1 Design of Precast Concrete Grease Interceptors Claude Goguen, PE National Precast Concrete Association 2015 Onsite Wastewater Mega Conference
2 Terminology
3 Terminology
4 Terminology
5 Grease is the Word If you have been in a commercial kitchen, it is obvious why grease interceptors are needed.
6 Why are Grease Interceptors Necessary? Problems Downstream Grease blockages in pipes Issues in treatment field Issues in septic tanks (if they re in series)
7 Configuration Options
8 Configuration Options
9 Factors that influence sizing and design Wastewater Strength Wastewater Constituents Globule Size Temperature Flow Rate Retention Time Pumping Frequency
10 Factors that influence sizing and design Concentration: strength of the influent waste
11 Wastewater Constituents Chemistry: Vegetable oils require longer retention times than animal fats. Emulsified oils require the longest retention times. (Soaps)
12 Globule Size
13 Factors that influence sizing and design Grease globule size has an effect
14 Temperature
15 Coagulation
16 Flow Rates
17 Different Types of flow Difference exists when draining a filled sink versus some sinks that are never filled and the flow is associated with the associated fixture. The potential contribution of the filled sinks is determined through the use of Manning s Equation in conjunction with various plumbing characteristics. Faucet flow contributions are calculated based on known peak discharge limitations for the various fixtures in a kitchen.
18 Different Types of flow
19 Factors that influence sizing and design Retention Time: Amount of time it takes one particle to travel through the system and discharge out. Metcaff & Eddy recommend 30 minutes Stokes Law
20 Key Factors Affecting Grease Removal Retention Time Depends on the size and the influent flow rate Baffles can increase retention time and prevent short-circuiting Size can increase retention time and promote cooling of liquids
21 Baffle or no Baffle?
22 WERF Report
23 WERF Report
24 WERF Report
25 WERF Report
26 WERF Report
27 Proper design goes beyond sizing
28 Proper design goes beyond sizing
29 Proper design goes beyond sizing
30 Factors that influence sizing and design Pumping Frequency: Size shall be sufficient to optimize cleaning and pump-outs. - FOG is 25% of liquid level
31 Interceptor Sizing Sizing Codes EPA GPM WTF? What s the Formula? DFU UPC
32 Interceptor Sizing UPC Appendix H (pre-2006) # Meals * peak. hour flow. rate * retention. time * storage. factor
33 Interceptor Sizing UPC Appendix H (pre-2006) # Meals * peak. hour flow. rate * retention. time * storage. factor Example: Restaurant with 100 meals per peak hour. They have a dishwasher connected to the interceptor. They are open from 6:00am to 10:00pm # meals/peak hr. = 100 meals/hr Flow rate (with dishwasher) = 6 gallons / meal Retention time (with dishwasher) = 2.5 Storage factor (16 hours of operation) = 2 Tank Capacity = 100 x 6 x 2.5 x 2 = 3,000 gallons
34 Interceptor Sizing UPC - ( )
35 Interceptor Sizing UPC - ( ) Example: A restaurant with the following fixtures and equipment: 3 floor drains Mop sink Food prep sink 1 commercial dishwasher (8GPM)
36 Interceptor Sizing UPC - ( ) Example: A restaurant with the following fixtures and equipment: 3 floor drains Mop sink Food prep sink 1 commercial dishwasher
37 Interceptor Sizing UPC - ( ) Example: A restaurant with the following fixtures and equipment: 3 floor drains Mop sink Food prep sink 1 commercial dishwasher
38 Interceptor Sizing UPC - ( ) Example: A restaurant with the following fixtures and equipment: 3 floor drains Mop sink Food prep sink 1 commercial dishwasher
39 Interceptor Sizing UPC - ( ) Example: A restaurant with the following fixtures and equipment: 3 floor drains Mop sink Food prep sink 1 commercial dishwasher
40 Interceptor Sizing UPC - ( ) Example: A restaurant with the following fixtures and equipment: 3 floor drains Mop sink Food prep sink 1 commercial dishwasher
41 Interceptor Sizing UPC - ( ) Example: A restaurant with the following fixtures and equipment: 3 floor drains 3 x 2 DFUs = 6 Mop sink 1 x 3 DFU = 3 Food prep sink 1 x 3 DFU = 3 1 commercial dishwasher = 2 Total DFU s = 14 DFU s
42 Interceptor Sizing UPC - ( ) Example: A restaurant with the following fixtures and equipment: 3 floor drains 3 x 2 DFUs = 6 Mop sink 1 x 3 DFU = 3 Food prep sink 1 x 3 DFU = 3 1 commercial dishwasher = 2 Total DFU s = 14 DFU s 750 Gallon Tank
43 Interceptor Sizing U.S. E.P.A. gal hours. open # seats * storage factor loading factor meal *. * *. 2 where: # seats (assume = 100 seats) # gal / meal = 5 Storage Factor = 1.7 to 2.5 (2.5 for onsite disposal) Hours Open = 8 Loading factor = 0.8 Example Tank Capacity = 100 x 5 x 2.5 x 8/2 x 0.8 = 4,000 gallons
44 Interceptor Sizing
45 WERF Report The results of this study seem to suggest that the development of a universal GI design that can be sized solely on the hydraulic loading and the FOG storage capacity is too simplistic. It is possible that analysis of the FOG influent characteristics will have to be assessed prior to the selection of the most appropriate GI size and design.
46 Proper design goes beyond sizing As a result of the analysis of grease interceptor performance, the researchers concluded: Extending the residence time in a standard GI by a factor of 3 only yielded a 10% improvement in performance, suggesting that FOG loading is only one of the factors affecting performance. FOG droplet size significantly affected FOG removal performance. Decrease in GI separation efficiency will result with the use of detergents and mixing while cleaning in-kitchen FOG wastes. Inlet/out configurations must be designed to distribute the flow. More effective FOG separation was achieved when fluid velocities near the inlet and outlet were kept below m/s. Only include baffle walls with specific inlet/outlet configurations. Design baffle wall to distribute the flow and minimize the occurrence of high local fluid velocities.
47 All Specifications should include.. ASTM C Standard Specification for Precast Concrete Grease Interceptor Tanks o Materials and Manufacture o Structural Design Requirements o Physical Design Requirements o Quality Control o Watertightness Requirements
48 Difference? Septic Tank ASTM C1227 Grease Interceptor ASTM C1613
49 Summary Retention time important factor, but not only factor Smooth slow laminar flow Many sizing formulas in absence of one, use UPC 2003 Appendix H Specify ASTM C1613 Septic Tank is not a Grease Interceptor Work with your precaster to find solutions
50 Additional Information Sources Claude Goguen : cgoguen@precast.org
51 QUESTIONS?
52 Design of Precast Concrete Grease Interceptors Claude Goguen, PE National Precast Concrete Association
GREASE SEPARATION DEVICE SIZING OPTIONS
GREASE SEPARATION DEVICE SIZING OPTIONS Method 1. Evaluation Based upon 20-25 Minute Hydraulic Retention Grease Separation Device Sizing Table Maximum, worst-case hydraulic loading conditions typified
More informationAPPENDIX F: GREASE SEPARATION DEVICE SIZING OPTIONS
APPENDIX F: GREASE SEPARATION DEVICE SIZING OPTIONS 55 Method 1. Evaluation Based upon 20-25 Minute Hydraulic Retention Grease Separation Device Sizing Table Maximum, worst-case hydraulic loading conditions
More informationEngineering Fact Sheet
GREASE INTERCEPTORS Service Alert Sensors Cast Iron Access Hatchway General Information Sewers back up an estimated 400,000 times each year in the United States causing approximately 40,000 municipal sanitary
More information4. TECHNOLOGY AND DESIGN CRITERIA
4. TECHNOLOGY AND DESIGN CRITERIA 12 Current FOG pretreatment technology typically takes the form of smaller, metal, grease-handling devices found in the kitchen area of the facility; or large, in-ground,
More informationGrease Interceptors and Oil Separators
Grease Interceptors and Oil Separators 1) All food service establishments and vehicle maintenance facilities shall have devices installed for separating and retaining grease and oils known as grease interceptors
More informationGrease Interceptors. General For the purpose of this standard, the following terms shall have the meaning indicated in this section.
Building Division 4800 W. 92 nd Avenue Westminster, Colorado 80031 303-658-2075 permits@cityofwestminster.us Grease Interceptors Where Required Every food serving, food preparing, food catering, or meat
More informationKeeping. Fats, Oils, and. Grease. Out of the Sewer
Keeping Fats, Oils, and Grease Out of the Sewer Questions and Answers for Food Service Establishments regarding Fats, Oil, and Grease and Grease Removal Devices City of Paso Robles, Wastewater Division,
More informationI. Best Management Practices (BMPs) to Prevent Blockages in the Sanitary Sewer System
BMP Train kitchen staff and other employees about how they can help ensure BMPs are implemented. Post "No Grease" signs above sinks and on the front of dishwashers. I. Best Management Practices (BMPs)
More informationCHaPTeR 10. TRaPS and INTeRCePTORS. Table 10-1 Horizontal lengths of Trap arms (except for water closets and similar fixtures)*
CHaPTeR 10 TRaPS and INTeRCePTORS 1001.0 Traps Required. 1001.1 Each plumbing fixture, excepting those having integral traps or as permitted in Section 1001.2, shall be separately trapped by an approved
More informationCHAPTER 10 TRAPS AND INTERCEPTORS The vent pipe opening from a soil or waste No more than one (1) approved slip joint
CHAPTER 10 TRAPS AND INTERCEPTORS 1001.0 Traps Required. 1001.1 Each plumbing fixture, excepting those having integral traps or as permitted in Section 1001.2, shall be separately trapped by an approved
More informationCHAPTER 10 TRAPS AND INTERCEPTORS TABLE 10-1 HORIZONTAL LENGTHS OF TRAP ARMS (EXCEPT FOR WATER CLOSETS AND SIMILAR FIXTURES) 1, 2
CHAPTER 10 TRAPS AND INTERCEPTORS < 1001.0 Traps Required. Each plumbing fixture, excepting those having integral traps or as permitted in Section 1001.1, shall be separately trapped by an approved type
More informationCHAPTER 8 APPURTENANCES
CHAPTER 8 APPURTENANCES 8.1 Introduction This chapter discusses several types of equipment used in onsite wastewater treatmenl 'disposal systems-that have 'general application to the components prev ously
More informationWho Needs BIG DIPPER?
Who Needs BIG DIPPER? Here s how An affordable Big Dipper system solves tough free-floating drainwater problems by removing and recovering up to 98.6% of the grease, oils, fats 1 2 and incidental food
More informationCHAPTER 10 TRAPS AND INTERCEPTORS
CAPTER 10 TRAPS AND INTERCEPTORS 1001.0 Traps Required. 1001.1 Each plumbing fixture, excepting those having integral traps or as permitted in Section 1001.2, shall be separately trapped by an approved
More informationBUILDING AND CODES DEPARTMENT 350 Pageant Lane Suite 309 Clarksville, TN 37040
Phone 931-648-5718 BUILDING AND CODES DEPARTMENT 350 Pageant Lane Suite 309 Clarksville, TN 37040 Fax 931-553-5121 Food Service Establishment Fats, Oil and Grease Best Management Practices 1. Introduction
More informationFats, Oils and Grease Program (FOG)
Fats, Oils and Grease Program (FOG) SECTION A GENERAL INFORMATION 1. Facility Name: 2. Facility Street Address: City: State: Zip: Phone Number: Fax Number: 3. Business Mailing Address: (if different from
More informationRESOLUTION Adopted this day of, President of June Lake Public Utility District and its Board of Directors
RESOLUTION 2017-04 RESOLUTION OF THE BOARD OF DIRECTORS OF JUNE LAKE PUBLIC UTILITY DISTRICT ESTABLISHING BEST MANAGEMENT PRACTICES FOR THE DISPOSAL OF FATS OILS AND GREASE Whereas, the June Lake Public
More informationProgram Introduction and Policy 1. Frequently Asked Questions 2. Device Maintenance..3. Best Management Practices...4
Carmel Utilities, in accordance with the National Pretreatment Program set forth by E.P.A. regulations (40 CFR 403), has hereby enacted a program for the controlling of Fats, Oils, and Grease discharges
More informationAPPENDIX J ILLUSTRATIONS
The following figures have been included in the 1994 edition of the Standard Plumbing Code to aid in interpreting this code. The figures are not to be construed as superseding the written text, but merely
More informationInnovative, Compact Design
Innovative, Compact Design Easy, Effective Compliance What in the world is? The Thermaco, Inc. Trapzilla Supercapacity Grease Trap collects free-floating (non-emulsifed) grease & oils contained in kitchen
More informationGREASE REMOVAL DEVICE GUIDELINES FOR PLOT/PLUMBING PLAN DRAWINGS AND INSTALLATION REQUIREMENTS
GREASE REMOVAL DEVCE GUDELNES FOR PLOT/PLUMBNG PLAN DRAWNGS AND NSTALLATON REQUREMENTS The removal of fats, oils, and grease (FOG) from kitchen wastewater is an essential operational requirement for Food
More informationPLEASE DO NOT DISCARD THE ATTACHED DOCUMENT IS NECESSARY FOR THE INSTALLATION OF YOUR GREASE TRAP.
PLEASE DO NOT DISCARD THE ATTACHED DOCUMENT IS NECESSARY FOR THE INSTALLATION OF YOUR GREASE TRAP. GI SERIES GREASE TRAP INSTALLATION GUIDE Overview Atlantic Metalworks GI series grease traps are designed
More informationF.O.G. 2/8/2013. Frequently Asked Questions. Defining Fats, Oils, & Grease (FOG)
F.O.G. Fats, Oils, and Grease by Dan Burke- National Waste Associates 1 Frequently Asked Questions What is FOG? Why is FOG an issue for my business? Is my business required to have a grease removal device?
More informationFat, Oil, and Grease (FOG) Program Frequently Asked Questions (FAQ)
Fat, Oil, and Grease (FOG) Program Frequently Asked Questions (FAQ) Q. Who is San Jacinto River Authority (SJRA)? A. San Jacinto River Authority (SJRA) is one of 10 major river authorities in Texas created
More informationREAD ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter X X X Adopt Entire Chapter as amended (amended sections listed below) X X X X X X X
CALIFORNIA PLUMBING CODE MATRIX ADOPTION TABLE CHAPTER 10 - TRAPS AND INTERCEPTORS (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state agency authority
More informationSpecifying High-Efficiency Water Heaters for Food Service
Specifying High-Efficiency Water Heaters for Food Service May 14 th, 2010 Presented by: Don Fisher Water Heater Selection and Specification Selection Efficiency Economics Myths & Limitations Tank versus
More informationTOWNSHIP OF WEST WINDSOR P.O. BOX 38; 271 CLARKSVILLE ROAD WEST WINDSOR, NJ (609) FAX (609)
TOWNSHIP OF WEST WINDSOR P.O. BOX 38; 271 CLARKSVILLE ROAD WEST WINDSOR, NJ 08550 (609) 936-8400 FAX (609) 799-2136 OPERATIONAL GREASE CONTROL PLAN APPLICATION EXISTING ESTABLISHMENTS Directions: Complete
More informationCombined FOG intercept and treatment system
BIOLOGICAL DRAIN MAINTENANCE SYSTEM Combined FOG intercept and treatment system designed to retain and breakdown Fats, Oils and Grease (FOG) to prevent them from entering the drainage system. The system
More informationSanitary Drainage Systems
11.1 MATERIALS See Section 3.1. Sanitary Drainage Systems 11.2 BUILDING SEWERS AND BUILDING DRAINS 11.2.1 Sewer or Drain in Filled Ground Chapter 11 Building sewers or building drains that are installed
More informationThere are a few factors critical in the operation of a grease interceptor, which are: Design, Sizing, Proper installation and maintenance.
TEL: 773-341-3030 FAX: 773-341-3046 TOLL FREE: 1-800-465-2736 WEBSITE: www.mifab.com Grease Interceptors Description of Operation: There are a few factors critical in the operation of a grease interceptor,
More informationProhibitions on using
Prohibitions on using Chemicals, Enzymes, or Bacteria in Grease Traps and Interceptors CHEMICALS ENZYMES BACTERIA Chemicals: the use of chemicals to clean grease traps or interceptors is strictly prohibited
More informationItem #: 145. SUBMITTER: Guy Wayne Harrison Josam Company RECOMMENDATION: Revise text as follows:
Item #: 145 UPC 2009- - (1005.0 ): SUBMITTER: Guy Wayne Harrison Josam Company RECOMMENDATION: Revise text as follows: 1005.0 Trap Seals. Each fixture trap shall have a water seal of not less than two
More informationCHAPTER 9 VENTS SECTION
CHAPTER 9 VENTS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall govern the materials, design, construction and installation of vent systems. 901.2 Trap seal protection. The plumbing
More informationCHAPTER 10 TRAPS AND INTERCEPTORS
CHAPTER 10 TRAPS AND INTERCEPTORS 1001.0 Traps Required. 1001.1 Each plumbing fixture, excepting those having integral traps or as permitted in Section 1001.2, shall be separately trapped by an approved
More informationHOW THE RIGHT GREASE INTERCEPTOR CAN HELP YOU SAVE SPACE IN A COMMERCIAL KITCHEN
HOW THE RIGHT GREASE INTERCEPTOR CAN HELP YOU SAVE SPACE IN A COMMERCIAL KITCHEN INTRODUCTION: THE UNCONVENTIONAL KITCHEN Many engineers and architects are all too familiar with this scenario: You ve been
More informationGrease Control Device Maintenance Recordkeeping
Grease Control Device Maintenance Recordkeeping All food service establishments are required to keep maintenance records for their grease traps, interceptors, and mechanical grease control devices for
More informationFood Service Plan Review Information
Food Service Plan Review Information New or remodeled food preparation facilities, and those changing ownership, must undergo a plan review process prior to a health permit being issued. The purpose of
More information168 Spotnap Road Charlottesville, VA Tel (434) Fax (434)
Re: Fats, Oils and Grease (FOG) Abatement Program Dear Restaurant/Food Service Facility Manager: The Albemarle County Service Authority (ACSA) prides itself on maintaining the general public health of
More informationProduct Overview. About Us. Grease Traps Generic Types. Extended Capacity Hydromechanical Grease Traps
About Us Product Overview Extended Capacity Hydromechanical Grease Traps Endura XL 75 Models DGT75 598L Light Trafficable Lid DGT75P 598L Pedestrian Lid Industry leading separation efficiency based on
More information2006 Thermaco, Inc. All rights reserved Patented/Patents Pending Specifications subject to change without notice
One to Three Compartment Sink When planning a multiple fixture discharge into a single Big Dipper, establish the size unit required by following the method outlined in the sizing section of this manual.
More informationWatch Water USA Green Chemical Technology
Filtersorb SP3 Installtion, Operation and Maintenance Manual Introduction The Filtersorb SP3 system provides protection from scale formation throughout the plumbing system. The Filtersorb SP3 system can
More informationCommercial food preparation and service
Commercial food preparation and service Released: 1 July 2017 Used waters from business activities such as food preparation and dish washing contain oil/grease and suspended solids at concentrations or
More informationSave Water... Save Energy With Efficient Hot Water Delivery
Steven Winter Associates, Inc. 2017 Save Water... Save Energy With Efficient Hot Water Delivery Presentation Overview Typical Systems in-unit electric or natural gas storage or tank-less heat pump water
More informationSummary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016
Summary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016 Ohio Administrative Code Rule Number OPC Section IPC origin Reason for proposed 4101:3-2-01 Alternate on-site 2015 Added definition
More informationTHE CITY OF CHANDLER BOARD OF ADJUSTMENT WILL MEET FOR A SCHEDULED MEETING MONDAY, APRIL 14, 2014 IN THE CITY HALL OF CHANDLER, TEXAS AT 6:00PM
THE CITY OF CHANDLER BOARD OF ADJUSTMENT WILL MEET FOR A SCHEDULED MEETING MONDAY, APRIL 14, 2014 IN THE CITY HALL OF CHANDLER, TEXAS AT 6:00PM AGENDA A. CALL TO ORDER B. INVOCATION C. ROLL CALL AND ANNOUNCE
More informationFats, Oil, & Grease (F.O.G.) Participant Data South San Luis Obispo County Sanitation District
Fats, Oil, & Grease (F.O.G.) Participant Data South San Luis Obispo County Sanitation District 1. Business Name: Owner: Mailing address: Street City State Zip Owner/Contact Telephone: ( ) 2. Physical address
More informationFATS, OIL AND GREASE (FOG) PROGRAM
FATS, OIL AND GREASE (FOG) PROGRAM LONDON GROVE TOWNSHIP MUNICIPAL AUTHORITY (LGTMA) October 17, 2014 Introductions Karen Crossan, LGTMA Manager Jeff Simpson, LGTMA WWTP Operator Ross Unruh, UTB&F Jerry
More information1 Exam Prep Plumber s Handbook Tabs and Highlights
1 Exam Prep Plumber s Handbook Tabs and Highlights These 1 Exam Prep Tabs are based on the Plumber s Handbook Revised 2006. Each Tabs sheet has five rows of tabs. Start with the first tab at the first
More informationc. Direct or indirect?
~ \ 1.) GENERAL a. Definitions: Chapter B Code References (1) Air-break Comm 81.01 (5) (2) Air-gap, drain system Comm 81.01 (6) (3) Flood level rim Comm 81.01(102) (4) sink Comm 81.01(105) (5) Indirect
More informationMurfreesboro Water Resources Department FOG Management Policy
Murfreesboro Water Resources Department FOG Management Policy Basis The Murfreesboro Water Resources Department Fats, Oils and Grease Management Policy is based on Article III, Chapter 33-36 of the Murfreesboro
More informationFATS, OIL & GREASE (FOG) POLICIES
BOXELDER SANITATION DISTRICT FATS, OIL & GREASE (FOG) POLICIES AND PROCEDURES MANUAL January 1, 2018 Boxelder Sanitation District Industrial Pretreatment Program 3201 E. Mulberry, Unit Q Ft. Collins, Colorado
More informationGuide to Starting a Food Business
Guide to Starting a Food Business Seneca County General Health District Environmental Health Division 71 S. Washington St., Suite 1102 Tiffin, OH 44883 (419) 447-3691 Every new or significantly altered
More informationFOOD ESTABLISHMENT CONSTRUCTION GUIDE Revised December 19, 2011 Reviewed January 10, 2014
FOOD ESTABLISHMENT CONSTRUCTION GUIDE Revised December 19, 2011 Reviewed January 10, 2014 This construction guide is to be used in conjunction with the Oklahoma Food Service Establishment Regulations (OAC
More informationInstallation, Operation and Maintenance Manual
Installation, Operation and Maintenance Manual H2Flow Anti-Scale System Chemical-Free, Salt-Free Scale Prevention Model CH2F-10 Model CH2F-12 Model CH2F-16 Model CH2F-20 Model CH2F-30 Introduction The
More informationA GUIDE TO PASSING THE PLUMBING EXAM
A GUIDE TO PASSING THE PLUMBING EXAM BASED ON THE INTERNATIONAL PLUMBING AND FUEL GAS CODES WRITTEN BY JOHN WHITE REVISED 2014 2007-2014 This manual is the sole property of Energy Marketing Services. No
More informationCOOKING GREASE ITS EFFECT ON OUR WATER INFRASTRUCTURE
COOKING GREASE ITS EFFECT ON OUR WATER INFRASTRUCTURE Sue Allen Environmental Health Specialist Registered Sanitarian EATING OUT IS ON THE RISE! Nearly 4.2 billion pounds of inedible grease produced each
More information2016 Plumbing Supplemental Plan Review List
Building Division 555 Santa Clara Street Vallejo CA 94590 707.648.4374 2016 Plumbing Supplemental Plan Review List POTABLE WATER SYSTEM P1. Specify which fixtures are for private use and which are for
More informationInstallation, Operation and Maintenance Manual
Installation, Operation and Maintenance Manual ScaleStop Residential Systems Chemical Free, Salt Free Scale Prevention NSS-744R NSS-844R NSS-948R NSS-1054R NSS-1252R next filtration technologies inc. P.O.
More informationFood Establishment Guidelines. Food Service Plan Review
Food Service Plan Review Food service plan review in the City of Grand Prairie begins at the Environmental Services Department at the Development Center, 201 NW 2 nd Street in Suite 100. The City of Grand
More informationHot Water System Performance Testing at PG&E s Applied Technology Services: Mimicking a Full-Service Restaurant in the Laboratory
Hot Water System Performance Testing at PG&E s Applied Technology Services: Mimicking a Full-Service Restaurant in the Laboratory Amin Delagah Project Engineer Fisher Nickel, a division of Frontier Energy
More informationMeeting the One-Cup Challenge
42 TECHNICAL SERIES HIGH PERFORMANCE HOT WATER SYSTEMS JANUARY/FEBRUARY 2010 OFFICIAL Meeting the One-Cup Challenge A SERIES ON HIGH PERFORMANCE HOT WATER SYSTEMS PART THREE: CENTRAL CORE PLUMBING About
More informationWastewater. Guidelines for Sizing mscdirect.com. Call MSC today to learn about the latest LittleGiant products.
Wastewater Guidelines for Sizing Features These guidelines cover the steps which need to be taken to accurately select the correct sewage pump and applicable systems to use in sewage ejectors. Work through
More informationFlorida Building Code 5 th Edition (2014) Building. Broward County Edition Loose-leaf Supplement
Board of Rules and Appeals FBC 5 th Edition (2014)- Building - Supplement No. 1 June 30, 2015 Florida Building Code 5 th Edition (2014) Building File removed pages for reference. Broward County Edition
More informationMINIMUM CONSTRUCTION STANDARDS AND SPECIFICATIONS CHECKLIST
Rev: 10/23/08 MINIMUM CONSTRUCTION STANDARDS AND SPECIFICATIONS CHECKLIST The following standards apply to constructing, renovating or converting buildings to use for preparing, processing, storing or
More informationSoftened Water Benefits Study: Energy Savings Detergent Savings. Independent studies demonstrate the link. Executive Summaries
Executive Summaries Softened Water Benefits Study: Energy Savings Detergent Savings Independent studies demonstrate the link /MarketTheResearch/ Introduction The Energy Savings Study (aka The Battelle
More informationPlan reviews are required for child care facilities that engage in diaper changing, meal preparation, and/or obtain drinking water from a well.
Dear Child Care Facility Designer/Engineer/Builder: Plan reviews are required for child care facilities that engage in diaper changing, meal preparation, and/or obtain drinking water from a well. Tri-County
More informationTOWNSHIP OF WEST WINDSOR 271 CLARKSVILLE ROAD, P.O. BOX 38 WEST WINDSOR, NJ (609) FAX (609)
TOWNSHIP OF WEST WINDSOR 271 CLARKSVILLE ROAD, P.O. BOX 38 WEST WINDSOR, NJ 08550 (609) 936-8400 FAX (609) 799-2136 RETAIL FOOD ESTABLISHMENT GREASE CONTROL PLAN APPLICATION Directions - Completed Forms
More informationSTACKS AND STACK VENTS
CHAPTER 9 VENTS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall govern the materials, design, construction and installation of vent systems. 901.2 Trap seal protection. The plumbing
More informationBest Management Practices (BMPs)
Best Management Practices (BMPs) Prevent Blockages in the Sanitary Sewer System Properly Maintain Grease Traps and Interceptors to Prevent Introduction into the Sanitary Sewer System Prevent Fats, Oil,
More informationICP Plumbing Exam. Name: Carefully read each question and then circle the letter of the best answer.
ICP Plumbing Exam Name: Date: Score: Carefully read each question and then circle the letter of the best answer. 1. A 1 inch diameter faucet, where the inside edge of the spout opening is 2.5 inches away
More informationADDITIONAL INFORMATION FOR RETAIL FOOD PREMISES
ADDITIONAL INFORMATION FOR RETAIL FOOD PREMISES INTRODUCTION Wastes like cooking oil, grease and food solids are produced by food outlets and services throughout the Timaru District every day. When this
More informationAPPENDIX P FAT, OIL AND GREASE MANAGEMENT ISSUE A AUGUST 17. Appendix P
APPENDIX P FAT, OIL AND GREASE MANAGEMENT ISSUE A AUGUST 17 Appendix P Fat, Oil & Grease (FOG) Management of Wastewater systems: Specification for Tenant Fit Out Introduction For sites involved in the
More informationAPPENDIX A. A 3.2 Determine the elevation of the highest. A 3.3 Subtract the sum of loss in static pressure
APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM Because of the variable conditions encountered, it is impractical to lay down definite detailed rules of procedure for determining the sizes
More informationKitchen Layouts L Shape Kitchen
Kitchen Layouts L Shape Kitchen The popular L layout provides space for a seating area in the kitchen. This kitchen layout causes longer distances to be travelled because of the tall and/or side cabinets
More informationSanitation: Ware Washers, Water Heaters and the Plumbing of the Future
Food Service Technology Center Sanitation: Ware Washers, Water Heaters and the Plumbing of the Food Service Technology Center 1 Water Heating is a System Business As Usual Hot water systems in restaurants
More informationHow To Size A Big Dipper Unit
Sizing Big Dipper Systems In Food Service Operations How To Size A Big Dipper Unit The purpose of this sizing procedure is to give a specifying engineer a simple method for determining the proper size
More informationTOWN OF BILLERICA DEPARTMENT OF PUBLIC WORKS WASTEWATER DIVISION BILLERICA HEALTH DEPARTMENT
TOWN OF BILLERICA DEPARTMENT OF PUBLIC WORKS WASTEWATER DIVISION BILLERICA HEALTH DEPARTMENT FATS, OILS AND GREASE (FOG) CONTROL PROGRAM GUIDANCE MANUAL MARCH 2014 SECTION TABLE OF CONTENTS PAGE NO. 1.
More informationARTESIAN 220 & 340 Instantaneous Indirect Water Heater By Dunkirk Boilers INSTALLATION AND OPERATING INSTRUCTIONS ENGINEERING MANUAL
ARTESIAN 220 & 340 Instantaneous Indirect Water Heater By Dunkirk Boilers INSTALLATION AND OPERATING INSTRUCTIONS ENGINEERING MANUAL Manufacturer's Warning To reduce the possibility of injury due to scalding,
More informationCHAPTER 31. VENTS Reserved 2003 INTERNATIONAL RESIDENTIAL CODE 425R
CHAPTER 31 VENTS Reserved 2003 INTERNATIONAL RESIDENTIAL CODE 425R This page left intentionally blank. 426R 2003 INTERNATIONAL RESIDENTIAL CODE For SI: PIPE SIZE (inches) TABLE P3107.3 COMMON VENT SIZES
More informationGUIDELINES FOR SIZING WATER HEATERS California Conference of Directors of Environmental Health September, 1995
GUIDELINES FOR SIZING WATER HEATERS California Conference of Directors of Environmental Health September, 1995 I. BACKGROUND A critical factor in preventing foodborne illnesses in a food facility is the
More informationDrain and Vent Systems 6 CE Hours
Drain and Vent Systems 6 CE Hours Wisconsin Contractors Institute N27 W23953 Paul Road, Suite 203 Pewaukee, WI 53072 www.wicontractorsinstitute.com 262-409-4282 What is the purpose of this course? The
More informationScale Stopper Plus Installation & Start-Up Guide
Clean Water Made Easy www.cleanwaterstore.com Scale Stopper Plus Installation & Start-Up Guide Thank you for purchasing a Clean Water System! With proper installation and a little routine maintenance your
More informationADAMS COUNTY HEALTH DEPARTMENT PLAN REVIEW APPLICATION FOR FOOD ESTABLISHMENTS This is not a Food Establishment application. Fees are non refundable
A7 ADAMS COUNTY HEALTH DEPARTMENT 108 W. MAIN, RITZVILLE, WASHINGTON 99169 - TELEPHONE (509) 659-3315 425 E. MAIN, STE. 700, OTHELLO, WASHINGTON 99344 - TELEPHONE (509) 488-2031 ADAMS COUNTY HEALTH DEPARTMENT
More informationNon-Domestic Water Audit Report
A Steak House in Massachusetts INTRODUCTION The Massachusetts Water Resources Authority (MWRA) has developed a program to audit the water use of some of its largest commercial, industrial and institutional
More informationGARLAND HEALTH DEPARTMENT
GARLAND HEALTH DEPARTMENT Construction and Equipment Standards for Food Service Establishments CLASS 1 FOOD SERVICE ESTABLISHMENTS 1720 Commerce St. Garland, TX 75040 Phone: (972) 205-3460 Fax: (972) 205-3505
More informationFlow Reversal in Primary/Secondary Systems by John Siegenthaler, P.E. April 17, 2007
Flow Reversal in Primary/Secondary Systems by John Siegenthaler, P.E. April 17, 2007 When flow reversal occurs, the heat transfer from the secondary circuit is mostly unaffected, as are the other secondary
More informationPLUMBING FIXTURES Reserved
CHAPTER 27 PLUMBING FIXTURES Reserved 2003 INTERNATIONAL RESIDENTIAL CODE 395R This page left intentionally blank. 396R 2003 INTERNATIONAL RESIDENTIAL CODE SECTION P2708 SHOWERS P2708.1 General. Shower
More informationEnergy-Efficiency Options for Residential Water Heating
Energy-Efficiency Options for Residential Water Heating Dave Bohac, PE Director of Research Center for Energy and Environment Duluth Energy Design Conference February, 2015 In accordance with the Department
More informationENERGY MARKETING SERVICES
1 IMPORTANT STUFF This manual has been designed as a supplemental aid for students preparing to take the Plumbing Exam based on the international codes. It is not intended to replace any manuals or material
More informationGREASE INTERCEPTORS. Z1192 GREASE RECOVERY APPLIANCE (GRA) INSTALLATION and OPERATION INSTRUCTIONS
Z1192 GREASE RECOVERY APPLIANCE (GRA) INSTALLATION and OPERATION INSTRUCTIONS Note: Zurn Grease Interceptors with grease recognizing sensors are efficient appliances designed to separate grease from water.
More informationWeb:
P.O Box - 95466, United Arab Emirates Tel: +971 4 2637073, Mobile: +971 55 2191246, +971 52 864 1667 Email: info@sancouae.com, Web: It's about Peace of mind and a job done right, First time, Every time
More informationOwners Guide ScaleSolver Residential System
Owners Guide ScaleSolver Residential System Models SS-5544S - 1 SS-5544E - 1 1/4 www.lifesourcewater.com CA Lic. #787179 - NV Lic. #059578 Table of Contents Our Promise Lifesource Is A Company You Can
More informationSewer System Management Plan - Appendices UC Berkeley Collection System APPENDIX D - RESOURCES. EH&S Fact Sheets
Sewer System Management Plan - Appendices UC Berkeley Collection System APPENDIX D - RESOURCES EH&S Fact Sheets Revised 05/28/14 Fats, Oils and Grease Management UC Berkeley Best Management Practices for
More informationSinks A clog, low water pressure a nonfunctioning sink can practically shut
EXPRESS FACELIFT I CHAPTER 1 I Sinks A clog, low water pressure a nonfunctioning sink can practically shut down a kitchen. It s good to know that minor repairs can get your sink up and running in no time.
More informationCHAPTER 5 Water, Plumbing, and Waste
CHAPTER 5 Water, Plumbing, and Waste Parts 5-1 Water 5-2 Plumbing System 5-3 Mobile Water Tank 5-4 Sewage, Other Liquid Waste, and Rainwater 5-5 Refuse, Recyclables, and Returnables 5-1 Water 5-101 Source
More informationFOOD FACILITY APPLICATION PACKET
FOOD FACILITY APPLICATION PACKET AMADOR COUNTY ENVIRONMENTAL HEALTH, 810 COURT STREET, JACKSON, CA 95642 (209) 223-6439 - www.amadorgov.org - ACEH@amadorgov.org AMADOR COUNTY ENVIRONMENTAL HEALTH FOOD
More informationTHREE RIVERS HEALTH DISTRICT APPLICATION FOR A TEMPORARY FOOD ESTABLISHMENT PERMIT
THREE RIVERS HEALTH DISTRICT APPLICATION FOR A TEMPORARY FOOD ESTABLISHMENT PERMIT Health Department Use Only: Date Application received Amt Received: $ How was fee paid? Cash Check No Credit Card Auth
More informationFats, Oils, & Grease (FOG)
Workshop for Area 7 Fats, Oils, & Grease (FOG) PROPOSED Program and Ordinance Orange County Sanitation District August 3, 2004 What is FOG? Fats from cooking meats Lard, shortening, cooking oils Fryer
More informationCHAPTER VI BUILDING PLUMBING
CHAPTER VI BUILDING PLUMBING 6.1. INTRODUCTION The chapter covers questions related to water demand, distribution and drainage. The basic principles for planning and installing common plumbing systems
More informationOPERATION, INSTALLATION AND MAINTENANCE INSTRUCTIONS SERIES INTERCEPTORS
OPERATION, INSTALLATION AND MAINTENANCE INSTRUCTIONS 5400-5500 SERIES INTERCEPTORS 5401 75 4NH 5500 50 3IPS INSTALLATION Place the Wade interceptor downstream of the drain which will supply the oil laden
More information