QUO Cite as: Maluk C and Bisby L. 2012. 120 years of structural fire testing: Moving away from the status quo. Invited plenary presentation at the 2nd Fire Engineering Conference, 25-26 October, 2012, Valencia,

More information

Indicative hoarding fire experiment. Prepared for: London Fire Brigade. 21 May 2014 Client report number

Indicative hoarding fire experiment. Prepared for: London Fire Brigade. 21 May 2014 Client report number Indicative hoarding fire experiment Prepared for: London Fire Brigade 21 May 2014 Client report number 292366 1 Hoarding fire demonstration Prepared on behalf of BRE Fire and Security by Name Dr Sung-Han

More information

PRELIMINARY ANALYSIS OF THE NUMBER OF OCCUPANTS, FIRE GROWTH, DETECTION TIMES AND PRE-MOVEMENT TIMES FOR PROBABILISTIC RISK ASSESSMENT

PRELIMINARY ANALYSIS OF THE NUMBER OF OCCUPANTS, FIRE GROWTH, DETECTION TIMES AND PRE-MOVEMENT TIMES FOR PROBABILISTIC RISK ASSESSMENT PRELIMINARY ANALYSIS OF THE NUMBER OF OCCUPANTS, FIRE GROWTH, DETECTION TIMES AND PRE-MOVEMENT TIMES FOR PROBABILISTIC RISK ASSESSMENT DAVID CHARTERS DEAN MCGRAIL Arup Fire, 78 East Street, Leeds, LS9

More information

ASSESSMENT OF TIMBER PARTITION MATERIALS WITH FIRE RETARDANTS WITH A ROOM CALORIMETER

ASSESSMENT OF TIMBER PARTITION MATERIALS WITH FIRE RETARDANTS WITH A ROOM CALORIMETER , Volume 6, Number 3, p.122-154, 2004 ASSESSMENT OF TIMBER PARTITION MATERIALS WITH FIRE RETARDANTS WITH A ROOM CALORIMETER C.W. Leung, W.K. Chow Department of Building Services Engineering, The Hong Kong

More information

An experimental study of the impact of tunnel suppression on tunnel ventilation

An experimental study of the impact of tunnel suppression on tunnel ventilation An experimental study of the impact of tunnel suppression on tunnel ventilation Yoon J. Ko and George Hadjisophocleous Civil and Environmental Engineering, Carleton University 1125 Colonel By Drive, Ottawa,

More information

How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015?

How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015? Plumis White Paper April 2017 How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015? As with the introduction of every new formal product category through

More information

How design fires can be used in fire hazard analysis

How design fires can be used in fire hazard analysis How design fires can be used in fire hazard analysis Yung, D.T.; Bénichou, N. NRCC-44511 A version of this document is published in / Une version de ce document se trouve dans : Fire Technology, v. 38,

More information

Characterising the smoke produced from modern materials and evaluating smoke detectors

Characterising the smoke produced from modern materials and evaluating smoke detectors www.bre.co.uk Briefing Paper Characterising the smoke produced from modern materials and evaluating smoke detectors Raman Chagger 01 Contents Abstract 02 Introduction 02 Background 03 The current test

More information

Research on fire protection methods and a case study "Futurum"

Research on fire protection methods and a case study Futurum Available online at www.sciencedirect.com Procedia Engineering 40 (2012 ) 339 344 Steel Structures and Bridges 2012 Research on fire protection methods and a case study "Futurum" J. Outinen a *, J. Samec

More information

Improvement of Granular Subgrade Soil by Using Geotextile and Jute Fiber

Improvement of Granular Subgrade Soil by Using Geotextile and Jute Fiber International Journal of Science, Technology and Society 2015; 3(5): 230-235 Published online August 3, 2015 (http://www.sciencepublishinggroup.com/j/ijsts) doi: 10.11648/j.ijsts.20150305.12 ISSN: 2330-7412

More information

The first tunnel fire. Benefits of fire

The first tunnel fire. Benefits of fire Benefits of fire suppression Quantifying the effects of suppression on energy release. This article by Fathi Tarada, managing director of fire safety, risk management, ventilation and CFD consultant Mosen

More information

Guidance Document on the Verification of the Adhesive Performance in Fire

Guidance Document on the Verification of the Adhesive Performance in Fire Fire safe use of bio-based building products Guidance Document on the Verification of the Adhesive Performance in Fire (N222-07) October 2018 FP1404 WG2 TG1 Editors: M. Klippel, J. Schmid 2 Guidance Document

More information

Test One: The Uncontrolled Compartment Fire

Test One: The Uncontrolled Compartment Fire The University of Edinburgh BRE Centre for Fire Safety Engineering One Day Symposium on The Dalmarnock Fire Tests: Experiments & Modelling Test One: The Uncontrolled Compartment Fire Cecilia Abecassis

More information

Available online at ScienceDirect. Procedia Engineering 84 (2014 )

Available online at  ScienceDirect. Procedia Engineering 84 (2014 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 84 (2014 ) 553 557 2014ISSST, 2014 International Symposium on Safety Science and Technology Research on fire endurance of tempered

More information

Fire Test Evaluation using the Kerosene and Aviation Fuel

Fire Test Evaluation using the Kerosene and Aviation Fuel Fire Test Evaluation using the Kerosene and Aviation Fuel K. S. Bang, J.C. Lee, C. S. Seo, K. S. Seo, H. J. Kim* Korea Atomic Energy Research Institute, 15 Dukjin-Dong, Yuseung-gu, Daejeon, Korea 35-353

More information

Travelling Fires for CFD

Travelling Fires for CFD Travelling Fires for CFD JOAKIM SANDSTRÖM 1,2, XUDONG CHENG 1, MILAN VELJKOVIC 1, ULF WICKSTRÖM 1,3, and TIM HEISTERMANN 1 1 Department of Civil, Mining and Environmental Engineering Luleå University of

More information

Classification of reaction to fire performance in accordance with EN : A1: 2009 on Superfoil SFNC. Prepared for:

Classification of reaction to fire performance in accordance with EN : A1: 2009 on Superfoil SFNC. Prepared for: Classification of reaction to fire performance in accordance with EN 13501-1: 2007 +A1: 2009 on Superfoil SFNC Prepared for: Boulder Developments Ltd Black Horse Farm Main Street Norwell Nottinghamshire

More information

CLT Adhesive Tests in Support of Mass Timber Buildings

CLT Adhesive Tests in Support of Mass Timber Buildings CLT Adhesive Tests in Support of Mass Timber Buildings DES604 Jason Smart, P.E. Manager, Engineering Technology American Wood Council Sam Francis, C.B.O. Senior Director, National Programs American Wood

More information

Fire-resistance test on fire collars protecting a concrete slab penetrated by services

Fire-resistance test on fire collars protecting a concrete slab penetrated by services INFRASTRUCTURE TECHNOLOGIES Fire-resistance test on fire collars protecting a concrete slab penetrated by services Test Report Author: Chris Wojcik Report number: FSP 1735 Date: 8 September 2016 Client:

More information

Laboratory study on the cooling effect of flash water evaporative cooling technology for ventilation and air-conditioning of buildings

Laboratory study on the cooling effect of flash water evaporative cooling technology for ventilation and air-conditioning of buildings Downloaded from orbit.dtu.dk on: May 5, 218 Laboratory study on the cooling effect of flash water evaporative cooling technology for ventilation and air-conditioning of buildings Fang, Lei; Yuan, Shu;

More information

- CONSTRUCTION FIRE SAFETY STANDARDS

- CONSTRUCTION FIRE SAFETY STANDARDS SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Hot Work Permits All construction sites shall implement a system of Hot Work Permits for all work activities that generate heat, sparks or flames. All of the

More information

Seminar on Standardisation in Research and Innovation Practical tools for the dissemination and implementation of research results

Seminar on Standardisation in Research and Innovation Practical tools for the dissemination and implementation of research results Seminar on Standardisation in Research and Innovation Practical tools for the dissemination and implementation of research results Brussels - 10 th November 2011 - Louis-Guy CAJOT DIFISEK & DIFISEK + DIssemination

More information

Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels

Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels Jack R. Mawhinney, P. Eng., FSFPE Javier J. Trelles, Ph.D. Authors & acknowledgement J. R. Mawhinney

More information

Materials Testing by Gregory Havel

Materials Testing by Gregory Havel Materials Testing by Gregory Havel July 24, 2017 One of the most common tests cited in the technical bulletins on building materials is ASTM E84 Standard Method of Test of Surface Burning Characteristics

More information

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS Jukka Vaari 1, Amit Lior 2 1 2 VTT Technical Research Centre of Finland, Espoo, Finland Marioff Corporation Oy, Vantaa,

More information

Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates

Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates Zhou Y., Fei Y.*, Hu S. Q. Nanjing Tech University, College of Fire Safety Science and Engineering &

More information

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM , Volume 11, Number 2, p.43-48, 2012 NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM Q. Kui Institute of Building Fire Research, China Academy of Building Research, Beijing,

More information

- CONSTRUCTION FIRE SAFETY STANDARDS

- CONSTRUCTION FIRE SAFETY STANDARDS SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Construction Planning All construction sites shall plan and sequence their construction activities to ensure the early installation and operation of permanent

More information

Indoor Climate Control Effect of AAC Panel Heat Capacity Experimental rooms and simulations with three structural materials

Indoor Climate Control Effect of AAC Panel Heat Capacity Experimental rooms and simulations with three structural materials Indoor Climate Control Effect of AAC Panel Heat Capacity Experimental rooms and simulations with three structural materials YUKO TSUKIYAMA 1, NOBUYUKI SUNAGA 2, AKIKO SUZUKI 2, TAMAKI FUKAZAWA 2, YOSUKE

More information

Fire Scenario Influence of Material of Boundary Condition on Results

Fire Scenario Influence of Material of Boundary Condition on Results Fire Scenario Influence of Material of Boundary Condition on Results HUGHES ASSOCIATES EUROPE, srl FIRE SCIENCE & ENGINEERING Luciano Nigro Andrea Ferrari Elisabetta Filippo Hughes Associates Europe srl

More information

PERFORMANCE OF PASSIVE FIRE PROTECTION IN JET FIRES

PERFORMANCE OF PASSIVE FIRE PROTECTION IN JET FIRES PERFORMANCE OF PASSIVE FIRE PROTECTION IN JET FIRES L. C. Shirvill Shell Research Ltd., Thornton Research Centre, P.O. Box 1, Chester CHI 3SH Emergency Shutdown Valves on offshore oil and gas risers must

More information

A Study into the Standardization of Using Fire Detectors in Rail Vehicles for China

A Study into the Standardization of Using Fire Detectors in Rail Vehicles for China Available online at www.sciencedirect.com Procedia Engineering 52 ( 2013 ) 240 244 A Study into the Standardization of Using Fire Detectors in Rail Vehicles for China LIU Xiao-lu *, WANG Wen-qing Shenyang

More information

COMPARISON OF CFD MODELLING WITH FIRE TESTS Comparison of CFD Modelling with Results of Full Scale Compartment Fire Tests in a Residential Unit

COMPARISON OF CFD MODELLING WITH FIRE TESTS Comparison of CFD Modelling with Results of Full Scale Compartment Fire Tests in a Residential Unit Application of Structural Fire Engineering, 19-20 April 2013, Prague, Czech Republic COMPARISON OF CFD MODELLING WITH FIRE TESTS Comparison of CFD Modelling with Results of Full Scale Compartment Fire

More information

INDIVIDUAL APARTMENT SUBSTATION TESTING DEVELOPMENT OF A TEST AND INITIAL RESULTS

INDIVIDUAL APARTMENT SUBSTATION TESTING DEVELOPMENT OF A TEST AND INITIAL RESULTS INDIVIDUAL APARTMENT SUBSTATION TESTING DEVELOPMENT OF A TEST AND INITIAL RESULTS Martin Crane CEng 1, 1 Carbon Alternatives Ltd Keywords: district heating, substation, low return temperature, performance

More information

Fire Collars for Floor Wastes Understanding BCA Compliance Options

Fire Collars for Floor Wastes Understanding BCA Compliance Options Fire Collars for Floor Wastes Understanding BCA Compliance Options February 2005 Introduction There has been a great deal of discussion in recent times regarding fire testing requirements for fire collars

More information

EFFECT OF CENTRAL PILE IN INCREASING THE BEARING CAPACITY OF BORED PILE GROUPS

EFFECT OF CENTRAL PILE IN INCREASING THE BEARING CAPACITY OF BORED PILE GROUPS EFFECT OF CENTRAL PILE IN INCREASING THE BEARING CAPACITY OF BORED PILE GROUPS Mohamed M. Shahin Department of Civil Engineering, 7 th October University, Misurata,, Libya, E-mail: Mohamed_zubi@yahoo.com

More information

Recent BRANZFIRE enhancements and validation

Recent BRANZFIRE enhancements and validation Recent BRANZFIRE enhancements and validation Michael Spearpoint University of Canterbury Summary BRANZFIRE is a multi-compartment fire zone model that has been under development since 1996 predominately

More information

Fire Suppression Performance of Manually Applied CAF and Other Water Based System

Fire Suppression Performance of Manually Applied CAF and Other Water Based System Fire Suppression Performance of Manually Applied CAF and Other Water Based System Andrew Kim and George Crampton Fire Suppression Research and Applications A Technical Working Conference (SUPDET2012) Outline

More information

Method for testing the suppression performance of fire suppression systems installed in engine compartments of buses and coaches

Method for testing the suppression performance of fire suppression systems installed in engine compartments of buses and coaches 2014-09-19 SP Method 4912 Method for testing the suppression performance of fire suppression systems installed in engine compartments of buses and coaches 2014-09-19 page 2 (17) Copyright This test method

More information

Kjell Wahlbeck the Fire Chief of Södra Älvsborg Fire & Rescue Services (SERF):

Kjell Wahlbeck the Fire Chief of Södra Älvsborg Fire & Rescue Services (SERF): Press Release issued by SERF on 12 March 2010 Södra Älvsborg Fire & Rescue Service (SERF), Sweden, has in collaboration with the SP Technical Research Institute of Sweden conducted scientific studies and

More information

A study of Transient Performance of A Cascade Heat Pump System

A study of Transient Performance of A Cascade Heat Pump System Available online at www.sciencedirect.com ScienceDirect Energy Procedia 79 (2015 ) 131 136 2015 International Conference on Alternative Energy in Developing Countries and Emerging Economies A study of

More information

Fire Resistance of Timber Structures

Fire Resistance of Timber Structures Fire Resistance of Timber Structures Dr. Andrea Frangi ETH Zurich, Institute of Structural Engineering (IBK), Switzerland Presentation at ENEM09 Coimbra, October 29, 2009 Datum Use of timber as building

More information

Durability of the Reaction to Fire Performance for FRT Wood Products in Different End Use Applications A Ten Years Report

Durability of the Reaction to Fire Performance for FRT Wood Products in Different End Use Applications A Ten Years Report Durability of the Reaction to Fire Performance for FRT Wood Products in Different End Use Applications A Ten Years Report Birgit A.-L. Östman 1 Lazaros D. Tsantaridis 2 ABSTRACT A long term experimental

More information

SAFE CABLING SYSTEMS IN TUNNELS UNDER FIRE

SAFE CABLING SYSTEMS IN TUNNELS UNDER FIRE - 249 - SAFE CABLING SYSTEMS IN TUNNELS UNDER FIRE Urs Welte Amstein + Walthert AG, Switzerland ABSTRACT The paper aims at a detailed analysis of the current know-how in the construction of tunnel cabling

More information

PART 1 THERMAL & MECHANICAL ACTIONS. DIF SEK Part 1: Thermal & Mechanical Actions 0/ 50

PART 1 THERMAL & MECHANICAL ACTIONS. DIF SEK Part 1: Thermal & Mechanical Actions 0/ 50 DIF SEK PART 1 THERMAL & MECHANICAL ACTIONS DIF SEK Part 1: Thermal & Mechanical Actions 0/ 50 Background of the RFCS Project DIFISEK+ This project is funded by the European Commission in the frame of

More information

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN , Volume 6, Number 4, p.248-254, 04 RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN C.L. Choi Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Water

More information

Laboratory fire experiments with a 1/3 train carriage mockup

Laboratory fire experiments with a 1/3 train carriage mockup SP Technical Research Institute of Sweden Laboratory fire experiments with a 1/3 train carriage mockup Alexander Claesson, Anders Lönnermark, Haukur Ingason, Johan Lindström, Ying Zhen Li and Mia Kumm

More information

Sprinklers in Combustible Concealed Spaces

Sprinklers in Combustible Concealed Spaces Sprinklers in Combustible Concealed Spaces G.D. Lougheed and J.K. Richardson Fire Research Section Institute for Research in Construction National Research Council Canada Ottawa, Ontario SUMMARY NFPA 13

More information

Behaviour of an Intumescing System Subjected to Different Heating Conditions. Johansson, Nils; Van Hees, Patrick; Jansson, Robert; Sjöström, Johan

Behaviour of an Intumescing System Subjected to Different Heating Conditions. Johansson, Nils; Van Hees, Patrick; Jansson, Robert; Sjöström, Johan Behaviour of an Intumescing System Subjected to Different Heating Conditions Johansson, Nils; Van Hees, Patrick; Jansson, Robert; Sjöström, Johan Published in: Fire and Materials - 13th International Conferance

More information

Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan

Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan Open Journal of Fluid Dynamics, 2017, 7, 205-218 http://www.scirp.org/journal/ojfd ISSN Online: 2165-3860 ISSN Print: 2165-3852 Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke

More information

Experiments to Validate the NRCC Smoke Movement Model for Fire Risk-Cost Assessment

Experiments to Validate the NRCC Smoke Movement Model for Fire Risk-Cost Assessment Experiments to Validate the NRCC Smoke Movement Model for Fire Risk-Cost Assessment AKIHIKO HOKUGO Building Research Institute Ministry of Construction Tatehara I, Tsukuba-City 305, Japan DAVID YUNG and

More information

Analysis of Pullout Resistance of Soil-Nailing in Lateritic Soil

Analysis of Pullout Resistance of Soil-Nailing in Lateritic Soil Analysis of Pullout Resistance of Soil-Nailing in Lateritic Soil B,L.A. Isaka 1, B.C. Madushanka 1 and N.H. Priyankara 1 1 Department of Civil and Environmental Engineering Faculty of Engineering University

More information

The cooling capacity of the Thermo Active Building System combined with acoustic ceiling

The cooling capacity of the Thermo Active Building System combined with acoustic ceiling The cooling capacity of the Thermo Active Building System combined with acoustic ceiling Peter Weitzmann, Technical consultant, BuildDesk A/S; peter.weitzmann@builddesk.dk Emanuele Pittarello, MSc, International

More information

Evaluation of Liquid Water Content in Thermal Efficient Heating Mechanism Using Water Vapor for Industrial Furnace

Evaluation of Liquid Water Content in Thermal Efficient Heating Mechanism Using Water Vapor for Industrial Furnace Journal of Mechanics Engineering and Automation 7 (2017) 160-164 doi: 10.17265/2159-5275/2017.03.005 D DAVID PUBLISHING Evaluation of Liquid Water Content in Thermal Efficient Heating Mechanism Using Water

More information

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings Justin A. Geiman, Noah L. Ryder Fire & Risk Alliance, Rockville, MD, USA André W. Marshall Custom Spray Solutions, Silver Spring,

More information

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Ad-hoc IEC 60331-2 x Ad-hoc investigation

More information

Sprinklers Modeling for Tunnel Road Fire Fighting

Sprinklers Modeling for Tunnel Road Fire Fighting Sprinklers Modeling for Tunnel Road Fire Fighting P. Ciambelli, M.G. Meo, P. Russo, S. Vaccaro Department of Chemical and Food Engineering, University of Salerno - ITALY 1. INTRODUCTION Loss of lives and

More information

CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL?

CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL? CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL? Marcelo M. Hirschler GBH International, USA ABSTRACT The results of three

More information

Specific Energy Consumption comparative study of Hot Air dryer and Heat Pump dryer for highland drying process Sayompon Srina

Specific Energy Consumption comparative study of Hot Air dryer and Heat Pump dryer for highland drying process Sayompon Srina Specific Energy Consumption comparative study of Hot Air dryer and Heat Pump dryer for highland drying process Sayompon Srina Department of Mechanical Engineering, Faculty of Engineering, King Mongkut

More information

Hot-air distribution in the floor heating

Hot-air distribution in the floor heating Agronomy Research 13(2), 494 499, 2015 Hot-air distribution in the floor heating P. Kic Czech University of Life Sciences Prague, Faculty of Engineering, Kamycka 129, CZ16521 Prague 6, Czech Republic;

More information

THE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS

THE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS THE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS Panu Mustakallio 1, Arsen Melikov 2, Marcin Duszyk 2, Risto Kosonen 1 1 Oy Halton Group Ltd., Helsinki, Finland. 2 International

More information

Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly

Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly ASTM E119-98: Standard Test Methods for Fire Tests of Building Construction and Materials* *Research-scale horizontal

More information

FIRE PROTECTION FOR NON-STORAGE OCCUPANCIES WITH HIGH CEILING CLEARANCES

FIRE PROTECTION FOR NON-STORAGE OCCUPANCIES WITH HIGH CEILING CLEARANCES FIRE PROTECTIO FOR O-STORAGE OCCUPACIES WITH HIGH CEILIG CLEARACES SOOIL AM, ATOIO BRAGA, HSIAG-CHEG KUG, and JOA M. A. TROUP FM Global Research, 1151 Boston-Providence Turnpike, orwood, Massachusetts

More information

Department for Communities and Local Government Research Report:

Department for Communities and Local Government Research Report: Department for Communities and Local Government Research Report: BD 2890 Investigation of real fires - Electrical consumer unit fire experiments 293761 (E3V2) CPD/04/102/027 Prepared for: Brian Martin

More information

Title: Indicative fire test. WF Report No: /A. Prepared for: Hoody Speaker Hoods Ltd

Title: Indicative fire test. WF Report No: /A. Prepared for: Hoody Speaker Hoods Ltd Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: Indicative fire test WF Report

More information

Tech Notes. TESTING PROTOCOL Fire Retardant Gel Coats. INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5

Tech Notes. TESTING PROTOCOL Fire Retardant Gel Coats. INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5 INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5 5 Tech Notes TESTING PROTOCOL Fire Retardant Gel Coats Issue Date: 4/22/2010 Document ID: TN-TS-05A 2010 Interplastic Corporation Testing Protocol

More information

EMPIRICAL MODEL SIMULATING RAINWATER HARVESTING SYSTEM IN TROPICAL AREA

EMPIRICAL MODEL SIMULATING RAINWATER HARVESTING SYSTEM IN TROPICAL AREA EMPIRICAL MODEL SIMULATING RAINWATER HARVESTING SYSTEM IN TROPICAL AREA Thamer Ahmad Mohammad, Abdul Halim Ghazali, Megat Johari Megat Mohd. Noor Department of Civil Engineering, Faculty of Engineering,

More information

SCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS

SCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS , Volume 11, Number 2, p.21-26, 212 SCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS C.Y. Tso and W.K. Chow Research Centre for Fire Engineering,

More information

This document is a preview generated by EVS

This document is a preview generated by EVS TECHNICAL REPORT RAPPORT TECHNIQUE TECHNISCHER BERICHT CEN/TR 15310-2 November 2006 ICS 13.030.10; 13.030.20 English Version Characterization of waste - Sampling of waste materials - Part 2: Guidance on

More information

CFD Model of a Specific Fire Scenario

CFD Model of a Specific Fire Scenario 16 th Australasian Fluid Mechanics Conference Crown Plaza, Gold Coast, Australia 2-7 December 27 CFD Model of a Specific Fire Scenario D. Mackay, T. Barber and E. Leonardi School of Mechanical and Manufacturing

More information