The Johns Hopkins Health Systems July 12, 2013 Facilities Standard Specification SECTION LIGHTING CONTROL SYSTEM PART 1 - GENERAL

Size: px
Start display at page:

Download "The Johns Hopkins Health Systems July 12, 2013 Facilities Standard Specification SECTION LIGHTING CONTROL SYSTEM PART 1 - GENERAL"

Transcription

1 SECTION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. All of the Contract Documents, as listed on the Table of Contents and including General and Supplementary Conditions and Division 1, General Requirements, shall be included in, and made part of, this Section. 1.2 DESCRIPTION OF WORK A. Furnish and install a complete lighting control system. System shall include lighting control devices and microprocessor based programmable lighting controllers. They system shall include switches, photocells and other control devices as required including, but not limited to, wire, conduit and other materials required for the installation. Exact quantities and equipment configurations shall be determined by the equipment manufacturer based on plans, specifications and control schedules. B. The system shall utilize the following strategies for lighting control: 1. Smart Time Scheduling vs. time scheduled switching 2. Daylight Harvesting 3. Task Tuning to limit light levels for a particular task 4. Occupancy/Vacancy Control 5. Personal Control thru control via a workstation applet 6. Variable Load Shedding C. The system shall utilized DALI type intelligent fluorescent ballasts for fluorescent fixtures. D. The work under this Contract shall also include all labor, materials, tools, equipment, transportation, insurance, temporary protection, supervision and incidental items essential for proper installation and operation, even though not specifically mentioned or indicated on the drawings, but which are usually provided or are essential for proper installation and operation of all systems as indicated on the drawings and specified herein. E. Coordination will be required to incorporate features of the lighting control system into the lighting fixtures as additional options. One example would be ordering light fixtures with a particular ballast that supports the DALI protocol. F. The specifications and drawings describe the minimum requirements that must be met by the Contractor for the installation of all work as shown on the drawings and as specified hereinunder

2 G. Provide lighting control systems for the following: 1. Exterior/site/façade lighting. 2. Pedestrian connector/corridor. 3. Public spaces/main lobby/floor lobbies/public corridors. 4. Private and open offices 5. Conference and meeting rooms 6. Laboratories 7. Closets; janitorial, supply, medical and laundry 8. Utility rooms 9. Other rooms or spaces as indicated on the electrical drawings. 1.3 RELATED WORK A. For work to be included as part of this Section, to be furnished and installed by the Contractor, refer to the Related Work section of Specification Section & B. Carefully examine all of the Contract Documents, criteria sheets and all other Sections of the specifications for requirements which affect work under this Section, whether or not such work is specifically mentioned in this Section. For example, occupancy or light level sensors built into the light fixtures or DALI ballasts. 1.4 REFERENCES A. The control panels shall be tested and listed under the UL 916 Energy Management Equipment standards by a nationally recognized testing laboratory B. The control system shall comply with all applicable National Electrical Codes regarding electrical wiring standards. C. The control system shall comply with all applicable portions of the NEMA standards regarding the types of electrical equipment enclosures. D. All control equipment shall undergo strict inspection standards. The equipment shall be previously tested and burned-in at the factory prior to installation. 1.5 QUALITY ASSURANCE A. The manufacturers listed within this specification have been preselected for use on this project. No submittal will be accepted from a manufacturer other than specified. B. To ensure system compatibility, all components of the lighting control system including panels, control devices, etc. shall be the products of one manufacturer

3 1.6 WARRANTY A. Attention is directed to provisions of the General Requirements, Supplementary General Requirements, Section Closeout Procedures and Section Electrical Special Conditions regarding guarantees and warranties for the work under this Contract. B. The manufacturer shall warrant each new system for a period of two (2) years from the date of substantial completion/owner occupancy, to be free from defects in the material and workmanship under the conditions of normal use and specified ambient temperature when installed and operated under the manufacturer s product specifications in accordance with the applicable National Electrical Code and Safety of Standards of Underwriter s Laboratory. C. This warranty covers the diagnostics of problems with the lighting control system and the cost of labor for repair, replacement, or adjustment of any and all the manufacturer s components, as necessary to restore the system to normal operation. D. The warrantee shall cover the complete system as specified herein including, but not limited to: 1. Control panels 2. Electronics 3. Control stations 4. Motion sensors 1.7 QUALIFICATIONS A. The manufacturer of the assembly shall be the manufacturer of the major components within the assembly. B. For the equipment specified herein, the manufacturer shall be ISO 9001 certified. C. The manufacturer of this equipment shall have produced similar electrical equipment for a minimum period of five (5) years. When requested by the Engineer, an acceptable list of installations with similar equipment shall be provided demonstrating compliance with this requirement. 1.8 MANUFACTURERS A. The following manufacturers shall be considered acceptable to supply the dimming system as herein specified: 1. Lithonia Acuity Brands 2. ILC 3. Cooper Controls 4. Lutron Quantum 5. Philips

4 B. The listing of a manufacturer as "acceptable" does not imply automatic approval. It is the sole responsibility of the Contractor to ensure that any price quotations received and submittals made are for devices that meet or exceed the specifications included herein. 1.9 SUBMITTALS A. Prepare and submit shop drawings in accordance with the requirements hereinbefore specified, and with the Shop Drawings, Product Data and Samples Section in the manner described therein, modified as noted hereinafter. B. Submit complete manufacturer's product data of all materials and systems to the Architect for approval, consisting of complete product description and specifications, complete performance test data, complete preparation and installation instructions, and all other pertinent technical data required for complete product and product use information. C. All shop drawings shall have clearly marked the appropriate specification number or drawing designation for identification of the submittal. D. Disposition of shop drawings shall not relieve the Contractor from the responsibility for deviations from drawings or specifications unless he has submitted, in writing, a letter itemizing or calling attention to such deviations at time of submission and secured written approval from the Architect, nor shall such disposition of shop drawings relieve the Contractor from responsibility for errors in shop drawings or schedules. E. The manufacturer shall provide a complete submittal package for approval prior to shipment. The package shall consist of the following: 1. Product cuts and specifications. 2. Bill of materials. 3. Warranty information. 4. Riser diagram indicating wiring requirements. 5. Point-to-point field wiring instructions. 6. Detailed layout of control stations. F. In addition to the submittals, a set of installation, operator and maintenance manuals shall be shipped with the equipment. PART 2 - PRODUCTS 2.1 LIGHTING CONTROL PANELS A. General 1. The lighting control system for the building shall consist of solid state lighting control panels with programmable switch inputs and fixture communications

5 Each panel shall provide a minimum of 32 switch inputs or a digital communications means to an equivalent number of switch inputs. 2. The control system shall provide total networking capability between control panels. Panels shall permit data sharing for global control. All inputs shall be transferable over the network to create any switching pattern. 3. The system shall permit customization of switch inputs, analog inputs and telephone override control. The user may determine how each control input functions. 4. Inputs may be customized to no OFF s, no ON s, no timer, ignored and/or setback. The system shall determine if the control input is available or unavailable for defined times, specific days and holidays. 5. The system shall support the creation of control panels via a touch screen interface. The lighting control system shall permit multiple touch screens. Touch screen control shall permit any authorized user to operate the lighting to any event required. The user may overlay or create any graphic desired through an off-the-shelf PC graphic/paint program, thus permitting the user to reconfigure the touch screen as the building requirements change. 6. The control system of each panel shall allow stand-alone control of each panel. Each panel shall have programmable inputs, time-of-day control and analog control (i.e., temperature, kw, photocell, etc.) Control system shall include: a. Flexible time-of day schedules b. Momentary or maintained inputs c. Network system inputs & outputs d. Analog inputs 1) Temperature control 2) Photocell control presetting footcandle level 3) Electrical power monitoring 7. Control panels shall include a Warn OFF (flash the lights) to inform occupants of an impending OFF command. The Warn OFF command shall allow 10 minutes for the occupants to override the lighting control system or exit the premises. Overrides shall be permitted for after hours use or cleaning. The overrides shall be hardwired inputs or voice-guided touch-tone telephone control. 8. The control panel shall log all change-of-state information. Time and date stamps shall be attached to all overrides, analog values and control device operations. 9. Programming of the system shall be through a local or remote networked terminal or may be accomplished off-line through a PC running the appropriate software. Central programming software shall be provided by the manufacturer and shall allow multiple users to access the lighting control system simultaneously

6 B. Contact Inputs 1. The control system shall allow dry contacts for override purposes. Momentary or maintained contacts shall be supported as three-wire (momentary) or twowire (SPST) inputs, respectively. Inputs shall be dry contacts (24 volts 12 ma internally supplied to the inputs). An input shall be capable of controlling any number of control devices for override control. C. Analog Inputs 1. Each control panel shall be capable of monitoring and controlling outputs from analog sensors. All control panels shall permit temperature, photocell and kwh monitoring. 2. Photocells a. The control system shall accept indoor, skylight and outdoor photosensing heads. Photo-sensing control shall permit the user to specify the actual footcandle level where desired control shall occur. An internal deadband timer shall exist to prevent the lights under photo-sensor control to adjust inadvertently as the sensor passes through the control threshold. 3. kwh Monitoring Hardware a. The control panel shall be capable of monitoring electrical power demand and consumption. Electrical power monitoring shall accept both current transformers and pulse metering. Kilowatt power monitoring through current and potential transformers shall provide true power monitoring. 4. Temperature Monitoring Hardware a. The control system shall accept temperature monitoring hardware for monitoring or building control. Temperature inputs shall consist of both monolithic integrated circuit temperature sensors and 4-20 ma temperature sensors. The control panel shall provide default temperature sensing ranges that are menu selectable or via Andover or Johnson Controls building automation system networked using BACnet. 5. Programmable 4-20 ma Sensor Loop a. The control system shall support 4-20 ma sensor loops. These sensors shall provide additional flexibility for building control. The system shall accept both sourcing (remote powered) and sinking (loop powered) 4-20 ma sensors. Control systems that do not provide analog sensor interfaces shall not be acceptable. Analog inputs shall be user selectable for 4-20 ma sinking or sourcing. D. Hardware Requirements 1. The lighting control system shall allow pilot lights on wall switches. The control panel shall provide the power to illuminate the pilot light and the light shall confirm control system operation. 2. The lighting control system shall allow control of remote mounted control devices. The control panel shall provide power and control to the remote control devices via communications cable per Standard Specification

7 E. Diagnostic Aides 1. Each control panel shall incorporate diagnostic aids for confirmation of proper operation or, in case of failure, to guide the user for troubleshooting of the system. The control panel shall employ light emitting diodes (LED s) that visibly indicate: a. Power b. Network communications c. System operational d. RS-232 transmit and receive e. Power on f. Memory confirmation g. Broadcast reception h. On/off status of each control device i. Memory cleared F. Status Indication of Control devices 1. The system shall provide visible status indication of all control devices through the window of each panel. The visual indication shall include ON, OFF and control device number. G. Service Overrides 1. The control panel shall include a three position service override for each control device and a master control switch for the entire panel. The service overrides shall be accessible from behind a locked door. 2. The individual control device service override shall be a three position switch with ON, OFF and AUTO positions. The system shall remember the last command to the control device. Upon returning the override switch to the AUTO position, the control device shall return to the most recent command state, even if the last command occurred during the service override condition. The control device s red (OFF) LED or green (ON) LED shall illuminate to indicate the status of the control device whether the switch is in the ON, OFF or AUTO position. 3. The master service override shall be a single, three position switch with ALL ON, ALL OFF and AUTO positions. This switch shall override and supercede all commands from the logic board when the switch is in the ALL ON (green LED) or ALL OFF (red LED) position. The LED s shall be in proximity to the switch. The master switch shall be functional with the logic board either removed or disabled. 4. The system shall remember the last command to each individual control device. Upon restoration of the master switch to the AUTO position, all control devices shall return to the most recent command state even if the last command occurred during the master override condition

8 H. Battery Back-Up 1. The system shall utilize a memory back-up device that is system integrated and maintenance free. Both the system clock and data in RAM shall be protected against power interruptions lasting as long as 7 days. Power restoration for as little as 30 minutes shall fully restore the battery to its full 7 day protection capability. I. Printer Port 1. The control panel shall include a USB printer port for local printing directly from the control panel. Each panel shall provide printouts of the programmed information within the control panel. 2. The central control system shall have means to print out all settings for archival purposes. J. Network 1. The control system shall be capable of panel-to-panel communications over a high speed, hard wired data network. The network shall consist of wiring as required by the manufacturer. K. Power Supply 1. The control panel shall incorporate the use of a multi-tapped transformer for its main power supply. The transformer shall allow 120 volt or 277 volt control power. 2.2 CONTROL DEVICES A. Control devices shall be rated 20 amperes, 277 volt. Control devices shall be magnetically held and shall include a 10 year warrantee. B. Control devices shall open upon loss of normal power to avoid creating a demand peak upon restoration of power. When normal power is restored, the system shall reset and the control devices shall return to the position they were in, sequentially, prior to the outage within 10 seconds. 2.3 EXTERNAL COMMUNICATIONS A. The control panel shall include a communications port with a means for external communications. The means shall utilize Hayes compatibility standard and enable modem access as defined by the Bell 212A and CCITT V.22 protocol standards or utilize means via a standard network TCP/IP connection. B. The system shall permit full screen video display terminal (VDT), local area network (LAN), on-site and off-site communications. The system shall be a multi-tasking system which shall permit more than one communications channel in operation at a time communicating on the network

9 2.4 PC BASED SOFTWARE A. PC based software shall enable a computer to program the lighting control panels connected to the network. The software shall be Microsoft Windows based. The software shall permit the authorized user to modify the control panel programming or configuration in either an on- or off-line mode. The software package shall store all programmed data and archive for future use. Note: The system shall be programmable directly from the control panel. The system shall not require the use of a computer for programming. B. The following features shall be available in the software: 1. Trend logging with set points (analog data) 2. Real time analog monitoring 3. kwh monitoring 4. Graphing of logged data 5. Exportation of logged data for data manipulation 6. Telecommunications 7. Password access (multiple levels) 8. Automatic upload of data from panels 9. Network status indication 10. Supervisor graphics interface 11. Touch screen programming 12. Tenant billing 13. Archive programs and all log information 14. Data base comparison checking 15. Uploading and downloading of programs C. Tenant Billing Software 1. Provide tenant billing software integral to the PC based software. Billing information shall be stored in the panels for retrieval by the system authorized user. Tenant hours of use may be uploaded from the panel and compiled into the billing program for calculation. Logged information may be printed on monthly billing statements. Time and date information shall be available for each billing occurrence. 2.5 TELEPHONE OVERRIDES A. The control panel shall provide software and hardware for a telephone override device. The telephone override device shall allow modem communications and touch-tone overrides from any touch-tone telephone. B. Touch-tone interface shall permit the control panel to place override information onto the network, and the pre-assigned control points shall be commanded

10 accordingly ON or OFF. All user interface shall be through the 12 touch-tone keys on a standard telephone. All entries into the override system shall be prompted from a digitized voice. C. The telephone override device shall provide individual user control passwords to define a preset group designation (number of control devices) and the duration of the telephone override. 2.6 ENCLOSURES A. Each control panel shall be enclosed in a lockable NEMA 1 enclosure. The enclosure shall be manufactured of minimum 1/16 inch steel and shall include prepunched knockouts. 2.7 TOUCH SCREENS A. The lighting control system shall include touch screens for user and/or event control. The system shall permit multiple touch screen control. The user may reconfigure, overlay or create any graphic representation for the touch screens through a standard graphics program. Building graphics superimposed onto the touch screen permit users intuitive use of the control system. The user shall have full control of the system from the touch screen and may lock-out unauthorized users from access. PART 3 - EXECUTION 3.1 COOPERATION AND WORK PROGRESS A. The Electrical work shall be carried on under the usual construction conditions, in conjunction with all other work at the site. The Contractor shall cooperate with the Architect, Construction Manager, all other trade Contractors and equipment suppliers working at the site. The Contractor shall coordinate the work and proceed in a manner so as not to delay the progress of the project. B. The Contractor shall coordinate his work with the progress of the building and other Trades so that he will complete his work as soon as conditions permit and such that interruptions of the building functions will be at a minimum. Any overtime hours worked or additional costs incurred due to lack of or improper coordination with other Trades or the Owner by the Contractor shall be assumed by him without any additional cost to the Owner. C. The Contractor shall furnish information on all equipment that is furnished under this Section but installed under another Section to the installing Subcontractor as specified herein. D. The Contractor shall provide all materials, equipment and workmanship to provide for adequate protection of all electrical equipment during the course of construction of the project. This shall also include protection from moisture and all foreign matter. The Contractor shall also be responsible for damage which he causes to the work of other Trades, and he shall remedy such injury at his own expense

11 E. Waste materials shall be removed promptly from the premises. All material and equipment stored on the premises shall be kept in a neat and orderly fashion. Material or equipment shall not be stored where exposed to the weather. The Contractor shall be responsible for the security, safekeeping and damages, including acts of vandalism, of all material and equipment stored at the job site. F. The Contractor shall be responsible for unloading all electrical equipment and materials delivered to the site. This shall also include all large and heavy items or equipment which require hoisting. Consult with the General Contractor for hoisting/crane requirements. During construction of the building, the Contractor shall provide additional protection against moisture, dust accumulation and physical damage of the main service and distribution equipment. This shall include furnishing and installing temporary heaters within these units, as approved, to evaporate excessive moisture and ventilate it from the room, as may be required. G. It shall be the responsibility of the Contractor to coordinate the delivery of the electrical equipment to the project prior to the time installation of equipment will be required; but he shall also make sure such equipment is not delivered too far in advance of such required installation, to ensure that possible damage and deterioration of such equipment will not occur. Such equipment stored for an excessively long period of time (as determined in the opinion of the Architect) on the project site prior to installation may be subject to rejection by the Architect. H. The Contractor shall erect and maintain, at all times, necessary safeguards for the protection of life and property of the Owner, Workmen, Staff and the Public. I. Prior to installation, the Contractor has the responsibility to coordinate the exact mounting arrangement and location of electrical equipment to allow proper space requirements as indicated in the NEC. Particular attention shall be given in the field to group installations. If it is questionable that sufficient space, conflict with the work of other Subcontractors, architectural or structural obstructions will result in an arrangement which will prevent proper access, operation or maintenance of the indicated equipment, the Contractor shall immediately notify the Contractor and not proceed with this part of the Contract work until definite instructions have been given to him by the Architect. 3.2 INSTALLATION A. The Contractor shall furnish all equipment, labor, system setup, and other services necessary for the proper installation of the devices as indicated on the drawings and specified herein. System setup shall include defining each dimmer's load type, assigning each load to a zone, and setting the control functions. B. Unless specifically noted or indicated otherwise, all equipment and material specified in Part 2 of this specification or indicated on the drawings shall be installed under this Contract whether or not specifically itemized herein. This Section covers particular installation methods and requirements peculiar to certain items and classes or material and equipment. C. The Contractor shall obtain detailed information from manufacturers of equipment provided under Part 2 of this specification as to proper methods of installation

12 D. The Contractor shall obtain final roughing dimensions and other information as needed for complete installation of items furnished under other Sections or furnished by the Owner. E. The Contractor shall keep fully informed of size, shape and position of openings required for material and equipment provided under this and other Sections. Ensure that openings required for work of this Section are coordinated with work of other Sections. Provide cutting and patching as necessary. F. All miscellaneous hardware and support accessories, including support rods, nuts, bolts, screws and other such items, shall be of a galvanized or cadmium plated finish or of another approved rust-inhibiting coating. G. Throughout this Section where reference is made to steel channel supports, it shall be understood to mean that the minimum size shall be 1 5/8" mild strip steel with minimum wall thickness of 0.105", similar to Unistrut P1000 or equal products manufactured by Kindorf or Husky Products Co. Where reference to channel supports is made under "Lighting Fixtures" paragraph of this Section, the maximum length of span shall be 10'-0". If longer spans are required, the size and wall thickness of the steel channel support shall be as specifically approved by the Engineer. 3.3 MATERIALS AND WORKMANSHIP A. All materials and equipment shall be new and unused and shall meet requirements of the latest Standards of NEMA, UL, IPCEA, ANSI and IEEE. Equipment shall have components required or recommended by OSHA, applicable NFPA documents and shall be UL listed and labeled. B. Despite references in the specifications or on the drawings to materials or pieces of equipment by name, make or catalog number, such references shall be interpreted as establishing standards of quality for materials and performance. C. Finish of materials, components and equipment shall not be less than Industry good practice. When material or equipment is visible or subject to corrosive or atmospheric conditions, the finish shall be as approved by the Architect. D. Provide proper access to material or equipment that requires inspection, replacement, repair or service. If proper access cannot be provided, confer with the Architect as to the best method of approach to minimize effects of reduced access. E. All work shall be installed in a neat and workmanlike manner and shall be done in accordance with all Local and State Codes. F. The Owner will not be responsible for material, equipment or the installation of same before testing and acceptance. 3.4 FIELD SUPPORT A. Manufacturer shall be capable of providing on-site service support within 24 hours anywhere in the continental U.S.A., and within five business days anywhere in the world, except where special visas are required

13 3.5 SYSTEM COMMISSIONING A. Reference Specification Section B. The system manufacturer shall provide on-site, factory technicians to thoroughly inspect the lighting control system installation and verify proper operation. The commissioning shall include three (3) separate visits to the project as defined below: 1. First Visit: Pre-Wire Inspection a. Review all low voltage wiring requirements 1) Daisy chain 2) Maximum run lengths 3) Control and dimmer/switching panel links 4) Cable requirements b. Review separation of power and low voltage/data wiring c. Review wire labeling d. Review information required on load schedules e. Review lighting control panel locations and installation f. Review control locations and addressing g. Review analog phone lines requirements and computer jack locations h. Review load circuit wiring i. Review connections to equipment by others j. Develop project schedule, including: 1) Contractor completion dates 2) Building opening dates 3) End user training 4) Contact names and numbers 2. Second Visit: Start-Up of System and Installation of System Software/data a. Verify proper connection of 1) Power feeds 2) Load circuits b. Verify proper connection of all controls c. Energize the main panel and download system data program d. Verify proper connection of panel links (low voltage/data) and address panels e. Download system panel data to lighting control panels f. Verify system operation control by control, circuit by circuit g. Verify proper operation of interfacing equipment

14 h. Verify operation of PC and installed programs i. Verify operation of PC modem and test dial up access if phone line provided j. Program and provide fine-tune adjustments of the following for each individual area with the Owner, Architect and Lighting Consultant present. 1) All preset scene values for each area. 2) Time clock events and functions. 3) Programming sequences k. Obtain sign off on systems function 3. Third Visit: Operator/End-User Training a. Upgrade systems software to the latest revision level, if necessary b. Train the end users on system operation and software (Set-Up and Operate programs) 1) Database file management 2) How to set scene values 3) How to set timeclock events 4) How to set sequences, if applicable c. System maintenance and trouble shooting 1) Job telephone numbers 2) Who to call 3) Diagnostics available 4) Modem 5) Telephone support 6) Service visit d. Persons to be available for this visit should include: 1) Manufacturer s Service Engineer 2) Electrical maintenance staff 3) System operators C. The manufacturer shall carry in his bids sufficient time to accomplish the above requirements to the satisfaction of the Owner, Architect, Lighting Consultant and Engineer. END OF SECTION

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

DIVISION 26 ELECTRICAL SECTION LIGHTING CONTROL SYSTEM

DIVISION 26 ELECTRICAL SECTION LIGHTING CONTROL SYSTEM DIVISION 26 ELECTRICAL SECTION 26 09 26 PART 1 GENERAL 1.01 DESCRIPTION A. The intent of this set of specifications is to provide a complete, functional, intelligent, lowvoltage lighting control system

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

C. The system shall be capable of turning luminaires on/off (where supported by the luminaire) as well as full range dimming.

C. The system shall be capable of turning luminaires on/off (where supported by the luminaire) as well as full range dimming. SECTION 260943 SPECIFICATIONS - Wireless Network Lighting Controls. PART 1 - GENERAL 1.1 RELATED DOCUMENTS 1.2 SUMMARY AND KEY SYSTEM DIFFERENTIATORS A. The lighting control system specified herein shall

More information

SECTION LIGHTING CONTROLS

SECTION LIGHTING CONTROLS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 09 23 LIGHTING CONTROLS SPEC WRITER NOTE: 1. Delete between //----// if not applicable to project. Also, delete any other item or paragraph not applicable to

More information

SECTION 26 NX DISTRIBUTED INTELLIGENCE LIGHTING CONTROL SYSTEM HUBBELL CONTROL SOLUTIONS

SECTION 26 NX DISTRIBUTED INTELLIGENCE LIGHTING CONTROL SYSTEM HUBBELL CONTROL SOLUTIONS SECTION 26 NX DISTRIBUTED INTELLIGENCE LIGHTING CONTROL SYSTEM HUBBELL CONTROL SOLUTIONS PART - 1 GENERAL 1 SYSTEM DESCRIPTION A. The distributed lighting control system as specified herein shall be comprised

More information

GE LightSweep Lighting Control System Guideform Specification

GE LightSweep Lighting Control System Guideform Specification GE Lighting Control GE LightSweep Lighting Control System Guideform Specification If you have any questions at all regarding this specification, please contact your local GE Lighting Control representative,

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Minimum lighting control (base scope of work) shall include all corridors. The lighting in all the corridors shall be turned on (if not already on) if

More information

CRESTRON: GREEN LIGHT NETWORK LIGHTING CONTROLS 1

CRESTRON: GREEN LIGHT NETWORK LIGHTING CONTROLS 1 GREEN LIGHT ARCHITECTURAL DIMMING CONTROLS (GLPD) Crestron Green Light and Green Light Express Network Dimming Control Systems are web accessible, network connected dimming control systems that receive

More information

ONYX FirstVision Specification Interactive Firefighters Display

ONYX FirstVision Specification Interactive Firefighters Display ONYX FirstVision Specification Interactive Firefighters Display NOTIFIER is a registered trademark, and ONYX FirstVision, NOTI FIRE NET, and VeriFire are trademarks of Honeywell International Inc. Microsoft

More information

Spectron LSN (Life Safety Network) Suggested Specifications

Spectron LSN (Life Safety Network) Suggested Specifications 1. General 1.1 Scope A Dual-Lite Spectron LSN (Life Safety Network) Series Inverter System shall be furnished to provide a reliable source of power, and shall operate during a utility line deficiency without

More information

PROJ. NO SECTION PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS

PROJ. NO SECTION PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS SECTION 26 92 50 PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SECTION DIGITAL-NETWORKING LIGHTING CONTROLS ENLIGHTED LIGHT MANAGEMENT SYSTEM

SECTION DIGITAL-NETWORKING LIGHTING CONTROLS ENLIGHTED LIGHT MANAGEMENT SYSTEM SECTION 260943.13 DIGITAL-NETWORKING LIGHTING CONTROLS ENLIGHTED LIGHT MANAGEMENT SYSTEM PART 1 - GENERAL 1.1 SUMMARY LED Lighting Upgrade 26 00 00 1 Digital Network Lighting Controls A. The following

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC

More information

CARD ACCESS CONTROL SYSTEM

CARD ACCESS CONTROL SYSTEM SECTION 13851 CARD ACCESS CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested, integrated proximity access control system, to operate on a proximity principle where

More information

SECTION SECURITY TESTING AND COMMISSIONING

SECTION SECURITY TESTING AND COMMISSIONING SECTION 280800 - SECURITY TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 WORK INCLUDES A. General Description: This specification section covers the provision of preliminary testing, acceptance testing,

More information

East Central College

East Central College SECTION 260923 LIGHTING CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

A. This Section includes the following lighting control devices:

A. This Section includes the following lighting control devices: Attachment G LIGHTING CONTROL SPECIFICATIONS (Download Document separately) LIGHTING CONTROL SPECIFICATIONS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including

More information

1. Division 26 Section Electrical General Requirements. 2. Division 26 Section "Wiring Devices" for wall-box dimmers and manual light switches.

1. Division 26 Section Electrical General Requirements. 2. Division 26 Section Wiring Devices for wall-box dimmers and manual light switches. PART 1 - GENERAL... 1 1.1 RELATED DOCUMENTS... 1 1.2 SUMMARY... 1 1.3 REFERENCES... 2 1.4 DEFINITIONS... 2 1.5 SUBMITTALS... 2 1.6 QUALITY ASSURANCE... 3 1.7 COORDINATION... 3 1.8 DELIVERY, STORAGE, AND

More information

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials.

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials. B B11.0 DIVISION 08 - OPENINGS SECTION 08 17 00 INTEGRATED DOOR OPENING ASSEMBLIES Specifier Note: Coordinate and edit articles and paragraphs below to suit project requirements. Add section numbers and

More information

Product Specifications Dialog Room Controller* (*patent pending)

Product Specifications Dialog Room Controller* (*patent pending) 1 Product Specifications Dialog Room Controller* (*patent pending) 1. GENERAL 1.1. OVERVIEW 1.1.1. Provide a complete stand-alone, decentralized, low voltage, digital lighting control system for classrooms,

More information

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2 Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...

More information

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply

More information

Specification for On-Line UPS Battery Monitoring and Data Management System

Specification for On-Line UPS Battery Monitoring and Data Management System 1 Scope This specification defines the minimum requirements for a predictive on-line Battery Monitoring BMDMS with test, analysis, and remote monitoring control capabilities. Unless noted otherwise, the

More information

WebStat Temperature Control System WITH WEB-BASED BUILDING MANAGEMENT

WebStat Temperature Control System WITH WEB-BASED BUILDING MANAGEMENT WebStat Temperature Control System WITH WEB-BASED BUILDING MANAGEMENT ENGINEERING GUIDE SPEC 1. GENERAL 1.1 SUMMARY A. Furnish all labor, materials, equipment, and service necessary for a complete and

More information

SECTION LOW VOLTAGE LIGHTING CONTROLS

SECTION LOW VOLTAGE LIGHTING CONTROLS SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY SECTION 22 11 23.13 DOMESTIC WATER PRESSURE BOOSTING PART 1 - GENERAL 1.1 SUMMARY A. Where utility water pressure cannot adequately meet the pressure requirements of the domestic water systems and where

More information

SECTION ELECTRICAL SYSTEMS COMMISSIONING

SECTION ELECTRICAL SYSTEMS COMMISSIONING SECTION 16990 PART 1 - GENERAL 1.01 SECTION INCLUDES A. Section Includes: 1. General requirements for Commissioning (Cx) of lighting systems components, lighting controls and HVAC systems line voltage

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION NURSE CALL SYSTEM

SECTION NURSE CALL SYSTEM NURSE CALL SMARTCARE NURSE CALL SOLUTION Architectural Specifications Part 1 General SECTION 275223 - NURSE CALL SYSTEM 1.0 Summary 1.1 This section includes nurse call system and requirements for system

More information

DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC

DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC PART 1 GENERAL SECTION 23 0923 DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC 1.01 RELATED WORK UNDER OTHER SECTIONS: A. In addition to the general building construction, work directly related to the automatic

More information

IN2 Lighting Control Devices

IN2 Lighting Control Devices Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Lighting Control Devices Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals

More information

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This

More information

A. This Section includes the following lighting control devices:

A. This Section includes the following lighting control devices: SECTION 26 09 23 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

The system should also be capable of recording events automatically on any compatible DVR and should be able to retrieve recordings based on events.

The system should also be capable of recording events automatically on any compatible DVR and should be able to retrieve recordings based on events. 0BThe System The Security Management System should be capable of Controlling and Monitoring Access through the doors, Monitor and control Inputs and Outputs, include an Integrated Video Badging, Integrate

More information

Guide Specification Model CTG Automatic Transfer Switch

Guide Specification Model CTG Automatic Transfer Switch Guide Specification Model CTG Automatic Transfer Switch PART 1 GENERAL 1.1 Scope A. It is the intent of this specification to secure a transfer switch that has been prototype tested, factory built, production

More information

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete

More information

Control/Communicator

Control/Communicator Architectural & Engineering Specifications Control/Communicator 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality

More information

SECTION GENERATOR PARALLELING CONTROLS

SECTION GENERATOR PARALLELING CONTROLS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 23 13 GENERATOR PARALLELING CONTROLS SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

Alarm Lock A Division of the Napco Security Group 333 Bayview Avenue Amityville, New York Phone (631) Fax (631)

Alarm Lock A Division of the Napco Security Group 333 Bayview Avenue Amityville, New York Phone (631) Fax (631) Alarm Lock ArchiTech Series Lockset Specification Alarm Lock A Division of the Napco Security Group 333 Bayview Avenue Amityville, New York 11701 Phone (631) 842-9400 Fax (631) 789-3383 http://www.alarmlock.com

More information

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings 1 T Consultant: NOTES, SYMBOLS & ABBREVIATIONS - MECHANICAL Number Description M001 Vestibule 117 LAN/IT Coffee 115 116 Mail Room 118 114 113 112 Scanning 119 Open Office 101 FIRST FLOOR PLAN - MECHANICAL

More information

_5120_School_Intercom_Rack_Spec.doc 09/21/04

_5120_School_Intercom_Rack_Spec.doc 09/21/04 ****************************************************************************************** 16720-3 Simplex TrueCom 5120 Inter Communication System Advanced 360 Station, Rack Mounted, Intercom / Paging

More information

ARCHITECTURAL SPECIFICATIONS

ARCHITECTURAL SPECIFICATIONS 1 B9.1 In Ground Page 1 of 6, Aug 12 DIVISION 08 - OPENINGS SECTION 08 71 13 POWER DOOR OPERATORS Specifier Note: Coordinate and edit articles and paragraphs below to suit project requirements. Add section

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

ACT2-CS Convenience Store Controller

ACT2-CS Convenience Store Controller Refrigeration Systems Technical Manual 804 Product Bulletins Section Product Bulletin Issue Date 0899 ACT2-CS Convenience Store Controller The ACT2-CS Convenience Store Controller is a fully programmable,

More information

SECTION INTRUSION DETECTION

SECTION INTRUSION DETECTION (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) SECTION 28 16 00 INTRUSION

More information

DETEX ARCHITECTURAL SPECIFICATIONS, June 2012 AO19 SERIES HEAVY DUTY LOW-ENERGY ELECTRIC SWING DOOR OPERATOR

DETEX ARCHITECTURAL SPECIFICATIONS, June 2012 AO19 SERIES HEAVY DUTY LOW-ENERGY ELECTRIC SWING DOOR OPERATOR DETEX ARCHITECTURAL SPECIFICATIONS, June 2012 AO19 SERIES HEAVY DUTY LOW-ENERGY ELECTRIC SWING DOOR OPERATOR SECTION 08 71 13 LOW ENERGY AUTOMATIC OPERATORS Specifier Note: Coordinate and edit articles

More information

LIGHTING CONTROL DEVICES

LIGHTING CONTROL DEVICES SECTION - PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this

More information

SPECIFICATIONS: FIREGUARD CROSS CORRIDOR CC

SPECIFICATIONS: FIREGUARD CROSS CORRIDOR CC SPECIFICATIONS: FIREGUARD CROSS CORRIDOR CC SECTION 08 35 13.23 ACCORDION FOLDING FIRE DOORS PART 1 GENERAL 1.01 SUMMARY OF WORK A. Division 0 and 1, as indexed, apply to this section. B. Furnish and install

More information

SECTION LIGHTING CONTROL DEVICES

SECTION LIGHTING CONTROL DEVICES SECTION 16145 LIGHTING CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL SECTION 21 13 16 DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

15900 HVAC INSTRUMENTATION AND CONTROLS

15900 HVAC INSTRUMENTATION AND CONTROLS 15900 HVAC INSTRUMENTATION AND CONTROLS PART 1 GENERAL - Andover Controls BAS system is the standard for the University, and may be specified as a proprietary item. 1.0 RELATED DOCUMENTS A. Drawings and

More information

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL MADE IN THE U.S.A. U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION SERIAL NUMBER The Cookson Company FIREFLY II PLUS Time Delay Release

More information

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

THE SS90 SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL S S S S S S S S 90 OLID TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT * PATENT PENDING LISTED U 99Y9 RESET L RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE

More information

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE PAGE 283100-1 SECTION 283100 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

B. After installation, the Owner shall be able to perform hardware configuration changes as desired without the services of the Integrator.

B. After installation, the Owner shall be able to perform hardware configuration changes as desired without the services of the Integrator. SECTION 281300 - ACCESS CONTROL SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Minimum standards for Access Control Systems. B. Related Requirements: 1. Section 087100 Door Hardware. 1.2 REFERENCES

More information

LightSweep. Lighting Control System

LightSweep. Lighting Control System LightSweep Lighting Control System Incredible Control GE LightSweep is a comprehensive indoor lighting control system designed to save money while improving the efficiency, comfort, safety and security

More information

DONALD H. BERG, ARCHITECT

DONALD H. BERG, ARCHITECT DONALD H. BERG, ARCHITECT DVA PROJECT 632-CSI-402 PET/CT ROOM #A0-10 RENOVATION BASEMENT LEVEL, BUILDING 200 ARCHITECT S PROJECT No. 0917-02 ADDENDUM NO. 1 JUNE 25, 2018 Page 1 of 1 ARCHITECTURAL 1. Specifications:

More information

MODEL B2 INSTALLATION MANUAL

MODEL B2 INSTALLATION MANUAL RELEASE DEVICES GENERAL DESCRIPTION MODEL B2 INSTALLATION MANUAL S/N: The B2 Series Time Delay Release Devices are UL Listed, Canadian Listed, and CSFM Listed for use on rolling doors, single-slide and

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

DTW Master Specification Section EMCS: Start Up, Verification and Commissioning

DTW Master Specification Section EMCS: Start Up, Verification and Commissioning Page 1 of 6 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Related Sections..1 The contractor is to ensure that all related work is co ordinated among all specification sections, as well as between Division 11,

More information

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION 1. GENERAL SPECIFICATION 1.1 The contractor shall provide an Intelligent AlarmLine Linear Heat Detection System to perform the following functionality: A. Fire Alarm, Supervisory and Trouble-Event Initiation

More information

SECTION BUILDING AUTOMATION SYSTEM

SECTION BUILDING AUTOMATION SYSTEM SECTION 25 10 00 BUILDING AUTOMATION SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Work hereunder includes a complete and operational, fully-tested, distributed logic, direct digital control system for control

More information

LIGHTING CONTROLS

LIGHTING CONTROLS 260923 LIGHTING CONTROLS PART 1: GENERAL 1.01 SUMMARY COMMENTS A. CU has developed this lighting control guideline to direct design professionals toward standard solutions that meet the University s performance

More information

SECTION (16460) - LOW-VOLTAGE TRANSFORMERS

SECTION (16460) - LOW-VOLTAGE TRANSFORMERS PART 1 GENERAL 1.01 SUMMARY SECTION 26 22 00 (16460) - LOW-VOLTAGE TRANSFORMERS A. Section Includes: 1. Dry-Type Distribution And Specialty Transformers Rated 1000 V And Less. a. General-Purpose Distribution

More information

ARCHITECTS & ENGINEERS SPECIFICATIONS ACS INTERCOM BUILDING ENTRY SYSTEM VERSION 6.0 AUGUST 1999

ARCHITECTS & ENGINEERS SPECIFICATIONS ACS INTERCOM BUILDING ENTRY SYSTEM VERSION 6.0 AUGUST 1999 ARCHITECTS & ENGINEERS SPECIFICATIONS ACS INTERCOM BUILDING ENTRY SYSTEM VERSION 6.0 AUGUST 1999 HOUSING DEVICES, INC. 407 R. MYSTIC AVE. MEDFORD, MA 02155 800-392-5200 www.housingdevices.com Housing Devices,

More information

WESTIN HOTEL. Smoke Control System. Testing Procedures Manual. October 10, Copyright Impact Engineering, Inc All Rights Reserved

WESTIN HOTEL. Smoke Control System. Testing Procedures Manual. October 10, Copyright Impact Engineering, Inc All Rights Reserved IMPACT ENGINEERING, INC. WESTIN HOTEL Smoke Control System Testing Procedures Manual October 10, 2016 Copyright Impact Engineering, Inc. 2016 All Rights Reserved This manual is protected by the U.S. Copyright

More information

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,

More information

UNC100 Integra Manual

UNC100 Integra Manual UNC100 Integra Manual New Generation Building Security July 30, 2014 V1.2 Copyright Notice Copyright 1995-2014 by All rights reserved Worldwide. Printed in Canada. This publication has been provided pursuant

More information

AIRPORT OFFICE BUILDING. Smoke Control System. Testing Procedures Manual. September 10, 2016

AIRPORT OFFICE BUILDING. Smoke Control System. Testing Procedures Manual. September 10, 2016 IMPACT ENGINEERING, INC. AIRPORT OFFICE BUILDING Smoke Control System Testing Procedures Manual September 10, 2016 All Rights Reserved This manual is protected by the U.S. Copyright Law (Title 17 United

More information

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 5/25/16 rev 6 elite Model ELN General Specification 550 W to 1.5 KW elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 1.0 General General Specification This specification

More information

The EN54 Part 2 & 4 Fire System

The EN54 Part 2 & 4 Fire System Scope of work: To design, supply, install and commission an Analogue Addressable Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54

More information

Lighting Control Relay Panels Lighting Control Solutions

Lighting Control Relay Panels Lighting Control Solutions Lighting Control Relay Panels Lighting Control Solutions Make the most of your energy SM Lighting control relay panels from Schneider Electric will put you in control of your lighting, your comfort and

More information

5120_School_Intercom_Rack_Spec.doc 10/10/07

5120_School_Intercom_Rack_Spec.doc 10/10/07 ****************************************************************************************** 16720-3 Simplex TrueCom 5120 Inter Communication System Advanced 360 Station, Rack Mounted, Intercom / Paging

More information

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters.

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters. SECTION 15622 DIRECT GAS-FIRED BURNER & MANIFOLD SYSTEM PART 1: GENERAL 1.1 Section includes: A. Direct gas-fired heater modules B. Controls C. Equipment schedule 1.2 Related Sections A. Section 01655:

More information

1.3 REFERENCE STANDARDS

1.3 REFERENCE STANDARDS SECTION 28 4600 FIRE DETECTION AND ALARM PART 1 -GENERAL 1.1 SECTION INCLUDES A. Fire alarm system design and installation, including all components, wiring, and conduit. B. Circuits from protected premises

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 21 0800 - COMMISSIONING OF FIRE SUPPRESSION SYSTEMS GENERAL 1.1 SUMMARY General 1. Work under this contract shall meet the requirements of Division 01, General Requirements, Conditions of Contract,

More information

opti-visor ultra-efficient chiller plant automation Typical specification

opti-visor ultra-efficient chiller plant automation Typical specification opti-visor ultra-efficient chiller plant automation Typical File No: 90.893 Date: february 9, 2015 Supersedes: 90.893 Date: april 20, 2012 contents 1.0 Chilled water plant 4 1.1 General system requirements

More information

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Revision 6/01.17 Contents 1. Introduction... 6 2. Terminology... 6 3. Function... 8 4. Technical data... 8 4.1. Physical configuration...

More information

Use this product according to this instruction manual. Please keep this instruction manual for future reference.

Use this product according to this instruction manual. Please keep this instruction manual for future reference. 273 Branchport Avenue Long Branch, NJ 07740 (732) 222-6880 Thank you for using our products. INSTALLATION INSTRUCTIONS REMOTE MICROPHONE (SINGLE CIRCUIT) Use this product according to this instruction

More information

Instruction manual MTL process alarm equipment. October 2016 CSM 725B rev 2 MTL RTK 725B. Configuration Software Manual

Instruction manual MTL process alarm equipment. October 2016 CSM 725B rev 2 MTL RTK 725B. Configuration Software Manual Instruction manual MTL process alarm equipment October 2016 CSM 725B rev 2 MTL RTK 725B Configuration Software Manual SECTION 1 - INTRODUCTION... 5 Basic Requirements... 5 SECTION 2 - SOFTWARE INSTALLATION...

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

Integrated Automation Instrumentation & Terminal Devices

Integrated Automation Instrumentation & Terminal Devices Sections Included In This Standard: 1.1 Building Systems Control 1.2 Building Aumotation Systems (BAS) 1.1 BUILDING SYSTEMS CONTROL A. HVAC CONTROLS: 1. General: Temperature control zones shall not combine

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 16721 FIRE ALARM SYSTEMS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work

More information

The Owner will provide the QEI inspection and certification services.

The Owner will provide the QEI inspection and certification services. General The Owner will provide the QEI inspection and certification services. Elevators Electric operated traction elevators are preferred; holeless hydraulic oil operation may be considered where use

More information

Across-the-Line SERIES MP300 Combined Manual and Automatic

Across-the-Line SERIES MP300 Combined Manual and Automatic Across-the-Line SERIES MP300 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for Centrifugal Fire Pumps

More information

Mark 25 Ultrapure Water Conductivity Analyzer

Mark 25 Ultrapure Water Conductivity Analyzer Martek Instruments, Inc. Mark 25 Ultrapure Water Conductivity Analyzer Instruction Manual WARRANTY POLICY Unless otherwise stated, MARTEK INSTRUMENTS, INC. warrants this equipment to be free from defects

More information

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features.

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features. CONsOlIDATOR 4 & 8 MulTI- C h ANNEl CONTROllERs ConsoliDator 4 Model PD940 ConsoliDator 4 Features Four 4-20 Four 4-20 Outputs ConsoliDator 8 Features Eight 4-20 Two 4-20 Outputs Common Features Four Pulse

More information

Emery County Senior Center Green River 06/07

Emery County Senior Center Green River 06/07 SECTION 260923 - LIGHTING CONTROL DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G E SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF DATE: 11/13/06 2/1/07 1 Copyright, E, Inc. E 1. ENERAL...4 1.1 Scope Of Work... 4 1.2 Codes and Standards... 4 2. PRODUCTS...5

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018 SECTION 26 2913 - ENCLOSED CONTROLLERS GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard

More information

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses PART 1 - GENERAL 1.1 SCOPE A. Through Class III Commodity Classification, up to 12.2m of single, double or multiple row rack storage, up to 14.6m building height (VanQuish Fire Sprinkler System). Cartoned

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency

More information

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions: SECTION 21 13 13 WET-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase General Specification 550 VA/Watts 1300 VA/Watts 1.0 GENERAL This specification defines the electrical and mechanical characteristics

More information

SENTRY PRODUCTS, INC. 01/98 SCAN - STAND-ALONE - Sample Specification

SENTRY PRODUCTS, INC. 01/98 SCAN - STAND-ALONE - Sample Specification This sample specification is for a duress only stand-alone SCAN system using SR series receivers with zone-within-a-zone and graphic display. SECTION 17 DURESS SYSTEM PART 1.00 - GENERAL 1.01 DESCRIPTION

More information

1 For All Programmable Digital Thermostat

1 For All Programmable Digital Thermostat OWNER'S MANUAL P/N P374-2300FM 1 For All Programmable Digital Thermostat Am OFF OVERRIDE Meets California Title 24 unts flush to the wall 7 Day Programmable 3 Occupied, 1 Unoccupied Auto-Changeover Large,

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

Product Specifications

Product Specifications Southwest Microwave, Inc. 9055 S. McKemy Street Tempe, Arizona 85284 USA (480) 783-0201 Fax (480) 783-0401 Product Specifications Procurement Specifications INTREPID MicroPoint Cable System Perimeter Detection

More information