4KV Switchgear Susceptibility to Main Steam Line Break. By: Akbar Moarefy Kyle Millenaar PE
|
|
- Harry Dennis
- 6 years ago
- Views:
Transcription
1 4KV Switchgear Susceptibility to Main Steam Line Break By: Akbar Moarefy Kyle Millenaar PE
2 OE Discovery of New Harsh Environment Conditions 10/19/09 Monticello issued LER due to the failure of a HELB door fusible link with potential result of losing 4kV SWGR in case of HELB. 04/18/10 Prairie Island entered LCO after discovering U1 turbine building truck Aisle rollup door security fence was closed. This fence was required to remain open to drain flood water resulting from HELB in the turbine building. 9/16/11 Callaway issued LER due to failure in implementation of HELB defense (HELB doors) challenging equipment operability in areas of the plant that were intended to be mild. 2/10/12 Cooper (Green NCV): Failure to translate design requirements associated with turbine building HELB into design information to demonstrate protection of safety related 4160V switchgear and EDG 2/10/12 Braidwood (Green NCV): Failure to report non-conservative assumption in actuation time for fusible links that protect ESF switchgear room from HELB. 05/08/12 Braidwood (Green NCV): EQ failed to consider temp/humidity changes in EDG, ESG and MEER rooms during a turbine building HELB 06/07/12 Millstone entered TS action statement when they determined that the practice of opening the switchgear room doors as compensatory measure when ventilation was OOS could allow steam from HELB enter the SWGR.
3 DCPP Discovery of New Harsh Environment Conditions In August 2014, Diablo Canyon Power Plant entered Technical Specifications due to non-conservative assumptions in a legacy calculation resulting in the Design Class 1E emergency power supply switchgear (4kV switchgear) being exposed to a high-temperature, high-humidity environment during a main steam line break (MSLB). Corrective action was implemented by closing the fire dampers isolating 4kV SWGR from turbine deck atmosphere. Issue became past operability assessment (29 years)
4 Background Unit 1: Start up date Unit 2: Start up date Legacy calculation dated 1983 (before plant startup) assumed dead volume of air in the 4kV SWGR preventing the entry of steam following HELB. It also made wrong assumptions about fusible links closing the fire dampers, isolating SWGR from HELB environment. Reexamination of calculation of record proved the assumption to be wrong. Following a HELB in turbine building steam can enter the 4kV SWGR when the thermostat controlled HVAC fans are not running causing humidity reach 100%RH. 4kV SWGR components were not qualified for a 100%RH environment.
5 False Assumptions Room HVAC supply fans provide a positive pressure of psi. Model shows steam pressure to be approximately 10x greater than supply fan
6 Background Turbine building ceiling curved First stage high pressure turbine
7 Background 4kV Exhaust duct on Turbine Deck
8 Background 4kV switchgear panel top vent 4kV switchgear panel bottom vent
9 Is it possible to retract entry into 3.0.0? DCPP EQ Group recommended testing all the 4kV SWGR components under the newly discovered adverse condition. Other groups including AREVA suggested to pursue parallel success paths to prove past operability.
10 Is it possible to retract entry into 3.0.0? AREVA was contracted to lead the project. Nutherm was subcontracted to perform qualification tests. Initial proposal was received by AREVA on 8/12 The Test Spec was drafted by DCPP on 9/2/14 Testing was completed on 9/12/14 Final report was issued on 9/19 (5 weeks)
11 Paths to Prove Past Operability ALPHA Path: Elimination of 0.9 sq-ft longitudinal split break Double Ended guillotine break results in a rapid isolation of the steam line and does not create adverse environment in the 4kV SWGR. a 0.9 sq-ft longitudinal split break which is not sufficient in size to isolate the steam line but does expose the vented cabinets in the switchgear room to a 100% humidity environment. STATUS: This success path failed
12 Paths to Prove Past Operability BRAVO Path: Remove conservatism from GOTHIC model using NRC Operability determination guidelines such as IM goal was to prove the environment in the 4kV SWGR would remain mild following a HELB on the turbine deck. STATUS: This success path failed
13 Paths to Prove Past Operability CHARLIE Path: Using Computational Fluid Dynamics (CFD) Analysis for the 4kV SWGR. Use CFD models of the switchgear rooms to simulate the temperature, flow fields and humidity distribution inside the switchgear rooms. These simplified models included the air flow within the switchgear room from the floor to the exhaust duct/turbine building interface. Goal of the model was to demonstrate that the hot humid air entering the room would flow out the normal air inlet without approaching the vented cabinet vent locations. Thus concluding that the SWGR components would not have been subjected to an adverse environment. STATUS: This success path failed
14 Paths to Prove Past Operability DELTA Path: Computational Fluid Dynamics Analysis of Vented Cabinets. The simplified CFD models created in the CHARLIE path were used to extend to model the air flow and humidity distribution within the vented cabinets. Goal of this success path was to demonstrate that the even with 100% humidity in the 4kV SWGR, the components within the cabinets will not be exposed to condensing environment. STATUS: This success path failed
15 Paths to Prove Past Operability ECHO Path: Vented Cabinet Components Already Qualified for 100% humidity conditions. Compare DCPP s component list and HELB qualification requirements to existing industry qualification reports to eliminate or reduce the need to test components in humid environment. STATUS: Only one component was eliminated
16 Paths to Prove Past Operability FOXTROT Path Conduct Qualification Testing on the 4kV SWGR components. STATUS: 35 components representing 756 components used in the 4kV SWGR cabinets were successfully tested. Leakage current on a terminal block with broken barrier wall in a 100%RH condensing environment was measured to be minimal with no adverse impact. Potential for arc flash was eliminated by test on high voltage components.
17 TEST CABINET TEST CHAMBER
18 Questions?
Union County Vocational - Technical Schools Scotch Plains, New Jersey
SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Balancing Air Systems: a. Constant-volume air systems. b. Variable-air-volume systems. 2.
More informationCity of Duluth Festival Center 04/25
SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More informationFlexible and efficient: Close Climate Control for IT equipment
GEA Multi-DENCO Flexible and efficient: Close Climate Control for IT equipment engineering for a better world GEA Heat Exchangers GEA Multi-Denco at a glance: Multiple functions and applications High flexibility
More informationSubmitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge
ESL-TR-99/12-04 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University-Corpus Christi (TAMU-CC) Corpus Christi, Texas Submitted to Texas
More informationBrown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA
PART 1 - GENERAL 1.1 Background SECTION 26 00 10- ELECTRICAL DESIGN CRITERIA A. Brown University maintains it own campus electrical distribution system which serves the majority of the buildings and facilities
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 23 0594 - TESTING, ADJUSTING, AND BALANCING (TAB) PART 1 - GENERAL 1.1 SUMMARY A. This Section includes testing, adjusting and balancing HVAC systems to provide design conditions as indicated by
More informationHAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001
This HAP e-help provides a high-level overview of induction beams, how they work and how to model them in HAP 4.8 (and later versions). The first half of the article explains how induction beams work.
More informationAir Distribution Fan and Outside Air Damper Recycling Control
building science.com 2008 Building Science Press All rights of reproduction in any form reserved. Air Distribution Fan and Outside Air Damper Recycling Control Research Report - 0991 5-July-1999 Armin
More informationSECTION TESTING, ADJUSTING AND BALANCING
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections
More informationSECTION AIR DUCT ACCESSORIES
SECTION 23 33 00 AIR DUCT ACCESSORIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes back-draft dampers, combination fire-and-smoke dampers, duct access doors, fire dampers, smoke dampers, volume control
More informationTunnel Fire Dynamics and Evacuation Simulations
Tunnel Fire Dynamics and Evacuation Simulations James Priest, PhD & James Niehoff DGS-SEE Seminar on Fire Protection for Physics Research Facilities 7 & 8 October 2015 Introduction (Background) Presentation
More informationCxA to Answer this Section
EXHIBIT 01 91 13-3, SAMPLE Construction checklist items are to be completed as part of initial checkout and subsequent startup, preparatory to Functional testing. This checklist does not take the place
More informationS and SF Inverted Bucket Steam Traps Installation and Maintenance Instructions
0772150/4 IM-P077-02 ST Issue 4 S and SF Inverted Bucket Steam Traps Installation and Maintenance Instructions 1. General safety information 2. General product information 3. Installation 4. Commissioning
More informationINVESTIGATION FINDINGS III IMPACT OF INADEQUATE VENTILATION AND DISCHARGE SYSTEMS
INVESTIGATION FINDINGS III IMPACT OF INADEQUATE VENTILATION AND DISCHARGE SYSTEMS SUMMARY Ammonia odours were reported in the community close to the time of the incident (Appendix D) and firefighters reported
More informationCompany Directive STANDARD TECHNIQUE : SP1N
Company Directive STANDARD TECHNIQUE : SP1N Heating, Dehumidification and Ventilation of Switch Rooms and Control Rooms at Grid, Primary and Major Network Substations ST:SP1N October 2013-1 of 9 - Document
More informationJob Name Control Systems Description Date
Job Name Control Systems Description Date Project Overview The project is a describe the building and its major HVAC systems (e.g. three-story office building, served by a rooftop unit VAV system ). In
More informationAugust 15, 2013 Page 1 of 19
Section C401 Application Compliance with C402, C403, C404 and C405 AND (either C406.2, C406.3 or C406.4) Compliance with C402, C403, C404 or C405 Section C402 Building Envelope (Climate Zone 5A) Space-Conditioning
More informationFire, Smoke and Control Dampers
MANUAL Fire, Smoke and Control Dampers v100 Issue Date: 04/02/15 2015 Price Industries Limited. All rights reserved. TABLE OF CONTENTS Maintenance, Testing and Inspection Recommendations Recommended Maintenance
More informationDevelopment of standards for MV Switchgear for Arc Flash protection. ABB Group May 20, 2013 Slide 1
Development of standards for MV Switchgear for Arc Flash protection May 20, 2013 Slide 1 Development of standards for MV Switchgear for Arc Flash protection Bryan Johnson ABB South Africa Shaping the world
More informationControl of temperature and humidity surrounding the stone chamber of Takamatsuzuka tumulus during its dismantlement
Control of temperature and humidity surrounding the stone chamber of Takamatsuzuka tumulus during its dismantlement Daisuke Ogura 1, Masahide Inuzuka 2, Shuichi Hokoi 1, Takeshi Ishizaki 2, Hiroyuki Kitahara
More informationFEATURES AND BENEFITS
FEATURES AND BENEFITS Product Features and Benefits Full Product Line Offering Feature All models are 80% thermally efficient Blower performance up to 3.0 W.C. DX or chilled water section with factory
More informationAIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University
AIR-CONDITIONING SYSTEMS AND APPLICATIONS Abdullah Nuhait Ph D. King Saud University AIR-CONDITIONING SYSTEMS Earliest air conditioning system used only for heating (winter) Provided heated air for comfort
More informationRAMAPO COLLEGE OF NEW JERSEY CCA0803 PHASE II HOUSING REHABILITATION 2012
SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More informationPALO VERDE NUCLEAR GENERATING STATION
PALO VERDE NUCLEAR GENERATING STATION HVAC Classroom Lesson HVAC Training Date: 01/13/2005 LP Number: NMH10X000502 Rev Author: Paula Stapleton Title: PAMU AC Units Technical Review: Duration : 1.5 Hours
More information1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process.
SECTION 239950 MECHANICAL COMMISSIONING SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process. B. Commissioning
More informationSubmitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge
ESL-TR-99/12-05 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University at Galveston (TAMU-G) Galveston, Texas Submitted to Texas A&M University
More informationCOMcheck Software Version Review Mechanical Compliance Certificate
COMcheck Software Version 4.0.7.2 Review Mechanical Compliance Certificate Section 1: Project Information Energy Code: 2014 Oregon Energy Efficiency Specialty Code Project Title: Benton County Health Project
More informationHeating and Cooling Coils
Heating and Cooling Coils Coils for All Comfort, Commercial and Industrial Applications Delta-Flo Fin Design The Delta-Flo coil features a staggered 1/2-inch tube pattern and unique fin design allowing
More informationSECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION
SECTION 15990 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the Specifier in correctly specifying Mechanical System Testing Adjusting
More informationINSTALLATION INSTRUCTIONS AH12 WALL MOUNT HOOD
Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer INSTALLATION INSTRUCTIONS AH12 WALL MOUNT HOOD Read All Instructions Thoroughly Before Beginning Installation WARNING
More informationLOW-NOX BURNER RETROFIT CHALLENGE
LOW-NOX BURNER RETROFIT CHALLENGE By Craig Lieb Applications Engineer Zeeco, Inc. Rutland, UK Ryan Roberts Project Engineering Manager Zeeco, Inc. Broken Arrow, OK, U.S.A. Ryan Roberts has more than 20
More informationSenior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1
Table of Contents Page Number(s) Executive Summary 2 Project Background 3 Proposed Depth Alternatives 4 Proposed Depth Redesign 5-7 Justification of Proposed Depth Redesign 8 Proposed Breath Redesign 9
More informationSubmitted to. Texas A&M University at Commerce The Texas A&M University System. Submitted by. Guanghua Wei Craig Campbell David Claridge Dan Turner
ESL-TR-99/12-09 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University at Commerce (TAMU-Commerce) Commerce, Texas Submitted to Texas
More informationINTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies
Pakistan s Largest Manufacturers of Air-Conditioners PACKAGE TYPE UNIT FOR MOBILE APPLICATIONS Provides Turnkey Projects Conceptual Planning to Commissioning of HVACR Projects THE LARGEST MANUFACTURER
More informationSoot Mitigation Strategies
Soot Mitigation Strategies Walter P. Drosjack, P.E. David L. Oar, P.E., F.S.F.P.E. 32 nd Nuclear Air Cleaning Conference June 18-19, 2012 Who is URS? URS is one of the world s largest engineering, construction
More informationGuide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:
Date: 05/21/2001 Time: 02:57:44 PM Job Name: EarthWise VAV Terminal Units Full Spec Location: AnyTown, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SINGLE & DUAL DUCT UNIT
More informationInstrumentation for Nuclear Applications
Instrumentation for Nuclear Applications Nuclear Instrumentation Overview Delta Controls has been designing and manufacturing instrumentation for the power and process industries for over 65 years and
More informationSteam Trap Inspection Methods And Steam Cost Analysis
Steam Trap Inspection Methods And Steam Cost Analysis 14 Hayes Street, Elmsford NY 10523-2536 USA Tel: 914-592-1220 Toll Free USA & Canada 24 Hour Fax Email: Internet 800-223-1325 914-347-2181 info@uesystems.com
More informationINSTRUMENTATION AND CONTROL DEVICES FOR HVAC
PART 1 GENERAL 1.01 RELATED REQUIREMENTS SECTION 23 0913 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC A. Section 26 2717 - Equipment Wiring: Electrical characteristics and wiring connections. 1.02 ADMINISTRATIVE
More informationMarch 2014 AHRI Presents Research Findings at Low-GWP AREP Conference
March 2014 AHRI Presents Research Findings at Low-GWP AREP Conference In addition to its regular research activities, AHRI is conducting the Low-Global Warming Potential Alternative Refrigerants Evaluation
More informationRESNET HERS Rater Sample Test Questions 2
RESNET HERS Rater Sample Test Questions 2 1. Which of the following is the best device for removing standing water from a crawl space? A. Dehumidifier B. Sump pump C. Air-to-air heat exchanger D. Crawl-space
More informationTechnical Presentation on
Technical Presentation on PID _00012345 Heating and refrigeration system using waste heat energy Photo (Author 1) Photo (Author 2) Author 1 Name Author 2 Name Restricted Circulation L&T Technology Services
More informationYARWAY NON-REPAIRABLE DRIP AND TRACER STEAM TRAPS SERIES PB, 29, 129Y AND 29S
SERIES PB, 29, 129Y AND 29S Economical and simplified solutions that offer quality and optimum steam trap service FEATURES 29S 29 Thermostatic traps Pressure assisted fail-open design Freeze proof Easy
More informationSteam Trap Presentation for IDEA Distribution Workshop. Presenter: Joe Radle
Steam Trap Presentation for IDEA Distribution Workshop Presenter: Joe Radle Proper Piping when Reducing Pipe Size Concentric reducer Eccentric reducer Correct Wrong Typical Steam Main Drip Station D Size
More informationWhite Paper. The Victaulic Vortex Fire Suppression System Fire Suppression for Electrical and Electronic Applications
White Paper The Victaulic Vortex Fire Suppression System Fire Suppression for Electrical and Electronic Applications Matthew Puzio, Senior Project Engineer, Fluid Control Technology, Victaulic updated
More informationUNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
More information1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT
Taylor Engineering 1080 Marina Village Parkway, Suite 501 Alameda, CA 94501-1142 (510) 749-9135 Fax (510) 749-9136 LLC HVAC DESIGN INTENT PART 1 - GENERAL 1.1 Overview A. The project consists of a 3-story
More informationCHAPTER 3 BASIC STEAM CYCLE
CHAPTER 3 BASIC STEAM CYCLE To understand steam generation, you must know what happens to the steam after it leaves the boiler. A good way to learn the steam plant on your ship is to trace the path of
More informationINSTY-PAC INTERNAL MOUNT WELDED MULTIPLE TUBE ASSEMBLY
Read and Save These Instructions Sheet No. LSIP-IM INSTY-PAC INTERNAL MOUNT WELDED MULTIPLE TUBE ASSEMBLY INSTALLATION AND ASSEMBLY INSTRUCTIONS Fig. 1 Strainer Secure to AHU/duct casing with 3/8-16 UNC
More informationScrew Compressors AS SERIES. Capacities from: 59 to 124 cfm Pressures from: 80 to 217 psig
Screw Compressors AS SERIES Capacities from: 59 to 124 cfm Pressures from: 80 to 217 psig Rotary Screw Compressor Maximum Reliability and Efficiency For years, customers have relied on Kaeser for reliable
More informationINTRODUCTION. JAU /JCC/JVC Series Jet Fans - for car park ventilation
JAU /JCC/JVC Series Jet Fans - for car park ventilation INTRODUCTION Pacific HVAC Engineering is able to offer a complete solution in car park ventilation at a competitive price with in house developed
More informationAIRPORT OFFICE BUILDING. Smoke Control System. Testing Procedures Manual. September 10, 2016
IMPACT ENGINEERING, INC. AIRPORT OFFICE BUILDING Smoke Control System Testing Procedures Manual September 10, 2016 All Rights Reserved This manual is protected by the U.S. Copyright Law (Title 17 United
More informationTunnel Axial Flow Fan
Tunnel Axial Flow Fan TUNNEL AXIAL FLOW FAN Tunnel fans are an axial flow fans and moves an airstream along the axis of the fan. The air is pressurized by the aerodynamic lift generated by the fan blades,
More informationIndirect Gas-Fired Make-Up Air
Indirect Gas-Fired Make-Up Air Model IG 800 to 7,000 cfm Up to 400,000 Btu/hr Multiple Furnace Control Options Optional Evaporative Cooling May 20041 Product Features Model IG Indirect Gas-Fired Make-Up
More informationInstallation Guide IM 1248
Installation Guide IM 1248 BACnet Thermostat for Heat Pump Units Group: Controls Part Number: IM 1248 Date: August 2015 Table of Contents Installation Guide Heat Pump.... 2 Applicable Models... 2 Mounting
More informationTESTING STEAM TRAPS TO KEEP YOUR SYSTEM OPERATING EFFECTIVELY AND EFFICIENTLY
TESTING STEAM TRAPS TO KEEP YOUR SYSTEM OPERATING EFFECTIVELY AND EFFICIENTLY A steam trap, which is a fully automated condensate drainage device, generally does not require routine maintenance. Steam
More informationSPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT
CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT SECTION 901 GENERAL 901.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration
More informationWorried aboutthe air quality in your schools?
Worried aboutthe air quality in your schools? Now you can breathe a little easier. (And so can everyone else.) EMA Chicago, Inc. The Situation The Environmental Protection Agency Documented that in 1995
More informationKINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION
SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to
More informationEL-TSTAT-8820 Safety & Installation Instructions
EL-TSTAT-8820 Safety & Installation Instructions TABLE OF CONTENTS WI-FI SETUP Wi-Fi Setup 2 INSTALLATION Installation location recommendations 3 Outdoor temperature sensor (included) 3 Remote temperature
More informationPut the V back in HVAC
Put the V back in HVAC V is for Ventilation A system or means of providing fresh air. Webster New Collegiate Dictionary Benjamin Franklin so unwholesome as air in a closed room that has been often breathed
More informationSIMPLICITY FULL MODULARITY?
D E S I G N I N G I N N O V A T I V E S O L U T I O N S AIR CONDITIONING & HEATING SOLUTIONS OR SIMPLICITY FULL MODULARITY? IDROFAN, BECAUSE YOU SHOULD NOT HAVE TO CHOOSE. Hydronic ducted fan coils Cooling
More informationEffects of Kitchen Ventilation on Residential Dwellings
Effects of Kitchen Ventilation on Residential Dwellings Anthony C. Jellen Engineering i Projects Incorporated 1 Personal Background U.S.N. (1994 2000) BS B.S. in Civil Engineering (2005) PHRC employee
More informationDOCUMENT TABLE OF CONTENTS
DOCUMENT 00003 June 16, 2005 TABLE OF CONTENTS DOCUMENT NO. INTRODUCTORY INFORMATION DOCUMENT 00003 TABLE OF CONTENTS DIVISION 1 GENERAL REQUIREMENTS SECTION 01011 SECTION 01025 SSP21.1-1 SECTION 01026
More informationModel: 400E-5M. Bermad Hydraulically Controlled Anti-Columning Deluge Valve, with Easylock Manual Reset. Installation Operation Maintenance
Model: 400E-5M Bermad Hydraulically Controlled Anti-Columning Deluge Valve, with Easylock Manual Reset Installation Operation Maintenance Application Engineering Bermad 1. Safety First BERMAD believes
More informationEnergy Saver 101: Home Energy Audits
Energy Saver 101: Home Energy Audits Take the first step to improving your home s energy efficiency: get a home energy audit. What is a home energy audit? A home energy audit helps you pinpoint where your
More informationCARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.
Volume 5, Issue 1 CARRIER edesign SUITE NEWS Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC Equipment Selection A design challenge sometimes occurs when computing design loads using
More informationRapid transfer port technology
Rapid transfer port technology High Purity day Vught, NL 04 June 2014 1 Objective Presentation of rapid transfer port technology AGENDA What is an RTP History of RTP s How do they work and where are they
More informationTMB Baking TSV Gas Oven TAG Series. Contractor s Utility Requirements
TMB Baking TSV Gas Oven TAG Series Contractor s Utility Requirements NATURAL GAS FIRED - INSTALL INSTRUCTIONS - This Manual is prepared for the use of licensed utility contractors. All gas, electrical,
More informationBasic Input Data Needed to Develop a High Performance Fan/Blower with Low Noise, Energy Saving and High Efficiency
Basic Input Data Needed to Develop a High Performance Fan/Blower with Low Noise, Energy Saving and High Efficiency Haiye Lou TurboMoni Applied Dynamics Lab Abstract It is often happened, when a project
More informationDEMAND CONTROLLED VENTILATION WITHOUT WIRES
DEMAND CONTROLLED VENTILATION WITHOUT WIRES With increased demand for intelligent climate control systems, more and more HVAC installations deploy VAV/VAQ terminals that allow temperature control in such
More informationHVAC OUTDOOR AIR VENTILATION STANDARD. ASHRAE Standard ASHRAE Standard
ASHRAE Standard 62.1-2013 BuildingsOne February 4, 2016 Landlord s HVAC system design capacity shall equal or exceed outdoor air ventilation requirements specified in ASHRAE Standard 62.1-2013 (prospect
More informationSECTION AIR COILS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 82 16 AIR COILS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in the section
More informationModular Supply Make-Up Air Unit
Modular Supply Make-Up Air Unit Model MSX Flexible Design Factory Assembled Heating Options Hot Water Steam Electric Cooling Options Evaporative Direct Expansion Chilled Water November 2009 Product Features
More informationInnovative Boiler & Heat Exchanger Concepts
www.wea-inc.com Wallace Eannace Associates Presents: Innovative Boiler & Heat Exchanger Concepts for Plumbing Applications Bob Barrett, CEM, LEED AP Sales Engineer Wallace Eannace Associates, Inc. www.wea-inc.com
More informationMuseum Archive Dehumidification in Hot & Humid Climates
Museum Archive Dehumidification in Hot & Humid Climates B. K. Browning, PE Principal Engineer KWR Services Austin, Texas ABSTRACT This paper discusses some of the difficulties found with a desiccant dehumidification
More informationAn Overview to Designing Smoke-Control Systems
The following article was published in ASHRAE Journal, June, 2002. Copyright 2002 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes
More informationSCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /
SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL 60202 fpeschulte@aol.com 504/220-7475 A CRITIQUE OF HUGHES ASSOCIATES, INC. PAPER TITLED: Analysis of the Performance of Ganged
More informationCARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems
Volume 6, Issue 1 CARRIER edesign SUITE NEWS Modeling 100% OA Constant Volume Air Systems This article provides an overview of how to model a stand-alone constant air volume (CAV) 100% OA system in HAP.
More informationInfrared Business Tips & Insight
Infrared Business Tips & Insight 2010 Infrared Training Center. All rights reserved. Intended for use by Infrared Training Center customers and prospects only Infrared Business Tips & Insight Presenter:
More informationNOx REDUCTION EXPERIENCE ON NATURAL GAS FIRED TURBO FURNACES
NOx REDUCTION EXPERIENCE ON NATURAL GAS FIRED TURBO FURNACES by D. E. Dorman, Staff Engineer DB Riley, Inc. Presented at the International Joint Power Generation Conference Miami Beach, Florida July 23-25,
More informationGas-Fired Indoor and Outdoor Duct Furnaces
July, 2008 Gas-Fired Indoor and Outdoor Duct Furnaces INDOOR GRAVITY VENTED DFG, DBG, DCG INDOOR SEPARATED COMBUSTION DFS, DBS, DCS OUTDOOR GRAVITY AND POWER EXHAUSTED H Series table of contents A complete
More informationBrown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS
SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett
More informationHow to ensure Thermal Comfort in buildings with CFD
How to ensure Thermal Comfort in buildings with CFD Using CFD Simulations to analyze and improve HVAC Systems Simulation in your browser How to Ensure Thermal Comfort in Buildings with CFD How to use CFD
More informationVALIDATION OF FINITE ELEMENT MODELS OF INJURY RISK IN VEHICLE-ROADSIDE BARRIER CRASHES
VALIDATION OF FINITE ELEMENT MODELS OF INJURY RISK IN VEHICLE-ROADSIDE BARRIER CRASHES Qian Wang, Hampton C. Gabler Virginia Tech-Wake Forest, Center for Injury Biomechanics Blacksburg, VA 24061 ABSTRACT
More informationEconomical and simplified solutions that offer quality and optimum steam trap service.
Economical and simplified solutions that offer quality and optimum steam trap service. It All Comes Down To Protection Regardless of the temperature and pressure characteristics of steam line drips or
More informationInstallation Instructions
FAVXXR6C2100-A01 Vent Damper and Control Installation Instructions FAMILIARIZE YOURSELF WITH THE INSTALLATION INSTRUCTIONS BEFORE STARTING ATTENTION INSTALLER: This product must be installed by a qualified
More informationFire Engineering in High Rise 15 November 2013
Fire Engineering in High Rise 15 November 2013 Neal Butterworth Arup UK www.arup.com Neal.Butterworth@arup.com Contents How do we protect against fire? How do we know this works? Why evacuate? What assumptions
More informationCALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS
CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS Presented to: Presented by: Sargon Ishaya, PE www.pragmaticprofessionalengineers.com Introduction Today s Agenda Overview Review
More informationExecutive Summary
Prepared by: Proctor Engineering Group, Ltd. San Rafael, CA 94901 (415) 451-2480 Investigation of Coil Failures - A Whole Systems Approach Prepared for: Geothermal Heat Pump Consortium Final Report July
More informationOff Design Operation of Hybrid Noncondensable Gas Removal Systems for Flash Steam Cycle Geothermal Power Plants
GRC Transactions, Vol. 40, 2016 Off Design Operation of Hybrid Noncondensable Gas Removal Systems for Flash Steam Cycle Geothermal Power Plants Jason Project Engineer, Vooner FloGard Corporation, Charlotte
More informationLife Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015. Peter McDonnell, PE, LEED AP BD+C McClure Engineering
Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015 Peter McDonnell, PE, LEED AP BD+C McClure Engineering UL DAMPER TEST STANDARDS UL 555 - FIRE DAMPERS UL555S SMOKE DAMPERS UL555C CEILING
More informationCONTENTS. B. System Design and Performance Requirements
15625 Water Chillers This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes
More informationStudy of Hot-air Recirculation around Off-road Tier-4 Diesel Engine Unit Using CFD Abbreviations Keywords Abstract Introduction and Background
Study of Hot-air Recirculation around Off-road Tier-4 Diesel Engine Unit Using CFD Siddharth Jain, Yogesh Deshpande, Atul Bokane, Arun Kumar Santharam, and Deepak Babar, Halliburton Abbreviations: Computational
More informationStart today and start saving!
Northeast Oklahoma REC s Do It Yourself Home Energy Audit Pllattiinum Levell Start today and start saving! First project (circle and initial when completed) Inadequate Ducts Objective: Check your ductwork
More informationStudy and Design Considerations of HRSG Evaporators in Fast Start Combined Cycle Plants. Govind Rengarajan, P.E.CEM, Dan Taylor
Study and Design Considerations of HRSG Evaporators in Fast Start Combined Cycle Plants Govind Rengarajan, P.E.CEM, Dan Taylor CMI Energy, Erie PA 1651 Bernd Pankow P.E, Pankow Engineering Abstract Combined
More informationISLAND MOUNT RANGE HOOD. This manual is made with 100 % recycled paper. Electronic version of this manual is available at:
ISLAND MOUNT RANGE HOOD This manual is made with 100 % recycled paper. Electronic version of this manual is available at: www.cosmoappliances.com Thank You Thank you for your purchase. We know that you
More informationWESTIN HOTEL. Smoke Control System. Testing Procedures Manual. October 10, Copyright Impact Engineering, Inc All Rights Reserved
IMPACT ENGINEERING, INC. WESTIN HOTEL Smoke Control System Testing Procedures Manual October 10, 2016 Copyright Impact Engineering, Inc. 2016 All Rights Reserved This manual is protected by the U.S. Copyright
More informationUNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:
SECTION 233423 - HVAC POWER VENTILATORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 PERFORMANCE REQUIREMENTS A. Operating
More informationAqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND
Aqua Balance AquaBalance TM CONTROL MODULE QUICK START GUIDE 10 1 Domestic Hot Water temperature setpoint decreasing button 2 Domestic Hot Water temperature setpoint increasing button 3 Central Heating
More information