1 I&C Upgradation and Modernization at CHASNUPP 1 & 2 Presented By: Waseem Uddin Farooqi PAEC, Pakistan
2 Contents of Presentation Nuclear Power in Pakistan I&C Overview of CHASNUPP-1 & 2 (C-1 & C-2) I&C Upgradation and Modernization at C-1 I&C Modernization at C-2 Conclusion
3 Nuclear Power in Pakistan (1/2) Installed Generation Capacity Oil Gas Hydro Nuclear Others 3.6% 1% 30% 37% 28.4% Total Installed Generation Capacity is MWe
4 Nuclear Power in Pakistan (2/2) S. Name Location Capacity Type Operation Contract No. 1 KANUPP Karachi 137MWe PHWR 1972 CGE 2 CHASHNUPP-1 Chashma 325 MWe PWR Sept CNNC 3 CHASHNUPP-2 Chashma 340 MWe PWR May 2011 CNNC Percentage Distribution 48% 7% 45% KANUPP CHASHNUPP-1 CHASHNUPP-2
5 Major I&C Systems of CHASNUPP-1 & 2 S No. System C-1 & C-2 1. Reactor Protection System Reactor Trip System Engineered Safety Features 2. Nuclear Instrumentation System Conventional, Hardwired, Modular 2/4 trip Logic, 26 Trip Parameters 06 actuation system 8 neutron detectors, 03 instrumentation ranges, Conventional signal processing Modules 3. Process and Control Systems Conventional sensors and transmitters Modular, PID controller (KMx Series), PLC 4. In-Core Instrumentation Flux Monitoring Temperature Monitoring 5. Main Control Room (MCR) Hybrid type 30 locations, 03 moveable chambers, Electromechanical insertion 36 thermocouple 6. Plant Computer System (CPC) Only for monitoring
6 I&C Upgradation and Modernization at C-1 Suppression of False Alarms Addition of Indications and Alarms Revision of Some Alarms Set Point Replacement of Instruments Addition of New Systems
7 Suppression of False Alarms Some alarms in MCR were continuously lit but do not indicate any process abnormality e.g. some alarms of low flow at pumps outlet but those pumps were not running as they were on standby duty. If the standby pumps come into operation with low flow, this abnormality will not be detected Currently, alarm suppression program is underway 48 alarms have been rectified up to RFO-6
8 Addition of Indications and Alarms On the basis of operation experience some alarms and indications are provided in MCR, LCR and CPC for example : Components Cooling Water System surge tank A&B liquid level low alarms are provided in MCR Flap close alarms for Auxiliary Feed Water System diesel driven pumps (A & B)are provided in MCR Low pressure alarm of NaOH tank is provided in MCR High pressure turbine vent valves status indication in MCR Oil & winding temperature of main transformer on CPC Main steam safety valves opening status on CPC Water level indication of Reactor Coolant System (during refueling) on CPC Pressure indication from discharge header of Domestic Water Yard Piping Network System in LCR
9 Revision of Some Alarms Set Point The availability and safety is being improved by revision of some alarms set point for example : High vibration alarm limit (set point) for motor shaft vibration of reactor coolant pumps A&B Alarm and trip set points of turbine differential expansion Set points of main exciter winding temperature of generator Pressure set point of pressure switches KP1 & KP2 of 220 kv GIS air compressors Alarm set point of auxiliary steam header pressure high
10 Replacement of Instruments To overcome the problem of obsolescence and ageing, some instruments have been upgraded for example : Boron Recycle System flow totalizer Low range pressure transmitter and pressure indicator of Hot Water Production and Distribution System Installation of Higher differential pressure range transmitters in Non-Essential Chilled Water Cooling System Liquid level transmitter at raw water purification system Provision of PC based printing system in MCR for online printing of trends & alarm to replace the obsolete printers Installation of new flow sensor and transmitter at 04 Pumps of Circulating Cooling Water Pumping Station System Some paper recorders in MCR have been replaced with paperless digital recorders
11 Addition of New Systems Reactor Internal Vibration Monitoring (IVMS) (Commissioned) Design and Engineering of Online Vibration Monitoring System (In Progress) Loose Part Monitoring System (LPMS) (To be installed in Next RFO)
12 Reactor Internal Vibration Monitoring Requirement of ASME-OM-05 Power range neutron detector signals are used Measures natural frequencies (shell and beam modes) of core barrel motion due to Flow Induced Vibration Core barrel displacements (in mm) Detection of relaxation in core barrel hold-down Spring Detection of possible contact between core barrel and Reactor Pressure Vessel (RPV) Collection of Reactor Noise Signatures during plant lifetime
13 I&C Modernization at C-2 General I&C Modernizations HMI Related Improvements Addition of New Systems
14 General I&C Modernization Communication System on UPS Plant Computer System (CPC) upgraded to state-of-the-art hardware and software Hydrogen Detectors in Battery Room Each Trip Condition Displayed on CPC Illumination level in the control room can be adjusted by the regulating control Recording function has been assigned to CPC
15 HMI Related Improvements (1/4) Layout of MCR In reference plant C-I, there was no walking space for operator directly from console to control board In C-2, walking space is provided for operator between consoles
16 HMI Related Improvements (2/4) Operator Ease In reference plant C-I, console are designed for seated monitoring and standing operation In C-2, dimensions of consoles are changed to be suitable for seated operation as well as seated monitoring
17 HMI Related Improvements (3/4) Elimination of White Alarm Windows In reference plant C-I, there are three types of alarm windows i.e., red, yellow & white Red alarms are of highest priority and white are of lowest Too many alarm windows in MCR cause overcrowding In C-2, white alarm windows are shifted to CPC Some important white alarm windows are converted into yellow alarm windows
18 HMI Related Improvements (4/4) Large Display Panel The incorporation of large display panels (LDP) is to provide visual aid to the operator Large display panel (LDP) provides dynamic overview display of plant variables and alarm information LDP is located at center of the main control room area at a height such that both operators and the shift supervisor can view it while sitting at their respective consoles Every new plant takes the advantage of advance technologies as compare to the reference plant and hence this is a good practice from HMI point of view
19 Addition 0f New Systems (1/3) Safety Systems Bypass and Inoperable Status Indication There is no automatic indication system for the bypass and inoperable state of safety system in the C- 1 design. Only the manual tag-out is applied to solve this problem in the MCR Automatic indication for the bypass and inoperable state of safety system is provided in the C-2 design and integrated in the CPC as per RG1.47 The bypass and in-operation status indication of 24 systems are implemented
20 Addition 0f New Systems (2/3) Loose Part Monitoring System The system is designed to detect a metallic loose part that weight from 0.11 kg to 13.6 kg canalsodetectanimpactwithakineticenergyof0.68 Joules on the inside surface of the reactor coolant system pressure boundary within 0.91 meter of a sensor Employs 16 piezo-electric accelerometers for detection of acoustic bursts (3 RPV Upper, 3 RPV Lower, 4 SG Each, 1 RCP Each) The system is designed to meet the requirements of Regulatory Guide (RG) (1977) and ASME OM S/G. (2000)
21 Addition 0f New Systems (3/3) Hydrogen Concentration Monitoring System To increase the accident detection capability, this system is added It measures the concentration of hydrogen in the containment atmosphere for accident management, to monitor the efficiency of Hydrogen Recombining System and Hydrogen Mixing System Indications and alarms are provided in the main control room
22 Conclusion I&C upgradation and modernization are being carried out at NPPs to overcome the problems of ageing, obsolescence and to take the advantages of technological advancements Some upgradation and modernization are based on the feedback of Operators and Reviewers to timely address the future needs and to improve Human Machine Interface Some upgradation and modernization are performed to comply with the Regulatory Requirements All the efforts done in the plants are to enhance plant safety, reliability and availability
23
Design Characteristics and Classification Issue of the I&C Systems for the JRTR
TRTR 2013 Annual Conference, September 23-26, St. Louis, MO Design Characteristics and Classification Issue of the I&C Systems for the JRTR J. Y. Keum*, J. Y. Park*, H.S. Kim**, and Y. K. Kim* * Republic
More informationReactor Protection Systems for the Replacement Research Reactor, ANSTO
IGORR 9: International Group on Research Reactors, 24-28 March 2003, Sydney, Australia Reactor Protection Systems for the Replacement Research Reactor, ANSTO Abstract The 20-MW Replacement Research Reactor
More informationCriteria I&C and Inherent Characteristics
Criteria 1.2.1 I&C and Inherent Characteristics IAEA INPRO DF-7 Vienna, November 19-22, 2013 JongTae Seo Initial Pre-application Meeting 0 1. INPRO Criteria 1.2.1 2. APR1400 I&C Design Characteristics
More informationBrazil. Current status in NPP I&C and Discussion Topics. 24th Meeting of the IAEA TWG-NPPIC
Brazil Current status in NPP I&C and Discussion Topics 24th Meeting of the IAEA TWG-NPPIC Marcos Candeias Silva Fuad Kassab Junior Ricardo Paulino Marques (Eletronuclear) (University of São Paulo) (University
More informationThe Opal Reactor s I&C Systems
The Opal Reactor s I&C Systems Charles R Morris Ex Group Leader Instrumentation and Control OPAL Engineering From a January 12 2007 IAEA Presentation 1 Topics OPAL General Information Instrumentation Interconnection
More informationTECHNICAL FEATURES OF MMIS DESIGN AND TECHNOLOGIES OF SMART
TECHNICAL MEETING ON INSTRUMENTATION AND CONTROL IN ADVANCED SMALL AND MEDIUM-SIZED REACTORS (SMRS) 21-24 May 2013 TECHNICAL FEATURES OF MMIS DESIGN AND TECHNOLOGIES OF SMART In Soo KOO iskoo@kaeri.re.kr
More informationSperansa 2008: Round table: Nuclear and sustainable development Universitad Politecnica de Valencia \UPV - Passive safety systems -
Universitad Politecnica de Valencia \UPV - Passive safety systems - complete+annex.doc 1 1.1 Definition of Passive Safety Systems...3 2. Passive safety systems for core decay heat removal....4 2.1 Pre-Pressurized
More informationANNEX V. AP600 & AP1000 Westinghouse Electric, USA
ANNEX V. AP600 & AP1000 Westinghouse Electric, USA Reactor System Reactor Type Power (MW th) Passive Safety Systems CORE/PRIMARY: Advanced Passive PWR (AP600) and (AP100) Westinghouse Electric, USA PWR
More informationFin-Fan Control System
IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 02, 2014 ISSN (online): 2321-0613 Fin-Fan Control System Pankaj Shah 1 Jignesh Vaghela 2 1, 2 Student 1, 2 Instrumentation
More informationPost Accident Monitoring in PFBR Safety in Nuclear Power Plant
Engineering Management Research; Vol. 3, No. 2; 2014 ISSN 1927-7318 E-ISSN 1927-7326 Published by Canadian Center of Science and Education Post Accident Monitoring in PFBR Safety in Nuclear Power Plant
More informationChapter 11. Design of Other BOP
Nuclear Systems Design Chapter 11. Design of Other BOP Prof. Hee Cheon NO 11.1 Condenser Design 11.1.1 Consider Performance Requirements Accepting heat rejected by steam cycle as final heat sink Maintaining
More informationAcoustic Resonance in Nuclear Boiling Water Reactors
Acoustic Resonance in Nuclear Boiling Water Reactors Thomas G. Scarbrough Division of Engineering Office of New Reactors U.S. Nuclear Regulatory Commission Pennsylvania State University Center for Acoustics
More informationDevelopment of Post-Accident Monitoring System for Severe Accidents
Development of Post-Accident Monitoring System for Severe Accidents Chang-Hwoi Kim a, Sup Hur b, Kwang-Sub Son c, and Tong-Il Jang d a b c d Abstract: To cope with a severe accident such as Fukushima Nuclear
More informationSteam and Power Conversion System
9 Chapter Major Balance-of-Plant Features It is difficult to completely standardize the plant design beyond the nuclear island. In addition to utility preferences in the steam and power conversion system,
More informationNumerical Standards Listing
ISA-RP2.1-1978 - Manometer Tables Numerical Standards Listing ANSI/ISA-5.1-1984 (R1992) - Instrumentation Symbols and Identification ANSI/ISA-5.2-1976 (R1992) - Binary Logic Diagrams for Process Operations
More informationAppendix B3 System/Component Cause Codes
Appendix B3 System/Component Cause Codes NUCLEAR UNITS INDEX TO SYSTEM/COMPONENT CAUSE CODES (Unit Codes 200-299) Cause Code NUCLEAR REACTOR Ranges Page No. Core/Fuel 2010-2090 B-NU-3 Control Rods and
More informationNumerical Standards Listing
ISA-RP2.1-1978 - Manometer Tables Numerical Standards Listing ISA-5.1-1984 (R1992) - Instrumentation Symbols and Identification (Formerly ANSI/ISA-5.1-1984 [R1992]) ISA-5.2-1976 (R1992) - Binary Logic
More informationE-16 Main Engine Remote Control System
Guideline No.E-16 (201510) E-16 Main Engine Remote Control System Issued date: 20 October, 2015 China Classification Society Foreword This Guide is a part of CCS Rules, which contains technical requirements,
More informationAn Instrumentation and Control for Loop Test
An Instrumentation and Control for Loop Test 21-24 Aug. 2012 S.H. Ahn, J.T. Hong, C.Y. Joung, S.J. Park Neutron Utilization Technology Division 0 Contents 1 Introduction Click to of add HANARO Title 2
More informationAP1000 Advanced Control Room
AP1000 Advanced Control Room Daryl Harmon Westinghouse Electric Co. April 18, 2006 AP1000 Advanced Control Room Presentation Outline Background Operations and Control Centers Human-machine machine Interface
More informationTetra Pak Pasteurizer D Efficient pasteurization for dairy applications
Efficient pasteurization for dairy applications Application Tetra Pak Pasteurizer for dairy applications is designed for continuous processing and pasteurization of market milk, cheese milk, yoghurt milk,
More informationANNEX A-1 GEOTHERMAL UNITS INDEX TO SYSTEM/COMPONENT CAUSE CODES BOILER BALANCE OF PLANT STEAM TURBINE GENERATOR MISCELLANEOUS - GEOTHERMAL EXTERNAL
ANNEX A-1 GEOTHERMAL UNITS INDEX TO SYSTEM/COMPONENT CAUSE CODES Boiler Piping System 0500-0620 Condensing System 3110-3199 Circulating Water Systems 3210-3285 Waste Water (zero discharge) 3290-3299 Condensate
More informationJames S. McMillen, P.E. Perkins Engineering Consultants, Inc., Arlington, Texas. May 25, 2012
James S. McMillen, P.E. Perkins Engineering Consultants, Inc., Arlington, Texas May 25, 2012 Why are we here? Project Background Blower Technology Owner s Perspective System Integration Wrap Up HST Blowers
More informationNumerical Standards Listing
Numerical Standards Listing ISA-RP2.1-1978 - Manometer Tables ISA-5.1-1984 (R1992) - Instrumentation Symbols and Identification (Formerly ANSI/ISA-5.1-1984 [R1992]) ISA-5.2-1976 (R1992) - Binary Logic
More informationPlant Data of Fukushima Daiichi Nuclear Power Station at the time of the Tohoku-Chihou-Taiheiyou-Oki Earthquake. May 16 th, 2011
Plant Data of Fukushima Daiichi Nuclear Power Station at the time of the Tohoku-Chihou-Taiheiyou-Oki Earthquake May 16 th, 2011 Tokyo Electric Power Company Disclaimer This English translation is only
More informationTable of Contents PART I: The History and Current Status of the Industrial HMI PART II: Fundamentals of HMI Design and Best Practices
Table of Contents PART I: The History and Current Status of the Industrial HMI We begin with the origin and evolution of the industrial HMI. The positive and negative issues posed by the introduction of
More informationEffective Alarm Management for Dynamic and Vessel Control Systems
DYNAMIC POSITIONING CONFERENCE October 12-13, 2010 OPERATIONS SESSION Effective Alarm Management for Dynamic and Vessel Control Systems By Steve Savoy Ensco Offshore Company 1. Introduction Marine control
More informationAppendix B9 Geothermal Unit Cause Codes
Appendix B9 Geothermal Unit Cause Codes GEOTHERMAL UNITS INDEX TO SYSTEM/COMPONENT CAUSE CODES (Unit Codes 800 899) Cause Code BOILER Ranges Page No. Boiler Piping System 0500-0620 B-GE-2 BALANCE OF PLANT
More informationDESIGN PHILOSOPHY FOR FIRE ALARM & DETECTION SYSTEM
DESIGN PHILOSOPHY FOR FIRE ALARM & DETECTION SYSTEM Page 1 of 5 CONTENT 1.0 Content 2-2 2.0 Introduction 3-3 3.0 Intent 3-3 4.0 Scope of Work 3-3 5.0 System Component overview 4-4 6.0 Operation Philosophy
More informationPlant Performance 2017 User Symposium
Plant Performance 2017 User Symposium Purdue University Reactor Protection and Control System 1 February 6, 2017 2014 Curtiss-Wright Presenters Clive Townsend (Purdue University) PUR-1 Reactor Supervisor
More information2x58 MW Coal Fired Power Plant at Mauritius
2x58 MW Coal Fired Power Plant at Mauritius The coal-fired power plant produces electricity by the burning of coal and air in a Circulating Fluidized Bed Combustion Boiler (CFBC), where it heats water
More informationSection UV DISINFECTION SYSTEM Greater Vernon Water Page 1 of 18 TABLE OF CONTENTS
Greater Vernon Water Page 1 of 18 TABLE OF CONTENTS 1. Introduction... 2 1.1 Process Overview... 2 1.2 Functionality of Equipment... 3 2. Controls... 8 2.1 Vendor Supplied PLC... 8 2.2 Remote-Auto... 9
More informationSoftware Failure Mode and Effects Analysis of Concept Phase for Radiation Monitoring System Digital Replacement
PSAM 2013 Topical Conference in Tokyo GS-III : PSA Applications and Software Reliability (#1079) Software Failure Mode and Effects Analysis of Concept Phase for Radiation Monitoring System Digital Replacement
More informationMST sterilizer overview
MST sterilizer overview MST medical steam sterilizers for 1 to 18 sterilization units 2 B-SAG July 2009 VEEX/MBE Medical steam sterilizers MST-H MST-H series with horizontal sliding doors Usable chamber
More informationcussons Refrigeration Assembly Range TECHNOLOGY REFRIGERATION AND AIR CONDITIONING CUSSONS TECHNOLOGY LABORATORY RECOMMENDATION
REFRIGERATION AND AIR CONDITIONING CUSSONS LABORATORY RECOMMENDATION Cussons Refrigeration laboratories are offered to provide teaching to a range of different skill levels. In all the laboratories teaching
More informationTitle Page. Report Title: Downhole Power Generation and Wireless Communications. for Intelligent Completions Applications
Title Page Report Title: Downhole Power Generation and Wireless Communications for Intelligent Completions Applications Type of Report: Quarterly Progress Report Project Report Period: Start Date April
More informationCELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL
Operation Manual Celltrol II Bioreactor Control System Page 1 of 33 Table of Contents 1) Introduction... 3 1.1) Scope of Document... 3 1.2) Control System Overview... 3 1.3) Introduction to Celltrol II...
More informationCONTROL SYSTEMS Combustion Control Burner Management Control Balance of Plant Equipment Control Supervisory Control and Data Acquisition
CONTROL SYSTEMS Combustion Control Burner Management Control Balance of Plant Equipment Control Supervisory Control and Data Acquisition CombustionPac LT MasterPac LT CombustionPac MasterPac ScadaPac CONTROL
More informationPage 1 of Relevant Provincial Jurisdictional legislation.
Page 1 of 15 1. Act, Regulations and Codes (6.7%): To locate information relating to the staffing, operation, maintenance, inspection, and testing of the refrigeration plant and its equipment using reference
More informationLata Mishra Bhabha Atomic Research Centre, INDIA
Lata Mishra Bhabha Atomic Research Centre, INDIA Outline of presentation Legal & Regulatory provisions / requirements Safety criteria & Safety objectives PIE s Safety & Seismic categorization Safety provisions
More informationLEAKAGE MONITORING OF SEAL PLUG FOR INDIAN PRESSURIZED HEAVY WATER REACTOR BY PSYCHOMETRICS ANALYSIS METHOD
Proceedings of the National Seminar & Exhibition on Non-Destructive Evaluation NDE 2011, December 8-10, 2011 LEAKAGE MONITORING OF SEAL PLUG FOR INDIAN PRESSURIZED HEAVY WATER REACTOR BY PSYCHOMETRICS
More informationSafety. Reliability. Experience.
Safety. Reliability. Experience. Instrumentation and Control Systems Class 1E Safety Balance of Plant Sensors and Transmitters System Upgrade Solutions Obsolescence Support Nuclear Quality Assurance (NQA)
More informationEXCELLENCE in Solutions Products Service
EXCELLENCE in Solutions Products Service Weed Instrument A World leader in Nuclear Qualified Instrumentation Weed Instrument has been supplying nuclear qualified temperature and pressure measurement instrumentation
More informationBoiler drum level controller using Microcontroller
ISSN:2348-2079 Volume-6 Issue-1 International Journal of Intellectual Advancements and Research in Engineering Computations Boiler drum level controller using Microcontroller E.K.Arulkarthick 1,M.Santhosh
More informationChapter 1. Introduction
1.1 Background of the Proposed Research The measurement of temperature has been playing a critical role in various technical areas from civilian to military applications. According to all recent major
More informationFIRE PROBABILISTIC SAFETY ASSESSMENT FOR KUDANKULAM NPP IN INDIA. G.Tokmachev. Atomenergoproekt, Bakuninskaya 7, Moscow, Russia
In: Proceedings of the 3rd International Conference on Reliability, Safety and Hazards ICRESH-05, Mumbai, India, December 1-3, 2005. "Advances in Risk-Informed Technology", Narosa Publishing House, 2006,
More informationFUNCTIONAL DESIGN SPECIFICATION
Issue Date: Issued To: Revision: FUNCTIONAL DESIGN SPECIFICATION Specification Number: SP-XXXX Company Name Signature Date Issued By: Manutec Ltd. Approved By: Approved By: Approved By: Approved By: Authorised
More informationDocument Code: 1 (13) Issuing date: Status:
Document Code: 1 (13) Project : MULTI FUEL CFB BOILER SIMULATOR Author: Approved: Language: JJA Document title: SYSTEM DESCRIPTION REHEAT STEAM SYSTEM Submitted for: Customer reference: Other information:
More informationFUNCTIONAL SAFETY IN FIRE PROTECTION SYSTEM E-BOOK
FUNCTIONAL SAFETY IN FIRE PROTECTION SYSTEM E-BOOK USEFUL TERMINOLOGY BASIC PROCESS CONTROL SYSTEM (BPCS) System which responds to input signals from the process, its associated equipment, other programmable
More informationIE Code IE Competency Title Credit OAC Ref.
Compulsory Workplace Competency Standards Level Four IE Code IE Competency Title Credit OAC Ref. IE119-4WC Design and draw electrical and electronic drawings including schematics, 4 F5 maintain documentation
More informationTraining Fees 4,000 US$ per participant for Public Training includes Materials/Handouts, tea/coffee breaks, refreshments & Buffet Lunch.
Training Title ADVANCED GC PROCESS Training Duration 5 days Training Venue and Dates Advanced GC Process 5 17 21 February, 2019 $4,000 Dubai, UAE Trainings will be conducted in any of the 5 star hotels.
More informationOverview of FRAP-K1 And Status of Major Modifications
Overview of FRAP-K1 And Status of Major Modifications GOOD PRACTICES IN OUTAGE MANAGEMENT AT KANUPP Penned By: Shahid Mahmood Malik Pakistan Atomic Energy Commission PAEC operates one CANDU & two PWR units.
More informationOPEN SPRINKLER SYSTEM
OPEN SPRINKLER SYSTEM Introduction Competence and innovation driven by consistent market development and customer requirements have shaped the successful development of the SHIELD Brand. The extensive
More informationCase Study: Preventing Reactor Feed-water 1X Vibration by the Addition of Axial Clearance in the Rotating Assembly
Case Study: Preventing Reactor Feed-water 1X Vibration by the Addition of Axial Clearance in the Rotating Assembly Joseph A. Silvaggio, Jr. Fellow Engineer Pump Projects and Engineering CASE STUDY PRESENTATION
More informationEach burner shall be equipped with a Micro-Processor Based Burner Management Flame Safeguard and Parallel Positioning Control System.
Product Guide Specification Nexus Integrated Burner Control System 1. General 1.1 Overview Each burner shall be equipped with a Micro-Processor Based Burner Management Flame Safeguard and Parallel Positioning
More informationDiagnostics with fieldbus
2002 Emerson Process Management. All rights reserved. View this and other courses online at www.plantwebuniversity.com. Fieldbus 105 Diagnostics with fieldbus Overview More than device maintenance Equipment
More informationNovember 11, City of Sparks 215 S. 21 st St. Sparks, NV
November 11, 2014 City of Sparks 215 S. 21 st St. Sparks, NV 89432-0857 Attn: Brian Cason Re: Sparks City Hall HVAC Upgrade Project-Alerton Direct Digital HVAC Control System to Match Existing City of
More informationSubstation Monitoring System
Substation Monitoring System SF6 Gas Density Monitoring System Description Introduction As a result of recent European legislation on the control of greenhouse gasses, utilities and manufacturers alike
More informationImproved Dryer Control
Improved Dryer Control Kenneth C. Hill President Kadant Johnson Systems Division David Vijh Senior Process Control Engineer Technical White Paper Series EXECUTIVE SUMMARY Significant improvements in dryer
More informationFire Risks of Loviisa NPP During Shutdown States
Fire Risks of Loviisa NPP During Shutdown States Sami Sirén a*, Ilkka Paavola a, Kalle Jänkälä a a Fortum Power And Heat Oy, Espoo, Finland Abstract: Fire PRA for all 15 shutdown states of Loviisa NPP
More informationA660 Air Conditioning Laboratory Unit
A660 Air Conditioning Laboratory Unit Figure 1: A660 Base Unit shown with all options fitted High accuracy wet and dry bulb sensors before and after each process to determine air condition. All processes
More informationProcess Control Systems Engineering
Process Control Systems Engineering Supply Infrastructure from A to Z von Leon Urbas 1. Auflage Process Control Systems Engineering Urbas schnell und portofrei erhältlich bei beck-shop.de DIE FACHBUCHHANDLUNG
More informationInternational Reactor Bulletin 1100 Corporation. Standard and Custom Reactors for the Chemical Process Industries
International Reactor Bulletin 1100 Corporation Standard and Custom Reactors for the Chemical Process Industries 2 International Reactor Corporation 521 Kiser Street Dayton, Ohio 45404-1641 Phone: 937-224-4444
More informationFrequently asked questions: Intelligent Transmitter Series
Frequently asked questions: Intelligent Transmitter Series The Wilcoxon family of Intelligent Transmitters, relay alarms, and communication modules can be used to implement low-cost online vibration monitoring
More informationVIBstudio is an intelligent platform for online condition monitoring, failure protection and vibration-based diagnostics of machinery.
VIBstudio VIBRATION MONITORING SYSTEMS VIBstudio is an intelligent platform for online condition monitoring, failure protection and vibration-based diagnostics of machinery. The platform allows to: reduce
More informationMPI Providing challenging ultrasonic solutions
Pipe-Clamp Technology High Volumetric Power Density (50 1000 W/dm 3 ) MPI offers custom Pipe-Clamp solutions for liquid processing applications where it is important to deliver uniform and homogenous ultrasonic
More informationCold Weather Preparedness Plant Winterization Lessons Learned & Best Practices
Cold Weather Preparedness Plant Winterization Lessons Learned & Best Practices Cold Weather Preparedness RF Criteria For Plant Visits: Generating facilities that experienced repeated freezing or cold weather
More informationAP1000 European 11. Radioactive Waste Management Design Control Document
11.5 Radiation Monitoring The radiation monitoring system (RMS) provides plant effluent monitoring, process fluid monitoring, airborne monitoring, and continuous indication of the radiation environment
More informationDesign & Control of an Elevator Control System using PLC
Design & Control of an Elevator Control System using PLC Prof. Omkar M. Shete 1, Ms. Amrita A. Vitekar 2, Ms. Ashwini N. Patil 3 Assistant Professor, Electrical Engineering Department, NBN Sinhgad School
More informationTasman Sea Control System
Tasman Sea Control System Operations Manual (Base System) PLC Firmware Version: 2.03 HMI Firmware Version: 1.22 Control System Operations Manual AGE Page 1 of 112 Document Revision: Version Author Date
More informationMechanical Heat Pump R515
P.A.Hilton Ltd Mechanical Heat Pump R515 Above: R515 shown fitted with standard wattmeter Stabilises in minutes allowing many tests to be conducted in a typical laboratory period. Allows a complete refrigerant
More informationImproved safety system in a nitric acid plant
NITR IC ACI D ALAR ARM AND SAFE FETY SYSTEM Improved safety system in a nitric acid plant The existing alarm and safety system in a nitric acid plant in Croatia was replaced by a new microprocessor-based
More informationHVAC Products. SAPHIR AirGo OEM Air Handling Unit Concept
s HVAC Products OEM Air Handling Unit Concept Control solutions otal solution competence Application know-how and flexibility Access to future-oriented technologies State-of-the-art and open communication
More informationStavros Chrysanthou Madrid DynAMo Alarm Management Secrets to unlocking complete Operational Integrity
Stavros Chrysanthou Madrid 2018 DynAMo Alarm Management Secrets to unlocking complete Operational Integrity Defining Operational Integrity 1 To secure a process plants integrity is to reduce the risk to
More informationComputer-based Alarm Processing and Presentation Methods in Nuclear Power Plants
Computer-based Alarm Processing and Presentation Methods in Nuclear Power Plants Jung-Woon Lee, Jung-Taek Kim, Jae-Chang Park, In-Koo Hwang, and Sung-Pil Lyu Abstract Computerized alarm systems have been
More informationPulse Firing Doubles Capacity and Cuts Fuel Costs
Honeywell Combustion Safety 11699 Brookpark Road Cleveland, Ohio 44130 www.combustionsafety.com Pulse Firing Doubles Capacity and Cuts Fuel Costs Why Pulse Fire? Many industrial manufacturing leaders are
More informationPROCESS CONTROL COURSES
PROCESS CONTROL COURSES To be a world class industrial training provider in Saudi Arabia. To provide world class industrial technical training to prepare a skilled and competent workforce for the hydrocarbon,
More informationFUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY CHAPTER I: AUXILIARY SYSTEMS 2. COMPONENT COOLING SYSTEM FOR THE NUCLEAR ISLAND (RRI [CCWS])
PAGE : 1/ 17 2. COMPONENT COOLING SYSTEM FOR THE NUCLEAR ISLAND (RRI [CCWS]) 2.0. SAFETY REQUIREMENTS 2.0.1. Safety functions The RRI [CCWS] system contribution to the three fundamental safety functions
More informationIntelligent addressable fire alarm control panel
Intelligent addressable fire alarm control panel Input current consumption: Panel rating: Batteries: Networking and Interfaces Panel to panel communication: Number of panels: Interface port: System capacity
More informationNFPA 85 COMPLIANCES OF BMS: A CASE STUDY OF BOILER CONTROL AT SBM OFFSHORE MALAYSIA COMPANY 1. AHMED ABOUELRISH 2 Universiti Teknologi Petronas
Journal of Contemporary Issues in Business Research ISSN 2305-8277 (Online), 2013, Vol. 2, No. 4, 109-123. Copyright of the Academic Journals JCIBR All rights reserved. NFPA 85 COMPLIANCES OF BMS: A CASE
More informationBORS - Bilge Oil Removal Systems
BORS - Bilge Oil Removal Systems MEPC 107 (49) Series OWS Specifications (at US Coast Guard 5 ppm Standard) BORS Model BORS-2.2T BORS-5T BORS-11T BORS-25T BORS-45T Height in/mm 48 / 1219.2 48 / 1219.2
More informationRVL471 Heating and Domestic Hot Water Controller Basic Documentation
RVL471 Heating and Domestic Hot Water Controller Basic Documentation Edition: 2.2 Controller series: C CE1P2524E 23.10.2002 Siemens Building Technologies HVAC Products 2/118 HVAC Products 23.10.2002 Contents
More informationMicroTech Series 200 Centrifugal Chiller
Protocol Data Information Packet Version 2.2 Group: Controls Date: March 1999 MicroTech Series 200 Centrifugal Chiller Data Communications Packet for Protocol 2002 McQuay International Revision History
More informationBP Alaska GC-1. Design Review Project. January 2003
BP Alaska GC-1 Design Review Project January 2003 January 03 _03 January BP Alaska GC-1 Design Review Project I. Statement of requirement The objective of this report is to review the current design drawings
More informationInsert Photo Here Bos Howard Johns Manville
What can TWO GUYS AND A TRUCK" do with PlantPAx? Insert Photo Here Bos Howard Johns Manville Rockwell Automation Process Solutions User Group (PSUG) November 14-15, 2011 Chicago, IL McCormick Place West
More informationUniGas Portable, Flue Gas Analysis Advanced Combustion Flue Gas Analyser
Portable, Flue Gas Analysis Advanced Combustion Flue Gas Analyser >10h Operation with Li-Ion Battery Pack Smart Autozero without Removal the Probe CO Dilution up to 10% Stores up to 250 Complete Analysis
More informationDevelopment of a measurement and control system for a 10 K refrigerator based on Siemens PLC S7-300
Development of a measurement and control system for a 0 kw@0 K refrigerator based on Siemens PLC S7-300 J Li,, L Q Liu, T Liu 3, X D Xu, B Dong, W H Lu, W Pan, J H Wu and L Y Xiong Key Laboratory of Cryogenics,
More informationConventional Fire Alarm Systems. ACCLAIM SERIES 10 Conventional Fire Alarm System ACCLAIM SERIES 10.
FIRE DETECTION : FIRE SUPPRESSION EMERGENCY VOICE COMMUNICATIONS SYSTEM INTEGRATION ACCLAIM SERIES 10 s Building the system you need ACCLAIM SERIES 10 Fire Alarm Panel provides many flexible choices from
More informationTurbomachinery Control on the Honeywell Experion PKS Platform
Turbomachinery Control on the Honeywell Experion PKS Platform Boris Pusin Statistics & Control, Inc. Education: 2012 Honeywell Users Group Bio BS and MS degrees in Engineering with emphasis on Steam and
More informationECOPlus SERIES OF HIGH-PRESSURE METERING MACHINES
ECOPlus SEIES OF HIGH-PESSUE METEING MACHINES The OMS ECOPlus series of high-pressure metering units provides the ideal solution for every PU application. eliability, ease of operation and attractive price-performance
More informationReactor-Boiler and Auxiliaries - Course 433 BOILER STEAM AND WATER SYSTEMS
Lesson 433.60-1 Reactor-Boiler and Auxiliaries - Course 433 BOILER STEAM AND WATER SYSTEMS It was noted in an earlier lesson, that the reactor is a source of heat, and serves the purpose of a "furnace"
More informationConsultant Specification AGILE Wireless Fire Detection System
Contents Scope of Work... 2 The EN54 Part 2 & 4 Fire System... 2 Standards... 2 Wireless Intelligent Photoelectric Smoke Detector Specification... 4 Wireless Intelligent Thermal Heat Detector Specification...
More informationThe Next Generation Machine Protection System
ST100 SafeMax PROTECTION SYSTEM ST100 SafeMax The Next Generation Machine Protection System Welcome to the new world of turbine protection, where speed, torque, acceleration, creep, can now be combined
More informationKNX module for smoke alarm devices Dual/VdS and Q-Label (Order no )
Product definition KNX module for smoke alarm devices Dual/VdS and Q-Label (Order no 2343 00) Art. no 2343 00 Page 1 of 22 Product definition Table of contents 1 Product definition... 3 1.1 Product catalogue...
More informationDi-440 The Modular Analyser
Di-440 The Modular Analyser Instrument Concept Single tool for a range of service, maintenance and inspection applications: Condition assessment tool highlights state of machinery today NOT for Predictive
More information2017 FSRUG Thermal Performance Feedwater Heater Troubleshooting FSRUG FWH Troubleshooting 1
2017 FSRUG Thermal Performance Feedwater Heater Troubleshooting 2017 FSRUG FWH Troubleshooting 1 Feedwater Heater Troubleshooting General Discussion on the process Example walkthrough 2017 FSRUG FWH Troubleshooting
More informationCOMPANY PROFILE. Design, Development & Installation of Electrical & Automatic Control Systems
COMPANY PROFILE Design, Development & Installation of Electrical & Automatic Control Systems MSB/ESB Main & Emergency Switchboards PMS Power Management Systems Engine Room Alarm Monitoring Systems Engine
More informationHEAT GENERATION 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. B. Section HVAC Basic Materials and Methods
230520 HEAT GENERATION Cornell s Design and Construction Standards provide mandatory design constraints and acceptable or required products for all construction at Cornell University. These standards are
More informationALARMING NEWS FROM INVENSYS PROCESS SYSTEMS, INC.
ALARMING NEWS FROM INVENSYS PROCESS SYSTEMS, INC. The Foxboro I/A Series and the newly developed and highly versatile I/A Series System Message Manager working in combination to meet all of your plant
More informationPetrolchimico. Alimentare. Milano, 29 novembre 2012!
Petrolchimico Alimentare Milano, 29 novembre 2012! SSE - Sirio Sistemi Elettronici Company Profile Niccolò Paoli Business Development Facts Year of Establishment : 1984 Share Capital, fully paid-up : 1.766.666
More information