BUSHFIRE THREAT ASSESSMENT REPORT. Special Fire Protection Purpose Development. North Byron Beach Resort. Proposed Central Facilities

Size: px
Start display at page:

Download "BUSHFIRE THREAT ASSESSMENT REPORT. Special Fire Protection Purpose Development. North Byron Beach Resort. Proposed Central Facilities"

Transcription

1 appendix i

2 BUSHFIRE THREAT ASSESSMENT REPORT Special Fire Protection Purpose Development North Byron Beach Resort Proposed Central Facilities Lots 1, 9, 10 & 11 DP Bayshore Drive, Byron Bay 4 November 2013 (amended)

3 Prepared by: BCA Check Pty Ltd trading as Bushfire Certifiers 4/57 Ballina Street Lennox Head NSW 2478 Australia (PO Box 375 LENNOX HEAD NSW 2478) ABN T: F: E: Peter Thornton Principal BPAD-A Certified Practitioner No MFireSafeEng Building Surveyor MAIBS DOCUMENT CONTROL Revision No. Date Description Prepared Checked Authorised A Draft Peter Thornton SJT Peter Thornton B Draft Peter Thornton SJT Peter Thornton Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 2

4 TABLE OF CONTENTS 1.0 Executive Summary Introduction General 2.2 Significant Environmental Features 2.3 Report Details 3.0 Proposed Development Bushfire Threat Assessment Asset Protection Zones and Construction Standards Water and Utility Services Water Services 6.2 Gas Services 6.3 Electricity Services 7.0 Access Landscaping Emergency and Evacuation Planning Conclusion References Appendices LIST OF TABLES AND FIGURES Table 1 Bushfire Threat Assessment Figure 1 Site plan of proposed Central Facilities... 9 Figure 2 Summary of bushfire threat assessment Figure 3 Byron Shire Council bushfire prone land map Figure 4 Concept landscape plan for the central facilities Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 3

5 1.0 EXECUTIVE SUMMARY The applicant is proposing to construct central facilities on the existing North Byron Beach Resort site at Lots 1, 9, 10 & 11 DP Bayshore Drive, Byron Bay. The development is considered as part of a Special Fire Protection Purpose (SFPP) development and also has a Class 9b use (conference rooms) that will also be considered with the intent of PBP2006. The report has established that full compliance with the acceptable solutions of Planning for Bushfire Protection 2006 is possible for the proposed central facilities only. The following table provides a summary of the recommendations of the report and the method of assessment for each of the heads of consideration. MEASURE RECOMMENDATION METHOD OF ASSESSMENT APZ Required 50m APZ to west, northwest; southwest and south. Acceptable Solution 30m APZ to the east and northeast 20m APZ to the north Water Supply Fire hydrants are to be provided within the site to comply with AS and s4.2.7 Acceptable Solution Electricity Supply Proposed electricity supply to be located below Acceptable Solution ground level Gas Supply Gas supply to comply with PBP2006 Acceptable Solution Construction Standards Landscape Access BAL 12.5 AS Appendix 3 PBP2006 Landscaping within the APZ is to comply with Appendix 5 of PBP2006. The property access road (Bayshore Drive) is to comply with Table 4.1 of PBP2006 and s4.1.3(1) although the requirements for 8m wide perimeter road is not required. Acceptable Solution Acceptable Solution Acceptable Solution The report makes the following recommendations for the development for the application for a Bush Fire Safety Authority (BFSA). The full report however is to be considered, including Section 2.2 that details the Significant Environmental Features that are not considered by this report. 1. The entire proposed central facilities and housekeeping buildings are to be constructed to BAL-12.5 AS Appendix 3 PBP Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 4

6 2. An Emergency Evacuation Plan is to be prepared in accordance with s4.2.7 PBP2006 and submitted to the Consent Authority and NSW Rural Fire Service for approval. 3. Should a gas service be installed the following aspects will require compliance: Reticulated or bottled gas installed and maintained in accordance with AS 1596 with metal piping used. Fixed gas cylinders to be kept clear of flammable material by a distance of 10m and shielded on the hazard side of the installation Gas cylinders close to the building are to have the release valves directed away from the building and at least 2m from flammable material with connections to and from the gas cylinder being of metal. Polymer sheathed flexible gas supply lines to gas meters adjacent to the buildings are not used. 4. An Asset Protection Zone around the central facilities and the house keeping building of 50m to the south, southwest, west and northwest; APZ of 30m to the east and northeast and 20m to the north shall be provided and maintained in perpetuity in accordance with Planning for Bushfire Protection Landscaping is to be undertaken within the Asset Protection Zone (APZ) in accordance with Appendix 5 Planning for Bushfire Protection A Monitoring and Fuel Management plans is to be prepared and approved by the NSW Rural Fire Service and included as a condition of consent and on the Fire Safety Schedule. 5. Fire hydrants are to be provided and installed in accordance with s4.2.7 of Planning for Bushfire Protection The upgrading works on Bayshore Drive are to comply with s4.1.3(1) of Planning for Bushfire Protection 2006 with exception for the requirement of an 8m wide perimeter road. Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 5

7 2.0 INTRODUCTION 2.1 GENERAL The proposed central facilities will replace the existing central facilities at the North Byron Beach Resort located on Lots 1, 9, 10 & 11 DP Bayshore Drive, Byron Bay. The existing development is identified by Clause 44 of the Rural Fires Regulation 2002 as being a Special Fire Protection Purpose (SFPP) development given that the site is a tourist facility. It is understood that a s96 application has been submitted and is currently under review by the Consent Authority for 75 cabins relating to a 1987 development consent. This report has not considered that application when assessing the central facilities pursuant to Planning for Bushfire Protection Under the provisions of section 100B of the Rural Fires Act 1997 as amended, a Bush Fire Safety Authority (BFSA) is required from the Commissioner of the NSW Rural Fire Service. The report has been prepared to address the requirements of clause 44 of the Rural Fires Regulation for an application for a Bush Fire Safety Authority as highlighted below except as identified in this report as exclusions. description (including the address) of the property on which the development the subject of the application is to be carried out, classification of the vegetation on and surrounding the property (out to a distance of 140 metres from the boundaries of the property) in accordance with the system for classification of vegetation contained in Planning for Bush Fire Protection, an assessment of the slope of the land on and surrounding the property (out to a distance of 100 metres from the boundaries of the property), identification of any significant environmental features on the property, the details of any threatened species, population or ecological community identified under the Threatened Species Conservation Act 1995 that is known to the applicant to exist on the property (note section 2.2) the details and location of any Aboriginal relic (being a relic within the meaning of the National Parks and Wildlife Act 1974) or Aboriginal place (within the meaning of that Act) that is known to the applicant to be situated on the property (note section 2.2), a bush fire assessment for the proposed development (including the methodology used in the assessment) that addresses the following matters: the extent to which the development is to provide for setbacks, including asset protection zones, the siting and adequacy of water supplies for fire fighting, Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 6

8 the capacity of public roads in the vicinity to handle increased volumes of traffic in the event of a bush fire emergency, whether or not public roads in the vicinity that link with the fire trail network have two-way access, the adequacy of arrangements for access to and egress from the development site for the purposes of an emergency response, the adequacy of bush fire maintenance plans and fire emergency procedures for the development site, the construction standards to be used for building elements in the development, the adequacy of sprinkler systems and other fire protection measures to be incorporated into the development, an assessment of the extent to which the proposed development conforms with or deviates from the standards, specific objectives and performance criteria set out in Chapter 4 (Performance Based Controls) of Planning for Bush Fire Protection. 2.2 SIGNIFICANT ENVIRONMENTAL FEATURES An assessment is to be undertaken with regard to: State Environmental Planning Policy No. 44 (Koala Habitat Protection). Threatened Species Conservation Act (1995). Environmental Protection and Biodiversity Conservation Act (1999). National Parks and Wildlife Act, 1974 (Wildlife Atlas) Native Vegetation Act This report does not consider the above legislation and in this regard this report should be read in conjunction with the Statement of Environmental Effects submitted with the development application. 2.3 REPORT DETAILS Report Reference No.: 13/116(a) Property Address: Lots 1, 9, 10 & 11 DP Bayshore Drive, Byron Bay Owners Name: North Byron Beach Resort Pty ltd Local Government Area: Proposal: Byron Shire Council Central facilities for tourist resort Drawings: Shane Thompson Architects, dated Report Prepared By: Peter Thornton MFireSafeEng Building Surveyor (MAIBS) BPAD A Certified Practitioner Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 7

9 3.0 PROPOSED DEVELOPMENT This report has been prepared at the request of the stated client to provide supporting information to enable the NSW Rural Fire Service to assess the proposal against the requirements of s100b of the Rural Fires Act 1997 for the issue of a Bush Fire Safety Authority. The proposal is for the establishment of resort Central Facilities at the North Byron Beach Resort. The North Byron Beach Resort is located at Belongil Beach, Byron Bay and is accessed via Bayshore Drive. The proposed buildings are the guest arrival point and main hub for the resort dining, recreation, events and operations. An ancillary "housekeeping" building and car parking area are co-located to the Central Facilities. The key elements and functions of the resort Central Facilities are: Reception, Lobby, Porte cochere and Administration; Restaurant and Bar; Central kitchen and food service area; Conference and function facilities; Multi-purpose room; Gymnasium; Lagoon swimming pool; Poolside cafe; Day spa; Kids play area; and Loading dock and waste management. Access to the restaurant, bar and day spa will be available to the public, visiting tourists and community members. The conference and function rooms will be available for private hire by appointment. The proposal will be located along the northern boundary of the North Byron Beach Resort site, where the current restaurant/function centre and the previous beach resort administration buildings and pool exists. The buildings will be located centrally to the resort accommodation and will support the operations of the resort and the cabins which exist on site. The new facilities will be sensitively designed in three (3) separate single-storey buildings arranged around the central lagoon pool and recreation area. The design of the proposal reflects a vibrant and modern architectural and landscape interpretation of a seaside resort destination. Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 8

10 Figure 1 Site plan of proposed Central Facilities (larger image in Appendix A) 4.0 BUSHFIRE THREAT ASSESSMENT The bushfire threat within 140m of the central facility is forested wetland to the south, southwest, west and northwest and beyond the rainforest to the southeast. Rainforest vegetation is located to the east, northeast and southeast with all vegetation located on flat topography. The existing development site within 100m of the proposed facilities is generally well maintained grass (mown <10cm in height) with scattered trees throughout. Whilst there are a larger number of existing trees in this area which occupy, in places, more than 20% of the 100m radius, this land is considered as managed land. Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 9

11 The existing site for 100m from the proposed building is currently welll managed land The primary bushfire impact for the development would be from the Tyagarah Nature Reserve to the northwest which is greater than 140m from the central facilities however the reserve would potentially create impact to the site primarily with ember attack. In this regard the construction standards of BAL Appendix 3 PBP2006 will provide reasonable resistance to potential ember attack. Figure 2 Summary of bushfire threat assessment Yellow forested wetland and scrub combination Green rainforest vegetation. All vegetation located on flat topography Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 10

12 The following table summarises the category of bushfire attack pursuant to Table A2.6 Planning for Bushfire Protection Table 1: Bushfire Threat Assessment ASPECT SLOPE VEGETATION CLASS APZ WIDTH (Table A2.1 PBP2006) Northwest 0 0 Forested Wetland 50m West 0 0 Forested Wetland 50m South, southwest 0 0 Forested Wetland 50m East 0 0 Rainforest 30m North 0 0 Grassland 20m Figure 3 Byron Shire Council bushfire prone land map Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 11

13 5.0 ASSET PROTECTION ZONES AND CONSTRUCTION STANDARDS Performance Criteria Acceptable Solutions Comment The intent may be achieved where: Radiant heat levels of greater than 10kW/m 2 will not be experienced by occupants or emergency services workers entering or exiting a building An APZ is provided in accordance with the relevant tables and figures in Appendix 2 of PBP2006. Exits are located away from the hazard side of the building. Complies Complies Applicants demonstrate that issues relating to slope are addressed: maintenance is practical, soil stability is not compromised and the potential for crown fires is negated. APZs are managed and maintained to prevent the spread of a fire towards the building. Vegetation is managed to prevent flame contact and reduce radiant heat to buildings, minimise the potential for wind driven embers to cause ignition and reduce the effects of smoke on residents and fire fighters. The APZ is wholly within the boundaries of the development site. Mechanisms are in place to provide for the maintenance of the APZ over the life of the development. The APZ is not located on lands with a slope exceeding 18 degrees In accordance with the requirements of Standards for Asset Protection Zones (RFS 2005). APZ are to be wholly within the property boundaries. Complies recommendation for monitoring and fuel management plan Complies Complies provided the appropriate condition is included on the BFSA. Compliance with Appendix 5 of PBP2006 Complies - Appropriate condition is to be included on the Bush Fire Safety Authority. Table 1 outlines the bushfire assessment and pursuant to Table AS and Planning for Bushfire Protection The proposed buildings are to be constructed to BAL Appendix 3 PBP2006. Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 12

14 6.0 WATER AND UTILITY SERVICES 6.1 WATER SERVICES The buildings are required to be serviced by fire hydrants in accordance with Australian Standard and s4.2.7 PBP2006 located on the subject property. A design certification by a suitable qualified and experience hydraulic consultant will be required. 6.2 GAS SERVICES Should a gas service be installed the following aspects will require to be complied with: Reticulated or bottled gas installed and maintained in accordance with AS 1596 with metal piping used. Fixed gas cylinders to be kept clear of flammable material by a distance of 10m and shielded on the hazard side of the installation Gas cylinders close to the building are to have the release valves directed away from the building and at least 2m from flammable material with connections to and from the gas cylinder being of metal. Polymer sheathed flexible gas supply lines to gas meters adjacent to the building is not used. 6.3 ELECTRICITY SERVICES Electrical transmission lines if required are to be placed underground. 7.0 ACCESS The proposed works on Bayshore Drive are to comply with s4.1.3(1) of Planning for Bushfire Protection 2006 with exception for the requirement of an 8m wide perimeter road. Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 13

15 8.0 LANDSCAPING The majority of buildings adversely impacted upon in a bushfire event happen through ember attack and in this regard combustible material surrounding the building e.g. landscaping can play a significant part during the event. Adequate management of landscaping is critical to the survivability of an asset and for occupant safety during a bushfire. It is recommended that landscaping for the entire development be undertaken in accordance Appendix 5 of Planning for Bushfire Protection 2006 and managed and maintained for the life of the development. It is noted that the landscaping for the central facility shows littoral rainforest species with high moisture content and any dunal grasses are located only along the verge of Bayshore Drive well away from the building. As required by Planning for Bushfire Protection 2006 the requirement for a monitoring and fuel management plan will be required. Figure 4 - Concept landscape plan for the central facilities only. The full landscape plans and specifications have not been specifically assessed however compliance with Planning for Bushfire Protection 2006 will be required. Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 14

16 9.0 EMERGENCY AND EVACUATION PLANNING An emergency evacuation procedure and detailed plans of all Emergency Assembly Areas (onsite and offsite) has been prepared in accordance with the RFS Guidelines for the Preparation of Emergency/Evacuation Plan and s4.2.7 Emergency and evacuation planning CONCLUSION This report has addressed the requirements of Planning for Bushfire Protection 2006 for the proposed central facilities. Compliance with the intent is considered to be achieved with the recommendations outlined in the executive summary and other sections of this report. Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 15

17 Disclaimer This report was prepared for the purposes and exclusive use of the stated client to accompany an application to Byron Shire Council specifically relating to the development detailed within this report and is not to be used for any other purpose or by any other person or Corporation. BCA Check Pty Ltd accepts no responsibility for any loss or damage suffered howsoever arising to any person or Corporation who may use or rely on this report in contravention of the terms of this clause. As identified in Planning for Bushfire Protection 2006 and the Building Code of Australia the report is to provide recommendations to reduce the risk of ignition and does not guarantee the complete protection of the building in the event of bush fire or that the building will not be adversely impacted upon. Reporting has been based on the relevant Council and Rural Fire Service Guidelines however recommendations or suggestions given in this report are based on our site investigation at the time of reporting. In some cases site conditions may change dramatically within a few years due to rapid vegetation re-growth and invading weed species. References: NSW Rural Fire Service and Planning NSW (2006), Planning for bushfire protection, A guide for councils planners fire authorities developers and homeowners. Rural Fire Service NSW Australia. Standards Australia, (2009), AS3959 Construction of buildings in bushfire prone areas, Australian Standards, Sydney. Legislation: Environmental Planning and Assessment Act 1979 and Regulations New South Wales. Parliamentary Counsel s Office, NSW Government Information Service. Rural Fires Act New South Wales. Parliamentary Counsel s Office, NSW Government Information Service. Rural Fires Regulation. New South Wales. Parliamentary Counsel s Office, NSW Government Information Service. Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 16

18 APPENDIX A Site plan Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 17

19

20 APPENDIX B Standards for Asset Protection Zones (RFS 2005) Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 19

21 Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 20

22 Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 21

23 Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 22

24 Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 23

25 Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 24

26 Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 25

27 Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 26

28 Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 27

29 Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 28

30 Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 29

31 Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 30

32 Bushfire Certifiers - Bushfire Threat Assessment Report North Byron Beach Resort (Central facilities) 31

BUSHFIRE CONSTRAINTS ASSESSMENT FOR THE SHONE AVENUE WEST DAPTO ROAD NEIGHBOURHOOD PLAN HORSLEY

BUSHFIRE CONSTRAINTS ASSESSMENT FOR THE SHONE AVENUE WEST DAPTO ROAD NEIGHBOURHOOD PLAN HORSLEY BUSHFIRE CONSTRAINTS ASSESSMENT FOR THE SHONE AVENUE WEST DAPTO ROAD NEIGHBOURHOOD PLAN HORSLEY Australian Bushfire Protection Planners Pty Limited ACN 083 085 474 32 Old Dog Trap Road, SOMERSBY 2250 NSW.

More information

North Byron Beach Resort. Central Facilities. Statement of Environmental Effects RPS AUSTRALIA EAST PTY LTD NORTH BYRON BEACH RESORT PTY LTD

North Byron Beach Resort. Central Facilities. Statement of Environmental Effects RPS AUSTRALIA EAST PTY LTD NORTH BYRON BEACH RESORT PTY LTD North Byron Beach Resort Central Facilities Prepared by: Prepared for: RPS AUSTRALIA EAST PTY LTD NORTH BYRON BEACH RESORT PTY LTD 743 Ann Street Fortitude Valley Queensland 4006 Bayshore Drive Byron Bay

More information

Bushfire Management Plan

Bushfire Management Plan Bushfire Management Plan Wentworth West Estate Bartram Road, Success LUSH FIRE & PLANNING PO Box 114 Woodanilling WA 6316 0418 954 873 ABN 74 232 678 543 Ref 18-004 Ver D May 2018 Site Address / Plan Reference:

More information

EXAMPLE. Bushfire Management Statement Construction of a single dwelling in a Bushfire Management Overlay

EXAMPLE. Bushfire Management Statement Construction of a single dwelling in a Bushfire Management Overlay Bushfire Management Statement Construction of a single dwelling in a Bushfire Management Overlay EXAMPLE Bushfire Management Statement Construction of a single dwelling in a Bushfire Management Overlay

More information

Bushfire Development Report

Bushfire Development Report Bushfire Development Report as Expert Evidence for the Kaufland Store Development at 266-268 Maroondah Highway Chirnside Park VIC 3116 Prepared for Kaufland Australia Pty Ltd November 2018 Terramatrix

More information

Bushfire Development Report

Bushfire Development Report Bushfire Development Report for the Kaufland Store Development at 1158 Nepean Highway Mornington VIC 3931 Prepared for Kaufland Australia Pty Ltd February 2019 Terramatrix project: Kaufland Australia Pty

More information

Draft Ada Street Cardiff Area Plan

Draft Ada Street Cardiff Area Plan Draft Ada Street Cardiff Area Plan (Draft Amendment to Lake Macquarie Development Control Plan 2014) Exhibition: The draft Area Plan is on public exhibition from 29 February 2016 to 29 March 2016. Submissions:

More information

Information Bulletin

Information Bulletin Consideration of emergency response in Alternative Solutions Version 1 Approved for release May 2015 1.0 Purpose statement The purpose of this document is to increase awareness and consideration of the

More information

BUSHFIRE RESPONSE PLAN

BUSHFIRE RESPONSE PLAN BUSHFIRE RESPONSE PLAN February 2014 2 Document Control Revision: 1 Date: 4 February 2014 Status: Document change control: Approved by EPC Revision # Change Description Date Author 1 Initial document release

More information

Planning Proposal Charlestown Swim and Leisure Centre LEP Amendment

Planning Proposal Charlestown Swim and Leisure Centre LEP Amendment Planning Proposal Charlestown Swim and Leisure Centre LEP Amendment Amendment No. 4 to Lake Macquarie Local Environmental Plan 2014 (PP_2014_LAKEM_005_00) Local Government Area: Name of Draft LEP: Lake

More information

Analysis. Bushfire protection review. Travers bushfire & ecology. Headland Preservation Group Inc. 10 Terminal Buildings Middle Head Road Mosman

Analysis. Bushfire protection review. Travers bushfire & ecology. Headland Preservation Group Inc. 10 Terminal Buildings Middle Head Road Mosman Analysis of Bushfire protection review by Travers bushfire & ecology for Headland Preservation Group Inc at 10 Terminal Buildings Middle Head Road Mosman Lot 203 DP 1022020 30 July 2014 Roger Fenwick Bush

More information

Planning Proposal Toronto Road, Booragul. Amendment to Lake Macquarie Local Environmental Plan (LMLEP) 2014

Planning Proposal Toronto Road, Booragul. Amendment to Lake Macquarie Local Environmental Plan (LMLEP) 2014 Planning Proposal Toronto Road, Booragul Amendment to Lake Macquarie Local Environmental Plan (LMLEP) 2014 Local Government Area: Name of Draft LEP: Subject Land: Land Owner: Applicant: Folder Number:

More information

Bushfire Evacuation Plan

Bushfire Evacuation Plan A Guide to Developing a Bushfire Evacuation Plan Developed by Planning & Environment Services NSW Rural Fire Service Table of Contents Table Of Contents... 2 Introduction... 3 Purpose & Objectives Of A

More information

UNCONTROLLED IF PRINTED. Issued with the authority of the Chief Commissioner and General Manager of Scouts Australia NSW

UNCONTROLLED IF PRINTED. Issued with the authority of the Chief Commissioner and General Manager of Scouts Australia NSW PROCEDURE Emergency preparedness Issued with the authority of the Chief Commissioner and General Manager of Chief Commissioner signature Chief Executive Officer signature Sponsor Head of Risk Document

More information

Planning Proposal Concurrent DA/LEP Amendment for Belmont North Pharmacy Amendment No. 24 to Lake Macquarie Local Environmental Plan (LMLEP) 2014

Planning Proposal Concurrent DA/LEP Amendment for Belmont North Pharmacy Amendment No. 24 to Lake Macquarie Local Environmental Plan (LMLEP) 2014 Planning Proposal Concurrent DA/LEP Amendment for Belmont North Pharmacy Amendment No. 24 to Lake Macquarie Local Environmental Plan (LMLEP) 2014 Local Government Area: Name of Draft LEP: Subject Land:

More information

Managing Fire Risk for New Rural Dwellings

Managing Fire Risk for New Rural Dwellings Managing Fire Risk for New Rural Dwellings Policy Options Paper Draft Proposed Changes to the Tasman Resource Management Plan For Public Consultation December 2011 January 2012 Executive Summary The current

More information

NZS 4517:2010. New Zealand Standard. Fire sprinkler systems for houses. Superseding NZS 4517:2002 NZS 4517:2010

NZS 4517:2010. New Zealand Standard. Fire sprinkler systems for houses. Superseding NZS 4517:2002 NZS 4517:2010 New Zealand Standard Fire sprinkler systems for houses Superseding NZS 4517:2002 NZS 4517:2010 NZS 4517:2010 COMMITTEE REPRESENTATION This Standard was prepared under the supervision of the P 4517 Committee,

More information

South Australian Regulatory Requirements

South Australian Regulatory Requirements South Australian Regulatory Requirements Australian Legislative Framework Act Act of Parliament Establishes the Law Primary legislation Regulation Subordinate legislation authorised by a specific Act Therefore

More information

PLANNING INSTITUTE OF AUSTRALIA, NSW DIVISION SUBMISSION ON THE NSW DRAFT HOUSING CODE AND NSW DRAFT COMMERCIAL CODE

PLANNING INSTITUTE OF AUSTRALIA, NSW DIVISION SUBMISSION ON THE NSW DRAFT HOUSING CODE AND NSW DRAFT COMMERCIAL CODE PLANNING INSTITUTE OF AUSTRALIA, NSW DIVISION SUBMISSION ON THE NSW DRAFT HOUSING CODE AND NSW DRAFT COMMERCIAL CODE This Submission provides detailed comment on draft Codes following feedback from PIA

More information

BUSHFIRE TEST ON GLAZED VERTICAL ELEMENTS

BUSHFIRE TEST ON GLAZED VERTICAL ELEMENTS BUSHFIRE TEST ON GLAZED VERTICAL ELEMENTS Report number FSZ 1572 CSIRO job number SV3559 Date of issue 22 FEBRUARY 2013 Client BREEZWAY AUSTRALIA PTY LTD Commercial-in-confidence Copyright CSIRO 2013 Copying

More information

8.1. Fire and Heritage. The maintenance series. Information sheet. Guidelines on Fire Safety in Heritage Buildings

8.1. Fire and Heritage. The maintenance series. Information sheet. Guidelines on Fire Safety in Heritage Buildings The maintenance series Information sheet 8.1 Fire and Heritage Destruction of the Prince of Wales Theatre by fire on 3 October 1860. It was situated at the corner of King and Castlereagh Streets, Sydney.

More information

SCHEDULE THREE TO THE DEVELOPMENT PLAN OVERLAY EASTERN GOLF COURSE KEY REDEVELOPMENT SITE

SCHEDULE THREE TO THE DEVELOPMENT PLAN OVERLAY EASTERN GOLF COURSE KEY REDEVELOPMENT SITE DD/MM/YY SCHEDULE THREE TO THE DEVELOPMENT PLAN OVERLAY Shown on the planning scheme map as DPO3 EASTERN GOLF COURSE KEY REDEVELOPMENT SITE 1.0 A permit may be granted before a development plan has been

More information

Fire Management Guide

Fire Management Guide Fire Management Guide Meeting day to day fire management obligations in WA requires reference to Health and Safety legislation, the Building Code of Australia, and multiple Australian Standards. This guide

More information

Child Minding Centres and Family Day Care

Child Minding Centres and Family Day Care Child Minding Centres and Family Day Care Policy Type: Local Planning Policy Policy Owner: Director Urban Planning Policy No. LPP1.12 Last Review Date: 20 September 2016 Policy Objectives To provide for

More information

Environmental Management System

Environmental Management System ILLAWARRA COAL Environmental Management System DENDROBIUM MINE BUSH FIRE MANAGEMENT PLAN REVIEW HISTORY Revision Description of Changes Date Approved 0 Draft submitted Nov 04 Bryan Quinn 1.0 Incorporating

More information

AMENDMENTS. Date Effective. Amendment No. Council. DCP 14 Davidson St, Greenacre Page 2

AMENDMENTS. Date Effective. Amendment No. Council. DCP 14 Davidson St, Greenacre Page 2 AMENDMENTS Amendment No. Description Adopted by Council Date Effective DCP 14 Davidson St, Greenacre Page 2 TABLE OF CONTENTS 1.0 INTRODUCTION... 4 1.1 NAME OF THIS PLAN... 4 1.2 COMMENCEMENT OF DEVELOPMENT

More information

Plan Change 56: Fire Fighting Water Supplies Code of Practice

Plan Change 56: Fire Fighting Water Supplies Code of Practice Plan Change 56: Fire Fighting Water Supplies Code of Practice n_292117 Contents 1. INTRODUCTION... 1 2. WHAT IS THE CODE?... 1 3. WHEN IS THE CODE APPLIED?... 1 4. ARE YOU AT RISK?... 1 5. HOW ARE HOUSE

More information

BUSHFIRE MANAGEMENT PLAN (BMP)

BUSHFIRE MANAGEMENT PLAN (BMP) Established 1907 BUSHFIRE MANAGEMENT PLAN (BMP) December 2015 Version Date Section Modified 1 February 2005 All 2 3 December 2010 December 2015 All All Reason for Modification Original Management Plan

More information

Planning Proposal under section 55 of the EP&A Act

Planning Proposal under section 55 of the EP&A Act FOR PUBLIC EXHIBITION [Brief description] Monday 10 October to Monday 27 October 2014 Planning Proposal under section 55 of the EP&A Act Port Macquarie-Hastings LEP 2011 (Amendment No 32) Mixed land zone

More information

George Hotel application STAFF REVIEW COMMITTEE OF THE WHOLE JANUARY 14, 2014

George Hotel application STAFF REVIEW COMMITTEE OF THE WHOLE JANUARY 14, 2014 George Hotel application STAFF REVIEW COMMITTEE OF THE WHOLE JANUARY 14, 2014 1 Presentation outline Purpose: to seek Council direction for next steps in the review process Application process to date

More information

statement of environmental effects

statement of environmental effects for single dwelling houses, granny flats and associated ancillary structures only property details Please provide the following details Lot N o/s. Section N o. DP N o. A statement of environmental effects

More information

Client Advisory Note June 2015:

Client Advisory Note June 2015: Client Advisory Note June 2015: Topics: 1. Substantially revised Fire Alarm and Smoke Control Standards for proposed adoption in NCC Volume One BCA 2016; 2. Independent review of Building Professionals

More information

FIRE SAFETY PLAN FOR CONSTRUCTION, RENOVATION AND DEMOLITION SITES

FIRE SAFETY PLAN FOR CONSTRUCTION, RENOVATION AND DEMOLITION SITES BACKGROUND INFORMATION Alberta Fire Code 2014: FIRE SAFETY PLAN FOR CONSTRUCTION, RENOVATION AND DEMOLITION SITES Alberta Fire Code (AFC) 2014, Division B, Section 5.6. requires a Fire Safety Plan for

More information

TRANSPORT AND WORKS ACT 1992 TRANSPORT AND WORKS (APPLICATIONS AND OBJECTIONS PROCEDURE)(ENGLAND AND WALES) RULES 2006

TRANSPORT AND WORKS ACT 1992 TRANSPORT AND WORKS (APPLICATIONS AND OBJECTIONS PROCEDURE)(ENGLAND AND WALES) RULES 2006 TRANSPORT AND WORKS ACT 1992 TRANSPORT AND WORKS (APPLICATIONS AND OBJECTIONS PROCEDURE)(ENGLAND AND WALES) RULES 2006 THE MIDLAND METRO (BIRMINGHAM CITY CENTRE EXTENSION LAND ACQUISITION AND VARIATION)

More information

FIRE SAFETY MANAGEMENT PLAN

FIRE SAFETY MANAGEMENT PLAN FIRE SAFETY MANAGEMENT PLAN February 2014 2 Document Control Revision: 1 Date: 4 February 2014 Status: Document change control: Approved by EPC Revision # Change Description Date Author 1 Initial document

More information

Dispute over the requirement for fire door signage to hotel suites at 124 Devon Street West, New Plymouth

Dispute over the requirement for fire door signage to hotel suites at 124 Devon Street West, New Plymouth Determination 2016/058 Dispute over the requirement for fire door signage to hotel suites at 124 Devon Street West, New Plymouth Summary This determination considers whether signage is required between

More information

Wingecarribee Shire Council

Wingecarribee Shire Council Connell Wagner Pty Ltd ABN 54 005 139 873 2 Palmer Street North Parramatta New South Wales 2151 Australia Telephone: +61 2 8896 4100 Facsimile: +61 2 9890 3558 Email: cwpar@conwag.com www.conwag.com Moss

More information

Steven Craft, PhD, P.Eng. FIRE SAFETY DURING THE COURSE OF CONSTRUCTION

Steven Craft, PhD, P.Eng. FIRE SAFETY DURING THE COURSE OF CONSTRUCTION Steven Craft, PhD, P.Eng. FIRE SAFETY DURING THE COURSE OF CONSTRUCTION Mid-Rise Workshop, Coast Plaza Inn, Calgary, Feb. 4 th, 2016 Outline Overview of risks Regulations Changes to 2015 NFC for mid-rise

More information

Fire resistance test on fire collars protecting a concrete slab penetrated by services

Fire resistance test on fire collars protecting a concrete slab penetrated by services INFRASTRUCTURE TECHNOLOGIES Fire resistance test on fire collars protecting a concrete slab penetrated by services Test Report Author: Mario Lara Report number: FSP 1601a Date: 11 April 2014 (This report

More information

STAFF REPORT. December 20, North York Community Council. Director, Community Planning, North York District

STAFF REPORT. December 20, North York Community Council. Director, Community Planning, North York District STAFF REPORT December 20, 2005 To: From: Subject: North York Community Council Director, Community Planning, North York District Preliminary Report Application to Amend the Official Plan and Zoning By-law

More information

Part 12 Precinct Area Plans - Wyee West

Part 12 Precinct Area Plans - Wyee West TABLE OF CONTENTS 1 INTRODUCTION... 1 1.1 BACKGROUND... 1 1.2 EXTENT OF AREA PLAN... 1 1.3 EXISTING CHARACTER... 2 1.4 ENVIRONMENTAL ATTRIBUTES AND CONSTRAINTS... 2 1.5 DESIRED FUTURE CHARACTER... 3 1.6

More information

FIRE-RESISTANCE TEST ON DOWNLIGHT COVERS INSTALLED IN PLASTERBOARD CEILINGS

FIRE-RESISTANCE TEST ON DOWNLIGHT COVERS INSTALLED IN PLASTERBOARD CEILINGS FIRE-RESISTANCE TEST ON DOWNLIGHT COVERS INSTALLED IN PLASTERBOARD CEILINGS Report number FSP 1290A CSIRO job number LP46ASP3085 Date of issue 30 NOVEMBER 2007 Client EFFICIENCY MATRIX PTY LTD and YOUNGEN

More information

Joe Pool Lake Lake Master Plan Public Information Meeting Presentation of Final Draft Revision July 31, 2018

Joe Pool Lake Lake Master Plan Public Information Meeting Presentation of Final Draft Revision July 31, 2018 Joe Pool Lake Lake Master Plan Public Information Meeting Presentation of Final Draft Revision July 31, 2018 Presented By Jeremy Spencer Lake Manager U.S. Army Corps of Engineers Fort Worth District US

More information

3. STATEMENTS OF DESIRED CHARACTER FOR PLANNING AREAS AND PRECINCTS

3. STATEMENTS OF DESIRED CHARACTER FOR PLANNING AREAS AND PRECINCTS 3.30 Planning Area No. 30 Mary River Valley 3.30.1 Location and Role This Planning Area encompasses rural lands in the western part of the Shire. These lands are located within the catchment area of the

More information

3. Aspects of the Proposed District Plan that may impact upon the operation of properties that the NZFS Commission owns.

3. Aspects of the Proposed District Plan that may impact upon the operation of properties that the NZFS Commission owns. Objective 8.1, Policy 8.5, Rule 8.4.3.3 and Rule 8.4.3.3 3. Aspects of the Proposed District Plan that may impact upon the operation of properties that the NZFS Commission owns. Rules: Rule 4.6.7, Rule

More information

Fire safety systems. Behaviour of fires

Fire safety systems. Behaviour of fires Fire safety systems The objective of the BCA Housing Provisions (Volume 2) with respect to Class 1 buildings (residential) and fire, is to safeguard occupants from illness or injury, to avoid the spread

More information

Strategic Environmental Assessment Screening Report. Dublin Port Masterplan Review 2017

Strategic Environmental Assessment Screening Report. Dublin Port Masterplan Review 2017 Strategic Environmental Assessment Screening Report Dublin Port Masterplan Review 2017 Table of Contents 1 Introduction... 1 2 Purpose of the Masterplan... 2 3 Task 1.1 Pre-Screening Check... 5 4 Task

More information

Amendment C146 Melton Planning Scheme Expert Evidence Statement Traffic & Transport Beattys Road, Plumpton

Amendment C146 Melton Planning Scheme Expert Evidence Statement Traffic & Transport Beattys Road, Plumpton 235 311 Beattys Road, Plumpton 16585REP001C-F 21 November 2016 onemilegrid.com.au 1/59 Keele Street, Collingwood, VIC 3066 (03) 9939 8250 onemilegrid ABN: 79 168 115 679 (03) 9939 8250 1/59 Keele Street

More information

Plan Modification to Chapter B2 of the Auckland Unitary Plan(AUP) Operative in part (15 November 2016)

Plan Modification to Chapter B2 of the Auckland Unitary Plan(AUP) Operative in part (15 November 2016) UNITARY PLAN UPDATE REQUEST MEMORANDUM TO FROM Phill Reid Linley Wilkinson DATE 25 September 2018 SUBJECT Plan Modification to Chapter B2 of the Auckland Unitary Plan(AUP) Operative in part (15 November

More information

BACKGROUND INFORMATION DOCUMENT (BID) AND INVITATION TO PARTICIPATE

BACKGROUND INFORMATION DOCUMENT (BID) AND INVITATION TO PARTICIPATE To: Interested and Affected Parties 2 October 2017 NOTIFICATION OF ENVIRONMENTAL IMPACT ASSESSMENT PROCESS FOR THE PROPOSED DEVELOPMENT OF RESIDENTIAL HOUSING ON PORTION 56 OF THE FARM CHELSEA NO. 25,

More information

Fire Safety Plan Information. For Construction and Demolition Sites

Fire Safety Plan Information. For Construction and Demolition Sites Fire Safety Plan Information For Construction and Demolition Sites FIRE CODE INTERPRETATION November 2009 FCI-09-03 Page 1 of 8 ISSUE: FIRE SAFETY PLAN Construction and Demolition Sites Safety provisions

More information

Fire Curtains and Radiation Attenuation

Fire Curtains and Radiation Attenuation The National Construction Code (NCC) provides a Deemed-to-Satisfy (DtS) method for fire barriers. This method generally requires these barriers to provide a specific fire resistance level (FRL) based on

More information

Firefighting operations on multi-tiered vehicle stacking buildings F5-13 GD

Firefighting operations on multi-tiered vehicle stacking buildings F5-13 GD DESIGNER S GUIDE Firefighting operations on multi-tiered vehicle stacking buildings F5-13 GD Introduction When to use Scope Use this chapter to provide a consistent Fire and Emergency New Zealand position

More information

LIDBURY, SUMMERS & WHITEMAN

LIDBURY, SUMMERS & WHITEMAN LIDBURY, SUMMERS & WHITEMAN Consulting Surveyors, Planners & Engineers Incorporating Degotardi, Smith & Partners (Forster) The Institution of Surveyors NSW The Institution of A.B.N. 48 470 231 954 P.O.

More information

DATE PURPOSE PREPARED REVIEWED SUBMITTED TO CLIENT

DATE PURPOSE PREPARED REVIEWED SUBMITTED TO CLIENT 2017 Bushfire Safety Consulting Pty Ltd. Document Information Prepared for Project Name Site Owners Marcus Sarich Red Hill Auditorium Ace Nominees Pty Ltd Document Control Bushfire Management and Evacuation

More information

FIRE-RESISTANCE TEST ON FIRE COLLARS PROTECTING A PLASTERBOARD WALL PENETRATED BY SERVICES

FIRE-RESISTANCE TEST ON FIRE COLLARS PROTECTING A PLASTERBOARD WALL PENETRATED BY SERVICES FIRE-RESISTANCE TEST ON FIRE COLLARS PROTECTING A PLASTERBOARD WALL PENETRATED BY SERVICES Report number FSP 1360 CSIRO job number SP3241 Date of issue 31 JULY 2009 Client SNAP FIRE SYSTEMS PTY LTD. Commercial-in-confidence

More information

DRAFT Anan Wildlife Observatory Recreation Site Master Plan. Prepared by: Wrangell Ranger District Tongass National Forest Alaska

DRAFT Anan Wildlife Observatory Recreation Site Master Plan. Prepared by: Wrangell Ranger District Tongass National Forest Alaska DRAFT Anan Wildlife Observatory Recreation Site Master Plan Prepared by: Wrangell Ranger District Tongass National Forest Alaska December, 2015 Signature Sheet Approved: James King Director of Recreation,

More information

Leading environmental solutions...

Leading environmental solutions... Leading environmental solutions... About Us Australian Wetlands Consulting (AWC) is a multi-award winning environmental design and consulting company committed to creating a better environment through

More information

Planning Proposal Wangi Power Station Complex Administrative Amendment Lake Macquarie Local Environmental Plan 2014

Planning Proposal Wangi Power Station Complex Administrative Amendment Lake Macquarie Local Environmental Plan 2014 Planning Proposal Wangi Power Station Complex Administrative Amendment Lake Macquarie Local Environmental Plan 2014 (Post Exhibition Version) Local Government Area: Name of Draft LEP: Subject Land: Land

More information

To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard

To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard SOCIAL ACCOUNTABILITY ACCREDITATION SERVICES To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard Background: After an

More information

Draft FPA Australia Technical Specification for Public Comment FPAA101D DRAFT

Draft FPA Australia Technical Specification for Public Comment FPAA101D DRAFT Draft FPA Australia Technical Specification for Public Comment FPAA101D These preliminary pages provide information on the background to this Technical Specification, the system it covers and the context

More information

Stage 2: WestConnex M5 King Georges Road Interchange Upgrade. Appendix B5 Construction Heritage Management Plan

Stage 2: WestConnex M5 King Georges Road Interchange Upgrade. Appendix B5 Construction Heritage Management Plan Stage 2: WestConnex M5 King Georges Road Interchange Upgrade Appendix B5 Construction Heritage Management Plan JULY 2016 DOCUMENT CONTROL File name Report name CEMP App B5 CHMP Rev E Revision number E

More information

Act On Fire Bca Compliance And Fire Safety Engineering

Act On Fire Bca Compliance And Fire Safety Engineering We have made it easy for you to find a PDF Ebooks without any digging. And by having access to our ebooks online or by storing it on your computer, you have convenient answers with act on fire bca compliance

More information

Welcome to our exhibition

Welcome to our exhibition Welcome to our exhibition The Homes & Communities Agency (HCA) welcomes you to this public exhibition explaining our proposals for the redevelopment of the former Lea Castle Hospital site. About the Homes

More information

Australian/New Zealand Standard

Australian/New Zealand Standard AS/NZS 4645.2:2008 AS/NZS 4645.2:2008 Australian/New Zealand Standard Gas distribution networks Part 2: Steel pipe systems AS/NZS 4645.2:2008 This Joint Australian/New Zealand Standard was prepared by

More information

ADMINISTRATION RECOMMENDATION(S) 2016 November 03. That Calgary Planning Commission recommends APPROVAL of the proposed Land Use Amendment.

ADMINISTRATION RECOMMENDATION(S) 2016 November 03. That Calgary Planning Commission recommends APPROVAL of the proposed Land Use Amendment. Page 1 of 7 EXECUTIVE SUMMARY This Land Use Amendment application seeks to redesignate a portion of the parcel from Industrial General (I-G) District to Special Purpose City and Regional Infrastructure

More information

7 May 9, 2012 Public Hearing APPLICANT AND PROPERTY OWNER: COASTAL ENTERPRISES, LLC

7 May 9, 2012 Public Hearing APPLICANT AND PROPERTY OWNER: COASTAL ENTERPRISES, LLC 7 May 9, 2012 Public Hearing APPLICANT AND PROPERTY OWNER: COASTAL ENTERPRISES, LLC REQUEST: Variance to Section 5B of the Site Plan Ordinance (Floodplain Regulations) ADDRESS / DESCRIPTION: 601 Sandbridge

More information

H7 Open Space zones. (a) provide for the needs of the wider community as well as the needs of the community in which they are located;

H7 Open Space zones. (a) provide for the needs of the wider community as well as the needs of the community in which they are located; H7. Open Space zones H7.1. Background The majority of land zoned as open space is vested in the Council or is owned by the Crown. However some areas zoned open space are privately owned. While the open

More information

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES Mandatory Fire Safety Instruction UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES Principal Contractor fire safety considerations in shared occupancy project or refurbishments

More information

What you need to know about. Maintaining essential safety measures in your building

What you need to know about. Maintaining essential safety measures in your building What you need to know about Maintaining essential safety measures in your building When the construction of a building is complete, the building owner is responsible for its upkeep and maintenance, particularly

More information

Biodiversity: My Hotel in Action

Biodiversity: My Hotel in Action Biodiversity: My Hotel in Action Hotel Manager s Checklist This checklist is designed to guide you in evaluating how many of the practices recommended in this guide have been implemented in your hotel.

More information

Planning Proposal (PP007) Rezoning of Kylor Pty Ltd Land at Manyana

Planning Proposal (PP007) Rezoning of Kylor Pty Ltd Land at Manyana Planning Proposal (PP007) Rezoning of Kylor Pty Ltd Land at Manyana Prepared by Planning & Development Services Group Shoalhaven City Council File 50064E Version 1 - Gateway March 2015 Shoalhaven City

More information

Wingecarribee Shire Council

Wingecarribee Shire Council Connell Wagner Pty Ltd ABN 54 005 139 873 2 Palmer Street North Parramatta New South Wales 2151 Australia Telephone: +61 2 8896 4100 Facsimile: +61 2 9890 3558 Email: cwpar@conwag.com www.conwag.com Moss

More information

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016 1. Introduction The intent of this document is to establish minimum standards for the practice of fire protection engineering within the State of Oklahoma as conducted by licensed professional engineers.

More information

Occupational Health & Safety Practitioner. Reading BUILDING FIRE SAFETY

Occupational Health & Safety Practitioner. Reading BUILDING FIRE SAFETY Occupational Health & Safety Practitioner Reading BUILDING FIRE SAFETY January 2009 Contents OVERVIEW...1 SECTION 1: INTRODUCTION...2 SECTION 2: BUILDING CLASSIFICATIONS...4 SECTION 3: PASSIVE AND ACTIVE

More information

Fire protection documentation. CFPA-E Guideline No 13:2015 F

Fire protection documentation. CFPA-E Guideline No 13:2015 F Fire protection documentation CFPA-E Guideline No 13:2015 F FOREWORD The European fire protection associations have decided to produce common guidelines in order to achieve similar interpretation in the

More information

UTT/17/2075/FUL - (BERDEN) (Referred to Committee by Councillor Janice Loughlin. Reason: In the Public Interest)

UTT/17/2075/FUL - (BERDEN) (Referred to Committee by Councillor Janice Loughlin. Reason: In the Public Interest) UTT/17/2075/FUL - (BERDEN) (Referred to Committee by Councillor Janice Loughlin. Reason: In the Public Interest) PROPOSAL: LOCATION: APPLICANT: Amendments to the design of a scheme for a 49.99MW battery

More information

April 11, 2016 Park Board Chair and Commissioners General Manager Vancouver Board of Parks and Recreation New Brighton Salt Marsh - Preferred Concept

April 11, 2016 Park Board Chair and Commissioners General Manager Vancouver Board of Parks and Recreation New Brighton Salt Marsh - Preferred Concept TO: FROM: SUBJECT: April 11, 2016 Park Board Chair and Commissioners General Manager Vancouver Board of Parks and Recreation New Brighton Salt Marsh - Preferred Concept RECOMMENDATION A. THAT the Vancouver

More information

Australian Standard. Fire detection, warning, control and intercom systems System design, installation and commissioning. Part 1: Fire AS 1670.

Australian Standard. Fire detection, warning, control and intercom systems System design, installation and commissioning. Part 1: Fire AS 1670. AS 1670.1 2004 (Incorporating Amendment No. 1) AS 1670.1 2004 Australian Standard Fire detection, warning, control and intercom systems System design, installation and commissioning Part 1: Fire This Australian

More information

Tāhuhu whakaruruhau ā-taone The sheltering ridge pole

Tāhuhu whakaruruhau ā-taone The sheltering ridge pole B2. Tāhuhu whakaruruhau ā-taone - Urban growth and form B2.1. Issues Tāhuhu whakaruruhau ā-taone The sheltering ridge pole Auckland s growing population increases demand for housing, employment, business,

More information

Fire Precautions During Construction of Large Buildings. Technical Design Guide issued by Forest and Wood Products Australia

Fire Precautions During Construction of Large Buildings. Technical Design Guide issued by Forest and Wood Products Australia 20 Fire Precautions During Construction of Large Buildings Technical Design Guide issued by Forest and Wood Products Australia Technical Design Guide issued by Forest and Wood Products Australia Technical

More information

Linden Homes Proposals for land off Ringwood Road, Verwood

Linden Homes Proposals for land off Ringwood Road, Verwood Welcome Welcome to Linden Homes first public exhibition displaying proposals for new homes on land off Ringwood Road in Verwood. Award-winning house builder Linden Homes, part of the Galliford Try Group,

More information

MAINTENANCE OF ESSENTIAL SAFETY MEASURES EXPLAINED (Building Regulations 2006)

MAINTENANCE OF ESSENTIAL SAFETY MEASURES EXPLAINED (Building Regulations 2006) MAINTENANCE OF ESSENTIAL SAFETY MEASURES EXPLAINED (Building Regulations 2006) 1. INTRODUCTION 1.1 Essential Safety Measures Defined Essential Safety Measures (previously called essential services) are

More information

International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A.

International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A. International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A.800(19) Magnus Arvidson SP Fire Research SP Technical Research Institute

More information

Proposed Southland District Plan 2012 Appeal Version October 2016

Proposed Southland District Plan 2012 Appeal Version October 2016 S e c t i o n 3. 5 - F i o r d l a n d / R a k i u r a Z o n e The Fiordland/Rakiura Zone encompasses the Fiordland and Rakiura National Parks and part of Mt Aspiring National Park. It also includes areas

More information

City of Chilliwack. Bylaw No A bylaw to regulate fire prevention and the protection of life and property

City of Chilliwack. Bylaw No A bylaw to regulate fire prevention and the protection of life and property City of Chilliwack Bylaw No. 3464 A bylaw to regulate fire prevention and the protection of life and property NOW THEREFORE the Council of the City of Chilliwack in open meeting assembled enacts as follows:

More information

Building Fire Safety Regulation 2008

Building Fire Safety Regulation 2008 Queensland Building Act 1975 Fire and Rescue Service Act 1990 Building Fire Safety Regulation 2008 Reprinted as in force on 1 July 2009 Reprint No. 1C This reprint is prepared by the Office of the Queensland

More information

Fire Safety Plan (FSP) Review Checklist 1

Fire Safety Plan (FSP) Review Checklist 1 Fire Safety Plan (FSP) Review Checklist 1 (Component of a BC Fire Code (BCFC) compliance inspection) COMPANY INFORMATION Company name: Building Name: Address: Street # and name City/Province Postal Code

More information

Fire-resistance test on fire collars protecting a concrete slab penetrated by services

Fire-resistance test on fire collars protecting a concrete slab penetrated by services INFRASTRUCTURE TECHNOLOGIES Fire-resistance test on fire collars protecting a concrete slab penetrated by services Test Report Author: Chris Wojcik Report number: FSP 1735 Date: 8 September 2016 Client:

More information

Fire Safety Plan (FSP) Review Checklist 1

Fire Safety Plan (FSP) Review Checklist 1 Fire Inspection & Prevention Initiative Fire Safety Plan (FSP) Review Checklist 1 (Component of a BC Fire Code (BCFC) compliance inspection) Date: COMPANY INFORMATION Company Name: Building Name: Address:

More information

Sawtell Town Centre Development Control Plan

Sawtell Town Centre Development Control Plan Sawtell Town Centre Development Control Plan ABN 79 126 214 487 CONTENTS INTRODUCTION... 1 PREAMBLE... 1 HOW TO USE THIS DCP... 1 LAND TO WHICH THIS PLAN APPLIES... 1 MASTERPLAN... 2 VISION... 2 CHARACTER

More information

Fire-resistance test on fire collars protecting a plasterboard wall penetrated by services

Fire-resistance test on fire collars protecting a plasterboard wall penetrated by services INFRASTRUCTURE TECHNOLOGIES Fire-resistance test on fire collars protecting a plasterboard wall penetrated by services Test Report Author: Peter Gordon Report number: FSP 1960 Date: 5 February 2019 Client:

More information

Australian/New Zealand Standard

Australian/New Zealand Standard AS/NZS 2918:2001 AS/NZS 2918 Australian/New Zealand Standard Domestic solid fuel burning appliances Installation Building Code of Australia Primary referenced Standard AS/NZS 2918:2001 This Joint Australian/New

More information

Planning Proposal. Rockdale Local Environmental Plan Two storey residential development in the R2 and R3 zones

Planning Proposal. Rockdale Local Environmental Plan Two storey residential development in the R2 and R3 zones Planning Proposal Rockdale Local Environmental Plan 2011 Two storey residential development in the R2 and R3 zones 16 October 2014 Contents Part 1 Part 2 Part 3 Part 4 Part 5 A statement of the Objectives

More information

COMPLYING DEVELOPMENT CERTIFICATE APPLICATION Made under the Environmental Planning and Assessment Act 1979 Sections 85, 85A

COMPLYING DEVELOPMENT CERTIFICATE APPLICATION Made under the Environmental Planning and Assessment Act 1979 Sections 85, 85A COMPLYING DEVELOPMENT CERTIFICATE APPLICATION Made under the Environmental Planning and Assessment Act 1979 Sections 85, 85A IDENTIFICATION OF BUILDING Address Lot, DP/MPS etc Suburb or town Post Code

More information

Substation Signage. Document Number: 1-11-FR-12

Substation Signage. Document Number: 1-11-FR-12 Substation Signage Document Number: 1-11-FR-12 VERSION 1.0 June 2018 This functional requirements document is in line with the organisation's 1-11-ACS-12 Substation Signage Asset Class Strategy Intellectual

More information

Rural (Urban Expansion) Environment

Rural (Urban Expansion) Environment RUEE.1 Rural (Urban Expansion) Environment Subsequent to the receipt of appeals, a 'marked up' version of the Proposed District Plan was prepared. The provisions of the Proposed Version of the Plan subject

More information

MINUTES OAK BAY ADVISORY PLANNING COMMISSION TUESDAY, JUNE 6, 2017 AT 5:00 PM COUNCIL CHAMBERS, MUNICIPAL HALL, 2167 OAK BAY AVENUE

MINUTES OAK BAY ADVISORY PLANNING COMMISSION TUESDAY, JUNE 6, 2017 AT 5:00 PM COUNCIL CHAMBERS, MUNICIPAL HALL, 2167 OAK BAY AVENUE MINUTES OAK BAY ADVISORY PLANNING COMMISSION TUESDAY, JUNE 6, 2017 AT 5:00 PM COUNCIL CHAMBERS, MUNICIPAL HALL, 2167 OAK BAY AVENUE MEMBERS PRESENT Andrew Appleton Rus Collins Pam Copley Virginia Holden

More information

CA.1 Coastal Area. Index. CA.1.1 Description and Expectations

CA.1 Coastal Area. Index. CA.1.1 Description and Expectations Index.1.2.3.4 CA.2 CA.2.1 CA.2.2 CA.2.3 CA.3 CA.3.1 CA.3.2 CA.3.1 CA.4 CA.4.1 CA.4.2 CA.4.3 CA.4.4 CA.5 CA.5.1 CA.5.2 Description and Expectations Objectives Policies Guidance Note Landuse Eligibility

More information

Australian Standard. Automatic fire detection and alarm systems System design, installation, and commissioning AS

Australian Standard. Automatic fire detection and alarm systems System design, installation, and commissioning AS AS 1670 1986 Australian Standard Automatic fire detection and alarm systems System design, installation, and commissioning This Australian standard was prepared by Committee FP/2, Automatic Fire Detection

More information