50 Hz ACS MODEL: R22 R407c AIR COOLED CHILLERS INSTALLATION, OPERATION & MAINTENANCE MANUAL WITH SCROLL COMPRESSORS

Size: px
Start display at page:

Download "50 Hz ACS MODEL: R22 R407c AIR COOLED CHILLERS INSTALLATION, OPERATION & MAINTENANCE MANUAL WITH SCROLL COMPRESSORS"

Transcription

1 Products That Perform...By People Who Care Form No: MM0423C INSTALLATION, OPERATION & MAINTENANCE MANUAL AIR COOLED CHILLERS WITH SCROLL COMPRESSORS MODEL: ACS R22 R407c 50 Hz

2 MANUAL INDEX Description Page 1.0 INTRODUCTION PHYSICAL SPECIFICATIONS INSTALLATION 2.1 GENERAL INSPECTION RIGGING General ACS Rigging and Moving SPACE REQUIREMENTS AND CLEARANCE General ACS FOUNDATION Air Cooled Units VIBRATION ISOLATION PIPING CONNECTION Water Connections Chilled Water Piping Water Connections Multiple Packaged Chillers Parallel Chilled Water Flow Units Series Chilled Water Flow Units Water Quality ELECTRICAL CONNECTIONS General REQUEST FOR START-UP REPRESENTATIVE OPERATION 3.1 GENERAL UNIT PIPING AIR COOLED PACKAGE START-UP SYSTEM START-UP LUBRICATION Oil Level Oil Type SYSTEM FLOW RATE SYSTEM CONTROL Capacity Control Solid-State operating Thermostat General Opstat Setting ELECTRICAL CONTROLS Electronic Thermostat IR32 Electronic Thermostat IR32 Electronic Thermostat Troubleshooting ACS Typical Wiring Schematic MAINTENANCE 4.1 GENERAL PERIODIC INSPECTION MONTHLY INSPECTION VESSEL MAINTENANCE General Evaporator Cleaning AIR COOLED CONDENSER CLEANING ELECTRICAL MALFUNCTION REFRIGERANT CHARGING General Air Cooled Package TROUBLE SHOOTING SAMPLE LOG SHEET SCHEMATIC DIAGRAM, GRAPH AND TABLE Figure ACS Rigging Figure 2.4.2A ACS Space Requirements Figure 2.4.2B ACS Dimensional Data Figure ACS Weight Distribution Figure ACS Typical Piping Schematic Figure 3.6 Water Side Pressure Drop Figure Controller Front Panel Table 1.1 Product Identification... 3 Table Capacity Control Table 4.4 Pressure/ Temperature Properties

3 1.0 INTRODUCTION This manual is prepared to provide all the necessary information of installation, operation and maintenance of the latest generation of Dunham- Bush air-cooled chillers with scroll compressors. In order to be able to make full use of the manual, you must first determine your unit model number from the unit name plate. Your Dunham-Bush package has been manufactured under a stringent quality control system. Each packaged chiller is performance tested at the factory at the specified field operating conditions as a final verification of reliability. If the package is installed, operated and maintained with care and attention to the instructions contained here in, it will yield many years of satisfactory service. It is assumed that the reader of this manual and those who install, operate and maintain the equipment have a basic understanding of the principles of air conditioning, refrigeration and electrical controls. TABLE 1.1 PRODUCTION IDENTIFICATION AC S 30-5 E P Air Cooled Packaged DX Chiller Blank - R22 P - R407C Scroll Compressor H - High Efficiency E - Energy Saving Nominal Capacity 5-50Hz 6-60Hz - 3 -

4 1.0 INTRODUCTION 1.1 PHYSICAL SPECIFICATIONS ENERGY SAVING R22 MODEL ACS 10-5-E 13-5-E 15-5-E 20-5-E 23-5-E 26-5-E COMPRESSOR MODEL (QTY) SPA (2) SPB (2) SPC (2) SPD (2) SPE (2) SPBB (2) RPM MIN. % UNIT CAPACITY REDUCTION 50% 50% 50% 50% 50% 25% NO. OF REFRIGERANT CIRCUIT EVAPORATOR MODEL HDD03 HDD03 HDD04 HDE03 HDE04 HDF03 WATER CONNECTOR INCH[MM] 3[76.2] 3[76.2] 3[76.2] 3[76.2] 3[76.2] 3[76.2] NOM. WATER FLOW / PD (GPM)/(FT IN WG) [m³/hr / kpa] 24.7 / 8.7 [5.6 / 26.0] 29.8 / [6.8 / 36.2] 34.6 / 7.5 [7.9 / 22.4] 42.8 / 7.6 [9.7 / 22.8] 52.9 / 14.2 [12.0 / 42.3] 61.3 / 12.2 [13.9 / 36.6] MIN/MAX. WATER FLOW (GPM)/[m³/hr] 19.5 / 58.1 [4.43 / 13.2] 19.3 / 58.1 [4.4 / 13.2] 29.1 / 87.2 [6.6 / 19.9] 37.2 / [8.5 / 25.3] 37.2 / [8.5 / 25.3] 42.0 / [9.5 / 28.6] MIN/MAX. WATER PD (FT IN WG) / [kpa] 5.66 / [16.9 / 120.5] 5.6 / [16.7 / 120.4] 5.48 / [17.3 / 118.9] 5.93 / [17.7 / 128.6] 7.53 / 54.7 [22.5 / 163.5] 6.2 / 44.5 [18.6 / 133.0] CONDENSER COIL ROWS DEEP/ TOTAL FA FT²[M²] 2 / 19.25[1.8] 3 / 19.25[1.8] 3/ 19.25[1.8] 3 / 26.5[2.5] 4 / 26.5[2.5] 3 / 44.4[4.1] TOTAL CFM NO OF FAN FAN DIA INCH[MM] 26.0[660.4] 26.0[660.4] 26.0[660.4] 26.0[660.4] 26.0[660.4] 26.0[660.4] MOTOR HP (QTY) 5/8 (2) 5/8 (2) 5/8 (2) 5/8 (3) 5/8 (3) 5/8 (4) FAN FLA, AMP (QTY) 2 (2) 2 (2) 2 (2) 2 (3) 2 (3) 2 (4) MIN. AMBIENT TEMP. ( F) (WITH FAN CYCLING AND SOLENOID CONTROL) ELECTRICAL NOM. VOLTAGE 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 RLA/CIRCUIT (QTY), AMPS 25.3 (1) 29.8 (1) 34.3 (1) 40.3 (1) 48.2 (1) 29.8 (2) UNIT MAX. INRUSH GENERAL UNIT LENGTH INCH[MM] 87.5[2222] 87.5[2222] 87.5[2222] 117.5[2984] 117.5[2984] 102[2591] UNIT WIDTH INCH[MM] 36[914] 36[914] 36[914] 38[965] 38[965] 88[2235] UNIT HEIGHT INCH[MM] 67.5[1714] 67.5[1714] 67.5[1714] 70[1778] 70[1778] 71[1803] SHIPPING WEIGHT LB[KG] 1920[873] 2032[924] 2062[937] 2880[1309] 3043[1383] 3742[1701] OPERATING WEIGHT LB[KG] 1942[883] 2052[933] 2081[946] 2935[1334] 3100[1409] 3789[1722] OPERATING CHARGE R22 LB[KG] 22[10] 29[13] 33[15] 44[20] 51[23] 57[26] - 4 -

5 1.0 INTRODUCTION ENERGY SAVING R22 MODEL ACS 30-5-E 40-5-E 46-5-E 55-5-E 60-5-E 70-5-E COMPRESSOR MODEL (QTY) SPCC (2) SPDD (2) SPEE (2) SPDD (3) SPDE (3) SPEE (3) RPM MIN. % UNIT CAPACITY REDUCTION 25% 25% 25% 16.7% 16.7% 16.7% NO. OF REFRIGERANT CIRCUIT EVAPORATOR MODEL HDF03 HDF04 HDH04 XTK08 XTK08 XTM09 WATER CONNECTOR INCH[MM] 3[76.2] 3[76.2] 4[101.6] 4[101.6] 4[101.6] 5[127.0] NOM. WATER FLOW / PD (GPM) /(FT IN WG) [m³/hr / kpa] 69.3 / 15.3 [15.8 / 45.6] 84.6 / 26.8 [19.2 / 79.9] / 13.2 [23.4 / 39.5] / 7.5 [29.9 / 22.5] / 8.9 [33.0 / 26.9] 163.4/ 10.6 [37.1/ 31.7] MIN/MAX. WATER FLOW (GPM)/[m³/hr] 42.0 / [9.5 / 28.6] 42.0 / [9.5 / 28.6] 62.5 / [14.2 / 42.3] / [26.2 / 78.4] / [26.2 / 78.4] / [23.2 / 69.8] MIN/MAX. WATER PD (FT IN WG) / [kpa] 6.23 / 44.5 [18.6 / 133.0] 7.62 / [22.8 / 163.0] 5.41 / [16.2 / 114.9] 6.0 / 41.7 [ / 124.6] 6.0 / 41.7 [ / 124.6] 4.6 / 32.3 [13.7 / 96.5] CONDENSER COIL ROWS DEEP/ TOTAL FA FT²[M²] 3 / 53.3[5.0] 3 / 53.3[5.0] 4 / 62.2[5.8] 2 / 102.7[9.5] 3 / 102.7[9.5] 3 / 102.7[9.5] TOTAL CFM NO OF FAN FAN DIA INCH[MM] 26.0[660.4] 26.0[660.4] 26.0[660.4] 30.0 [762] 30.0 [762] 30.0 [762] MOTOR HP (QTY) 5/8 (4) 5/8 (4) 5/8 (4) 1.5(6) 1.5(6) 1.5(6) FAN FLA, AMP (QTY) 2 (4) 2 (4) 2 (4) 3.2 (6) 3.2 (6) 3.2 (6) MIN. AMBIENT TEMP. ( F) (WITH FAN CYCLING AND SOLENOID CONTROL) ELECTRICAL NOM. VOLTAGE 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 RLA/CIRCUIT (QTY), AMPS 34.3 (2) 40.3 (2) 48.2 (2) 40.3 (3) 44.9 (3) 48.2 (3) UNIT MAX. INRUSH GENERAL UNIT LENGTH INCH[MM] 102[2591] 102[2591] 102[2591] 136[3454] 136[3454] 136[3454] UNIT WIDTH INCH[MM] 88[2235] 88[2235] 88[2235] 88[2235] 88[2235] 88[2235] UNIT HEIGHT INCH[MM] 71[1803] 71[1803] 71[1803] 78.5[1994] 78.5[1994] 78.5[1994] SHIPPING WEIGHT LB[KG] 3962[1801] 4319[1963] 4481[2037] 6257[2838] 6389[2898] 6527[2961] OPERATING WEIGHT LB[KG] 4026[1830] 4398[1999] 4560[2073] 6499[2948] 6651[3017] 6770[3071] OPERATING CHARGE R22 LB[KG] 66[30] 88[40] 102[46] 122[55] 132[60] 154[70] - 5 -

6 1.0 INTRODUCTION HIGH EFFICIENCY R22 MODEL ACS 10-5-H 13-5-H 15-5-H 20-5-H 23-5-H 26-5-H COMPRESSOR MODEL (QTY) SPA (2) SPB (2) SPC (2) SPD (2) SPE (2) SPBB (2) RPM MIN. % UNIT CAPACITY REDUCTION 50% 50% 50% 50% 50% 25% NO. OF REFRIGERANT CIRCUIT EVAPORATOR MODEL HDD03 HDD03 HDD04 HDE03 HDE04 HDF03 WATER CONNECTOR INCH[MM] 3[76.2] 3[76.2] 3[76.2] 3[76.2] 3[76.2] 3[76.2] NOM. WATER FLOW / PD (GPM)/(FT IN WG) [m³/hr / kpa] 25.7 / 9.31 [5.8 / 27.8] 31.0 / 6.2 [7.0 / 18.4] 35.6 / 21.5 [8.1 / 64.3] 45.2 / 10.7 [10.3 / 32.0] 53.6 / 9.6 [12.2 / 28.7] 60.9/ 12.1 [13.8 / 36.1] MIN/MAX. WATER FLOW (GPM)/[m³/hr] 19.5 / 58.1 [4.4 / 13.2] 29.1 / 87.2 [6.6/ 19.8] 19.5 / 58.1 [4.4 / 13.2] 37.2 / [8.5 / 25.4] 42.0 / [9.5 / 28.6] 42 / [9.5 / 28.6] MIN/MAX. WATER PD (FT IN WG) / [kpa] 5.7 / 40.3 [17.0 / 120.5] 5.5 / 39.8 [16.4 / 119.0] 7.3 / 52 [21.8 / 155.4] 7.5 / 54.7 [22.4 / 163.5] 6.2 / 44.5 [18.5 / 133.0] 6.2 / 44.5 [18.5 / 133.0] CONDENSER COIL ROWS DEEP/ TOTAL FA FT²[M²] 3 / 19.25[1.8] 3 / 19.25[1.8] 4 / 19.25[1.8] 4 / 26.5[2.5] 4 / 26.5[2.5] 3 / 44.4[4.1] TOTAL CFM NO OF FAN FAN DIA INCH[MM] 26.0[660.4] 26.0[660.4] 26.0[660.4] 26.0[660.4] 26.0[660.4] 26.0[660.4] MOTOR HP (QTY) 5/8 (2) 5/8 (2) 5/8 (2) 5/8 (3) 5/8 (3) 5/8 (4) FAN FLA, AMP (QTY) 2 (2) 2 (2) 2 (2) 2 (3) 2 (3) 2 (4) MIN. AMBIENT TEMP. ( F) (WITH FAN CYCLING AND SOLENOID CONTROL) ELECTRICAL NOM. VOLTAGE 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 RLA/CIRCUIT (QTY), AMPS 24.4 (1) 28.6 (1) 32.9 (1) 38.5 (1) 46.0 (1) 28.6 (2) UNIT MAX. INRUSH GENERAL UNIT LENGTH INCH[MM] 87.5[2222] 87.5[2222] 87.5[2222] 117.5[2984] 117.5[2984] 102[2591] UNIT WIDTH INCH[MM] 36[914] 36[914] 36[914] 38[965] 38[965] 88[2235] UNIT HEIGHT INCH[MM] 67.5[1714] 67.5[1714] 67.5[1714] 70[1778] 70[1778] 71[1803] SHIPPING WEIGHT LB[KG] 2085[948] 2207[1003] 2239[1018] 3128[1422] 3305[1502] 3742[1701] OPERATING WEIGHT LB[KG] 2109[959] 2228[1013] 2260[1027] 3187[1449] 3367[1530] 3789[1722] OPERATING CHARGE R22 LB[KG] 22[10] 29[13] 33[15] 44[20] 51[23] 58[26] - 6 -

7 1.0 INTRODUCTION HIGH EFFICIENCY R22 MODEL ACS 30-5-H 40-5-H 46-5-H 55-5-H 60-5-H 70-5-H COMPRESSOR MODEL (QTY) SPCC (2) SPDD (2) SPEE (2) SPDD (3) SPDE (3) SPEE (3) RPM MIN. % UNIT CAPACITY REDUCTION 25% 25% 25% 16.7% 16.7% 16.7% NO. OF REFRIGERANT CIRCUIT EVAPORATOR MODEL HDF03 HDF04 HDH04 XTK08 XTK08 XTM09 WATER CONNECTOR INCH[MM] 3[76.2] 4[101.6] 4[101.6] 4[101.6] 4[101.6] 5[127.0] NOM. WATER FLOW / PD (GPM) /(FT IN WG) [m³/hr / kpa] 71.6 / 9.9 [16.3 / 29.6] 88.9 / 10.2 [20.2 / 30.4] / 7.5 [25.1 / 22.3] / 8 [31.9 / 23.9] / 13.2 [33.8 / 39.5] / 6.6 [37.7 / 19.7] MIN/MAX. WATER FLOW (GPM)/[m³/hr] 56.0 / [12.7 / 38.1] 62.0 / [14.1 / 42.4] 85.3 / [19.4 / 58.2] / [26.2 / 78.4] 96.1 / [21.8 / 65.5] / [26.4 / 78.9] MIN/MAX. WATER PD (FT IN WG) / [kpa] 6.4 / 46.0 [19.1 / 137.5] 5.3 / 38.6 [16.0 / 115.4] 4.7 / 33.7 [14.0 / 100.7] 6 / 41.7 [17.9 / 124.6] 6.1 / 43 [18.4 / 128.5] 5.1 / 35.3 [15.2 / 105.6] CONDENSER COIL ROWS DEEP/ TOTAL FA FT²[M²] 3 / 53.3[5.0] 4 / 62.2[5.8] 4 / 62.2[5.8] 3 / [9.5] 3 /102.7 [9.5] 3 / [9.5] TOTAL CFM NO OF FAN FAN DIA INCH[MM] 26.0[660.4] 26.0[660.4] 30 [762] 30 [762] 30 [762] 30 [762] MOTOR HP (QTY) 5/8 (4) 5/8 (4) 1.5(4) 1.5(6) 1.5(6) 1.5(6) FAN FLA, AMP (QTY) 2 (4) 2 (4) 3.2 (4) 3.2 (6) 3.2 (6) 3.2 (6) MIN. AMBIENT TEMP. ( F) (WITH FAN CYCLING AND SOLENOID CONTROL) ELECTRICAL NOM. VOLTAGE 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 RLA/CIRCUIT (QTY), AMPS 32.9 (2) 38.5 (2) 46 (2) 40.3 (3) 44.9 (3) 48.2 (3) UNIT MAX. INRUSH GENERAL UNIT LENGTH INCH[MM] 102[2591] 102[2591] 102[2591] 136[3454] 136[3454] 136[3454] UNIT WIDTH INCH[MM] 88[2235] 88[2235] 88[2235] 88[2235] 88[2235] 88[2235] UNIT HEIGHT INCH[MM] 71[1803] 71[1803] 71[1803] 76.5[1943] 76.5[1943] 76.5[1943] SHIPPING WEIGHT LB[KG] 4303[1956] 4690[2132] 4866[2212] 6257[2838] 6389[2898] 6527[2961] OPERATING WEIGHT LB[KG] 4372[1987] 4776[2171] 4952[2251] 6499[2948] 6651[3017] 6770[3071] OPERATING CHARGE R22 LB[KG] 66[30] 88[40] 102[46] 122[55] 132[60] 154[70] - 7 -

8 1.0 INTRODUCTION ENERGY SAVING R407c MODEL ACS 10-5-E-P 13-5-E-P 15-5-E-P 20-5-E-P 23-5-E-P 26-5-E-P COMPRESSOR MODEL (QTY) SPAE (2) SPBE (2) SPCE (2) SPDE (2) SPEE (2) SPBBE (2) RPM MIN. % UNIT CAPACITY REDUCTION 25% 25% 25% 25% 25% 25% NO. OF REFRIGERANT CIRCUIT EVAPORATOR MODEL HDD03 HDD03 HDD04 HDE03 HDE04 HDE04 WATER CONNECTOR INCH[MM] 3 [76.2] 3 [76.2] 3 [76.2] 3 [76.2] 3 [76.2] 3 [76.2] NOM. WATER FLOW / PD (GPM)/(FT IN WG) [m³/hr / kpa] 25.0 / 8.85 [5.7 / 26.5] 29.6 / 22.1 [6.8 / 66.1] 34.2 / 7.4 [7.8 / 22.1] 42 / 7.37 [9.6 / 22.0] 51.2 / 5.6 [11.6 / 16.7] 59.7 / 17.6 [13.6 / 52.6] MIN/MAX. WATER FLOW (GPM)/[m³/hr] 19.4 / 58.1 [4.4 / 13.3] 14.7 / 43.7 [3.3 / 9.9] 29.1 / 87.2 [6.6 / 19.9] 37.2 / [8.5 / 25.5] 49.7 / [11.3 / 33.9] 37.2 / [8.5 / 25.4] MIN/MAX. WATER PD (FT IN WG) / [kpa] 5.63 / [16.8 / 120.5] 6.3 / 44.6 [18.8 / 133.3] 5.48 / [17.3 / 118.9] 5.93 / [17.7 / 128.6] 5.3 / 38.8 [15.8 / 116.0] 7.5 / 54.7 [22.4 / 163.5] CONDENSER COIL ROWS DEEP/ TOTAL FA FT²[M²] 2 / 19.25[1.8] 3 / 19.25[1.8] 3/ 19.25[1.8] 3 / 26.5[2.5] 4 / 26.5[2.5] 3 / 44.4[4.1] TOTAL CFM NO OF FAN FAN DIA INCH[MM] 26.0[660.4] 26.0[660.4] 26.0[660.4] 26.0[660.4] 26.0[660.4] 26.0[660.4] MOTOR HP (QTY) 5/8 (2) 5/8 (2) 5/8 (2) 5/8 (3) 5/8 (3) 5/8 (4) FAN FLA, AMP (QTY) 2 (2) 2 (2) 2 (2) 2 (3) 2 (3) 2 (4) MIN. AMBIENT TEMP. ( F) (WITH FAN CYCLING AND SOLENOID CONTROL) ELECTRICAL NOM. VOLTAGE 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 RLA/CIRCUIT (QTY), AMPS 25.3 (1) 29.8 (1) 34.3 (1) 40.3 (1) 48.2 (1) 29.8 (2) UNIT MAX. INRUSH GENERAL UNIT LENGTH INCH[MM] 87.5[2222] 87.5[2222] 87.5[2222] 117.5[2984] 117.5[2984] 102[2591] UNIT WIDTH INCH[MM] 36[914] 36[914] 36[914] 38[965] 38[965] 88[2235] UNIT HEIGHT INCH[MM] 67.5[1714] 67.5[1714] 67.5[1714] 70[1778] 70[1778] 71[1803] SHIPPING WEIGHT LB[KG] 1920[873] 2032[924] 2062[937] 2880[1309] 3043[1383] 3742[1701] OPERATING WEIGHT LB[KG] 1942[883] 2052[933] 2081[946] 2935[1334] 3100[1409] 3789[1722] OPERATING CHARGE R407C LB[KG] 22[10] 29[13] 33[15] 44[20] 51[23] 58[26] - 8 -

9 1.0 INTRODUCTION ENERGY SAVING R407C MODEL ACS 30-5-E-P 40-5-E-P 46-5-E-P 55-5-E-P 60-5-E-P 70-5-E-P COMPRESSOR MODEL (QTY) SPCCE (2) SPDDE (2) SPEEE (2) SPDDE (3) SPDEE (3) SPEEE (3) RPM MIN. % UNIT CAPACITY REDUCTION 25% 25% 25% 16.7% 16.7% 16.7% NO. OF REFRIGERANT CIRCUIT EVAPORATOR MODEL HDF04 HDH03 HDH04 XTK08 XTK08 XTM09 WATER CONNECTOR INCH[MM] 3 [76.2] 4 [101.6] 4 [101.6] 4 [101.6] 4 [101.6] 5 [127.0] NOM. WATER FLOW / PD (GPM) /(FT IN WG) [m³/hr / kpa] 69.7 / 9.4 [15.8 / 28.2] 83.6 / 17.3 [19.0 / 51.7] / 13.0 [23.1 / 38.9] / 10.4 [29.5 / 31.1] 143 / 12.4 [32.5 / 37.1] / 10.4 [36.9 / 31.1] MIN/MAX. WATER FLOW (GPM)/[m³/hr] 56.0 / [12.7 / 38.2] 46.6 / [10.6 / 31.8] 62.5 / [14.2 / 42.4] 96.1 / [21.8 / 65.5] 96.1 / [21.8 / 65.5] / [23.3 / 69.8] MIN/MAX. WATER PD (FT IN WG) / [kpa] 6.4 / 46.2 [19.0 / 138.1] 6.1 / 43.3 [18.2 / 129.5] 5.4 / 38.6 [16.1 / 115.3] 6.1 / 43 [18.4 / 128.5] 6.1 / 43 [18.4 / 128.5] 4.6 / 32.3 [13.7 / 96.5] CONDENSER COIL ROWS DEEP/ TOTAL FA FT²[M²] 3 / 53.3[5.0] 4 / 53.3[5.0] 4 / 62.2[5.8] 2 / [9.5] 3 /102.7 [9.5] 3 / [9.5] TOTAL CFM NO OF FAN FAN DIA INCH[MM] 26.0[660.4] 26.0[660.4] 26.0[660.4] 30 [762] 30 [762] 30 [762] MOTOR HP (QTY) 5/8 (4) 5/8 (4) 5/8 (4) 1.5(6) 1.5(6) 1.5(6) FAN FLA, AMP (QTY) 2 (4) 2 (4) 2 (4) 3.2 (6) 3.2 (6) 3.2 (6) MIN. AMBIENT TEMP. ( F) (WITH FAN CYCLING AND SOLENOID CONTROL) ELECTRICAL NOM. VOLTAGE 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 RLA/CIRCUIT (QTY), AMPS 34.3 (2) 40.3 (2) 48.2 (2) 40.3 (3) 44.9 (3) 48.2 (3) UNIT MAX. INRUSH GENERAL UNIT LENGTH INCH[MM] 102[2591] 102[2591] 102[2591] 136[3454] 136[3454] 136[3454] UNIT WIDTH INCH[MM] 88[2235] 88[2235] 88[2235] 88[2235] 88[2235] 88[2235] UNIT HEIGHT INCH[MM] 71[1803] 71[1803] 71[1803] 76.5[1943] 76.5[1943] 76.5[1943] SHIPPING WEIGHT LB[KG] 3962[1801] 4319[1963] 4481[2037] 6257[2838] 6389[2898] 6527[2961] OPERATING WEIGHT LB[KG] 4026[1830] 4398[1999] 4560[2073] 6499[2948] 6651[3017] 6770[3071] OPERATING CHARGE R407C LB[KG] 66[30] 88[40] 102[46] 122[55] 132[60] 154[70] - 9 -

10 1.0 INTRODUCTION HIGH EFFICIENCY R407c MODEL ACS 10-5-H-P 13-5-H-P 15-5-H-P 20-5-H-P 23-5-H-P 26-5-H-P COMPRESSOR MODEL (QTY) SPAE (2) SPBE (2) SPCE (2) SPDE (2) SPEE (2) SPBBE (2) RPM MIN. % UNIT CAPACITY REDUCTION 50% 50% 50% 50% 50% 25% NO. OF REFRIGERANT CIRCUIT EVAPORATOR MODEL HDD03 HDD03 HDD04 HDE03 HDE04 HDE04 WATER CONNECTOR INCH[MM] 3 [76.2] 3 [76.2] 3 [76.2] 3 [76.2] 3 [76.2] 3 [76.2] NOM. WATER FLOW / PD (GPM)/(FT IN WG) [m³/hr / kpa] 25.9 / [5.9 / 52.4] 31.2 / 17 [7.1 / 50.8] 36.5 / 16.0 [8.3 / 47.7] 44.5 / 22.7 [10.1 / 67.9] 53.3 / 9.5 [12.1 / 28.5] 63.7 / 19.8 [14.5 / 59.1] MIN/MAX. WATER FLOW (GPM)/[m³/hr] 14.7 / 43.6 [3.4 / 10.0] 19.5 / 58.1 [4.5 / 13.3] 25.0 / 74.6 [5.7 / 17.0] 25.0 / 74.6 [5.7 / 17.0] 42.0 / [9.5 / 28.6] 37.2 / [8.5 / 25.4] MIN/MAX. WATER PD (FT IN WG) / [kpa] 6.33 / [18.9 / 132.6] 7.28 / [21.8 / 155.3] 8.1 / 57.7 [24.2 / 172.4] 8.1 / 57.7 [24.2 / 172.4] 6.2 / 44.5 [18.6 / 133.1] 7.5 / 54.7 [22.4 / 163.5] CONDENSER COIL ROWS DEEP/ TOTAL FA FT²[M²] 3 / 19.25[1.8] 3 / 19.25[1.8] 4 / 19.25[1.8] 4 / 26.5[2.5] 4 / 26.5[2.5] 3 / 44.4[4.1] TOTAL CFM NO OF FAN FAN DIA INCH[MM] 26.0[660.4] 26.0[660.4] 26.0[660.4] 26.0[660.4] 26.0[660.4] 26.0[660.4] MOTOR HP (QTY) 5/8 (2) 5/8 (2) 5/8 (2) 5/8 (3) 5/8 (3) 5/8 (4) FAN FLA, AMP (QTY) 2 (2) 2 (2) 2 (2) 2 (3) 2 (3) 2 (4) MIN. AMBIENT TEMP. ( F) (WITH FAN CYCLING AND SOLENOID CONTROL) ELECTRICAL NOM. VOLTAGE 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 RLA/CIRCUIT (QTY), AMPS 24.4 (1) 28.6 (1) 32.9 (1) 38.5 (1) 46.0 (1) 28.6 (2) UNIT MAX. INRUSH GENERAL UNIT LENGTH INCH[MM] 87.5[2222] 87.5[2222] 87.5[2222] 117.5[2984] 117.5[2984] 102[2591] UNIT WIDTH INCH[MM] 36[914] 36[914] 36[914] 38[965] 38[965] 88[2235] UNIT HEIGHT INCH[MM] 67.5[1714] 67.5[1714] 67.5[1714] 70[1778] 70[1778] 71[1803] SHIPPING WEIGHT LB[KG] 2085[948] 2207[1003] 2239[1018] 3128[1422] 3305[1502] 3742[1701] OPERATING WEIGHT LB[KG] 2109[959] 2228[1013] 2260[1027] 3187[1449] 3367[1530] 3789[1722] OPERATING CHARGE R407C LB[KG] 22[10] 29[13] 33[15] 44[20] 51[23] 58[26]

11 1.0 INTRODUCTION HIGH EFFICIENCY R407C MODEL ACS 30-5-H-P 40-5-H-P 46-5-H-P 55-5-H-P 60-5-H-P 70-5-H-P COMPRESSOR MODEL (QTY) SPCCE (2) SPDDE (2) SPEEE (2) SPDDE (3) SPDEE (3) SPEEE (3) RPM MIN. % UNIT CAPACITY REDUCTION 25% 25% 25% 16.7% 16.7% 16.7% NO. OF REFRIGERANT CIRCUIT EVAPORATOR MODEL HDF04 HDH03 HDH04 XTK08 XTK08 XTM09 WATER CONNECTOR INCH[MM] 3 [76.2] 4 [101.6] 4 [101.6] 4[101.6] 4[101.6] 5[127.0] NOM. WATER FLOW / PD (GPM) /(FT IN WG) [m³/hr / kpa] 73.7 / 10.4 [16.8 / 31.1] 90.9 / 10.6 [20.7 / 31.6] 110.1/ 7.4 [25.0 / 22.1] / 7.8 [31.6 / 23.3] / 9 [33.0 / 26.9] / 9.6 [37.8 / 28.7] MIN/MAX. WATER FLOW (GPM)/[m³/hr] 56.0 / [12.7 / 38.1] 62.0 / [14.1 / 42.4] 85.5 / [19.4 / 58.2] / [26.2 / 78.4] / [26.2 / 78.4] / [26.4 / 78.9] MIN/MAX. WATER PD (FT IN WG) / [kpa] 6.4 / 46.0 [19.1 / 137.5] 5.3 / 38.6 [16.0 / 115.4] 4.7 / 33.7 [14.0 / 100.7] 6 / 41.7 [17.9 / 124.6] 6 / 41.7 [17.9 / 124.6] 5.1 / 35.3 [15.2 / 105.6] CONDENSER COIL ROWS DEEP/ TOTAL FA FT²[M²] 3 / 53.3[5.0] 4 / 62.2[5.8] 4 / 62.2[5.8] 3 / [9.5] 3 /102.7 [9.5] 4 / [9.5] TOTAL CFM NO OF FAN FAN DIA INCH[MM] 26.0[660.4] 26.0[660.4] 30 [762] 30 [762] 30 [762] 30 [762] MOTOR HP (QTY) 5/8 (4) 5/8 (4) 1.5(4) 1.5(6) 1.5(6) 1.5(6) FAN FLA, AMP (QTY) 2 (4) 2 (4) 3.2 (4) 3.2 (6) 3.2 (6) 3.2 (6) MIN. AMBIENT TEMP. ( F) (WITH FAN CYCLING AND SOLENOID CONTROL) ELECTRICAL NOM. VOLTAGE 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 RLA/CIRCUIT (QTY), AMPS 32.9 (2) 38.5 (2) 46 (2) 40.3 (3) 44.9 (3) 48.2 (3) UNIT MAX. INRUSH GENERAL UNIT LENGTH INCH[MM] 102[2591] 102[2591] 102[2591] 136[3454] 136[3454] 136[3454] UNIT WIDTH INCH[MM] 88[2235] 88[2235] 88[2235] 88[2235] 88[2235] 88[2235] UNIT HEIGHT INCH[MM] 71[1803] 71[1803] 71[1803] 76.5[1943] 76.5[1943] 76.5[1943] SHIPPING WEIGHT LB[KG] 4303[1956] 4690[2132] 4866[2212] 6257[2838] 6389[2898] 6527[2961] OPERATING WEIGHT LB[KG] 4372[1987] 4776[2171] 4952[2251] 6499[2948] 6651[3017] 6770[3071] OPERATING CHARGE R407C LB[KG] 66[30] 88[40] 102[46] 122[55] 132[60] 154[70]

12 2.0 INSTALLATION 2.1 GENERAL The ACS chiller is designed to cool water or other non-corrosive liquids. Water is circulated through the direct expansion evaporator where it is cooled to the desired temperature and then circulated to cooling coils for air conditioning, or to other types of heat exchangers for process cooling. Care should be taken to ensure that the equipment is properly installed and adjusted. An installer or operator should first be familiar with the information in this manual. 2.2 INSPECTION When the equipment is delivered, it is important that the following inspection be completed in the presence of the carrier's representative: 1. Check all crates and cartons received against the Bill of Lading/Shipping Papers to be sure they tally. 2. Check the model number and the electrical characteristics on the nameplate to determine if they are correct. 3. Check for freight damage, shortages or other discrepancies and take note of them on the delivery receipt before signing. Should any damage be found, a damage claim should immediately be filed by the purchaser against the delivering carrier as all shipments are made at the purchaser's risk. 2.3 RIGGING GENERAL Each unit has been carefully tested and packed at the factory where every care is taken to ensure that the unit reaches you in perfect condition. It is very important that the riggers and movers use the same care and precaution in moving the equipment into place. Make sure that chains, cables, or other moving equipment are placed so as to avoid damage to the unit or piping. The refrigerant piping should not be used as a ladder or as a handle. Do not attach a chain hoist sling to the piping or equipment. Move the unit in an upright position and let it down gently from trucks or rollers RIGGING AND MOVING Any unit mounted on skids may be moved with a forklift, but care must be taken not to damage the unit with forks. The skids should not be removed until the unit is at its final location. The ACS model can be lifted by the method showing in Figure SPACE REQUIREMENTS AND CLEARANCE GENERAL The dimensional data and clearances that follow are useful for determining space requirements. The unit should be placed to make the clearance noted available for proper servicing. Failure to allow such clearance will cause serious problems and result in higher costs for operation, maintenance and repair ACS The dimensional data are shown in Figure 2.4.2B and space requirements are shown in Figure 2.4.2A. The most important consideration which must be taken into account when deciding on the location of an air cooled equipment, is the provision for supply of ambient air to the condenser, and removal of heated air from the condenser area. When this essential requirement is not provided, it will result in higher condensing temperatures, which will cause poor operation, higher power consumption and eventually failure of equipment. Units must not be located in the vicinity of steam, hot air or fume exhausts. Another consideration which must be taken into account is that the unit should be mounted away from noise sensitive spaces and must have adequate support to avoid vibration and noise transmission into the building. Units should be mounted over corridors, utility areas, rest rooms or other auxiliary areas where sound levels are not an important factor. Sound and structural experts should be consulted for recommendations on critical installations

13 2.0 INSTALLATION FIGURE ACS RIGGING ACS 10-5, 13-5, 15-5 ACS 20-5,

14 2.0 INSTALLATION ACS 26-5, 30-5, 40-5, 46-5 ACS 55-5, 60-5,

15 2.0 INSTALLATION FIGURE 2.4.2A ACS SPACE REQUIREMENTS Walls or Obstructions The unit should be located so that air may circulate freely and not be recirculated. For proper air flow and access all sides of the unit must be a minimum of four feet away from any wall or obstruction. It is preferred that this distance be increased whenever possible. Make sure that there is ample room for maintenance work through access doors and panels. Overhead obstructions are not permitted. When the unit is in an area where it is enclosed by three walls the unit must be installed as indicated for units in a pit. Multiple Units For units placed side by side, the minimum distance between units is 8 feet [2438mm]. If units are placed end to end, the minimum distance between units is 4 feet [1219mm]. Units in Pits The top of the unit should be level with the top of the pit, and side distance increased to 8 feet [2438mm]. If top of the unit is not level with the top of pit, discharge cones or stacks must be used to raise discharge air to the top of the pit. This is a minimum requirement. Stacks cannot be used on direct driven unit. Belt driven units must be reinforced internally to support the weight of stacks, and larger fan motors may be required. Contact your local Dunham-Bush representative for details. Decorative Fences Fences must have 50% free area, with a 1 foot [305mm] undercut, a 4 foot [1219mm] minimum clearance, and it must not exceed the top of unit. If these requirements are not met, unit must be installed as indicated for "Units in a Pit"

16 2.0 INSTALLATION FIGURE 2.4.2B ACS DIMENSIONAL DATA ACS 10-5, 13-5, 15-5 ACS 20-5, 23-5 NOTE: ALL DIMENSIONS ARE IN INCHES [MM]

17 2.0 INSTALLATION ACS 26-5, 30-5, 40-5, 46-5 ACS 55-5, 60-5, 70-5 NOTE: ALL DIMENSIONS ARE IN INCHES [MM]

18 2.0 INSTALLATION 2.5 FOUNDATION AIR COOLED UNITS The foundation must be level for proper operation and functioning of controls and provision must be made for supporting the individual load points as shown in Figure 2.5.1, Roof mounted units must be supported on adequate steel structures. If units are located on the ground level, a concrete plinth is recommended. 2.6 VIBRATION ISOLATION Under certain critical conditions, it may be necessary to install vibration isolators under the base of the Packaged Chiller. Rubber-in-shear or spring vibration isolators are offered as optional items. When spring isolators are used, flexible connectors must be installed in the water piping system and in the refrigerant lines of split systems. Kindly note that: These flexible connectors must be suitable for the fluid and pressures involved. When using flexible connectors in refrigerant piping, they must be mounted in the refrigerant discharge and liquid lines close to the packaged chiller, in a horizontal position and parallel to the compressor crankshaft. All piping which is external to the packaged chiller must be supported by spring mounted hangers and any piping which goes through the wall, ceiling or floor should be properly pivoted to prevent transmission of piping vibration to the structure. FIGURE ACS WEIGHT DISTRIBUTION ACS 10-5, 13-5, 15-5 NOTE: ALL DIMENSIONS ARE IN INCHES [MM]. MODEL LOADS LBS [KG] A B C D TOTAL OPERATING WEIGHT LBS [KG] ACS [238] 447 [203] 447 [203] 524 [238] 1942 [882] ACS [251] 472 [215] 472 [215] 554 [251] 2052 [933] ACS [255] [218] [218] 562 [255] 2081 [946]

19 2.0 INSTALLATION ACS 20-5, 23-5 ACS 26-5, 30-5, 40-5, 46-5 ACS 55-5, 60-5, 70-5 NOTE: ALL DIMENSIONS ARE IN INCHES [MM]. MODEL LOADS - LBS [KG] A B C D E F TOTAL OPERATING WEIGHT LBS [KG] ACS [334] 734 [333] 734 [333] 736 [334] [1334] ACS [353] 774 [351] 774 [351] 778 [353] [1408] ACS [379] 1063 [482] 1063 [482] 836 [379] [1722] ACS [403] 1129 [512] 1129 [512] 888 [403] [1830] ACS [440] 1232 [559] 1232 [559] 970 [440] [1998] ACS [456] 1279 [580] 1279 [580] 1005 [456] [2072] ACS [796] 1349 [612] 944 [428] 848 [385] 817 [371] 787 [357] 6499 [2948] ACS [814] 1381 [626] 966 [438] 868 [394] 836 [379] 805 [366] 6651 [3017] ACS [828] 1406 [658] 983 [446] 883 [401] 851 [386] 820 [ [3071]

20 2.0 INSTALLATION 2.7 PIPING CONNECTIONS WATER CONNECTIONS CHILLED WATER PIPING After the unit has been leveled, the external water piping may be set up. Be sure that the water piping is connected to the corresponding connectors. The wateroutlet connection of the cooler is closest to the expansion valve (refrigerant circuit) end. Water flow through the cooler must remain constant for proper chiller operation. Water pressure gauges are recommended to check the water pressure and flow rate in the system, before and after the cooler, and to determine if variations occur in the coole r and system. When installing pressure taps to measure the amount of pressure drop across the water side of the cooler, the taps should be located at least twenty-four (24) inches [610mm] downstream from any connections (flange, elbow, etc.) in the water piping. There are many piping and control systems which may be used to ensure constant water flow through the cooler. A typical system is shown in Figure 2.7A. A three-way motorized valve, which operates in response to the discharge air temperature of the cooling coil, is used. Another system which is sometimes used consists of a two-way modulating control valve, which also responds to the discharge air temperature of the cooling coil, used with a spring loaded bypass regulating valve as shown in Figure 2.7B The bypass valve must be set to ensure full flow of circulating chilled water when the modulating valve is completely closed. Other systems are noted in the ASHRAE Handbook and may operate equally well. Whatever the system is selected, the water flow must be constant WATER CONNECTIONS - Multiple Packaged Chillers Multiple unit package chillers have been successfully applied to parallel and series piping systems for years. Special attention, however, must be given to the particulars involved for each application or serious operational problems can result. The following guidelines should be followed for multiple unit application. It is assumed that the chilled water flow rate is constant Parallel Chilled Water Flow Units Method A: Both units operate simultaneously, modulating with load variations. Each packaged chiller operating thermostat senses the return water temperature using standard controls (See Figure 2.7C). The set point of each thermostats will be set to maintain the desired unloading. In addition to that, for each chiller package, the suction sensing hot gas by-pass valve provides modulating capacity reduction from 100% to approximately 30% on single compressor models with hot gas by-pass. Method B: Install units the same as Method A, but add a third thermostat in the return water, as shown in Figure 2.7E. This thermostat will be set to cycle off one of the units when the load drops below 50%. When this condition is reached, the leaving mixed water temperature will rise, causing the return water temperature to rise and the unit operating will load up. The "off" unit is sequencing to start again before full system load temperature is reached

21 2.0 INSTALLATION FIGURE 2.7A FIGURE 2.7B FIGURE 2.7C FIGURE 2.7D FIGURE 2.7E

22 2.0 INSTALLATION This system will be as stable as Method A, in operation, but in normal air-conditioning applications, this is not detrimental. The advantage of Method B is a better part load efficiency. Also a lead-lag control can be added Series Chilled Water Flow Units WATER QUALITY Units should be equally sized. The upstream unit will carry a larger load because it cools higher temperature water. The thermostats sense inlet water temperatures. (See figure 2.7D). The number 1 unit thermostat will unload or cycle off the packaged chiller before unloading occurs of the Number 2 unit. Coolers used in this packages is made of steel and copper and are suitable for operation with well-maintained water systems. However, if the water used in cooler is corrosive, high in mineral content or entrained solids, the water can reduce the performance and even damage the heat exchangers. Therefore, it may be necessary to obtain the service of a water treatment consultant and to provide and maintain water treatment. This is particularly important with glycol systems and with cooling tower loops. 2.8 ELECTRICAL CONNECTIONS GENERAL All units are wired as completely as possible at the factory prior to delivery. The connections which must be made by the installer are to the main power source, starting equipment and interlocking the satellite equipment. In connecting power wiring to the unit, the following precautions should be taken: - All field wirings are to be in accordance with the National Electrical Code and state and local codes. - All wirings are to be checked for damage and all terminal connections are to be tested for tightness. Unit terminal blocks are to be connected with copper conductors only and sized per ampacity listed on unit data plate. - The power supply should match the unit nameplate in volts, phase and Hertz. Voltage must be within ±10% of nameplate value and voltage imbalance between phases must not exceed 2% 2.9 REQUEST FOR START-UP REPRESENTATIVE Start-up service is an option upon request when an order for the unit is placed. If you request for start-up service, then after the installation has been completed and checked, a written notice shall be given to the Dunham-Bush representative. Following receipt of written notice, a representative will be sent to the customer. The purchaser should have competent service and operating personnel in attendance to assist in the work involved, and also to be trained in the operation and maintenance of this unit. The representative will inspect the installation to determine whether it meets Dunham-Bush requirements, perform the initial start-up of the installation determine whether it is in satisfactory operating condition, and instruct specified customer personnel in its operation and maintenance for the length of time specified in the purchase contract

23 3.0 OPERATION 3.1 GENERAL The unit should be started up only by a refrigeration technician who is familiar with the accepted operation practices for refrigeration systems. Use the scroll unit start-up report, to record all temperature, pressure, electrical readings and control settings. A copy must be forwarded to Dunham-Bush service department, before warranty will be honored. 3.2 UNIT PIPING See Figure for typical unit piping schematics. 3-3 AIR COOLED PACKAGES START-UP The unit is ready for start-up when the following procedures have been completed: 1. Water piping for the evaporator is installed and tested. 2. Electrical connections are made and properly fused. 3. Unit has been leak tested, leaks corrected and charge completed. 4. Compressor crankcase heater(s) has been energized for a minimum of 24 hours. 5. Calibrated refrigerant gauges have been connected to the suction and discharge ports. 6. Turn On the chilled water pump, check direction of rotation and adjust the water flow through the cooler to the specified flow rate. Bleed off all entrained air. 7. Manually energize the fan starters and check the fan rotation. Fans should pull air through the condenser coil and discharge vertically upwards. Rotation can be changed on 3-phase motors by interchanging only two wires on the main terminal block. 8. Check all refrigerant valves to be sure they are open. 9. Proceed to section 3.4 System Start-Up. 3.4 SYSTEM START-UP 1. Before starting the compressor(s), check all three phases of supply voltage, of all legs of the motor. They must be within ±10% of the nameplate voltage. 2. Start compressor(s), check the gauges and note if the pressures are within the prescribed limits. 3. Check the refrigerant sight glass to be sure it is free of bubbles. If not, charge as specified per section 4.8 Charging. 4. Shut the compressor down and check the compressor crankcase sight glass for oil level. It should be between 1/2 to 3/4 of the complete sightglass. If not, see Section 3.5 Lubrication. 5. Restart the compressor. After an hour of operation the expansion valve superheat setting should be checked, it should be between 8 F [4.4 C] and 10 F [5.6 C] at full load design conditions. In some instances, it will be necessary to lower the superheat setting to ensure proper distribution. Turn the TX valve adjustment stem clockwise to increase the superheat setting and counterclockwise to decrease the setting. Be sure and allow ample time between each adjustment for the system to rebalance. 6. The temperature of the chilled water both in and out, should be checked to insure the unit is operating within the desired temperatures. 3.5 LUBRICATION OIL LEVEL A properly operated unit should run with the compressor crankcase warm to touch. Check oil level frequently to see that a sufficient amount of oil remains in the crankcase. Compressor oil level can be checked by the sight glass. To make sure that proper oil level is observe, operate the compressor for 15 minutes, then stop the compressor. Oil should appear from 1/2 to 3/4 in the sight glass with the compressor stopped

24 3.0 OPERATION FIGURE ACS TYPICAL PIPING SCHEMATIC ACS 10-5, 13-5, 15-5, 20-5,

25 3.0 OPERATION ACS 26-5, 30-5, 40-5,

26 3.0 OPERATION ACS 55-5, 60-5,

27 3.0 OPERATION OIL TYPE If the oil becomes discolored indicating contamination, the contamination can be take care of by installing a new filter-drier in the liquid line and changing the oil. WARNING: Use Only Dunham-Bush Approved Refrigeration Oil, Warranty Will Be Void If Other Than Approved Oil Is Used. It is recommended to change oil annually to prolong the compressor life-time. Oil charge for a complete recharge shown in the following table. Oil type and approved oils are also listed for each compressor. After recharge the oil level should be maintained per section COMPRESSOR OIL CHARGE (l) APPROVED OIL SPAE SPBE SPCE SPDE SPEE SPBBE SPCCE SPDDE SPDEE SPEEE DB26 (R22 Refrigerant) / DB02 (R407c Refrigerant) 3.6 SYSTEM FLOW RATE The quantity of chilled water being circulated can be estimated by determining the water pressure drop through the cooler by reading GPM [L/S] from the appropriate pressure drop curve. (See Figure 3.6) An alternate method of determining GPM [L/S]is to measure pressure difference from pump inlet to outlet and read GPM [L/S] from pump curve. Water flow rate must not vary more than ±10% from design flow rate. 3.7 SYSTEM CONTROL CAPACITY CONTROL The standard system capacity control operates as follows: - As the chiller load initially drops, the suction of the compressor(s) starts dropping proportionately, thus balancing minor load variations. - Variation of unit capacity in response to system load requirements is controlled by an operating thermostat, which monitors the return water temperature. - On multiple compressor units, capacity is controlled by compressor staging. Refer to Table to determine the capacity control scheme for your specific unit. TABLE CAPACITY CONTROL COMPRESSOR CYLINDER UNLOADING AND STAGING SCHEDULE ACS 10-5, 13-5, 15-5, 20-5, 23-5 ACS CAPACITY COMPRESSOR OFF 0.0% COMPRESSOR 1 ON 100 % 50% ACS 26-5, 30-5, 40-5, 46-5 COMPRESSOR OFF 0.0% COMPRESSOR 1 ON 100 % 25% COMPRESSOR 2 ON 100 % 50% COMPRESSOR 3 ON 100 % 75% COMPRESSOR 4 ON 100 % 100% ACS 55-5, 60-5, 70-5 COMPRESSOR OFF 0.0% COMPRESSOR 1 ON 100 % 16.67% COMPRESSOR 2 ON 100 % 33.33% COMPRESSOR 3 ON 100 % 50.0% COMPRESSOR 4 ON 100 % 66.7% COMPRESSOR 5 ON 100 % 83.4% COMPRESSOR 6 ON 100 % 100% SOLID-STATE OPERATING THERMOSTAT General A four-stage solid-state operating thermostat, FSE, is used on all AC packages. The opstat senses return chilled water or air temperature and by staging and/or unloading compressors is able to control leaving chilled water or air temperature to a narrow band of temperature Opstat Settings Each four-stage electronic opstat is factory, adjusted to your specified conditions, A field check of the controller may be made by first determining your design range (R). To determine the range of a water chiller, subtract the design leaving water temperature (TLW) from the return water temperature (TRW) (R =TRW-TLW)

28 3.0 OPERATION FIGURE 3.6 WATER SIDE PRESSURE DROP 1a.) ENERGY SAVING IMPERIAL UNITS 100 R22 ACS 10 ACS 13 ACS 46 PRESSURE DROP - FT.WG.. 10 ACS 15 ACS 23 ACS 40 ACS 20 ACS 26 ACS 30 ACS 55 ACS 60 ACS CHILLED WATER FLOW RATE - GPM 1b.) HIGH EFFICIENCY - IMPERIAL UNITS R ACS 15 ACS 10 PRESSURE DROP - FT.WG.. 10 ACS 13 ACS 20 ACS 23 ACS 26 ACS 30 ACS 40 ACS 60 ACS 46 ACS 55 ACS CHILLED WATER FLOW RATE - GPM

29 3.0 OPERATION 1c.) ENERGY SAVING IMPERIAL UNITS R407c 100 ACS 13 ACS 10 ACS 30 ACS 15 ACS 26 PRESSURE DROP - FT.WG.. 10 ACS 20 ACS 40 ACS 23 ACS 46 ACS 55 ACS 60 ACS CHILLED WATER FLOW RATE - GPM 1d.) HIGH EFFICIENCY - IMPERIAL UNITS R407c 100 ACS 10 ACS 13 ACS 30 PRESSURE DROP - FT.WG.. 10 ACS 15 ACS 20 ACS 26 ACS 23 ACS 40 ACS 46 ACS 55 ACS 60 ACS CHILLED WATER FLOW RATE - GPM

30 3.0 OPERATION 2a.) ENERGY SAVING S. I. UNITS R PRESSURE DROP - kpa ACS 10 ACS 13 ACS 15 ACS 23 ACS 40 ACS 20 ACS 46 ACS 26 ACS 30 ACS 55 ACS 60 ACS CHILLED WATER FLOW RATE - m³/hr 2b.) HIGH EFFICIENCY S. I. UNITS R PRESSURE DROP - kpa ACS 15 ACS 10 ACS 13 ACS 20 ACS 23 ACS 26 ACS 30 ACS 40 ACS 60 AC S 46 ACS 55 ACS CHILLED WATER FLOW RATE - m³/hr

31 3.0 OPERATION 2c.) ENERGY SAVING S. I. UNITS R407c 1000 PRESSURE DROP - kpa. 100 ACS 13 ACS 10 ACS 15 ACS 26 ACS 20 ACS 40 ACS 23 ACS 30 ACS 55 ACS 60 ACS 70 ACS CHILLED WATER FLOW RATE - m³/hr 2d.) HIGH EFFICIENCY - S. I. UNITS R407c 1000 PRESSURE DROP - kpa. 100 ACS 10 ACS 13 ACS 15 ACS 20 ACS 26 ACS 23 ACS 30 ACS 55 ACS 60 ACS ACS 40 ACS CHILLED WATER FLOW RATE - m³/hr

32 3.0 OPERATION The standard range is 10 F [5.6 C]. To determine the range of a condensing unit, subtract the design no load return air temperature (TNL) from the design full load return air temperature (TFL) (R= TFL- TNL). The standard range is 6 F [3.3 C]. Set point of the opstat should be your design leaving chilled water temperature (TLW) for water chillers. The standard adjustment range for AC units is 32 to 104 F [0 to 40 C]. The location of setting knob is shown in Figure 3.7.2A. Step Temp adjusts the temperature range per stage in degrees F. To determine TRB. For a standard condensing unit TRB= 0.25 x R. Check the dial setting on the opstat. The approximate setting of Step Temp is shown in the Figure 3.7.2B by the Step Temp should be changed by an authorized serviceman only. 3.8 ELECTRICAL CONTROLS MCCB/MCB - Main Circuit Breaker This is an automatic, calibrated, ambient compensated, magnetic trip circuit breaker, which provides both direct line-break compressor branch circuit. short circuit locked rotor and overload protection. It has a manually operable handle for compressor circuit disconnect, and an auxiliary NO. switch (optional) which interrupts the 230V compressor control circuit when the breaker opens. M - Contactor (Compressor and Fan Motor)- Optional The contactor, operated by the control circuit, provides power individually to the compressor and fan motors. Contactors are used either singly or in parallel pairs for across-the-line start (simultaneous operation). These devices are amp rated to handle both rated load amp and locked rotor amps. CR - Relays (Miscellaneous Control) These relays provide the necessary circuit logic for lock-in, lock -out and transfer functions. HTR - Crankcase Heater Energized continuously as long as control circuit power disconnect switch (not supplied with the unit) is closed and compressor is off. This heater maintains crankcase temperature above the system temperature during the compressor off cycle, preventing refrigerant migration into the crankcase and consequent compressor damage. SOL- i.) Liquid Line Solenoid Valve Closes when the compressor(s) is off to prevent any liquid refrigerant from accumulating in the chiller during the off cycle. ii.) Discharge Solenoid Control (Optional) This function is used in low ambient application. Discharge solenoid is turn off to reduce condensing surface and to increase head pressure. OL - Motor Overload (Manual Reset) For AC the compressor is protected by overload relays utilizing quick trip, ambient compensated heaters. The overload relays are manually reset. OUVR - Over Under Voltage Relay (Optional) Protects the unit from the following electric supply malfunctions: over voltage, under voltage, please reversal, single phasing and phase imbalance. If the OUVR trips, a control relay will de-energize and open the control circuit. A red LED trip light, located on the OUVR, will indicate a supply malfunction. Tile OUVR is a manual reset control device

33 3.0 OPERATION FIGURE 3.7.2A CONTROLLER FRONT PANEL 1- Display: shows the value measured by the connected sensor. In the event of alarm condition the sensor value will be displayed alternately with the codes of the active alarms. When programming the instrument, the display shows the parameter codes being introduced and their values. 2- Decimal Point LED: lights up when the controlled parameter is displayed. 3- Reverse LED: flashes when at least one relay working in the "Reverse" mode is active. The Led flashes as many times as the number of active 'reverse' relays. There is a two seconds' pause between a flashing stage and the next one. 4- Direct LED: flashes when at least one relay working in the "Direct" mode is active. Its working logic is the same as the "Reverse" LED. 5- SEL Button: displays and/or allows you to select the Set-point. If pressed for 5 seconds together with PRG/MUTE it allows you to enter the password and the configuration parameters (having a "Cxx" type code). 6- PRG/Mute Button: if pressed for 5 seconds it allows you to access the menu of the more frequently used parameters (having a "Pxx" type code). In the event of alarm condition, it silences the buzzer and, if pressed after the cause that determined the alarm has disappeared, it resets any other alarm. It completes the programming procedure storing all the values of the modified parameters. 7- Button : increases the value of the set-point or that of any other selected parametel: 8 - Button : decreases the value of the set-point or that of any other selected parametel: In NTC input versions it can display the value of the second sensor (holding "Down" pressed while the display shows the value of the main sensor). Note: for Infrared Universal, Series models, please refer to the table at the end of the manual FIGURE 3.7.2B TYPICAL CONTROL SEQUENCE WITH 2 STAGE OPERATING THERMOSTAT AT 10 C RETURN WATER SETPOINT, 3.0 C DIFFERENTIAL

34 3.0 OPERATION ELECTRONIC THERMOSTAT Keypad Operation 1) Set-point display: Press [SEL] key to display set-point. 2) Set-point modification: Press [SEL] key for few sec to change St1 setpoints. Release [SEL] key, actual set-point value flashes. Use [up arrow] or [down arrow]key to change value. Press [SET] key to confirm new value. 3) "P" Parameters modification: Press [PRG/mute] key for 5 sec allows you to access the most frequent used parameters ("Pxx" type code).use [up arrow] or [down arrow] key to require parameter. Press [SEL] key to display this parameter. Use [up arrow] or [down arrow] key to set value. Press [SEL] key to confirm. Repeat procedure for other parameters. Press [PRG/mute] key to store modified data and go back to normal operation. 4) "C" Parameters modification: Press [SEL] key + PRG/mute] key for 5 sec allows you to enter password and configuration parameters ("Cxx" type code). Display show 0. Select password by pressing [up arrow] key until 22 or 77 display. Press [SEL] key to confirm. Code C0 displayed if password is correct else repeat procedure. Use [up arrow] or [down arrow] key to desire parameter. Press [SEL] to confirm. Use [up arrow] or [down arrow] key to desire value. Press [SEL] to confirm. Repeat procedure for other parameters. Press [PRG/mute] key to exit. 5) Alarm Handling: In the event of alarm condition, press [PRG/mute] key to silence the buzzer. If pressed after the cause of alarm disappeared, it resets any other alarm. 6) Second Probe Display: For NTC input versions, 2nd probe value can be displayed by pressing [down arrow] key while the main probe value is displayed IR32 ELECTRONIC THERMOSTAT PARAMETERS LIST Par. Description Min. Max. Default Fac. Set St1 Set Point 1 min probe max probe 20 6 St2 Set Point 2 (Modes 6,7,8,9) min probe max probe 40 NA CO Operation Mode Setting Differentials P1 Set Point 1 Differential (absolute value) P2 Set Point 2 Differential NA P3 Dead Zone Differential (Modes 3,4,5) (absolute value) NA C4 Authority. NTC models only with Mode 1or and C19 = 2, 3 or 4 C5 Control Action: 0=Proportional (P) 1=Prop+Integral (P+I) Outputs C6 Delay time (sec) btw energization of different relays C7 Min time (min) btw energization of the same relay C8 Min off time (min) of the same relay C9 Min on time (min) of the same relay C10 Outputs Status in the event of sensor alarm: = All relays de-energized 1 = All relays energized 2 = DA relays energized, all others de-energized 3 = RA relays energized, all others de-energized C11 Output Rotation: (Modes 1,2,6,7,8 only) 0 = No rotation 1 = Standard rotation 2 = 2+2 rotation (compressor on relays 1 & 3) 3 = 2+2 rotation (valve normal open)

35 3.0 OPERATION Par. Description Min. Max. Default Fac. Set C11 Output models only (A and Z) = Rotation of relays 3 & 4 (No rotation for 1 & 3) 5 = Rotation of relays 1 & 2 (No rotation for 3 & 4) 6 = Separate rotation of coupled relays 1-2 & = Rotation on relays 2,3,4 (No rotation for 1) C12 PWM cycle time (sec) NA Sensor C13 Probe type: 0 = 4-20, 1 = 0-20; 0 = K tc 1 = J tc NTC probe : 0 = normal function, 1= invert function, (instrument display NTC2 and control on NTC1) P14 Probe calibration or offset C15 Analog Input min.scaling value -99 C16 0 NA C16 Analog Input max.scaling value C NA C17 Probe response time (noise filter) C18 Temperature unit: 0 = C, 1 = F C19 2nd Probe: NTC only, Mode 1 or = no modification on std. Mode 1 = differential mode (NTC1 - NTC2) 2 = summer offset 3 = winter offset 4 = active offset with Dead zone P2 C21 Set point 1 min. limit -99 C22 min. probe -50 C22 Set point 1 max. limit C max. probe 90 C23 Set point 2 min. limit -99 C24 min. probe -50 C24 Set point 2 max. limit C max. probe 90 Alarms P25 Low temp. alarm set point -99 P26 min. probe -50 P26 High temp. alarm set point P max. probe 90 P27 Alarm hysteresis P28 Alarm delay, min C29 Digital input 1 configuration (CO different from 6,7,8) In case of alarm the status of relays depends on C31 0 = non active input 1 = immediate alarm with automatic reset 2 = immediate alarm with manual reset 3 = delay alarm (P28) with manual reset 4 = on/off of the control C30 Digital input 2 configuration (IRDR only) NA option as for C29 C31 Outputs Status in case of alarm condition detected via digital input: 0 = All relays de-energized 1 = All relays energized 2 = DA relays energized, all others de-energized 3 = RA relays energized, all others de-energized Others C32 Unit address (for serial connection) Special Parameters C33 Special mode of operation: 0 = No, 1 = Yes DO NOT MODIFY THIS PARAMETER Set and programmed starting mode C0 before modifying C33 C50 Keypad(KP) and Remote Control(RC) activation: = KP off, RC on (only type P parameters) 1 = KP on, RC on (only type P parameters) 2 = KP off, RC off 3 = KP on, RC off 4 = KP on, RC on (all parameters) C51 Remote IR controller activation code

36 3.0 OPERATION IR32 ELECTRONIC THERMOSTAT TROUBLESHOOTING Code Description Cause Control Action Reset Remedies Er0 Sensor error faulty sensor depends on C10 R: automatic V: manual Check connection. Check sensor signal Er1 Sensor NTC2 faulty sensor if C19=1 & Mode R: automatic Check connection. Check error =1 or 2 V: manual sensor signal see Er0 Er2 Memory error voltage drop stoppage R: automatic Reset factory-set values. during programming stage, V: manual Turn off controller, turn on again holding [PRG/mute] key memory damaged by electromagnetic interference Er3 Alarm via contact linked to depends on C31 R: depends Check C29, C30, C31 & external contact digital input is on C29 & P28. on digital input open C30 Check the external contact V: manual Er4 Er4 High temp > P26 for a nil R: automatic Check P26, P27 & P28. temperature time interval > V: manual alarm P28 Er5 Low temp < P25 for a nil R: automatic Check P26, P27 & P28. temperature time interval > V: manual alarm P28 NOTE: R = Control action Resetting the instrument means to restore normal operating conditions after the cause that determinied the alarm has been cleared. V = Display Display and buzzer. Display reset means that normal display of usual values is restored

37 3.0 OPERATION ACS TYPICAL WIRING SCHEMATIC ACS 10-5, 13-5,

38 3.0 OPERATION ACS 20-5, 23-5 Ω Ω

39 3.0 OPERATION ACS 26-5, 30-5, 40-5,

40 3.0 OPERATION ACS 55-5, 60-5,

41 3.0 OPERATION Ω Ω Ω Ω Ω Ω

42 4.0 MAINTENANCE 4.1 GENERAL As with all mechanical equipment, a program of regular inspection, cleaning and preventive maintenance by trained personnel will contribute greatly to the long satisfactory service life of this product. 4.2 PERIODIC INSPECTION Read essential temperatures and pressures periodically to see that they indicate normal operation. It is a good idea to record these readings on a log sheet. If any abnormal operation is observed, try to remedy it. See Trouble Shooting Guide Section. 4.3 MONTHLY INSPECTION Check cooling tower water treatment system, Wipe down external surfaces of unit. Shut unit down, open main disconnect, inspect control panel, checking for loose wires, burned contacts, signs of overheated wires, etc. Restart unit and check performance of controls. Check sight glasses for proper refrigerant charge. 4.4 VESSEL MAINTENANCE GENERAL The efficient performance of the cooler and condenser heat transfer surfaces is essential for efficient performance of your packaged water cooling machine. If these surfaces accumulate a film of dirt, scale or slime, their performance efficie ncy will degrade substantially. The refrigerant side of heat transfer surfaces does not foul since refrigerant is a good solvent and it is in a closed, filtered cycle. Water side surfaces can foul from the water system. A program of water treatment can slow the rate of fouling on heat transfer surfaces, but not eliminate it COOLER CLEANING The effects of fouling can be detected by recording full load performance data on the log sheet. If the difference between the leaving water from the cooler and saturated suction temperature at the compressor is 2 F [1.1 C] greater than the difference recorded at clean conditions, the tubes should be cleaned. It is generally advisable to clean the cooler water side surfaces at least annually, and more often if severely foul water is used. This cleaning must be done chemically. In chemical cleaning, a caustic solution is pumped through the heat exchanger, which attacks dirt, slime, and mineral deposits and flushes them away. Chemicals can be recommended by water treatment specialists, but it is important to rinse the system thoroughly after cleaning to remove the chemicals before they attack the metal surfaces. The cooler water side (shell side) cannot be physically cleaned because of the crossflow baffle construction. 4.5 AIR COOLED CONDENSER CLEANING The face of the condenser should be cleaned at least once month during operation. If conditions are bad and condensers pick up dirt very quickly, it is suggested that they can be cleaned more frequently

43 4.0 MAINTENANCE TABLE 4.4 PRESSURE/ TEMPERATURE PROPERTIES 1.) R22 psig Pressure Temperature Pressure Temperature Pressure Temperature kpa o F o C psig kpa o F o C psig kpa o F o C

44 4.0 MAINTENANCE 2.) R407C Pressure Temperature Temperature Temperature Pressure Pressure Bubble Dew Bubble Dew Bubble Dew psig kpa F C F C psig kpa F C F C psig kpa F C F C

45 4.0 MAINTENANCE If the condenser is allowed to get too dirty, the unit will run at high head pressure and will not give satisfactory performance. Dirty coils can be cleaned using a soft brush or by flushing with cool water or commercially available coil cleaners. DO NOT USE HOT WATER OR STEAM. To do so will cause excessive pressure in the system. The face of the condenser should be cleaned at the beginning of the season and periodically thereafter if conditions require. 4.6 ELECTRICAL MALFUNCTION The unit has four devices designed to protect compressor motors and manual motor controllers from electrical malfunctions: Circuit breakers. starter overload relays, under voltage relay (optional), and motor over temperature protectors. If the under voltage relay trips, it is a sign of trouble in incoming power. If it trips again after resetting, call your electric utility to investigate the problem. If circuit breaker or motor overload relay or motor over temperature protectors trip, this is a sign of possible motor trouble. DO NOT reset and try to run compressor again. Call authorized service representative to check for motor trouble. Resetting these safety devices and repeated starting could turn a minor motor problem into a costly major motor burnout. 4.7 REFRIGERANT CHARGE GENERAL All packaged chiller units are given a complete charge of refrigerant at the factory. The type and amount of refrigerant required is in Physical Specifications. The total refrigerant shown is for the entire system. Since these units have separate circuits, each circuit should be considered separately for charging. In order to check proper refrigerant charge, look in each liquid line sight glass with the aid of a flashlight during system operation. At all operating conditions, the sight glass should be clear. If bubbles are visible at any operating condition, the circuit is short of charge. Be careful not to overcharge the machine. overcharging will result in considerable liquid logging in the condenser, and excessive condensing pressure. To add refrigerant, connect a refrigerant vessel to the 1/4" [6.4mm] back seating port of the suction valve. Purge the air from the tube with refrigerant gas before connecting. With the unit running, open the refrigerant vessel vapor connection slightly. If the refrigerant vessel is warmer than the cooler, refrigerant will more readily flow from the vessel into the unit AIR COOLED PACKAGES To determine the proper refrigerant charge, check the amount of subcooling if possible. The amount of subcooling at the liquid line (liquid line saturation temperature corresponding to liquid line pressure minus liquid line temperature) should be between 15 F [8.3 C] and 20 F [11.1 C]. Subcooling at the condenser out-subcooler inlet trap should not exceed 5 F [2.8 C]. This sight glass should be clear with no bubbles

46 4.0 MAINTENANCE 4.8 TROUBLE SHOOTING SYMPTOM POSSIBLE CAUSE REMEDY 1. Unit will not start 1. Power off 2. Main line open 3. Incorrect wiring 4. Loose terminals 5. Control circuit open 1. Check main disconnect switch. 2. Check main fuses. 3. Check with wiring diagrams. 4. Tighten terminals. 5. Check pump fuses, starter heater elements, pressure and temperature controls. 2. Compressor hums but does not start 1. Low voltage 2. No power on one phase of 3 phase unit 3. Faulty starter or contactor 1. Check at main entrance and at unit. Consult power company if voltage is low and increase wire size to the unit if voltage is normal at main and low at unit. Voltage must be within 10% of motor nameplate rating. 2. Check fuses and wiring. 3. Check the contacts and time delay on part wind start. 3. Compressor cycles on low pressure control 1. Refrigerant shortage 2. No load on chiller 3. Restriction in liquid line 4. Head pressure too low 1. Check for leaks and add refrigerant. 2. Check pump operation and water flow. 3. a.) Plugged drier. If temperature drop exists across the drier remove and replace cores. b.) Liquid line or suction valve partially closed. Open valves fully and close in one full turn. c.) Expansion valve clogged or inoperative. Check superheat setting. Check charge and thermo bulb. 4. Restrict water flow to condenser by adjusting the water regulating valve or cycle cooling tower fan. 4. Compressor cycles on high pressure control 1. Compressor discharge valve partially closed. 2. Air in system 3. Overcharge of refrigerant 4. High pressure control improperly set 5. Main water valve closed 6. Water regulating valve set high or defective 7. Condenser fan inoperative 8. Dirty condenser 9. Fan cycle switches inoperative, or set too high 10.Fan motors not running 11.Fan motor reverse rotation 1. Open valve fully and close with one turn 2. Flush water valve. If pressure in system exceeds the pressure corresponding to the water temperature purge air from compressor gauge connection. 3. Purge system while in operation until bubbles show in sight glass. Close valve and add small amount of refrigerant until sight glass just clears. 4. Adjust the control. 5. Open the water valve. 6. Reset or replace valve. 7. Check, replace or repair set screw (pulley), fan motor, or inoperative fan control. 8. Clean condenser surfaces with brush and/or vacuum. 9. Check and readjust. 10.Check contactor, thermal overload relay, check motor, check capacitor. (If single phase) 11.Reverse two fan motor leads. (3 phase only)

47 4.0 MAINTENANCE 4.9 SAMPLE LOG SHEET SHEET NO... DUNHAM-BUSH SCROLL COMPRESSOR PACKAGED CHILLER NAMEPLATE DATA: UNIT MODEL NO.... UNIT NO.... VOLTS:... Hz... UNIT SERIAL NO.... COMPRESSOR MODEL NOS... START UP : DATE... TIME... DATE TIME ELAPSED TIME METERS COMP. NO. 1. SUCTION 2. PRESSURE 3. DISCHARGE 2. PRESSURE 3. DISCHARGE 2. TEMPERATURE 3. DISCHARGE SUPERHEAT 2. (DISC. TEMP.-SAT. DISCH.)* 3. DISCHARGE SUPERHEAT 2. (DISC. TEMP.-SAT. SUCT.)* 3. EVAPORATOR WATER TEMPERATURE-IN EVAPORATOR WATER TEMPERATURE-OUT EVAPORATOR PRESSURE DROP Ft.wg. [KPa] EVAPORATOR WATER FLOW gpm[m³/hr] CONDENSER AIR TEMPERATURE-IN (AMBIENT) AC ONLY ACTUAL VOLTAGE 2. COMPRESSOR AMPS 3. FAN AMPS VOLTS *USE TABLE 4.4 FOR OBTAINING SATURATED TEMPERATURE THIS LOG SHEET IS PROVIDED AS A RECOMMENDATION OF THE READINGS THAT SHOULD BE TAKEN ON A PERIODIC BASIS. THE ACTUAL READINGS TAKEN AND THE FREQUENCY WILL DEPEND UPON THE UNITS APPLICATION, HOURS OF USE, ETC. THIS TYPE OF INFORMATION CAN PROVE VERY USEFUL IN PREVENTING AND/ OR SOLVING PROBLEMS THAT MIGHT OCCUR DURING THE LIFE OF THE UNIT

48

R407C. WCS Series 50Hz. Water Cooled Scroll Direct Expansion Chillers Cooling Capacity: 12 to 53 TR (42 to 186 kw)

R407C. WCS Series 50Hz. Water Cooled Scroll Direct Expansion Chillers Cooling Capacity: 12 to 53 TR (42 to 186 kw) WCS Series 50Hz Water Cooled Scroll Direct Expansion Chillers Cooling Capacity: 12 to 53 TR (42 to 186 kw) R407C Products that perform...by people who care TABLE OF CONTENTS Page No Nomenclature... 2 Standard

More information

MACH N-407 Heat Pump Air-Cooled Chiller

MACH N-407 Heat Pump Air-Cooled Chiller MACH060-01-N-407 Heat Pump Air-Cooled Chiller Heat Pump Air-Cooled Chillers for Global Residential and Light Commercial Microclimates MACH NOMENCLATURE BREAKDOWN MACH-060-01 - N - 407 Refrigerant Type

More information

Service Step by Step Trouble-Shooting Check-List

Service Step by Step Trouble-Shooting Check-List WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:

More information

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC. WYETH-AYERST CANADA INC. 1025, BOUL. MARCEL-LAURIN S T - L A U R E N T, Q U É B E C INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER MODEL P448800LT--55WC--22C66S Prepared par Claude Gadoury, P.

More information

60Hz. R134a HXWC SERIES. 205 to 560 Tons. Products That Perform...By People Who Care WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS

60Hz. R134a HXWC SERIES. 205 to 560 Tons. Products That Perform...By People Who Care WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS R Products That Perform...By People Who Care FORM NO: MS0455A WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS R134a HXWC SERIES 205 to 560 Tons 60Hz INTRODUCTION Dunham-Bush's HXWC water cooled

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin WCU_O&I 01 June 2003 Condensing Unit Installation and Operating Instructions WCU Air Cooled Condensing Unit Table of Contents Section 1. Section 2. Section 3. Section 4. Section 5. Section 6.

More information

Installation, Operation, and Maintenance Information

Installation, Operation, and Maintenance Information Installation, Operation, and Maintenance Information Air Cooled Condensers 8-2016 Rev 0 Table of Contents General Safety Information 2 Inspection 2 Installation 2 6 Rigging and Assembly 2 Unit Location

More information

MAC N-407 Air-Cooled Chiller

MAC N-407 Air-Cooled Chiller MAC036-01-N-407 Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial MicroClimates MAC036 NOMENCLATURE BREAKDOWN MAC036-01 - N - 407 Refrigerant Type Air-Cooled Chiller 036=

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703 TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin ACU_O&I 02 August 2016 Condensing Unit Installation and Operating Instructions ACU Air Cooled Condensers Table of Contents Section 1. General Information... 2 Section 2. Refrigeration Piping...

More information

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N PROAIR Air Conditioner CR23 Model INSTRUCTION MANUAL Rev. D P/N 89112522 TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

Direct Drive Fluid Coolers

Direct Drive Fluid Coolers H-IM-68 March 2000 Part No. 25001301 Replaces H-IM-44 Direct Drive Fluid Coolers Installation and Maintenance Data Table of Contents Inspection System Warranty Installation...2 Rigging Instructions...3

More information

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N SPECTRACOOL Air Conditioner N21 Model INSTRUCTION MANUAL Rev. G P/N 89115088 TABLE OF CONTENTS WARRANTY AND RETURN POLICY...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

PDF Created with deskpdf PDF Writer - Trial ::

PDF Created with deskpdf PDF Writer - Trial :: Instruction Manual Index Introduction Uncrating and Checking for Damage Locating Your Unit Installation Fill Tank Process Connections Pre Startup Startup Sequence Trouble Shooting Chart Operating Lights

More information

.2 Section Waste Management and Disposal.

.2 Section Waste Management and Disposal. Issued 2005/06/01 Section 15624 Packaged Rotary Screw Water Chillers Page 1 of 5 PART 1 General 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL nvent Rev. I P/N

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL nvent Rev. I P/N PROAIR Air Conditioner CR29 Model INSTRUCTION MANUAL Rev. I P/N 89104461 TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE CAS Product Specifications Single stage cooling capacity control on all models with Micro channel

More information

WCOX B Water-Cooled Packaged Chillers with Helical Rotary Compressors

WCOX B Water-Cooled Packaged Chillers with Helical Rotary Compressors WCOX056-07B Water-Cooled Packaged Chillers with Helical Rotary Compressors Installation, Operation, and Maintenance Instructions TABLE OF CONTENTS PAGE. GENERAL INFORMATION...2. Receiving and Inspection...

More information

PROAIR Air Conditioner. CR43 Model INSTRUCTION MANUAL nvent Rev. H P/N

PROAIR Air Conditioner. CR43 Model INSTRUCTION MANUAL nvent Rev. H P/N PROAIR Air Conditioner CR43 Model INSTRUCTION MANUAL Rev. H P/N 10-1008-130 TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N T-SERIES Air Conditioner T20 Model INSTRUCTION MANUAL Rev. C P/N 89114993 TABLE OF CONTENTS Warranty and Return Policy... 2 IMPORTANT NOTICE... 2 RECEIVING THE AIR CONDITIONER... 3 HANDLING AND TESTING

More information

R407C. WCS Series 50Hz. Water Cooled Scroll Direct Expansion Chillers Cooling Capacity: 12 to 53 TR (42 to 186 kw)

R407C. WCS Series 50Hz. Water Cooled Scroll Direct Expansion Chillers Cooling Capacity: 12 to 53 TR (42 to 186 kw) WCS Series 50Hz Water Cooled Scroll Direct Expansion Chillers Cooling Capacity: 12 to 53 TR (42 to 186 kw) R407C Products that perform...by people who care TABLE OF CONTENTS Page No Nomenclature... 2 Standard

More information

MODELS W1LC220, 260 AND 320 STYLE B

MODELS W1LC220, 260 AND 320 STYLE B LIQUID CHILLER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: 570.05-NY (494) 570.05-N3Y (495) MODELS WLC0, 60 AND 30 STYLE B 035-3053 Only -5 and -46 voltage codes GENERAL YORK s WLC Packaged Air-Cooled

More information

Call us today! (800)

Call us today! (800) 500 TON AIR-COOLED CHILLER PA-ACCTR-500 Call us today! (800)341-4297 The 500-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

Commercial High-Efficiency Condensing Units

Commercial High-Efficiency Condensing Units FORM NO. A22-193 REV. 3 Supersedes Form No. A22-193 Rev. 2 Commercial High-Efficiency Condensing Units 15 & 20 TON MODEL [52.8 & 70.3 kw] 10 & 12.5 TON MODEL [35.2 & 44.0 kw] 10 THROUGH 20 NOMINAL TON

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance Series R Air-Cooled Helical Rotary Liquid Chiller RTAD 085-180 (50Hz) Standard, Free Cooling and Heat Recovery models RTAD-SVX01F-E4 General information Foreword These

More information

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811 Description These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of Refrigerant R-410A for storage

More information

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N T-SERIES Air Conditioner T29 Model INSTRUCTION MANUAL Rev. I P/N 89104464 TABLE OF CONTENTS Warranty and Return Policy...2 IMPORTANT NOTICE...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE

More information

OWNER S MANUAL. Vintage Classic HEAT COOL models. Proudly Made in the USA

OWNER S MANUAL. Vintage Classic HEAT COOL models. Proudly Made in the USA OWNER S MANUAL Vintage Classic HEAT COOL models Proudly Made in the USA support@aquacomfort.com www.aquacomfort.com/service-and-support 888-475-7443 Manufacturing High Quality, High Efficiency Heat Pump

More information

C13-Series Engineering Guide

C13-Series Engineering Guide Engineering Guide Effective January 2018 Horizontal Air-Cooled, Water-Cooled, Chilled Water and Heat Pump Contents Product Features............................... 3 Product Options................................

More information

Call us today! (800)

Call us today! (800) PA-ACCTR-200 Call us today! (800)341-4297 The 200-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable, efficient and quiet chiller

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions 38AH044-134 Air-Cooled Condensing Units 50/60 Hz Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................

More information

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N T-SERIES Air Conditioner T43 Model INSTRUCTION MANUAL Rev. I P/N 10-1008-145 TABLE OF CONTENTS Warranty and Return Policy...2 IMPORTANT NOTICE...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING

More information

Rev. E 2013 Pentair Technical Products P/N Distributed by: McLean Parts

Rev. E 2013 Pentair Technical Products P/N Distributed by: McLean Parts PROAIR Water-Cooled Air Conditioner CR43WC Model INSTRUCTION MANUAL Rev. E 2013 Pentair Technical Products P/N 10-1008-167 TABLE OF CONTENTS HANDLING & TESTING THE AIR CONDITIONER...3 INSTALLATION INSTRUCTIONS...4

More information

Air-Cooled Condensers

Air-Cooled Condensers Air-Cooled Condenser Installation & Operation Bulletin No. H-IM-90 February 2017 Part Number 25007301 Replaces H-IM-90, October 2015 Air-Cooled Condensers Installation and Operation Guide Applicable for

More information

T-Series Air Conditioner T15 Model

T-Series Air Conditioner T15 Model INSTRUCTION MANUAL T-Series Air Conditioner T15 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200

More information

Liebert CSU3000 Chiller

Liebert CSU3000 Chiller CSI 15620 - Packaged Water Chillers Liebert CSU3000 Chiller Guide Specifications for 7.5-37 Ton CS/CD/CT Models 1.0 GENERAL 1.1 CS/CD MODELS The main-frame coolant supply unit shall be a Liebert Model,

More information

T-Series Air Conditioner T20 Model

T-Series Air Conditioner T20 Model INSTRUCTION MANUAL T-Series Air Conditioner T20 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200

More information

AFHX 195-5QR MODEL: 50 Hz SCREW COMPRESSOR AIR COOLED FLOODED CHILLERS INSTALLATION, OPERATION & MAINTENANCE MANUAL

AFHX 195-5QR MODEL: 50 Hz SCREW COMPRESSOR AIR COOLED FLOODED CHILLERS INSTALLATION, OPERATION & MAINTENANCE MANUAL Products That Perform...By People Who Care Form No: MM0446A-Ford Otomotiv, Turkey INSTALLATION, OPERATION & MAINTENANCE MANUAL SCREW COMPRESSOR AIR COOLED FLOODED CHILLERS MODEL: AFHX 195-5QR R-134A 50

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz) DESCRIPTION These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of refrigerant-22 for storage

More information

MAC-120HE-03 Air-Cooled Chiller

MAC-120HE-03 Air-Cooled Chiller MAC-120HE-03 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 380/415/460-3-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-03

More information

Packaged Air-Cooled Water Chiller

Packaged Air-Cooled Water Chiller Installation, Operation and Maintenance Manual IOMM ALR-3 Group: Chiller Part Number: 330145710 Effective: September 2001 Supersedes: IM ALR-2 Packaged Air-Cooled Water Chiller ALR 110F - ALR 150F Refrigerant

More information

T-SERIES Air Conditioner. T50 Model INSTRUCTION MANUAL nvent Rev. F P/N

T-SERIES Air Conditioner. T50 Model INSTRUCTION MANUAL nvent Rev. F P/N T-SERIES Air Conditioner T50 Model INSTRUCTION MANUAL Rev. F P/N 10-1008-203 TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

GENESIS Air Conditioners. All Models INSTRUCTION MANUAL nvent Rev. K P/N

GENESIS Air Conditioners. All Models INSTRUCTION MANUAL nvent Rev. K P/N GENESIS Air Conditioners All Models INSTRUCTION MANUAL Rev. K P/N 89104462 TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

Call us today! (800)

Call us today! (800) 150 TON AIR-COOLED CHILLER PA-ACCTR-150 Call us today! (800)341-4297 The 150-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME: Supersedes: 201.28-CL2 (817) Form 201.28-CL2 (1017) MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: PHONE: JOB NAME: CUSTOMER ORDER NO: JCI CONTRACT NO: CHILLER MODEL

More information

Installation, Operation and Maintenance Manual. RQ Series. Mold Temperature Control Units 0.75 to 7.5 hp and 0 to 24 kw

Installation, Operation and Maintenance Manual. RQ Series. Mold Temperature Control Units 0.75 to 7.5 hp and 0 to 24 kw Installation, Operation and Maintenance Manual RQ Series Mold Temperature Control Units 0.75 to 7.5 hp and 0 to 24 kw Copyright 2010 Thermal Care Inc. Table of Contents Foreward... 3 Safety Guidelines...

More information

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.1 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.1 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with non authorized factory parts voids all warranty

More information

Installation, Start-Up and Service Instructions

Installation, Start-Up and Service Instructions 38AH044-134 Air-Cooled Condensing Units 50/60 Hz Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION................................

More information

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.2 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO: Supersedes: (316) Form QTC4-CL2 (617) MODEL QTC4 EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: ADDRESS: PHONE: JOB NAME: LOCATION: CUSTOMER ORDER NO: TEL NO: ORDER NO: CONTRACT NO: CHILLER MODEL

More information

AFHX 195-5SR MODEL: 50 Hz SCREW COMPRESSOR AIR COOLED FLOODED CHILLERS INSTALLATION, OPERATION & MAINTENANCE MANUAL

AFHX 195-5SR MODEL: 50 Hz SCREW COMPRESSOR AIR COOLED FLOODED CHILLERS INSTALLATION, OPERATION & MAINTENANCE MANUAL Products That Perform...By People Who Care Form No: MM0448A Kamtek : Iskan Bakanligi Kibris Turkey INSTALLATION, OPERATION & MAINTENANCE MANUAL SCREW COMPRESSOR AIR COOLED FLOODED CHILLERS MODEL: AFHX

More information

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER 2001927 Prepared by: 860 Douglas Way PO Box 530 Natural Bridge Station, VA 24579 1 1.0 SCOPE: This

More information

Air-Cooled Split System Condensing Unit for Rooftop Systems and Air Handlers

Air-Cooled Split System Condensing Unit for Rooftop Systems and Air Handlers Catalog 221-1 Air-Cooled Split System Condensing Unit for Rooftop Systems and Air Handlers Model RCS 025C to 135C R-22/R-407C Refrigerant Contents Introduction............................... 3 The Condensing

More information

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION 100 TON AIR-COOLED SCROLL PACKAGED SPECIFICATIONS Call us today! (800)341-4297 Trane Portable Packaged Air Conditioner units contain the best compressor technology available, in order to achieve the highest

More information

R134a. MODEL: HXWC Series INSTALLATION, OPERATION & MAINTENANCE MANUAL. Water Cooled Screw Flooded Chillers. 60Hz. 65 to 200 Tons (229 to 703 kw)

R134a. MODEL: HXWC Series INSTALLATION, OPERATION & MAINTENANCE MANUAL. Water Cooled Screw Flooded Chillers. 60Hz. 65 to 200 Tons (229 to 703 kw) Form No: M-M-0489A-0410 Products that perform...by people who care INSTALLATION, OPERATION & MAINTENANCE MANUAL Water Cooled Screw Flooded Chillers MODEL: HXWC Series R134a 60Hz 65 to 200 Tons (229 to

More information

ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL

ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER 2001829 OPERATIONS AND MAINTENANCE MANUAL Prepared by: 860 Douglas Way PO Box 530 Natural Bridge Station, VA 24579 1.0 SCOPE: This Operations and Maintenance

More information

Commercial High-Efficiency Condensing Units

Commercial High-Efficiency Condensing Units FORM NO. A22-194 REV. 2 Supersedes Form No. A22-194 Rev. 1 Commercial High-Efficiency Condensing Units RAWL High Efficiency 6.5 & 7.5 TON MODEL [22.86 & 26.38 kw] TABLE OF CONTENTS Model Number Designation...2

More information

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM EFFICIENT UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM 208/230 Volt 1- phase REFRIGERATION CIRCUIT S 2- stage scroll compressors

More information

OWNER S MANUAL. Models: AC110, AC125, AC150 made from 2003 through Proudly Made in the USA

OWNER S MANUAL. Models: AC110, AC125, AC150 made from 2003 through Proudly Made in the USA OWNER S MANUAL Models: AC110, AC125, AC150 made from 2003 through 2010 Proudly Made in the USA support@aquacomfort.com www.aquacomfort.com/service-and-support/ (888) 475-7443 Manufacturing High Quality,

More information

R22 R407C. 60Hz. ACHDX Series. 225 to 415 Tons. Air Cooled Horizontal Rotary Screw Chillers. Products That Perform...

R22 R407C. 60Hz. ACHDX Series. 225 to 415 Tons. Air Cooled Horizontal Rotary Screw Chillers. Products That Perform... R Products That Perform...By People Who Care Form No: MS0464A Air Cooled Horizontal Rotary Screw Chillers R22 R407C Series 225 to 415 Tons 60Hz TABLE OF CONTENTS Page No. Page No. Nomenclature... 2 Physical

More information

PACKAGE AIR CONDITIONER

PACKAGE AIR CONDITIONER PACKAGE AIR CONDITIONER FORM NO. ATZ-206 TZAA- HIGH EFFICIENCY SERIES NOMINAL SIZE 10 TON [35.2 kw] 10 TON MODEL [35.2 kw] This product is shipped with a nitrogen holding charge that must be vented prior

More information

Water-Cooled Dual Compressor Screw Chiller

Water-Cooled Dual Compressor Screw Chiller Installation Manual IM 692-1 Group: Chiller Part Number: 629955 Effective: May 1997 Supersedes: IM663-1 IM683 IM692 Water-Cooled Dual Compressor Screw Chiller Installation Manual PFS 155C through PFS 210C,

More information

Air-Cooled Condensing Units with Compact Screw Compressors

Air-Cooled Condensing Units with Compact Screw Compressors LK-SCUTB March 2015 Air-Cooled Condensing Units with Compact Screw s Technical Bulletin Models SSV DSV Table of Contents Nomenclature Chart... 2 Introduction... 3 Bitzer TM s... 4 Magnum TM Microprocessor...

More information

Product Data. Features/Benefits. 07DA, DB 07EA, EB, ED Condensing Units. 06D, 06E Compressors. 3 to 40 Nominal Tons

Product Data. Features/Benefits. 07DA, DB 07EA, EB, ED Condensing Units. 06D, 06E Compressors. 3 to 40 Nominal Tons Product Data 07DA, DB 07EA, EB, ED Condensing Units 3 to 40 Nominal Tons 06D, 06E Compressors An excellent choice for your built-up system Carrier 07 Series condensing units built for the engineer who

More information

Catalog Air Cooled Split System Condensing Units for Rooftop Systems and Air Handlers

Catalog Air Cooled Split System Condensing Units for Rooftop Systems and Air Handlers Air Cooled Split System Condensing Units for Rooftop Systems and Air Handlers Models RCS 025C through 135C 25 to 135 Tons R-22/R407C Refrigerant Catalog 221-1 Table of Contents Introduction.... 3 The Condensing

More information

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes). Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage

More information

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw) FALCON Rooftop Units ACPSE 50/60Hz Cooling : 36 to 1388 MBH (11 to 407 ) Heating : 40 to 1298 MBH (12 to 380 ) R Products that perform...by people who care NOMENCLATURE 6 AC P S E 435 P - HP G Q 6-60 Hz

More information

MODELS B1PA024, 030 AND 036

MODELS B1PA024, 030 AND 036 STELLAR 2000 SINGLE PACKAGE HEAT PUMPS INSTALLATION INSTRUCTION Supersedes: 511.26-N1Y (892) 511.26-N1Y (893) MODELS B1PA024, 030 AND 036 035-11622 GENERAL YORK Model B1PA units are factory assembled heat

More information

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw Air-Cooled Liquid Chillers Nominal cooling capacity 21-94 kw Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products. The

More information

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS SUNLINE 2000ô MODELS: H5CE090, H3CE120 & H1CE150 7-1/2, 10, & 12-1/2 NOMINAL TONS 9.0-9.5 EER DESCRIPTION These Sunline 2000ô units are completely

More information

As a standard, heat exchangers are provided with flange water connections (BS Standard Table E). All evaporator are supplied fully insulated.

As a standard, heat exchangers are provided with flange water connections (BS Standard Table E). All evaporator are supplied fully insulated. NOMENCLATURE INTRODUCTION The HTT HWDX water-cooled chillers range is the latest addition to HTT s growing family of commercial products, featuring the most current technologies advances. The HWDX main

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available May 2006 10 12 167 - GB - 00 MARKING

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

SYSTEM DESIGN REQUIREMENTS

SYSTEM DESIGN REQUIREMENTS P a g e 1 SYSTEM DESIGN REQUIREMENTS WFC-S SERIES WATER-FIRED SINGLE-EFFECT ABSORPTION CHILLERS / CHILLER-HEATERS Yazaki WFC-S Series water-fired chillers and chiller-heaters are available with nominal

More information

Contour TM Screw Compressors

Contour TM Screw Compressors Contour TM Screw Compressors Semi-Hermetic Compact Operating Instruction SCH1 High Temp Compressors Form No. 99-77 1. Introduction This series of semi-hermetic compact screw compressors is designed for

More information

Installation, Operation, and Maintenance Information

Installation, Operation, and Maintenance Information Installation, Operation, and Maintenance Information Low Velocity Unit Coolers Bulletin No. IOM 110.3 Table of Contents Inspection... 2 Installation... 2 4 General... 2 Location... 2 Drain Line... 3 Refrigerant

More information

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017 Zeta Rev LN HP 10.2 Configured unit accessories 1PS - One user-side pump with tank LN - Low noise RG - Condensation control with fan speed regulator CSP - Set point compensation depending on external air

More information

40 RM/RMS Packaged Air-Handling Units

40 RM/RMS Packaged Air-Handling Units ConcepcionCarrier Air conditioning Company Philippines 40 RM/RMS 008034 Packaged AirHandling Units INSTALLATION MANUAL, STARTUP & SERVICE INSTRUCTIONS Contents Page Page Safety Considerations 1 40RM Physical

More information

Installation Instructions

Installation Instructions 30GTN015-035 Reciprocating Liquid Chillers with ComfortLink Controls 50/60 Hz Installation Instructions CONTENTS Page SAFETY CONSIDERATIONS...................... 1 INSTALLATION.................................1-11

More information

VertiCool CLASSIC. Engineering Guide. Effective March Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump

VertiCool CLASSIC. Engineering Guide. Effective March Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump VertiCool CLASSIC Engineering Guide Effective March 2018 Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump Contents Product Features... 3 UNIT FEATURES... 3 OPTIONS:... 3 Physical Data...

More information

Liebert Xtreme Density Chiller (XDC) Unit Warranty Inspection Check Sheet

Liebert Xtreme Density Chiller (XDC) Unit Warranty Inspection Check Sheet The following information must be completed and forwarded to your local Liebert sales office to establish your equipment warranty. Installer Address Owner Address Owner e-mail address Date of Installation:

More information

YCIV Hz & Hz

YCIV Hz & Hz YCIV 0590-1500 50Hz & 0157-0397 60Hz Start-up Checklist SERVICE POLICY & PROCEDURES Supersedes: Nothing Form 201.23-CL1 (309) Commissioning PREPARATION Commissioning of this unit should only be carried

More information

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation INTRODUCTION In recent years air conditioning industry technology has advanced rapidly. An important byproduct of this growth has been development of the heat pump. Altogether too much mystery has surrounded

More information

HTD. High Temperature Non-Cycling Refrigerated Compressed Air Dryers. Operation & Maintenance Manual. MODELS HTD 21 thru HTD 100

HTD. High Temperature Non-Cycling Refrigerated Compressed Air Dryers. Operation & Maintenance Manual. MODELS HTD 21 thru HTD 100 HTD High Temperature Non-Cycling Refrigerated Compressed Air Dryers Operation & Maintenance Manual MODELS HTD 21 thru HTD 100 - TABLE OF CONTENTS - 1.0 GENERAL 2 1.1 How to use this manual 1.2 Symbols

More information

V-SERIES Air Conditioner. VA08 Model INSTRUCTION MANUAL nvent Rev. F P/N

V-SERIES Air Conditioner. VA08 Model INSTRUCTION MANUAL nvent Rev. F P/N V-SERIES Air Conditioner VA08 Model INSTRUCTION MANUAL Rev. F P/N 90164959 TABLE OF CONTENTS Warranty and Return Policy...2 RECEIVING THE AIR CONDITIONER...3 HANDLING AND TESTING THE AIR CONDITIONER...3

More information

User s Information and Installation Instructions

User s Information and Installation Instructions Outdoor Air Conditioner User s Information and Installation Instructions 13 SEER R-410A High Efficiency Split System These units have been designed and tested for capacity & efficiency in accordance with

More information

TITAN SERIES Complete Central Chiller & Pump Tank Package 20 to 70 Tons 20 F to 70 F

TITAN SERIES Complete Central Chiller & Pump Tank Package 20 to 70 Tons 20 F to 70 F Temperature Control Units Water & Oil - F Portable Chillers Air & Water-Cooled - 7 F Central Chillers Air & Water-Cooled Packages & Modules - 7 F Pump Tank Stations Chilled or Tower Water - gallons Cooling

More information

SECTION AIR COOLED WATER CHILLERS

SECTION AIR COOLED WATER CHILLERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Chiller package B. Charge of refrigerant and oil C. Controls and control connections D. Chilled water connections E. Starters F. Electrical power connections 1.2

More information

MODELS LIST. Nominal Capacity RT

MODELS LIST. Nominal Capacity RT 1. MODELS LIST. NOMENCLATURE 3. FEATURES 4. PRODUCT DATA 5. PERFORMANCE CORRECTION 6. ANTIFREEZE 7. INSTALLATION 8. ELECTRICAL DATA 9. SCHEMATIC WIRING DIAGRAM 10.MICROPROCESSOR CONTROLLER 11.APPLICATION

More information

T-Series Air Conditioner T53 Model

T-Series Air Conditioner T53 Model INSTRUCTION MANUAL T-Series Air Conditioner T53 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200

More information

VertiCool Aurora Engineering Guide

VertiCool Aurora Engineering Guide Engineering Guide Effective August 2016 Air-Cooled, Water-Cooled and Water Source Heat Pump Contents Product Features... 3 Options... 4 Physical Data...5-6 Air-Cooled Performance Data (a) (b) (c)...7-8

More information

POLAR TEMP FARM MORTALITY UNIT OPERATION MANUAL

POLAR TEMP FARM MORTALITY UNIT OPERATION MANUAL POLAR TEMP FARM MORTALITY UNIT OPERATION MANUAL www.polartemp.com TABLE OF CONTENT Disclaimer.......................................... Page 3 Inspection, unpacking and FMU setup.................. Page

More information

KCS-Line Air Cooled Condensers

KCS-Line Air Cooled Condensers PRODUCT DATA & INSTALLATION Bulletin K50-KCS-PDI-5 Part # 1085695 PRODUCT SUPPORT web: k-rp.com/kcs email: acc-fc@k-rp.com call: 1-844-893-3222 x526 scan: KCS-Line Air Cooled Condensers R407A R407C R448A

More information

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer 5/16 Rev. A 57-02509 2 Contents INTRODUCTION... 4 WARNING LABELS AND SAFETY INSTRUCTIONS... 5 PS SERIES PARALLEL

More information

Installation Owner Diagnostics

Installation Owner Diagnostics Installation Owner Diagnostics Split System Cooling Condensers Model CTA 7 1/2 to 15 Tons Models A and later Design Sequence CTA 090A***A 60 HZ 120A***A 60 HZ 120B***A 60 HZ 180B***A 60 HZ SS-SVN11A-EN

More information

MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH

MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH 318 MHNCCX NOMENCLATURE BREAKDOWN 4-Pipe Heat/Cool Ceiling Concealed Fan Coil MHNCCW- XX - XX Ceiling Concealed

More information

High Profile Evaporator

High Profile Evaporator PRODUCT DATA & INSTALLATION Bulletin K30-KHPA-PDI-5 Part # 1081585 PRODUCT SUPPORT web: k-rp.com/khp email: evaps@k-rp.com call: 1-844-893-3222 x520 scan: High Profile Evaporator High & Medium Temperature

More information