FS1. User manual FLOAT LEVEL GAUGE. No ZAM-SERVIS s.r.o. Křišťanova 1116/14 Ostrava-Přívoz
|
|
- Christiana Sutton
- 5 years ago
- Views:
Transcription
1 User manual FLOAT LEVEL GAUGE No This User manual includes: Instructions for assembly, installation, commissioning, use, operation, settings, maintenance and servicing, disassembly, disposal and technical conditions. Keep this manual for future use! User manual 1/9
2 ontents User manual...3 Use...3 Description and function...3 aution!...4 Installation and assembly...4 Operating instructions...4 Maintenance...4 Repairs and spare parts...4 Delivery, transport and storage...4 Fire safety, ecology, disposal, recycling...5 Manufacturer and service organization...5 Related standards, regulations and documents...5 Technical parameters...6 Appearance...7 Dimension Drawing User manual 2/9
3 User manual This User manual includes instructions for assembly, installation, commissioning, use, operation, setting, maintenance and servicing, disassembly and disposal, and technical specifications. All workers installing, putting into operation, operating, maintaining and servicing the unit must be demonstrably familiarized with these operating instructions. Keep this manual for future use. Use The float level gauge is intended for switching on/off control and signalling circuits depending on liquid level. Thanks to its construction, it can be used in heavy duty industrial conditions in environments with high relative humidity; it can be immersed also in mechanically polluted liquids with the specific density up to 1.4 g/cm 3 in the temperature range from +1 to 80 o. It can be used for all inflammable liquids. It is made with IP68 protection and is also designed for potentially explosive atmospheres with occurrence of methane in IM2 Ex ia Mb design according to ČSN EN , for underground mines. The device can be used in the gas and monitoring system for level monitoring. Description and function The float level gauge (Fig. 2) is made as a waterproof case hanging on a wire. There is a switching mechanism inside the case. For level gauging application in potentially explosive atmospheres with occurrence of methane, the float level gauge is housed in a special enclosure. After it is immersed in a liquid, the float level gauge turns over due to the upward hydrostatic pressure and weights, and the microswitch connects or disconnects contacts. The required difference for overturning the float is from 160 to 180 mm. On Level difference Off Fig. 1. Float level gauge principle User manual 3/9
4 aution! 1. The device must not be used where there is a risk of mechanical damage or risk of chemical damage of the supply cable or case of the level gauge! 2. In case of mine applications, the level gauge is allowed to be connected only to intrinsically safe circuits! 3. The maximum length of the supply cable must be selected so that the values of o L o specified in the certificate of the used follow-up unit are not exceeded. Installation and assembly 1. At surface applications, protection against electric shock for the device is ensured by supplying from a safety transformer and by IP68 protection. The level gauge wire is fixed to the tank above its maximum level. In special cases when the difference of levels comes up to 5 m, it is recommended to place the level gauge behind a partition, which calms the flow of liquid, or to fix it to the tank wall. 2. For level gauging application in potentially explosive atmospheres with occurrence of methane, the float level gauge is placed in a special enclosure (see Fig.), which is to be fixed to the timbering of mine roads where we want to gauge flooding of mine roads. Operating instructions After installed, the device operates unattended. Maintenance The device is maintenance-free. However, it is necessary to check the surface of the gauge and if supply wire for integrity. It is recommended to have the unit checked by personnel from the manufacturer or a relevant authorised representative once a year. Repairs and spare parts All repairs and spare parts are provided by the manufacturer. Delivery, transport and storage Order code: for mine Float level gauge including special structure The delivery includes: This User manual A copy of the Declaration of onformity The product itself All components must be transported with attention to reduce potential shocks and vibrations. Store User manual 4/9
5 in dry places at temperatures from 0 to 40 in one layer. Fire safety, ecology, disposal, recycling Do not expose to open flame; harmful substances are produced by burning. When operated properly, the product has no harmful effects on the environment and ecology. After expiration of the lifetime, return the product to the manufacturer for disposal. The address is listed below. After expiration of the lifetime, the electrical and electronic equipment may not be disposed of as ordinary municipal waste. The product must be forwarded to a relevant collection point for proper processing, regeneration and recycling of the electrical and electronic equipment. For more information about the collection point and recycling of this product, please contact the local authorities, a municipal waste management company at your place or the dealer where you purchased this product. Manufacturer and service organization ZAM - SERVIS s.r.o. Křišťanova 1116/14, Ostrava Přívoz, phone: zam@zam.cz Related standards, regulations and documents LVD: ČSN Low voltage electrical installations Electric installations Part 4: Safety hapter 41: Protection against electric shock. ČSN EN ČSN EN ed2 ČSN EN ATEX: ČSN EN ČSN EN Degrees of protection provided by enclosures (IP ode) Safety of power transformers, power supply units Part 2-1: Particular requirements for separating transformers for general use Part 2: Particular requirements for automatic electrical water level operating controls of the float type for household and similar applications Explosive atmospheres Part 0: Equipment General requirements Explosive atmospheres Part 11: Equipment protection by intrinsic safety i User manual 5/9
6 Technical parameters ZAM-SERVIS s.r.o. Křišťanova 1116/14 Ostrava-Přívoz Nominal supply voltage Surface: 48 V from safety transformer Nominal current Surface 2 A/D, 4 A/A Mine Supply voltage U i 30 V A/D Input power P i 3.07 W Inductance L i 0 apacity i 0 Service life engagements Weight 1.3kg Dimensions ase diameter 75 mm, length 123 mm Design I M2 Ex ia Mb User manual 6/9
7 Appearance Level gauge & supply cable Level gauge fastening structure Fig. 2 detector appearance User manual 7/9
8 Dimension Drawing ZAM-SERVIS s.r.o. Křišťanova 1116/14 Ostrava-Přívoz Supply cable attachment Tiltable cover Reinforcement holder Float Holes Vessel body Fig. 3 Fastening frame installation User manual 8/9
9 DKD11-IO X DKD11-IO X Fig. 3 Exaple connection with DKD11-IO, basic connection and with the rollover control. DKD11-ABV 12 DKD11-ABV X X X X Fig. 3 Exaple connection with DKD11-ABV, basic connection and with the rollover control User manual 9/9
INSTRUCTIONS FOR OPERATION
ZAM-SERVIS s.r.o., Křišťanova 1116/14, 70200 Ostrava Přívoz, Phone: O69/6135422, Fax: 069/6135425 E-mail: obchod@zam-servis.cz INSTRUCTIONS FOR OPERATION (TRANSPORT, STORAGE, INSTALLATION, ASSEMBLY AND
More informationEU DECLARATION OF CONFORMITY
The Low Voltage Directive (LVD) 2014/35/EU and Electromagnetic Compatibility (EMC) Directive 2014/30/EU. Capacitive level sensor DLS 27N(T) Capacitive level sensor type DLS 27N(T) is designed to bistable
More informationInstruction Manual. Alarm Unit For Low Gas Level # Read manual before use! Observe all safety information! Keep manual for future use!
Mess-, Regel- und Überwachungsgeräte für Haustechnik, Industrie und Umweltschutz Lindenstraße 20 74363 Güglingen Telefon +49 7135-102-0 Service +49 7135-102-211 Telefax +49 7135-102-147 info@afriso.de
More informationStira e Aspira M0S O08
Stira e Aspira M0S05484 1O08 Read these instructions carefully before using the appliance. KEY 1) Ironing surface 2) Opening handle 3) Vaporella supporting-grill 4) On/off switch 5) Suction switch 6) Supply
More informationDUR 40Ex Intrinsically Safe SMOKE DETECTOR
DUR 40Ex Intrinsically Safe SMOKE DETECTOR Installation and Maintenance Manual IK E317 001GB IB Issue 2 IK E317 001GB The Universal Optical Smoke Detector DUR 40Ex covered by the present manual, complies
More informationNZQA registered unit standard version 1 Page 1 of 5. Install fixed gas detection apparatus in hazardous areas
Page 1 of 5 Title Install fixed gas detection apparatus in hazardous areas Level 4 Credits 2 Purpose This unit standard covers the installation, calibration, and response checking of fixed gas detection
More informationATEX, NOMENCLATURE AND CODING
Technical Notes ATEX, NOMENCLATURE AND CODING The intent of this technical note is approach to the user to the ATEX normative. For this we will begin defining, what is an explosive atmosphere, what are
More informationCRU-S Series Stainless Steel Condensate Recovery Unit
IM-UK-CRU-S UK Issue 1 CRU-S Series Stainless Steel Condensate Recovery Unit 1. Safety information 2. General product information 3. Installation 4. Commissioning 5. Storage, shutdown and equipment protection
More informationTIH 300 S / TIH 400 S / TIH 500 S / TIH 700 S / TIH 900 S / TIH 1100 S
TIH 300 S / TIH 400 S / TIH 500 S / TIH 700 S / TIH 900 S / TIH 1100 S EN OPERATING MANUAL INFRARED HEATING PANEL TRT-BA-TIH300S-TIH400S-TIH500S-TIH700S-TIH900S-TIH1100S-TC-002-EN Table of contents Notes
More informationFLAMMABLE GAS DETECTOR DAX 3F-C INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS. DAX3FC_MAN01_EN.indd Ver. V1R2
FLAMMABLE GAS DETECTOR INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS DAX3FC_MAN01_EN.indd Ver. V1R2 Introduction These instructions must be read carefully by any person who has or will have the
More informationFlammable gases Detectors. Model DAX 03F DAX 03F- C DAX 03F- H. Note for installation, use and maintenance. Version 1.2
Flammable gases Detectors Model DAX 03F DAX 03F- C DAX 03F- H Note for installation, use and maintenance Version 1.2 Introduction This handbook must be read carefully by any person who has or will have
More informationATEX, NOMENCLATURE AND CODING
ATEX, NOMENCLATURE AND CODING The intent of this technical note is approach to the user to the ATEX normative. For this we will begin defining, what is an explosive atmosphere, what are ATEX, as well as
More informationPressure sensors. Ex ia I / IIC T6 acc. to ATEX. Features. Description. Measuring ranges. Applications
Force Pressure Temperature Switch Pressure sensors Ex ia I / IIC T6 acc. to ATEX with internal diaphragm with front flush diaphragm Accuracy: 0,25% and 0,5 % Standard output: 4...20 ma; 2-wire system Description
More informationEx SOLENOID / ALARM DRIVER. PRepower 5203B. Table of contents. Applications Safety instructions Technical characteristics...
14 Ex SOLENOID / ALARM DRIVER PRepower 5203B Table of contents Warnings... 16 Safety instructions... 17 Declaration of Conformity... 19 How to dismantle SYSTEM 5000... 20 Application... 21 Technical characteristics...
More informationVQ500 Series Combustible Gas Detector Elements
VQ500 Series Combustible Gas Detector Elements FEATURES * Optimised for combustible gases and vapours * Thermal conductivity versions available * Certified flameproof component * Integral pellistors *
More informationMatters Needing Attention of Electrical Equipment Installation Engineering in Hazardous Areas. Wang Qiaoli
Matters Needing Attention of Electrical Equipment Installation Engineering in Hazardous Areas Wang Qiaoli Nanyang Explosion Protected Electrical Apparatus Research Institute wqliii@163.com Keywords: hazardous
More information1. GENERAL TECHNICAL INFORMATION
1. GENERAL TECHNICAL INFORMATION 1.1 EXPLOSIVE ATMOSPHERES: Every time that dangerous quantities and concentration of flammable gas, vapors mixture or dust clouds exists, risk of explosions may arise.
More informationTrusted worldwide since 1989 INTRINSICALLY SAFE RANGE
Trusted worldwide since 1989 INTRINSICALLY SAFE RANGE Trusted worldwide We are now in our 28th year designing and manufacturing portable rechargeable lighting systems. Our main objective is to offer high
More informationORIGINAL OPERATING INSTRUCTIONS ASH VACUUM CLEANER / 18L
ORIGINAL OPERATING INSTRUCTIONS 02-11 ASH VACUUM CLEANER / 18L IMPORTANT! SAFETY INSTRUCTIONS When using the appliance, a few safety precautions must be observed to avoid injuries and damage. Please read
More informationApproval of Ex (Electrical) Equipment for use/installation in Hazardous Areas.
Approval of Ex (Electrical) Equipment for use/installation in Hazardous Areas. Requirement under Rule 102 of the Petroleum Rules, 2002 lays down that no electrical wiring shall be installed and no electrical
More informationMODEL: SP12C7. (Portable 4 gas detector) Operating Manual
MODEL: SP12C7 (Portable 4 gas detector) Operating Manual Guarantee and Repair Senko Co., Ltd. guarantees the products of SP series for 24 months from the shipping date and repairs or replaces the defected
More informationWHAT WHITE PAPER IS POTENTIALLY EXPLOSIVE ATMOSPHERE CERTIFICATION AND WHY YOU. June 2010
WHITE PAPER WHAT IS POTENTIALLY EXPLOSIVE ATMOSPHERE CERTIFICATION AND WHY YOU MAY NEED IT! June 2010 Copyright Extronics Ltd 2010 The information contained in this document is subject to change without
More informationOPERATION AND MONTAGE MANUAL ROOF FANS
NO RFEC/U/2017-1 (EN) (valid since 18.08.2017) ROOF FANS RF/EC...-... / RFV/EC...-... Venture Industries Sp. z o.o. is not responsible for any damage caused by improper use of the fan and reserves the
More informationAIRGOCLEAN 10 E OPERATING MANUAL AIR CLEANER TRT-BA-AIRGOCLEAN10E-TC-001-EN
AIRGOCLEAN 10 E EN OPERATING MANUAL AIR CLEANER TRT-BA-AIRGOCLEAN10E-TC-001-EN Table of contents Notes regarding the operating manual... 1 You can download the current version of the operating manual and
More informationUSER MANUAL FOR EXPLOSION PROTECTED FLUORESCENT LIGHT FITTING type PSF 236
CONTENT 1. Manufacturer 1 2. General safety informations 1 3. Purpose 2 4. Product compliance 2 5. Degree of protection and technical data 2 6. Type 3 7. Mounting and installation 3 8. Dimensions 6 9.
More informationTTV 1500 / TTV 3000 OPERATING MANUAL CONVEYING FAN TRT-BA-TTV TC EN
TTV 1500 / TTV 3000 EN OPERATING MANUAL CONVEYING FAN TRT-BA-TTV1500-3000-TC2016-26-004-EN Table of contents Notes regarding the operating manual... 2 You can download the current version of the operating
More informationMETAL CERAMIC FAN HEATER
EN METAL CERAMIC FAN HEATER OPERATING INSTRUCTIONS Read the instructions carefully before installing and operating the appliance or performing maintenance operations. Observe all the safety instructions;
More informationHazardous Areas - EXPLOSIONPROOF SOLENOIDS
Hazardous Areas - EXPLOSIONPROOF SOLENOIDS SOME HISTORY The classification of hazardous areas into zones established the level of protection required for electrical equipment installed in explosive gas
More informationGuide to Explosion Protection and Plant Safety
Guide to Explosion Protection and Plant Safety Explosion Protection and Plant Safety In almost every industrial application flammable substances are used. Equipment installed in these areas needs to be
More informationELECTRIC HEATER WITH CARBON FIBER HEATING ELEMENTS
EN ELECTRIC HEATER WITH CARBON FIBER HEATING ELEMENTS OPERATING INSTRUCTIONS Read the instructions carefully before installing and operating the appliance or performing maintenance operations. Observe
More informationtesto 316-EX gas leak detector Instruction manual
testo 316-EX gas leak detector Instruction manual 2 1 Safety and the environment 1 Safety and the environment 1.1. About this document Use > Please read this documentation through carefully and familiarize
More informationRead this manual through carefully before installing/using the cleaner, paying special attention to the SAFETY INSTRUCTIONS
PW1370TD 2 EN Read this manual through carefully before installing/using the cleaner, paying special attention to the SAFETY INSTRUCTIONS 3 E3 E1 C3 A1-A2-A3-A4 B4 B1 B5 B2 C1 B3 D 1 4 1 2 3 4 5 6 7 Ø13
More informationA guide to the use of electrical equipment in potentially explosive atmospheres To view this document in PDF format click here.
A guide to the use of electrical equipment in potentially explosive atmospheres To view this document in PDF format click here Introduction Potentially Explosive Atmospheres exist where there is a risk
More informationDXAPV3N. Air Purifier. With. Enviro-neutralising Technology DXAPV3N
DXAPV3N Air Purifier With Enviro-neutralising Technology DXAPV3N WARNING: Please read before use these instructions and keep them for future reference. SAFETY WARNINGS ATTENTION! This unit is regarded
More informationOPERATING INSTRUCTIONS
EN TABLE AND STAND FAN OPERATING INSTRUCTIONS Read the instructions carefully before operating the appliance or carrying out maintenance operations. Observe all the safety instructions; failure to observe
More informationUL Topic III. Converting European EEx Certificates. Into. North American Division Certificates
Note: While this material was originally prepared for presentation in February 1999, it has been updated to reflect the evolving technical requirements now applicable as of April 2003. UL Topic III Converting
More informationInstallation, Operating and Servicing Instructions
Installation, Operating and Servicing Instructions Opus 700 Electric Induction Hobs OE7013, OE7014 Please make a note of your product details for future use: Date Purchased: Model Number: Serial Number:
More informationATM Lighting sp. z o.o
INSTALLATION AND MAINTENANCE MANUAL FOR EXPLOSIONPROOF LIGHT FITTING EXL210LED Carefully read the instructions before mounting the light fitting. ATM Lighting sp. z o.o., ul. Budowlanych 31, 80-298 Gdańsk,
More informationHYTEK ATEX APPROVED BUND ALARM
Technical Data HYTEK ATEX APPROVED BUND ALARM BA3A.BP Applies to the following models only: - BA3A.BP - BA3A.BS - BA3A.BSP - BA3A.BAB Please read carefully before commencing installation Registered Office:
More informationInductive slot sensor
0102 Model Number Features 2 mm slot width Technical Data specifications Switching function Normally closed (NC) Output type NAMUR Slot width 2 mm Depth of immersion (lateral) 5... 7 mm, typ. 6 mm Output
More informationIS (Intrinsic safety) - Ex (Epsilon x) ATEX CENELEC
IS (Intrinsic safety) - Ex (Epsilon x) ATEX CENELEC By: Helge Knudsen, Test&Approval, Niros Telecommunication A/S You may have heard those expressions concerning Transceivers and other electric equipment
More informationPolti S.p.A. reserves the right to change equipment or accessory specification without prior notice.
Daisy R 1) Iron temperature adjustment knob 2) Boiler ON/OFF switch 3) Steam button 3a) Iron heating indicator light 3b) Pressure indicator light 3c) Continuous steam jet button 4) Iron on/off switch 5)
More informationSubmersible Garden Pump USER'S MANUAL
FVC 5005 EC FVC 5010 EK Table of Contents 3 EN Submersible Garden Pump USER'S MANUAL Thank you for purchasing this pump. Before you start using it, please, carefully read this user's manual and save it
More informationMODEL: SP2nd (Portable Single Gas Detector) Operating Manual
MODEL: SP2nd (Portable Single Gas Detector) Operating Manual Edaphic Scientific Pty Ltd www.edaphic.com.au info@edaphic.com.au Guarantee and Repair Senko Co., Ltd. guarantees the products of SP series
More informationINTRINSICALLY SAFE LIGHTING RANGE
Trusted worldwide since 1989 INTRINSICALLY SAFE LIGHTING RANGE SAFE PORTABLE RECHARGEABLE AC MAINS Trusted worldwide We are now in our 28th year designing and manufacturing portable rechargeable lighting
More informationIECEx Certificate of Conformity
IECEx Certificate of Conformity INTERNATIONAL ELECTROTECHNICAL COMMISSION IEC Certification Scheme for Explosive Atmospheres for rules and details of the IECEx Scheme visit www.iecex.com Certificate IECEx
More informationLUCCI AIRFUSION BREEZE WALL FAN INSTALLATION OPERATION MAINTENANCE WARRANTY INFORMATION CAUTION READ INSTRUCTIONS CAREFULLY FOR SAFE
LUCCI AIRFUSION BREEZE WALL FAN INSTALLATION OPERATION MAINTENANCE WARRANTY INFORMATION CAUTION READ INSTRUCTIONS CAREFULLY FOR SAFE INSTALLATION AND FAN OPERATION. V1.0- E N ( 0 8 / 2 0 1 8 ) THANK YOU
More informationSurvey of electrical equipment installed in hazardous areas on tankers
(June 2015) Survey of electrical equipment installed in hazardous areas on tankers 1. Application The recommendations in this document apply for survey of electrical installation in hazardous areas on
More informationM-Switch Float Operated Liquid Level Switch
Product Data Sheet M-Switch Float Operated Liquid Level Switch Reliably detects the liquid level to give a voltage free contact operation for alarm signalling or as part of a pump control system Small
More informationInspection Light LED 6149/2. Operating instructions EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN
Inspection Light LED Operating instructions Additional languages www.stahl-ex.com Contents 1 General Information...3 1.1 Manufacturer...3 1.2 Information regarding the operating instructions...3 1.3 Conformity
More informationMAINS KLARGESTER SEPARATOR ALARM INSTALLATION & OPERATIONS MANUAL
MAINS KLARGESTER SEPARATOR ALARM INSTALLATION & OPERATIONS MANUAL Contents IMPORTANT... 3 General Description... 4 General Operation... 4 Changing Factory Settings... 4 Alarm Type... 4 Check Interval...
More informationMICROpeL 75 Combustible Gas Sensor Part Number: PM
MICROpeL 75 Combustible Gas Sensor Part Number: PM759-000 Key Features & Benefits: ATEX, UL and CSA Approvals Withstands EN/IEC 60079-0 impact test Enhanced H 2 S and silicone poison resistance Reduced
More informationinstructions for use Air Purifier with ionizer _00/
Instructions for use Air Purifier with Ionizer 5713710041_00/07.12 H T S R Q L P N O M I H A B C D E U F G Fig. 2 Fig. 3 Fig. 4 2 introduction Thank you for choosing a De Longhi product. Please take a
More informationSAFETY AND OPERATING MANUAL. Original Instructions 5.0
SAFETY AND OPERATING MANUAL Original Instructions 5.0 Read all safety warnings and all instructions before use. Failure to follow the warnings and instructions may result in electric shock, fire and/or
More informationPLUG-IN PERSONAL CERAMIC FAN HEATER
EN PLUG-IN PERSONAL CERAMIC FAN HEATER This product is only suitable for well insulated spaces or occasional use. The front metal grill becomes very hot during use. Therefore avoid contact of unprotected
More informationSafety instructions VEGADIF DF65.GX*****H/Z/P/F***** IECEx BVS
Safety instructions VEGADIF DF65.GX*****H/Z/P/F***** IECEx BVS 10.0008 Ex td A20, A20/21, A20/22, A21 IP66 T 0044 37675 Contents 1 Area of applicability 3 2 General information 3 2.1 Zone 20 instruments
More informationMODEL: SP12C7. (Portable 4 gas detector) Operating Manual
MODEL: SP12C7 (Portable 4 gas detector) Operating Manual Guarantee and Repair Senko Co., Ltd. guarantees the products of SP series for 24 months from the shipping date and repairs or replaces the defected
More informationUSER MANUAL FOR EXPLOSION PROTECTED FLUORESCENT LIGHT FITTING type PSF 218
CONTENT 1. Manufacturer 1 2. General safety informations 1 3. Purpose 2 4. Product compliance 2 5. Degree of protection and technical data 2 6. Type 3 7. Mounting and installation 3 8. Dimensions 6 9.
More informationAD.3.XG... Atex directive ch. I Page 22 Atex classification ch. I Page 23. Tab.1 Assembly ch. I Page 25
Atex directive ch. I Page 22 Atex classification ch. I Page 23 Series ch. I Page 24 Technical specifications Ch. I Page 24 Ordering code ch. I Page 24 Tab. Assembly ch. I Page 25 Tab. 2 Voltages ch. I
More informationCRU 200 and 500 Series Condensate Recovery Unit Installation and Maintenance Instructions
6810850/1 IM-P681-07 ST Issue 1 CRU 200 and 500 Series Condensate Recovery Unit Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning
More informationOilSET Installation and Operating Instructions. Oil Separator Alarm Device with SET/DM3AL sensor
Labkotec UK Ltd Adminicle House 1 Lumb Lane Audenshaw Manchester M34 5WH GREAT BRITAIN Tel: 0844 3350 477 Fax: 0161 4281 179 E-mail: info@labkotec.co.uk 10.8.2012 Internet: www.labkotec.co.uk 1/13 OilSET-1000
More informationReflux Extractor BM106. Impact Test Equipment Ltd & User Guide. User Guide
Reflux Extractor BM106 Impact Test Equipment Ltd www.impact-test.co.uk & www.impact-test.com User Guide User Guide Impact Test Equipment Ltd. Building 21 Stevenston Ind. Est. Stevenston Ayrshire KA20 3LR
More informationJunction boxes control boxes THU 93.1 THU 93.6 THU 94.1 THU 94.9 PTB 98 ATEX March 1999
Junction boxes control boxes THU 93.1 THU 93.6 THU 94.1 THU 94.9 PTB 98 ATEX 3116 March 1999 thuba Ltd. CH-4015 Basle Telefon +41 061 307 80 00 Telefax +41 061 307 80 10 Headoffice@thuba.com www.thuba.com
More informationOperating Instructions
Operating Instructions Before first use of the unit read these operating instructions and act in accordance with them. 5.962-066.0 02/07 Dear Customer, Please read and comply with these instructions prior
More informationThe CENTURY. High Performance Oscillating Fan OWNER S GUIDE FOR MODELS 9002X & 9702X
The CENTURY High Performance Oscillating Fan OWNER S GUIDE FOR MODELS 9002X & 9702X 41479-01 01/06/2005 41479-01 Rev 01-06-05.pmd 1 IMPORTANT SAFETY INFORMATION Read & Save These Instructions WARNING To
More informationOPERATION AND MONTAGE MANUAL ROOF FANS
NO RF/U/2017 (ENGLISH) (valid since 13.10.2017) ROOF FANS RF / RFV Venture Industries Sp. z o.o. is not responsible for any damage caused by improper use of the fan and reserves the right to modify this
More informationAdditional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-nA.
Additional Operating Instructions SITRANS F Vortex flowmeters Ex-nA Edition 08/207 CONTENTS Safety instructions 3. General notes... 3.2 EU conformity... 3.3 Approval according to the IECEx scheme... 3.4
More informationGTF 103-Ex. GREISINGER electronic GmbH D Regenstauf, Hans-Sachs-Straße 26. Temperature Probe for potentially explosive atmospheres
Z31.0.XX.6C-11 Temperature Probe for potentially explosive atmospheres (Measuring ranges from -200 to +900 C) Operating Manual GTF 103-Ex 0081 GREISINGER electronic GmbH D - 93128 Regenstauf, Hans-Sachs-Straße
More informationREGULATIONS EUROPEAN ATEX DIRECTIVE. INTERNATIONAL SCHEME: IECEx AREAS CLASSIFICATION DEFINED BY DIRECTIVE 1999/92/EC
EUROPEAN ATEX DIRECTIVE > European Directive 2014/34/EU ATEX Directive 2014/34/EU is a "new approach" directive that applies to protective systems against explosions as well as all equipment used in or
More informationAdditional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-d.
Additional Operating Instructions SITRANS F Vortex flowmeters Ex-d Edition 09/208 CONTENTS Safety instructions 3. General notes... 3.2 EU conformity... 3.3 Approval according to the IECEx scheme... 3.4
More informationSFE 2311BK. EN Desktop Fan. Copyright 2017, Fast ČR, a.s
SFE 2311BK EN Desktop Fan - 1 - EN Desktop Fan Important safety instructions READ CAREFULLY AND STORE FOR FUTURE USE. This appliance may be used by children 8 years of age and older and by persons with
More informationNON ELECTRICAL EQUIPMENT IN HAZARDOUS AREAS
NON ELECTRICAL EQUIPMENT IN HAZARDOUS AREAS The ATEX Directive consists of two EU Directives, ATEX Directive 2014/34/EU and ATEX Directive 99/92/EC. ATEX Directive 2014/34/EU embodies the European minimum
More informationVL FOREVER 600 INOX - VL FOREVER 600
7 10 8 3a 11 9 3 7 11 6 4 5 2 1 10 8 6a 3a 9 3 Fig.1 2 Fig.2 1 Fig.3 Fig.4 Fig.5 VL FOREVER 600 /600 INOX M0S08218 1O07 Read these instructions carefully before using the appliance. KEY 1) Cable winder
More informationPortable Oxygen Monitor OX-07. (Type B) <No Gas alarm type> Operating Manual
PT0E-0922 Portable Oxygen Monitor OX-07 (Type B) Operating Manual Request for the Customers Read and understand this operating manual before using this gas monitor. Use it in accordance
More informationLocal air conditioner
Instruction Manual Local air conditioner LAC08C16 Contents Safety Warnings...4 Unpacking...7 Product Overview...8 Front View...8 Rear View...8 Control Panel...9 Remote Control... 10 Moving the Unit...10
More informationTechnical Data. General specifications Switching element function Rated operating distance s n 4 mm
0102 Model Number Features 4 mm non-flush Accessories BF 12 Mounting flange, 12 mm Technical Data specifications Switching element function NAMUR, NO Rated operating distance s n 4 mm Installation non-flush
More informationENGLISH INSTALLATION AND USER S MANUAL FRENCH NOTICE D INSTALLATION ET D UTILISATION ITALIAN MANUALE D ISTRUZIONE
ENGLISH INSTALLATION AND USER S MANUAL FRENCH NOTICE D INSTALLATION ET D UTILISATION ITALIAN MANUALE D ISTRUZIONE 1 INSTALLATION AND USER S MANUAL CONTENT INTRODUCTION 03 SAFETY PRECAUTION 03 SPECIFICATION
More informationINSTRUCTION MANUAL IS-mB1 Minialite Intrinsically Safe Round LED Beacon
INSTRUCTION MANUAL Minialite Intrinsically Safe Round LED This instruction sheet describes installations which conform to EN60079:Part14:2008 Electrical Installation in Hazardous Areas. When designing
More informationMSM400 Ultrasonic Suspended Solids Monitoring and Control System
Product Data Sheet MSM400 Ultrasonic Suspended Solids Monitoring and Control System Continuous sludge discharge monitor for up to 50% suspended solid The MSM400 system contains a control unit and either
More information750MM INDUSTRIAL PEDESTAL DRUM FAN
750MM INDUSTRIAL PEDESTAL DRUM FAN 360 ROTATION & 2 ADJUSTABLE TILT CONSTRUCTION INCLUDES ANTI-TRIP BASE ENERGY EFFICIENT MOTOR KP1013 ED1 (JULY 15) 1 Table of Contents Know Your Product... 2 Fan Safety
More informationManual for Ceiling Patio Heater
Manual for Ceiling Patio Heater 13-01-2017 Please read these instructions carefully before using your new halogen heater. Thank you for choosing our Indoor/Outdoor Patio Heater. This owner s manual will
More informationATM Lighting sp. z o.o
INSTALLATION AND MAINTENANCE MANUAL FOR EXPLOSIONPROOF LIGHT FITTING EXL390LED Carefully read the instructions before mounting the light fitting. ATM Lighting sp. z o.o., ul. Budowlanych 31, 80-298 Gdańsk,
More informationIreland. Australia. New Zealand
UK Ireland Australia New Zealand 2 3 4 5 Intended use Your Black & Decker vacuum cleaner has been designed to vacuum dry substances. This product is intended for household use only. Safety instructions
More informationED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR
ED820 24V MODEL fire DETECTOR INSTRUCTION MANUAL Address: Enigma House, Enigma Business Park, Malvern, Worcestershire, WR14 1GD Tel: 44 (0)1684 891500 Fax: 44 (0)1684 891600 Email: sales@electronicdevices.co.uk
More informationWeighing Solutions for Hazardous Areas FULL COMPLIANCE WITH ATEX DIRECTIVE
Weighing Solutions for Hazardous Areas FULL COMPLIANCE WITH ATEX DIRECTIVE PUE HX5.EX explosion-proof hazardous area indicator ATEX APPROVAL PUE HX5.EX is a cutting-edge weighing indicator, designed to
More informationRegulated Ex-Heater HEX with internal controller, HEX with external controller II 3 G II 3 D
Regulated Ex-Heater HEX5-1.08 with internal controller, HEX5-2.08 with external controller II 3 G II 3 D Instruction Manual Version 1.02.00 Dear customer, we have made up this operating manual in such
More informationSHIATSU MASSAGE CUSHION
YOUR SAFETY & INSTRUCTION MANUAL PLEASE READ CAREFULLY SHIATSU MASSAGE CUSHION MODEL C90009 1 TECHNICAL DATA Description: Shiatsu Massage Cushion Power adaptor: Input: 100-240V ~50/60Hz 1.0A Max Output:
More informationSTAINLESS STEEL FLAMMABLE GAS DETECTOR DAX 3F-I INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS. DAX3FI_MAN01_EN Ver. V1R2
STAINLESS STEEL FLAMMABLE GAS DETECTOR INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS DAX3FI_MAN01_EN Ver. V1R2 1 Introduction These instructions must be read carefully by any person who has or will
More informationDräger X-am 7000 Multi-Gas Detection
Dräger X-am 7000 Multi-Gas Detection Dräger X-am 7000 is the solution for the simultaneous and continuous measurement of up to five gases. It is the ideal companion in a variety of applications where the
More informationInstruction Manual. Model No and Self-Leveling Cross-Line Laser Level
Self-Leveling Cross-Line Laser Level Model No. 40-6620 and 40-6625 Instruction Manual Congratulations on your choice of this Self-Leveling Cross-Line Laser Level. We suggest you read this instruction manual
More informationOPERATING INSTRUCTIONS
EN OIL FILLED RADIATOR OPERATING INSTRUCTIONS Read the instructions carefully before operating the panel or carrying out maintenance operations. Observe all the safety instructions; failure to observe
More informationNATIONAL RULES FOR ELECTRICAL INSTALLATIONS IN POTENTIALLY EXPLOSIVE ATMOSPHERES. ET 105:2001 (Second Edition)
NATIONAL RULES FOR ELECTRICAL INSTALLATIONS IN POTENTIALLY EXPLOSIVE ATMOSPHERES ET 105:2001 (Second Edition) Consolidated Amendments, Corrigenda and Errata 01/2010 Introduction When ET 105:2001 was originally
More informationSUPPLEMENT REPORT No.: XPL/13600/
(Pty) Ltd Certex Appointed Ex Laboratory Reg No: 1999/027771/07 Government Approved Test Laboratory (Previously AIA) T0104 7 Spanner rd, PO Box 467 Tel: +27 (11) 316 4601 Olifantsfontein Fax: +27 (11)
More informationOperation Manual Airbrush Compressor AH28A ARTICLE 34247
Operation Manual Airbrush Compressor AH28A ARTICLE 34247 Read and follow the operating instructions and safety information before using for the first time. Technical changes reserved! Due to further developments,
More informationSAFETY INSTRUCTIONS. euromotori. Safety Instructions electric motors LEX series
Pag. 1/6 Enclosure for asynchronous electric motors Series LEX 80,90,100,112,132,160,180,200,225,250,280,315 and 355 Ex na, Ex td execution II 3G, II 2D SAFETY INSTRUCTIONS euromotori motori elettrici
More informationSITRANS T. SITRANS T Explosion protected temperature sensor. General information. Marking of the degree of protection. Range of uses.
General information 1 Marking of the degree of protection 2 SITRANS T SITRANS T Explosion protected temperature sensor Operating Instructions Range of uses 3 Installation 4 Assembly and disassembly 5 Commissioning
More informationTranslation of the assembly instructions with operating instructions and technical appendix
BA Ex-SBU Switch box type SBU-x(1,2,3)x Translation of the assembly instructions with operating instructions and technical appendix In accordance with EU ATEX Directive 2014/32/EU In accordance with EU
More informationPERSONAL COMBUSTIBLE GAS DETECTOR
PERSONAL COMBUSTIBLE GAS DETECTOR FEATURES Continuous LCD Reading with Back Light Electronic Audio Alarm Visual Alarms include Icons and Red LED Easy Handling Certified Intrinsically Safe Auto Test When
More informationSuits all KPF849 models
Kambrook - Australia Ground Floor, Suite 2, 170-180 Bourke Rd Alexandria NSW 2015, Australia Locked Bag 2000 Botany NSW 1455 Customer Service Line 1300 139 798 Customer Service Fax 1800 621 337 www.kambrook.com.au
More informationOperating Instructions for Limit switch Model: NBK-R NBK-RM NBK-RT NBK-RA
Operating Instructions for Limit switch Model: NBK-R NBK-RM NBK-RT NBK-RA 1. Contents 1. Contents... 2 2. Note... 3 3. Instrument Inspection... 3 4. Regulation Use... 3 4.1 Electrical limit switch... 4
More information