JEFFERSON COUNTY PUBLIC SCHOOLS FIRE WATCH PROGRAM
|
|
- Alexandrina Preston
- 5 years ago
- Views:
Transcription
1 1 JEFFERSON COUNTY PUBLIC SCHOOLS FIRE WATCH PROGRAM PURPOSE: To minimize potential structural damages and to protect the life safety of all building occupants during periods when the automatic fire alarm and/or extinguishing systems are inoperable for 4 hours or more during a 24 hour period or when hot work is being conducted in or on the grounds of a Jefferson County Public Schools (JCPS) facility. OBJECTIVES: 1. To ensure all pertinent agencies are notified of a fire in a timely manner to provide adequate response time in an effort to minimize structural damage. 2. To provide immediate notification of a fire or signs of a fire to building occupants to ensure the timely evacuation of occupied structures in order to protect the life safety of all occupants. 3. To comply with applicable Occupational Safety and Health Administration (OSHA) standards and National Fire Protection Association (NFPA) codes. SCOPE: This plan applies to all JCPS facilities and to all JCPS employees and contractors throughout the entire calendar year. DEFINITIONS 1. AHJ- Authority Having Jurisdiction 2. Fire Watch- The assignment of a person or persons to an area for the express purpose of notifying the fire department, the building occupants, or both of an emergency; preventing a fire from occurring; extinguishing small fires; or protecting the public from fire or life safety dangers. (NFPA ) 3. Hot Work- Any activity that utilizes a process or equipment that produces a spark, flame or heat. This includes, but is not limited to, welding, heat treating, grinding, thawing pipe, powder driven fasteners, hot riveting, torch work, and similar applications. (NFPA ) 4. Hot Work Permit- The JCPS approved permit that documents that the applicable OSHA and NFPA fire prevention and protection requirements have been implemented prior to beginning the hot work operations; it shall indicate the date(s) the hot work will be conducted; and identify the object on which hot work is to be preformed. The permit shall be kept on file until the hot work operation is complete. ([OSHA (k)(2)])
2 2 5. Post: To require or initiate a fire watch. 6. Tour: A periodic inspection of the building or area for which a fire watch has been posted. 7. Qualified Person- A person who meets or exceeds the qualification requirements provided in this plan. RESPONSIBILITIES Fire Watch Personnel The duties and functions of those personnel assigned to conduct the fire watch are as follows: 1. Conducting tours and/or inspections of the facility and/or affected area for fire or signs that a fire is likely to occur. 2. Discovery of fire and immediate notification to 911 and (Radio Room). 3. Operation of fire extinguishers. 4. Monitoring signals of fire alarm systems. 5. Detecting conditions likely to reduce the effectiveness with which a fire may be controlled, such as missing or discharged fire extinguishers or damaged fire safety equipment. 6. Maintain a detailed log of activities conducted throughout the duration of the fire watch. Radio Room Dispatcher The Radio Room Dispatcher will document the date and time the fire watch was initiated and the date and time the fire watch was ended. In addition, the dispatcher will be responsible for notifying the Safety and Environmental Services upon receiving notification of the fire watch. Safety and Environmental Services The Safety and Environmental Services department will be responsible for maintaining and updating the Fire Watch program as needed or required. Safety and Environmental Services will contact the AHJ when a fire watch is initiated or special approval is needed. Contractors All contractors, their employees, and subcontractors must fully comply with this program whenever hot work is being conducted or fire alarm and/or suppression systems are disabled they must seek the appropriate JCPS Department Manager for approval. JCPS Directors and Department Managers Departmental Managers shall ensure that all employees and contractors fully comply with this program and are provided with this plan prior to conducting any activities that would require the initiation of a fire watch as set forth in this plan. In addition, a Director, Manager or designee must approve and sign all hot work permits prior to work being conducted.
3 3 POSTING REQUIREMENTS A fire watch shall be posted and the entirety of this program shall be implemented anytime one or more of the following conditions exist: Occupied Facilities The fire protection sprinkler system is completely disabled or disabled to a point where the system cannot be relied upon to activate in the event of a fire. The fire alarm system is silenced or in trouble. The standpipe system is completely disabled or disabled to a point where the system cannot be relied upon to deliver water for fire fighting operations. The fire alarm and/or sprinkler system is disabled in any part of the facility. The Authority Having Jurisdiction (AHJ) determines that a situation requires the posting of a fire watch. Authorized hot work is being conducted in or adjacent to the facility. (See JCPS Hot Work Safety Program) Unoccupied Facilities Unoccupied facilities will not maintain a fire watch unless it is determined necessary by the AHJ to be required. Authorized hot work is being conducted in the facility or on JCPS grounds. (See JCPS Hot Work Safety Program) QUALIFICATION REQUIREMENTS Personnel assigned to conduct a fire watch, whether a JCPS employee or outside contractor, shall meet the following minimum requirements: Must be 18 or older. Must be mentally alert. Must be able to effectively communicate in spoken English. Must be able to comprehend written English. Must be able to climb stairs that may be part of the building or area placed under the fire watch. Must be able to recognize the indicators of fire through the senses of sight, hearing and touch. Must be capable of using a two-way radio and telephone. Must be equipped with a radio and/or cellular phone that is independent from the facility s phone line that is capable of contacting the Radio Room Dispatcher and 911. Must be equipped with and carry a flashlight at all times.
4 4 COMMUNICATION REQUIREMENTS All fire watch personnel must have a dedicated phone line or other acceptable means of communication that is independent of the facilities phone system. When possible, fire watch personnel should have a radio that is capable of communicating with facility management or administration when the facility is occupied. FIRE WATCH PROCEDURES The following procedures will be implemented each time a fire watch is implemented at any JCPS facility. Notification Sign: If a fire watch is in affect because of an inoperable fire alarm or sprinkler system a sign will be posted at each main entrance and exit point to the facility that will notify entrants that a fire watch is in affect and that the applicable system is operable. See Appendix A. A fire watch sign is not required for hot work operations unless the fire alarm or sprinkler system is inoperable at anytime during the hot work operations. Initial Notification: Safety & Environmental Services at , JCPS Radio Room at , and the AHJ(Safety and Environmental Services will contact the AHJ) shall be notified at least 24 hours in advance of any situation where it is foreseeable, as set forth in this program, that a fire watch must be initiated. In the event of an unforeseen shutdown or disablement of the fire detection system and/or fire extinguishing system(s), Safety & Environmental Services and the JCPS Radio Room shall be notified immediately and a fire watch shall be initiated for the affected area or entire building. Tours and Inspections The following procedures shall be followed when the fire watch person is touring the facility and/or affected area: In the event of a fire the fire watch personnel shall: 1. Immediately notify facility administration and all occupants in the facility to evacuate immediately. 2. Call 911 and report the fire. 3. Call the JCPS Radio Room dispatcher at and report the fire. Do not open any door to an area that is suspected of containing a fire. This could result in injury or the spread of the fire into uninvolved areas. All pertinent information shall be recorded on the fire watch log.
5 5 Length of Tour or Inspection: One complete tour of the building or area, no longer than 45 minutes, shall be completed each hour. If the size of the building or other circumstance prevents the tour or inspection from being completed in a 45-minute period, additional fire watch personnel shall be posted. Fire watch personnel shall not leave their patrol unless properly relieved by a qualified person. All tour or inspection times shall be recorded on the fire watch log. Areas that Require Tours, Inspections, and/or Monitoring All hallways and common areas shall be patrolled. Laboratories, classrooms and offices are not required to be checked, unless specifically indicated by a representative of JCPS. Personnel assigned to a fire watch should be alert for signs of fire inside of a laboratory, classroom, or office. Signs may include: the sight or smell of smoke heat radiating from the door to a room blistering paint on the door or walls of a room "crackling" or "popping" noises originating from a room flickering or glowing light under the door Particular attention should be given to new construction or alterations that may be in progress. If the fire watch is due to a hot work permit only the affected area must be inspected. This area is to be monitored the entire time the hot work is being conducted. In addition to the JCPS fire watch procedures, all JCPS hot work procedures must be fully complied prior to, during, and after hot work activities. Initial Tour or Inspection: The first tour or inspection shall begin immediately after the fire watch is posted. A thorough inspection of the building and/or area shall be conducted. During this first inspection, the fire watch person should become familiar with the building layout and fire safety equipment. Completion of Fire Watch: When the system is restored or hot work is complete the JCPS Radio Room shall be notified.
6 6 FIRE WATCH LOG A log shall be kept by the authorized person(s) conducting the fire watch activities. The purpose of this log is to provide proof of the initiation of the fire watch at times required by this program and to ensure personal safety of fire watch personnel. 1. Fire Watch Log Requirements: The following elements shall be included and completed in the fire watch log: Printed name and contact number for all fire watch personnel. Employer or department name and supervisor contact information. Date and time the fire watch was initiated. Time each tour or inspection is started and finished. Date and time fire watch ended. TRAINING Safety and Environmental Services will conduct annual training on this program for all applicable JCPS employees. In addition, training may be scheduled on an as needed basis upon request from other department heads. Individual department Directors and Managers are responsible for ensuring that all contractors are educated and trained on the requirements of this program. REFERENCES OSHA OSHA Subpart Q NFPA 1 NFPA 101 APPENDIXES A. Fire Watch Notification Sign B. Fire Watch Decision Tree C. Fire Watch Log
7 7 APPENDIX A: FIRE WATCH NOTIFICATION SIGN FIRE WATCH FIRE ALARM SYSTEM IS INOPERABLE IN CASE OF FIRE: NOTIFY ALL PERSONS IN THE BUILDING TO EVACUATE. EVACUATE THE BUILDING. CALL AND REPORT THE FIRE. CALL THE JCPS RADIO ROOM AT 3121 AND REPORT THE FIRE.
8 APPENDIX B: 8
9 9 APPENDIX C: FIRE WATCH LOG FACILITY/ASSIGNED AREA: DATE: YOUR NAME: INITIALS: FIRE WATCH TIMES: STARTED ENDED Fire watch personnel must perform continuous tours such that each room in their assigned area is checked at not less than 1 hour intervals. The first entry in this log must be made within 30 minutes of the start of the fire watch and every hour thereafter. Times must be recorded using the 24-hour clock and initialed. Any problems found during the fire watch must be documented (along with the time found and initialed) and reported to the JCPS Radio Room at I certify (by my initials below) that I completed a tour of my entire assigned area at the following times: Time Tour Completed Initials Time Tour Completed Initials Time Tour Completed Initials Additional Comments:
Date Issued: December 14, 2017 Revision: 2.1
2.1 1. Introduction A is implemented to ensure the fire safety of building occupants or a building area when the Fire Alarm System or a Fire Protection System has been temporarily disabled due to malfunction,
More informationOXNARD FIRE DEPARTMENT Fire Watch Guidelines
OXNARD FIRE DEPARTMENT Fire Watch Guidelines What is a Fire Watch? A Fire Watch is a temporary measure intended to ensure continuous and systematic surveillance of an activity, building or portion thereof
More informationFire System Impairment Policy
Fire System Impairment Policy Purpose: To establish procedures to be followed, when a fire protection or suppression system is taken out of service, due to construction, alteration, power outage, repair,
More informationCedar Hammock Fire Rescue Standard Operational Guidelines FIRE WATCH. General. Requirements for a Fire Watch
Cedar Hammock Fire Rescue Standard Operational Guidelines FIRE WATCH General This information is provided to clarify the requirements for a fire watch. A fire watch is the action of a person or persons
More informationUC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION
SECTION: UC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION INITIATOR: DALE SAUNDERS REVISION DATE: September 2015 1. Program Description 2. Scope 3. Definitions
More informationMount Laurel Fire Department, Office of The Fire Marshal FIRE WATCH NOTIFICATION
Mount Laurel Fire Department, Office of The Fire Marshal FIRE WATCH NOTIFICATION (Please Print or Type) PREMISE DATE TIME ADDRESS RESPONSIBLE PERSON PHONE ORDERED BY RECEIVED BY CIRCUIT INTERVALS FIRE
More informationFire Watch Program. Building Administrators Building Administrators will inform building occupants about fire watch events and building evacuations.
SUNY Cortland - Environmental Health and Safety Office Fire Watch Program Date of Inception: May 12, 2011 Latest Revision/Review Date: August 1, 2018 Previous Revision/Review Date: June 28, 2017 Fire Watch
More informationBuilding Emergency Policies and Procedures
Building Emergency Policies and Procedures For Langsam Library 2911 Woodside Cincinnati, OH 45221 June 2017 University of Cincinnati Department of Public Safety Department Table of Contents A. Introduction
More informationProcedure DESCRIPTION/OVERVIEW
Applies To: UNMH Responsible Department: Life Safety Revised: 07.08.16 Procedure Patient Age Group: (X ) N/A ( ) All Ages ( ) Newborns ( ) Pediatric ( ) Adult DESCRIPTION/OVERVIEW To assure the safety
More informationFire Prevention Plan
Fire Prevention Plan TABLE OF CONTENTS Section Title Page 1.0 Objective. 3 2.0 Background 3 3.0 Assignment of Responsibility.. 4 4.0 Plan Implementation..... 5 5.0 Types of Hazards...... 6 6.0 Training........
More informationDutchess Community College. Emergency Action Plan. Conklin Hall College Residence
Dutchess Community College Emergency Action Plan Conklin Hall College Residence June 2014 1 TABLE OF CONTENTS Purpose Page 3 Introduction Page 3 Evacuation Page 4 Fire Emergencies Page 5 Evacuating Individuals
More informationHOT WORK SAFETY PROGRAM:
HOT WORK SAFETY PROGRAM: 1.0 Purpose. To establish safe procedure for open flame or hot work process at Oklahoma City Community College (OCCC) to avoid loss of property and injury to personnel. 2.0 Scope.
More informationUNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY
Revision No.: 5 Page 1 of 6 I. PURPOSE This policy outlines the guidelines for posting a fire watch if the fire alarm and/or fire suppression system in any University building becomes inoperable and the
More informationCLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau
CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8.h.3 TITLE: SCOPE: PURPOSE: HOT-WORK OPERATIONS PERMIT/PLAN SUBMITTAL
More informationDUQUESNE UNIVERSITY. Fire Protection System Impairment Program (Red etag Permit)
DUQUESNE UNIVERSITY Fire Protection System Impairment Program (Red etag Permit) Prepared by: Environmental Health and Safety Department TABLE OF CONTENTS Page Purpose 1 Scope 1 Exceptions 2 Definitions
More informationFire Prevention Plan
Fire Prevention Plan TABLE OF CONTENTS Section Title Page 1.0 Objective. 3 2.0 Background 3 3.0 Assignment of Responsibility.. 4 4.0 Plan Implementation..... 5 5.0 Types of Hazards...... 6 6.0 Training........
More informationEmergency Action Plan Program
Page 1 Emergency Action Plan Program Daniel Schmid 4-7-17 Dan Schmid Safety Director Todd Osman 4-10-17_ Dave Gelhar 4-11-17 Todd Osman Dave Gelhar RVI President SpecSys President Page 2 Table of Contents
More informationBuilding Emergency Policies and Procedures
Building Emergency Policies and Procedures For Van Wormer Hall 2614 Mc Micken Circle Cincinnati, OH 45221 June 2017 University of Cincinnati Department of Public Safety Department Table of Contents A.
More informationUNIVERSITY. Facilities Management
EAST TENNESSEE STATE UNIVERSITY Facilities Management Policy Number: 700.10 Title: Fire Protection Impairment Program Implementation Date: April, 2008 Last Revised: August 4th, 2014 Introduction The probability
More informationCLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Ls Vegas, NV (702) FAX (702)
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Ls Vegas, NV 89119 (702) 455 7316 FAX (702) 455 7347 105.8.h.3 2 TITLE: HOT WORK OPERATIONS PERMIT/PLAN SUBMITTAL RENEWABLE
More informationHot Work Policy and Procedures
Environmental Health & Safety Office of the Fire Marshal Hot Work Policy and Procedures In Accordance With New Jersey Fire Code And National Fire Protection Association 505 Ramapo Valley Road, Building
More informationWELDING, CUTTING, AND BRAZING SAFETY PROGRAM
WELDING, CUTTING, AND BRAZING SAFETY PROGRAM HOT WORK TABLE OF CONTENTS 1.0 Introduction 1.1 Purpose 1.2 Scope 2.0 Responsibilities 2.1 Building Office 2.2 Building Personnel 2.3 Individuals Performing
More informationSt. Vincent s Health System Page 1 of 6
St. Vincent s Health System Page 1 of 6 TITLE: Fire Plan Code Red FACILITY: St. Vincent s East FUNCTION: ORIGINATING DEPT: HOSPITAL SHARED POLICY? EFFECTIVE DATE: _X Yes No DOCUMENT NUMBER: 801 ORIGINATION
More informationI. Scope: II. Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018
Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018 Prepared by: EH&S The probability of casualties and major structural damage increases when fire
More informationPurpose: To establish procedures for identifying fire hazards and preventing fires. Scope: All Central New Mexico Community College (CNM) Community.
CNM WAY PROCESS CNM Process Name Fire Safety Program (04/10/2018 Revision) Overview of Fire Safety Program Purpose: To establish procedures for identifying fire hazards and preventing fires. Scope: All
More informationEmergency Action Fire Prevention Plan
Emergency Action Fire Prevention Plan Table of Contents Section Title Page 1.0 Purpose 2 2.0 Scope and Application 2 3.0 Responsibilities 2-3 University Safety Coordinator 2-3 Department Heads, Supervisors
More informationFIRE PREVENTION PLAN EMERGENCY ACTION
FIRE PREVENTION PLAN EMERGENCY ACTION 1.0 PURPOSE This Plan is presented for University employees to be informed so that they react safely and effectively during an emergency situation. The Plan also reinforces
More informationDepartment of Fire Safety Policy and Procedures for Fire Watch, Preformed by Residence Education and Services Staff
Department of Fire Safety Policy and Procedures for Fire Watch, Preformed by Residence Education and Services Staff Montclair State University Department of Fire Safety Document Version: 02/25/2011 Table
More informationTEN STEP PROCESS PREPARING FIRE SAFETY PLANS
TEN STEP PROCESS PREPARING FIRE SAFETY PLANS STEP 1 CONDUCT FIRE SAFETY AUDIT IDENTIFY BUILDING FEATURES AND HUMAN RESOURCES. STEP 2 APPOINTMENT OF SUPERVISORY STAFF IDENTIFY TRAINED SUPERVISORY STAFF
More informationSubject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: August 2014 Distribution All YC Employees
Subject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: August 2014 Distribution All YC Employees Purpose: To establish procedures to be followed when a fire
More informationFire Watch Policy and Procedures
Ramapo College of New Jersey Environmental Health & Safety Office of the Fire Marshal Fire Watch Policy and Procedures In Accordance With New Jersey Fire Code and National Fire Protection Association 505
More informationFire Prevention Program
Fire Prevention Program Updated February 2010 REGULATORY AUTHORITY California Code of Regulations, Title 8, Section 3221, Title 19 (19CCR) and Title 24 (24CCR), along with National Fire Protection Association
More informationUniversity of Maryland FIRE EVACUATION PLAN NATIONAL DENTAL MUSEUM POLICE FIRE MEDICAL EMERGENCY Anyone discovering excessive heat,
University of Maryland FIRE EVACUATION PLAN NATIONAL DENTAL MUSEUM POLICE - 711 FIRE - 711 MEDICAL EMERGENCY - 711 Anyone discovering excessive heat, smoke, or fire inside your building will immediately
More informationNova Scotia Fire Dispatch Minimum Standards (2017)
Fire Service Association of Nova Scotia Nova Scotia Fire Dispatch Minimum Standards (2017) July 14, 2017 Scope This document sets out the minimum standards to which fire dispatch operations are expected
More informationHot Work Policy. Department of Risk Management. 1. Purpose. 2. Authority. 3. Scope
1. Purpose The purpose of the University of Denver Hot Work policy is to protect personnel and property from a fire caused by hot work. The DU Hot Work policy defines the responsibilities and requirements
More informationBoard Policy 6819 Fire Safety and Prevention Plan
Board Policy 6819 Fire Safety and Prevention Plan The West Hills Community College District is committed to the safety of faculty, staff, students and visitors. The Fire Safety and Prevention Plan is designed
More informationFIRE EVACUATION PLAN PRATT STREET PARKING GARAGE AND ATHLETIC CENTER POLICE FIRE MEDICAL EMERGENCY
University of Maryland FIRE EVACUATION PLAN PRATT STREET PARKING GARAGE AND ATHLETIC CENTER POLICE - 711 FIRE - 711 MEDICAL EMERGENCY - 711 Anyone discovering excessive heat, smoke, or fire inside your
More informationFire Safety Plan (FSP) Review Checklist 1
Fire Safety Plan (FSP) Review Checklist 1 (Component of a BC Fire Code (BCFC) compliance inspection) COMPANY INFORMATION Company name: Building Name: Address: Street # and name City/Province Postal Code
More informationUNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY
Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during
More informationFire Safety Plan (FSP) Review Checklist 1
Fire Inspection & Prevention Initiative Fire Safety Plan (FSP) Review Checklist 1 (Component of a BC Fire Code (BCFC) compliance inspection) Date: COMPANY INFORMATION Company Name: Building Name: Address:
More informationFIRE SAFETY PLAN FOR CONSTRUCTION, RENOVATION AND DEMOLITION SITES
BACKGROUND INFORMATION Alberta Fire Code 2014: FIRE SAFETY PLAN FOR CONSTRUCTION, RENOVATION AND DEMOLITION SITES Alberta Fire Code (AFC) 2014, Division B, Section 5.6. requires a Fire Safety Plan for
More informationTable OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS
901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.
More informationUniversity of Maryland FIRE EVACUATION PLAN
University of Maryland FIRE EVACUATION PLAN PLAZA PARKING GARAGE POLICE - 711 FIRE - 711 MEDICAL EMERGENCY - 711 Anyone discovering excessive heat, smoke, or fire inside your building will immediately
More informationFire Prevention Plan for Alter Hall 3743 Ledgewood Drive
Administrative Office and Classroom Building for Alter Hall 3743 Ledgewood Drive Xavier University October 2, 2006 Page 1 3/3/2016 Table of Contents Introduction... 3 Responsibilities... 3 Major Workplace
More informationTABLE OF CONTENTS Part 6 Legal Basis for Fire Safety Planning... 2
TABLE OF CONTENTS Part 6 Legal Basis for Fire Safety Planning... 2 6.1] GENERAL... 2 6.2] EXCERPTS FROM 2012 BC FIRE CODE PART 2 BUILDING AND OCCUPANT FIRE SAFETY... 3 6.3] EXCERPTS FROM 2012 BC FIRE CODE
More informationUniversity of Maryland FIRE EVACUATION PLAN Columbus Center POLICE FIRE MEDICAL EMERGENCY - 911
University of Maryland FIRE EVACUATION PLAN Columbus Center POLICE - 911 FIRE - 911 MEDICAL EMERGENCY - 911 Anyone discovering excessive heat, smoke, or fire will immediately sound an alarm and report
More informationFIRE SAFETY PLAN ADMINISTERED BY: DEPARTMENT OF ENVIRONMENTAL HEALTH AND SAFETY
FIRE SAFETY PLAN ADMINISTERED BY: DEPARTMENT OF ENVIRONMENTAL HEALTH AND SAFETY WRIGHT STATE UNIVERSITY FIRE SAFETY PLAN INTRODUCTION: Occupational Safety and Health (OSHA) standards for fire safety are
More informationSavard Labor & Marine Staffing, Inc. Fire Prevention Program Rev3/14
Fire Prevention Program Purpose The Company Fire Safety Plan has been developed to work in conjunction with company emergency plans and other safety programs. This includes reviewing all new building construction
More informationSafe Operating Procedure
Safe Operating Procedure (Revised 10/17) HOT WORK PERMIT OPERATIONS Authority In recognition of the inherent hazards posed by certain hot work processes, the National Fire Protection Agency adopted Standard
More informationEmergency Action Plan For Alumni Center 1507 Dana Avenue
University Relations Division Department of Physical Plant Human Resources Community Building Institute Office of University Communications and Administrative Office Building Emergency Action Plan For
More informationEmergency Action Plan
Emergency Action Plan Company Name Current as of Company Address Phone Number Contents EMERGENCY ACTION PLAN 2 SCOPE OF THE PLAN 2 Emergency Plan Coordinators 2 First Aid and CPR certified employees 2
More informationShould you have further questions, please feel free to contact the Fire Prevention Branch.
Fire Prevention Branch Fire Hall # 5 200 Saprae Creek Trail Fort McMurray, AB T9H 4P1 November 8 th, 2017 RE: PERMIT REQUIRED TO WORK ON SPECIAL FIRE SUPPRESSION SYSTEMS IN THE RMWB All annual special
More informationEmergency Action Plan for
Kuhlman Hall Emergency Action Plan for Kuhlman Hall 3824 Ledgewood Drive Xavier University November 9, 2006 Ken Grossman Page 1 11/7/2013 Table of Contents Emergency Action Plan Introduction... 3 Responsibilities...
More informationFIRE EVACUATION PLAN
FIRE EVACUATION PLAN LATTA PAVILION CONDOMINIUMS 1320 FILLMORE AVE. CHARLOTTE, NORTH CAROLINA NOVEMBER 2002 PURPOSE The purpose of this plan is to establish procedures for the systematic, safe, and orderly
More informationXavier Field Office Fire Prevention Plan. for. Xavier Field Office Dana Avenue
Xavier Field Office for Xavier Field Office 1601 Dana Avenue Xavier University January 30, 2012 Ken Grossman Page 1 10/29/2013 Table of Contents Introduction... 3 Responsibilities... 3 Major Workplace
More informationMulch fires, trash can fires, or other fire outside a building should be reported by the following methods:
University of Maryland FIRE EVACUATION PLAN HEALTH SCIENCE FACILITY I (HSF I) POLICE - 711 FIRE - 711 MEDICAL EMERGENCY - 711 Anyone discovering excessive heat, smoke, or fire inside your building will
More informationCLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau
CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 Permit Type: 105.7.14 Control Number: A.0 Effective Date: 9/14/11 TITLE:
More informationGrossmont Cuyamaca Community College District Fire Report 2014
Grossmont Cuyamaca Community College District Fire Report 2014 Overview The Higher Education Opportunity Act (Public Law 110-315) became law in August, 2008. It requires all academic institutions to produce
More informationFIRE SAFETY PLAN Revised December
FIRE SAFETY PLAN Revised December 2017 1 INTRODUCTION The Fire Safety Plan (herein after called the FSP) has been developed for the safety of staff, students and visitors who use the school. These procedures
More informationSection 9 THE GUIDELINES FOR DEVELOPING AN EVACUATION PLAN FOR INDIVIDUALS WITH DISABILITIES. Shelton School District Emergency Response Plan
Section 9 THE GUIDELINES FOR DEVELOPING AN EVACUATION PLAN FOR INDIVIDUALS WITH DISABILITIES Introduction.8.1 Buildings with Inaccessible Exits for Individuals with Disabilities...8.1 Definitions...8.1
More informationProperty Name & Address [ Property Name ] - [ Property Address ]
Emergency Procedure FIRE Property Name & Address [ Property Name ] - [ Property Address ] Purpose To ensure effective response and evacuation, by the property s Emergency Response Organization, to a fire
More informationEmergency Procedures for Persons Requiring Assistance in Evacuation
Emergency Procedures for Persons Requiring Assistance in Evacuation This document is available in an alternate format, upon request. Developed by Health and Safety and the Office of Human Rights, Equity
More informationSafety & Security Services Services de Sûreté et Sécurité. Hot Work Protocol
Article 1 Purpose Vanier College has established a to minimize the potential for injuries and loss of property due to fire or explosion as a result of hot work. Article 2 Scope This protocol applies to
More information[Name/title] is the Alternate Safety Officer/ Alternate Emergency Coordinator.
Community Health Center ================================================================= Subject: EMERGENCY EVACUATION PROCEDURE ================================================================= Policy
More informationEmergency Evacuation Plan South Patterson Building (SPB)
Emergency Evacuation Plan 1700 South Patterson Building (SPB) 2014 Table of Contents Section I: Purpose and Objectives Section II: General Guidelines Section III: Responsibilities of Emergency Coordinator
More informationCAMPUS COMMUNITY FIRE AND LIFE SAFETY POLICY
CAMPUS COMMUNITY FIRE AND LIFE SAFETY POLICY Origination Date: July 1 st 2009 1. PURPOSE The purpose of this policy is to create a safe environment for faculty, staff, students and visitors by applying
More informationSURREY FIRE SERVICE. Construction Fire Safety Plan Bulletin
SURREY FIRE SERVICE Construction Fire Safety Plan Bulletin The B.C. Fire Code requires building owners/contractors to comply with the requirements of the BC Fire Code 5.6 Construction and Demolition Sites
More informationFIRE SAFETY PLAN. Ceramics/Sculpture Building 47 Service Rd 1 S Winnipeg, MANITOBA. May / Prepared by: Chris Pancoe
FIRE SAFETY PLAN Ceramics/Sculpture Building 47 Service Rd 1 S Winnipeg, MANITOBA May / 2017 Prepared by: Chris Pancoe TABLE OF CONTENTS Contents A. BUILDING AUDIT:... 3 BUILDING DESCRIPTION... 3 1. Level
More informationXavier Field Office Emergency Action Plan. For. Xavier Field Office Dana Avenue
Xavier Field Office Emergency Action Plan For Xavier Field Office 1601 Dana Avenue January 30, 2012 Ken Grossman Staff 10/22/2013 Page 1 Table of Contents Emergency Action Plan Introduction... 3 Responsibilities...
More information1.2 To ensure the safety of all persons working in or occupying a building where a hot work operation is performed.
REQUIREMENT 2. HOT WORK OPERATIONS 1.0 PURPOSE 1.1 To establish a requirement with responsibilities for any hot work operations during all phases of construction, renovation and routine maintenance work
More informationTHIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS.
THIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS. IF YOU RECEIVED A NOTICE BY MAIL AND YOU DO NOT CURRENTLY HAVE A FIRE ALARM INSTALLED IN YOUR BUILDING, YOU MAY DISREGARD THE NOTICE. Dear Building
More informationFIRE PROTECTION INTRODUCTION
SECTION IV. Fire/Life Safety Chapter 1. Fire Protection Revision Date 11/19/02 Review Date 01/2007 FIRE PROTECTION INTRODUCTION PURPOSE It is the policy of Duke University to take all possible steps to
More informationFIRE PROTECTION PROGRAM
Fire Protection Program Page 1 of 13 FIRE PROTECTION PROGRAM 1.0 Objective The objective of this performance assessment is to evaluate the effectiveness of the laboratory's fire protection program as implemented
More informationDoc #: 2100-AD Revision: - 4M Fire Watch Procedures. Author(s): Tammie Lavoie
Doc #: 2100-AD-015-0072 Revision: - 4M Fire Watch Procedures Author(s): Tammie Lavoie Contents Revision History... 3 1.0 Purpose... 4 2.0 Applicable To... 4 3.0 Scope... 4 4.0 Definitions... 4 5.0 Training...
More informationFire Prevention Plan for Campus Services Building 1630 Musketeer Drive
Application Services and Technology Support Mailing Services for Campus Services Building 1630 Musketeer Drive Xavier University October 31, 2006 Ken Grossman Page 1 10/29/2013 Table of Contents Introduction...
More informationGEORGIA DEPARTMENT OF CORRECTIONS Standard Operating Procedures
Policy Number: 511.09 Effective Date: 4/13/2018 Page Number: 1 of 5 I. Introduction and Summary: This policy sets forth the guidelines and requirements for the development of the Facility Fire Safety/Emergency
More informationRE: PERMIT REQUIRED TO WORK ON FIRE ALARM SYSTEMS IN THE RMWB
Fire Prevention Branch Fire Hall # 5 200 Saprae Creek Trail Fort McMurray, AB T9H 4P1 November 8 th, 2017 RE: PERMIT REQUIRED TO WORK ON FIRE ALARM SYSTEMS IN THE RMWB All fire alarm system work permits
More informationBUILDING EMERGENCY ACTION PLAN. for Your Building Name
BUILDING EMERGENCY ACTION PLAN for Your Building Name Building Emergency Action Plan for Non-residential Campus Buildings Building Name: SAMPLE ONLY Date of last update/review: 01/01/2013 (The plan should
More informationALARM SYSTEMS AND EVACUATION PLANS SELF INSPECTION CHECKLIST
OPTIONAL INFORMATION Name of School: Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ALARM SYSTEMS AND EVACUATION PLANS Guidelines: This checklist covers regulations issued
More informationFire Prevention and Protection Plan
Fire Prevention and Protection Plan Last Reviewed: 09/28/16 I. PURPOSE... 2 II. SCOPE... 2 III. REFERENCES... 2 IV. RESPONDING TO A FIRE... 2 A. First, call 911.... 2 B. Then, call Community Safety...
More informationUAB Administration Building Disaster Plan
UAB Administration Building Disaster Plan Sponsored by the Department of Occupational Health and Safety Last Updated: June, 2014 This Administration Building specific plan is maintained and revised by
More informationSecond Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement
of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections
More informationFORM MUST BE SIGNED AND RETURNED FOR VENDOR PARTICIPATION
Fire Prevention Bureau 95 Culver Street, Simcoe, Ontario N3Y 2V5 519-426-4115 Fax: 519-426-4140 Administration Headquarters Norfolk County Fire and Rescue Services Approval Form Vendor Fire Safety Requirements
More informationLiberal Arts and Humanities. Building # 275. Emergency Evacuation Plan
Liberal Arts and Humanities Building # 275 Emergency Evacuation Plan Prepared by: Jeff Watson Revised: June 16, 2016 Last Revision: March 19, 2014 Introduction All campus facilities are required to have
More informationFire Prevention Plan for St. Barbara Hall 3904 Winding Way
Military Science Department for St. Barbara Hall 3904 Winding Way Xavier University November 16, 2006 Ken Grossman Page 1 10/29/2013 Table of Contents Introduction... 3 Responsibilities... 3 Major Workplace
More informationUpon activation of the building fire alarm system or verbal command to evacuate a building: All personnel shall evacuate the building immediately.
Emergency Preparedness Evacuation Plan Upon activation of the building fire alarm system or verbal command to evacuate a building: All personnel shall evacuate the building immediately. 1. Staff in labs
More informationFire Prevention Plan for Residence Life 1625 Musketeer Drive
Residence Life for Residence Life 1625 Musketeer Drive Xavier University November 14, 2006 Ken Grossman Page 1 10/29/2013 Table of Contents Introduction... 3 Responsibilities... 3 Major Workplace Fire
More informationGrossmont Cuyamaca Community College District Fire Report 2012
Grossmont Cuyamaca Community College District Fire Report 2012 Overview The Higher Education Opportunity Act (Public Law 110-315) became law in August, 2008. It requires all academic institutions to produce
More informationBusiness Emergency Plan
Business Name Date Company Name Address Telephone Contact Name Title Last Revision Date Policy and Organizational Statements Identify the goals and objectives for the emergency response plan. Define what
More informationEmergency Action Plan for Sycamore House 3818 Winding Way
Psychological Services Center Emergency Action Plan for Sycamore House 3818 Winding Way Xavier University November 17, 2006 Ken Grossman Page 1 11/7/2013 Table of Contents Emergency Action Plan Introduction...
More informationEmergency Action Plans (OSHA ) Abstract. Introduction. Emergency Action Plan (EAP) Elements of an EAP
1 Fire Protection Report Number: FP-45-10 Release Date: July 12, 2000 Section Title: Emergency Management Abstract OSHA 1910.38 requires employers of more than ten people to establish a written emergency
More informationTable of Contents. EMERGENCY PROCEDURES Policy 190
Table of Contents EMERGENCY PROCEDURES Policy 190 1. TRAINING ON EMERGENCY PROCEDURES... 2 2. EVACUATION PLAN... 2 2.1 Purpose... 2 2.2 Initiation Of Evacuation Alarm... 2 2.3 Evacuation Procedures...
More informationDUNCAN STUDENT CENTER. Emergency Action Plan
DUNCAN STUDENT CENTER Emergency Action Plan August 21, 2017 DUNCAN STUDENT CENTER - EMERGENCY ACTION PLAN An emergency action plan describes the actions employees should take in case of fire or other emergency
More informationBP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6
BP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6 1. Purpose This policy sets forth requirements for preventing and detecting fires, sounding an alarm, and suppressing fires. Fire protection
More informationEmergency Evacuation Plan. Kettering Labs. School of Engineering
Emergency Evacuation Plan Kettering Labs School of Engineering May 2018 Table of Contents Section I: Purpose and Objectives Section II: General Guidelines Section III: Responsibilities of Emergency Coordinator
More informationVICI. Emergency Evacuation Plan
VICI Building # 1814 664 Raymond Stotzer Pkwy College Station, TX 77843 Emergency Evacuation Plan Prepared by: Heather Quiram, LeTisha Zepeda and Michaela Thomas June 23, 2016 Last Revision: June 23, 2016
More informationEvacuation and Lockdown Plan
Evacuation and Lockdown Plan Table of Contents 1 Introduction... 2 2 Evacuation... 2 2.1 General guidelines... 2 2.2 Evacuation of persons with disabilities... 3 2.3 Accountability for students... 3 2.4
More informationFire Safety Plan Information. For Construction and Demolition Sites
Fire Safety Plan Information For Construction and Demolition Sites FIRE CODE INTERPRETATION November 2009 FCI-09-03 Page 1 of 8 ISSUE: FIRE SAFETY PLAN Construction and Demolition Sites Safety provisions
More informationAgency for Health Care Administration
Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title
More informationIIPP. Injury & Illness Prevention Program Hartog Drive San Jose CA Responsibilities. Workplace Hazards. Training. Incident Investigations
Injury & Illness Prevention Program Responsibilities Training Workplace Hazards IIPP Recordkeeping Incident Investigations Employee Communications 1876 Hartog Drive San Jose CA 95131 Page 1 of 23 IIPP
More information