1 SION Withdrawable module with vacuum circuit-breaker 3AE and installation accessories kv, ka kv, 40 ka 24 kv, ka OPERATING INSTRUCTIONS Siemens AG All rights reserved. Order no.: A Order from: E D MV C MF115 Berlin AG en
2 For your safety Warning and safety notices serve to enable you to avoid hazards and subsequent damage and are marked as follows: DANGER indicates, within the scope of these instructions and the warning notices on the SION withdrawable module and the installation accessories themselves that death, severe personal injury or substantial property damage will result if proper precautions are not taken. WARNING indicates, within the scope of these instructions and the warning notices on the SION withdrawable module and the installation accessories themselves that death, severe personal injury or substantial property damage can result if proper precautions are not taken. CAUTION indicates, within the scope of these instructions and the warning notices on the SION withdrawable module and the installation accessories themselves that slight personal injury or property damage can result if proper precautions are not taken. Note indicates, within the scope of these instructions and the warning notices on the SION withdrawable module and the installation accessories themselves that the circuit-breaker or an object can be damaged if the relevant notices are not complied with. Qualified personnel For the purpose of these operating instructions or warning notices on the withdrawable module and the SION vacuum circuit-breaker, a "qualified person" is one who is familiar with the installation, construction, commissioning, maintenance and operation of the product and who has e.g. the following qualifications: Is trained and authorized to energize, de-energize, clear, ground and tag circuits and equipment in accordance with established safety practices. Is trained in the proper care and use of protective equipment in accordance with established safety practices. Is trained in rendering first aid Note Product liability claims are valid only if the spare parts purchased have been replaced by Siemens personnel trained and certified to do so A
3 Contents Transport/storage/packing...3 Transport...3 Crane transport...5 Storage...6 Description...7 Structure...7 Scope of delivery...8 Versions - technical data...8 Rating plate...8 Installation...9 Preparations...9 Fitting the withdrawable frame...10 Operation...13 Using the SION vacuum circuit-breaker with a withdrawable section in the withdrawable frame...13 Installation accessories...15 Assembling installation accessories...15 Withdrawable frame with earthing switch...19 Maintenance...25 Maintenance...25 Accessories and spare parts Manufacturer's product liability Service...25 Disposal...26 Index A 1
4 Blank page A
5 Transport/storage/packing Transport/storage/packing WARNING Risk of injury! Pay attention to the weight! Use means of transport suited to the requirements and load carrying capacity! Suspend the SION vacuum circuit-breaker in the withdrawable frame from a crane only in the inserted state! Transport Unpacking Open the packing from above. Detach the packing at the sides Cut through the adhesive tape holding the foil covering in place and carefully remove the foil Undo the hexagon screws (10 mm) on the withdrawable frame, as shown in Fig. 1 Use the fitted transport beam to suspend the withdrawable module in the withdrawable frame from a crane. Fig. 1 Unpacking the withdrawable module A 3
6 Transport/storage/packing CAUTION Damage! The SION withdrawable module with vacuum circuit-breaker and earthing switch can tilt over after removal from the packing and must be supported. Open the packing from above Remove cover board secured with clips in the upward direction Remove cross struts secured with clips Remove side walls secured with clips Fig. 2 Unpacking the SION withdrawable module with earthing switch Cut through the adhesive tape holding the foil covering in place and carefully remove the foil Undo the wood screws, as shown in Fig. 3 Undo the hexagon screws (10 mm) from the brackets, as shown in Fig. 3, and remove the brackets Use suitable hoisting gear to lift the SION withdrawable module with earthing switch out of the packing. Fig. 3 Unpacking the SION withdrawable module with earthing switch A
7 Transport/storage/packing Crane transport WARNING Risk of injury! Pay attention to the weight! Use means of transport suited to the requirements and load carrying capacity! Suspend the SION vacuum circuit-breaker in the withdrawable frame from a crane only in the inserted state! For crane transport, especially of heavy circuitbreaker versions, we recommend use of a workshop crane, for example the Compac CC055 or CC055 junior from the following company: KSM ServiceTechnik GmbH & Co. KG Bosch contract wholesaler Robert-Koch-Strasse Winsen / Luhe Germany Max. Ø 19 mm, min. 18 mm hook opening Max. weight of the withdrawable module with the SION vacuum circuit-breaker: 230 kg! Fig. 4 Transporting the withdrawable module! Max. Ø 19 mm, min. 18 mm hook opening Max. weight of the withdrawable module with the SION vacuum circuit-breaker and earthing switch: 330 kg! Fig. 5 Transporting the withdrawable module with earthing switch A 5
8 Transport/storage/packing Storage CAUTION Damage! If the packing has been opened, make sure during storage that the SION vacuum circuit-breaker is in the following state in the withdrawable frame: OPEN (OFF) position Closing spring relaxed Until it is installed, store the withdrawable module with the SION vacuum circuit-breaker (and earthing switch) in closed, dry, well-ventilated and, as far as possible, dust-free rooms in its foil (dense packing for overseas transport). Relative humidity in storage rooms should be less than 60 %. The withdrawable module with the SION vacuum circuit-breaker (and earthing switch) can be stored and transported outside the context of its normal operating conditions within the limit temperature range of -40 C to +55 C in closed foil (tight and closed packing). As the stacking quantity depends on the weight of the packing unit, the load-carrying capacity of the packing and its overall height, no more than three packing units should be stacked on one another. The weight of the packing unit is documented on the delivery note. The withdrawable module with the SION vacuum circuit-breaker (and earthing switch) for overseas transport are packed with VCI foil. The VCI foil creates a protective atmosphere that safeguards the circuit-breaker against corrosion. The protective atmosphere evaporates without residues after a short time when the VCI foil is removed, so the circuit-breaker can be used directly out of the packing without any subsequent treatment A
9 Description Description Structure Fig. 6 Withdrawable module with SION vacuum circuit-breaker 1 SION vacuum circuit-breaker 10 Withdrawable section 11 Shutter operating mechanism 12 Link 100 Withdrawable frame 110 Contact system 120 Contact arm (Ø40 mm, Ø60 mm) 130 Shutter 131 Swivel lever 140 Bushing 141 Mating contact 142 Bushing cover 143 Busbar terminal A 7
10 Description Scope of delivery Delivery includes: SION vacuum circuit-breaker with withdrawable section Withdrawable frame Contact systems and contact arms Mating contact, bushing and bushing cover (depending on the version) Earthing switch (optional) System-side isolation shells (optional) Hand crank, circuit-breaker 3AX1530-2B (optional) Handle, withdrawable section 3AX1430-2C (optional) Handle, earthing switch 3AX1430-2D (optional) Handle, earthing switch 3AX1430-3D (optional) Operating instructions Versions - technical data Rated voltage Rated operating current Rated short-time current Pole center distance Distance between top and bottom terminals U r (kv) I r (A) I k (ka) mm mm 7,2 17, ,5-31,5 150*; *; 310 7,2 17, , ; * I r 1250 A Fig. 7 Versions with withdrawable module Rating plate / II-3de Typ 3AE Nr. S 3AE/ Ur 12 kv, 50/60 Hz Isc 31,5 ka Ud/Up 28/75 kv Bauform 1A Baujahr 2005 Ir 1250 A tk 3 s m 180 kg Klasse nach IEC MADE IN GERMANY Fig. 8 Withdrawable frame rating plate Q Kontr Manufacturer 2 Type identification 3 Year of manufacture 4 Rated operating current I r 5 Rated short-circuit duration t k 6 Mass m 7 Classification to IEC Rated short-time AC voltage U d 9 Rated lightning impulse withstand voltage U p 10 Rated short-circuit breaking current I sc 11 Rated voltage U r 12 Works serial number 13 Type designation 14 Quality control stamp A
11 TInstallationT Installation DANGER High voltage! Mortal danger! Do not touch live parts! Make sure that the SION vacuum circuit-breaker in the withdrawable frame is operated only by qualified personnel who are familiar with the operating instructions and who comply with the warning notices. WARNING Risk of injury! Do not touch live parts! Before and during installation in switchgear, check whether minimum clearances from insulated and live parts, as well as parts subject to spring force, are maintained. Preparations Before installation in the functional unit: Remove packed accessories from the spaces Move the SION vacuum circuit-breaker out of the withdrawable frame and remove it after opening the interlocks Detach the transport beam. 1. Undo the screw on one side of the transport beam. 2. Pull out the transport beam towards the other side. Fig. 9 Detaching the transport beam A 9
12 TInstallationT Fitting the withdrawable frame Installing the withdrawable frame in the functional unit To secure the withdrawable frame (100) in the functional unit, Ø 6.6 mm holes can be produced in the functional unit's space in conformity with the hole pattern of the withdrawable frame's side walls, and steel L-brackets (see Fig. 10) can be placed under it. Insert the withdrawable frame and lower it onto the L-brackets. Fig. 10 Installing the withdrawable frame (100) in the functional unit Secure the withdrawable frame (100) in the functional unit, for example with blind rivets to ISO x 12-St/St Fig. 11 Securing the withdrawable frame (100) in the functional unit A
13 TInstallationT Busbars before assembly: Roughen Clean Grease with Vaseline to protect against corrosion Clean and grease silver-plated busbar terminals (143)! Fig. 12 Preparing the busbar terminals (143) Firmly bolt the busbars onto the busbar terminals (143). Tightening torque for M12: 40 ±4 Nm Tightening torque applies to greased threads only! Fit the bushing covers (142) (depending on the version) onto the bushing (140) so that they engage in the recesses (A). Fig. 13 Securing the busbars onto the busbar terminals (143) A 11
14 TInstallationT Earth the withdrawable frame (100) on the pressure pads for the withdrawable section: Screw suitable earthing cables or busbars (2 x 100 mm 2 ) with an M10 earthing screw onto the through-holes (1) with the earthing symbol labels ( ). Fig. 14 Earthing the withdrawable frame (100) A
15 Operation Operation DANGER High voltage! Mortal danger! Do not touch live parts! Make sure that the withdrawable module with the SION vacuum circuit-breaker is operated only by qualified personnel who are familiar with the operating instructions and who comply with the warning notices. WARNING Risk of injury! During operation of electrical switching devices and systems, hazardous voltages are present in parts of the withdrawable module with the SION vacuum circuit-breaker. Mechanical parts may move fast, also by remote control. Do not remove covers! Do not reach into openings! Do not touch circuit-breaker poles! Using the SION vacuum circuit-breaker with a withdrawable section in the withdrawable frame Insert the SION vacuum circuit-breaker with withdrawable section in the fitted withdrawable frame (100) and push it in the direction indicated by the arrow. Fig. 15 Inserting the SION vacuum circuit-breaker in the withdrawable frame (100) A 13
16 Operation Slide the SION vacuum circuit-breaker with withdrawable section into the withdrawable frame (100) up to the side stops (large arrow); to do this, move the locking handles towards the center of the circuit-breaker (small arrows). Note If an undervoltage release 3AX1103 is fitted, it must be connected to control voltage for switching operations (mechanical or electrical), as otherwise closing is not possible. Fig. 16 Inserting and locking the SION vacuum circuitbreaker with withdrawable section in the withdrawable frame (100) CAUTION When moving it on the withdrawable section, make sure that the SION vacuum circuit-breaker is in the following state: OPEN (OFF) position Closing spring relaxed Insert the handle of the withdrawable section 3AX1430-2C in the withdrawable section's coupling and turn it clockwise to move the SION vacuum circuit-breaker up to a tangible stop. Fig. 17 Moving the SION vacuum circuit-breaker with withdrawable section in the withdrawable frame (100) A
17 Installation accessories Installation accessories DANGER High voltage! Mortal danger! Do not touch live parts! Make sure that the SION vacuum circuit-breaker in the withdrawable frame is operated only by qualified personnel who are familiar with the operating instructions and who comply with the warning notices. WARNING Risk of injury! Do not touch live parts! Before and during installation in switchgear, check that minimum clearances from insulated and live parts, as well as parts subject to spring force, are maintained. Assembling installation accessories Fitting contact arms and systems 1. Grease the screwed-in parts of the threaded rods with Vaseline. 2. Screw in the threaded rod, paying attention to correct choice of the screw-in depths. Fig. 18 Cleaning and fitting threaded rods for contact arms A 15
18 Installation accessories 1. Firmly screw threaded rods onto contact faces. Tightening torque for M12: 40 ±4 Nm M16: 100 ±10 Nm Tightening torques apply to greased threads only. 2. Roughen the faces of the copper contact arms, clean them and grease them with Vaseline. Clean faces with silver-plated contact faces and grease them with Vaseline. Fig. 19 Cleaning and fitting contact arms (120) Fig. 20 Fitting contact arms (120) A
19 Installation accessories For contact arms (120) (in the case of rated operating current I r 1250 A), insert them with Ø 40 mm contact arm adapters in the contact system (110): 1. Grease the contact finger in the contact system (110) with Molykote Longterm 2 2. Adjust the contact arm adapter in the contact system (110) with the screw, washers and nut 3. Tighten the contact arm adapter with an openended wrench in the contact system (110) 4. Undo the screw with washers and nut. Fig. 21 Preparing contact systems (120) (up to 24 kv, 1250 A) Fit the contact system (110) onto the threaded rod and contact arm (120), paying attention to the position of the contact system (round outer edge towards the contact arm). Firmly screw down the contact system (110) with a torque wrench. Tightening torque for M12: 40 ±4 Nm Tightening torques apply to greased threads only. Grease the other side of the contact system (110) with Molykote Longterm 2. Fig. 22 Securing contact systems (110) on contact arms (120) with Ø 40 mm A 17
20 Installation accessories On one side (round outer edge), grease the inside of the contact system (110, on the contact fingers) with Molykote Longterm 2. In the case of contact arms (120) with Ø 60 mm (rated operating current I r > 1250 A), fit contact systems (110) without a contact arm adapter onto the threaded rod and contact arms (pay attention to the contact system's position: round outer edge towards the contact arm). Firmly screw down the contact system (110) with a torque wrench. Tightening torque for M16: 100 ±10 Nm Tightening torque applies to greased threads only! Grease the other side of the contact system (110) with Molykote Longterm 2. Fig. 23 Securing contact systems (110) on contact arms (120) with Ø 60 mm Fitting the bushing and mating contact Screw bushings (140) with mating contacts (141), each with 4 saucer-head screws DIN 603 M8x with a square neck contact washers and hexagon nuts onto a non-ferromagnetic steel sheet in the functional unit or the rear of the withdrawable frame (100). Tightening torque: 25 ±2 Nm Tightening torque applies to greased threads only! Fit the bushing cover (142) from the other side. Fig. 24 Securing the bushing (140) with mating contact (141) onto the withdrawable frame (100) or sheet A
21 Withdrawable frame with earthing switch Installation accessories Fitting the withdrawable frame with earthing switch Prepare fitting of the withdrawable frame with earthing switch as described in Section Preparations, page 9. To secure the withdrawable frame with earthing switch in the functional unit, Ø 6.6 mm holes can be produced in the functional unit's space in conformity with the hole pattern of the withdrawable frame's side walls, and steel L-brackets (see Fig. 25) can be placed under it. Insert the withdrawable frame with earthing switch and lower it onto the L-brackets. Fig. 25 Fitting the withdrawable frame with earthing switch Note When securing the withdrawable frame with earthing switch in the functional unit, ensure that the earthing switch is installed so that easy access is possible if it later becomes necessary to replace the earthing switch gearing. Fig. 26 Earthing switch gearing detail A 19
22 Installation accessories For connection of the main conductors, the busbars with the geometries and dimensions shown in Fig. 27 must be used in accordance with the switch version listed in Fig. 28. The busbars must be dimensioned in compliance with DIN (aluminium busbars) or DIN (copper busbars). Fig. 27 Busbars Switch version Busbar version Dimensions A (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm) J (mm) K ( ) L (mm) a/f: 275 mm U r 17.5 kv; I 1250 A, r I 31.5 ka sc a/f: 310 mm U r 17.5 kv; I 1250 A, r I 31.5 ka sc 1) 87,5 237, ) 87,5 257, U 17.5 kv; 1) 37,5 267,5 174, , r I > 1250 A, r I 31.5 ka sc U 24 kv; 1) 37,5 320, r I 1250 A, r I 25 ka sc Ur 24 kv; 1) 37,5 320, I > 1250 A, r I 25 ka sc Ur 17.5 kv; 2) 27,2 221, , x 12.5 I 3150 A, r I 40 ka sc a/f: U r : I r : I sc : width across flats, distance between top and bottom contact arms Rated voltage Rated operating current Rated short-circuit breaking current Fig. 28 Busbar dimensions A
23 Installation accessories Note The busbars of the earthing switch must be stabilized during their connection. Fig. 29 Connecting busbars Operation To operate the earthing switch Push the slider up (vertical arrow) Insert the earthing switch handle 3AX1430-2D (or 3AX1430-3D in the case of the kv, 40 ka version) completely Fig. 30 Preparing operation of the earthing switch with withdrawable module and SION vacuum circuitbreaker A 21
24 Installation accessories To switch on Turn the earthing switch handle 3AX1430-2D (or 3AX1430-3D) clockwise through 180. To switch off Turn the earthing switch handle 3AX1430-2D (or 3AX1430-3D) counterclockwise through 180. Note Due to a built-in return lock, it is only possible to turn back the earthing switch handle when the end position has been reached and 180 rotation has been completed. Fig. 31 Closing the earthing switch with withdrawable module and SION vacuum circuit-breaker Remove the earthing switch handle when the earthing switch is activated. The opening for the earthing switch handle stays open, and the indicator of the earthing switch shows: Fig. 32 Earthing switch with withdrawable module and SION vacuum circuit-breaker earthed A
25 Installation accessories Interlocks Position of the vacuum circuit-breaker Removed Insert/ remove* Disconnected position Move Connected position Circuit-breaker primary contacts closed Circuit-breaker cannot be moved X Circuit-breaker cannot be moved Circuit-breaker primary contacts open Earthing switch closed X Circuit-breaker X X cannot be moved Earthing switch open Possible X Not possible * Inserting or removing the circuit-breaker into/from the withdrawable frame Fig. 33 Interlocks Note Earthing switch handle 3AX1430-2D (or 3AX1430-3D) inserted or earthing switch activated Moving the withdrawable unit not possible Handle for withdrawable section 3AX1430-2C cannot be inserted Withdrawable section cannot be removed from the withdrawable frame. Handle for withdrawable section 3AX1430-2C inserted or withdrawable section between connected and disconnected positions: Activating the earthing switch not possible Opening for the earthing switch handle 3AX1430-2D (or 3AX1430-3D) cannot be operated A 23
26 Installation accessories Blank page A
27 Maintenance Maintenance DANGER Risk of injury! Working on the withdrawable module with the SION vacuum circuit-breaker activated/deactivated and with the spring energy store charged can lead to mortally serious injuries. Disconnect the operating voltage and switch off the lowvoltage supply before performing maintenance work! Close and open the vacuum circuit-breaker manually. By doing so, you will make sure that the circuit-breaker is open and that the spring energy store is relaxed. Close and open the vacuum circuit-breaker manually. By doing so, you will make sure that the circuit-breaker is open and that the spring energy store is relaxed. Maintenance General The SION vacuum circuit-breaker requires no maintenance under normal conditions. We nevertheless recommend a regular visual check. For optimum insulation, the insulating parts must be clean: Switch off the low-voltage supply before performing maintenance work! In the event of heavy soiling, wipe off all other parts with a lint-free cleaning cloth. Grease the contact faces to busbars with Vaseline. Accessories and spare parts Manufacturer's product liability Service Accessories Accessories Circuit-breaker hand crank Withdrawable section handle Earthing switch handle Molykote Longterm 2 contact grease Order number 3AX1530-2B 3AX1430-2C 3AX1430-2D or 3AX1430-3D (for kv, 40 ka version) 3AX1133-2L Operating instructions Fig. 34 Accessories available for ordering Replacing spare parts To ensure that the unit remains in reliable working order, spare parts may only be replaced by trained and certified personnel A 25
28 Maintenance Product liability The manufacturer's product liability will be rendered null and void if at least one of the following criteria applies: Original Siemens spare parts are not used. Fitters performing replacement have not been trained and certified by Siemens PTD M C. Parts have been incorrectly fitted or adjusted. Settings are not made in accordance with Siemens specifications. After installation and setting, no final check is performed with a tester approved by PTD M C including documentation of the test results. So that documentation can be kept complete, it is important for measurement results to be submitted to PTD M C Q. Service For details of contacts for service work, consult Siemens PTD Services Tel.: / Fax: / or on the Internet at the Web address: by support.energy@siemens.com or any local Siemens office. Disposal If possible, the materials of the withdrawable module should be recycled. Disposal of the withdrawable module with minimum environmental impact is possible on the basis of existing legal regulations. The components of the withdrawable module, of the SION vacuum circuit-breaker and of the installation accessories can be recycled as mixed scrap, although dismantling to the maximum extent possible into sorted scrap and mixed scrap residues is more environmentally sustainable. Electronic scrap must be disposed of in accordance with applicable regulations. The withdrawable module with the SION vacuum circuit-breaker consists of the following materials: Steel (partly phosphatized, galvanized and yellow chromated) Copper (partly silver-plated) Aluminum (partly silver-plated) Plastics (polyamide, polyester, polycarbonate, ABS-PC mixture; partly fiberglass-reinforced) Rubber materials Ceramics Lubricants When delivered by Siemens, the circuit-breaker does not contain any hazardous substances in terms of the hazardous substances regulations applicable to the territory of the Federal Republic of Germany. For operation outside the Federal Republic of Germany, the applicable local laws and regulations must be complied with. Packing materials, consisting of galvanized sheet steel, wood, cardboard, plastic foils (VCI foil, PE and PP) and hoops (PET), should also be recycled after correct sorting or should be passed on for disposal. Contact your Siemens service center if you require further information A
29 Index Index A Accessories Assembly B Busbar... 12, 13, 22, 23 Busbar terminal... 8 Busbar version Bushing... 8, 9, 12, 20 Bushing cover... 8, 9, 12, 20 Locking...15 Locking handles...15 M Main conductor...22 Maintenance...27 Mass...9 Mating contact...8, 9, 20 Mixed scrap...28 Molykote Longterm , 20, 27 C O Circuit-breaker hand crank 3AX1530-2B Operation...14 Classification to IEC P Connected position Packing...3, 4, 7 Contact arm... 8, 9, 17, 18, 19, 20, 22 Pole center distance...9 Contact arm adapter Pressure pad...13 Contact face... 18, 27 Primary contacts...25 Contact finger Product liability...28 Contact system... 8, 9, 19, 20 Control voltage R Crane transport... 3, 6 Rated frequency...9 Rated lightning impulse withstand voltage...9 D Rated operating current...9, 19, 22 Data, technical... 9 Rated short-circuit breaking current...9, 22 Disconnected position Rated short-circuit duration...9 Disposal Rated short-time AC voltage...9 E Rated short-time current...9 Earthing Rated voltage...9, 22 Earthing switch... 7, 9, 21, 23, 24, 25 Rating plate...9 Earthing switch handle 3AX1430-2D or 3D Return lock...24 Earthing switch indicator S Scope of delivery...9 F Service...28 Fitting Service work...28 Functional unit... 10, 11, 20, 21 Shutter...8 Shutter operating mechanism...8 G Spare parts...27 Grease... 12, 17, 18, 19, 20, 27 Storage...7 H Switch version...22 Hand crank, circuit-breaker 3AX1530-2B... 9 Swivel lever...8 Handle, earthing switch 3AX1430-2D or 3D. 9, 23, 24 System-side isolation shells...9 Handle, withdrawable section 3AX1430-2C T Handle, withdrawable section 3AX1430-2C (optional) Technical data Threaded rod...17, 18, 19, 20 Hole pattern... 11, 21 Transport...3 Humidity, relative... 7 Transport beam...3, 10 I Type designation...9 Inserting Type identification...9 Installation U Installation accessories Undervoltage release...15 Interlocks... 10, 25 Unpacking...3 Internet V L Vacuum circuit-breaker... L-bracket... 11, , 4, 6, 7, 8, 9, 10, 14, 15, 17, 23, 24, 25, 27, 28 Link A 27
30 Index Vaseline...12, 17, 18, 27 Withdrawable section... 8, 9, 13, 14, 15 Versions... 9 Withdrawable section handle 3AX1430-2C Works serial number... 9 W Workshop crane... 6 Weight... 6 Width across flats Y Withdrawable frame..3, 6, 8, 9, 11, 13, 14, 15, 20, 25 Year of manufacture... 9 Withdrawable module...3, 6, 8, 9, 23, 24, A
31 Blank page A 29
32 Published by Published by Energy Sector Power Distribution Division Medium Voltage Components Berlin Schaltwerk switchgear factory D Berlin
SION Lateral OPERATING INSTRUCTIONS. Vacuum circuit-breaker 12 kv 24 kv 12.5 ka 25 ka
SION Lateral Vacuum circuit-breaker 12 kv 24 kv 12.5 ka 25 ka OPERATING INSTRUCTIONS Order No.: 9229 0020 176 0- Ordered from: EM LP IEC PRM MVP AG 09.2016 en Siemens AG 2016. All rights reserved. For
More information3AH3 OPERATING INSTRUCTIONS. Vacuum circuit-breaker 3AH AH33. Order no.: E Ordering location: IC LMV LP PO P C41 AG 08.
3AH3 Vacuum circuit-breaker 3AH30... 3AH33 OPERATING INSTRUCTIONS Order no.: 9229 9860 176 0E Ordering location: IC LMV LP PO P C41 AG 08.2013 en Siemens AG 1996. All rights reserved. For your safety Signal
More informationOPERATING INSTRUCTIONS
3AH4 Vacuum circuit-breaker 3AH41, 3AH42 and 3AH43 OPERATING INSTRUCTIONS Order no.: 9229 9862 176 0D Ordering location: IC LMV LP PO P C41 AG 08.2013 en Siemens AG 1996. All rights reserved. For your
More information3AK7 OPERATING INSTRUCTIONS. 3AK7 vacuum circuit-breaker. Order no.: A Ordering location: IC LMV LP PO P C41 AG 09.
3AK7 3AK7 vacuum circuit-breaker OPERATING INSTRUCTIONS Order no.: 9229 0055 176 0A Ordering location: IC LMV LP PO P C41 AG 09.2013 en Siemens AG 2008. All rights reserved. For your safety Signal terms
More informationSiemens Parts 3AH47 OPERATING INSTRUCTIONS. Vacuum circuit-breaker 17.5 kv Hz and 27.5 kv - 50/60 Hz
3AH47 Vacuum circuit-breaker 17.5 kv - 16.7 Hz and 27.5 kv - 50/60 Hz OPERATING INSTRUCTIONS Siemens AG 1996. All rights reserved. Order no.: 9229 9947 176 0C Ordering location: IC LMV LP PO P C41 AG 03.2013
More informationGMA Panels with double busbar
L1 L2 L3 GAS-INSULATED SWITCHGEAR >> GMA Panels with double busbar Operating Instructions No. AGS 532 521-01 Edition 09/07 (Supplement to Operating Instructions AGS 531 521-01) Technical Instructions AREVA
More informationINSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC
AQB09JJ6WC_IM_E_2585 2006.4.17 4:26 PM Page 17 INSTALLATION MANUAL Indoor Unit AQB09JJWC AQB12JJWC Outdoor Unit UQB09JJWC UQB12JJWC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)
More informationGESTRA Steam Systems DK 45. English. Installation Instructions Steam Trap DK 45
GESTRA Steam Systems DK 45 EN English Installation Instructions 818676-00 Steam Trap DK 45 1 Contents Important Notes Page Usage for the intended purpose...4 Safety note...4 Danger...4 Attention...4 PED
More informationINSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC
AQB8J6WC_IM_E_25864 2006.4.4 3:29 PM Page 7 INSTALLATION MANUAL Indoor Unit AQB8J6WC AQB24J2WC Outdoor Unit UQB8J6WC UQB24J2WC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)
More informationInstruction Manual. Orayonne. Glass radiation heater
Instruction Manual Orayonne Glass radiation heater Table of Contents General...19 Safety information...20 Manufacturing state, packaging and recycling...21 Installation instructions for the fitter...22
More informationLUCCI AIRFUSION QUEST II CEILING FAN
LUCCI AIRFUSION QUEST II CEILING FAN WITH IR REMOTE INSTALLATION OPERATION MAINTENANCE WARRANTY INFORMATION CAUTION READ INSTRUCTIONS CAREFULLY FOR SAFE INSTALLATION AND FAN OPERATION. V1.0 QUEST II IR
More informationUser Manual GV25 GV35 GV702. Company information: Original instructions GV12066 (1)
User Manual Original instructions GV25 GV35 GV702 Company information: www.vipercleaning.eu info-eu@vipercleaning.com GV12066 (1) 2012-04-10 USER MANUAL ENGLISH TABLE OF CONTENTS Introduction... 4 Manual
More informationAOYG18LFC OUTDOOR UNIT INSTALLATION MANUAL INSTALLATION MANUAL. For authorized service personnel only. PART NO
AOYG8LFC OUTDOOR UNIT INSTALLATION MANUAL INSTALLATION MANUAL For authorized service personnel only. English PART NO. 93778639 93778639_IM.indb /20/20 6:07:25 PM AIR CONDITIONER OUTDOOR UNIT INSTALLATION
More informationCEILING FAN OWNER S MANUAL
CEILING FAN OWNER S MANUAL VERA CRUZ 5/04 GENERAL INSTALLATION & OPERATION INSTRUCTIONS IMPORTANT SAFEGUARDS: 1. To ensure the success of the installation, be sure to read the instructions and review the
More informationInstallation Instructions. Mira LED Light System
Installation Instructions Mira LED Light System w w w. a m i c o. c o m Contents Symbols Used in This Manual 4 Safety Instructions 5 Variants 7 Scope Of Delivery 8 Installing Mira LED Ceiling Mounted Installing
More informationAdditional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-i.
Additional Operating Instructions SITRANS F Vortex flowmeters Ex-i Edition 09/2018 CONTENTS 1 Safety instructions 3 1.1 General notes... 3 1.2 EU conformity... 3 1.3 Approval according to the IECEx scheme...
More informationTransportation. Distribution
Distribution Transportation Busbar Shielded Systems type: Cast Resin Low Voltage The shielded busbar system, ISOBUSBAR, type IS isolated in polyester or epoxy resin, have been specifically developed for
More informationPlease read operating instructions carefully before use and keep it for further reference.
GB OPERATING INSTRUCTIONS Automatic hot-air welding machine Please read operating instructions carefully before use and keep it for further reference. APPLICATION Overlap and tape welding of coated fabric
More informationUSER MANUAL FOR EXPLOSION PROTECTED FLUORESCENT LIGHT FITTING type PSF 218
CONTENT 1. Manufacturer 1 2. General safety informations 1 3. Purpose 2 4. Product compliance 2 5. Degree of protection and technical data 2 6. Type 3 7. Mounting and installation 3 8. Dimensions 6 9.
More informationCENTAFLEX Series A Assembly and operating instructions CF-AR M EN Rev. 2
Contents 1 General remarks... 5 2 Safety... 6 2.1 Safety remarks... 6 2.1.1 Signal words... 6 2.1.2 Pictograms... 7 2.2 Qualification of deployed personnel... 7 2.3 Intended application... 7 2.4 Application
More informationInstallation Manual PS-225 & PS-275
Installation Manual PS-225 & PS-275 Table of Contents Pre-Uncrating Checklist... 1 Verifying System Requirements... 2 Verifying System Direction... 2 Verifying the Electrical Requirements... 2 Removal
More informationLevel Electrode NRG NRG Original Installation Instructions English
Level Electrode NRG 10-52 NRG 16-52 EN English Original Installation Instructions 819123-02 Contents Important notes Page Usage for the intended purpose...4 Function...4 Safety note...4 Directives and
More informationDisposal Unit (BKSDU) Burger King Shortening. Operation, Service & Parts Manual BURGER KING BKSDU
BURGER KING BKSDU Burger King Shortening Disposal Unit (BKSDU) Operation, Service & Parts Manual Frymaster, a member of the Commercial Food Equipment Service Association, recommends using CFESA Certified
More informationGrain crusher Universal. Purpose: This machine is designed for the crushing of grain in agricultural operation.
Grain crusher Universal. Purpose: This machine is designed for the crushing of grain in agricultural operation. Operating instructions and parts catalogue This grain crusher provides you with a machine
More informationBMI / BRI VERTICAL AGITATOR
INSTALLATION, SERVICE AND MAINTENANCE INSTRUCTIONS BMI / BRI VERTICAL AGITATOR INOXPA, S.A. c/telers, 54 Aptdo. 174 E-17820 Banyoles - Girona (Spain) Tel. : (34) 972-57 52 00 Fax. : (34) 972-57 55 02 Email:
More informationSCHMIDT Flow Sensor SS Ex - Supplementary instructions for use in explosive atmospheres ATEX
SCHMIDT Flow Sensor SS 20.600 Ex - Supplementary instructions for use in explosive atmospheres ATEX SCHMIDT Flow Sensor SS 20.600 Ex ATEX version Table of Contents 1 Important information... 3 2 Storage
More informationSpare parts list. Hydraulic compactor RC
Spare parts list Hydraulic compactor RC 150 RC 150 Valid from serial number BGF0102397 Valid to serial number www.cp.com RC 150 Spare parts list General information This spare parts list applies to the
More informationSCC-E Sample Gas Feed Unit. Operator s Manual 42/23-58 EN Rev. 1
SCC-E Sample Gas Feed Unit Operator s Manual 42/23-58 EN Rev. 1 Contents Page Preface 3 General Safety Information 4 Safety Tips for Handling Electronic Measurement Devices 5 Chapter 1 Chapter 2 Chapter
More informationF17W44_MFB_F_EN INSTALLATION INSTRUCTIONS
F17W44_MFB_F_EN INSTALLATION INSTRUCTIONS Contents Page User instructions 3-5 General 3 Fan installation 3-4 Maintenance 3 Electrical installation 5 Troubleshooting 5 Technical description 6-8 General
More informationCEILING FAN OWNER S MANUAL
CEILING FAN OWNER S MANUAL LX SERIES 5/04 WARNING: Read and follow these instructions carefully and be mindful of all warnings shown throughout. GENERAL INSTALLATION & OPERATION INSTRUCTIONS IMPORTANT
More informationNRG NRG NRG NRG
GESTRA Steam Systems NRG 16-50 NRG 17-50 NRG 19-50 NRG 111-50 EN English Installation Instructions 818954-04 Level Electrodes NRG 16-50, NRG 17-50, NRG 19-50, NRG 111-50 1 Contents Important Notes Page
More information52 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V.
Irene 52 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V. 60Hz TABLE OF CONTENTS Tools and Materials Required... 1 Package Contents... 1 Safety Rules... 2 Mounting Options... 3 Hanging
More informationSteam Trap BK 45 BK 45-U BK 45-LT BK 46
Steam Trap BK 45 BK 45-U BK 45-LT BK 46 Original Installation Instructions 810437-08 Contents Foreword... 3 Availability... 3 Formatting features in the document... 3 Safety... 3 Use for the intended purpose...
More informationGESTRA Steam Systems BK 15. Installation Instructions Steam Trap BK 15, DN 40-50
GESTRA Steam Systems BK 15 Installation Instructions 810682-02 Steam Trap BK 15, DN 40-50 Contents Important Notes Page Usage for the intended purpose...4 Safety note...4 Danger...4 Attention...4 PED (Pressure
More informationElectric Space Heater
The Choice of Professionals Model No. FUH Series Electric Space Heater Installation & Maintenance Instructions SPECIFICATIONS: FUH 54B Heater Rating and Voltage 5000 W @ 40V 465W @ 40V 333W @ 40V 500W
More informationMontageanleitung RLO (Original) Mounting Instructions RLO (Translation of the original)
Montageanleitung (Original) (Translation of the original) DE MA_ 1.0 06/2014 Taperlock Clamping-bush system _0 _1 Fixed hub Inlet nozzle with IMV 1. Revision index Revision Date MA_ 1.0 06/2014 2. Safety
More informationSPECIFICATION FOR GAPLESS METAL OXIDE DISTRIBUTION TYPE SURGE ARRESTERS WITH POLYMERIC HOUSING
SPECIFICATION FOR GAPLESS METAL OXIDE DISTRIBUTION TYPE SURGE ARRESTERS WITH POLYMERIC HOUSING Page 1 of 10 CONTENTS 1 SCOPE 2 DEFINITIONS 2.1 SURGE ARRESTER 2.2 GAPLESS METAL-OXIDE SURGE ARRESTERS 2.3
More informationMechanical seals external, single or double, to DIN EN 12756
INSTALLATION AND OPERATING MANUAL Translation of the original manual Series SCK Bearing pedestal group: 0 Mechanical seals external, single or Keep for future use! This operating manual must be strictly
More informationOperating instructions Rotary iron HM
Operating instructions Rotary iron HM 21-140 To prevent accidents and machine damage read these instructions en - US, CA before installation or use. M.-Nr. 07 660 861 Contents Important Safety Instructions.................................................................3
More informationModels , Equinox, and Sirens Clutch Replacement Service Manual
Models 2001-130, Equinox, and 508-128 Sirens Clutch Replacement Service Manual 25500297 Rev. A0 1115 Printed in U.S.A. Copyright 2015 Federal Signal Corporation Contents Safety Messages... 3 General Description...
More informationAll-Metal Control Valve
Operating Instructions All-Metal Control Valve Thermomechanically and manually actuated UDV 146 BP 805 281 BE (0203) 1 Product Identification In all communications with Pfeiffer Vacuum, please specify
More informationSION Vacuum Circuit-Breakers
www.siemens.com/sion SION Vacuum Circuit-Breakers Medium-voltage circuit-breakers precise form and function Answers for infrastructure and cities. Contents 2 Compact design for perfect switching everywhere
More informationREVIVAL LITE VITREOUS CHINA REVERSE TRAP TOILET
REVIVAL LITE VITREOUS CHINA REVERSE TRAP TOILET BEFORE YOU BEGIN HOW TO USE THESE INSTRUCTIONS Please read these instructions carefully to familiarize yourself with the required tools, materials, and installation
More informationLIMITED LIFETIME WARRANTY
LIMITED LIFETIME WARRANTY Model No.: F0023 / F0024 aireryder ORIGINAL CEILING FAN LIMITED LIFETIME WARRANTY The limited lifetime warranty covers this ceiling fan, for residential use by the original purchaser,
More informationHeight-adjustable Unit
Height-adjustable Unit for Ropox Toilet Support Arms PDF 6142 / 01.10.2016 User Manual and Mounting Instructions Keep this manual with the product at all times Contents CONTENTS... 2 USER MANUAL... 3 MOUNTING
More informationINFRARED IP55 HEATER INSTRUCTIONS FOR: MODEL:- QZWP45N 1. SAFETY INSTRUCTIONS
INSTRUCTIONS FOR: INFRARED IP55 HEATER MODEL:- QZWP45N Thank you for purchasing a Consort Claudgen product. Manufactured to a high standard this product will, if used according to these instructions and
More informationVERSAFLOW VORTEX Supplementary instructions
VERSAFLOW VORTEX Supplementary instructions Vortex flowmeter Equipment category II 2G CONTENTS VERSAFLOW VORTEX 1 Safety instructions 3 1.1 General notes... 3 1.2 EC conformity... 3 1.3 Approval according
More informationHD Kompakt Service Manual
HD Kompakt Service Manual English 5.906-583.0 Rev. 00 (08/13) 1 1 Contents 1 Contents.................................................... 2 2 Preface.....................................................
More informationInstallation Manual PS-200 & PS-201
Installation Manual PS-200 & PS-201 Table of Contents Pre-Uncrating Checklist... 1 Verifying System Requirements... 2 Verifying System Direction... 2 Verifying the Electrical Requirements... 2 Removal
More informationGROTON. U.S. Patent(s) Pending INSTRUCTION MANUAL WARRANTY CERTIFICATE
GROTON BY U.S. Patent(s) Pending INSTRUCTION MANUAL WARRANTY CERTIFICATE This product is protected by United States Federal and/or State Law, including Patent, Trademark and/or Copyright laws. Manual design
More information7165 Dust Collector Owner s Manual
7165 Dust Collector Owner s Manual Oliver Machinery M-7165 12/2016 Seattle, WA Copyright 2003-2017 info@olivermachinery.net www.olivermachinery.net CONTENTS IMPORTANT SAFETY RULES----------------------------------------------------------------
More information51AKB / 51 AKC OWNER S MANUAL
51AKB / 51 AKC OWNER S MANUAL This manual applies to the following models 51AKB 009 51AKB 012 51AKC 009 51AKC 012 Read this instruction manual thoroughly before using the air conditioner. Control panel
More informationContents. 1. Instructions for safety and use 20
Contents 1. Instructions for safety and use 20 2. Positioning in the counter top 21 2.1 Fixing to the supporting structure 21 2.2 Positioning the adhesive sponge 22 2.3 Positioning the fastening clips
More informationFlow switch. Operating Manual. English manual page Page 1 of 15 Fax:
Operating Manual www.jlso-tec-trade.de Flow switch English manual page 1-15 Page 1 of 15 Flow switch Table of Contents Page 1 Device Description and Intended Use... 19 1.1 Flow switch version VH...X...
More informationSHORT WAVE INFRARED PANEL DRYER
INSTRUCTIONS FOR: SHORT WAVE INFRARED PANEL DRYER MODEL: IR3000 Thank you for purchasing a Sealey product. Manufactured to a high standard this product will, if used according to these instructions and
More informationUSER MANUAL FOR EXPLOSION PROTECTED FLUORESCENT LIGHT FITTING type PSF 236
CONTENT 1. Manufacturer 1 2. General safety informations 1 3. Purpose 2 4. Product compliance 2 5. Degree of protection and technical data 2 6. Type 3 7. Mounting and installation 3 8. Dimensions 6 9.
More informationClosomat Lima Vita installation & user guide
Closomat Lima Vita installation & user guide design manufacture supply install service recycle Technical data The Closomat toilet MUST be installed by a competent or qualified person. Explanation of symbols
More informationSINAMICS G130. Cabinet design and EMC. Operating instructions 03/2011 SINAMICS
SINAMICS G130 Operating instructions 03/2011 SINAMICS s Safety information 1 General 2 SINAMICS SINAMICS G130 Basic information about EMC 3 EMC-compliant design and control cabinet configuration 4 Cabinet
More informationR32. Installation Manual Split Type Wall Mounted Air Conditioner. This appliance shall be installed in accordance with: REFRIGERANT
SWING LRSWING Installation Manual Split Type Wall Mounted Air Conditioner COOL RUN C SPEED TURBO ON/OFF FAN COOL HEAT SWING SWING Rinnai Systems Models System Indoor Outdoor HSNRQ25B HINRQ25B HONRQ25B
More informationSINAMICS G130. Cabinet design and EMC. Operating Instructions 05/2010 SINAMICS
SINAMICS G130 Operating Instructions 05/2010 SINAMICS s Safety information 1 General 2 SINAMICS SINAMICS G130 Basic information about EMC 3 EMC-compliant design and control cabinet configuration 4 Cabinet
More informationTechnical Data. Name: ERIKA Automat fully automatic machine to divide and to round dough pieces of the same size
AUTOMAT MANUAL 1 Technical Data Name: ERIKA Automat fully automatic machine to divide and to round dough pieces of the same size Type Divisions Dough Portions (in ounces) Plate Nos. 3 30 1.0 3.5 #35 4/40A
More informationFlameproof Manual Call Points
Operating instructions Additional languages www.r-stahl.com CS & Clifford & Snell Contents General Information.... Manufacturer.... Information regarding the operating instructions.... Further documents....
More informationLifting Station Type ABS Sanimax
1051-00 15970278EN (11/2015) EN Installation and Operating Instructions www.sulzer.com 2 Installation and Operating Instructions (Original Instructions) : R 202 MF 154 R 202/C MF 154HW MF 324 Contents
More informationCEILING FAN OWNER S MANUAL
Style that revolves around you. CEILING FAN OWNER S MANUAL Total fan weight *53 lbs. WEXFORD 11/05 WARNING: Read and follow these instructions carefully and be mindful of all warnings shown throughout.
More informationSECTION AUTOMATIC TRANSFER SWITCHES
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph
More informationWAILEA OWNER S MANUAL
WAILEA OWNER S MANUAL The blades in each pack are matched for equal weight to assure smooth fan operation. If more than one fan is being installed, be careful not to mix blades from different cartons.
More informationFSW300 Series Flow Switch
. FSW300 Series Flow Switch - 2 - Series FSW300 Series FSW300 Table of contents page 0 About this operating manual... 4 1 Device description... 5 1.1 Intended use... 5 1.1.1 Reed contact - Switching of
More informationMK 45-1 MK 45-2 MK 45 A-1 MK 45 A-2
GESTRA Steam Systems MK 45-1 MK 45-2 MK 45 A-1 MK 45 A-2 Installation Instructions 810348-07 Steam Traps MK 45-1, MK 45-2, MK 45 A-1, MK 45 A-2 Contents Important Notes Page Usage for the intended purpose...4
More informationUnpacking and removing shipping bolts. Connecting the drain line Leveling the washer Connecting to the power supply
11 INSTALLATION Installation Overview Choosing the proper location Unpacking and removing shipping bolts Connecting the water line Connecting the drain line Leveling the washer Connecting to the power
More informationNavigation Lights Signalling Lights Searchlights Whistles TECHNICAL DOCUMENT. DHR 230RCN 230 Remote Controlled Searchlight. Den Haan Rotterdam
Navigation Lights Signalling Lights Searchlights Whistles TECHNICAL DOCUMENT DHR 0RCN 0 Remote Controlled Searchlight Since 9 (Intentionally blank page) Version.0 October 08 ! Safety notes: Turn power
More informationOperation, Maintenance and Installation Manual
Manual No. FS-OM1-5 1-16 in. FloodSafe Inflow Preventer Operation, Maintenance and Installation Manual INTRODUCTION... 1 RECEIVING AND STORAGE... 1 DESCRIPTION OF OPERATION... 1 INSTALLATION... 2 CONSTRUCTION...
More informationInstallation Instructions
40MBFQ Floor Console Ductless System Sizes 09 to 58 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 WIRING... 4 DIMENSIONS... 5 CLEARANCES...
More informationNHS VERTICAL AGITATOR
INSTALLATION, SERVICE AND MAINTENANCE INSTRUCTIONS NHS VERTICAL AGITATOR INOXPA, S.A. c/telers, 54 Aptdo. 174 E-17820 Banyoles Girona (Spain) Tel. : (34) 972-57 52 00 Fax. : (34) 972-57 55 02 Email: inoxpa@inoxpa.com
More informationMAYFIELD CEILING FAN LISTED E ITEM # MODEL #BTH44ABZC5C BTH44BNK5C Español p. 20 ATTACH YOUR RECEIPT HERE.
Harbor Breeze is a registered trademark of LF, LLC. All Rights Reserved. ITEM #0331094 0331096 MAYFIELD CEILING FAN MODEL #BTH44ABZC5C BTH44BNK5C Español p. 20 ATTACH YOUR RECEIPT HERE Serial Number Purchase
More informationSTRATA BY INSTRUCTION MANUAL WARRANTY CERTIFICATE
STRATA BY INSTRUCTION MANUAL WARRANTY CERTIFICATE This product is protected by United States Federal and/or State Law, including Patent, Trademark and/or Copyright laws. Manual design and all elements
More informationENGINEER S MANUAL No.01
1-NEEDLE, UNISON FEED, LOCKSTITCH MACHINE (AUTOMATIC LUBRICATION) LU-1510 1-NEEDLE, UNISON FEED, LOCKSTITCH MACHINE WITH AUTOMATIC THREAD TRIMMER (AUTOMATIC LUBRICATION) LU-1510-7 1-NEEDLE, UNISON FEED,
More informationGESTRA Steam Systems BK 37 BK 28 BK 29. Installation Instructions Steam Trap BK 37, BK 28, BK 29 BK 37 ASME, BK 28 ASME, BK 29 ASME
GESTRA Steam Systems BK 37 BK 28 BK 29 Installation Instructions 818689-00 Steam Trap BK 37, BK 28, BK 29 BK 37 ASME, BK 28 ASME, BK 29 ASME Contents Important Notes Page Usage for the intended purpose...4
More informationTECHNICAL SPECIFICATION AUTOMATIC SINGLE POLE AND THREE POLE CIRCUIT BREAKERS FOR LV SUPPLIES
HELLENIC ELECTRICITY DISTRIBUTION NETWORK OPERATOR S.A. NOTICE OF CALL FOR TENDERS No ND-207 PROJECT: Pilot Telemetering and Management System for the Electric Power Supply Demand by Residential and Small
More information1. Description INSTRUCTION FOR AIR BLAST COOLER TYPE COOL 450
1. Description General The cooler is used for cooling of water, oil or other liquid by use of air. The liquid is passing in the tubes where it transfere the energy to the air via the fins on the outside
More informationWSD-E WHEEL DETECTOR QUICK REFERENCE GUIDE JUNE 2016 DOCUMENT NO. SIG-QG VERSION A
QUICK REFERENCE GUIDE WSD-E WHEEL DETECTOR JUNE 2016 DOCUMENT NO. SIG-QG-16-01 VERSION A Siemens Industry, Inc. Rail Automation 9568 Archibald Ave., Suite 100, Rancho Cucamonga, California 91730 1-800-793-SAFE
More informationC-IV 60 CEILING FAN READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 120V. 60Hz
C-IV 60 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V. 60Hz Please do not use any electric or battery powered tools in the assembly and installation of this or any Matthews Fan Company
More informationDiaphragm pump 4 - headed
Operation Manual (EN) Translation of the german original manual Diaphragm pump 4 - headed Model: 67000062 412743-23 2016-10-17 Gardner Denver Thomas GmbH Am Vogelherd 20 98693 Ilmenau Germany T +49 3677
More informationManual / Handbuch Spare parts list / Ersatzteilliste
Manual / Handbuch Spare parts list / Ersatzteilliste Equipment Imp.-Exp. GmbH Zitterpappelweg 9 D - 22391 Hamburg Tel.: + 49 40 60009468-0 Fax: + 49 40 536 75 01 E - M a i l : i n f o @ w e s c o - n a
More informationALUMA INSTRUCTION MANUAL WARRANTY CERTIFICATE
ALUMA BY INSTRUCTION MANUAL WARRANTY CERTIFICATE Manual design and all elements of manual design are protected by U.S. Federal and/or State Law, including Patent, Trademark and/or Copyright laws. The Minka-Aire
More informationELSTON 52 CEILING FAN
ELSTON 52 CEILING FAN MODEL #10290 Español p. 21 Questions, problems, missing parts? Before returning to your retailer, call our customer service department at 1-877-361-3883, Monday - Thursday, 8 am -
More informationModel: AC-108. Instruction Manual
Model: AC-108 Instruction Manual Attention: This appliance is not intended for use by persons (including Children) with reduced physical, sensory or mental capabilities or lack of experience and knowledge
More informationInstallation Instructions
40MBFQ Floor Console Ductless System Sizes 09 to 12 Installation Instructions TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 DIMENSIONS... 5 CLEARANCES... 5
More informationOperator's manual. Rebar tier DF en / 004
Operator's manual Rebar tier DF 16 03.2009 0214885en / 004 Manufacturer Wacker Neuson SE Preußenstraße 41 80809 München www.wackerneuson.com Tel.: +49-(0)89-354 02-0 Fax: +49-(0)89-354 02-390 Translation
More informationInstruction Manual. B Issue B. next Pump Accessories
Instruction Manual B811-00-880 Issue B next Pump Accessories This page has been intentionally left blank. Contents Section Page 1 Introduction... 1 Contents gea/0086/06/10 1.1 Scope and definitions...
More informationCeiling Fan Ow n e r s Manual
Style that revolves around you. Ceiling Fan Ow n e r s Manual Akina 1/08 WARNING: Read and follow these instructions carefully and be mindful of all warnings shown throughout. General Installation & Operation
More informationVACUUM CONTACTOR TYPE SVC-T 32. 7,2 kv A MANUAL FOR MOUNTING, OPERATION AND MAINTENANCE
VACUUM CONTACTOR TYPE SVC-T 32 7,2 kv - 400 A MANUAL FOR MOUNTING, OPERATION AND MAINTENANCE CONTENTS PAGE 1. Introduction...2 1.1 Acceptance inspection on delivery...2 2. General...2 3. Standards and
More information5HP CYCLONE DUST COLLECTOR MANUAL
5HP CYCLONE DUST COLLECTOR MANUAL LAGUNA TOOLS 2072 Alton Parkway Irvine, California 92606 Ph: 800.234.1976 www.lagunatools.com 2018, Laguna Tools, Inc. LAGUNA and the LAGUNA Logo are the registered trademarks
More informationQuartzone. Infrared Quartz Tube & Metal Sheathed Electric Heaters. Owner s Manual. File E COMFORT HEATERS for INDOOR* and OUTDOOR** USE
Quartzone Infrared Quartz Tube & Metal Sheathed Electric Heaters Owner s Manual File E97759 COMFORT S for INDOOR* and OUTDOOR** USE *Excluding Residences ** With Quartz Elements and when mounted Underneath
More informationInstalling the assembly SIMATIC. Installing the assembly. Overview 1. Installing the assembly. Getting Started A5E
Overview 1 2 SIMATIC Getting Started 03/2013 A5E03973659-01 Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as
More informationThis is a preview - click here to buy the full publication. High-voltage switchgear and controlgear
IEC/PAS 62271-109 Edition 1.0 2002-07 High-voltage switchgear and controlgear Part 109: Alternating-current series capacitor by-pass switches PUBLICLY AVAILABLE SPECIFICATION INTERNATIONAL ELECTROTECHNICAL
More informationU tube models PTU 09, 12, 15, 25, 30, 35, 40, 45. single linear tube models PTS 09, 12, 15, 25, 30, 35, 40, 45
U tube models PTU 09, 2, 5, 25, 30, 35, 40, 45 & single linear tube models PTS 09, 2, 5, 25, 30, 35, 40, 45 installation, servicing & operating instructions INSTALLATION, SERVICING AND OPERATING INSTRUCTIONS
More informationJAVA BY INSTRUCTION MANUAL WARRANTY CERTIFICATE
JAVA BY INSTRUCTION MANUAL WARRANTY CERTIFICATE 2017 Minka Lighting Inc. Manual design and elements of manual design are protected by United States Federal and/or State Law including Patents, Trademark,
More informationIMPORTANT SAFETY INSTRUCTIONS DANGER: WARNING:
IMPORTANT SAFETY INSTRUCTIONS YOUR SAFETY AND THAT OF OTHERS IS PARAMOUNT This manual and the appliance itself provide important safety warnings, to be read and observed at all times. This is the attention
More informationModel ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description
Technical Services 800-381-9312 +1-401-781-8220 www.tyco-fire.com Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description The TYCO Model ESFR-17 Dry
More informationOwner s Guide and Installation Manual
For Your Records and Warranty Assistance For reference, also attach your receipt or a copy of your receipt to the manual. Model Name Type 2A Models Owner s Guide and Installation Manual Model No. Date
More information