BOOST8n. Technical Data Sheet. Domestic fire sprinkler pump system complying with and significantly surpassing BS
|
|
- Jason Hodges
- 6 years ago
- Views:
Transcription
1 Technical Data Sheet BOOST8n Domestic fire sprinkler pump system complying with and significantly surpassing BS Industry leading fire sprinkler pump system with plc control and simple LCD screen with product and system information Automatic weekly testing is carried out on the fire pump and the starting pressure switches (as EN12845). Any failure is reported via a fault output and displayed on screen providing reliability and resilience Screen showing the weekly test has passed P1 pressure switch 1 went low pressure P2 pressure switch 1 went low pressure P1H pressure switch 2 returned healthy P2H pressure switch 2 returned healthy Our innovative flow control system shows our understanding of domestic fire sprinkler installations and problems contractors need to overcome. Flow controlled pumps can reduce tank size, saving valuable space and upfront costs (for town main boosting see page 4) The pump acts as a jockey pump and then a fire pump if required, with an automatic cooling line (as EN12845) Engineers know what's happening with the system at all times NEW PRODUCT FEATURES The flow switch gives a fault signal when the pump is latched then a 20 second flow counter displays on screen until the fire alarm signal is given, reducing false alarms as the British standard demands PRODUCT FEATURES Two pressure switches giving switch backup (as EN12845) Failsafe wiring the pressure switch circuits will operate the pump if they go open circuit (as EN12845) Jockey pump the pump will operate for 8 seconds to remake pressure loss Fire pump the pump will operate if pressure is not maintained after a jockey run, with LCD and fault indication Comprehensive Combined Alarms; Weekly test failed, jockey limit, fire pump on demand (EN12845), annual test due and power failure- available as open on fault, SPDT optional Auto Cooling, if the fire pump operates, the solenoid valve opens every 20 seconds for 2 seconds to cool the impeller ensuring functionality even when a property is unoccupied. Automotive technology, a black electrophoretic bonded paint finish is applied to the pipe work inside and out, giving better protection and an attractive finish LPCB approved fire rated power and alarm cables Tel: +44 (0) sales@grifen.co.uk
2 FLOW CONTROL SYSTEM are a fire sprinkler product designer and manufacturer, not a pump manufacturer and we understand the regulations of systems and the implications on site, as a result we are able to provide systems that work for you and the end user. Our two unique flow controlled pump sets (B and B230-25/85) give the following benefits; Cavitation of the pump is not possible Q max is limited allowing tank size to be more easily calculated and reduced in size The product is configured for tank fed systems and is designed to give better functionality than BS and excellent competitiveness. NEW BOOST8n FEATURES Weekly test failed (updated), now remembered on screen after power down, if the householder turns off the power a small black square remains on the screen until the next weekly test is passed, the fault alarm will stay on during power fail and return when power is reapplied Solenoid activation displayed every time the solenoid operates SOL appears on screen Flow switch pre wired with plc controlled delay and visual LCD 20 second counter, when the pump is latched and the flow counter reaches 20 seconds the fire alarm contact changes state, This alarm operates when the fire pump is on demand reducing false alarms as required by BS FIRE ALARM silencing If filling/ refilling a system the fire alarm will trigger after 20 seconds of flow but you can silence it very easily before it even operates, so no need to go off watch/ cause disturbance), it can t be silenced at any other time. ANNUUAL SERVICE force on the service facility can be forced on ahead of time allowing improved planning of time ANNUAL SERVICE silencing, the annual service fault can be silenced for 2 weeks at a time Button depressed when the button is pressed appears on screen allowing you to know for certain the button is pressed and allowing accurate timing TOWN MAIN BOOSTING BOOST8n can be configured for town main boosting. We need to know; Flow rate from the main is higher than the pump can deliver The static pressure of the main in order to set the pressure switch correctly, please note if the main has a high static pressure we may have to fit a different pressure gauge and switch. To use the town main you will need permission from the water board and fit a suitable non return valve on the incoming supply The solenoid will always dump water every week, as a responsible company we would recycle that waste water, we hope you will do the same The maximum pressure of the pump and main must be below 10 bars OTHER CONSIDERATIONS Alarm obligations under BS9251:2014 Fault alarm required for: power failed (monitored by BOOST8n as standard) automatic test failed (monitored by BOOST8n as standard) Low water level (optional if you want us to monitor it, the fault will be displayed on screen and transmitted on the fault signal) Must be heard or seen in occupied part of building. All electrically operated alarm devices should be capable of carrying out their function in the event of a complete failure of the mains electrical power supply.
3 STATUS INDICATORS AND ALARMS Events are displayed on the LCD screen and the fault alarm covering the following conditions to make fault finding simpler; Jockey stop/ start alarm - Check for possible leaks Weekly test failed pump, contactor, solenoid, pressure switch failure Weekly test passed LCD only Fire pump latched (pump on demand EN12845) Annual service due/ failed keeps the system in compliance annually, with your company name and phone number Power supply warnings AC failure (also 24VDC with optional tank low level SET UP AND SELF COMMISSIONING The pump will run until both pressures are healthy and there is no more flow. The filling sequence will stop after 2 minutes, enabling the system to go into auto mode, enabling the fault alarm to be active if needed P U M P P U R G E D P U M P W I L L S T A R T P 1 P 2 A start up screen gives anyone the chance to switch off if not purged/ valves open etc When the pump starts it displays this screen (right) during filling if any input device is unhealthy it will display in real time and extinguish when healthy. P1 pressure switch number 1 P2 Pressure switch number 2 FS flow switch and its operational time P U M P R U N & F I L L I N G P 1 P 2 F S L L The fire signal will trigger after 20 seconds of continuous flow, the fire signal can be disabled for the fill period which is 2 minutes. A new feature brings the product out of fill mode ensuring the pump could latch and give the fault alarm if necessary. NORMAL OPERATION When the system is OK, the time and date flash intermittently. The product s weekly test is time and date stamped by this clock. The jockey pump function is operational for the first time this hour, it has run for 5 of its 8 second run time (centre below) If the jockey pump operates more than 8 times in an hour JOCKEY LIMIT appears on the screen and fault alarm and screen can be cleared A U T O M O D E A U T O M O D E A U T O M O D E S Y S T E M O K J O C K E Y N O 1 J O C K E Y 1 8 / 0 5 / T I M E 5 / 8 L I M I T 1 The product keeps a count of the number of times it starts as a jockey pump. This aims to give pre failure warnings due to any system or product leaks. The jockey counter resets every hour if less than 8 starts have occurred. The system will keep a count of the number of times jockey limit has been reached, shown in the bottom right of the screen, it can not be cleared
4 THE AUTOMATIC WEEKLY TEST SUPASSING BS BASED ON EN12845 PRINCIPALS TESTED AUTOMATICALLY every Monday at 10am PRESSURE DROP TEST PEFORMED (EN12845) 2 NORMALLY CLOSED PRESSURE SWITCHES TESTED ON EACH PUMP (EN12845) ALARM IN FAILURE OR POWER DOWN SIMPLE RECORD KEPT IF ALL CONDITIONS ARE NOT HEALTHY ON DEMAND WEEKLY TEST AT ANY TIME REQUIRED A U T O M O D E W E E K L Y T E S T F A I L P 1 WEEKLY TEST The system is in automatic mode, but the last weekly test failed The cause of the failure was P1. The system can also indicate P2 failure or both. P1 or P2 will fail if they don t go unhealthy during the solenoid drain, they must be healthy at the end of the pump run sequence, The black square in the corner indicates this weekly test has failed. If the power is cycled and this square is on the screen, the last test failed. The square will only extinguish and the alarm clear when a successful test is completed. A weekly test will always repeat the next week, whether it passed or failed The pump can be tested manually at any time (by following a simple step, the auto test will then be repeated) NB If service is due on screen a 6 minute service run will take priority, the auto test will still take place. To perform a manual on demand weekly test a successful service must be performed first. FIRE PUMP AND ALARMS P U M P L A T C H E D + F I R E A L A R M P 1 F A U L T S O L P 1 F S 2 0 PUMP LATCHED (fault alarm condition changed state),(en fire pump on demand) the pump will now run continually until switched off at the mains +FIRE ALARM indicates the flow switch has been flowing for 20 seconds, the fire alarm signal will now have changed state SOL The solenoid is cooling the pump P1 fault (could also indicate P2 or both) this indicates which pressure switch was unhealthy when the pump latched after the jockey sequence P1 (bottom row) indicates P1 is currently at low pressure (could also indicate P2) ANNUAL SERVICE A U T O M O D E S E R V I C E D U E 1 9 / 0 5 / When an annual service is due the screen will scroll with the purchasers name and phone number when this occurs the general alarm will change state. To reset the annual service (beyond silencing) screen and alarm a successful test must be carried out. The annual test must check the correct function of the pump and all the switches. If it passes the unit will warn again in 12 months, if fails it will alarm and must be repeated and pass to clear the fault SERVICES to be carried out by fire sprinkler companies, ensuring ongoing compliance with BS If an annual service is not carried out the system will still function as normal. At any time when the annual test is carried out correctly the alarm will silence for one year. The pump system can be forced to do an annual service before it is due, BOOST8n will call for a service in 1 year regardless of whether it is forced on or not If the pump is switched off the power failed alarm will operate. When power is restored the device will remember its last annual status and operate the alarm if a test remains due. The sprinkler system can remain pressurised at all building levels when maintenance is being carried out. The flow test can be carried out on the pump only ensuring the motor and impeller are capable of the duty at the correct pressure, ignoring any hydrostatic head. Tel: +44 (0) sales@grifen.co.uk
5 SPECIFIERS GUIDE TO UNIQUE FEATURES WEEKLY PRESSURE DROP TEST PEFORMED (as EN12845) WEEKLY TEST FAILURE REPORTED with on screen indication as to the cause BACKUP PRESSURE SWITCHES wired (as EN12845) LCD SCREEN PUMP ON DEMAND AUTO COOLING (this feature cools the pump in the case of people being away from the house/ it has saved many pumps in the field over the years) JOCKEY PUMP MONITORING PLC WITH ELCTRONICALLY CONTROLLED FLOW SWITCH GENERATED FIRE ALARM AND VISUAL TIME COUNTER, complete with silence facility on initial fill ANNUAL SERVICE WARNING ANTI TAMPER ALARMS, (remembers service due and weekly test failed after power down until they are satisfied, also alarms when switched off) PLC technology requires no input or intervention when monitoring your fire sprinkler system. Where alarms are referred to volt free contacts are provided, these must be connected to suitable battery backed up alarms on site. We reserve the right to make technical adjustments to the specifications, we are happy to discuss site specific modifications/ technical improvements. Below; Prewired flow switch with LPCB approved FP200 fire rated cable with super accurate PLC controlled time delay FLOWST8n offers higher flow rates and pressures for residential applications, local mist system protection, suction lift capability. We also manufacture integrated duty/ backup pumps and supply uninterruptable power systems. DUPLIC8 offers either 2 x 1/2 or 2 x full duty fully integrated intelligent pump package We also manufacture low pressure water mist pump systems PRODUCT OPTIONS Your scrolling service message with your telephone number (included as a no cost option) Monitored valves Integrated battery backed up fault and fire alarm system, we can manufacture this as a complete turnkey kit, please contact us if you would like us to bring this to market CHOOSING YOUR PUMP We are here to help, please feel free to call and ask for advice. We have laid out all the BOOST8n pumps on one easy read graph (page 7), the following pages give the three variations with finer detail including electrical data etc. Dont forget you now need to use a fuse of high rupturing capacity, MCBs are not permitted Below: Screen showing FS20 with a PLC counter and super accurate electronic delay SOL shows the solenoid is active in cooling or weekly test P U M P L A T C H E D + F I R E A L A R M P 1 F A U L T S O L P 1 F S 2 0 Tel: +44 (0) sales@grifen.co.uk
6 BOOst8n series Grifen sprinkler solutions Standard BOOST8n BOOST8n options BOOST8n high flow B230-25/ bar B bar BH bar B bar B bar BH bar B bar B bar BH bar B bar B bar BH bar
7 Boost8n delivery data Pressure (bar) Flow Rate (litres/min) BOOST8n series Model Duty Voltage Kw Full load current (amps) Inlet Outlet B230-25/ bar B bar B bar B bar
8 Boost8n BH pumps Pressure (bar) Flow Rate (litres/min) BH series Model Duty Voltage Kw Full load current (amps) Inlet Outlet BH bar BH bar BH bar BH bar
9 Boost8n option pumps Pressure (bar) Flow Rate (litres/min) BOOST8n options Model Duty Voltage Kw Full load current (amps) Inlet Outlet B bar B bar B bar B bar
10 Technical Specifications Model Flow at duty point Qmax H max VAC kw Full Load Current (Amps) inlet outlet test Suction centre line (mm) B bar 112 l/min 5.0 bar /4 115 B230-25/ bar 102 l/min 5.0 bar /4 115 B bar 130 l/min 5.0 bar /4 115 B bar 150 l/min 5.4 bar /4 140 B bar 120l/min 6.3 bar /4 166 B bar 130 l/min 5.8 bar /4 90 B bar 130l/min 6.9 bar /4 90 B bar 130 l/min 8.1 bar /4 90 BH bar 165 l/min 3.6 bar BH bar 205 l/min 4.8 bar BH bar 212 l/min 6.0 bar BH bar 220 l/min 7.2 bar WHO WE ARE were started in 1999 as a sole trader, we became a limited company some 8 years later, we are an innovative provider of electro mechanical sprinkler products We design all our own products and software and we are happy to make changes/ develop products which you may require, our in-house capabilities are all value added UK skills Our ethos is improve where possible you will see from this new software package that this is action and not just words, we want to make things better. The testing of our products at design stage is based on the principals of introducing failures and mitigating against them wherever possible, you may not be aware of those details, but they are there and are likely to be unique product features which give robustness and reliability for your system. Example, we set out with the idea what are we trying to do? that has resulted in; backup pressure switches not required but the rules could be critical one day Failsafe wiring of the pressure switches not covered by rules but could be critical one day Uncommanded starts; we provide pump cooling, we know people leave houses unattended, if a faulty cable starts and runs the pump it could be destroyed on your return or worse, this feature has save countless pumps from burning out, and leaves the pump available for fire fighting if required By calling us you will receive technical support to guide you through any problems you may have Please give us a call and arrange to visit our demo room where you can try these features for yourself Tel: +44 (0) sales@grifen.co.uk
6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL
6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0)
More informationIntelligent Security & Fire Ltd
full installation, commissioning and operating manuals can be downloaded from www.haes-systems.co.uk combined addressable / conventional fire alarm control panel User Guide Approved Document No. MFBU-04
More information3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL
3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273 Web:
More informationVersion 1.03 January-2002 USER S MANUAL
Version 1.03 January-2002 1 USER S MANUAL 2 Version 1.03 January-2002 System Details CUSTOMER:...... PHONE:... FAX:... INSTALLED BY:...... PHONE:... FAX:... MAINTENANCE & SERVICE:...... PHONE:... FAX:...
More informationhighline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10
highline WINDOW CONTROLS INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM SVCS-1 * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10 CERTIFICATE OF COMPLIANCE SVCS-1 We the undersigned
More information3500 CONVENTIONAL FIRE ALARM CONTROL PANEL
3500 CONVENTIONAL FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273 Web:
More informationSolution Ultima Series Operators Manual ISSUE 1.00
Solution Ultima Series Operators Manual ISSUE 1.00 Solution Ultima Series Operators Manual Copyright 1998 by, SYDNEY, AUSTRALIA Document Part Number MA488O DOCUMENT ISSUE 1.00 Printed 16 February 1999
More information2000 SERIES DIAGNOSTIC ALARM CONTROL SYSTEM
2000 SERIES DIAGNOSTIC ALARM CONTROL SYSTEM OPERATING INSTRUCTIONS MODELS: 2300 2500 2700 This information is relevant to systems fitted with Issue 4.1 (or later) Master Keypad Software, also to Networked
More informationGas Safety Products. Installation, operating and maintenance. Merlin 1000S+i Gas & Electric Utility Controller. Rev: 03 Date:
Gas Safety Products Merlin 1000S+i Gas & Electric Utility Controller Installation, operating and maintenance Rev: 03 Date: 14-08-18 1 Table of contents 1 General information... 3 2 Installation... 3 2.1
More informationST9400S User Guide. 1 Day Programmer, 2 channel With Boiler Service Reminder / Shut-down Feature
PLEASE RESPECT YOUR ENVIRONMENT! Take care to dispose of this product and any packaging or literature in an appropriate way WHAT IS A PROGRAMMER?...an Explanation for Householders (as recommended by the
More informationUser s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas
User s Manual TIGER S EYE E-Series Mark V Jockey TIGERFLOW Systems, Inc. 4034 Mint Way Dallas, Texas 75237 214-337-8780 www.tigerflow.com TABLE OF CONTENTS Introduction... 4 Sequence of Operation... 5
More informationREPEATER FS5200R OPERATION MANUAL
REPEATER FS5200R OPERATION MANUAL 1. Function Repeater FS5200R receives and transmits data for Fire condition and Fault condition from remote fire control panels (repeaters) and provides information about
More informationUSER MANUAL & MAINTENANCE GUIDE OG OO
M+48. USER MANUAL & MAINTENANCE GUIDE OG OO What to do if the Fire Alarm Panel shows an Alarm (Red LED) Write down which LEDs are lit (either in the log book, or on a piece of paper for transferring to
More information5000 SERIES 8 ZONE INSTRUCTION MANUAL
5000 SERIES 8 ZONE INSTRUCTION MANUAL NESS SECURITY PRODUCTS 4/167 PROSPECT HIGHWAY SEVEN HILLS. 2147 NSW AUSTRALIA SYDNEY Phone: (02) 8825 9222 (Head Office) BRISBANE Phone: (07) 3343 7744 MELBOURNE Phone:
More informationZP3 Operator & Maintenance Manual Version 1
ZP3 Operator & Maintenance Manual Version 1 Introduction Thank you for selecting Clymac Ltd. Clymac can provide maintenance for the system, emergency call out, telephone support and any modifications required
More informationAlgo-Tec 6500/6600 INTERACTIVE ADDRESSABLE FIRE CONTROL SYSTEM
Algo-Tec 6500/6600 INTERACTIVE ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) USER MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND +44 (0) 1282 717171 www.protec.co.uk
More informationBaxi Maxflow Combi FS
Baxi Maxflow Combi FS Gas Fired Floor Standing Combination Boiler with Unvented Hot Water Storage Please keep these instructions safe. Should you move house, please hand them over to the next occupier.
More informationBaxi Maxflow Combi WM
Baxi Maxflow Combi WM Gas Fired Wall Mounted Combination Boiler with Unvented Hot Water Storage Please keep these instructions safe. Should you move house, please hand them over to the next occupier. User
More informationU ser's Guide PC6010
User's Guide PC6010 Quick Reference Guide This manual is for Basic and Advanced users. Each of these types of user can access a different set of functions. The and symbols next to the title of each procedure
More informationCERAMIC HEATER MODEL NO: DEVIL 350B 230V/110V OPERATING & MAINTENANCE INSTRUCTIONS PART NO: & ORIGINAL INSTRUCTIONS GC ISS 1
CERAMIC HEATER MODEL NO: DEVIL 350B 230V/110V PART NO: 6920330 & 6920332 OPERATING & MAINTENANCE INSTRUCTIONS ORIGINAL INSTRUCTIONS GC1218 - ISS 1 INTRODUCTION Thank you for purchasing this CLARKE Ceramic
More informationControl Panel User Guide
Fire Detection & Alarm System Control Panel V4.14 Control Panel User Guide (TO BE RETAINED BY USER) 26-0397 Issue 6 Fike s policy is one of continual improvement and the right to change a specification
More informationFire Alarm Control Panel. System Maintenance and Log Book
Fire Alarm Control Panel System Maintenance and Log Book Fire Alarm System Maintenance A fire alarm system must provide early and reliable warning of the outbreak of fire. To achieve this, the system remains
More informationDL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL
DL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. GENERAL DESCRIPTION... 2 2. STANDARD AND OPTIONAL PARTS LIST... 2 3. FEATURE DEFINITIONS... 3 4. TERMINAL DRAWING AND SPECIAL
More informationSolution Ultima 862 Operators Manual ISSUE 1.10
Solution Ultima 862 Operators Manual ISSUE 1.10 Solution Ultima 862 Operators Manual Copyright 2001 by, SYDNEY, AUSTRALIA Document Part Number MA486O DOCUMENT ISSUE 1.10 Printed 24 April 2001 This documentation
More informationHA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE
D (OPERATION) INITIATE A DYNAMIC BATTERY TEST The system tests the back-up battery once every 24 hours. The owner can initiate a dynamic battery test at any time with the following codes while the system
More informationREPEATER FS5200R INSTRUCTION MANUAL
REPEATER FS5200R INSTRUCTION MANUAL Instruction Manual Page1 CONTENTS 1. Introduction... 3 2. Function... 3 3. Technical data... 3 4. Contents of delivery... 4 5. General information... 5 6. Duty Mode...
More informationZX1e ZX2e ZX5e. Document No Issue 01 user manual
ZX1e ZX2e ZX5e Document No. 996-130 Issue 01 user manual MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels Table of Contents 1 INTRODUCTION... 4 1.1 NOTICE... 4 1.2 WARNINGS AND CAUTIONS... 4 1.3 NATIONAL
More informationInstallation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels
Installation and user manual for the FX range of fire panels 1, 2, 4 and 8 zone panels Contents Panel installation 3 Panel connections 3 Wiring connection drawings 4 Panel facilities 6 Installation check
More informationDIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)
DIESEL ENGINE CONTROL UNIT DCU 205 - USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) 64 84 52 00 Fax: (+47) 64 84 52 12 office@auto-maskin.no - 1 - TABLE OF CONTENTS 1. INTRODUCTION TO THE DCU 205...4
More informationPARAGON PLUS USER INSTRUCTIONS USER INSTRUCTIONS J?>5 J?>5 J?>5 J?>5 J?>5 J?>5 B??=
D D D < USER INSTRUTIONS USER INSTRUTIONS PYRONIX LIMITED JULY 2000 RINS 154 Issue-1 INSTALLATION OMPANY: TEL: ADDRESS: ONTAT: PARAGON D * PLUS &J?>5@B?7B1==9>7D1DE5 J?>5 J?>5 J?>5 J?>5
More informationConventional Fire System. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual
Conventional Fire System BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual Contents Contents 1. INTRODUCTION... 3 1.1 Purpose...3 1.2 Definitions....3 Premises Management...
More informationSafety / Kit Components 1
Installation & Operation Manual Industrial Wall Control IWC0 (incorporating SmartHub and Fault Indicating features) Safety / Kit Components SAFETY Please read this manual carefully. Your failure to do
More informationBaxi Combi 133 HE Plus Baxi Combi 100 HE Plus Baxi Combi 80 HE Plus. User s Operating Instructions
User s Operating Instructions Baxi Combi 133 HE Plus Baxi Combi 100 HE Plus Baxi Combi 80 HE Plus Gas Fired Wall Mounted Condensing Combination Boiler Please keep these instructions safe. Should you move
More informationSmoke Vent Control Panel PCB4 V4 Installation Manual
Smoke Vent Control Panel PCB4 V4 Installation Manual 10A PCB4 Control Panel Do Not Remove From PCB4 Control Panel www.besafedirect.com Page 1 Contents Page 3) Important Regulations, Safety, Maintenance,
More informationUser's Instructions. Alpha CB50
User's Instructions Alpha CB50 Wall Mounted, Fan Assisted, Room Sealed, Gas Fired Combination Boiler with Unvented Hot Water Storage (From Boiler Serial No. 27B32500001) For Technical help or for Service
More informationCRX Single Zone Wireless Controller. Installation and User Guide. 1. Getting to know your CRX2 wireless controller
Please read this guide carefully and retain for future use and maintenance. CRX2-01 Single Zone Wireless Controller Installation and User Guide 1. Getting to know your CRX2 wireless controller An illustration
More informationPWM. Solar Charge controller with Ethernet. Solar Smart PWM 20Amp. Hardware Description : Release : 19 June 2014
Solar Charge controller with Ethernet Release : 19 June 2014 Hardware Version : Version 1 Firmware version 1 PC Application Software : Version 1.0.0.0 Hardware Description : The Solar Smart regulator was
More informationHOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4
HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4 INTRODUCTION Thank you for purchasing the Hokkim Integrated Automatic Mains Failure Control Board model HAMF- 8 or HAMF-4. We shall
More informationRANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL
RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION... 2 STANDARD AND OPTIONAL PARTS LIST... 2 PARTS DIAGRAM... 3 TERMINAL DRAWING AND SPECIAL NOTES...
More informationGas Safety Products. Installation, operating and maintenance. Merlin 1500S Gas Interlock System. Rev: 03 Date:
Gas Safety Products Merlin 1500S Gas Interlock System Installation, operating and maintenance Rev: 03 Date: 08-01-18 1 Table of contents 1 General information... 3 2 Installation... 3 2.1 Panel Mounting....
More informationIntroduction. OM-THA2
Introduction. The OM-THA2 is a multi-function product that monitors Temperature, Humidity and Dew Point, provides alarms for out of range conditions, and continuously logs data. It consists of a base unit
More informationSolution 880 Operators Manual. Issue 1.00
Solution 880 Operators Manual Issue 1.00 Solution 880 Operators Manual Copyright 1998 by, SYDNEY, AUSTRALIA Document Part Number MA408O Document ISSUE 1.00 Printed 15 June 1998 This documentation is provided
More informationSecurity System. User s Guide for the Text Command Center
User s Guide for the Text Command Center MY ALARM COMPANY IS: CALL BEFORE TEST: THIS SECURITY SYSTEM IS CONNECTED TO TELEPHONE NUMBER: THE SECURITY CONTROL PANEL IS CONNECTED TO THE PHONE JACK LOCATED:
More informationIntruder alarm panel Terxon MX Operating instructions
Intruder alarm panel Terxon MX Operating instructions Operating instructions Perfect Security for home and office These operating instructions are an important product accessory. They contain important
More informationBaxi Bahama 100. Gas Fired Wall Mounted Combination Boiler. User s Operating Instructions
Baxi Bahama 100 Please keep these instructions safe. Should you move house, please hand them over to the next occupier. Gas Fired Wall Mounted Combination Boiler User s Operating Instructions Natural Gas
More informationUser's Instructions. Alpha CD24C/32C. Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired, High Efficiency Condensing Combination Boilers
User's Instructions Alpha CD24C/32C Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired, High Efficiency Condensing Combination Boilers For Technical help or for Service call... ALPHA HELPLINE
More informationUser s Guide. SUB-MA7240O-0001.OG.Solution doc. Created: 6/05/03. Last Updated: 23/09/03. MA7240AO-0001 Version 1.0
User s Guide SUB-MA7240O-0001.OG.Solution40-111.doc Created: 6/05/03 Last Updated: 23/09/03 MA7240AO-0001 Version 1.0 2 Table Of Contents User List...6 Quick Reference..7 Features...7 Keypad User's Guide...8
More informationSyncro AS. Analogue Addressable Fire Control Panel. User Manual
Syncro AS Analogue Addressable Fire Control Panel User Manual Man-1100 Issue 02 Nov. 2008 Index Section Page 1. Introduction...3 2. Safety...3 3. Panel Controls...4 3.1 Access Level 1...4 3.2 Access Level
More informationINTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3
INTELLIGENT FIRE TECHNOLOGY Twinflex and Multipoint V3 User Guide (TO BE RETAINED BY USER) 26-0340 Issue 3 Rafiki Protection Limited Rafiki policy is one of continual improvement and the right to change
More informationThe Challenger. Quick Reference User Guide
The Challenger Quick Reference User Guide INTRODUCTION The Challenger panel combines sophisticated design with versatility. It is easy to user; and this, together with it s many other features, makes the
More informationZM2 OPERATING AND MAINTENANCE INSTRUCTIONS
ZM2 OPERATING AND MAINTENANCE INSTRUCTIONS CONTENTS 1. System Overview 2. User responsibilities 3. First Line controls and indications 3.1 Logging on to the fire alarm system 3.2 Checking system status
More informationGas Safety Products. Installation, operating and maintenance. Merlin 1000VW+ Gas Interlock, Gas Proving, Electric & Water Isolation System
Gas Safety Products Merlin 1000VW+ Gas Interlock, Gas Proving, Electric & Water Isolation System Installation, operating and maintenance Read these instructions carefully before operating or servicing
More informationAVANT DGi. Thermal Electric Radiator. Operating and Installation Instructions. (Read these instructions carefully and retain for future reference)
(v13. 20180906) MODE CONFIG. PROG. AVANT DGi Thermal Electric Radiator Operating and Installation Instructions (Read these instructions carefully and retain for future reference) Models: AVANT-DGi 350
More informationCRU-S Series Stainless Steel Condensate Recovery Unit
IM-UK-CRU-S UK Issue 1 CRU-S Series Stainless Steel Condensate Recovery Unit 1. Safety information 2. General product information 3. Installation 4. Commissioning 5. Storage, shutdown and equipment protection
More informationGENERATOR SELF-TEST VERIFIER (GSV300) INSTALLATION INSTRUCTIONS
GENERATOR SELF-TEST VERIFIER (GSV300) INSTALLATION INSTRUCTIONS Page 1 GSV300 Installation Manual Rev XC INTRODUCTION The GSV300 is an easy to use, multifunction generator monitor that is packed with useful
More informationInstallation Manual Premier 412/816/832. Issue 10
Installation Manual Premier // Issue 0 Premier // Installation Manual 5. Operating the System Introduction Before attempting to operate the alarm system ensure you have familiarised yourself with all the
More informationInstallation, Operating and Maintenance Manual
STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS
More informationSK642 THE TELEPHONE DIALER REQUIRES A LAND TELEPHONE LINE TO MAKE OUTGOING CALLS AND ELECTRICITY.
SK642 WIRELESS WATER ALARM SYSTEM WITH AUTO DIALER OWNER'S MANUAL AND SET UP INSTRUCTIONS. Thank you for choosing Ideal Security s Wireless Water Alarm with Telephone Dialer. Please read through complete
More informationFIRE ALARM SYSTEMS FOR PURPOSE-BUILT FLATS & APARTMENTS: A NEW APPROACH
FIRE ALARM SYSTEMS FOR PURPOSE-BUILT FLATS & APARTMENTS: A NEW APPROACH C-TEC HQ Typical tower block Andy Green Marketing Manager at C-TEC, a leading independent UK manufacturer of life safety electronic
More informationLCD and 16-Zone LED Keypads. User s Manual
LCD and 16-Zone LED Keypads 1689 1641 16-Zone LED Keypad LCD Keypad User s Manual TABLE OF CONTENTS 1.0 INTRODUCTION...3 2.0 BASIC OPERATION...4 2.1 Keypad Indicator Lights... 4 2.2 Visual Feedback...
More information2) This manual covers Fire and General Alarm systems. The differences are described in the appropriate sections.
ISSUES ISSUE DATE RELEASED DETAILS OF CHANGE AUTHOR 4 Rev 2 September 2004 Changes for 4000 series. DB 4 Rev 3 April 2005 Screen shots updated and other minor changes K.Z. 4 Rev 4 September 2006 4 Rev
More informationFIRE ALARM CONTROL PANEL FVC01-08
FIRE ALARM CONTROL PANEL FVC01-08 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Radal Technology Limited Unit 1, Webber Court Billington Road, Burnley Lancashire, BB11 5UB Tel: +44 (0) 1282 463 770 Fax: +44
More informationXFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL. user manual and log book. approved document no. DFU Rev 1
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL user manual and log book approved document no. DFU2000501 Rev 1 CONTENTS Important safety notes...3 Introduction...4 Fire alarm systems - an
More informationBaxi Combi 80Eco. Gas Fired Wall Mounted Combination Boiler. User s Operating Instructions
Baxi Combi 80Eco Please keep these instructions safe. Should you move house, please hand them over to the next occupier. Gas Fired Wall Mounted Combination Boiler User s Operating Instructions Natural
More informationGASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL
GASGUARDIAN 2 3 2-Channel Controller OPERATING & INSTALLATION MANUAL GasGuardian 2 3 Operating and Installation Manual Table of Contents General description.... 3 Installation. 3 Locating the GasGuardian-2..
More informationKELCO F29 PROGRAMMABLE FLOW SWITCH
KELCO F29 PROGRAMMABLE FLOW SWITCH PROGRAMMING INSTRUCTIONS Version 010916 KELCO Engineering Pty Ltd Sydney Australia www.kelco.com.au VERY IMPORTANT This Kelco controller has been fully tested and calibrated.
More informationQUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6536A891, 6536B891 & 6536C891 TWO TON PACKAGED HEAT PUMPS
QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6536A891, 6536B891 & 6536C891 TWO TON PACKAGED HEAT PUMPS Note: This manual may also be used for 6536-871 series heat pumps if the 6535-3209 Replacement
More informationPAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00
PAT E N T System 88 COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00 Pg 1 of 12 CONTENTS 1. GENERAL 1.1 Introduction 2 1.2 System Description
More informationGG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual
GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL Installation and Operation Manual 2 GG-2 Warning Use this product only in the manner described in this manual. If the equipment is used in a manner not specified
More informationQUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6535D, 6537C, 6538 A&B SERIES TWO TON PACKAGED HIGH EFFICIENCY HEAT PUMPS
QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6535D, 6537C, 6538 A&B SERIES TWO TON PACKAGED HIGH EFFICIENCY HEAT PUMPS RV Products A Division of Airxcel, Inc. P.O. Box 4020 Wichita, KS 67204 1-316-832-4357
More informationCHAPTER 20 SERVICE EQUIPMENT
SERVICE EQUIPMENT CHAPTER 20 SERVICE EQUIPMENT Service equipment includes service cabinets and the equipment and materials necessary for installation. 20.1 Signal Service Cabinet For MnDOT traffic control
More informationGas Safety Products. Installation, operating and maintenance 11/18/2015. Merlin 1000S+ Gas Utility & Electrical Isolation Controller
Gas Safety Products Installation, operating and maintenance 11/18/2015 American Gas Safety LLC 1 Table of contents 1 General information... 3 2 Installation... 3 2.1 Panel Mounting.... 3 2.2 Power Supply....
More informationGas Safety Products. Installation, operating and maintenance. Merlin 1000BH Gas Proving/Gas Detection System
Gas Safety Products Merlin 1000BH Gas Proving/Gas Detection System Installation, operating and maintenance Read these instructions carefully before operating or servicing Rev: 05 Date: 08-01-18 1 Table
More informationST9400A User Guide. Features
Features Easy to use slider and buttons combined with LoT Technology and an OK button, allows you to confi rm changes and stay in control. PLEASE RESPECT YOUR ENVIRONMENT! Take care to dispose of this
More informationTECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014
January 16, 2014 Release Control Panel 290a 1. Description The Viking VFR400 is a microprocessor based releasing control panel for use on preaction, deluge, Surefire, Firecycle multicycle sprinkler systems,
More informationAnalox 1000 Series. User Manual. Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK
Analox 1000 Series User Manual Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK T: +44 (0)1642 711400 F: +44 (0)1642 713900 W: www.analox.net E: info@analox.net
More informationTPOne-B. Electronic Programmable Room Thermostat. Installation Guide. Danfoss Heating
TPOne-B Electronic Programmable Room Thermostat Danfoss Heating Installation Guide TPOne is an intelligent programmable heating control made easy. TPOne includes features which are designed to save energy.
More informationUser's Instructions. Alpha CD25X/28X. Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired, High Efficiency Condensing Combination Boilers
User's Instructions Alpha CD5X/8X Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired, High Efficiency Condensing Combination Boilers For Technical help or for Service call... ALPHA HELPLINE Tel:
More informationPrem1er EVACS16. Installation Manual VOICE ALARM CONTROL PANEL 4 16 ZONES
Prem1er EVACS16 VOICE ALARM CONTROL PANEL 4 16 ZONES Installation Manual Approved Document No: GLT.MAN-141 PAGE 1 INDEX INDEX... 2 Summary... 3 Safety information & use of this manual... 5 Installation
More informationTHA2 TEMPERATURE/ HUMIDITY/ DEWPOINT ALARM WITH LOGGING CAPABILITY. 99 Washington Street Melrose, MA Phone Toll Free
99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com THA2 TEMPERATURE/ HUMIDITY/ DEWPOINT ALARM WITH LOGGING CAPABILITY Introduction.
More informationDS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel
DS9400 Series EN Release Notes for Firmware V2.07 Fire Alarm Control Panel DS9400 Series Release Notes for Firmware V2.07 Trademarks Trademarks Gentex is a trademark of Gentex Corporation, Fire Protection
More informationLEAKSTOPPER MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND OPERATION MANUAL
LEAKSTOPPER MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND OPERATION MANUAL The LeakStopper Multizone detects the presence of water in environments where it is not supposed to be. Should water
More informationUnity DAU Voice Alarm System
Unity DAU Voice Alarm System User Manual & Log Book Site Name Address Contractor Commissioned Introduction Voice Alarm (VA) systems are the quickest way to evacuate the public & staff from a building.
More informationSolution 4+4 Operators Manual ISSUE 1.25
Solution 4+4 Operators Manual ISSUE 1.25 Solution 4+4 Operators Manual Copyright 1997 by, SYDNEY, AUSTRALIA Document Part Number MA400O Document ISSUE 1.25 Printed 02 August 1999 This documentation is
More informationAlarm Controller Fire and CO
Alarm Controller Fire and CO Model: Ei450 Instruction Manual Read and retain carefully for as long as the product is being used. It contains vital information on the operation and installation of your
More informationElectronic Dual Cylinder Thermostat Installation Instructions
ESCTDEB Electronic Dual Cylinder Thermostat Installation Instructions Thank you for choosing ESi Controls. All our products are tested in the UK so we are confident this product will reach you in perfect
More informationFTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS
QUICK USER GUIDE FOR, 2 & 4 ZONE PANELS INDICATORS COLOUR INDICATION MON FAULT Yellow On when a fault condition has occurred, or if no other fault Led is on, this indicates 24v auxiliary fuse failure.
More informationWatchguard WGAP864 User Manual
Watchguard WGAP864 User Manual v1.0 Issued September 2016 1 2 Table of Contents Glossary... 5 1. Introduction to your Watchguard WGAP864... 6 2. Before Operating your Alarm System... 6 3. Understanding
More informationBaxi System 100 HE Plus. User s Operating Instructions. Wall Mounted Powered Flue Condensing Gas Fired Central Heating Boiler
User s Operating Instructions Baxi System 100 HE Plus Wall Mounted Powered Flue Condensing Gas Fired Central Heating Boiler Please keep these instructions safe. Should you move house, please hand them
More informationFire detection and alarm
Fire detection and alarm Aesthetic Install all cabling and cable containment neatly and unobtrusively, meeting the highest electrical industry installation standards. Neatly lay and securely fix cables.
More informationModel: Ei450. Instruction Manual
Alarm Controller Fire and CO Model: Ei450 Instruction Manual Read and retain carefully for as long as the product is being used. It contains vital information on the operation and installation of your
More informationGeyserWise MAX. Instruction manual. All in one hot water management
GeyserWise MAX All in one hot water management Before operating and installation, carefully read all instructions. Do not discard this manual. DISPLAY The display is the feedback mechanism to the user
More informationSentinel. Kinetic MVHR and Kinetic Plus MVHR. Operation & Monitoring. Stock Ref. N
V:\Technical\ARTWORK\Fitting & Wiring\Word Files COMPLETE\442073S.doc Sentinel Kinetic MVHR and Kinetic Plus MVHR Operation & Monitoring Stock Ref. N 438222 Kinetic B 438222A Kinetic BS 443319 Kinetic
More informationDigiplex LED Keypads User s Manual
KLEDEU03.fm Page -1 Friday, May 4, 2001 11:25 AM Digiplex LED Keypads User s Manual KLEDEU03.fm Page 0 Friday, May 4, 2001 11:25 AM KLEDEU03.fm Page 1 Friday, May 4, 2001 11:25 AM TABLE OF CONTENTS 1.0
More informationFire detection and alarm system Operating instructions
Fire detection and alarm system Operating instructions Operating instructions Table of Contents User responsibility - - - - - - - - - - - - 4 Daily - - - - - - - - - - - - - - - - - - - 4 Weekly - - -
More informationZM1 User Manual JVA TECHNOLOGIES.
ZM1 User Manual JVA TECHNOLOGIES www.jva-fence.com Contents 1 Introduction.... 6 1.1 Equipment Requirements and Options..................... 6 1.1.1 Requirements.....................................6 1.1.2
More informationEasyTronic III MANUAL SERVICE
rev.6 EasyTronic III MANUAL SERVICE General characteristics: Power supply 24 Vac ±15% Max consumption at 24Vac 300mA Relay outputs 6 Maximum relay current 8 A res. Serial standard RS232 2 Serial standard
More information3 In 1 AIR CONDITIONER with REMOTE CONTROL MODEL NO: CA9000 PART No: OPERATION & MAINTENANCE INSTRUCTIONS
3 In 1 AIR CONDITIONER with REMOTE CONTROL MODEL NO: CA9000 PART No: 32305600 OPERATION & MAINTENANCE INSTRUCTIONS 0304 Parts List Item Part No Description Qty 1 FT900001 Top Cover 1 2 FT900002 Filter
More informationProduct Data Sheet. Merlin GDP2. Gas Safety Products. Merlin GDP2. Installation, operating and maintenance 23/08/2016. S&S Northern Ltd 1
Gas Safety Products Merlin GDP2 Installation, operating and maintenance 23/08/2016 S&S Northern Ltd 1 Table of contents 1 General information... 3 2 Installation... 3 2.1 Panel Mounting..... 3 2.2 Mains
More informationSecurity System. User Guide for the LED Command Center
Security System User Guide for the LED Command Center National Security Systems Inc (800)457-1999 MY SECURITY COMPANY IS: CALL BEFORE TEST: THIS SECURITY SYSTEM IS CONNECTED TO TELEPHONE NUMBER: THE SECURITY
More information